BALLISTIC EVALUATION CENTER AUGUST 14, 2012
NEW YORK DISTRICT USACOE - PICATINNY AMENDMENT 2
PROJECT TABLE OF CONTENTS
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
00 31 31 GEOTECHNICAL DATA
00 41 00 BID SCHEDULES
00 80 00.00 18 SPECIAL CONTRACT REQUIREMENTS
DIVISION 01 - GENERAL REQUIREMENTS
01 12 00.00 18 DESIGN AND RECORD DRAWING REQUIREMENTS
01 32 01.00 18 PROJECT SCHEDULE
01 33 00.00 18 SUBMITTAL PROCEDURES
01 33 29 LEED(TM) DOCUMENTATION
01 35 26 GOVERNMENTAL SAFETY REQUIREMENTS
01 42 00 SOURCES FOR REFERENCE PUBLICATIONS
01 45 02.00 18 QUALITY CONTROL SYSTEM (QCS)
01 45 04.00 18 CONTRACTOR QUALITY CONTROL
01 45 20.00 18 TESTING FOR MECHANICAL AND ELECTRICAL SYSTEMS
01 45 30.00 18 CONTRACTOR WARRANTY MANAGEMENT
01 52 60.00 18 CONSTRUCTION INDOOR AIR QUALITY (IAQ) MANAGEMENT
01 57 20.00 10 ENVIRONMENTAL PROTECTION
01 62 35 RECYCLED / RECOVERED MATERIALS
01 74 19 CONSTRUCTION AND DEMOLITION WASTE MANAGEMENT
01 78 23.00 18 OPERATION AND MAINTENANCE DATA
DIVISION 02 - EXISTING CONDITIONS
02 41 00 DEMOLITION AND DECONSTRUCTION
02 82 14.00 10 ASBESTOS HAZARD CONTROL ACTIVITIES
02 83 13.00 20 LEAD IN CONSTRUCTION
DIVISION 03 - CONCRETE
03 20 00.00 10 CONCRETE REINFORCING
03 30 00 CAST-IN-PLACE CONCRETE
DIVISION 05 - METALS
05 12 00 STRUCTURAL STEEL
05 30 00 STEEL DECKS
05 50 13 MISCELLANEOUS METAL FABRICATIONS
05 51 00 METAL STAIRS
05 51 33 METAL LADDERS
05 52 00 METAL RAILINGS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
06 10 00 ROUGH CARPENTRY
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 17 00 BENTONITE WATERPROOFING
07 21 13 BOARD AND BLOCK INSULATION
07 21 16.12 MINERAL FIBER BLANKET INSULATION
07 22 00.12 ROOF AND DECK INSULATION
07 41 13 METAL ROOF PANELS
07 42 63 FABRICATED WALL PANEL ASSEMBLIES
07 54 19 ETHYLENE INTERPOLYMER (KEE) ROOFING
PROJECT TABLE OF CONTENTS Page 1
07 60 00 FLASHING AND SHEET METAL
07 84 00 FIRESTOPPING
07 92 00 JOINT SEALANTS
DIVISION 08 - OPENINGS
08 11 13 STEEL DOORS AND FRAMES
08 33 23 OVERHEAD COILING DOORS
08 34 16.10 STEEL SLIDING HANGAR DOORS
08 39 53 BLAST RESISTANT SLIDING DOORS
08 39 54 BLAST RESISTANT DOORS
08 41 13 ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
08 56 53 BLAST RESISTANT GLASS WINDOWS
08 71 00 DOOR HARDWARE
08 81 00 GLAZING
08 91 00 METAL WALL AND DOOR LOUVERS
DIVISION 09 - FINISHES
09 22 00 SUPPORTS FOR PLASTER AND GYPSUM BOARD
09 29 00 GYPSUM BOARD
09 30 00 CERAMIC TILE, QUARRY TILE, AND PAVER TILE
09 51 00 ACOUSTICAL CEILINGS
09 65 00 RESILIENT FLOORING
09 65 66 RESILIENT RUBBER FLOORING
09 67 23.14 CHEMICAL RESISTIVE RESINOUS FLOORING
09 90 00 PAINTS AND COATINGS
09 96 00 HIGH-PERFORMANCE COATINGS
DIVISION 10 - SPECIALTIES
10 14 02 INTERIOR SIGNAGE
10 22 13 WIRE MESH PARTITIONS
10 26 13 WALL AND CORNER GUARDS
10 28 13 TOILET ACCESSORIES
10 44 16 FIRE EXTINGUISHERS
10 56 29.16 PALLET STORAGE RACK
DIVISION 11 - EQUIPMENT
11 13 13 LOADING DOCK BUMPERS
11 53 00 LABORATORY EQUIPMENT AND FUMEHOODS
DIVISION 12 - FURNISHINGS
12 31 00 MANUFACTURED METAL CASEWORK
DIVISION 13 - SPECIAL CONSTRUCTION
13 48 00 SEISMIC PROTECTION FOR MISCELLANEOUS EQUIPMENT
DIVISION 14 - CONVEYING EQUIPMENT
14 24 00 HYDRAULIC ELEVATORS
DIVISION 21 - FIRE SUPPRESSION
21 13 13.00 10 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION
21 13 17.00 10 DRY PIPE SPRINKLER SYSTEM, FIRE PROTECTION
PROJECT TABLE OF CONTENTS Page 2
21 13 19.00 10 ULTRA HIGH SPEED SPRINKLER SYSTEMS, FIRE PROTECTION
DIVISION 22 - PLUMBING
22 00 00 PLUMBING, GENERAL PURPOSE
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING
23 00 00 AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST SYSTEMS
23 05 15 COMMON PIPING FOR HVAC
23 05 48 VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND
EQUIPMENT
23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC
23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS
23 08 00.00 10 COMMISSIONING OF HVAC SYSTEMS
23 09 23.13 20 BACnet DIRECT DIGITAL CONTROL SYSTEMS FOR HVAC
23 23 00 REFRIGERANT PIPING
23 57 10.00 10 FORCED HOT WATER HEATING SYSTEMS USING WATER AND STEAM
HEAT EXCHANGERS
23 82 02.00 10 UNITARY HEATING AND COOLING EQUIPMENT
DIVISION 26 - ELECTRICAL
26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS
26 05 48.00 10 SEISMIC PROTECTION FOR ELECTRICAL EQUIPMENT
26 08 00 APPARATUS INSPECTION AND TESTING
26 20 00 INTERIOR DISTRIBUTION SYSTEM
26 23 00 SWITCHBOARDS
26 24 16.00 40 PANELBOARDS
26 27 13.10 30 ELECTRIC METERS
26 28 01.00 10 COORDINATED POWER SYSTEM PROTECTION
26 32 33.00 10 UNINTERRUPTIBLE POWER SUPPLY (UPS) SYSTEM ABOVE 15 KVA
CAPACITY
26 41 01.00 10 LIGHTNING PROTECTION SYSTEM
26 51 00 INTERIOR LIGHTING
26 55 53.00 10 EXTERIOR LIGHTING INCLUDING SECURITY AND CCTV APPLICATIONS
DIVISION 27 - COMMUNICATIONS
27 05 28.36 40 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS
27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM
27 21 00.00 20 INTERCOMMUNICATION PUBLIC ADDRESS SYSTEM
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
28 16 01.00 10 SMALL INTRUSION DETECTION SYSTEM
28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM
DIVISION 31 - EARTHWORK
31 00 00 EARTHWORK
31 05 19 GEOTEXTILE
31 11 00 CLEARING AND GRUBBING
31 21 13 RADON MITIGATION
31 23 00.00 20 EXCAVATION AND FILL
31 31 16 SOIL TREATMENT FOR SUBTERRANEAN TERMITE CONTROL
31 32 11 SOIL SURFACE EROSION CONTROL
DIVISION 32 - EXTERIOR IMPROVEMENTS
PROJECT TABLE OF CONTENTS Page 3
