About this file

W912DS-17-R-0003-APPENDIX CC

View the file

Other files

File Type Posted
W912DS-17-R-0003-AMENDMENT_0001.pdf PDF
Appendix_R_-_Geotechnical_Investigations.pdf PDF
Appendix_E_-_Spill_Prevention-Response_Plan.pdf PDF
Appendix_S_-_Pacer_Goose_Shipping_Instructions.pdf PDF
Appendix_C_-_Natural_Resources_Management_Plan.pdf PDF
Appendix_G_-_Solid_Waste_Mgmt_Plan.pdf PDF
Appendix_Z_-_Fuel_Pricing_and_DLA_Instructions.pdf PDF
Appendix_V_-_Exterior_Building_Photos.pdf PDF
Appendix_I_-_Slug_Mgmt_Plan.pdf PDF
Appendix_J_-_Installation_HAZMAT_Management_Plan.pdf PDF
Package_1_-_RFP_Bldg_98_Renovation.pdf PDF
Appendix_U_-_Thule_Facilities_Excellence_Plan_2012.pdf PDF
Appendix_M_-_PCB_Repl_Plan.pdf PDF
Appendix_W_-_Existing_Site_Utilities.pdf PDF
Appendix_F_-_PPM_Plan.pdf PDF
Appendix_B_-_NFS_Material_Borrow_Site.pdf PDF
Appendixs_AA_-_Preliminary_Code_Analysis.pdf PDF
Appendix_A_-_Active_Landfills.pdf PDF
Appendix_T_-_DBA_Waiver.pdf PDF
Appendix_X_-_Bldg_98_As-builds.pdf PDF
Appendix_P_-_Unaccompanied_Housing_Design_Guide.pdf PDF
Appendix_O_-_Lead_Paint_Mgmt_Plan.pdf PDF
Appendixs_EE_-_CID_Package.pdf PDF
Appendix_Q_-_FY17_Sealift_Rates.pdf PDF
Appendix_Y_-_Asbestos_Survey.pdf PDF
Appendix_D_-_HWM_Plan.pdf PDF
Appendix_L_-_Affirmative_Proc_Plan.pdf PDF
Appendix_K_-_FGS-GL_(Environmental_Protection).pdf PDF
Appendix_N_-_Asbestos_Mgmt_Plan.pdf PDF
Appendixs_BB_-_Bldg_98_Concept_Drawings_and_Elevations.pdf PDF
Appendixs_FF_-_Thermistor_Profile.pdf PDF
Appendix_H_-_Storm_Water_Mgmt_Plan.pdf PDF
W912DS-17-R-0003-SOLLICITATION.pdf PDF
Show all 33

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REQUEST FOR PROPOSAL: DESIGN BUILD 05 OCTOBER 2016

RENOVATE DORMITORY BUILDING 98, THULE AIR BASE, GREENLAND

Appendices

APPENDIX CC

PRODUCT DATA SHEETS

THIS PAGE INTENTIONALLY LEFT BLANK

TEMPORARY HEAT EXCHANGER CONTAINER

#97 Temporary Containerbased Heat Exchanger Page 1 of 4 /THJ. D. 2014.06.10

#97 Temporary Prefab heat exchanger Container

Generally, Thule is steadily is converting from steam to a more energy effective hot water production & distribution system, so this should be implemented for Building #97 as well.

Locally at facility #97 this is cheapest/best done by installing a temporary 20’ container based steam to hot water exchanger unit heat exchanger. Cheapest a standard available insulated container is used. (e.g. an earlier intended refrigerator container. Typically this would be cheaper than including on onsite building of the steam to hot water exchanger in the facility. In long term when hot water becomes available in the heat distribution it is relatively simple to bypass the container, use it elsewhere on base or ship it out of Thule Airbase

Example of container based exchanger unit. Note The out/return manifold shown here has 4 outlets.

#97 Temporary Containerbased Heat Exchanger Page 2 of 4 /THJ. D. 2014.06.10

Suitable location could be:

#97 Temporary Containerbased Heat Exchanger Page 3 of 4 /THJ. D. 2014.06.10

(Typically to double nominal heat exchange capacity is approximately. 30% price increase).So increasing capacity from 0,3MW (appr. to 0,6MW) and doubling outlets on manifold would enable USAF to use the same temporary container in its proposed position for the future programmed renovation of #99 (WWCX10-3007).

