Package 2-Pituffik SB B99 Reno Appendices RTA.pdf
PDF 31 MB Posted
- Solicitation number
- W912DS25R0002
About this file
This document appears to be an advance notice for a Request for Proposals (RFP) for the renovation of Building 99 at Pituffik Space Base in Greenland. The solicitation, numbered W912DS25R0002, is for a Firm Fixed Price (FFP) contract to be awarded in the 1st or 2nd Quarter of Fiscal Year 2025.
The renovation work involves site work, utilities, repair of the metal roof and exterior, and complete interior renovation, including updating mechanical, electrical, and control systems, as well as installing fire suppression and keyless entry. The building was constructed in 1959 and requires lifecycle replacement. The work is estimated to cost between $25,000,000 and $100,000,000 and is anticipated to take approximately 3 years to complete. Liquidated damages of $5,000 per calendar day will be assessed for delays. This procurement is restricted to Danish and Greenlandic firms only. The U.S. Army Corps of Engineers, New York District, is the procuring agency.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| ATTACHMENT 5.docx | DOCX document | |
| Amendment 0001.pdf | ||
| ATTACHMENT 2.docx | DOCX document | |
| W912DS25R0002.pdf | ||
| Package 1-Pituffik SB_B99 Reno DB RFP - RTA.pdf | ||
| Package 3-Pituffik SB B99 Reno CID-FFE-RTA.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Design-Build Request for Proposal
Package 2 - Appendices
Repair Dormitory Building 99 Pituffik Space Base, Greenland
FINAL SUBMISSION
19 September 2024
BAUTISA
Snapshot
BAUTISA
Rectangle
BAUTISA
Snapshot
Building 99 Renovation 19 September 2024
Pituffik Space Base, Greenland Design-Build Request For Proposal
APPENDIX
Appendix Title
A Preliminary Code Analysis
B Existing Site Utilities Plans
C Concept Drawings
D Structural Calculations
E Facilities Excellent Plan (Sept 2012)
F Defense Base Act Waiver - Greenland
G Justification and Approval (J&A) Interior Colors and
Finishes
H Justification and Approval (J&A) HVAC
I Non-Frost Susceptible (NFS) Material Locations
J Landfill Locations Map
K Installation Hazmat Management Program (IHMP)
L Spill Prevention and Response Plan
M Storm Water Pollution Prevention Plan
N Wastewater Slug Prevention Plan
O Overseas INCRMP
P Asbestos Management Plan
Q B99 Hazmat Inspection Report
R Overseas Hazardous Waste Management Plan
S Pest Management Plan
T Environmental FGS-GL 2020
U BUILDER Instructions (Excel file under separate cover)
APPENDIX
APPENDIX A
PRELIMINARY CODE ANALYSIS
PRELIMINARY CODE ANALYSIS
A. GENERAL
REFERENCES:
CODE YEAR TITLE
NFPA 1 2024 Fire Code
NFPA 10 2022 Standard for Portable Fire Extinguishers
NFPA 13 2022 Standard for the Installation of Sprinkler Systems
NFPA 14 2024 Standard for the Installation of Standpipe and Hose Systems
NFPA 24
2022 Standard for the Installation of Private Fire Service Mains and Their Appurtenances
NFPA 70 2023 National Electric Code
NFPA 72 2022 National Fire Alarm and Signaling Code
NFPA 90A
2024 Standard for the Installation of Air-Conditioning and Ventilation Systems
NFPA 101 2024 Life Safety Code
NFPA 241 2022 Standard for Safeguarding Construction, Alteration, and Demolition Operations
NFPA 291
2022 Recommended Practice for Fire Flow Testing and Marking of Hydrants
Other NFPA standards as applicable
UL Standards as appropriate
IBC 2021 International Building Code
IEBC 2021 International Existing Building Code
UFC 1-200-01 2022 General Building Requirements, With Change 2 (06/12/2023)
UFC 3-600-01 2016 Fire Protection Engineering For Facilities, With Change 6 (05/06/2021)
UFC 4-010-06 2023 Cybersecurity of Facility-Related Control Systems
UFC 4-021-01 2008 Design and O&M: Mass Notification Systems, With Change 1 (04/09/2008)
B. REQUIREMENTS
Dormitory B99 at Thule AFB, Greenland, will be provided with a fire alarm system, portable fire extinguishers, standpipe system, and complete automatic sprinkler protection. All existing fire protection systems will be demolished and replaced with new systems. The fire alarm system will be provided in accordance with NFPA 72 and UFC 3-600-01. The automatic sprinkler system will be provided in accordance with the NFPA 13 and UFC 3-600-01. Class I standpipes that comply with NFPA 14 will be provided in each stairwell that comply. Portable fire extinguishers will be provided in accordance with NFPA 10.
C. FIRE ALARM SYSTEM
The fire alarm system will be provided in accordance with NFPA 72 and UFC 3-600-01. The system will be an addressable system manufactured by Notifier (Model NFS2-640) in accordance with the base standard. A J&A will be required to sole source the Notifier panel.
The panel will utilize an addressable microprocessor based type system with manual and automatic alarm initiation. Signal transmission will be a multiplex format and be dedicated to fire alarm service only. All devices will be new.
Audible fire alarm indication will be provided via horns.
Visual alarm indication will be by synchronized strobes with clear lenses, marked “FIRE”.
Sleeping units will be equipped with local horn/strobes emitting a 520 Hz tone upon fire alarm activation.
The NAC (Notification Appliance Circuits) will be class “B”, survivability level “1”.
The SLC (Signal Line Circuits) will be class “B”, survivability level “1”.
The IDC (Initiating Device Circuits) circuits will be class “B”, survivability level “1”.
All fire alarm circuits must be installed in EMT. EMT will be minimum ¾-inch, and will be marked with red stripes every 10 ft with red face plates on all junction boxes. Looped conduits will have a 4-ft horizontal separation, or a 10-ft vertical separation, in compliance with the recommendations of NFPA 72.
All signals from the fire alarm panel will be transmitted through a 2-strand, single-mode fiber optic cable connection to the base-wide fire alarm network.
The building fire alarm control panel will be provided with a lockable cabinet. The FACP location will be in the mechanical room on the 1st floor. A remote annunciator will be located at the designated primary entrance.
Smoke detectors with integral sounder base will be installed in each sleeping unit and above all fire alarm panels. Sleeping room smoke detectors must transmit a distinct alarm signal to the FACP, but must not activate the facility notification appliances.
Manual pull stations must be installed at each exit and within 200 feet travel distances.
Sprinkler water flow and tamper switches must be monitored by the fire alarm system.
Duct smoke detection must be provided and monitored by the fire alarm system in accordance with NFPA 90A.
D. MASS NOTIFICATION SYSTEM
A mass notification system will be provided to match the base standard, which is to use an IP-based PA system that does not strictly comply with UFC 4-021-01. Refer to the Telecommunication section for more information.
E. FIRE SUPPRESSION SYSTEM
The building will be fully protected with an automatic wet-pipe sprinkler system. The wet-pipe sprinkler system design will be in accordance with UFC 3-600-01 and NFPA 13. Sprinkler piping must be sized such that a fire pump is not needed. Each floor will have one sprinkler zone. Each zone will be provided with a separate riser consisting of a butterfly valve, tamper switch, check valve, flow switch, pressure gauge, test and drain valve assembly and drain line. Test and drain lines will be routed to a common drain line and will discharge to grade at the exterior of the building. A remote inspector’s test connection, discharging outside, will be located at a remote portion of each zone. All drain and test connections discharging to the building exterior must be provided with a concrete splash block. Where subject to freezing, a minimum of 4 feet of exposed drain pipe will be in a heated area between the drain valve and the exterior wall when the drain piping extends through the wall to the outside. The 4 feet of exposed pipe beyond the valve provides a frost break that will prevent water in the system from freezing due to the cold air. Automatic air vents will be provided at the high point at each sprinkler zone.
