EXISTING FIRE HYDRANT

TO BE REMOVED

SAWCUT EXISTING

PAVEMENT

EXISTING BUILDING

TO BE REMOVED

IN ENTIRETY BY OTHERS

INSERTION VALVE

CUT & CAP EX'G. WATER LINE

APPROXIMATE LIMIT OF DISTURBANCE

ENTIRE AREA TO BE CLEARED / REGRADED

AS REQUIRED FOR PROPOSED SITE

CONSTRUCTION EXISTING PAVEMENT

TO BE REMOVED

OVERHEAD ELECTRIC

WIRES AND POLES

TO BE REMOVED

WATER LINE

TO BE REMOVED

REFER TO PLANS BY

GSIPT FOR REMOVAL OF

EXISTING BUILDING AND

SURROUNDING FEATURES

(BY OTHERS)

EXISTING OVERHEAD WIRE

TO BE REMOVED

PLAN VIEW

M A

T C

H

L I N

E

S

E

T

KEY MAP

NOT TO SCALE

NOTE:

EXISTING IMPROVEMENTS / CONDITIONS

TO BE REMOVED ARE SHOWN DARK.

ITEMS TO REMAIN ARE SHOWN HALF-TONE.

TYPICAL FOR DEMOLITION PLANS ONLY.

SAWCUT EXISTING

PAVEMENT

EXISTING WOODED

AREA TO BE

REMOVED (TYP.)

EXISTING PAVEMENT

TO BE REMOVED (TYP.)

EXISTING BUILDING TO BE

REMOVED BY OTHERS;

CONCRETE PAD TO REMAIN

EXISTING WATER LINE

TO BE REMOVED

EXISTING HYDRANT & VALVE

TO BE REMOVED

EXISTING WATER VAULT

& BOLLARDS TO BE REMOVED

EXISTING BUILDING

TO BE REMOVED

IN ENTIRETY BY OTHERS

EX'G. PAVEMENT

TO BE REMOVED

AS REQUIRED FOR

UTILITY INSTALLATION

INSERTION VALVE,

CUT & CAP EX'G.

6" WATER MAIN

EXISTING WATER MAIN

TO BE REMOVED

UTILITY POLE

AND OVERHEAD WIRE

TO BE REMOVED

PLAN VIEW

M A

T

E

KEY MAP

NOT TO SCALE

M A T C H L I N E

CONCRETE

SIDEWALK

MEET EXISTING

PAVEMENT

MEET EXISTING

PAVEMENT

10+00

11+00

12+00 13+00 14+00

15+00 16+00 17+00

EXISTING BUILDING

#3350

TO BE RECONSTRUCTED BY OTHERS

NEW

BUILDING

#3349

F.F. 965.90

TURRET STAND

R

AM

P U

P

R

AM

P D

O W

N

3' WIDE CONCRETE WALK

DRY LAID BLOCK

RETAINING WALL (TYP.)

CONCRETE PAD FOR

CRANE LOADING OPERATIONS

5' WIDE CONCRETE

SIDEWALK (TYP.)

CHILLER ENCLOSURE

W/ CONCRETE PAD

6'x6' CONCRETE PAD

FOR TRANSFORMER

8'x8' CONCRETE PAD

FOR TRANSFORMER

10" CONCRETE CURB (TYP.)

GRAVEL

4' WIDE CONCRETE WALK

6'

JIB CRANE LOCATION

SEE STRUCTURAL DWGS.

12' D.C.

(2) R7-8 VA

MOUNTED ON

FENCE

91.50'

D.C.

.5

0'

29.33'

223.21'

16.42'

123.05'

14.75'

8.66'F.F.

963.90

FULL DEPTH

BITUMINOUS

PAVEMENT

(OPTION 1)

EOP

EOP

STA. 15+26.88

N 772331.4072 E 481530.8601

STA. 14+35.38

N 772411.8570 E 481574.4499

DRY LAID MODULAR

BLOCK STEPS

WITH HANDRAILS

10'

CURB

TAPER

10'

CURB

TAPER

24' D.C.

60' D.C.

(2) PREFERRED PARKING

SIGNS, FENCE-MOUNTED

COORDINATE DEPRESSED

CURB LOCATION WITH

BUILDING 3350

CONSTRUCTION

PLANS BY OTHERS

DRY LAID MODULAR BLOCK

RETAINING WALL WITH

TRENCH DRAIN (TYP.)