32 01 16.17 COLD MILLING OF BITUMINOUS PAVEMENTS
32 11 23 AGGREGATE BASE COURSE
32 12 10 BITUMINOUS TACK AND PRIME COATS
32 12 16 HOT-MIX ASPHALT (HMA) FOR ROADS
32 13 13.06 PORTLAND CEMENT CONCRETE PAVEMENT FOR ROADS AND SITE
FACILITIES
32 15 00 AGGREGATE SURFACE COURSE
32 16 13 CONCRETE SIDEWALKS AND CURBS
32 17 23.00 20 PAVEMENT MARKINGS
32 31 13 CHAIN LINK FENCES AND GATES
32 32 23 SEGMENTAL CONCRETE BLOCK RETAINING WALL
32 92 19 SEEDING
DIVISION 33 - UTILITIES
33 11 00 WATER DISTRIBUTION
33 30 00 SANITARY SEWERS
33 40 00 STORM DRAINAGE UTILITIES
33 61 00 PREFABRICATED UNDERGROUND HEATING/COOLING DISTRIBUTION
SYSTEM
33 61 13 PRE-ENGINEERED UNDERGROUND HEAT DISTRIBUTION SYSTEM
33 71 02.00 20 UNDERGROUND ELECTRICAL DISTRIBUTION
33 82 00 TELECOMMUNICATIONS OUTSIDE PLANT (OSP)
DIVISION 34 - TRANSPORTATION
34 71 13.16 TRAFFIC GUARD RAILS
DIVISION 41 - MATERIAL PROCESSING AND HANDLING EQUIPMENT
41 22 13.14 BRIDGE CRANES, OVERHEAD ELECTRIC, TOP RUNNING
-- End of Project Table of Contents --
PROJECT TABLE OF CONTENTS Page 4
SECTION 03 30 00
CAST-IN-PLACE CONCRETE
11/10
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ACI INTERNATIONAL (ACI)
ACI/MCP-1 (2010) Manual of Concrete Practice Part 1
ACI/MCP-2 (2010) Manual of Concrete Practice Part 2
ACI/MCP-3 (2010) Manual of Concrete Practice Part 3
ACI/MCP-4 (2010) Manual of Concrete Practice Part 4
AMERICAN ASSOCIATION OF STATE HIGHWAY AND TRANSPORTATION OFFICIALS
(AASHTO)
AASHTO M 182 (2009) Standard Specification for Burlap Cloth Made from Jute or Kenaf and Cotton Mats
AASHTO M 322M/M 322 (2007) Standard Specification for Rail-Steel and Axle-Steel Deformed Bars for Concrete Reinforcement
AMERICAN HARDBOARD ASSOCIATION (AHA)
AHA A135.4 (1995; R 2004) Basic Hardboard
AMERICAN WELDING SOCIETY (AWS)
AWS D1.4/D1.4M (2005) Structural Welding Code - Reinforcing Steel
ASTM INTERNATIONAL (ASTM)
ASTM A 185/A 185M (2007) Standard Specification for Steel Welded Wire Reinforcement, Plain, for Concrete
ASTM A 496/A 496M (2007) Standard Specification for Steel Wire, Deformed, for Concrete Reinforcement
ASTM A 497/A 497M (2007) Standard Specification for Steel Welded Wire Reinforcement, Deformed, for Concrete
ASTM A 53/A 53M (2007) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, SECTION 03 30 00 Page 1
Welded and Seamless
ASTM A 615/A 615M (2009b) Standard Specification for Deformed and Plain Carbon-Steel Bars for Concrete Reinforcement
ASTM A 82/A 82M (2007) Standard Specification for Steel Wire, Plain, for Concrete Reinforcement
ASTM C 1017/C 1017M (2007) Standard Specification for Chemical Admixtures for Use in Producing Flowing Concrete
ASTM C 1107/C 1107M (2008) Standard Specification for Packaged Dry, Hydraulic-Cement Grout (Nonshrink)
ASTM C 1260 (2007) Standard Test Method for Potential Alkali Reactivity of Aggregates (Mortar-Bar Method)
ASTM C 143/C 143M (2010) Standard Test Method for Slump of Hydraulic-Cement Concrete
ASTM C 150/C 150M (2009) Standard Specification for Portland Cement
ASTM C 156 (2009a) Standard Test Method for Water Retention by Concrete Curing Materials
ASTM C 1567 (2008) Standard Test Method for Potential Alkali-Silica Reactivity of Combinations of Cementitious Materials and Aggregate (Accelerated Mortar-Bar Method)
ASTM C 171 (2007) Standard Specification for Sheet Materials for Curing Concrete
ASTM C 172 (2008) Standard Practice for Sampling Freshly Mixed Concrete
ASTM C 173/C 173M (2010a) Standard Test Method for Air Content of Freshly Mixed Concrete by the Volumetric Method
ASTM C 192/C 192M (2007) Standard Practice for Making and Curing Concrete Test Specimens in the Laboratory
ASTM C 231 (2009b) Standard Test Method for Air Content of Freshly Mixed Concrete by the Pressure Method
ASTM C 233 (2007) Standard Test Method for Air-Entraining Admixtures for Concrete
ASTM C 260 (2006) Standard Specification for Air-Entraining Admixtures for Concrete
ASTM C 295 (2008) Petrographic Examination of
SECTION 03 30 00 Page 2
Aggregates for Concrete
ASTM C 309 (2007) Standard Specification for Liquid Membrane-Forming Compounds for Curing Concrete
ASTM C 31/C 31M (2009) Standard Practice for Making and Curing Concrete Test Specimens in the Field
ASTM C 311 (2007) Sampling and Testing Fly Ash or Natural Pozzolans for Use as a Mineral Admixture in Portland-Cement Concrete
ASTM C 33/C 33M (2008) Standard Specification for Concrete Aggregates
ASTM C 39/C 39M (2009a) Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
ASTM C 42/C 42M (2010) Standard Test Method for Obtaining and Testing Drilled Cores and Sawed Beams of Concrete
ASTM C 494/C 494M (2010) Standard Specification for Chemical Admixtures for Concrete
ASTM C 595/C 595M (2010) Standard Specification for Blended Hydraulic Cements
ASTM C 618 (2008a) Standard Specification for Coal Fly Ash and Raw or Calcined Natural Pozzolan for Use in Concrete
ASTM C 881/C 881M (2002) Standard Specification for Epoxy-Resin-Base Bonding Systems for Concrete
ASTM C 932 (2006) Standard Specification for Surface-Applied Bonding Compounds for Exterior Plastering
ASTM C 94/C 94M (2009a) Standard Specification for Ready-Mixed Concrete
ASTM C 989 (2009a) Standard Specification for Slag Cement for Use in Concrete and Mortars
ASTM C 990 (2009) Standard Specification for Joints for Concrete Pipe, Manholes and Precast Box Sections Using Preformed Flexible Joint Sealants
