Watervliet_Arsenal_1A1_Approvals.pdf

PDF 4 MB Posted

Attached to
General Purpose Storage Building, Watervliet, NY Federal contract opportunity
Solicitation number
W912DS-18-B-0014
Issued by
Department of the Army Corps of Engineers Engineering District New York

About this file

Watervliet Arsenal 1A1 Approvals

View the file

Other files for this federal contract opportunity

Other files attached to General Purpose Storage Building, Watervliet, NY, newest first.
File Type Posted
Bid_Abstract_-__W912DS18B0014.pdf PDF
EP-601_(revision_2).pdf PDF
W912DS18B0014-0007.pdf PDF
A-501.pdf PDF
A-601.pdf PDF
photo 9.jpg JPG image
03_30_00._00_10.pdf PDF
A-101.pdf PDF
photo 5.jpg JPG image
photo 14.jpg JPG image
photo 13.jpg JPG image
M-101.pdf PDF
W912DS18B0014-0007.pdf PDF
photo 10.jpg JPG image
A-502.pdf PDF
A-201.pdf PDF
C-505__24JUL18.pdf PDF
10_44_16.pdf PDF
photo 11.jpg JPG image
S-001.pdf PDF
G-003.pdf PDF
EP-602_-_PANEL_SCHEDULES_(24jul18).pdf PDF
photo 22.jpg JPG image
photo 19.jpg JPG image
A-401.pdf PDF
photo 3.jpg JPG image
SUBMITTAL_REGISTER.PDF PDF
photo 12.jpg JPG image
EP-101_24jul18.pdf PDF
photo 20.jpg JPG image
W912DS18B0014-0006.pdf PDF
12_21_00.pdf PDF
41_22_13.14.pdf PDF
03_33_00.pdf PDF
22_00_00.pdf PDF
08_71_00.pdf PDF
W912DS18B0014-0005_-_Revised_7.27.pdf PDF
08_33_23.pdf PDF
00_73_00.00_18.pdf PDF
09_30_10.pdf PDF
C-101_AMENDMENT.pdf PDF
S-404_Watervliet_Warehouse_Loading_Dock_Amendment.pdf PDF
W912DS18B0014-0005.pdf PDF
W912DS18B0014_-_0003.pdf PDF
WVA_Storage_Warehouse_sign_in_sheet.pdf PDF
specification_41_22_13.14.pdf PDF
W912DS18B0014_-_0001.pdf PDF
W912DS18B0014.pdf PDF
WATERVLIETWHSE_100PCNT_SPECS_RTA.pdf PDF
75906_WVA_Warehs_Dwg_RTA.pdf PDF
Show all 50

General Purpose Storage Building, Watervliet, NY has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Watervliet Arsenal Substation 1A1 Approval Drawings 2/23/2018

OOwner:

Watervliet Arsenal

Contractor:

Visionary

Distributor:

Graybar Albany

Adam Hasenfus Field Services Project Manager North American Operating Division 781-724-2664 adam.hasenfus@schneider-electric.com

The following information is pertinent with the return of this submittal. Please initial the applicable items that you have reviewed and have determined to be correct.

Date:

Job Name:

Factory Order #:

Contractor Name:

Customer Comments/Rejected Items:

Contractors Signature or Stamp:

> Lug sizes

> Top or bottom entry for all equipment

> Shipping splits

> Nameplate information

> Orientation of breakers

> Wire sizes

> Amperages of all bus and breakers

> Surface or flush for panels

> Size of all equipment

> AIC ratings

> Copper or aluminum bus

> Release approved sections for manufacture Re-submit rejected section

> No release Re-submit all

> Release all for manufacture.

Make necessary changes, show Changes on construction Drawings

> Release all manufacture No re-submittal required

03MAR18

Substation 1A1 replacement

Visionary Services

X

HLS

HLS

HLS

HLS

HLS

HLS

HLS

HLS

HLS

HLS

HLS

4/0 conductors shall be utilized, to include the grounding conductor(s), not 3/0 to supply power from the copper buss to the individual buckets/breakers. Ensure all lugs are sized appropriately to accommodate this change and use the depicted quantity of conductors still.

STEPHENS.HARRY.LEROY.JR.1259105257

Digitally signed by STEPHENS.HARRY.LEROY.JR.1259105257 DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USA, cn=STEPHENS.HARRY.LEROY.JR.1259105257 Date: 2018.03.03 10:49:59 -05'00'

Approval Drawings

This Approval Drawing Package is submitted as our interpretation of the contract drawings and/or the specifications for this job.

It is the obligation of the electrical contractor and reviewing engineer to determine that the item quantities and accuracy of this submittal is correct as required for the job. Any inaccuracies or deviations must be addressed with Schneider Electric before release to manufacturing. Any releases of material to manufacturing by the above parties constitute an acceptance of the accuracy of the submittal.