CABLE GATE

(UTILIZE BOLLARD

AS END POST)

R = 10.5

R = 75 LOADING DOCK

AND RAMP TO BE

CONSTRUCTED

BY OTHERS

REFER TO PLANS

BY GSIPT FOR

IMPROVEMENTS

(BY OTHERS)

10'

CURB

TAPER

PLAN VIEW

M A

T

E

KEY MAP

NOT TO SCALE

9' 18'

R

10" CONCRETE

CURB

4" WIDE WHITE

STRIPING (TYP.)

BITUMINOUS

PAVEMENT

(TYP.)

15' x 20' DUMPSTER

ENCLOSURE

CONCRETE

LOADING PAD

6" WIDE YELLOW

STRIPING

FIRE SERVICE

PUMP STATION

FULL-DEPTH

BITUMINOUS

PAVEMENT

(OPTION 1)

NEW

BUILDING

#3353

F.F. 968.00

RAMP

R

AM

P

LOADING DOCK;

REFER TO

STRUCTURAL PLANS

17+00 18+00 19+00

R70.5'

50'

8'

6' WIDE

CONCRETE

SIDEWALK

EXISTING CONCRETE PAD

TO REMAIN

#3352

EL. 965.61

20+00

20' WIDE BITUMINOUS RAMP

FLUSH W/ CONCRETE PAD

10' CURB TAPER

90 LF DRY LAID

RETAINING WALL

(2) R7-8 VA

8' 8'

8'

EOP

FULL DEPTH

PAVEMENT

REPLACEMENT

M

EE

T

EX

IS

TI

NG

(T

YP

199.00'

199.00'

.5

0' 60.50'

EDGE OF PAVEMENT

MEET EXISTING

PAVEMENT

CABLE

GATE

DRY LAID

MODULAR BLOCK

STEPS W/ HANDRAILS

CONCRETE PLATFORM

4'

4'

BICYCLE RACK 21+00

FULL DEPTH

PAVEMENT

REPLACEMENT

FULL DEPTH

PAVEMENT

REPLACEMENT

CONCRETE

TRANSFORMER

PAD

"ROOF OPTION"

TO BE CONSTRUCTED

OVER EXISTING CONCRETE

PAD (BY OTHERS)

FULL DEPTH

PAVEMENT

REPLACEMENT

M

EE

T

EX

IS

TI

NG

(T

YP

PLAN VIEW

M A

T

E

KEY MAP

NOT TO SCALE

10+00 11+00

12+00 13+00 14+00 15+00 16+00 17+00

9+00

+2.50 %

PVI = 10+05

EL. = 967.00

50' VC

P V

C

+8

E

L.

.3

P V

T

+3

E

L.

.3

PVI = 12+15

EL. = 970.08

250' VC

HP = 11+80.5

EL. = 968.91

P V

C

0+

E

L.

.2

P V

T

+4

E

L.

.8

PVI = 14+00

EL. = 965.28

100' VC

P V

C

3+

E

L.

.5

P V

T

+5

E

L.

.0

PVI = 16+00

EL. = 964.12

100' VC

LP = 15+93.6

EL. = 964.28

P V

C

5+

E

L.

.4

P V

T

+5

E

L.

.5

P V

C

6+

E

L.

.6

S

TA

. 9 +4

8± E

L.

.5

M

EE

T

EX

IS

TI

N G

+1.45 %

-2.60 %

-0.59 % +0.75 %

M A

TC

H

L

IN

7+

EXISTING GRADE

PROPOSED GRADE

6.

7.

8.

8.

8.

8.

7.

6.

5.

5.

4.

4.

4.

4.

4.

12'12' CURB OR E.O.P.

PER PLAN

SEE PAVEMENT DETAIL

2.0 %2.0 %

TYPICAL ROAD SECTION

STATION 10+50 TO 19+00

10+00

11+00

12+00 13+00 14+00

15+00 16+00 17+00

EXISTING BUILDING

#3350

TO BE RECONSTRUCTED BY OTHERS

NEW

BUILDING

#3349

F.F. 965.90

TURRET STAND

PAD

ELEV.

966.25

D.C.

D.C. D.C.

91.50'

.5

0'

29.33'

223.21'

16.42'

123.05'

14.75'

8.66'F.F.