ASTM D 1557 (2009) Standard Test Methods for Laboratory Compaction Characteristics of Soil Using Modified Effort (56,000 ft-lbf/ft3) (2700 kN-m/m3)
ASTM D 1751 (2004; R 2008) Standard Specification for
SECTION 03 30 00 Page 3
Preformed Expansion Joint Filler for Concrete Paving and Structural Construction (Nonextruding and Resilient Bituminous Types)
ASTM D 1752 (2004a; R 2008) Standard Specification for Preformed Sponge Rubber Cork and Recycled PVC Expansion
ASTM D 5759 (1995; R 2005) Characterization of Coal Fly Ash and Clean Coal Combustion Fly Ash for Potential Uses
ASTM E 1745 (2009) Standard Specification for Water Vapor Retarders Used in Contact with Soil or Granular Fill under Concrete Slabs
ASTM E 329 (2009) Standard Specification for Agencies Engaged in the Testing and/or Inspection of Materials Used in Construction
CONCRETE REINFORCING STEEL INSTITUTE (CRSI)
CRSI 10MSP (2001; 27Ed) Manual of Standard Practice
NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY (NIST)
NIST PS 1 (2007) DOC Voluntary Product Standard PS 1-07, Structural Plywood
U.S. ARMY CORPS OF ENGINEERS (USACE)
COE CRD-C 572 (1974) Corps of Engineers Specifications for Polyvinylchloride Waterstops
U.S. DEPARTMENT OF COMMERCE (DOC)
DOC/NIST PS1 (1995) Construction and Industrial Plywood with Typical APA Trademarks
U.S. GENERAL SERVICES ADMINISTRATION (GSA)
FS MMM-A-001993 (1978) Adhesive, Epoxy, Flexible, Filled (For Binding, Sealing, and Grouting)
FS SS-S-200 (Rev E; Am 2) Sealant, Joint, Two-Component, Jet-Blast-Resistant, Cold-Applied, for Portland Cement Concrete Pavement
U.S. GREEN BUILDING COUNCIL (USGBC)
LEED (2002; R 2005) Leadership in Energy and Environmental Design(tm) Green Building Rating System for New Construction
(LEED-NC)
SECTION 03 30 00 Page 4
1.2 DEFINITIONS
a. "Cementitious material" as used herein must include all portland cement, pozzolan, fly ash, and ground granulated blast-furnace slag.
b. "Exposed to public view" means situated so that it can be seen from eye level from a public location after completion of the building. A public location is accessible to persons not responsible for operation or maintenance of the building.
c. "Chemical admixtures" are materials in the form of powder or fluids that are added to the concrete to give it certain characteristics not obtainable with plain concrete mixes.
d. "Workability (or consistence)" is the ability of a fresh (plastic) concrete mix to fill the form/mould properly with the desired work (vibration) and without reducing the concrete's quality. Workability depends on water content, chemical admixtures, aggregate (shape and size distribution), cementitious content and age (level of hydration).
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00.00 18 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Fabrication Drawings for concrete formwork must be submitted by the Contractor in accordance with paragraph entitled, "Shop Drawings," of this section, to include the following:
Formwork; G, AE Column Forms; G, AE Wall Forms; G, AE Floor Forms; G, AE Ceiling FormsG, AE Reinforcing steel; G, AE
Reproductions of contract drawings are unacceptable.
Provide erection drawings for concrete Formwork that show placement of reinforcement and accessories, with reference to the contract drawings.
SD-03 Product Data
Materials for curing concrete; G, AE Joint sealants; (LEED); G, AE
Submit manufacturer's product data, indicating VOC content.
Manufacturer's catalog data for the following items must include printed instructions for admixtures, bonding agents, epoxy-resin adhesive binders, waterstops, and liquid chemical floor hardeners.
Joint filler; (LEED); G, AE Cement; (LEED); G, AE
SECTION 03 30 00 Page 5
Portland Cement; G, AE Ready-Mix Concrete; G, AE Vapor retarder and Vapor barrier; G, AE Bonding Materials; G, AE Floor Finish Materials; G, AE Concrete Curing Materials; G, AE Reinforcement; (LEED); G, AE Reinforcement Materials; G, AE Liquid Chemical Floor Hardener; G, AE
Submit documentation indicating percentage of post-industrial and post-consumer recycled content per unit of product. Indicate relative dollar value of recycled content products to total dollar value of products included in project.
Epoxy bonding compoundG, AE WaterstopsG, AE Wood FormsG, AE Local/Regional Materials; (LEED)
Submit documentation indicating distance between manufacturing facility and the project site. Indicate distance of raw material origin from the project site. Indicate relative dollar value of local/regional materials to total dollar value of products included in project.
SD-05 Design Data
Concrete mix design; G, AE
Thirty days minimum prior to concrete placement, submit a mix design for each strength and type of concrete. Submit a complete list of materials including type; brand; source and amount of cement, fly ash, pozzolans, ground slag, and admixtures; and applicable reference specifications. Provide mix proportion data using at least three different water-cement ratios for each type of mixture, which produce a range of strength encompassing those required for each class and type of concrete required. If source material changes, resubmit mix proportion data using revised source material. Provide only materials that have been proven by trial mix studies to meet the requirements of this specification, unless otherwise approved in writing by the Contracting Officer.