Site Plan with temporary container location and heat supply for facility #97 (Red solid) and potential future renovation #99 (Red Dashed).

#97 Temporary Containerbased Heat Exchanger Page 4 of 4 /THJ. D. 2014.06.10

Example of temporary containbaset Nominal capacity of 550 kW heat exchanger with redundant pump setup

Job Name Thule Greenland Dormitory

39MN Sz03Mark for

Date December 13, 2015

Unit Parameters

Aero Indoor Air Handler

Unit Size: Size 03

Insulation: R-13 Double Wall Sealed Panel

Exterior Finish: Galvanized Exterior Panels

Interior Finish: Galvanized Interior Panels

Level I Thermal Break

6 inch tall Base Rail

Filter Mixing Box

Damper: Rear Premium Parallel

2In. Angle Filter

Qty (2) 16in. x 25in.

Door Left Side

Angle Filter

4In. Angle Filter

Qty (2) 16in. x 25in.

Door Left Side

Hot Water Coil

Hot Water 3.47 sq.ft 4 Row 14 FPI Full Circuit

Coil Connection Right Side

1/2 in. Tube Diameter

AL fins Galv. Casing

Steel Header

No Coating

Draw-Thru Supply Fan

Rear Inlet

Fan Sled

Forward Curve B FCA9_4A

1394 fanRPM Class I

UpBlast Rear Discharge

Right Side Fan Motor Location

6.39

SUBJECT TO CHANGE WITHOUT NOTICE

Job Name Thule Greenland Dormitory

39MN Sz03Mark for

Date December 13, 2015

Spring Fan Isolation

Motor

1 HP Premium Efficiency ODP 208-230/460 3Ph 60Hz 1800 RPM

Manufacturer - Generic

Frame Size - 143T

Motor Shaft Diameter (in.) - 0.875

Voltage Selected - 460/3/60

Full Load Amps - 1.4

MCA - 1.8

MOCP - 3

Efficiency - 85.5%

Belt Drive

1.2 Service Factor

Fixed Pitch Drive

1 or more belts

Variable Frequency Drive

460 Volts 3 Phase 60Hz

Field Mounted No Bypass

Door Right Side

Configuration Notes

Discharge duct(s) must be gasketed and screwed directly to the discharge panel of the unit.

Careful consideration must be made for mixing outside and return air streams in VAV applications due to reduced velocity in heating mode.

Consider the use of a blow-thru plenum fan as a mixing device.

Weights and Dimensions

(LxWxH in ft in) 8' 0" x 2' 9" x 3' 1" **

Operating 1243 LB ** Weights and Dimensions are approximate. Weights include base unit weight, coils (wet & dry), fans and fan motors, and other components, but does not include filters, drives and skids. Approximate dimensions are provided primarily for shipping purposes. Shipping skids are not included.

All filter media efficiency ratings are for the filter media only.

6.39

SUBJECT TO CHANGE WITHOUT NOTICE

v6.39a11/16/15 www.carrier.com

Heating Application's Balance Criteria: Fluid Flow Coil Model Carrier 28MH Row / FPI / Circ 4 / 14 / FL Fin Type Sine Wave Face Area Type Large Coil Face Area 3.47 sqft Face Velocity 288.0 fpm Fin-Casing Material Al-Galv.

Tube Diameter 0.5 in Tube spacing: Stf x Str 1.25 x 0.781 in Tube Wall Thickness 0.016 in Actual Airflow 1000 CFM Site Altitude 0 ft Heating Capacity 172.33 MBH Fluid Flow Rate 4.9 gpm Fluid Pressure Drop 0.1 ft wg Fluid Velocity 0.4 ft/s Entering Fluid Temperature 176.00 F Leaving Fluid Temperature 104.00 F Fluid Temperature Drop 72.0 F Entering Air Temperature -40.00 F Leaving Air Temperature 87.05 F Air Friction 0.32 in wg Brine FW Brine Concentration 0 % Fouling Factor 0.0 (hr-sqft-F)/BTU

NOTE: Coil is outside of the scope of AHRI Standard 410.