963.90

ALL DISTURBED AREAS

TO BE RESTORED WITH

TOPSOIL, FERTILIZER,

AND SEED UNLESS

OTHERWISE NOTED

REFER TO PLANS

BY GSIPT FOR

IMPROVEMENTS

(BY OTHERS)

D.C.

PLAN VIEW

PROFILE - CENTER LINE OF WHITEK ROAD

SCALE AS SHOWN

M A

T

17+00 18+00 19+00 20+00 21+00

PVI = 17+75

EL. = 965.43

200' VC

HP = 17+60.7

EL. = 965.01

P V

T

+7

E

L.

.4

PVI = 20+00

EL. = 963.18

100' VC

P V

C

9+

E

L.

.6

P V

T

+5

E

L.

.7

S

TA

. 2 1+

B C

E L.

.0

-2.72 %

-1.00 %

M A

TC

H

L

7+

4.

5.

4.

4.

4.

3.

2.

1.

0.

NEW

BUILDING

#3353

F.F. 968.00

17+00 18+00 19+00

EXISTING CONCRETE PAD

TO REMAIN

#3352

EL. 965.61

20+00

FIRE SERVICE

PUMP HOUSE

ELEV. 968.50

199.00'

199.00'

.5

0' 60.50'

21+00

ALL DISTURBED AREAS

TO BE RESTORED WITH

TOPSOIL, FERTILIZER,

AND SEED UNLESS

OTHERWISE NOTED

DISTURBED AREAS TO BE

REGRADED AT 2:1 AND RESTORED

WITH TYPE VI STABILIZATION MAT

AND WILDFLOWER SEED MIX

16+00

17+00

FULL DEPTH

PAVEMENT

REPLACEMENT

M

EE

T

EX

IS

TI

NG

(T

YP

PLAN VIEW

PROFILE - CENTER LINE OF WHITEK ROAD

SCALE AS SHOWN

M A

T

KEY MAP

NOT TO SCALE

10+00

11+00

12+00 13+00 14+00

15+00 16+00 17+00

EXISTING BUILDING

#3350

TO BE RECONSTRUCTED BY OTHERS

2" DOMESTIC WATER

6" FIRE SERVICE WATER

6" SANITARY CONNECTION

INV. 961.25

NEW

BUILDING

#3349

F.F. 965.90

TURRET STAND

GAS

3" DOMESTIC WATER

4" SAN. - INV. 959.90±

DROP C/O INV. 958.47

(2) 4" COMM.

CONDUIT

4" SAN. INV. 961.90±

DROP C/O

INV. 959.00

6" FIRE SERVICE

WATER

(2) 4" COMM. CONDUIT

(4) 4" ELECTRIC CONDUIT

A

B A B

C

REFER TO MECHANICAL

PLANS FOR PIPING FROM

MECHANICAL ROOM TO

CHILLER ENCLOSURE

UNDERGROUND ELECTRIC

TO TRANSFORMERS

UNDERGROUND

COMMUNICATION LINE

91.50'

.5

0'

29.33'

223.21'

16.42'

123.05'

14.75'

8.66'F.F.

963.90

ELECTRIC / COMMUNICATIONS

MANHOLE (TYP.)

2" SUMP PUMP DISCHARGE ONTO

3' x 3' x 6" THICK RIP RAP PAD

INV. 957.00

GAS

METER

GAS

SERVICE

A

B

C

A B

2" SUMP PUMP DISCHARGE ONTO

3' x 3' x 6" THICK RIP RAP PAD

INV. 957.00

C/O INV. 963.00

A

A A

A

A A

A A

A

C/O INV. 961.75

C/O INV. 962.65

(5) 4" ELECTRIC CONDUIT

(6) 4" ELECTRIC CONDUIT

REFER TO PLANS

BY GSIPT FOR IMPROVEMENTS

(BY OTHERS)

PLAN VIEW

M A

T

E

NEW

BUILDING

#3353

F.F. 968.00

17+00 18+00 19+00

GAS SERVICE

EXTENSION

OVERHEAD ELECTRIC AND

COMMUNICATION SERVICES

EXISTING OVERHEAD ELECTRIC

AND COMMUNICATIONS SERVICES

(FIBER OPTICS BEING EXTENDED

ALONG BELT ROAD UNDER

SEPARATE PROJECT)

SANITARY MANHOLE

(11 TYP.)