Indicate clearly in the submittal where each mix design is used when more than one mix design is submitted. Submit additional data regarding concrete aggregates if the source of aggregate changes. Submit copies of the fly ash, and pozzolan test results, in addition. The approval of fly ash, and pozzolan test results must be within 6 months of submittal date. Obtain acknowledgement of receipt prior to concrete placement.
Calculations; G, AE
SD-06 Test Reports
Concrete mix design; G, AE Fly ash; G, AE Pozzolan; G, AE Ground granulated blast-furnace slag; G, AE
SECTION 03 30 00 Page 6
Aggregates; G, AE Tolerance report; G, AE Compressive strength tests; G, AE Air Content; G, AE Slump; G, AE Air Entrainment; G, AE
SD-07 Certificates
Curing concrete elements; F, AE Pumping concrete; F, AE Form removal schedule; F, AE VOC Content for form release agents, curing compounds, and concrete penetrating sealers; F, AE Material Safety Data Sheets; F, AE
SD-08 Manufacturer's Instructions
Fly ash; F, AE Ground granulated blast-furnace slag; F, AE
1.4 MODIFICATION OF REFERENCES
Accomplish work in accordance with ACI publications except as modified herein. Consider the advisory or recommended provisions to be mandatory.
Interpret reference to the "Building Official," the "Structural Engineer," and the "Architect/Engineer" to mean the Contracting Officer.
1.5 DELIVERY, STORAGE, AND HANDLING
Do not deliver concrete until vapor retarder, vapor barrier, forms, reinforcement, embedded items, and chamfer strips are in place and ready for concrete placement. ACI/MCP-2 for job site storage of materials.
Protect materials from contaminants such as grease, oil, and dirt. Ensure materials can be accurately identified after bundles are broken and tags removed. Do not store concrete curing compounds or sealers with materials that have a high capacity to adsorb volatile organic compound (VOC) emissions. Do not store concrete curing compounds or sealers in occupied spaces.
1.5.1 Reinforcement
Store reinforcement of different sizes and shapes in separate piles or racks raised above the ground . Protect from contaminants such as grease, oil, and dirt. Ensure bar sizes can be accurately identified after bundles are broken and tags removed.
1.6 QUALITY ASSURANCE
1.6.1 Design Data
1.6.1.1 Formwork Calculations
ACI/MCP-4. Include design calculations indicating arrangement of forms, sizes and grades of supports (lumber), panels, and related components.
Furnish drawings and calculations of shoring and re-shoring methods proposed for floor and roof slabs, spandrel beams, and other horizontal
SECTION 03 30 00 Page 7 concrete members.
1.6.2 Drawings
1.6.2.1 Shop Drawings
Fabrication Drawings for concrete formwork for Reinforcement Materials, Column Forms, Wall Forms, Floor Forms, and Ceiling Forms must indicate concrete pressure calculations with both live and dead loads, along with material types. Provide all design calculations in accordance with ACI/MCP-2 and ACI/MCP-3.
1.6.2.2 Formwork
Drawings showing details of formwork including, but not limited to; joints, supports, studding and shoring, and sequence of form and shoring removal.
Reproductions of contract drawings are unacceptable.
Design, fabricate, erect, support, brace, and maintain formwork so that it is capable of supporting without failure all vertical and lateral loads that may reasonably be anticipated to be applied to the formwork.
1.6.2.3 Reinforcing Steel
ACI/MCP-4. Indicate bending diagrams, assembly diagrams, splicing and laps of bars, shapes, dimensions, and details of bar reinforcing, accessories, and concrete cover. Do not scale dimensions from structural drawings to determine lengths of reinforcing bars.
1.6.3 Control Submittals
1.6.3.1 Curing Concrete Elements
Submit proposed materials and methods for curing concrete elements.
1.6.3.2 Pumping Concrete
Submit proposed materials and methods for pumping concrete. Submittal must include mix designs, pumping equipment including type of pump and size and material for pipe, and maximum length and height concrete is to be pumped.
1.6.3.3 Form Removal Schedule
Submit schedule for form removal indicating element and minimum length of time for form removal.
1.6.3.4 VOC Content for form release agents, curing compounds, and concrete penetrating sealers
Submit certification for the form release agent, curing compounds, and concrete penetrating sealers that indicate the VOC content of each product.
1.6.3.5 Material Safety Data Sheets
Submit Material Safety Data Sheets (MSDS) for all materials that are regulated for hazardous health effects. Prominently post the MSDS at the construction site.
SECTION 03 30 00 Page 8
1.6.4 Test Reports
1.6.4.1 Concrete Mix Design
Submit copies of laboratory test reports showing that the mix has been successfully tested to produce concrete with the properties specified and that mix must be suitable for the job conditions. Include mill test and all other test for cement, aggregates, and admixtures in the laboratory test reports. Provide maximum nominal aggregate size, gradation analysis, percentage retained and passing sieve, and a graph of percentage retained verses sieve size. Submit test reports along with the concrete mix design. Obtain approval before concrete placement.
1.6.4.2 Fly Ash and Pozzolan
Submit test results in accordance with ASTM C 618 for fly ash and pozzolan. Submit test results performed within 6 months of submittal date. Submit manufacturer's policy statement on fly ash use in concrete.
1.6.4.3 Ground Granulated Blast-Furnace Slag
Submit test results in accordance with ASTM C 989 for ground granulated blast-furnace slag. Submit test results performed within 6 months of submittal date. Submit manufacturer's policy statement on slag use in concrete.
1.6.4.4 Aggregates
ASTM C 1260 for potential alkali-silica reactions, ASTM C 295 for petrographic analysis.
1.6.5 Field Samples
1.6.6 Special Finisher Qualifications
For 35 percent or more fly ash content as a percentage of cementitious materials, finisher must have a minimum of 3 years' experience finishing high-volume fly ash concrete.
1.7 ENVIRONMENTAL REQUIREMENTS
Provide space ventilation according to manufacturer recommendations, at a minimum, during and following installation of concrete curing compound and sealer. Maintain one of the following ventilation conditions during the curing compound/sealer curing period or for 72 hours after installation:
a. Supply 100 percent outside air 24 hours a day.
b. Supply airflow at a rate of 6 air changes per hour, when outside temperatures are between 55 degrees F and 84 degrees F and humidity is between 30 percent and 60 percent.
c. Supply airflow at a rate of 1.5 air changes per hour, when outside air conditions are not within the range stipulated above.