Seismic protection must be provided in accordance with NFPA 13.
A wall-type fire department Siamese connection (Croker Model 6405 or approved equal) will be provided for the wet-pipe sprinkler system. The FDC will be located on the exterior of the building in a location as directed by the fire department. The FDC will be located 3-ft above grade to prevent concealment during heavy snows.
The incoming fire protection water line will be separate from the domestic water line to allow for the future connection to a dedicated fire protection water main. The diameter of the fire protection line must not be less than 6 inches. An indicating type valve conforming to base standards will be provided on the incoming fire protection line. The incoming fire protection service will be routed directly to the first floor mechanical room. A double check valve backflow preventer must be provided with OS&Y valves, with tamper switches, at each end to isolate the assembly.
Listed quick response sprinklers must be provided throughout the facility, with exception of the residential areas. The residential areas must be provided with residential sprinklers. Sprinkler densities must be based on the criteria spelled out in UFC 3-600-01. Sprinkler system densities and spacing must be as follows:
Sprinkler System Design
Area Classification K-factor Density/Area Hose
Dwelling Units, Kitchen/Dining, Stairs, Corridors
Light 5.6 0.10 gpm/ft2
1500 ft2 250 gpm 60 minutes
Mechanical Room, Electrical Room, Laundry
Ordinary 8.0 0.20 gpm/ft2
2500 ft2 250 gpm 60 minutes
The base water supply is supplied by dedicated pumping stations. The pumps can be adjusted to accommodate the anticipated flow and pressure requirements anticipated on the base.
Hydraulic flow test data (no older than 6 months) must be used in the hydraulic analysis and as the basis for the design of the sprinkler system. A preliminary analysis was done based on the following water supply information:
Static Pressure: 73 psi
Residual Pressure: 42 psi
Flow: 759 gpm
Estimated sprinkler system demand:
Demand (GPM) = Density (GPM/sq ft) x Area (sq ft) x Safety Factor + Hose Stream (GPM)
Light Hazard Areas:
= 0.10 GPM / ft2 x 1,500 ft2 x 1.2 + 250 GPM = 430 GPM
= 180 GPM + 250 GPM = 430 GPM
Estimated Required Pressure for 3rd Floor:
Elevation (40 ft): 17 psi
End Head Pressure: 13 psi
Backflow Preventer: 8 psi
Total Pressure required without consideration for friction loss: 38 psi
F. STANDPIPES
Class I automatic wet standpipes in accordance with NFPA 14 are desired by the Air Force, so the design requires standpipes in each stairwell, with 2-1/2” angle valve hose outlets at each floor stair landing. Standpipes must be combined with the sprinkler piping.
G. FIRE HYDRANTS
Fire Hydrants must be provided in accordance with UFC 3-600-01, NFPA 24 and NFPA 1963.
Hydrants must be aboveground type and must be protected from freezing.
Hydrants must be installed adjacent to paved areas, accessible to fire department apparatus. For installation requirements, refer to UFC 3-600-01, Sections §3-7.3.1 and §3-7.3.2.
A sufficient number of hydrants must be provided so that hose stream demand can be met without taking more than 1,250 gpm from any single hydrant. Hydrants must be spaced at intervals no greater than 350 feet in accordance with UFC 3-600-01 Section §9-3.5.8.2. Hydrants must be located with consideration given to emergency vehicle access. At least one hydrant must be located within 150 feet of the fire department connection (UFC 3-600-01, §3-7.3).
Hydrants located adjacent to parking areas or other vehicle traffic areas must be protected by bollards.
Fire hydrants must be UL listed, FM approved, or listed or classified by another NRTL and must have two 2-1/2-inch hose outlets and one 4-1/2-inch suction connection with national standard fire hose threads. Confirm with the base prior to installation that the fire hydrants match the base standards.
H. PORTABLE FIRE EXTINGUISHERS
Portable fire extinguishers must be provided in accordance with NFPA 10. General purpose fire extinguishers must be used in the dormitory areas, and Class K fire extinguishers must be used in the kitchens.
I. CODE ANALYSIS
Minimum Construction Type of: Type III-B (IBC §602) (Existing)
Sprinkler System: Fully Sprinklered
Use and Occupancy: Residential (R-2) (IBC §310)
Dormitory – NFPA 101, Chapter 28
Allowable Building Height: 75 feet (IBC Table §504.3)
Provided: 40 feet
Allowable Number of Stories Above Grade Plane: 5 Stories (IBC Table §504.4)
Provided: 3 Stories
Allowable Area: 48,000 ft2 (IBC Table §506.2)
Provided: 8,569 ft2
J. REQUIRED FIRE RESISTANCE RATINGS
Structural Frame 0 Hrs IBC Table 601
Exterior Bearing Walls 2 Hrs IBC Table 601
Non-Bearing Exterior Walls 0 Hrs IBC Table 601 and 602
Interior Bearing Walls 0 Hrs IBC Table 601
Non-Bearing Interior Walls 0 Hrs IBC Table 601
Roof Construction 0 Hrs IBC Table 601
Stair Enclosures (< 4 Stories) 1 Hr NFPA 101 §7.1.3.2.1(1)
Shaft Enclosures (< 4 Stories) 1 Hr NFPA 101 §8.6.5(2)
Separation between dwelling units (floors and walls)
30 Min NFPA 101 §28.3.7.2
Corridor walls 30 Min NFPA 101 §28.3.6.1.3
Mechanical & Electrical Rooms
1 Hour NFPA 101 Table §28.3.2.2.2
Laundry Rooms 1 Hour NFPA 101 Table §28.3.2.2.2
Protection of Openings:
Fire and Smoke Dampers: Fire and smoke dampers must be installed in accordance with NFPA 90A. Fire dampers will be provided in all air transfer openings in partitions that are required to have a fire resistance rating and in which other openings are required to be protected. Smoke dampers will be installed at or adjacent to the point where air ducts pass through required smoke barriers.
Door Fire Resistance Ratings (NFPA 101 Table §8.3.3.2.2)
• 1-hour fire barrier wall: ¾-hour
• 1-hour fire barrier enclosing shafts, exit enclosures and exit passageways: 1-hour
• 20 minutes for doors in corridor/sleeping room walls
K. EGRESS ANALYSIS
Maximum Travel Distance to Exit:
Residential: 100 ft – (NFPA 101 §28.2.6.3.1)
Measured from guest room door
Maximum Dead-end Corridor:
Residential: 50 ft – (NFPA 101 §28.2.5.3.1)
Maximum Common Path of Travel:
Residential: 50 ft – (NFPA 101 §28.2.5.2.1)
Minimum Egress Width (Clear Width):
Doors: 32 in (NFPA 101 §7.2.1.2.4)
Capacity: 0.2 in / occupant (NFPA 101 §7.3.3.1) – Doors and other horizontal components
Stairs: 44 in (NFPA 101 §7.2.2.2.1.2)
Capacity: 0.3 in / occupant (NFPA 101 §7.3.3.1)
Occupant Load (NFPA 101 §7.3.1):
The occupant load of the building must be determined using the appropriate occupant load factors for the use of the area in question.
Use (Occupancy)
Occupant Load Factor
(NFPA 101 §7.3.1.2)
Residential 200 gross
Business 150 ft2/person
Assembly 15 net
Kitchens 100 ft2/person
Storage 500 ft2/person
L. FIRE DEPARTMENT ACCESS
Fire department vehicle access will be unaffected by this project.