14+00

15+00

EXISTING CONCRETE PAD

TO REMAIN

#3352

EL. 965.61

UNDERGROUND ELECTRIC

TO TRANSFORMER

4" FIRE ALARM

CONDUIT

(2) 2" POWER CONDUIT

4" SANITARY, INV. 960.00

(2) 4" COMM. CONDUIT

(3) 4" ELECTRIC CONDUIT

2" DOMESTIC WATER

8" FIRE SERVICE WATER

S

(2) 3" HOT WATER

(2) 2" COLD WATER

2" COMPRESSED AIR

(2) 2 1/2" HOT WATER

(2) 2" COLD WATER

TO BLDG. #3350

REFER TO PLANS BY OTHERS

FOR CONTINUATION

8" DIP DOMESTIC

WATER MAIN

8" DIP DOMESTIC

WATER MAIN

8" DIP FIRE SERVICE

WATER MAIN

20+00

A B

C A B

A

B

A B

A

B

A

B

A

B

A

B C

199.00'

199.00'

.5

0' 60.50'

190 LF 15" ROOF DRAIN

COLLECTION SYSTEM /

TRENCH DRAIN @ 0.50% SLOPE

150 LF 12" HDPE

ROOF DRAIN

COLLECTION SYSTEM

STUB FOR CONNECTION

FROM BUILDING 3350,

DESIGN BY OTHERS

A B

A

B

C

A B

C

A

A

B

C/O INV. 962.85 C/O INV. 961.85

C/O INV. 962.00

150 LF 12" HDPE

ROOF DRAIN

COLLECTION SYSTEM

C/O INV. 963.50

175 LF 12" ROOF DRAIN

COLLECTION SYSTEM /

HDPE TRENCH DRAIN

C/O INV. 961.00

C/O

INV. 960.70

300 LF 42" NON-PERF.

HDPE DETENTION SYSTEM

(5 ROWS @ 50' EACH)

C/O INV. 961.92

C/O INV. 962.50

A

A A

A

B

B

A

A A AB

C

21+00

6' L x 4' W SCOUR HOLE d50=7", 14" THICK

W/ FILTER FABRIC

UNDERGROUND COMM.

CONDUIT TO BLDG. 3353

16+00

17+00

WET TAP & VALVE

PLAN VIEW

M A

T

E

KEY MAP

NOT TO SCALE

10+00

11+00

12+00 13+00 14+00

15+00 16+00 17+00

EXISTING BUILDING

#3350

TO BE RECONSTRUCTED BY OTHERS

NEW

BUILDING

#3349

F.F. 965.90

TURRET STAND

91.50'

.5

0'

29.33'

223.21'

16.42'

123.05'

14.75'

8.66'F.F.

963.90

INLET PROTECTION

(TYP.)

APPROXIMATE LIMIT OF DISTURBANCE

165,870 SF (3.81 ACRES)

STABILIZED CONSTRUCTION

ENTRANCE

A

B

C

A B

2" SUMP PUMP DISCHARGE ONTO

3' x 3' x 6" THICK RIP RAP PAD

INV. 957.00

C/O INV. 963.00

A

A A

A

A A

A A

A

C/O INV. 961.75

C/O INV. 962.65

REFER TO PLANS

BY GSIPT FOR IMPROVEMENTS

(BY OTHERS)

ADDITIONAL AREA OF DISTURBANCE:

16,915 SF (0.39 ACRES)

PLAN VIEW

M A

T

E

NEW

BUILDING

#3353

F.F. 968.00

17+00 18+00 19+00

EXISTING CONCRETE PAD

TO REMAIN

#3352

EL. 965.61

20+00

199.00'

199.00'

.5

0' 60.50'

190 LF 12" ROOF DRAIN

COLLECTION SYSTEM /

TRENCH DRAIN @ 1.00% SLOPE

INLET PROTECTION

(TYP.)

APPROXIMATE LIMIT OF DISTURBANCE

165,870 SF (3.81 ACRES)

TEMPORARY TOPSOIL

STOCKPILE

SILT FENCE

(TYP.)

