Watervliet Arsenal Substation 1A1 Approval Drawings 2/23/2018
OOwner:
Watervliet Arsenal
Contractor:
Visionary
Distributor:
Graybar Albany
Adam Hasenfus Field Services Project Manager North American Operating Division 781-724-2664 adam.hasenfus@schneider-electric.com
The following information is pertinent with the return of this submittal. Please initial the applicable items that you have reviewed and have determined to be correct.
Date:
Job Name:
Factory Order #:
Contractor Name:
Customer Comments/Rejected Items:
Contractors Signature or Stamp:
> Lug sizes
> Top or bottom entry for all equipment
> Shipping splits
> Nameplate information
> Orientation of breakers
> Wire sizes
> Amperages of all bus and breakers
> Surface or flush for panels
> Size of all equipment
> AIC ratings
> Copper or aluminum bus
> Release approved sections for manufacture Re-submit rejected section
> No release Re-submit all
> Release all for manufacture.
Make necessary changes, show Changes on construction Drawings
> Release all manufacture No re-submittal required
03MAR18
Substation 1A1 replacement
Visionary Services
X
HLS
HLS
HLS
HLS
HLS
HLS
HLS
HLS
HLS
HLS
HLS
4/0 conductors shall be utilized, to include the grounding conductor(s), not 3/0 to supply power from the copper buss to the individual buckets/breakers. Ensure all lugs are sized appropriately to accommodate this change and use the depicted quantity of conductors still.
STEPHENS.HARRY.LEROY.JR.1259105257
Digitally signed by STEPHENS.HARRY.LEROY.JR.1259105257 DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USA, cn=STEPHENS.HARRY.LEROY.JR.1259105257 Date: 2018.03.03 10:49:59 -05'00'
Approval Drawings
This Approval Drawing Package is submitted as our interpretation of the contract drawings and/or the specifications for this job.
It is the obligation of the electrical contractor and reviewing engineer to determine that the item quantities and accuracy of this submittal is correct as required for the job. Any inaccuracies or deviations must be addressed with Schneider Electric before release to manufacturing. Any releases of material to manufacturing by the above parties constitute an acceptance of the accuracy of the submittal.
Any changes after release will be viewed as a change order, subject to pricing changes.
Please take the time to review this package for accuracy to prevent any after-shipment problems. This will allow the job to be shipped correctly and prevent any delay in energization.
Specification Exceptions/Clarifications ETQ Doc No: 10052 Rev: 3/2/09
ENGR: MN DATE: February 23, 2018 PG 1 OF 1 STATUS: Approval REV: - DOC # : T40153618-002-EX
• This form must be reviewed / approved by the customer and returned with the approval package.
• All Spec. Clarification items must be addressed and resolved to the satisfaction of the Customer prior to job being released to Manufacturing
• Some items may require a change order to implement. Note: Change orders could negatively impact advanced record drawing dates and ship dates
• Items below in Boldface Type Require information that must be received when the approval package is returned. Failure to do so will result in a delay of shipment
Customer Approval (Required):
Approved: _______________
Approved as Noted: __________________
• Customer terminal block numbers (Example: TTC numbers) may be changed during the electrical design phase
1. Square D standard bus arrangement will be A-B-C, top to bottom, left to right, and front to back as viewed from the front of the switch.
2. All documents in the approval package without requested modifications must be “APPROVED” or “APPROVED AS NOTED” and signed by the proper reviewing authority.
3.
Clarification Please confirm the amount and sizes of lugs for the incoming cables and confirm incoming/outgoing cables location on the floor plan.
Customer response:
4. Clarification Please confirm that power supply to be thru sec#1.
Customer response:
5. Clarification Please send a marked-up version of drawings for any comments or changes needed.
Customer response:
Visionary or supplier representative needs to contact me directly to verify exactly what is needed. All of this information was originally detailed from site visits.
Please confirm what you are asking. Any power supplied to this station will be in the form of 13.2 kV, then stepped down to 480Y/277V. If control power is needed, it is to be built into this design.
Completed.
Acknowledged.
Please make changes, and if any marks need to be added, I shall after this is complete.
STEPHENS.HARRY.
LEROY.JR.1259105
Digitally signed by
STEPHENS.HARRY.LEROY.JR.1259105257
DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USA, cn=STEPHENS.HARRY.LEROY.JR.1259105257 Date: 2018.03.03 10:52:09 -05'00'
STEPHENS.HARRY.LEROY.JR.1
259105257
Digitally signed by STEPHENS.HARRY.LEROY.JR.1259105257 DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USA, cn=STEPHENS.HARRY.LEROY.JR.1259105257 Date: 2018.03.03 11:13:03 -05'00'
PO
WE
R C
AS
T I I
S ch ne id er E le ct ric
ENGRAVED NAMEPLATES DATA SHEET
ENGR: B. SARVER DATE: February 08, 2018 PG 1 OF 1
STATUS: APPROVAL REV: - DOC # : N40893614-002-01
AE: BFS PRODUCT CODE (MC, ME, MCC) __MC
TYPE FIELD/
(TY) LETTERS
SIZE
(S)
NP
HEIGHT
NP
WIDTH
CHAR
HEIGHT
MAX.
LINES
MAX.
CHAR/LINE
WB WHITE/BLACK A 0.75" 4.6" 3/16" 2 26
BW BLACK/WHITE B 0.75" 2.0" 1/8" 3 11
RW RED/WHITE C 9001
DEVICE
1/8" 3 14
D 2.0" 6.0" 5/16" 4 19 E 1.0" 2.5" 1/8" 4 16 F 0.75" 2.0" 1/8" 3 11
CODES A-E ARE FOR DOOR MOUNTED DEVICES.
CODE F APPLIES TO INTERNALLY MOUNTED DEVICES.
SPECIAL NAMEPLATES ARE CODED SA, SB, SC, ... WITH ASSOCIATED DETAILS NOTED.
Nameplate mounting holes .0781” diameter, A nameplates have holes 3.5” apart centered, D nameplates have holes 5.5” apart centered.
NP # TYPE SIZE QTY TEXT CONTENT
1 9001 C 12 BREAKER
OPEN
2 9001 C 12 BREAKER
CLOSED
3 WB A 1 HVL 1
4 WB A 1 HVL 2
5 WB A 1 MAIN 1
6 WB A 1 FEEDER BKR 1
7 WB A 1 FEEDER BKR 2
8 WB A 1 FEEDER BKR 3
9 WB A 1 FEEDER BKR 4
10 WB A 1 FEEDER BKR 5
11 WB A 1 FEEDER BKR 6
12 WB A 1 FEEDER BKR 7
13 WB A 1 FEEDER BKR 8
14 WB A 1 FEEDER BKR 9