M. INTERIOR FINISH
Interior finish must comply with UFC 3-600-01 and NFPA 101
N. EMERGENCY LIGHTING
Emergency lighting required in accordance with NFPA 101 §7.9. Emergency illumination must be provided for a minimum of 1.5 hours in the event of failure of normal lighting. Emergency lighting fixtures must be arranged to provide initial illumination that is not less than an average of 1 ft-candle and, at any point, not less than 0.1 ft-candle measured along the path of egress at floor level.
O. ILLUMINATION OF MEANS OF EGRESS
The floors and other walking surfaces within an exit and within the portions of the exit access and exit discharge designated in NFPA 101 §7.8.1.1 must be illuminated to at least the following values at floor or walking surface level:
• The minimum illumination must be 1 ft-candle (NFPA 101 §7.8.1.3(2)) for floors and walking surfaces other than stairs. The minimum illumination for stairs must be 10 ft-candle (NFPA 101 §7.8.1.3(1)).
• Illumination must be arranged so that the failure of any single lighting unit does not result in an illumination level of less than 0.2 ft-candle in any designated area (NFPA 101 §7.8.1.4).
Automatic lighting control devices must be permitted to temporarily turn off the illumination within the means of egress, provided that each lighting control device complies with all the following:
• Lighting control device is listed.
• Lighting control device is equipped to automatically energize any controlled lights required for compliance with NFPA 101 §7.9 upon loss of normal power and is evaluated for this purpose.
• Illumination timers are provided and are set for a minimum 15-minute duration.
• Lighting control device is activated by any occupant movement in the area served by the lighting unites.
• The lighting control device is activated by activation of the building fire alarm system.
• Lighting control device does not turn off any lights relied upon for activation of photoluminescent exit signs or path markers.
• Lighting control device does not turn off any battery-equipped emergency luminaires, until equipment, or exit signs.
P. MARKING OF MEANS OF EGRESS
Means of egress must have signs in accordance with NFPA §7.10. Exits must be marked by an approved sign that is readily visible from any direction of exit access. Exit signs must be provided with an emergency power source.
APPENDIX B
EXISTING SITE UTILITIES PLANS
REPAIR DORMITORY BUILDING 99 - RENOVATION
GREENLAND
PITUFFIK SPACE BASE
A Joint Venture
PRELIMINARY - NOT FOR CONSTRUCTION
16 JANUARY 2024
EXISTING DRAINAGE PLAN
19 SEPTEMBER 2024
PITUFFIK SPACE BASE
A Joint Venture
PRELIMINARY - NOT FOR CONSTRUCTION
16 JANUARY 2024
EXISTING ELECTRICAL PLAN
PITUFFIK SPACE BASE
A Joint Venture
PRELIMINARY - NOT FOR CONSTRUCTION
16 JANUARY 2024
EXISTING SANITARY SEWER PLAN
4"
4"
PITUFFIK SPACE BASE
A Joint Venture
PRELIMINARY - NOT FOR CONSTRUCTION
16 JANUARY 2024
EXISTING HEATING WATER PLAN
1 ST. ST.
DSON A
VE.
15010
U N
N
AM
ED
R
O
AD
0m m H
W S/
R
200mm HWS/R
200mm HWS/R
0m m H W
S/ R
50mm HWS/R
200mm HWS/R mm H
W S/R
PITUFFIK SPACE BASE
A Joint Venture
PRELIMINARY - NOT FOR CONSTRUCTION
16 JANUARY 2024
EXISTING WATERLINE PLAN
PITUFFIK SPACE BASE
A Joint Venture
PRELIMINARY - NOT FOR CONSTRUCTION
16 JANUARY 2024
PARKING LAYOUT PLAN
9' x 18.5' PARKING
SPACE (TYP)
24 SPACES TOTAL
VEHICLE ENGINE
HEATER (HOT PLUG)
TWO CONNECTIONS
PER PEDESTAL, 24
CONNECTIONS TOTAL
EXISTING ROADWAY
APPENDIX C
CONCEPT DRAWINGS
PITUFFIK SPACE BASE
FINAL SUBMISSION
A Joint Venture
PRELIMINARY - NOT FOR CONSTRUCTION
N
LIVING ROOM
UTILITIES AND BUILDING SUPPORT SERVICE
LEGEND
RESTROOM
MULTI-PURPOSE
MECHANICAL ROOM
KITCHEN/DINING BEDROOM
CIRCULATION
TOTAL FLOOR AREA : 9,860 S.F.
12’ 9’ 6’ 3’ 0 6’ 12’
FIRST FLOOR PLAN
PITUFFIK SPACE BASE
FINAL SUBMISSION
A Joint Venture
PRELIMINARY - NOT FOR CONSTRUCTION
19 SEPTEMBER 2024
N
LIVING ROOM
UTILITIES AND BUILDING SUPPORT SERVICE
LEGEND
RESTROOM
MULTI-PURPOSE
MECHANICAL ROOM
KITCHEN/DINING BEDROOM
CIRCULATION
TOTAL FLOOR AREA : 9,860 S.F.
12’ 9’ 6’ 3’ 0 6’ 12’
SECOND FLOOR PLAN
PITUFFIK SPACE BASE
FINAL SUBMISSION
A Joint Venture
PRELIMINARY - NOT FOR CONSTRUCTION
N
LIVING ROOM
UTILITIES AND BUILDING SUPPORT SERVICE
LEGEND
RESTROOM
MULTI-PURPOSE
MECHANICAL ROOM
KITCHEN/DINING BEDROOM
CIRCULATION
TOTAL FLOOR AREA : 9,860 S.F.
12’ 9’ 6’ 3’ 0 6’ 12’
THIRD FLOOR PLAN
PITUFFIK SPACE BASE
A Joint Venture
EXTERIOR ELEVATION
PRELIMINARY - NOT FOR CONSTRUCTION
16’ 12’ 8’ 4’ 0 8’ 16’ FINAL SUBMISSION 19 SEPTEMBER 2024
PITUFFIK SPACE BASE
A Joint Venture
EXTERIOR WALL SECTION
PRELIMINARY - NOT FOR CONSTRUCTION
4’ 3’ 2’ 1’ 0 2’ 4’ FINAL SUBMISSION 19 SEPTEMBER 2024
A Joint Venture
PRELIMINARY - NOT FOR CONSTRUCTION
N
REPAIR DORMITORY BUILDING 99 - RENOVATION
12’ 9’ 6’ 3’ 0 6’ 12’ FINAL SUBMISSION
FIRST FLOOR LIFE SAFETY PLAN
A Joint Venture
PRELIMINARY - NOT FOR CONSTRUCTION
N
REPAIR DORMITORY BUILDING 99 - RENOVATION
12’ 9’ 6’ 3’ 0 6’ 12’ FINAL SUBMISSION
SECOND FLOOR LIFE SAFETY PLAN
A Joint Venture
PRELIMINARY - NOT FOR CONSTRUCTION
N
REPAIR DORMITORY BUILDING 99 - RENOVATION
12’ 9’ 6’ 3’ 0 6’ 12’ FINAL SUBMISSION
THIRD FLOOR LIFE SAFETY PLAN
JANITOR
LAUNDRY
CLOSET
REPAIR DORMITORY BUILDING 99 - RENOVATION
GREENLAND
PITUFFIK SPACE BASE
A Joint Venture TYPICAL FURNITURE PLANS
PRELIMINARY - NOT FOR CONSTRUCTION
12’ 9’ 6’ 3’ 0 6’ 12’ 19 SEPTEMBER 2024
APPENDIX D
STRUCTURAL CALCULATIONS
REQUEST FOR PROPOSAL
Pituffik Space Base, Greenland RFP Submission
PRELIMINARY STRUCTURAL CALCULATIONS
TABLE OF CONTENTS
1. Design Criteria Pages 3-6
2. Existing Structural Evaluation Pages 7-36
PURPOSE STATEMENT
The purpose of this Preliminary Structural Calculation Package is only to assess the feasibility of components of the proposed renovation to Building 99. These calculations include assumptions of criteria and loading that must be verified by the Design Build Contractor once final construction materials and details have been established. Calculations included in this document do not relieve the Design-Build Contractor of the responsibility to ensure all elements of the design comply with applicable UFCs. The Design-Build Contractor is responsible for evaluating all elements included in their complete design.
