CB_Amendment 0008 Reissued drawings_final.pdf

PDF 4 MB Posted

Attached to
Camp Buckner Phase I, West Point, New York
Solicitation number
W912DS21B0005
Issued by

About this file

This document summarizes a federal contract opportunity for revitalization work at Camp Buckner in West Point, New York. The U.S. Army Corps of Engineers, New York District intends to issue an invitation for bids seeking a firm-fixed price contract to repair 12 buildings and upgrade utility infrastructure at the camp. Work includes abatement of hazardous materials, installation of air conditioning and vapor barriers, and modernization of fire suppression, alarm, and mass notification systems. The contract value is estimated between $10-25 million and will be set aside for small businesses. The solicitation is anticipated to be issued on December 10-15, 2020 with bids due approximately 30 days later and a site visit scheduled December 16-18. The period of performance is 400 calendar days from notice to proceed. Interested parties can access the solicitation on Contract Opportunities at beta.sam.gov when posted. The North American Industry Classification code is 236220 and bids must be submitted electronically.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

X

J

S

F

T

T

2/E201

1200:5

12.47KV

120V

(L,S,I,G)

800A

100A

45KVA

T1

PC

SM

TC

SWITCHBOARD

ELECTRICAL SYMBOLS

SITE PLAN

DRAWING/DETAIL NUMBER

SHEET NUMBER ON WHICH

DETAIL IS DRAWN

KEYED NOTE REFERENCE

LIGHTING

SHEET NUMBER ON WHICH

CONDITION IS SHOWN

EXIT SIGN, ARROWS AS INDICATED. DARKENED AREA DENOTES

LIGHTED FACE

EMERGENCY LIGHTING UNIT, FIXTURE TYPE AS NOTED

SWITCH, SPST, 20A, 120/277V

SWITCH, 20A, 120/277V, "2" DENOTES DPST, "3" DENOTES THREE-WAY, "4"

DENOTES FOUR-WAY, "X" DENOTES LIGHT FIXTURES CONTROLLED

SWITCH, SPST, 20A, 120/277V, "K" DENOTES KEY, "P" DENOTES PILOT LIGHT,

"D" DENOTES DIMMING, "T" DENOTES TIMER, "LV" DENOTES LOW VOLTAGE

SWITCH.

RECEPTACLES AND OUTLETS

FLUSH FLOOR MOUNTED RECEPTACLE, NEMA 5-20R

JUNCTION BOX

CIRCUITING AND WIRING

DIRECT ELECTRICAL CONNECTION TO EQUIPMENT

CONDUIT STUB DOWN

CONDUIT STUB UP

LA-2,4,6

CIRCUIT BELOW SLAB OR GRADE OR CAST IN SLAB

ABOVE GRADE UNLESS OTHERWISE NOTED

WHERE SHOWN, INDICATES HOMERUN TO PANEL

WITH CIRCUIT NUMBER(S) AS INDICATED.

ELECTRICAL EQUIPMENTONE LINE AND RISER DIAGRAMS (CONT'D)

PHOTOCELL CONTROL

SINGLE OR THREE PHASE MOTOR WITH HORSEPOWER AND PHASE AS

INDICATED. IN THIS EXAMPLE, "1-3PH" DENOTES 1 HORSEPOWER 3 PHASE

DISCONNECT (SAFETY) SWITCH IN THIS EXAMPLE, "200/3/150" DENOTES

200 AMPERES / 3 POLE / 150 AMP FUSE. "NF" DENOTES NON-FUSED.

PROVIDE 30/3/NF UNLESS OTHERWISE NOTED. FUSES SHALL BE DUAL-ELEMENT

RK5 TYPE UNLESS NOTED OTHERWISE. "N-3R" DENOTES NEMA 3R

WEATHERPROOF ENCLOSURE.

COMBINATION DISCONNECT (SAFETY) SWITCH AND MOTOR STARTER, IN

THIS EXAMPLE, "15CB/3/0" DENOTES 15A CIRCUIT BREAKER, 3 POLES, NEMA 0

STARTER SIZE. "NF" DENOTES NON-FUSED SWITCH. "FS" INDICATES FUSED SWITCH

WITH THE FUSE RATING INDICATED; FOR EXAMPLE "10FS/3P/N-0" DENOTES 10A

FUSES IN SWITCH, 3 POLES, NEMA 0 STARTER SIZE.

FUSES SHALL BE DUAL-ELEMENT RK5 TYPE UNLESS NOTED OTHERWISE.

"N-3R" DENOTES NEMA 3R WEATHERPROOF ENCLOSURE. SINGLE PHASE,

FRACTIONAL HORSE POWER. MANUAL MOTOR STARTER, AND

DISCONNECT SWITCH WITH THERMAL OVERLOAD

ONE LINE AND RISER DIAGRAMS

CURRENT TRANSFORMER(CT), RATED AS SHOWN

LIGHTNING ARRESTOR

GROUND CONNECTION

POTENTIAL TRANSFORMER(PT), RATING AS SHOWN

TRANSFORMER, DESIGNATION AND RATINGS AS NOTED

(DELTA-CONNECTED PRIMARY AND WYE - CONNECTED

SECONDARY) UNLESS OTHERWISE NOTED.

SWITCH, RATINGS AS SHOWN, 3 POLE UNLESS

OTHERWISE NOTED

CIRCUIT BREAKER, TRIP RATING AS SHOWN, 3 POLE

UNLESS OTHERWISE NOTED

DENOTES CIRCUIT BREAKER WITH ADJUSTABLE TRIP

SETTINGS AS NOTED BELOW:

L=LONG, S=SHORT, I=INSTANTANEOUS, G=GROUND FAULT

PROTECTION, GI = GROUND FAULT, INDICATION ONLY

MISCELLANEOUS

SCHEDULE DEFINED QUANTITIES

GENERAL NOTES

A. PROVIDE BRANCH CIRCUITS WITH CONDUCTOR AND CONDUIT SIZES AS INDICATED ON

PANELBOARD SCHEDULES. UP TO THREE CIRCUITS MAY BE COMBINED IN ONE 3/4 INCH

CONDUIT IF ALL CONDUCTORS ARE #12 AWG. UP TO THREE CIRCUITS MAY BE COMBINED

IN ONE 1 INCH CONDUIT IF ALL CONDUCTORS ARE #10 AWG OR SMALLER. PROVIDE

SEPARATE NEUTRALS FOR EACH CIRCUIT IN A RACEWAY AND ONE GROUNDING

CONDUCTOR FOR EACH RACEWAY. FOR SHARED RACEWAYS, INCREASE CONDUIT SIZE

IF REQUIRED TO COMPLY WITH NFPA 70 OR TO ACCOMMODATE FIELD CONDITIONS.

B. UNLESS OTHERWISE NOTED, ALL CONDUCTORS ARE SIZED FOR TYPE THWN, THHN,

RATED FOR 75°C (MINIMUM).

C. PROVIDE FEEDERS WITH CONDUCTOR AND CONDUIT SIZES AS INDICATED ON

PANELBOARD SCHEDULES AND SINGLE LINE DIAGRAMS. FEEDERS SHALL BE IN

SEPARATE CONDUITS AND SHALL NOT BE PERMITTED TO SHARE CONDUITS WITH OTHER

FEEDERS OR CIRCUITS. INCREASE CONDUIT SIZE IF REQUIRED TO COMPLY WITH NFPA

70 OR TO ACCOMMODATE FIELD CONDITIONS.

D. CIRCUITS ARE SIZED ASSUMING NO MORE THAN THREE CURRENT CARRYING

CONDUCTORS IN A SINGLE CONDUIT. FOR CONDUITS CONTAINING MORE THAN THREE,

PROVIDE APPROPRIATE DERATING OF CONDUCTORS PER NEC.

E. FOR ALL LOCATIONS WHERE MOTORS AND MOTOR STARTERS ARE SHOWN, PROVIDE

CONTROL CIRCUITS FROM MECHANICAL CONTROL PANELS, THERMOSTATS, REMOTE

SENSORS, TIME CLOCKS, ETC. AS SPECIFIED.

F. ELECTRICAL WORK INDICATED IS NEW UNLESS NOTED OTHERWISE.

G. TRACE EXISTING POWER AND LIGHTING LOADS AFFECTED DURING CONSTRUCTION.

IDENTIFY EXISTING CIRCUITS TO REMAIN ON PANEL SCHEDULES.

H. FIELD VERIFY EXISTING CONDITIONS. CONTACT CONTRACTING OFFICER WHERE FIELD

CONDITIONS ARE DIFFERENT FROM DRAWINGS.

I. PERFORM ALL ELECTRICAL WORK IN ACCORDANCE WITH NFPA 70 AND APPLICABLE

UFC. IN THE EVENT OF A CONFLICT BETWEEN NFPA 70 AND UFC, THE MOST STRINGENT

WILL APPLY.

DRAWING/DETAIL REFERENCE KEY

MOUNTING HEIGHTS (UNLESS OTHERWISE NOTED)

48" A.F.F. TO CENTER OF SWITCH

WALL DIMMER SWITCHES:

RECESSED WALL MOUNTED DUPLEX WALL RECEPTACLE, NEMA 5-20R, 20A,

125V, 18" ABOVE FINISHED FLOOR UNO. REFER TO RECEPTACLE TYPE

DESIGNATIONS BELOW.

RECESSED WALL MOUNTED QUAD WALL RECEPTACLE CONSISTING OF TWO

DUPLEX RECEPTACLE. REFER TO RECEPTACLE TYPE DESIGNATIONS BELOW.

WALL MOUNTED SPECIAL RECEPTACLE, NEMA CONFIGURATION AS NOTED

FLUSH CEILING/SOFFIT MOUNTED 120V RECEPTACLE. NEMA 5-20R UNLESS

NOTED OTHERWISE.

TIMECLOCK

X

ABBREVIATIONS

SPD

VFD

SURGE PROTECTION DEVICE

VARIABLE FREQUENCY DRIVE

MGB MAIN GROUNDING BUSBAR

GEC GROUNDING ELECTRODE CONDUCTOR

(ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED ON PLANS)

NEW UNDERGROUND SECONDARY

DUPLEX RECEPTACLE, SWITCHED OUTLET, NEMA 5-20R.