1.7.1 Submittals for Environmental Performance
a. Provide data indication the percentage of post-industrial pozzolan (fly ash, blast furnace slag) cement substitution as a percentage of the
SECTION 03 30 00 Page 9 full product composite by weight.
b. Provide data indicating the percentage of post-industrial and post-consumer recycled content aggregate.
c. Provide product data indicating the percentage of post-consumer recycled steel content in each type of steel reinforcement as a percentage of the full product composite by weight.
d. Provide product data stating the location where all products were manufactured
e. For projects using FSC certified formwork, provide chain-of-custody documentation for all certified wood products.
f. For projects using reusable formwork, provide data showing how formwork is reused.
g. Provide MSDS product information data showing that form release agents meet any environmental performance goals such as using vegetable and soy based products.
h. Provide MSDS product information data showing that concrete adhesives meet any environmental performance goals including low emitting, low volatile organic compound products.
1.8 SUSTAINABLE DESIGN REQUIREMENTS
1.8.1 Local/Regional Materials
Use materials or products extracted, harvested, or recovered, as well as manufactured, within a 500 mile radius from the project site, if available from a minimum of three sources.See Section 01 33 29 LEED(tm) DOCUMENTATION for cumulative total local material requirements. Concrete materials may be locally available.
1.9 QUALIFICATIONS FOR CONCRETE TESTING SERVICE
Perform concrete testing by an approved laboratory and inspection service experienced in sampling and testing concrete. Testing agency must meet the requirements of ASTM E 329.
1.10 CONCRETE SAMPLING AND TESTING
Testing by the Contractor must include sampling and testing concrete materials proposed for use in the work and testing the design mix for each class of concrete. Perform quality control testing during construction.
Sample and test concrete aggregate materials proposed for use in the work in accordance with ASTM C 33/C 33M.
Sample and test portland cement in accordance with ASTM C 150/C 150M.
Sample and test air-entraining admixtures in accordance with ASTM C 233.
Testing must be performed by a Grade I Testing Technician.
SECTION 03 30 00 Page 10
PART 2 PRODUCTS
2.1 MATERIALS FOR FORMS
Provide wood, plywood, or steel. Use plywood or steel forms where a smooth form finish is required.
2.1.1 Wood Forms
Use lumber as specified in Section 06 10 00 ROUGH CARPENTRY and as follows. Provide lumber that is square edged or tongue-and-groove boards, free of raised grain, knotholes, or other surface defects. Provide plywood that complies with DOC/NIST PS1, B-B concrete form panels or better or AHA A135.4, hardboard for smooth form lining.
2.1.1.1 Concrete Form Plywood (Standard Rough)
Provide plywood that conforms to NIST PS 1, B-B, concrete form, not less than 5/8-inch thick.
2.1.1.2 Overlaid Concrete Form Plywood (Standard Smooth)
Provide plywood that conforms to NIST PS 1, B-B, high density form overlay, not less than 5/8-inch thick.
2.1.2 Steel Forms
Provide steel form surfaces that do not contain irregularities, dents, or sags.
2.2 FORM TIES AND ACCESSORIES
The use of wire alone is prohibited. Provide form ties and accessories that do not reduce the effective cover of the reinforcement.
2.2.1 Polyvinylchloride Waterstops
COE CRD-C 572.
2.2.2 Dovetail Anchor Slot
Preformed metal slot approximately 1 by 1 inch of not less than 22 gage galvanized steel cast in concrete. Coordinate actual size and throat opening with dovetail anchors and provide with removable filler material.
2.3 CONCRETE
2.3.1 Contractor-Furnished Mix Design
Indicate the compressive strength (f'c) of the concrete for each portion of the structure.
SECTION 03 30 00 Page 11
Location f'c (Min.
28-day comp.
strength) (psi)
ASTM C 33
Max.
Nominal Aggregate
Range of Slump
(inches)
Maximum Water-cement Ratio (by weight)
Air Entrainment (percent)
Concrete exposed to weather
(foundations and walls) Foundations
4000 1 inch 3-inches to 5-inches
0.45 6
Floor Slabs Slab on Grade
4000 3/4 inch 2-inches to 4-inches
0.45 3
All Other Areas
5000 3/4 inch 3-inches to 5-inches
0.45 6-exterior 3-interior
Maximum slump shown above may be increased 1 inch for methods of consolidation other than vibration. slump may be increased to 8 inches when superplasticizers are used. provide air entrainment using air-entraining admixture. Provide air entrainment within plus or minus 1.5 percent of the value specified.
2.3.1.1 Mix Proportions for Normal Weight Concrete
Trial design batches, mixture proportioning studies, and testing requirements for various classes and types of concrete specified are the responsibility of the Contractor. Base mixture proportions on compressive strength as determined by test specimens fabricated in accordance with ASTM C 192/C 192M and tested in accordance with ASTM C 39/C 39M. Samples of all materials used in mixture proportioning studies must be representative of those proposed for use in the project and must be accompanied by the manufacturer's or producer's test report indicating compliance with these specifications. Base trial mixtures having proportions, consistencies, and air content suitable for the work on methodology described in ACI/MCP-1. In the trial mixture, use at least three different water-cement ratios for each type of mixture, which must produce a range of strength encompassing those required for each class and type of concrete required on the project. The maximum water-cement ratio required must be based on equivalent water-cement ratio calculations as determined by the conversion from the weight ratio of water to cement plus pozzolan, and ground granulated blast-furnace slag by weight equivalency method. Design laboratory trial mixture for maximum permitted slump and air content. Each combination of material proposed for use must have
SECTION 03 30 00 Page 12 separate trial mixture, except for accelerator or retarder use can be provided without separate trial mixture. Report the temperature of concrete in each trial batch. For each water-cement ratio, at least three test cylinders for each test age must be made and cured in accordance with ASTM C 192/C 192M and tested in accordance with ASTM C 39/C 39M for 7 and 28 days. From these results, plot a curve showing the relationship between water-cement ratio and strength for each set of trial mix studies. In addition, plot a curve showing the relationship between 7 and 28 day strengths.
2.3.1.2 Required Average Strength of Mix Design
The selected mixture must produce an average compressive strength exceeding the specified strength by the amount indicated in ACI/MCP-2. When a concrete production facility has a record of at least 15 consecutive tests, the standard deviation must be calculated and the required average compressive strength must be determined in accordance with ACI/MCP-2. When a concrete production facility does not have a suitable record of tests to establish a standard deviation, the required average strength must follow ACI/MCP-2 requirements.
2.3.2 Ready-Mix Concrete
Provide concrete that meets the requirements of ASTM C 94/C 94M.