DESIGN CRITERIA
| ������������ | � | |
| ������� | �� | |
| ��� |
������������ �!�"#�"$�����#�"�%&�'()'�*"%�+'(�,��"-��./�%�0�'��"�'12��#,��1�*#13%��#�4(%��#�5�01'"�(1�%�(����"��'12��#,6
7.89:�.;
>?@ABC DEFEC
GHIJKLKMNOP
:�20��9Q
GRSTIJKMSUVORP
W#���0"�5
XYZZ[�\[�����]��Z�\̂
_HONOÙJ
_SVaNOÙJ bb6cdbecfc gdh6iijcjidhhhhhhb klmnKopqqnKrsptu klmnKopqqnKrvsLtu
=lovKMwxqy<=z =lovKMwxqy<=z l ll lll l{ { l ll lll l{ {
|ci |cj |}f |}d |jj iih ifj icd i}| fef om<kK_<wnlmy y=<~mnKom<kKrpo�u �=<oxKpqmqx=wxl<mKrlmu y=<~mnKom<kKrvpwu �=<oxKpqmqx=wxl<mKrssu
�%��01'"0�5"�"$�(��"�"(0"*0� oqloslMKnwxw pyw r�yu o r�yu o r�yu
|} fh |j nNI��HN�JR����(0������(��1#-"�(1��&#�%����5�1����(%�3�*%(���(%�*�0(���5��1�*��'1##�'�$�����;"�(1�"0���%�(�2���1��Q2(05(�4��'(��'�%�"�5�(�%�%&1�%1#%�"�5�'1��#(*2�1#%
"%%2-���1�0("*(0(�,��1#�(�%�"''2#"',6�:���-"��#("0�&#�%����5�%�1205��1��*��2%�5��1#�"�,�%&�'()'�"&&0('"�(1��3(��12��#��(�3�*,���4(���#%�1#�1���#�0('��%�5���%%(1�"0%6
:���2%�#%�1������(��1#-"�(1���#1-���(%�3�*%(���"%%2-��"00�0("*(0(�,�"#(%(�4��#1-�%2'��2%�6�955(�(1�"00,$�����#�%20�%�(�5('"��5���#��51��1��#���'��"-��5-���%�-"5��*, %�"���1#�01'"0��2#(%5('�(1�%6��%�#%�%�1205�'��'��"�,�5"�"�1*�"(��5��#1-���(%��110�3(�������01'"0�92��1#(�,��"�(�4��2#(%5('�(1��*��1#��'��5(�4�3(���5�%(4�6 o �
JOB TITLE Building 99 Reno Pituffik Space Base
WWCX103007
JOB NO. 20230410 SHEET NO.
CALCULATED BY CDH DATE
CHECKED BY DATE
www.struware.com
CODE SUMMARY
Code: UFC 3-301-01
Live Loads:
Roof 0 to 200 sf: 20 psf 200 to 600 sf: 24 - 0.02Area, but not less than 12 psf over 600 sf: 12 psf
Typical Floor 40 psf Partitions 15 psf Corridors serving as egress 80 psf to multiple private rooms Mechanical Equipment (General) 100 psf Stairs and exit ways 100 psf
Dead Loads:
Floor 110.8 psf Roof 23.0 psf
Roof Snow Loads:
Design Uniform Roof Snow load = 20.0 psf Flat Roof Snow Load Pf = 17.5 psf Balanced Snow Load Ps = 17.5 psf Ground Snow Load Pg = 25.0 psf Importance Factor I = 1.00 Snow Exposure Factor Ce = 1.00 Thermal Factor Ct = 1.00 Sloped-roof Factor Cs = 1.00 Drift Surcharge load Pd = 17.3 psf Width of Snow Drift w = Width of Stair Enclosure
Earthquake Design Data:
Risk Category = II Importance Factor I = 1.00 Mapped spectral response accelerations Ss = 39.00
S1 = 18.00 Site Class = C Spectral Response Coef. Sds = 0.338
Sd1 = 0.180 Seismic Design Category = C Basic Structural System = Moment-resisting Frame Systems Seismic Resisting System = Steel ordinary moment frames Design Base Shear V = 0.097W Seismic Response Coef. Cs = 0.097
Response Modification Factor R = 3.5
Analysis Procedure = Equivalent Lateral-Force Analysis
Wind Design Data:
Ultimate Design Wind Speed 148 mph Nominal Design Wind Speed 114.64 mph Risk Category II Mean Roof Ht (h) 36.5 ft Exposure Category C Enclosure Classif. Enclosed Building Internal pressure Coef. +/-0.18
Directionality (Kd) 0.85
JOB TITLE Building 99 Reno Pituffik Space Base
WWCX103007
JOB NO. 20230410 SHEET NO.
CALCULATED BY CDH DATE
CHECKED BY DATE
www.struware.com
Component and Cladding Ultimate Wind Pressures
Roof Surface Pressure (psf)
Area 2 sf 10 sf 20 sf 50 sf 75 sf 100 sf 200 sf 250 sf
Negative Zone 1 & 2e -106.4 -106.4 -106.4 -64.7 -46.3 -33.2 -33.2 -33.2
Negative Zone 2n, 2r &3e -155.2 -155.2 -134.1 -106.4 -94.1 -85.3 -64.3 -57.6
Negative Zone 3r -184.4 -184.4 -158.0 -123.0 -107.6 -96.6 -96.6 -96.6
Positive All Zones 42.9 34.9 31.5 26.9 24.9 23.4 23.4 23.4
Overhang Zone 1 & 2e -122.0 -122.0 -122.0 -94.2 -81.9 -73.2 -73.2 -73.2
Overhang Zone 2n & 2r -170.8 -170.8 -155.0 -134.2 -125.0 -118.4 -102.7 -97.6
Overhang Zone 3e -200.0 -200.0 -172.7 -136.6 -120.6 -109.3 -82.0 -73.2
Overhang Zone 3r -229.3 -229.3 -194.1 -147.5 -126.8 -112.2 -112.2 -112.2
Overhang soffit pressure equals adj wall pressure (which includes internal pressure of 8.8 psf)
Parapet Solid Parapet Pressure (psf)
Area 10 sf 20 sf 50 sf 100 sf 250 sf 500 sf
CASE A: Zone 2e : 0.0 0.0 0.0 0.0 0.0 0.0
Zone 2n, 2r & 3e : 0.0 0.0 0.0 0.0 0.0 0.0
Zone 3r : 0.0 0.0 0.0 0.0 0.0 0.0
CASE B: Interior zone : 0.0 0.0 0.0 0.0 0.0 0.0
Corner zone : 0.0 0.0 0.0 0.0 0.0 0.0
Wall Surface Pressure (psf)
Area 10 sf 100 sf 200 sf 500 sf
Negative Zone 4 -62.5 -53.8 -51.2 -47.8
Negative Zone 5 -77.1 -59.9 -54.7 -47.8
Positive Zone 4 & 5 57.6 49.0 46.4 42.9
EXISTING STRUCTURE EVALUATION
EwingCole
Current Date: 1/8/2024 10:57 AM
Units system: English
File name: W:\20230410\03_Production\05_Stru\Calcs\Existing Roof Purlin Down.rcb
Design Results Continuous Beam
Design code AISC 360-2016 LRFD
General Information
Spans:
Span Span length Section Material
[ft]
1 12.50 W 6X8.5 A7
Nodes:
Distance Restraint Tx Ty Rz
[ft]
0.00 Pinned 1 1 0
12.50 Pinned 1 1 0
Load Conditions
Condition Description Comb. Category Duration Self Weight
DL Dead Load No DL -- Yes
LL Live Load No LL -- --
S1 DL Yes Service -- Yes
S2 DL+LL Yes Service -- Yes
S3 DL+0.75LL Yes Service -- Yes
D1 1.4DL Yes Design -- Yes
D2 1.2DL+1.6LL Yes Design -- Yes
Page1
EXISTING ROOF PURLIN
EVALUATION FOR GRAVITY LOADS
Distributed loads on spans
Condition Span(s) Dist1 Dist2 Val1 Val2
[ft] [ft] [Kip/ft] [Kip/ft]
DL 1 0.00 12.50 -0.14 -0.14
LL 1 0.00 12.50 -0.20 -0.20
Loads summary
Reactions
Page2
Nodes condition Rx Ry Mz
[Kip] [Kip] [Kip*ft]
1 D1 0.00 1.30 0.00
2 D1 0.00 1.30 0.00
1 D2 0.00 3.11 0.00
2 D2 0.00 3.11 0.00
1 Min. 0.00 1.30 0.00
2 Min. 0.00 1.30 0.00
1 Max. 0.00 3.11 0.00
2 Max. 0.00 3.11 0.00
Member forces and inflection points
Station Condition Distance Shear V Moment M
[%] [ft] [Kip] [Kip*ft]
0 D1 0.00 1.30 0.00
50 D1 6.25 0.00 4.06
100 D1 12.50 -1.30 0.00
0 D2 0.00 3.11 0.00
50 D2 6.25 0.00 9.73
100 D2 12.50 -3.11 0.00