EXISTING PADMOUNTED TRANSFORMER

SHADING DENOTES FIXTURE ON EMERGENCY POWER CIRCUIT, FIXTURE

TYPE AS NOTED

1'X4' SURFACE, PENDANT, OR WALL MOUNTED FLUORESCENT, FIXTURE

TYPE AS NOTED

SHADING DENOTES FIXTURE EMERGENCY BATTERY BACKUP. NL DENOTES

NIGHT LIGHT, FIXTURE TYPE AS NOTED

DOWNLIGHT OR GLOBE FIXTURE, FIXTURE TYPE AS NOTED

WALLWASH FIXTURE, FIXTURE TYPE AS NOTED

WALL MOUNTED FIXTURE, FIXTURE TYPE AS NOTED

2'X4' FLUORESCENT TROFFER, FIXTURE TYPE AS NOTED

A

A

A

A

A

A

A

A

A

A

DRY-TYPE TRANSFORMER

DISTRIBUTION PANEL OR PANELBOARD. (FLUSH OR SURFACE

MOUNT) AS INDICATED ON PANEL SCHEDULE. HATCH REPRESENTS

CLEARANCE

A

2'X2' FLUORESCENT, FIXTURE TYPE AS NOTED

48" A.F.F. TO CENTER OF

SWITCH

WALL SWITCHES:

WALL RECEPTACLES:

UNFINISHED AREAS: 42" A.F.F.

TO CENTER OF RECEPTACLE

FINISHED AREAS: AS INDICATED

X

K

GFI

WP

A

ROOM CONTROLLER CEILING MOUNT FOR LIGHTING AND RECEPTACLE

CONTROL.

OCCUPANCY SENSOR CONTROL, CEILING MOUNTED, HARSH ENVIRONMENT

TYPE AS SPECIFIED.

RECEPTACLE TYPE DESIGNATIONS:

WP DENOTES WEATHERPROOF COVER RATED FOR "IN USE" OPERATION

USB DENOTES DUPLEX RECEPTACLE WITH ONE USB-A PORT AND ONE

USB-C PORT IN ADDITION TO THE TWO 120VAC PORTS

A ARC FAULT INTERRUPTER TYPE, WIRED FOR ARC FAULT TRIP FOR

DESIGNATED RCPT ONLY; NON-FEED-THRU INSTALLATION

AF ARC FAULT INTERRUPTER TYPE, WIRED FOR ARC FAULT PROTECTION

OF RCPT AND ALL RCPT'S DOWNSTREAM ON SAME CIRCUIT;

FEED-THRU INSTALLATION

G GROUND FAULT INTERRUPTER TYPE, WIRED FOR GFCI TRIP FOR

DESIGNATED RCPT ONLY (NON-FEED-THRU INSTALLATION)

GF GROUND FAULT INTERRUPTER TYPE, WIRED FOR GFCI PROTECTION

OF RCPT AND ALL RCPT'S DOWNSTREAM ON SAME CIRCUIT -

FEED-THRU INSTALLATION

AF

GF COMBINATION ARC FAULT INTERRUPTER & GROUND FAULT

INTERRUPTER TYPE RECEPTACLE, WIRED FOR ARC FAULT

PROTECTION AND GROUND FAULT PROTECTION OF RCPT AND ALL

RCPT'S DOWNSTREAM ON SAME CIRCUIT; FEED-THRU

INSTALLATION

H66 DENOTES MOUNTING HEIGHT IN INCHES ABOVE FINISHED FLOOR TO BOTTOM

OF RECEPTACLE BOX; 66" AFF IN THIS EXAMPLE

C6 DENOTES MOUNTING HEIGHT TO BOTTOM OF RECEPTACLE BOX IN INCHES

ABOVE LAVATORY, COUNTER, SINK, OR DESK; 6" ABOVE COUNTER/SINK/DESK

IN THIS EXAMPLE

SM DENOTES SURFACE MOUNTED RECEPTACLE ON EXST

WALL/PARTITION TO REMAIN.

N14-30R SPECIAL PURPOSE RCPT TYPE; TYPE N14-30R IN THIS EXAMPLE.

SEE SPECIAL PURPOSE RECEPTACLE SCHEDULE.

EWC RECEPTACLE FOR ELECTRICAL WATER COOLER UNIT. REFER TO

PLUMBING DRAWINGS FOR REQUIREMENTS AND COORDINATE

RECEPTACLE MOUNTING / LOCATION WITH EQUIPMENT AND FIELD

CONDITIONS.

JB-12X12X4

12 INCH X 12 INCH X 4 INCH NEMA 1 JUNCTION BOX

WITH SCREW COVER.

OC

RC

S

S

S

RGS RIGID GALVANIZED STEEL

SYMBOLS DESCRIPTION

GROUNDING ELECTRODE CONDUCTOR #1/0 AWG UNLESS SPECIFIED

OR INDICATED OTHERWISE; BARE COPPER CONDUCTOR 30" BELOW

GRADE WHERE SHOWN EXTERIOR TO BUILDING; INSULATED IN 1"

CONCEALED CONDUIT WHERE SHOWN INTERIOR TO BUILDING

GEC

TELECOMMUNICATIONS BONDING BACKBONE CONDUCTOR, #2 AWG

IN 1" CONDUIT; EXPOSED IN TELECOMMUNICATIONS SPACES AND

CONCEALED ALL OTHER.

TBC

EQUIPMENT GROUNDING CONDUCTOR #4/0 AWG UNLESS SPECIFIED

OR INDICATED OTHERWISE BLACK INSULATED COPPER.

EGC

GROUNDING BONDING CONDUCTOR #4/0 AWG UNLESS SPECIFIED OR

INDICATED OTHERWISE BARE COPPER.

GBJ

GROUNDING BONDING CONDUCTOR #2 AWG UNLESS SPECIFIED OR

INDICATED OTHERWISE BARE SOLID TINNED COPPER.

GROUND ROD WITH GROUND CONDUCTOR EXOTHERMICALLY

CONNECTED UNLESS NOTED OR SPECIFIED OTHERWISE. SEE DETAIL

B1/E501: MINIMUM SPACING BETWEEN GROUND RODS SHALL BE 20

FEET. COORDINATE LOCATIONS WITH FIELD CONDITIONS.

MECHANICAL GROUND CONDUCTOR CONNECTION

EXOTHERMIC WELD GROUND CONDUCTOR CONNECTION

TELECOMMUNICATIONS PRIMARY BONDING BUS; REFER TO

TELECOMMUNICATIONS DRAWINGS AND SPECIFICATIONS FOR GROUND

CONDUCTORS/CONNECTIONS, REQUIREMENTS AND

LOCATION/MOUNTING.

TELECOMMUNICATIONS RACK BONDING BUS; REFER TO

TELECOMMUNICATIONS DRAWINGS AND SPECIFICATIONS FOR GROUND

CONDUCTORS/CONNECTIONS, REQUIREMENTS AND

LOCATION/MOUNTING.

PBB

RBB

GROUND ROD WITH GROUND CONDUCTORS EXOTHERMICALLY

CONNECTED WITHIN A TEST WELL ASSEMBLY. SEE DETAIL

B4/E501: MINIMUM SPACING BETWEEN GROUND RODS SHALL BE 20

FEET. COORDINATE LOCATIONS WITH FIELD CONDITIONS.

T

GROUNDING LEGEND

SPD SURGE PROTECTION DEVICE

HOA

N-3R

HAND-OFF-AUTO (HOA) CONTROL SWITCH IN ENCLOSURE.

N-3R INDICATES NEMA 3R WEATHERPROOF ENCLOSURE.

1-3PH

200/3/150

10FS/3P/N-0

100/3

F-100

F-MFR

TC

OVERLOAD RELAYS, 1 EACH PER PHASE

FUSED DISCONNECT SWITCH. SEE DESCRIPTIONS ABOVE FOR

DISCONNECT SWITCH AND FUSE CHARACTERISTICS.

FUSE, EACH PHASE. SEE DISCONNECT SWITCH DESCRIPTIONS ABOVE

FOR 600V OR LESS FUSE CHARACTERISTICS. FUSES WITH RATINGS

GREATER THAN 600 VOLTS SHALL BE CURRENT LIMITING MEDIUM

VOLTAGE PRIMARY TYPE, UNLESS INDICATED OR SPECIFIED OTHERWISE.

IN THIS EXAMPLE, DENOTES 100 AMPERE, 3 POLE DEVICE.

IN THIS EXAMPLE, DENOTES DEVICE FUSED AT 100 AMPERES. SEE

DESCRIPTIONS ABOVE FOR DISCONNECT SWITCH AND FUSE CHARACTERISTICS.

DENOTES DEVICE FUSED IN ACCORDANCE WITH UTILIZATION EQUIPMENT

MANUFACTURER'S INSTRUCTIONS. SEE DESCRIPTIONS ABOVE FOR

DISCONNECT SWITCH AND FUSE CHARACTERISTICS.

TIME CLOCK. SEE WIRING DIAGRAMS FOR ACCESSORIES AND

CONFIGURATION.

MOTOR WITH HORSEPOWER INDICATED; 1HP 3 PHASE IN THIS EXAMPLE

MOTOR STARTER WITH NEMA RATING INDICATED;

NEMA 0 IN THIS EXAMPLE

1-3PH

MOTORS AND CONTROLS

J. THE ELECTRICAL DISTRIBUTION SYSTEM HAS BEEN PRIVATIZED UNDER THE U.S.

ARMY'S UTILITIES PRIVATIZATION (UP) INITIATIVE. THE SYSTEM OWNER IS CITY LIGHT &

POWER AWP, LLC (CLP). COORDINATE ELECTRICAL WORK WITH CLP. POINT OF

CONTACT IS TODD HUGHES (845) 322-8225.