STUB FOR CONNECTION

FROM BUILDING 3350,

DESIGN BY OTHERS

A B

A

B

C

A B

C

A

A

B

C/O INV. 964.50 C/O INV. 962.60

C/O INV. 962.00

150 LF 12" HDPE

ROOF DRAIN

COLLECTION SYSTEM

C/O INV. 963.50

175 LF 12" ROOF DRAIN

COLLECTION SYSTEM /

HDPE TRENCH DRAIN

C/O INV. 961.00

C/O

INV. 960.70

300 LF 42" NON-PERF.

HDPE DETENTION SYSTEM

(5 ROWS @ 50' EACH)

C/O INV. 962.65

C/O INV. 962.50

A

A A

A

B

B

A

A A AB

C

21+00

6' L x 4' W SCOUR HOLE d50=7", 14" THICK

W/ FILTER FABRIC

PLAN VIEW

M A

T

E

KEY MAP

NOT TO SCALE

M A T C H L I N E

M A T C H L I N E

Sequence of Construction:

1. Install perimeter silt fencing. 3 days

2. Install stabilized construction entrance. 2 days

3. Clear and grub all additionally disturbed areas, strip and stockpile topsoil, encompass with silt fence. 5 days

4. Rough grade site. 15 days

5. Construct stormwater management from scour hole to detention basin. 20 days

6. Temporarily stabilize all disturbed areas. 5 days

7. Begin building construction, including walls. -

8. Rough grade roadway. 8 days

9. Install roadway drainage and inlet protection. 10 days

10. Install Building 3353 trench drain and additional silt fencing. 4 days

11. Extend water, gas, and sanitary sewer to site. Stop at cul-de-sac area. 30 days

12. Install turrets and all other heavy equipment within buildings. -

13. Extend all utilities to buildings. 30 days

14. Install site curbing. 10 days

15. Install bituminous pavements and concrete pads. 15 days

16. Install all walkways. 10 days

17. Permanently stabilize all disturbed areas. 3 days

18. Complete building construction. 300 days

19. Remove all temporary stabilization measures once all areas are permanently stabilized. 2 days

NOTE: Refer to plans by GSIPT for sequence of construction for Building 3350 improvements.

SHEET NOTES

KEY NOTES

1A-512

B U

IL

D

G

S E

C T

IO

N

D

T A

IL

S

A.

B4

DETAIL

1-1/2" = 1’ - 0"

B3

DETAIL

1-1/2" = 1’ - 0"

C4 1-1/2" = 1’ - 0"

B2

DETAIL

1-1/2" = 1’ - 0"

A4

DETAIL

1-1/2" = 1’ - 0"

C1 1-1/2" = 1’ - 0"

B1 1-1/2" = 1’ - 0"

EXPANSION JOINT

WINDOW DETAILS BY PEMB

MANUFACTURER

B.

1’ 2’0 6"

SCALE:1-1/2"=1’

SCALE:3/4"=1’

0 1’ 2’ 3’

CL CL

TYP

T Y

P

T Y

P T

Y P

5 STEEL SUPPORT ANGLE

6 HORIZONTAL GIRT (PEMB)

7 METAL FLASHING W/ DRIP EDGE

8 INSULATED METAL PANEL 1 (PEMB)

9 WINDOW (PEMB)

10 3 5/8" METAL STUD ASSEMBLY

2 1/2" METAL STUD ASSEMBLY11

12 5/8" GYPSUM BOARD

13 PAINTED METAL SILL CAP

METAL CONDUCTOR HEAD WITH

OVERFLOW

16 DOWNSPOUT SUPPORT CLIP

17 DECK EXPANSION JOINT COVER

18 CONTINUOUS RUBBER GUTTER SLOPED

1/8" PER FOOT TO CONDUCTOR HEAD

20 INSULATED METAL PANEL 2

22 METAL PANEL 1 (PEMB)

23 CEILING

SLOPE

24 STEEL PLATE DECK

CL

VARIES, REFER TO CIVIL

25 PRE-FABRICATED METAL ROOF CURB

27 MECH EQUIPMENT

28 WOOD BLOCKING

2"

30 ALUMINUM FASCIA SLIP JOINT

FASTENED TO CONDUCTOR HEAD

8"8"

CL

EXPANSION JOINT

7" 7"

7" 7"