Fluid velocity is outside the scope of AHRI Std. 410

Thule Greenland Dormitory 39MN Sz03

Project:

Tag:

Hot Water Coil Performance Summary v6.39a11/16/15 www.carrier.com

Fan Model 39M Unit Size 03 Fan Type FORWARD CURVED Fan Wheel Diameter 9 Fan Class I Fan Application Draw Thru Orientation Horizontal

Actual Airflow, CFM 1000 Site Altitude, ft 0 Upstream Ext. Static, in wg 0.00 Downstream Ext. Static, in wg 1.00 Cooling Coil Static, in wg 0.00 Heating Coil Static, in wg 0.32 Other Losses, in wg 0.00 Total Accessory Static, in wg 0.15 Total Static Pressure, in wg 1.47 Calculated Fan RPM / Motor RPM 1394 / 1800 Class I Max. RPM 2132 Static Efficiency (%) 44 Fan BHP 0.5

Acoustic Data:

CasingInletDischarge

707477 63 Hz 697477 125 Hz 626874 250 Hz 636773 500 Hz 636975 1000 Hz 616772 2000 Hz 606671 4000 Hz 586368 8000 Hz

Sound power levels for 39M units are rated in accordance with AHRI Standard 260.

Accessories:

(1) Filter/Mixing Box Pleated (2") MERV 8 [0.05]

(1) ANG Synthetic (4") MERV 13 [0.06]

(1) Mixing or Exhaust Box [0.03]

Thule Greenland Dormitory 39MN Sz03

Project:

Tag:

Supply Fan Performance Summary

VFD Submittal Project:

Unit Tag:

Note: Unbracketed dimensions listed in millimeters [Bracketed dimensions listed in inches]

Manufacturer Part Number Voltage Frame Size .................................................................................... R1 Application Horsepower Maximum Continuous Output (A) UL Class T Fuse Amps MCCB Rated Amps

General Dimensions

Height (in.)

Width (in.)

Depth (in.)

Shipping Weight (lbs.)

39MN Sz03 Thule Greenland Dormitory

ACH550-UH-03A3-4

460 Volts 3 Phase 60Hz

R1

1 HP

3.3

14.5 4.9 8.3 14.3

Air Filter Submittal

Carrier Part Number Kit Description Unit Airflow, CFM Filter Velocity, FPM Filter Sizes and Quantities

Quality Pleat MERV 8 Pleated Filter

The 100% synthetic graduated density media is continuously bonded to a 30 gauge galvanized, corrosion resistant, expanded metal support grid with an effective open area of 96%. The media is resistant to a wide range of chemicals, does not absorb moisture and will not support microbial growth.

The controlled pleat spacing maximizes surface area and dust holding capacity and is bonded to the enclosure frame to prevent dust bypass. The enclosure frame is constructed of high wet strength moisture resistant beverage board. The diagonal support members of the frame are bonded to the entering and exiting apexes of each pleat to prevent pleat collapse and filter bowing.

0.1

0.2

0.3

0.4

200 250 300 350 400 450 500 550 600 650 700

In it ia l R es is ta nc e (in

. w .g

Filter Face Velocity (feet per minute)

Filter Pleated (2") MERV 8

Thule Greenland Dormitory 39MN Sz03

31KFD39MD003522

Filter Kit, 2'' ANG/FMB Pleated (MERV8), 39M003 Qty (2) 16in. x 25in.

v6.39a11/16/15

Air Filter Submittal

Carrier Part Number Kit Description Unit Airflow, CFM Filter Velocity, FPM Filter Sizes and Quantities

Quality Pleat MERV 13 Pleated Filter

The 100% synthetic graduated density media is continuously bonded to a 30 gauge galvanized, corrosion resistant, expanded metal support grid with an effective open area of 96%. The media is resistant to a wide range of chemicals, does not absorb moisture and will not support microbial growth.

The controlled pleat spacing maximizes surface area and dust holding capacity and is bonded to the enclosure frame to prevent dust bypass. The enclosure frame is constructed of high wet strength moisture resistant beverage board. The diagonal support members of the frame are bonded to the entering and exiting apexes of each pleat to prevent pleat collapse and filter bowing.

0.1

0.2

0.3

0.4

0.5

0.6

200 250 300 350 400 450 500 550 600 650 700

In it ia l R es is ta nc e (in

. w .g

Filter Face Velocity (feet per minute)

Filter Pleated (4") MERV 13

Thule Greenland Dormitory 39MN Sz03

31KFG39MD003842

Filter Kit, 4'' ANG/FMB Pleated (MERV13), 39M003 Qty (2) 16in. x 25in.

v6.39a11/16/15

THULE AIR BASE

DISTRICT HEATING STANDARD