AIC AMPS INTERRUPTING CAPACITY

SCCR SHORT CIRCUIT CURRENT RATING

COR CONTRACTING OFFICER'S REPRESENTATIVE

CLP CITY LIGHT & POWER

FAMN FIRE ALARM/MASS NOTIFICATION CONTROL PANEL

EM

EM1

N-3R

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

E-001

E L E

C T

R

IC

A L L

E G

E N

D A

N D

G E

N E

R A

L N

O T

E S

W E

S T

P O

IN

T

N

Y W

M

C C

A L L

J H

U R

S O

N

D K

O L O

W

IT

Z

D E

C E

M B

E R

W D

S D

AMENDMENT 7

R E

V

IT

A L

IZ

A T

IO

N

O F

C A

M P

B U

C K

N E

R

R

E V

IS

E

D P

E R

A M

E N

D M

E N

T

/2

/2

F E

F E

F E

F E

F E

B-1 B-2 B-3 B-4 B-5 B-6 B-7

B-A

B-B

UTILITY

MEN WOMEN

D1

E-501

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

USB

WP

G

N-3R

FAMN PANEL

AF

GF

H66H66

AF

GF

H66

H66

H66

USB

USB

H66

H66

AF

GF

H66

H66

H66

AF

GF

H66

H66

H66

H66

AF

GF

H66

H66 H66

AF

GF

H66

H66

H66

H66

H66

AF

GF

H66

H66

H66

AF

GF

H66

H66

H66

H66

AF

GF

H66

H66

H66

H66

AF

GF

H66

H66

H66

H66

AF

GF

H66

WP

H48

ACCU-1

N-3R

H48

AC-1

GEC

G E

C

G E C

G E

C

PBB RBB

G E

C

B-39

G

B-23

ACCU-1

GF

B-27

T

EP101

D9

AHU-1 OR AHU-3 AS INDICATED

ON MECHANICAL PLANS AND

CIVIL UTILITY PLANS

H42

GEC GEC

PNL "B"

L-1 L-2 L-3 L-4 L-5 L-6 L-7

L-A

L-B

MEN'S SHOWER

MEN'S LOCKER

MEN

WOMEN

CORRIDOR

WOMEN'S

SHOWER

WOMEN'S

LOCKER

JANJAN

G

G C6

G C6

G C6

G C6

G C6

G C6

G C6

G C6

G C6

G C6

G C6

15 15 17

G C6

G C6

G C6

G

G

G

G C6

G C6

G C6

G C6

G C6

G C6

G C6

G C6

WP

GF

N-3R

H44 1

GEC

G E

C

G E C

G E

C

G E

C

EWC

G

T

AHU-2

L-39

EWC

G

G

H44

G

H44

G

H44

G

H44

FAMN PANEL

G

G

PNL "L"PNL "L"

B-1

B-A

USB

USB

H18

AF

GF

H18

SCALE: 3/16" = 1'-0"

026 4

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

PLAN NORTH

*TRUE NORTH VARIES

EP101

F

IR

S T

F L O

O R

P L A

N

P O

W E

R

W E

S T

P O

IN

T

N

Y W

M

C C

A L L

J H

U R

S O

N

D K

O L O

W

IT

Z

D E

C E

M B

E R

W D

S D

AMENDMENT 7

R E

V

IT

A L

IZ

A T

IO

N

O F

C A

M P

B U

C K

N E

R

SCALE: 3/16" = 1'-0"EP101

FOR BUILDINGS 1612, 1613, 1615, 1616, 1617, 1618, 1619, 1620 & 1624), UNLESS NOTED OTHERWISED1

KEYED NOTES

1. PANELBOARD "B" MOUNTED 6'-0" TO TOP AFF.

2. 2.5 INCH RIGID GALVANIZED STEEL CONDUIT MAST WITH

WEATHERHEAD AND CONDUCTORS INDICATED ON SINGLE

LINE DIAGRAM.

3. 2.5 INCH RIGID GALVANIZED STEEL CONDUIT LB FITTING FOR

SERVICE CONDUCTORS.

4. THE DISCONNECT SWITCH RATINGS AND OVERCURRENT

PROTECTION RATINGS SHOWN BELOW FOR THE MECHANICAL

HVAC EQUIPMENT ARE BASED ON THE BASIS OF DESIGN

EQUIPMENT MANUFACTURER'S RECOMMENDATIONS AND NEC

ARTICLE 430. CONTRACTOR SHALL VERIFY THE

MANUFACTURER'S INSTALLATION REQUIREMENTS FOR THE

SPECIFIC UNITS PROVIDED, AND SHALL BE RESPONSIBLE FOR

PROVIDING THE REQUIRED OVERCURRENT DEVICE RATINGS,

SWITCH RATINGS, AND FEEDER RATINGS WITH ALL REQUIRED

CHANGES PROVIDED AT NO ADDITIONAL COST TO THE

GOVERNMENT. ALL WORK SHALL COMPLY WITH THE

MANUFACTURER'S INSTRUCTIONS AND NEC ARTICLE 430.

INCLUDE PROPOSED RATINGS OF ALL RELATED ELECTRICAL

SERVICES FOR MECHANICAL EQUIPMENT IN SUBMITTALS FOR

APPROVAL.

A. SLEEPING QUARTERS 1612, 1613, 1615, 1618, & 1624:

AHU-1; 100A 3P FUSED DISCONNECT SWITCH IN NEMA

3R ENCLOSURE; 80A RK5 FUSES

B. SLEEPING QUARTERS 1616 & 1620: AHU-3; 200A 3P

FUSED DISCONNECT SWITCH IN NEMA 3R ENCLOSURE;

175A RK5 FUSES

C. SLEEPING QUARTERS 1617, & 1619: NO CENTRAL AIR

CONDITIONING AHU

D. SLEEPING QUARTERS 1612, 1613, 1615, 1616, 1617, 1618,

1619, 1620 & 1624: ACCU-1; 30A 3P FUSED DISCONNECT

SWITCH IN NEMA 3R ENCLOSURE; 25A RK5 FUSES

E. SLEEPING QUARTERS 1612, 1613, 1615, 1616, 1617, 1618,

1619, 1620 & 1624: AC-1; 30A 2P FUSED DISCONNECT

SWITCH IN NEMA 1 ENCLOSURE; 15A RK5 FUSES

F. LATRINES 1611, 1614 & 1621; AHU-2; 200A 3P FUSED

DISCONNECT SWITCH IN NEMA 3R ENCLOSURE; 175A

RK5 FUSES

5. NOT USED.

6. NOT USED.

7. NOT USED.

8. DENOTES OVERHEAD SERVICE LOCATION AND RELATED

GROUNDING WORK FOR BUILDINGS 1611, 1612, 1613, 1614,

1618, 1619, 1620, 1621, AND 1624. REFER TO CIVIL SITE PLAN

FOR UTILITY COMPANY POLE

LOCATIONS.

9. DENOTES OVERHEAD SERVICE LOCATION AND RELATED

GROUNDING WORK FOR BUILDINGS 1615, 1616, AND 1617.

REFER TO CIVIL SITE PLAN FOR UTILITY COMPANY POLE

LOCATIONS.

10. CONDUCTORS FOR AHU INDICATED ON PANEL SCHEDULE

SHALL BE EXTENDED TO AHU VIA RGS CONDUIT AT LEAST 24

INCHES BELOW GRADE. STUB UP CONDUIT IN POWER

ENTRANCE COMPARTMENT OF AHU. COORDINATE LOCATION

WITH EQUIPMENT REQUIREMENTS.

11. SURGE PROTECTIVE DEVICE (SPD) IN NEMA 1 ENCLOSURE

ADJACENT TO PANELBOARD. REFER TO SPECIFICATIONS.

12. NOT USED.

13. BOND TO WATER LINE WITHIN 5 FEET OF BUILDING

ENTRANCE.

14. BOND TO BUILDING STEEL

15. 2.5-INCH RGS CONDUIT LB FITTING FOR SERVICE

CONDUCTORS.

16. SLEEPING QUARTERS BUILDINGS: PANEL "B" MOUNTED 6'-0"

TO TOP LATRINE BUILDINGS: PANEL "L" MOUNTED 6'-0" TO

TOP.

17. DENOTES TELECOMMUNICATIONS BONDING BUS; REFER TO

TELECOMMUNICATIONS DRAWINGS AND SPECIFICATIONS FOR

GROUND CONDUCTORS/CONNECTIONS, REQUIREMENTS AND

LOCATION/MOUNTING.

18. COORDINATE RECEPTACLE MOUNTING AND LOCATION INSIDE

THE TELECOMMUNICATIONS CABINET WITH THE CABINET

LOCATION AND EQUIPMENT INSTALLED THEREIN, AS

APPROVED BY THE CONTRACTING OFFICER'S

REPRESENTATIVE.

19. DENOTES LOCATION OF PANELBOARD "L" FOR BUILDING 1614

ONLY,AS REQUIRED FOR THE BUILDING ORIENTATION ON THE

SITE RELATIVE TO THE OVERHEAD ELECTRICAL SERVICE

LINES. PROVIDE ALL WORK RELATED TO THE PANEL AS

INDICATED ON THE WEST END OF THE BUILDING, BUT

OPPOSITE HAND ORIENTATION. GROUND RODS AND RELATED

WORK SHALL BE ON PLAN NORTH SIDE OF THE BUILDING.

GENERAL NOTES

A. REFER TO DRAWING E-001 FOR ELECTRICAL LEGEND AND GENERAL

NOTES.

REFER TO CIVIL UTILITY PLAN CU101 FOR THE FOLLOWING

INFORMATION:

1. LOCATIONS AND ORIENTATION OF ALL BUILDINGS IN

PROJECT.

2. LOCATIONS AND DESIGNATIONS OF AIR HANDLER

UNITS.

3. LOCATIONS OF OVERHEAD UTILITY LINES AND

POLES.

NOTE: ELECTRICAL PLAN DRAWINGS REPRESENT THE

ELECTRICAL WORK TO BE PROVIDED IN EACH FACILITY, BUT THE

FACILITY ORIENTATION AND LAYOUT WILL VARY FROM BUILDING TO

BUILDING. COORDINATE ELECTRICAL WORK WITH CIVIL UTILITY

PLAN CU101, EXISTING FIELD CONDITIONS, AND BUILDING PLANS

ON ARCHITECTURAL, MECHANICAL, PLUMBING, AND FIRE

PROTECTION DRAWINGS.

C. NEW WIRING SHALL BE RUN CONCEALED WITHIN WALLS AND ABOVE

CEILING, EXCEPT IN UTILITY ROOM. DO NOT RUN NEW WIRING BELOW

EXISTING SLAB EXCEPT FOR CONNECTIONS REQUIRED TO ARMS ROOM

EQUIPMENT.

D. PROVIDE PERMANENT MACHINE-PRINTED PERMANENT ADHESIVE

LABELS FOR ALL RECEPTACLES DENOTING PANEL AND CIRCUIT NUMBER.

SCALE: 3/16" = 1'-0"EP101

LATRINE LEVEL 1 FLOOR PLAN - POWER (TYPICAL FOR BUILDINGS 1611, 1614, & 1621), UNLESS NOTED OTHERWISEA1

SCALE: 3/16" = 1'-0"EP101

REF SHEET: EP101

SLEEPING QUARTERS OFFICE POWERD9

NOTE: THE ALTERNATE OFFICE

LAYOUT IS INCLUDED IN

BUILDINGS 1612, 1616, AND 1620.