Critical deflections
Condition Span Distance @ Deflection Allowable
[ft] [%] [in] f(L) [in]
S1 1 6.25 50.00 0.19204 (L/781) 0.41667
S2 1 6.25 50.00 0.45053 (L/333) 0.41667
S3 1 6.25 50.00 0.38591 (L/389) 0.41667
Envelopes
Page3
M33 bending moment:
Moments [Kip*ft], Length [ft]
V2 shear forces:
Forces [Kip], Length [ft]
Vertical Translation
Deflection [in], Length [ft]
Page4
Design
Span : 1 (W 6X8.5_A7) - OK
Section information
Section name: W 6X8.5 (US)
Dimensions bf = 3.940 [in] Width d = 5.830 [in] Depth k = 0.445 [in] Distance k k1 = 0.500 [in] Distance k1 tf = 0.195 [in] Flange thickness tw = 0.170 [in] Web thickness
Properties Unit Major axis Minor axis
Gross area of the section. (Ag) [in2] 2.520
Moment of Inertia (local axes) (I) [in4] 14.900 1.990
Moment of Inertia (principal axes) (I') [in4] 14.900 1.990
Bending constant for moments (principal axis) (J') [in] 0.000 0.000
Radius of gyration (local axes) (r) [in] 2.432 0.889
Radius of gyration (principal axes) (r') [in] 2.432 0.889
Saint-Venant torsion constant. (J) [in4] 0.033
Section warping constant. (Cw) [in6] 15.800
Distance from centroid to shear center (principal axis) (xo,yo) [in] 0.000 0.000
Top elastic section modulus of the section (local axis) (Ssup) [in3] 5.100 1.010
Bottom elastic section modulus of the section (local axis) (Sinf) [in3] 5.100 1.010
Top elastic section modulus of the section (principal axis) (S'sup) [in3] 5.100 1.010
Bottom elastic section modulus of the section (principal axis) (S'inf) [in3] 5.100 1.010
Plastic section modulus (local axis) (Z) [in3] 5.730 1.560
Plastic section modulus (principal axis) (Z') [in3] 5.730 1.560
Polar radius of gyration. (ro) [in] 2.589
Area for shear (Aw) [in2] 1.540 0.990
Torsional constant. (C) [in3] 0.147
Material : A7
Properties Unit Value
Yield stress (Fy): [Kip/in2] 30.00
Tensile strength (Fu): [Kip/in2] 60.00
Elasticity Modulus (E): [Kip/in2] 29000.00
Shear modulus for steel (G): [Kip/in2] 11153.85
Design Criteria
Description Unit Value
Length for tension slenderness ratio (L) [ft] 12.50
Page5
Distance between member lateral bracing points
Length (Lb) [ft]
Top Bottom
0.00 6.25
Laterally unbraced length
Length [ft] Effective length factor
Major axis(L33) Minor axis(L22) Torsional axis(Lt) Major axis(K33) Minor axis(K22) Torsional axis(Kt)
12.50 12.50 12.50 1.0 1.0 1.0
Additional assumptions
Continuous lateral torsional restraint No
Tension field action No
Continuous flexural torsional restraint No
Effective length factor value type None
Major axis frame type Sway
Minor axis frame type Sway
Design Checks
Axial Tension Design
Axial tension
Ratio : 0.00
Capacity : 68.04 [Kip] Reference : Cl.D2
Demand : 0.00 [Kip] Ctrl Eq. : D1 at 0.00%
Intermediate results Unit Value Reference
Factored axial tension capacity(φPn): [Kip] 68.04 Cl.D2
Nominal axial tension capacity (Pn) [Kip] 75.60 Eq.D2-1
Axial Compression Design
Compression in the major axis 33
Ratio : 0.00
Capacity : 57.58 [Kip] Reference : Cl.E3
Demand : 0.00 [Kip] Ctrl Eq. : D1 at 0.00%
Intermediate results Unit Value Reference
Section classification
Unstiffened element classification -- Non slender
Unstiffened element slenderness (λ) -- 10.10
Unstiffened element limiting slenderness (λr) -- 17.41 Table.B4.1a.Case1
Stiffened element classification -- Non slender
Stiffened element slenderness (λ) -- 29.06
Stiffened element limiting slenderness (λr) -- 46.33 Table.B4.1a.Case5
Factored flexural buckling strength(φPn33): [Kip] 57.58 Cl.E3
Unbraced length (L33) [ft] 12.50 Cl.E2
Page6
Effective slenderness ((KL/r)33) -- 61.69 Cl.E2
Elastic critical buckling stress (Fe33) [Kip/in2] 75.21 Eq.E3-4
Effective area of the cross section based on the effective width (A... [in2] 2.52
Critical stress for flexural buckling (Fcr33) [Kip/in2] 25.39 Eq.E3-2
Nominal flexural buckling strength (Pn33) [Kip] 63.98 Eq.E3-1
Compression in the minor axis 22
Ratio : 0.00
Capacity : 19.98 [Kip] Reference : Cl.E3
Demand : 0.00 [Kip] Ctrl Eq. : D1 at 0.00%
Intermediate results Unit Value Reference
Section classification
Unstiffened element classification -- Non slender
Unstiffened element slenderness (λ) -- 10.10
Unstiffened element limiting slenderness (λr) -- 17.41 Table.B4.1a.Case1
Stiffened element classification -- Non slender
Stiffened element slenderness (λ) -- 29.06
Stiffened element limiting slenderness (λr) -- 46.33 Table.B4.1a.Case5
Factored flexural buckling strength(φPn22): [Kip] 19.98 Cl.E3
Unbraced length (L22) [ft] 12.50 Cl.E2
Effective slenderness ((KL/r)22) -- 168.80 Cl.E2
Elastic critical buckling stress (Fe22) [Kip/in2] 10.05 Eq.E3-4
Effective area of the cross section based on the effective width (A... [in2] 2.52
Critical stress for flexural buckling (Fcr22) [Kip/in2] 8.81 Eq.E3-3
Nominal flexural buckling strength (Pn22) [Kip] 22.20 Eq.E3-1
Factored torsional or flexural-torsional buckling strength(φPn11): [Kip] 46.97 Cl.E4
Unbraced length (L11) [ft] 12.50 Cl.E2
Torsional or flexural-torsional elastic buckling stress (Fe11) [Kip/in2] 33.89 Eq.E4-2
Effective area of the cross section based on the effective width (A... [in2] 2.52
Critical stress for torsional or flexural-torsional buckling (Fcr11) [Kip/in2] 20.71 Eq.E3-2
Nominal torsional or flexural-torsional buckling strength (Pn11) [Kip] 52.19 Eq.E4-1
Flexural Design
Bending about major axis, M33
Ratio : 0.75
Capacity : 12.89 [Kip*ft] Reference : Cl.F2.1
Demand : 9.73 [Kip*ft] Ctrl Eq. : D2 at 50.00%
Intermediate results Unit Value Reference
Section classification
Unstiffened element classification -- Compact
Unstiffened element slenderness (λ) -- 10.10
Limiting slenderness for noncompact unstiffened element (λr) -- 31.09