Ready-mixed concrete manufacturer must provide duplicate delivery tickets with each load of concrete delivered. Provide delivery tickets with the following information in addition to that required by ASTM C 94/C 94M:
a. Type and brand cement
b. Cement content in 95-pound bags per cubic yard of concrete
c. Maximum size of aggregate
d. Amount and brand name of admixtures
e. Total water content expressed by water/cement ratio
2.3.3 Concrete Curing Materials
2.3.3.1 Absorptive Cover
Provide burlap cloth cover for curing concrete made from jute or kenaf, weighing 10 ounces plus or minus 5 percent per square yard when clean and dry, conforming to ASTM C 171, Class 3; or cover may be cotton mats as approved.
2.3.3.2 Moisture-Retaining Cover
Provide waterproof paper cover for curing concrete conforming to ASTM C 171, regular or white, or polyethylene sheeting conforming to ASTM C 171, or polyethylene-coated burlap consisting of a laminate of burlap and a white opaque polyethylene film permanently bonded to the burlap; burlap must conform to ASTM C 171, Class 3, and polyethylene film must conform to ASTM C 171. When tested for water retention in accordance with ASTM C 156, weight of water lost 72 hours after application of moisture retaining covering material must not exceed 0.039 gram per square centimeter of the mortar specimen surface.
SECTION 03 30 00 Page 13
2.3.3.3 Membrane-Forming Curing Compound
Provide liquid type compound conforming to ASTM C 309, Type 1, clear, Type 1D with fugitive dye for interior work and Type 2, white, pigmented for exterior work.
2.4 MATERIALS
2.4.1 Cement
ASTM C 150/C 150M, Type I or II or ASTM C 595/C 595M, Type IP(MH) or IS(MH) blended cement except as modified herein. Provide blended cement that consists of a mixture of ASTM C 150/C 150M, Type II, cement and one of the following materials: ASTM C 618 pozzolan or fly ash, ASTM C 989 ground granulated blast-furnace slag. For portland cement manufactured in a kiln fueled by hazardous waste, maintain a record of source for each batch.
Supplier must certify that no hazardous waste is used in the fuel mix or raw materials. Supplier must certify that the hazardous waste is neutralized by the manufacturing process and that no additional pollutants are discharged. For exposed concrete, use one manufacturer for each type of cement, ground slag, fly ash, and pozzolan.
2.4.1.1 Fly Ash and Pozzolan
ASTM C 618, Type N, F, or C, except that the maximum allowable loss on ignition must be 6 percent for Types N and F. Add with cement. Fly ash content must be a minimum of 25 percent by weight of cementitious material, provided the fly ash does not reduce the amount of cement in the concrete mix below the minimum requirements of local building codes. Where the use of fly ash cannot meet the minimum level, provide the maximum amount of fly ash permittable that meets the code requirements for cement content.
Report the chemical analysis of the fly ash in accordance with ASTM C 311.
Evaluate and classify fly ash in accordance with ASTM D 5759.
High contents of supplementary cementitious materials can have some detrimental effects on the concrete properties, such as slowing excessively the strength gain rate, and delaying and increasing the difficulty of finishing. The recommended maximum content (by weight of the total cementitious material) for these materials are:
1. For GGBF slag: 50 percent
2. For fly ash or natural pozzolan: 40 percent (25 percent in cold climates)
3. For silica fume: 10 percent
2.4.1.2 Ground Granulated Blast-Furnace Slag
ASTM C 989, Grade 120. Slag content must be a minimum of 25 percent by weight of cementitious material.
2.4.1.3 Portland Cement
Provide cement that conforms to ASTM C 150/C 150M, Type I, IA, II, or IIA.
Use one brand and type of cement for formed concrete having exposed-to-view finished surfaces.
SECTION 03 30 00 Page 14
2.4.2 Water
Minimize the amount of water in the mix. The amount of water must not exceed 45 percent by weight of cementitious materials (cement plus pozzolans), and in general, improve workability by adjusting the grading rather than by adding water. Water must be fresh, clean, and potable; free from injurious amounts of oils, acids, alkalis, salts, organic materials, or other substances deleterious to concrete.
2.4.3 Aggregates
ASTM C 33/C 33M, except as modified herein. Furnish aggregates for exposed concrete surfaces from one source. Provide aggregates that do not contain any substance which may be deleteriously reactive with the alkalies in the cement.
Fine and coarse aggregates must show expansions less than 0.08 percent at 16 days after casting when testing in accordance with ASTM C 1260. Should the test data indicate an expansion of 0.08 percent or greater, reject the aggregate(s) or perform additional testing using ASTM C 1567 using the Contractor's proposed mix design. In this case, include the mix design low alkali portland cement and one of the following supplementary cementitious materials:
a. GGBF slag at a minimum of 40 percent of total cementitious
b. Fly ash or natural pozzolan at a minimum of total cementitious of
1) 30 percent if (SiO2+Al2O3+Fe2O3) is 65 percent or more,
2) 25 percent if (SiO2+Al2O3+Fe2O3) is 70 percent or more,
3) 20 percent if (SiO2+Al2O3+Fe2O3) is 80 percent or more,
4) 15 percent if (SiO2+Al2O3+Fe2O3) is 90 percent or more.
If a combination of these materials is chosen, the minimum amount must be a linear combination of the minimum amounts above. Include these materials in sufficient proportion to show less than 0.08 percent expansion at 16 days after casting when tested in accordance with ASTM C 1567.
Aggregates must not possess properties or constituents that are known to have specific unfavorable effects in concrete when tested in accordance with ASTM C 295.
2.4.3.1 Aggregates/Combined Aggregate Gradation (Floor Slabs Only)
ASTM C 33/C 33M, uniformly graded and as follows: Nominal maximum aggregate size of 1 inch. A combined sieve analysis must indicate a well graded aggregate from coarsest to finest with not more than 18 percent and not less than 8 percent retained on an individual sieve, except that less than 8 percent may be retained on coarsest sieve and on No. 50 (0.3mm) sieve, and less than 8 percent may be retained on sieves finer than No. 50 (0.3mm). Provide sand that is at least 50 percent natural sand.
2.4.4 Nonshrink Grout
ASTM C 1107/C 1107M.
SECTION 03 30 00 Page 15
2.4.5 Admixtures
ASTM C 494/C 494M: Type A, water reducing; Type B, retarding; Type C, accelerating; Type D, water-reducing and retarding; and Type E, water-reducing and accelerating admixture. Do not use calcium chloride admixtures.
2.4.5.1 Air-Entraining
ASTM C 260.
2.4.5.2 High Range Water Reducer (HRWR) (Superplasticizers)
ASTM C 494/C 494M, Type F and ASTM C 1017/C 1017M.
2.4.5.3 Pozzolan
Provide fly ash or other pozzolans used as admixtures that conform to
ASTM C 618.