SLEEPING QUARTERS BARRACKS LEVEL 1 FLOOR PLAN - POWER (TYPICAL

FOR BUILDINGS 1612, 1613, 1615, 1616, 1617, 1618, 1619, 1620 & 1624)

R

E V

IS

E

D P

E R

A M

E N

D M

E N

T

/2

/2

BOILER

BUILDING

GEC

G E

C

G E C

G E

C

T

G E

C

GEC

TC

HWRP-1

1-3PH

D1

PNL "H"

D2

10FS/3P/N-0

D1

E-501

Sim

H-3

B-1 B-2

B-A

B-B

ARMS ROOM

ARMS ROOM

VESTIBULE

SM

18G

B-16 B-14

EXISTING

SECURITY PANEL

8 9

B-1 B-2

B-A

B-B

ARMS ROOM

VESTIBULE

ARMS ROOM

SM

18G

B-16

B-14

EXISTING

SECURITY PANEL

B-1 B-2 B-3

B-A

B-B

ARMS ROOM

ARMS ROOM

VESTIBULE

SM

G 18

B-16

B-14

EXISTING

SECURITY PANEL

SCALE: 3/16" = 1'-0"

026 4

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

EP102

A R

M S

R O

O M

S

B O

IL

E

R B

L D

G F

L O

O R

P L A

N

P O

W E

R

W E

S T

P O

IN

T

N

Y W

M

C C

A L L

J H

U R

S O

N

D K

O L O

W

IT

Z

D E

C E

M B

E R

W D

S D

AMENDMENT 7

R E

V

IT

A L

IZ

A T

IO

N

O F

C A

M P

B U

C K

N E

R

SCALE: 3/16" = 1'-0"EP102

BOILER BUILDING FLOOR PLAN (TYPICAL FOR BUILDINGS 1599, 1622, & 1623, UNLESS NOTED OTHERWISE)E2

SCALE: 3/16" = 1'-0"EP102

B 1620 - EXISTING ARMS ROOMSA1

SCALE: 3/16" = 1'-0"EP102

B 1616 - EXISTING ARMS ROOMSA4

SCALE: 3/16" = 1'-0"EP102

B 1612 - EXISTING ARMS ROOMA7

KEYED NOTES

1. PANELBOARD "H" MOUNTED 6'-0" TO TOP AFF. RECONNECT EXISTING

CIRCUITS TO REMAIN.

2. 2.5 INCH RIGID GALVANIZER STEEL CONDUIT MAST WITH

WEATHERHEAD FOR SERVICE CONDUCTORS. VERIFY HEIGHT

REQUIRED FOR NEW MAST WITH UTILITY COMPANY CITY LIGHT AND

POWER.

3. 2.5 INCH RIGID GALVANIZER STEEL CONDUIT LB FITTING FOR SERVICE

CONDUCTORS.

4. SURGE PROTECTIVE DEVICE (SPD) IN NEMA 1 ENCLOSURE ADJACENT

TO PANELBOARD. REFER TO SPECIFICATIONS.

5. BOND TO BUILDING STEEL AND 3-INCH COLD WATER LINE.

6. NOT USED.

7. REMOVE EXISTING RECEPTACLES AND WIRING IN ARMS ROOM AND

VESTIBULE AND PROVIDE NEW RECEPTACLE AND NEW CIRCUIT

WIRING FOR HUMIDIFIER AS INDICATED ON PLAN AND PANEL

SCHEDULES.

8. REMOVE EXISTING WIRING IN ARMS ROOM AND VESTIBULE FOR

SECURITY PANEL AND PROVIDE NEW CIRCUIT WIRING FOR SECURITY

PANEL TO REMAIN AS INDICATED ON PLAN AND PANEL SCHEDULES.

9. REMOVE EXISTING WIRING IN ARMS ROOM AND VESTIBULE FOR

EXISTING LIGHTING FIXTURES AND SWITCHES, AND PROVIDE NEW

CIRCUIT WIRING FOR EXISTING LIGHTING FIXTURES AND SWITCHES

AS INDICATED ON PLAN AND PANEL SCHEDULES.

10. WIRING AND RELATED WORK FOR PUMP HWRP-1 SHALL BE PROVIDED

FOR BOILER BUILDING 1599 ONLY.

GENERAL NOTES

DEMOLITION NOTES

REMOVE EXISTING PANELBOARD AND REPLACE WITH PANELBOARD

INDICATED. RECONNECT EXISTING LIGHTING AND POWER CIRCUITES

TO NEW PANELBOARD AS INDICATED ON PANELBOARD SCHEDULE

SHEET E-611.

REMOVE EXISTING SERVICE MAST AND REPLACE WITH SERVICE

MAST INDICATED. RECONNECT NEW ELECTRICAL SERVICE TO NEW

PANELBOARD AS INDICATED ON DETAIL D1/E-501.

D1.

D2.

A. REFER TO DRAWING E-001 FOR ELECTRICAL LEGEND AND GENERAL

NOTES.

REFER TO CIVIL UTILITY PLAN CU101 FOR THE FOLLOWING

INFORMATION:

1. LOCATIONS AND ORIENTATION OF ALL BUILDINGS IN

PROJECT.

2. LOCATIONS AND DESIGNATIONS OF AIR HANDLER UNITS.

3. LOCATIONS OF OVERHEAD UTILITY LINES AND POLES.

NOTE: ELECTRICAL PLAN DRAWINGS REPRESENT THE

ELECTRICAL WORK TO BE PROVIDED IN EACH FACILITY, BUT THE

FACILITY ORIENTATION AND LAYOUT WILL VARY FROM BUILDING TO

BUILDING. COORDINATE ELECTRICAL WORK WITH CIVIL UTILITY

PLAN CU101, EXISTING FIELD CONDITIONS, AND BUILDING PLANS ON

ARCHITECTURAL, MECHANICAL, PLUMBING, AND FIRE PROTECTION

DRAWINGS.

C. NEW WIRING SHALL BE RUN CONCEALED WITHIN WALLS AND ABOVE

CEILING, EXCEPT IN UTILITY ROOM. DO NOT RUN NEW WIRING BELOW

EXISTING SLAB EXCEPT FOR CONNECTIONS REQUIRED TO ARMS ROOM

EQUIPMENT.

D. EMERGENCY LIGHTING UNITS AND EQUIPMENT SHALL BE WIRED AHEAD

OF LOCAL SWITCHES OR OCCUPANCY SENSORS ON AN UNSWITCHED LEG

OF THE BRANCH CIRCUITS INDICATED.

R

E V

IS

E

D P

E R

A M

E N

D M

E N

T

/2

/2

2.5 INCH RGS CONDUIT LB

FITTING FOR SERVICE CONDUIT.

LOCATE FITTING FOR

ENTRANCE CONDUIT TO

DIRECTLY ENTER THE WIRING

GUTTER BELOW THE

PANELBOARD.

INSULATED ATTACHMENT POINT FOR

OVERHEAD SERVICE DROP.

ATTACHMENT POINT TO BE LOCATED ON

MAST 12-16" BELOW WEATHERHEAD.

ADJUST HEIGHT TO ACCOMMODATE

FIELD CONDITIONS. CLP WILL PROVIDE

OVERHEAD CONDUCTOR SUPPORT

CABLE FOR CONNECTION BY

CONTRACTOR.

OVERHEAD SERVICE CONDUCTORS BY CITY LIGHT &

POWER (ELECTRICAL UTILITY SERVICE PROVIDER)

EXTENDING DOWN TO THE SERVICE MAST CONNECTIONS

2.5-INCH RIGID GALVANIZED STEEL CONDUIT MAST

WITH WEATHERHEAD AND SERVICE MAST

CONDUCTORS. PROVIDE 3 FEET OF SLACK CABLE

FOR DRIP LOOP IN SERVICE CONDUCTORS BELOW

WEATHERHEAD. LOCATE SERVICE MAST DIRECTLY

BELOW ROOF OVERHANG SO THAT WEATHERHEAD

AND DRIP LOOP ARE AT LEAST 10'-0" ABOVE GRADE

AND WALKWAY. VERIFY LOCATION WITH

CONTRACTING OFFICER'S REPRESENTATIVE AND

CITY LIGHT & POWER; ADJUST SERVICE MAST

LOCATION AS REQUIRED TO COORDINATE WITH FIELD

CONDITIONS AND NFPA 70 REQUIREMENTS.

CONNECTION OF SERVICE MAST CONDUCTORS BY

CONTRACTOR TO OVERHEAD LINES WILL BE MADE BY CLP.

SPD

DRIVEN GROUND ROD

COPPER CLAD STEEL

3/4" X 10' (MINIMUM)

M

IN

SIZE AS

INDICATED

CONDUCTOR

BARE GROUND

CONNECTION

EXOTHERMIC WELD

FINISHED GRADE

SPD

THE TEST WELL SHALL BE SET IN A

24" x 24" x 5" THICK CONCRETE SLAB.

12" DIAMETER

EXOTHERMIC

WELD

COPPER CONDUCTOR

AS SHOWN ON

GROUNDING PLAN

NOTES 1 AND 2 3/4" x 10'-0" COPPERCLAD STEEL

GROUND ROD

PVC GROUND ROD TEST WELL

WITH 1/4" GALVANIZED STEEL

COVER. PROVIDE LABEL ON LID

INDICATING "GROUND ACCESS

WELL"

GRAVEL

NOTES:

1.

2.

COORDINATE INSTALLATION WITH SITE CONDITIONS.

TEST WELL SHALL BE LOCATED IN AREAS NOT SUBJECT TO VEHICULAR

TRAFFIC; VERIFY LOCATION WITH CONTRACTING OFFICER'S

REPRESENTATIVE.

NOTE 6

COPPER

GROUNDING

ELECTRODE

CONDUCTOR (TYP)

NEUTRAL BUS

G N

D B

U S

20' MIN

GROUND LUG BUSHING (TYP)

GROUNDING ELECTRODE

CONDUCTOR CONDUIT (TYP)

EXOTHERMIC CONNECTION-TYPICAL

FOR ALL CONNECTIONS TO GROUND

ELECTRODES, UNO.

MAIN BONDING JUMPER

NEAREST AVAILABLE

EFFECTIVELY

GROUNDED METAL

STRUCTURE MEMBER

EXST

GROUND

ELECTRODE

CONNECT TO UNDERGROUND

WATER SERVICE MAIN LINE

WITHIN 5' INSIDE BUILDING

COMPRESSION/BOLTED LUG CONNECTION-

TYPICAL FOR ALL BUS CONNECTIONS.

SERVICE EQUIPMENT-PANELBOARD

GROUND LUG BUSHING (TYP)

BRANCH CIRCUIT/

FEEDER CONDUIT (TYP)

3/4" X 10' GROUND

ROD (TYP); LOCATION AS

INDICATED ON POWER

PLANS.

UNSPLICED

BONDING JUMPER

GROUNDING ELECTRODE & JUMPER CONDUCTORS SHALL BE #1/0

COPPER MINIMUM. MAIN BONDING JUMPER CONDUCTORS INDICATED

SHALL BE #1/0 COPPER MINIMUM.

NOTES:

1.

CONNECT UTILITY ROOM

ELECTROSTATIC FLOORING

COPPER STRIP (BY FLOORING

MANUFACTURER) TO STEEL

WITH A DRILLED/TAPPED HOLE

AND MACHINE SCREW.