Limiting slenderness for compact unstiffened element (λp) -- 11.81
Stiffened element classification -- Compact
Stiffened element slenderness (λ) -- 29.06
Limiting slenderness for noncompact stiffened element (λr) -- 177.22
Limiting slenderness for compact stiffened element (λp) -- 116.90
Factored yielding strength(φMn): [Kip*ft] 12.89 Cl.F2.1
Yielding (Mn) [Kip*ft] 14.33 Eq.F2-1
Factored lateral-torsional buckling strength(φMn): [Kip*ft] 11.78 Cl.F2.2
Limiting laterally unbraced length for yielding (Lp) [ft] 4.05 Eq.F2-5
Page7
Effective radius of gyration used in the determination of Lr (r ts) [in] 1.05 Eq.F2-7
Lateral-torsional factor (c) -- 1.00 Eq.F2-8a
Limiting laterally unbraced length for inelastic lateral-torsional bucklin... [ft] 13.66 Eq.F2-6
Lateral-torsional buckling modification factor (Cb) -- 1.00 Eq.F1-1
Nominal lateral-torsional buckling moment strength (Mn) [Kip*ft] 13.09 Eq.F2-2
Bending about minor axis, M22
Ratio : 0.00
Capacity : 3.51 [Kip*ft] Reference : Cl.F6.1
Demand : 0.00 [Kip*ft] Ctrl Eq. : D1 at 0.00%
Intermediate results Unit Value Reference
Section classification
Unstiffened element classification -- Compact
Unstiffened element slenderness (λ) -- 10.10
Limiting slenderness for noncompact unstiffened element (λr) -- 31.09
Limiting slenderness for compact unstiffened element (λp) -- 11.81
Stiffened element classification -- Compact
Stiffened element slenderness (λ) -- 29.06
Limiting slenderness for noncompact stiffened element (λr) -- 177.22
Limiting slenderness for compact stiffened element (λp) -- 116.90
Factored yielding strength about a geometric axis(φMn): [Kip*ft] 3.51 Cl.F6.1
Yielding (Mn) [Kip*ft] 3.90 Eq.F6-1
Shear Design
Shear in major axis 33
Ratio : 0.00
Capacity : 24.89 [Kip] Reference : Cl.G1
Demand : 0.00 [Kip] Ctrl Eq. : D1 at 0.00%
Intermediate results Unit Value Reference
Factored shear capacity(φVn): [Kip] 24.89 Cl.G1
Web buckling coefficient (kv) -- 1.20 Cl.G6
Web buckling coefficient (Cv) -- 1.00 Eq.G2-9
Nominal shear strength (Vn) [Kip] 27.66 Eq.G6-1
Shear in minor axis 22
Ratio : 0.17
Capacity : 17.82 [Kip] Reference : Cl.G1
Demand : 3.11 [Kip] Ctrl Eq. : D2 at 0.00%
Intermediate results Unit Value Reference
Factored shear capacity(φVn): [Kip] 17.82 Cl.G1
Web buckling coefficient (kv) -- 5.34 Eq.G2-5
Web buckling coefficient (Cv) -- 1.00 -
Nominal shear strength (Vn) [Kip] 17.82 Eq.G2-1
Combined Actions Design
Page8
Combined flexure and axial
Ratio : 0.75
Ctrl Eq. : D2 at 50.00% Reference : Eq.H1-1b
Intermediate results Unit Value Reference
Interaction of flexure and axial force: -- 0.75 Eq.H1-1b
Available flexural strength about strong axis (Mc33) [Kip*ft] 12.89 Cl.H1.1
Available flexural strength about weak axis (Mc22) [Kip*ft] 3.51 Cl.H1.1
Available axial strength (Pc) [Kip] 68.04 Cl.H1.1
Page9
Current Date: 1/8/2024 10:53 AM
Units system: English
File name: W:\20230410\03_Production\05_Stru\Calcs\Existing Roof Purlin Up.rcb
Design Results Continuous Beam
Design code AISC 360-2016 LRFD
General Information
Spans:
Span Span length Section Material
[ft]
1 12.50 W 6X8.5 A7
Nodes:
Distance Restraint Tx Ty Rz
[ft]
0.00 Pinned 1 1 0
12.50 Pinned 1 1 0
Load Conditions
Condition Description Comb. Category Duration Self Weight
DL Dead Load No DL -- Yes
LL Live Load No LL -- --
S1 DL Yes Service -- Yes
S2 0.6DL+0.6LL Yes Service -- Yes
D1 1.4DL Yes Design -- Yes
D2 0.9DL+LL Yes Design -- Yes
Page1
EXISTING ROOF PURLIN
EVALUATION FOR WIND UPLIFT
[ft] [ft] [Kip/ft] [Kip/ft]
DL 1 0.00 12.50 -0.14 -0.14
LL 1 0.00 12.50 0.51 0.51
Loads summary
[Kip] [Kip] [Kip*ft]
1 D1 0.00 1.30 0.00
2 D1 0.00 1.30 0.00
1 D2 0.00 -2.35 0.00
2 D2 0.00 -2.35 0.00
1 Min. 0.00 -2.35 0.00
2 Min. 0.00 -2.35 0.00
1 Max. 0.00 1.30 0.00
2 Max. 0.00 1.30 0.00
Member forces and inflection points
Station Condition Distance Shear V Moment M
[%] [ft] [Kip] [Kip*ft]
0 D1 0.00 1.30 0.00
50 D1 6.25 0.00 4.06
100 D1 12.50 -1.30 0.00
0 D2 0.00 -2.35 0.00
50 D2 6.25 0.00 -7.35
100 D2 12.50 2.35 0.00
Critical deflections
Condition Span Distance @ Deflection Allowable
[ft] [%] [in] f(L) [in]
S1 1 6.25 50.00 0.19204 (L/781) 0.41667
S2 1 6.25 50.00 0.28026 (L/535) 0.41667
Envelopes
M33 bending moment:
V2 shear forces:
Forces [Kip], Length [ft]
Vertical Translation
Deflection [in], Length [ft]
Design
Span : 1 (W 6X8.5_A7) - OK
Section information
Section name: W 6X8.5 (US)
Dimensions bf = 3.940 [in] Width d = 5.830 [in] Depth k = 0.445 [in] Distance k k1 = 0.500 [in] Distance k1 tf = 0.195 [in] Flange thickness tw = 0.170 [in] Web thickness
Properties Unit Major axis Minor axis
Gross area of the section. (Ag) [in2] 2.520
Moment of Inertia (local axes) (I) [in4] 14.900 1.990
Moment of Inertia (principal axes) (I') [in4] 14.900 1.990
Bending constant for moments (principal axis) (J') [in] 0.000 0.000
Radius of gyration (local axes) (r) [in] 2.432 0.889
Radius of gyration (principal axes) (r') [in] 2.432 0.889
Saint-Venant torsion constant. (J) [in4] 0.033
Section warping constant. (Cw) [in6] 15.800
Distance from centroid to shear center (principal axis) (xo,yo) [in] 0.000 0.000
Top elastic section modulus of the section (local axis) (Ssup) [in3] 5.100 1.010
Bottom elastic section modulus of the section (local axis) (Sinf) [in3] 5.100 1.010
Top elastic section modulus of the section (principal axis) (S'sup) [in3] 5.100 1.010
Bottom elastic section modulus of the section (principal axis) (S'inf) [in3] 5.100 1.010
Plastic section modulus (local axis) (Z) [in3] 5.730 1.560
Plastic section modulus (principal axis) (Z') [in3] 5.730 1.560
Polar radius of gyration. (ro) [in] 2.589
Area for shear (Aw) [in2] 1.540 0.990