2.4.6 Vapor Retarder and Vapor Barrier
ASTM E 1745 multi-layer plastic extrusion virgin polyolefin resins, minimum 10 mil thickness.
a. Sheet Vapor Retarder: Class C, except with maximum perm rating of 0.018; 0.022 perms after conditioning. Include manufacturer's recommended adhesive or pressure-sensitive tape.
b. Mastic and tape by manufacturer for use with polyolefin retarder.
2.4.7 Materials for Curing Concrete
Use water-based curing compounds, sealers, and coatings with low (maximum 160 grams/liter, less water and less exempt compounds) VOC content.
Consider the use of water based or vegetable or soy based curing agents in lieu of petroleum based products. Consider agents that are not toxic and emit low or no Volatile Organic Compounds (VOC). Consider the use of admixtures that offer high performance to increase durability of the finish product but also have low toxicity and are made from bio-based materials such as soy, and emit low levels of Volatile Organic Compounds (VOC).
2.4.7.1 Impervious Sheeting
ASTM C 171; waterproof paper, clear or white polyethylene sheeting, or polyethylene-coated burlap.
2.4.7.2 Pervious Sheeting
AASHTO M 182.
2.4.7.3 Liquid Membrane-Forming Compound
ASTM C 309, white-pigmented, Type 2, Class B.
2.4.8 Liquid Chemical Sealer-Hardener Compound
Provide surface treatments containing certain chemicals, including sodium
SECTION 03 30 00 Page 16 silicate and the fluosilicates of magnesium and zinc. Provide compound that does not reduce the adhesion of resilient flooring, tile, paint, roofing, waterproofing, or other material applied to concrete.
2.4.9 Expansion/Contraction Joint Filler
ASTM D 1751, ASTM D 1752, cork or 100 percent post-consumer paper meeting ASTM D 1752 (subparagraphs 5.1 to 5.4). Material must be 1/2 inch thick, unless otherwise indicated.
2.4.10 Joint Sealants
Use concrete penetrating sealers with a low (maximum 100 grams/liter, less water and less exempt compounds) VOC content.
2.4.10.1 Waterstops
Provide waterstops made of polyvinylchloride (PVC) and that conform to
ASTM C 990.
2.4.10.2 Joint Sealant Compound
Provide cold-applied, two-component, elastomeric polymer type compound conforming to FS SS-S-200.
2.4.11 Epoxy Bonding Compound
ASTM C 881/C 881M. Provide Type I for bonding hardened concrete to hardened concrete; Type II for bonding freshly mixed concrete to hardened concrete; and Type III as a binder in epoxy mortar or concrete, or for use in bonding skid-resistant materials to hardened concrete. Provide Grade 1 or 2 for horizontal surfaces and Grade 3 for vertical surfaces. Provide Class A if placement temperature is below 40 degrees F; Class B if placement temperature is between 40 and 60 degrees F; or Class C if placement temperature is above 60 degrees F.
2.5 REINFORCEMENT
2.5.1 Reinforcing Bars
ACI/MCP-2 unless otherwise specified. Use deformed steel.
ASTM A 615/A 615M and AASHTO M 322M/M 322 with the bars marked A, S, W, Grade 60.
2.5.2 Mechanical Reinforcing Bar Connectors
ACI/MCP-2. Provide 125 percent minimum yield strength of the reinforcement bar.
2.5.3 Wire
ASTM A 82/A 82M or ASTM A 496/A 496M.
2.5.3.1 Welded Wire Fabric
ASTM A 185/A 185M or ASTM A 497/A 497M. Provide flat sheets of welded wire fabric for slabs and toppings.
SECTION 03 30 00 Page 17
2.5.3.2 Steel Wire
Wire must conform to ASTM A 82/A 82M.
2.5.4 Reinforcing Bar Supports
Provide bar ties and supports of coated or non corrodible material. Use recycled plastic with 100 percent recycled content.
2.5.5 Chairs and Bolsters: Plastic
Plastic may contain post-consumer or post-industrial recycled content.
2.5.6 Dowels for Load Transfer in Floors
Provide dowels for load transfer in floors of the type, design, weight, and dimensions indicated. Provide dowel bars that are plain-billet steel conforming to ASTM A 615/A 615M, Grade 40. Provide dowel pipe that is steel conforming to ASTM A 53/A 53M.
2.5.7 Supports for Reinforcement
Supports include bolsters, chairs, spacers, and other devices necessary for proper spacing, supporting, and fastening reinforcing bars and wire fabric in place.
Provide wire bar type supports conforming to ACI/MCP-3, ACI/MCP-4 and
CRSI 10MSP.
Legs of supports in contact with formwork must be hot-dip galvanized, or plastic coated after fabrication, or stainless-steel bar supports.
2.6 BONDING MATERIALS
2.6.1 Concrete Bonding Agent
Provide aqueous-phase, film-forming, nonoxidizing, freeze and thaw-resistant compound agent suitable for brush or spray application conforming to ASTM C 932.
2.6.2 Epoxy-Resin Adhesive Binder
Provide two-component, epoxy-polysulfide polymer type binder with an amine-type curing-agent conforming to FS MMM-A-001993, Type I or
ASTM C 881/C 881M.
2.7 FLOOR FINISH MATERIALS
2.7.1 Liquid Chemical Floor Hardener
Hardener must be a colorless aqueous solution containing a blend of magnesium fluorosilicate and zinc fluorosilicate combined with a wetting agent. Solution must contain not less than 1/2 pounds of fluorosilicates per gallon. An approved proprietary chemical hardener may be used provided hardener is delivered ready for use in manufacturer's original containers.
2.7.2 Dry Materials for Colored Wear-Resistant Finish
Provide materials that are packaged, dry, and a combination of materials
SECTION 03 30 00 Page 18 formulated for producing colored and wear-resistant monolithic surface treatments; they must include portland cement, graded-quartz aggregate, coloring pigments, and dispersing agents. Provide coloring pigments that are finely ground, nonfacing mineral oxides prepared especially for the purpose and interground with the cement.
2.8 CLASSIFICATION AND QUALITY OF CONCRETE
2.8.1 Concrete Classes and Usage
Provide concrete classes, compressive strength, requirements for air entrainment, and usage as follows:
MIN. 28-DAY
COMPRESSIVE
STRENGTH REQUIREMENT
CONCRETE POUNDS PER FOR AIR
CLASS SQ. IN. ENTRAINMENT USAGE
4A 4,000 Air- For structural concrete entrained work exposed to freezing and thawing, including foundation, loading dock, slabs on grade, and slug butt slabs on grade.
4N 4,000 Nonair- For structural concrete entrained work not exposed to freezing and thawing such as interior slabs on grade.