OCCUPANCY SENSORS -

QUANTITY AS INDICATED FOR

ROOM/AREA

POWER PACK

LIGHTING

LOAD

PHASENEUTRAL

CON-

TROL

RELAY

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

E-501

D E

T A

IL

S

W E

S T

P O

IN

T

N

Y W

M

C C

A L L

J H

U R

S O

N

D K

O L O

W

IT

Z

D E

C E

M B

E R

W D

S D

AMENDMENT 7

R E

V

IT

A L

IZ

A T

IO

N

O F

C A

M P

B U

C K

N E

R

SCALE: NONEE-501

OVERHEAD ELECTRICAL SERVICE DETAIL (BUILDINGS VARY)D1

KEYED NOTES - BOILER BUILDINGS

1. PANELBOARD "H" FOR BOILER BUILDINGS.

2. 2.5-INCH RIGID GALVANIZED STEEL CONDUIT MAST WITH

WEATHERHEAD AND 3#3/0, #3/0N SERVICE CONDUCTORS .

REFER TO DETAIL D1/E-501 FOR ADDITIONAL

REQUIREMENTS PERTAINING TO CONDUIT MAST AND

WEATHERHEAD.

3. 2.5 INCH RIGID GALVANIZED STEEL CONDUIT LB FITTING

FOR SERVICE CONDUIT

4. 3#3/0, #3/0N, IN 2.5 INCH RIGID GALVANIZED STEEL

CONDUIT.

5. OVERHEAD SERVICE CONDUCTORS BY CITY LIGHT &

POWER (CLP) EXTENDING TO THE STEEL CONDUIT

MAST/WEATHERHEAD. REFER TO DETAIL D1/E-501 FOR

ADDITIONAL REQUIREMENTS PERTAINING TO SUPPORT

CABLE AND SERVICE MAST CONNECTION BRACKET.

6. CONNECTION OF SERVICE MAST CONDUCTORS BY

CONTRACTOR TO OVERHEAD LINES WILL BE MADE BY CLP.

VERIFY REQUIREMENTS WITH COR & CLP AND

COORDINATE WORK WITH CLP.

GENERAL NOTES

A. REFER TO DRAWING E-001 FOR ELECTRICAL LEGEND AND

GENERAL NOTES.

B. WORK RELATED TO ELECTRICAL SERVICES SHALL BE

COORDINATED WITH LOCAL UTILITY CLP AND SHALL

COMPLY WITH CLP REQUIREMENTS AND ELECTRICAL

SERVICE CONNECTIONS STANDARD MANUAL.

R

E V

IS

E

D P

E R

A M

E N

D M

E N

T

/2

/2

SCALE: NONEE-501

BOILER BUILDINGSB8

SCALE: NONEE-501

GROUND ROD DETAILB1

ELECTRICAL RISER DIAGRAM

SCALE: NONEE-501

AND LATRINE BUILDINGSB6

SLEEPING QUARTERS BARRACKS

KEYED NOTES - SLEEPING QUARTERS

BARRACKS AND LATRINE BUILDINGS

1. PANELBOARD "L" FOR LATRINE FACILITY; PANELBOARD "B"

FOR BARRACKS SLEEPING QUARTERS.

2. 2.5-INCH RIGID GALVANIZED STEEL CONDUIT MAST WITH

WEATHERHEAD AND 3#4/0, #4/0N SERVICE CONDUCTORS .

PROVIDE DRIP LOOP IN SERVICE CONDUCTORS BELOW

WEATHERHEAD. REFER TO DETAIL D1/E-501 FOR

ADDITIONAL REQUIREMENTS PERTAINING TO CONDUIT

MAST AND WEATHERHEAD.

3. 2.5 INCH RIGID GALVANIZED STEEL CONDUIT LB FITTING

FOR SERVICE CONDUIT

4. 3#4/0, #4/0N, IN 2.5 INCH RIGID GALVANIZED STEEL

CONDUIT.

5. OVERHEAD SERVICE CONDUCTORS BY CITY LIGHT &

POWER (CLP) EXTENDING TO THE STEEL CONDUIT

MAST/WEATHERHEAD. REFER TO DETAIL D1/E-501 FOR

ADDITIONAL REQUIREMENTS PERTAINING TO SUPPORT

CABLE AND SERVICE MAST CONNECTION BRACKET.

6. CONNECTION OF SERVICE MAST CONDUCTORS BY

CONTRACTOR TO OVERHEAD LINES WILL BE MADE BY CLP.

VERIFY REQUIREMENTS WITH COR & CLP AND

COORDINATE WORK WITH CLP.

7. 2.5-INCH RIGID GALVANIZED STEEL CONDUIT MAST WITH

WEATHERHEAD AND 3#3/0, #3/0N SERVICE CONDUCTORS.

PROVIDE DRIP LOOP IN SERVICE CONDUCTORS BELOW

WEATHERHEAD. REFER TO DETAIL D1/E-501 FOR

ADDITIONAL REQUIREMENTS PERTAINING TO CONDUIT

MAST AND WEATHERHEAD.

SCALE: NONEE-501

GROUND ROD TEST WELLB3

TYPICAL EXOTHERMIC

ELECTRICAL RISER DIAGRAM

SCALE: NONEE-501

SERVICE EQUIPMENT GROUNDING DETAILD6

SCALE: NONEE-501

OCCUPANCY SENSOR WIRING DIAGRAMD9

PANEL

"B"

1-3PH

0 TC

20A20A

100 AMP, 208Y/120V 3∅, 4W + G

100A

(BUS TO BRANCH CIRCUITS)

30/3 F-10

PUMP

HWRP-1

ELECTRONIC

POWER

METERING

REFER TO PANEL SCHEDULE FOR ADDITIONAL

REQUIREMENTS AND FEEDER/BRANCH CIRCUIT

WIRING REQUIREMENTS

3#3/0, #3/0N, IN 2.5 INCH

RIGID GALVANIZED STEEL CONDUIT

CONNECTION TO OVERHEAD UTILITY LINES

COMBINATION

STARTER WITH RK5

DUAL-ELEMENT

FUSES

25,000A SCCR

1200:5

PANEL

"B"

15A25A20A

225 AMP, 208Y/120V 3∅, 4W + G

225A

(BUS TO BRANCH CIRCUITS)

AC-1ACCU-1ELECTRONIC

POWER

METERING

REFER TO PANEL SCHEDULE FOR

ADDITIONAL REQUIREMENTS AND

FEEDER/BRANCH CIRCUIT WIRING

REQUIREMENTS

3#4/0, #4/0N, IN 2.5 INCH

RIGID GALVANIZED STEEL CONDUIT

CONNECTION TO OVERHEAD UTILITY LINES

30/3

F-25 NOTE 4D

N-3R 25,000A

SCCR

30/3

F-15 NOTE 4E

N-3R 25,000A

SCCR

NOTE 4A: 100/3; F-80

NOTE 4B: 200/3; F-175

NOTE 4C: N/A

N-3R

25,000A SCCR

1200:5

HVAC

AHU'S

200/3

F-175; NOTE 4F

N-3R 25,000A

SCCR

PANEL

"L"

(BUS TO BRANCH CIRCUITS)

225A

225 AMP, 208Y/120V 3∅, 4W + G

20A 175A

CONNECTION TO OVERHEAD UTILITY LINES

3#4/0, #4G IN 2.5 INCH

RIGID GALVANIZED STEEL CONDUIT

REFER TO PANEL SCHEDULE FOR

ADDITIONAL REQUIREMENTS AND

FEEDER/BRANCH CIRCUIT WIRING

REQUIREMENTS

ELECTRONIC

POWER

METERING

AHU-2

1200:5

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

E-601

O N

E -L

IN

E

D

IA

G R

A M

S

W E

S T

P O

IN

T

N

Y W

M

C C

A L L

J H

U R

S O

N

D K

O L O

W

IT

Z

D E

C E

M B

E R

W D

S D

AMENDMENT 7

R E

V

IT

A L

IZ

A T

IO

N

O F

C A

M P

B U

C K

N E

R

R

E V

IS

E

D P

E R

A M

E N

D M

E N

T

/2

/2

SCALE: NONEE-601

ELECTRICAL RISER DIAGRAM - BOILER BUILDINGSE4

SCALE: NONEE-601

ELECTRICAL RISER DIAGRAM - SLEEPING QUARTERS BARRACKSE7

SCALE: NONEE-601

ELECTRICAL RISER DIAGRAM - LATRINE BUILDINGSB7

GENERAL NOTES

A. REFER TO DRAWING E-001 FOR ELECTRICAL LEGEND AND

GENERAL NOTES.

B. PROVIDE ARC FLASH LABELS INSIDE PANELBOARDS,

DISCONNECT SWITCHES, AND MOTOR STARTERS IN

ACCORDANCE WITH NFPA 70 AND SPECIFICATIONS.

C. WHERE REQUIRED TO ACCOMMODATE CIRCUIT BREAKER

LUG RATINGS FOR CONDUCTOR SIZES INDICATED,

PROVIDE UL-LISTED COMPRESSION CRIMP COPPER

PIGTAIL ADAPTERS.

KEYED NOTES

1. METERING CURRENT TRANSFORMERS (CT'S) SHALL BE

PROVIDED AS A PART OF THE METERING EQUIPMENT PACKAGE.

2. CIRCUIT BREAKERS SERVING HVAC AHU'S SHALL BE RATED AS

FOLLOWS:

A. AHU-1 FOR BUILDINGS 1612, 1613, 1615, 1618, & 1624: 80A

BREAKER

B. AHU-3 FOR BUILDINGS 1616 & 1620: 175A BREAKER

C. BUILDINGS 1617 & 1619: SPARE 80A BREAKER ONLY (NO

WIRING)

3. WIRING AND RELATED WORK FOR PUMP HWRP-1 SHALL BE

PROVIDED FOR BOILER BUILDING 1599 ONLY.

4. THE DISCONNECT SWITCH RATINGS AND OVERCURRENT

PROTECTION RATINGS SHOWN BELOW FOR THE MECHANICAL

HVAC EQUIPMENT ARE BASED ON THE BASIS OF DESIGN

EQUIPMENT MANUFACTURER'S RECOMMENDATIONS AND NEC

ARTICLE 430. CONTRACTOR SHALL VERIFY THE

MANUFACTURER'S INSTALLATION REQUIREMENTS FOR THE

SPECIFIC UNITS PROVIDED, AND SHALL BE RESPONSIBLE FOR

PROVIDING THE REQUIRED OVERCURRENT DEVICE RATINGS,

SWITCH RATINGS, AND FEEDER RATINGS WITH ALL REQUIRED

CHANGES PROVIDED AT NO ADDITIONAL COST TO THE

GOVERNMENT. ALL WORK SHALL COMPLY WITH THE

MANUFACTURER'S INSTRUCTIONS AND NEC ARTICLE 430.