Torsional constant. (C) [in3] 0.147
Material : A7
Properties Unit Value
Yield stress (Fy): [Kip/in2] 30.00
Tensile strength (Fu): [Kip/in2] 60.00
Elasticity Modulus (E): [Kip/in2] 29000.00
Shear modulus for steel (G): [Kip/in2] 11153.85
Design Criteria
Description Unit Value
Length for tension slenderness ratio (L) [ft] 12.50
Distance between member lateral bracing points
Length (Lb) [ft]
Top Bottom
0.00 6.25
Laterally unbraced length
Length [ft] Effective length factor
Major axis(L33) Minor axis(L22) Torsional axis(Lt) Major axis(K33) Minor axis(K22) Torsional axis(Kt)
12.50 12.50 12.50 1.0 1.0 1.0
Additional assumptions
Continuous lateral torsional restraint No
Tension field action No
Continuous flexural torsional restraint No
Effective length factor value type None
Major axis frame type Sway
Minor axis frame type Sway
Design Checks
Axial Tension Design
Axial tension
Ratio : 0.00
Capacity : 68.04 [Kip] Reference : Cl.D2
Demand : 0.00 [Kip] Ctrl Eq. : D1 at 0.00%
Intermediate results Unit Value Reference
Factored axial tension capacity(φPn): [Kip] 68.04 Cl.D2
Nominal axial tension capacity (Pn) [Kip] 75.60 Eq.D2-1
Axial Compression Design
Compression in the major axis 33
Ratio : 0.00
Capacity : 57.58 [Kip] Reference : Cl.E3
Demand : 0.00 [Kip] Ctrl Eq. : D1 at 0.00%
Intermediate results Unit Value Reference
Section classification
Unstiffened element classification -- Non slender
Unstiffened element slenderness (λ) -- 10.10
Unstiffened element limiting slenderness (λr) -- 17.41 Table.B4.1a.Case1
Stiffened element classification -- Non slender
Stiffened element slenderness (λ) -- 29.06
Stiffened element limiting slenderness (λr) -- 46.33 Table.B4.1a.Case5
Factored flexural buckling strength(φPn33): [Kip] 57.58 Cl.E3
Unbraced length (L33) [ft] 12.50 Cl.E2
Effective slenderness ((KL/r)33) -- 61.69 Cl.E2
Elastic critical buckling stress (Fe33) [Kip/in2] 75.21 Eq.E3-4
Effective area of the cross section based on the effective width (A... [in2] 2.52
Critical stress for flexural buckling (Fcr33) [Kip/in2] 25.39 Eq.E3-2
Nominal flexural buckling strength (Pn33) [Kip] 63.98 Eq.E3-1
Compression in the minor axis 22
Ratio : 0.00
Capacity : 19.98 [Kip] Reference : Cl.E3
Demand : 0.00 [Kip] Ctrl Eq. : D1 at 0.00%
Intermediate results Unit Value Reference
Section classification
Unstiffened element classification -- Non slender
Unstiffened element slenderness (λ) -- 10.10
Unstiffened element limiting slenderness (λr) -- 17.41 Table.B4.1a.Case1
Stiffened element classification -- Non slender
Stiffened element slenderness (λ) -- 29.06
Stiffened element limiting slenderness (λr) -- 46.33 Table.B4.1a.Case5
Factored flexural buckling strength(φPn22): [Kip] 19.98 Cl.E3
Unbraced length (L22) [ft] 12.50 Cl.E2
Effective slenderness ((KL/r)22) -- 168.80 Cl.E2
Elastic critical buckling stress (Fe22) [Kip/in2] 10.05 Eq.E3-4
Effective area of the cross section based on the effective width (A... [in2] 2.52
Critical stress for flexural buckling (Fcr22) [Kip/in2] 8.81 Eq.E3-3
Nominal flexural buckling strength (Pn22) [Kip] 22.20 Eq.E3-1
Factored torsional or flexural-torsional buckling strength(φPn11): [Kip] 46.97 Cl.E4
Unbraced length (L11) [ft] 12.50 Cl.E2
Torsional or flexural-torsional elastic buckling stress (Fe11) [Kip/in2] 33.89 Eq.E4-2
Effective area of the cross section based on the effective width (A... [in2] 2.52
Critical stress for torsional or flexural-torsional buckling (Fcr11) [Kip/in2] 20.71 Eq.E3-2
Nominal torsional or flexural-torsional buckling strength (Pn11) [Kip] 52.19 Eq.E4-1
Flexural Design
Bending about major axis, M33
Ratio : 0.62
Capacity : 11.78 [Kip*ft] Reference : Cl.F2.2
Demand : -7.35 [Kip*ft] Ctrl Eq. : D2 at 50.00%
Intermediate results Unit Value Reference
Section classification
Unstiffened element classification -- Compact
Unstiffened element slenderness (λ) -- 10.10
Limiting slenderness for noncompact unstiffened element (λr) -- 31.09
Limiting slenderness for compact unstiffened element (λp) -- 11.81
Stiffened element classification -- Compact
Stiffened element slenderness (λ) -- 29.06
Limiting slenderness for noncompact stiffened element (λr) -- 177.22
Limiting slenderness for compact stiffened element (λp) -- 116.90
Factored yielding strength(φMn): [Kip*ft] 12.89 Cl.F2.1
Yielding (Mn) [Kip*ft] 14.33 Eq.F2-1
Factored lateral-torsional buckling strength(φMn): [Kip*ft] 11.78 Cl.F2.2
Limiting laterally unbraced length for yielding (Lp) [ft] 4.05 Eq.F2-5
Page7
Effective radius of gyration used in the determination of Lr (r ts) [in] 1.05 Eq.F2-7
Lateral-torsional factor (c) -- 1.00 Eq.F2-8a
Limiting laterally unbraced length for inelastic lateral-torsional bucklin... [ft] 13.66 Eq.F2-6
Lateral-torsional buckling modification factor (Cb) -- 1.00 Eq.F1-1
Nominal lateral-torsional buckling moment strength (Mn) [Kip*ft] 13.09 Eq.F2-2
Bending about minor axis, M22
Ratio : 0.00
Capacity : 3.51 [Kip*ft] Reference : Cl.F6.1
Demand : 0.00 [Kip*ft] Ctrl Eq. : D1 at 0.00%
Intermediate results Unit Value Reference
Section classification
Unstiffened element classification -- Compact
Unstiffened element slenderness (λ) -- 10.10
Limiting slenderness for noncompact unstiffened element (λr) -- 31.09
Limiting slenderness for compact unstiffened element (λp) -- 11.81
Stiffened element classification -- Compact
Stiffened element slenderness (λ) -- 29.06
Limiting slenderness for noncompact stiffened element (λr) -- 177.22
Limiting slenderness for compact stiffened element (λp) -- 116.90
Factored yielding strength about a geometric axis(φMn): [Kip*ft] 3.51 Cl.F6.1
Yielding (Mn) [Kip*ft] 3.90 Eq.F6-1
Shear Design
Shear in major axis 33
Ratio : 0.00