Any changes after release will be viewed as a change order, subject to pricing changes.

Please take the time to review this package for accuracy to prevent any after-shipment problems. This will allow the job to be shipped correctly and prevent any delay in energization.

Specification Exceptions/Clarifications ETQ Doc No: 10052 Rev: 3/2/09

ENGR: MN DATE: February 23, 2018 PG 1 OF 1 STATUS: Approval REV: - DOC # : T40153618-002-EX

• This form must be reviewed / approved by the customer and returned with the approval package.

• All Spec. Clarification items must be addressed and resolved to the satisfaction of the Customer prior to job being released to Manufacturing

• Some items may require a change order to implement. Note: Change orders could negatively impact advanced record drawing dates and ship dates

• Items below in Boldface Type Require information that must be received when the approval package is returned. Failure to do so will result in a delay of shipment

Customer Approval (Required):

Approved: _______________

Approved as Noted: __________________

• Customer terminal block numbers (Example: TTC numbers) may be changed during the electrical design phase

1. Square D standard bus arrangement will be A-B-C, top to bottom, left to right, and front to back as viewed from the front of the switch.

2. All documents in the approval package without requested modifications must be “APPROVED” or “APPROVED AS NOTED” and signed by the proper reviewing authority.

3.

Clarification Please confirm the amount and sizes of lugs for the incoming cables and confirm incoming/outgoing cables location on the floor plan.

Customer response:

4. Clarification Please confirm that power supply to be thru sec#1.

Customer response:

5. Clarification Please send a marked-up version of drawings for any comments or changes needed.

Customer response:

Visionary or supplier representative needs to contact me directly to verify exactly what is needed. All of this information was originally detailed from site visits.

Please confirm what you are asking. Any power supplied to this station will be in the form of 13.2 kV, then stepped down to 480Y/277V. If control power is needed, it is to be built into this design.

Completed.

Acknowledged.

Please make changes, and if any marks need to be added, I shall after this is complete.

STEPHENS.HARRY.

LEROY.JR.1259105

Digitally signed by

STEPHENS.HARRY.LEROY.JR.1259105257

DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USA, cn=STEPHENS.HARRY.LEROY.JR.1259105257 Date: 2018.03.03 10:52:09 -05'00'

STEPHENS.HARRY.LEROY.JR.1

259105257

Digitally signed by STEPHENS.HARRY.LEROY.JR.1259105257 DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USA, cn=STEPHENS.HARRY.LEROY.JR.1259105257 Date: 2018.03.03 11:13:03 -05'00'

PO

WE

R C

AS

T I I

S ch ne id er E le ct ric

ENGRAVED NAMEPLATES DATA SHEET

ENGR: B. SARVER DATE: February 08, 2018 PG 1 OF 1

STATUS: APPROVAL REV: - DOC # : N40893614-002-01

AE: BFS PRODUCT CODE (MC, ME, MCC) __MC

TYPE FIELD/

(TY) LETTERS

SIZE

(S)

NP

HEIGHT

NP

WIDTH

CHAR

HEIGHT

MAX.

LINES

MAX.

CHAR/LINE

WB WHITE/BLACK A 0.75" 4.6" 3/16" 2 26

BW BLACK/WHITE B 0.75" 2.0" 1/8" 3 11

RW RED/WHITE C 9001

DEVICE

1/8" 3 14

D 2.0" 6.0" 5/16" 4 19 E 1.0" 2.5" 1/8" 4 16 F 0.75" 2.0" 1/8" 3 11

CODES A-E ARE FOR DOOR MOUNTED DEVICES.

CODE F APPLIES TO INTERNALLY MOUNTED DEVICES.

SPECIAL NAMEPLATES ARE CODED SA, SB, SC, ... WITH ASSOCIATED DETAILS NOTED.

Nameplate mounting holes .0781” diameter, A nameplates have holes 3.5” apart centered, D nameplates have holes 5.5” apart centered.

NP # TYPE SIZE QTY TEXT CONTENT

1 9001 C 12 BREAKER

OPEN

2 9001 C 12 BREAKER

CLOSED

3 WB A 1 HVL 1

4 WB A 1 HVL 2

5 WB A 1 MAIN 1

6 WB A 1 FEEDER BKR 1

7 WB A 1 FEEDER BKR 2

8 WB A 1 FEEDER BKR 3

9 WB A 1 FEEDER BKR 4

10 WB A 1 FEEDER BKR 5

11 WB A 1 FEEDER BKR 6

12 WB A 1 FEEDER BKR 7

13 WB A 1 FEEDER BKR 8

14 WB A 1 FEEDER BKR 9

File details come from the government source that posted it.