INCLUDE PROPOSED RATINGS OF ALL RELATED ELECTRICAL

SERVICES FOR MECHANICAL EQUIPMENT IN SUBMITTALS FOR

APPROVAL.

A. SLEEPING QUARTERS 1612, 1613, 1615, 1618, & 1624:

AHU-1; 100A 3P FUSED DISCONNECT SWITCH IN NEMA 3R

ENCLOSURE; 80A RK5 FUSES

B. SLEEPING QUARTERS 1616 & 1620: AHU-3; 200A 3P FUSED

DISCONNECT SWITCH IN NEMA 3R ENCLOSURE; 175A RK5

FUSES

C. SLEEPING QUARTERS 1617, & 1619: NO CENTRAL AIR

CONDITIONING AHU

D. SLEEPING QUARTERS 1612, 1613, 1615, 1616, 1617, 1618,

1619, 1620 & 1624: ACCU-1; 30A 3P FUSED DISCONNECT

SWITCH IN NEMA 3R ENCLOSURE; 25A RK5 FUSES

E. SLEEPING QUARTERS 1612, 1613, 1615, 1616, 1617, 1618,

1619, 1620 & 1624: AC-1; 30A 2P FUSED DISCONNECT

SWITCH IN NEMA 1 ENCLOSURE; 15A RK5 FUSES

F. LATRINES 1611, 1614 & 1621; AHU-2; 200A 3P FUSED

DISCONNECT SWITCH IN NEMA 3R ENCLOSURE; 175A RK5

FUSES

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

E-611

P A

N E

L B

O A

R D

S C

H E

D U

L E

S

S L E

E P

IN

G

Q U

A R

T E

R S

B A

R R

A C

K S

W E

S T

P O

IN

T

N

Y W

M

C C

A L L

J H

U R

S O

N

D K

O L O

W

IT

Z

D E

C E

M B

E R

W D

S D

AMENDMENT 7

R E

V

IT

A L

IZ

A T

IO

N

O F

C A

M P

B U

C K

N E

R

GENERAL NOTES

A. REFER TO DRAWING E-001 FOR ELECTRICAL LEGEND AND

GENERAL NOTES.

R

E V

IS

E

D P

E R

A M

E N

D M

E N

T

/2

/2

4. REFER TO SPECIFICATIONS FOR METERING AND SURGE PROTECTIVE DEVICE (SPD) EQUIPMENT.

3. NEC CIRCUIT GROUND CONDUCTOR SHALL BE PROVIDED IN EACH RACEWAY; 3/4 INCH CONDUIT MINIMUM SIZE; REFER TO GENERAL NOTES FOR ADDITIONAL REQUIREMENTS.

2. NO MORE THAN THREE SINGLE PHASE CIRCUITS PER CONDUIT; SHARED NEUTRALS SHALL NOT BE PERMITTED; REFER TO GENERAL NOTES FOR ADDITIONAL REQUIREMENTS.

1. BRANCH CIRCUIT WIRING SHALL BE 2#12, #12 GND IN 3/4 INCH CONDUIT, UNLESS NOTED OTHERWISE.

PANEL BOARD NOTES:

VERSION: 1.0

TIME: 11:08:39 AM A. 6 INCH FACTORY WIRE GUTTER AT BOTTOM

DATE: 1/19/2021 PANELBOARD ACCESSORIES:

3 - THREE-POLE BREAKER

TOTAL LOAD = 16380 VA 45 AMPS AVG 2 - TWO-POLE BREAKER

TOTAL LOAD PHASE C = 4860 VA = 41 AMPS L - LOCK-ON DEVICE

TOTAL LOAD PHASE B = 5690 VA = 47 AMPS G - GND FAULT INTERRUPTER

TOTAL LOAD PHASE A = 5830 VA = 49 AMPS S - SHUNT TRIP SF-SUBFEED MOUNTING

OPTIONS:

80 41 ---------C-- 42 30 0

SPARE 3 80 39 ------B----- 40 30 0 3 SPD 3#10, #10N, #10G, 1"C

80 37 --A--------- 38 30 0

10 20 35 ---------C-- 36 20 SPARE

SPARE 3 10 20 33 ------B----- 34 20 SPARE

10 20 31 --A--------- 32 20 SPARE

100 15 29 ---------C-- 30 20 390 LIGHTING

2#12, #12GND, 3/4"C AC-1 2 100 15 27 ------B----- 28 20 900 LIGHTING

1300 25 25 --A--------- 26 20 SPARE

2#10,#10GND, 3/4"C ACCU-1 2 1300 25 23 ---------C-- 24 20 SPARE

SPARE 20 21 ------B----- 22 20 SPARE

SPARE 20 19 --A--------- 20 20 SPARE

RECEPTACLES 180 20 17 ---------C-- 18 20 SPARE

RECEPTACLES 360 20 15 ------B----- 16 20 SPARE

FIRE ALARM PANEL FAMN L 200 20 13 --A--------- 14 20 SPARE

RECEPTACLES 360 20 11 ---------C-- 12 20 SPARE

RECEPTACLES 900 20 9 ------B----- 10 20 900 RECEPTACLES

RECEPTACLES 900 20 7 --A--------- 8 20 900 RECEPTACLES

RECEPTACLES 1260 20 5 ---------C-- 6 20 1260 RECEPTACLES

RECEPTACLES 1260 20 3 ------B----- 4 20 1260 RECEPTACLES

RECEPTACLES 1260 20 1 --A--------- 2 20 1260 RECEPTACLES

DESCRIPTION OPT LOAD TRIP NO. A B C NO. TRIP LOAD OPT DESCRIPTION

FED FROM: UTILITY SERVICE SERVICE ENTRANCE: YES

PHASE,WIRE: 3,4 GENERAL NOTES: 1,2, 3, & 4 AIC RATING: 25,000 AMPS

VOLTAGE: 208Y/120 DOOR LOCK: YES TOP OR BOTTOM MAIN: BOTTOM

BUILDINGS: 1617 & 1619 (SLEEPING QTRS) NEUTRAL: 100% MAIN BKR RATING: 225

PANELBOARD: B MOUNTING: SURFACE MAIN LUGS RATING: 225

CONNECT CIRCUITS INDICATED TO THE EXISTING SECURITY PANEL AND THE EXISTING LIGHTING CIRCUIT WITHIN THE ARMS ROOM.

5. ARMS ROOMS ARE BELOW MAIN LEVELS OF BLDGS (1612), 1616, & 1620. FOR OTHER BLDGS, PROVIDE ONLY SPARE CIRCUIT BREAKER AND NO WIRING.

4. REFER TO SPECIFICATIONS FOR METERING AND SURGE PROTECTIVE DEVICE (SPD) EQUIPMENT.

3. NEC CIRCUIT GROUND CONDUCTOR SHALL BE PROVIDED IN EACH RACEWAY; 3/4 INCH CONDUIT MINIMUM SIZE; REFER TO GENERAL NOTES FOR ADDITIONAL REQUIREMENTS.

2. NO MORE THAN THREE SINGLE PHASE CIRCUITS PER CONDUIT; SHARED NEUTRALS SHALL NOT BE PERMITTED; REFER TO GENERAL NOTES FOR ADDITIONAL REQUIREMENTS.

1. BRANCH CIRCUIT WIRING SHALL BE 2#12, #12 GND IN 3/4 INCH CONDUIT, UNLESS NOTED OTHERWISE.

PANEL BOARD NOTES:

VERSION: 1.0

TIME: 11:12:47 AM A. 6 INCH FACTORY WIRE GUTTER AT BOTTOM

DATE: 1/19/2021 PANELBOARD ACCESSORIES:

3 - THREE-POLE BREAKER

TOTAL LOAD = 63060 VA 175 AMPS AVG 2 - TWO-POLE BREAKER

TOTAL LOAD PHASE C = 20940 VA = 175 AMPS L - LOCK-ON DEVICE

TOTAL LOAD PHASE B = 20990 VA = 175 AMPS G - GND FAULT INTERRUPTER

TOTAL LOAD PHASE A = 21130 VA = 176 AMPS S - SHUNT TRIP SF-SUBFEED MOUNTING

OPTIONS:

15200 175 41 ---------C-- 42 30 0

3#2/0,#6GND, 2"C AHU-3 3, SF 15200 175 39 ------B----- 40 30 0 3 SPD 3#10, #10N,#10G, 1"C

15200 175 37 --A--------- 38 30 0

10 20 35 ---------C-- 36 20 SPARE

SPARE 3 10 20 33 ------B----- 34 20 SPARE

10 20 31 --A--------- 32 20 SPARE

100 15 29 ---------C-- 30 20 390 LIGHTING

2#12, #12GND, 3/4"C AC-1 2 100 15 27 ------B----- 28 20 900 LIGHTING

1300 25 25 --A--------- 26 20 SPARE

2#10,#10GND, 3/4"C ACCU-1 2 1300 25 23 ---------C-- 24 20 SPARE

SPARE 20 21 ------B----- 22 20 SPARE

SPARE 20 19 --A--------- 20 20 SPARE

RECEPTACLES 180 20 17 ---------C-- 18 20 880 L ARMS ROOM DEHUMIDIFIER RCPT (NOTE 5)

RECEPTACLES 360 20 15 ------B----- 16 20 100 L ARMS ROOM EXST SECURITY PANEL (NOTE 5)

FIRE ALARM PANEL FAMN L 200 20 13 --A--------- 14 20 100 L ARMS ROOM EXST LIGHTING CIRCUIT (NOTE 5)

RECEPTACLES 360 20 11 ---------C-- 12 20 SPARE

RECEPTACLES 900 20 9 ------B----- 10 20 900 RECEPTACLES

RECEPTACLES 900 20 7 --A--------- 8 20 900 RECEPTACLES

RECEPTACLES 1260 20 5 ---------C-- 6 20 1260 RECEPTACLES

RECEPTACLES 1260 20 3 ------B----- 4 20 1260 RECEPTACLES

RECEPTACLES 1260 20 1 --A--------- 2 20 1260 RECEPTACLES

DESCRIPTION OPT LOAD TRIP NO. A B C NO. TRIP LOAD OPT DESCRIPTION

FED FROM: UTILITY SERVICE SERVICE ENTRANCE: YES

PHASE/WIRE: 3 PHASE-4 WIRE GENERAL NOTES: 1,2, 3, & 4 AIC RATING: 25,000 AMPS

VOLTAGE: 208Y/120 DOOR LOCK: YES TOP OR BOTTOM MAIN: BOTTOM

BUILDINGS: 1616 & 1620 (SLEEPING QTRS) NEUTRAL: 100% MAIN BKR RATING: 225

PANELBOARD: B MOUNTING: SURFACE MAIN LUGS RATING: 225

CONNECT CIRCUITS INDICATED TO THE EXISTING SECURITY PANEL AND THE EXISTING LIGHTING CIRCUIT WITHIN THE ARMS ROOM.