Capacity : 24.89 [Kip] Reference : Cl.G1
Demand : 0.00 [Kip] Ctrl Eq. : D1 at 0.00%
Intermediate results Unit Value Reference
Factored shear capacity(φVn): [Kip] 24.89 Cl.G1
Web buckling coefficient (kv) -- 1.20 Cl.G6
Web buckling coefficient (Cv) -- 1.00 Eq.G2-9
Nominal shear strength (Vn) [Kip] 27.66 Eq.G6-1
Shear in minor axis 22
Ratio : 0.13
Capacity : 17.82 [Kip] Reference : Cl.G1
Demand : 2.35 [Kip] Ctrl Eq. : D2 at 0.00%
Intermediate results Unit Value Reference
Factored shear capacity(φVn): [Kip] 17.82 Cl.G1
Web buckling coefficient (kv) -- 5.34 Eq.G2-5
Web buckling coefficient (Cv) -- 1.00 -
Nominal shear strength (Vn) [Kip] 17.82 Eq.G2-1
Combined Actions Design
Page8
Combined flexure and axial
Ratio : 0.62
Ctrl Eq. : D2 at 50.00% Reference : Eq.H1-1b
Intermediate results Unit Value Reference
Interaction of flexure and axial force: -- 0.62 Eq.H1-1b
Available flexural strength about strong axis (Mc33) [Kip*ft] 11.78 Cl.H1.1
Available flexural strength about weak axis (Mc22) [Kip*ft] 3.51 Cl.H1.1
Available axial strength (Pc) [Kip] 68.04 Cl.H1.1
Page9
Current Date: 1/8/2024 10:48 AM
Units system: English
File name: W:\20230410\03_Production\05_Stru\Calcs\Existing Corridor Beam.rcb
Design Results Continuous Beam
Design code AISC 360-2016 LRFD
General Information
Spans:
Span Span length Section Material
[ft]
1 6.00 W 6X8.5 A7
Nodes:
Distance Restraint Tx Ty Rz
[ft]
0.00 Pinned 1 1 0
6.00 Pinned 1 1 0
Load Conditions
Condition Description Comb. Category Duration Self Weight
DL Dead Load No DL -- Yes
LL Live Load No LL -- --
S1 DL Yes Service -- Yes
S2 0.6DL+0.6LL Yes Service -- Yes
D1 1.4DL Yes Design -- Yes
D2 0.9DL+LL Yes Design -- Yes
Page1
EXISTING CORRIDOR BEAM
EVALUATION FOR GRAVITY LOADING
[ft] [ft] [Kip/ft] [Kip/ft]
DL 1 0.00 6.00 -1.38 -1.38
LL 1 0.00 6.00 -1.25 -1.25
Loads summary
[Kip] [Kip] [Kip*ft]
1 D1 0.00 5.81 0.00
2 D1 0.00 5.81 0.00
1 D2 0.00 7.49 0.00
2 D2 0.00 7.49 0.00
1 Min. 0.00 5.81 0.00
2 Min. 0.00 5.81 0.00
1 Max. 0.00 7.49 0.00
2 Max. 0.00 7.49 0.00
Member forces and inflection points
Station Condition Distance Shear V Moment M
[%] [ft] [Kip] [Kip*ft]
0 D1 0.00 5.81 0.00
50 D1 3.00 0.00 8.72
100 D1 6.00 -5.81 0.00
0 D2 0.00 7.49 0.00
50 D2 3.00 0.00 11.23
100 D2 6.00 -7.49 0.00
Critical deflections
Condition Span Distance @ Deflection Allowable
[ft] [%] [in] f(L) [in]
S1 1 3.00 50.00 0.10012 (L/719) 0.20000
S2 1 3.00 50.00 0.11435 (L/630) 0.20000
Envelopes
M33 bending moment:
V2 shear forces:
Forces [Kip], Length [ft]
Vertical Translation
Deflection [in], Length [ft]
Design
Span : 1 (W 6X8.5_A7) - OK
Section information
Section name: W 6X8.5 (US)
Dimensions bf = 3.940 [in] Width d = 5.830 [in] Depth k = 0.445 [in] Distance k k1 = 0.500 [in] Distance k1 tf = 0.195 [in] Flange thickness tw = 0.170 [in] Web thickness
Properties Unit Major axis Minor axis
Gross area of the section. (Ag) [in2] 2.520
Moment of Inertia (local axes) (I) [in4] 14.900 1.990
Moment of Inertia (principal axes) (I') [in4] 14.900 1.990
Bending constant for moments (principal axis) (J') [in] 0.000 0.000
Radius of gyration (local axes) (r) [in] 2.432 0.889
Radius of gyration (principal axes) (r') [in] 2.432 0.889
Saint-Venant torsion constant. (J) [in4] 0.033
Section warping constant. (Cw) [in6] 15.800
Distance from centroid to shear center (principal axis) (xo,yo) [in] 0.000 0.000
Top elastic section modulus of the section (local axis) (Ssup) [in3] 5.100 1.010
Bottom elastic section modulus of the section (local axis) (Sinf) [in3] 5.100 1.010
Top elastic section modulus of the section (principal axis) (S'sup) [in3] 5.100 1.010
Bottom elastic section modulus of the section (principal axis) (S'inf) [in3] 5.100 1.010
Plastic section modulus (local axis) (Z) [in3] 5.730 1.560
Plastic section modulus (principal axis) (Z') [in3] 5.730 1.560
Polar radius of gyration. (ro) [in] 2.589
Area for shear (Aw) [in2] 1.540 0.990
Torsional constant. (C) [in3] 0.147
Material : A7
Properties Unit Value
Yield stress (Fy): [Kip/in2] 30.00
Tensile strength (Fu): [Kip/in2] 60.00
Elasticity Modulus (E): [Kip/in2] 29000.00
Shear modulus for steel (G): [Kip/in2] 11153.85
Design Criteria
Description Unit Value
Length for tension slenderness ratio (L) [ft] 6.00
Distance between member lateral bracing points
Length (Lb) [ft]
Top Bottom
0.00 12.50
Laterally unbraced length
Length [ft] Effective length factor
Major axis(L33) Minor axis(L22) Torsional axis(Lt) Major axis(K33) Minor axis(K22) Torsional axis(Kt)
6.00 6.00 6.00 1.0 1.0 1.0
Additional assumptions
Continuous lateral torsional restraint No
Tension field action No
Continuous flexural torsional restraint No
Effective length factor value type None
Major axis frame type Sway
Minor axis frame type Sway
Design Checks
Axial Tension Design
Axial tension
Ratio : 0.00
Capacity : 68.04 [Kip] Reference : Cl.D2
Demand : 0.00 [Kip] Ctrl Eq. : D1 at 0.00%
Intermediate results Unit Value Reference
Factored axial tension capacity(φPn): [Kip] 68.04 Cl.D2
Nominal axial tension capacity (Pn) [Kip] 75.60 Eq.D2-1
Axial Compression Design
Compression in the major axis 33
Ratio : 0.00
Capacity : 65.47 [Kip] Reference : Cl.E3
Demand : 0.00 [Kip] Ctrl Eq. : D1 at 0.00%
Intermediate results Unit Value Reference
Section classification
Unstiffened element classification -- Non slender
Unstiffened element slenderness (λ) -- 10.10
Unstiffened element limiting slenderness (λr) -- 17.41 Table.B4.1a.Case1
Stiffened element classification -- Non slender
Stiffened element slenderness (λ) -- 29.06
Stiffened element limiting slenderness (λr) -- 46.33 Table.B4.1a.Case5
Factored flexural buckling strength(φPn33): [Kip] 65.47