2.5A 2,500 Air- For concrete not entrained reinforced and not exposed to freezing and thawing
2.5N 2,500 Nonair- For concrete not entrained reinforced and not exposed to freezing and thawing
5A 5,000 Air- For structural concrete entrained work including elevated slabs, beams, walls, and columns exposed to freezing and thawing.
5N 5,000 Nonair- For structural concrete entrained work including elevated slabs, beams, walls and columns not exposed to freezing and thawing.
2.8.2 Limits for Concrete Proportions
Provide limits for maximum water/cement ratio and minimum cement content
SECTION 03 30 00 Page 19 for each concrete class as follows:
MIN. CEMENT FOR 3- TO
CONCRETE MAX. WATER/CEMENT RATIO 4-INCH SLUMP, (NO. OF 94-
CLASS BY WEIGHT POUND SACKS) PER CU. YD.
2.5A 0.58 4.75
2.5N 0.62 4.75
3A 0.50 5.25
3N 0.54 5.25
4A 0.46 6.0
4N 0.48 6.0
5A 0.41 6.5
5N 0.44 6.5
* Weight of water to weight of cement in pounds in one cubic yard of concrete
2.8.3 Maximum Size of Aggregate
Size of aggregate, designated by the sieve size on which maximum amount of retained coarse aggregate is 5 to 10 percent by weight, must be as follows:
MAXIMUM ASTM C 33/C 33M
SIZE OF SIZE
AGGREGATE NUMBER TYPE OF CONSTRUCTION
1-1/2 inches 467 Monolithic slabs on ground, concrete fill, and other flatwork having a depth of not less than 5 inches and a clear distance between reinforcing bars of not less than 2 inches
3/4 inch 67 Reinforced walls, columns, girders, beams, and other formed sections having a dimension between forms of not less than 6 inches and clear distance between reinforcing bars or reinforcing bar and face of form of not less than 1 inch
Maximum size of aggregate may be that required for most critical type of construction using that concrete class.
Specify gradation of aggregates for separate floor topping.
SECTION 03 30 00 Page 20
2.8.4 Slump
Provide slump for concrete at time and in location of placement as follows:
TYPE OF CONSTRUCTION SLUMP
Footings, unreinforced Not less than 1 inch nor more walls than 3 inches
Columns, beams, Not less than 1 inch nor more reinforced walls, than 4 inches monolithic slabs
Ramps and other sloping 0 nor more than 3 inches surfaces
2.8.5 Total Air Content
Air content of exposed concrete and interior concrete must be in accordance with ASTM C 260 and/or as follows:
LIMITS REQUIREMENT
CONCRETE FOR AIR MAXIMUM SIZE TOTAL AIR CONTENT
EXPOSURE ENTRAINMENT OF AGGREGATE BY VOLUME
Exposed to Air- 1-1/2 or 4 to 6 percent freezing entrained 2 inches and thawing 3/4 inch 5 to 7 percent or subjected to hydraulic 1/2 or 6 to 8.5 percent pressure 3/8 inch
Provide concrete exposed to freezing and thawing or subjected to hydraulic pressure that is air-entrained by addition of approved air-entraining admixture to concrete mix.
PART 3 EXECUTION
3.1 EXAMINATION
Do not begin installation until substrates have been properly constructed;
verify that substrates are plumb and true.
If substrate preparation is the responsibility of another installer, notify Architect/Engineer of unsatisfactory preparation before processing.
Check field dimensions before beginning installation. If dimensions vary too much from design dimensions for proper installation, notify Architect/Engineer and wait for instructions before beginning installation.
3.2 PREPARATION
Determine quantity of concrete needed and minimize the production of excess concrete. Designate locations or uses for potential excess concrete before the concrete is poured.
3.2.1 General
Surfaces against which concrete is to be placed must be free of debris, loose material, standing water, snow, ice, and other deleterious substances
SECTION 03 30 00 Page 21 before start of concrete placing.
Remove standing water without washing over freshly deposited concrete.
Divert flow of water through side drains provided for such purpose.
3.2.2 Subgrade Under Foundations and Footings
When subgrade material is semiporous and dry, sprinkle subgrade surface with water as required to eliminate suction at the time concrete is deposited. When subgrade material is porous, seal subgrade surface by covering surface with specified vapor retarder; this may also be used over semiporous, dry subgrade material instead of water sprinkling.
3.2.3 Subgrade Under Slabs on Ground
Before construction of slabs on ground, have underground work on pipes and conduits completed and approved.
Previously constructed subgrade or fill must be cleaned of foreign materials and inspected by the Contractor for adequate compaction and surface tolerances as specified.
Actual density of top 12 inches of subgrade soil material-in-place must not be less than the following percentages of maximum density of same soil material compacted at optimum moisture content in accordance with
ASTM D 1557.
SOIL MATERIAL PERCENT MAXIMUM DENSITY
Capillary water barrier 100
Cohesionless soil material 100
Cohesive soil material 95
Finish surface of capillary water barrier under interior slabs on ground must not show deviation in excess of 1/4 inch when tested with a 10-foot straightedge parallel with and at right angles to building lines.
Finished surface of subgrade or fill under exterior slabs on ground must not be more than 0.02-foot above or 0.10-foot below elevation indicated.
Prepare subgrade or fill surface under exterior slabs on ground as specified for subgrade under foundations and footings.
3.2.4 Formwork
Complete and approve formwork. Remove debris and foreign material from interior of forms before start of concrete placing.
3.2.5 Edge Forms and Screed Strips for Slabs
Set edge forms or bulkheads and intermediate screed strips for slabs to obtain indicated elevations and contours in finished slab surface and must be strong enough to support vibrating bridge screeds or roller pipe screeds if nature of specified slab finish requires use of such equipment. Align concrete surface to elevation of screed strips by use of strike-off templates or approved compacting-type screeds.
SECTION 03 30 00 Page 22
3.2.6 Reinforcement and Other Embedded Items
Secure reinforcement, joint materials, and other embedded materials in position, inspected, and approved before start of concrete placing.
3.3 FORMS
ACI/MCP-2. Provide forms, shoring, and scaffolding for concrete placement. Set forms mortar-tight and true to line and grade. Chamfer above grade exposed joints, edges, and external corners of concrete 0.75 inch unless otherwise indicated. Provide formwork with clean-out openings to permit inspection and removal of debris. Forms submerged in water must be watertight.
3.3.1 General
Construct forms to conform, within the tolerances specified, to shapes dimensions, lines, elevations, and positions of cast-in-place concrete members as indicated. Forms must be supported, braced, and maintained sufficiently rigid to prevent deformation under load.
3.3.2 Design and Construction of Formwork
Provide formwork design and construction that conforms to…