5. ARMS ROOMS ARE BELOW MAIN LEVELS OF BLDGS 1612, (1616, & 1620). FOR OTHER BLDGS, PROVIDE ONLY SPARE CIRCUIT BREAKER AND NO WIRING.

4. REFER TO SPECIFICATIONS FOR METERING AND SURGE PROTECTIVE DEVICE (SPD) EQUIPMENT.

3. NEC CIRCUIT GROUND CONDUCTOR SHALL BE PROVIDED IN EACH RACEWAY; 3/4 INCH CONDUIT MINIMUM SIZE; REFER TO GENERAL NOTES FOR ADDITIONAL REQUIREMENTS.

2. NO MORE THAN THREE SINGLE PHASE CIRCUITS PER CONDUIT; SHARED NEUTRALS SHALL NOT BE PERMITTED; REFER TO GENERAL NOTES FOR ADDITIONAL REQUIREMENTS.

1. BRANCH CIRCUIT WIRING SHALL BE 2#12, #12 GND IN 3/4 INCH CONDUIT MINIMUM, UNLESS NOTED OTHERWISE.

PANEL BOARD NOTES:

VERSION: 1.0

TIME: 11:02:54 AM A. 6 INCH FACTORY WIRE GUTTER AT BOTTOM

DATE: 1/19/2021 PANELBOARD ACCESSORIES:

3 - THREE-POLE BREAKER

TOTAL LOAD = 37260 VA 103 AMPS AVG 2 - TWO-POLE BREAKER

TOTAL LOAD PHASE C = 12340 VA = 103 AMPS L - LOCK-ON DEVICE

TOTAL LOAD PHASE B = 12390 VA = 103 AMPS G - GND FAULT INTERRUPTER

TOTAL LOAD PHASE A = 12530 VA = 104 AMPS S - SHUNT TRIP SF-SUBFEED MOUNTING

OPTIONS:

6600 80 41 ---------C-- 42 30 0

3#4, #8GND, 1"C AHU-1 3 6600 80 39 ------B----- 40 30 0 3 SPD 3#10, #10N, #10G, 1"C

6600 80 37 --A--------- 38 30 0

10 20 35 ---------C-- 36 20 SPARE

SPARE 3 10 20 33 ------B----- 34 20 SPARE

10 20 31 --A--------- 32 20 SPARE

100 15 29 ---------C-- 30 20 390 LIGHTING

2#12, #12GND, 3/4"C AC-1 2 100 15 27 ------B----- 28 20 900 LIGHTING

1300 25 25 --A--------- 26 20 SPARE

2#10,#10GND, 3/4"C ACCU-1 2 1300 25 23 ---------C-- 24 20 SPARE

SPARE 20 21 ------B----- 22 20 SPARE

SPARE 20 19 --A--------- 20 20 SPARE

RECEPTACLES 180 20 17 ---------C-- 18 20 880 L ARMS ROOM DEHUMIDIFIER RCPT (NOTE 5)

RECEPTACLES 360 20 15 ------B----- 16 20 100 L ARMS ROOM EXST SECURITY PANEL (NOTE 5)

FIRE ALARM PANEL FAMN L 200 20 13 --A--------- 14 20 100 L ARMS ROOM EXST LIGHTING CIRCUIT (NOTE 5)

RECEPTACLES 360 20 11 ---------C-- 12 20 SPARE

RECEPTACLES 900 20 9 ------B----- 10 20 900 RECEPTACLES

RECEPTACLES 900 20 7 --A--------- 8 20 900 RECEPTACLES

RECEPTACLES 1260 20 5 ---------C-- 6 20 1260 RECEPTACLES

RECEPTACLES 1260 20 3 ------B----- 4 20 1260 RECEPTACLES

RECEPTACLES 1260 20 1 --A--------- 2 20 1260 RECEPTACLES

DESCRIPTION OPT LOAD TRIP NO. A B C NO. TRIP LOAD OPT DESCRIPTION

FED FROM: UTILITY SERVICE SERVICE ENTRANCE: YES

PHASE,WIRE: 3,4 GENERAL NOTES: 1,2, 3, & 4 AIC RATING: 25,000 AMPS

VOLTAGE: 208Y/120 DOOR LOCK: YES TOP OR BOTTOM MAIN: BOTTOM

BUILDINGS: 1612, 1613, 1615, 1618, & 1624 (SLEEPING QTRS) NEUTRAL: 100% MAIN BKR RATING: 225

PANELBOARD: B MOUNTING: SURFACE MAIN LUGS RATING: 225

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

E-612

P A

N E

L B

O A

R D

S C

H E

D U

L E

S

B O

IL

E

R A

N D

L A

T R

IN

E

B U

IL

D

IN

G

S

W E

S T

P O

IN

T

N

Y W

M

C C

A L L

J H

U R

S O

N

D K

O L O

W

IT

Z

D E

C E

M B

E R

W D

S D

AMENDMENT 7

R E

V

IT

A L

IZ

A T

IO

N

O F

C A

M P

B U

C K

N E

R

5. PANELBOARD BRANCH CIRCUIT QUANTITY CAPACITY IS 18 MINIMUM.

4. REFER TO SPECIFICATIONS FOR METERING AND SURGE PROTECTIVE DEVICE (SPD) EQUIPMENT.

3. NEC CIRCUIT GROUND CONDUCTOR SHALL BE PROVIDED IN EACH RACEWAY; 3/4 INCH CONDUIT MINIMUM SIZE; REFER TO GENERAL NOTES FOR ADDITIONAL REQUIREMENTS.

2. NO MORE THAN THREE SINGLE PHASE CIRCUITS PER CONDUIT; SHARED NEUTRALS SHALL NOT BE PERMITTED; REFER TO GENERAL NOTES FOR ADDITIONAL REQUIREMENTS.

1. BRANCH CIRCUIT WIRING SHALL BE 2#12, #12 GND IN 3/4 INCH CONDUIT, UNLESS NOTED OTHERWISE.

PANEL BOARD NOTES:

VERSION: 1.0

TIME: 11:22:46 AM A. 6 INCH FACTORY WIRE GUTTER AT BOTTOM

DATE: 1/19/2021 PANELBOARD ACCESSORIES:

3 - THREE-POLE BREAKER

TOTAL LOAD = 2990 VA 8 AMPS AVG 2 - TWO-POLE BREAKER

TOTAL LOAD PHASE C = 590 VA = 5 AMPS L - LOCK-ON DEVICE

TOTAL LOAD PHASE B = 1090 VA = 9 AMPS G - GND FAULT INTERRUPTER

TOTAL LOAD PHASE A = 1310 VA = 11 AMPS S - SHUNT TRIP SF-SUBFEED MOUNTING

OPTIONS:

N/A - SPACE PANELBOARD 41 ---------C-- 42 N/A - SPACE PANELBOARD

N/A - SPACE PANELBOARD 39 ------B----- 40 N/A - SPACE PANELBOARD

N/A - SPACE PANELBOARD 37 --A--------- 38 N/A - SPACE PANELBOARD

N/A - SPACE PANELBOARD 35 ---------C-- 36 N/A - SPACE PANELBOARD

N/A - SPACE PANELBOARD 33 ------B----- 34 N/A - SPACE PANELBOARD

N/A - SPACE PANELBOARD 31 --A--------- 32 N/A - SPACE PANELBOARD

SPACE 29 ---------C-- 30 SPACE

SPACE 27 ------B----- 28 SPACE

SPACE 25 --A--------- 26 SPACE

SPACE 23 ---------C-- 24 SPACE

SPACE 21 ------B----- 22 SPACE

SPACE 19 --A--------- 20 SPACE

SPARE 20 17 ---------C-- 18 19 SPARE

SPARE 20 15 ------B----- 16 20 SPARE

SPARE 20 13 --A--------- 14 20 SPARE

10 20 11 ---------C-- 12 20 SPARE

SPARE 3 10 20 9 ------B----- 10 20 500 EXST LIGHTING

10 20 7 --A--------- 8 20 720 EXST RECEPTACLES

580 20 5 ---------C-- 6 30 0

3#12, #12G, 1"C PUMP HWRP-1 3 580 20 3 ------B----- 4 30 0 3 SPD 3#10, #10N,#10G, 1"C

580 20 1 --A--------- 2 30 0

DESCRIPTION OPT LOAD TRIP NO. A B C NO. TRIP LOAD OPT DESCRIPTION

FED FROM: UTILITY SERVICE SERVICE ENTRANCE: YES

PHASE,WIRE: 3,4 GENERAL NOTES: 1,2, 3, 4, & 5 AIC RATING: 25,000 AMPS

VOLTAGE: 208Y/120 DOOR LOCK: YES TOP OR BOTTOM MAIN: BOTTOM

BUILDINGS: 1599, 1622, & 1623 (BOILER BLDG) NEUTRAL: 100% MAIN BKR RATING: 100

PANELBOARD: H MOUNTING: SURFACE MAIN LUGS RATING: 100

4. REFER TO SPECIFICATIONS FOR METERING AND SURGE PROTECTIVE DEVICE (SPD) EQUIPMENT.

3. NEC CIRCUIT GROUND CONDUCTOR SHALL BE PROVIDED IN EACH RACEWAY; 3/4 INCH CONDUIT MINIMUM SIZE; REFER TO GENERAL NOTES FOR ADDITIONAL REQUIREMENTS.

2. NO MORE THAN THREE SINGLE PHASE CIRCUITS PER CONDUIT; SHARED NEUTRALS SHALL NOT BE PERMITTED; REFER TO GENERAL NOTES FOR ADDITIONAL REQUIREMENTS.

1. BRANCH CIRCUIT WIRING SHALL BE 2#12, #12 GND IN 3/4 INCH CONDUIT, UNLESS NOTED OTHERWISE.

PANEL BOARD NOTES:

VERSION: 1.0

TIME: 11:25:25 AM A. 6 INCH FACTORY WIRE GUTTER AT BOTTOM

DATE: 1/19/2021 PANELBOARD ACCESSORIES:

3 - THREE-POLE BREAKER

TOTAL LOAD = 57770 VA 160 AMPS AVG 2 - TWO-POLE BREAKER

TOTAL LOAD PHASE C = 18980 VA = 158 AMPS L - LOCK-ON DEVICE

TOTAL LOAD PHASE B = 19190 VA = 160 AMPS G - GROUND FAULT INTERRUPTER

TOTAL LOAD PHASE A = 19600 VA = 163 AMPS S - SHUNT TRIP SF-SUBFEED MOUNTING

OPTIONS:

16000 175 41 ---------C-- 42 30 0

3#2/0,#6GND, 2"C AHU-2 3 16000 175 39 ------B----- 40 30 0 3 SPD 3#10, #10N,#10G, 1"C

16000 175 37 --A--------- 38 30 0

10 20 35 ---------C-- 36 20 SPARE

SPARE 3 10 20 33 ------B----- 34 20 SPARE

10 20 31 --A--------- 32 20 SPARE

SPARE 20 29 ---------C-- 30 20 450 LIGHTING

SPARE 20 27 ------B----- 28 20 660 LIGHTING

SPARE 20 25 --A--------- 26 20 690 LIGHTING

SPARE 20 23 ---------C-- 24 20 SPARE

SPARE 20 21 ------B----- 22 20 360 RECEPTACLES 2#10,#10G, 3/4"C

FIRE ALARM PANEL FAMN L 200 20 19 --A--------- 20 20 720 RECEPTACLES-EWC 2#10,#10G, 3/4"C

2#10,#10G, 3/4"C RECEPTACLES 360 20 17 ---------C-- 18 20 720 RECEPTACLES-EWC 2#10,#10G, 3/4"C

2#10,#10G, 3/4"C RECEPTACLES 360 20 15 ------B----- 16 20 360 RECEPTACLES 2#10,#10G, 3/4"C

2#10,#10G, 3/4"C RECEPTACLES 360 20 13 --A--------- 14 20 360 RECEPTACLES 2#10,#10G, 3/4"C

2#10,#10G, 3/4"C RECEPTACLES 360 20 11 ---------C-- 12 20 360 RECEPTACLES 2#10,#10G, 3/4"C

2#10,#10G, 3/4"C RECEPTACLES 360 20 9 ------B----- 10 20 360 RECEPTACLES 2#10,#10G, 3/4"C

2#10,#10G, 3/4"C RECEPTACLES 360 20 7 --A--------- 8 20 360 RECEPTACLES 2#10,#10G, 3/4"C

2#10,#10G, 3/4"C RECEPTACLES 360 20 5 ---------C-- 6 20 360 RECEPTACLES 2#10,#10G, 3/4"C

2#10,#10G, 3/4"C RECEPTACLES 360 20 3 ------B----- 4 20 360 RECEPTACLES 2#10,#10G, 3/4"C

2#10,#10G, 3/4"C RECEPTACLES 180 20 1 --A--------- 2 20 360 RECEPTACLES 2#10,#10G, 3/4"C

DESCRIPTION OPT LOAD TRIP NO. A B C NO. TRIP LOAD OPT DESCRIPTION

FED FROM: UTILITY SERVICE SERVICE ENTRANCE: YES

PHASE,WIRE: 3,4 GENERAL NOTES: 1,2, 3, & 4 AIC RATING: 25,000 AMPS

VOLTAGE: 208Y/120 DOOR LOCK: YES TOP OR BOTTOM MAIN: BOTTOM

BUILDINGS: 1611, 1614 & 1621 (LATRINE) NEUTRAL: 100% MAIN BKR RATING: 225

PANELBOARD: L MOUNTING: SURFACE MAIN LUGS RATING: 225

GENERAL NOTES

A. REFER TO DRAWING E-001 FOR ELECTRICAL LEGEND AND

GENERAL NOTES.

R

E V

IS

E

D P

E R

A M

E N

D M

E N

T

/2

/2

Sheets
E-001 - ELECTRICAL LEGEND AND GENERAL NOTES
E-501 - DETAILS
E-601 - ONE-LINE DIAGRAMS
E-611 - PANELBOARD SCHEDULES - SLEEPING QUARTERS BARRACKS
E-612 - PANELBOARD SCHEDULES - BOILER AND LATRINE BUILDINGS
ED101 - FIRST FLOOR DEMOLITION PLAN - POWER AND LIGHTING
EL101 - FIRST FLOOR PLAN - LIGHTING
EL601 - LUMINAIRE SCHEDULE
EP101 - FIRST FLOOR PLAN - POWER
EP102 - ARMS ROOMS & BOILER BLDG FLOOR PLAN - POWER
Sheets
E-001 - ELECTRICAL LEGEND AND GENERAL NOTES
E-501 - DETAILS
E-601 - ONE-LINE DIAGRAMS
E-611 - PANELBOARD SCHEDULES - SLEEPING QUARTERS BARRACKS
E-612 - PANELBOARD SCHEDULES - BOILER AND LATRINE BUILDINGS
ED101 - FIRST FLOOR DEMOLITION PLAN - POWER AND LIGHTING
EL101 - FIRST FLOOR PLAN - LIGHTING
EL601 - LUMINAIRE SCHEDULE
EP101 - FIRST FLOOR PLAN - POWER
EP102 - ARMS ROOMS & BOILER BLDG FLOOR PLAN - POWER
Sheets
E-001 - ELECTRICAL LEGEND AND GENERAL NOTES
E-501 - DETAILS
E-601 - ONE-LINE DIAGRAMS
E-611 - PANELBOARD SCHEDULES - SLEEPING QUARTERS BARRACKS
E-612 - PANELBOARD SCHEDULES - BOILER AND LATRINE BUILDINGS
ED101 - FIRST FLOOR DEMOLITION PLAN - POWER AND LIGHTING
EL101 - FIRST FLOOR PLAN - LIGHTING
EL601 - LUMINAIRE SCHEDULE
EP101 - FIRST FLOOR PLAN - POWER
EP102 - ARMS ROOMS & BOILER BLDG FLOOR PLAN - POWER
Sheets
E-001 - ELECTRICAL LEGEND AND GENERAL NOTES
E-501 - DETAILS
E-601 - ONE-LINE DIAGRAMS
E-611 - PANELBOARD SCHEDULES - SLEEPING QUARTERS BARRACKS
E-612 - PANELBOARD SCHEDULES - BOILER AND LATRINE BUILDINGS
ED101 - FIRST FLOOR DEMOLITION PLAN - POWER AND LIGHTING
EL101 - FIRST FLOOR PLAN - LIGHTING
EL601 - LUMINAIRE SCHEDULE
EP101 - FIRST FLOOR PLAN - POWER
EP102 - ARMS ROOMS & BOILER BLDG FLOOR PLAN - POWER
Sheets
E-001 - ELECTRICAL LEGEND AND GENERAL NOTES
E-501 - DETAILS
E-601 - ONE-LINE DIAGRAMS
E-611 - PANELBOARD SCHEDULES - SLEEPING QUARTERS BARRACKS
E-612 - PANELBOARD SCHEDULES - BOILER AND LATRINE BUILDINGS
ED101 - FIRST FLOOR DEMOLITION PLAN - POWER AND LIGHTING
EL101 - FIRST FLOOR PLAN - LIGHTING
EL601 - LUMINAIRE SCHEDULE
EP101 - FIRST FLOOR PLAN - POWER
EP102 - ARMS ROOMS & BOILER BLDG FLOOR PLAN - POWER
Sheets
E-001 - ELECTRICAL LEGEND AND GENERAL NOTES
E-501 - DETAILS
E-601 - ONE-LINE DIAGRAMS
E-611 - PANELBOARD SCHEDULES - SLEEPING QUARTERS BARRACKS
E-612 - PANELBOARD SCHEDULES - BOILER AND LATRINE BUILDINGS
ED101 - FIRST FLOOR DEMOLITION PLAN - POWER AND LIGHTING
EL101 - FIRST FLOOR PLAN - LIGHTING
EL601 - LUMINAIRE SCHEDULE
EP101 - FIRST FLOOR PLAN - POWER
EP102 - ARMS ROOMS & BOILER BLDG FLOOR PLAN - POWER
Sheets
E-001 - ELECTRICAL LEGEND AND GENERAL NOTES
E-501 - DETAILS
E-601 - ONE-LINE DIAGRAMS
E-611 - PANELBOARD SCHEDULES - SLEEPING QUARTERS BARRACKS
E-612 - PANELBOARD SCHEDULES - BOILER AND LATRINE BUILDINGS
ED101 - FIRST FLOOR DEMOLITION PLAN - POWER AND LIGHTING
EL101 - FIRST FLOOR PLAN - LIGHTING
EL601 - LUMINAIRE SCHEDULE
EP101 - FIRST FLOOR PLAN - POWER
EP102 - ARMS ROOMS & BOILER BLDG FLOOR PLAN - POWER
Sheets
E-001 - ELECTRICAL LEGEND AND GENERAL NOTES
E-501 - DETAILS
E-601 - ONE-LINE DIAGRAMS
E-611 - PANELBOARD SCHEDULES - SLEEPING QUARTERS BARRACKS
E-612 - PANELBOARD SCHEDULES - BOILER AND LATRINE BUILDINGS
ED101 - FIRST FLOOR DEMOLITION PLAN - POWER AND LIGHTING
EL101 - FIRST FLOOR PLAN - LIGHTING
EL601 - LUMINAIRE SCHEDULE
EP101 - FIRST FLOOR PLAN - POWER
EP102 - ARMS ROOMS & BOILER BLDG FLOOR PLAN - POWER
Sheets
E-001 - ELECTRICAL LEGEND AND GENERAL NOTES
E-501 - DETAILS
E-601 - ONE-LINE DIAGRAMS
E-611 - PANELBOARD SCHEDULES - SLEEPING QUARTERS BARRACKS
E-612 - PANELBOARD SCHEDULES - BOILER AND LATRINE BUILDINGS
ED101 - FIRST FLOOR DEMOLITION PLAN - POWER AND LIGHTING
EL101 - FIRST FLOOR PLAN - LIGHTING
EL601 - LUMINAIRE SCHEDULE
EP101 - FIRST FLOOR PLAN - POWER
EP102 - ARMS ROOMS & BOILER BLDG FLOOR PLAN - POWER
Sheets
E-001 - ELECTRICAL LEGEND AND GENERAL NOTES
E-501 - DETAILS
E-601 - ONE-LINE DIAGRAMS
E-611 - PANELBOARD SCHEDULES - SLEEPING QUARTERS BARRACKS
E-612 - PANELBOARD SCHEDULES - BOILER AND LATRINE BUILDINGS
ED101 - FIRST FLOOR DEMOLITION PLAN - POWER AND LIGHTING
EL101 - FIRST FLOOR PLAN - LIGHTING
EL601 - LUMINAIRE SCHEDULE
EP101 - FIRST FLOOR PLAN - POWER
EP102 - ARMS ROOMS & BOILER BLDG FLOOR PLAN - POWER

File details come from the government source that posted it. Updated .