B4

1A-512

DOWNSPOUT TO CONCRETE

SPLASHBLOCK

CONDUCTOR HEAD AND DOWNSPOUT

TO BE FASTENED TO ONE SIDE OF

THE EXPANSION JOINT ONLY

DETAIL- WINDOW SILL

DETAIL- WINDOW HEAD

DRIFT CLIP

C3C2

GUARDRAIL AT EXPANSION JOINTSECTION & ELEVATION

DECK LEVEL GUARDRAIL

3 /4 " = 1’ - 0" 3 /4 " = 1’ - 0"

A2 1-1/2" = 1’ - 0"

EQUIPMENT PENETRATION AT DECK

MULTIPLE EQUIPMENT PENETRATIONS

B2

1A-512

B3

1A-512

19 STEEL SUPPORT PLATE ATTACHED

FULLY TO CONDUCTOR HEAD

TUBULAR STEEL POST WELDED TO

STEEL DECK

TUBULAR STEEL GUARDRAIL

33 SEALANT W/ BACKERROD

35 FIELD CUT PANEL AT PENETRATION

36 NON-CURING BUTYL SEALANT

37 SILICONE SEALANT FILLET BEAD

AROUND PENETRATIONS

NOT USED

NOT USED

NOT USED

NOT USED

5 5/8 "

A K

K P

G L

STEEL ANGLE WELDED CONTINUOUSLY TO

AT STEEL DECK AND AT VERTICAL JOINTS

ALUMINUM FASCIA, PAINTED.

METAL FLASHING W/ POP RIVETS,

PAINTED TO MATCH ADJACENT.

A

D E

N D

M

4’-0"

*** Safety Pays ***

*** Support Value Engineering - It Pays ***

NEW YORK DISTRICT

A R

L

IN

G T

O N

V

IR

G

IA

T E

L

F A

X

R

O

R

E

IT

D w n b y

D e s ig n e d b y

R e v ie w e d b y

D a t e

R e v

C k d b y u b m it t e d b

J W

F il e n a m e

P lo t d a t t s c a le h ie f

A r c h

B r a n c

IC

Y

S L

A B s ig n f il e n o r a w in g c o d s c r ip t io n M a r k

A p p r

M a r k

D a t e

D a t e

A p p r

US Army Corps of Engineers

A

B

D

21 4 5

Sheet reference number:

2 4 51

C

N

K

IS

T R

IC

T

N

T R

IC

T

J

U L

R K

N

S T

E

B O

R A

T O

R

S T

E

B O

R A

T O

R

Sheet of 195

3A-602

O

H E

D U

L E

VINYL

TRANSITION

REDUCER

VCT

VCT

METAL

THRESHOLD

REFER TO DOOR SCHEDULE

FOR SIZE OR TYPE OF DOOR.

M A

X

S1

B2

DOOR TYPE

�" - 1’-0"B1 �" - 1’-0"

FRAME TYPE

C1

TRANSITION DETAIL

NTS C2

TRANSITION DETAIL

NTS C3 NTS

REDUCER DETAIL

D1

TYP-DOOR LOCATION

�" - 1’-0" D2 �" - 1’-0"

S1-METAL THRESHOLD

E F

NOTE: LOCATE INTERIOR DOORS

AS INDICATED ABOVE U.O.N

A1 3 " - 1’-0"

JAMB DETAIL

3 " - 1’-0"

HEAD DETAIL

A2 3 " - 1’-0"

JAMB DETAIL

3 " - 1’-0"

HEAD DETAIL

A3 3 " - 1’-0"

JAMB DETAIL

3 " - 1’-0"

HEAD DETAIL

A4 3 " - 1’-0"

JAMB DETAIL

3 " - 1’-0"

HEAD DETAIL

2"

T

Y P

T

Y P

T

Y P

HOLLOW

METAL

FRAME

SEALANT, TYP

W

ID

T H

V A

R

IE

S

2"

T

Y P

METAL FLASHING

W/ DRIP EDGE

1 15/16"

T Y

P

4"

TYP

1 15/16"

METAL FLASHING

W/ DRIP EDGE

T Y

P

A1.1 A2.1 A3.1 A4.1

WIDTH TO MATCH

DOOR FRAME, UON

D O

IG

H T

2" DOOR WIDTH

F1 F2

D O

IG

H T

2" DOOR WIDTH

A B

6"

C D

INACTIVE LEAF

ACTIVE LEAF

6"

NOTE: INTERIOR HM DOOR FRAMES TO BE LEVEL 2

EXTERIOR HM DOOR FRAMES TO BE LEVEL 3 GALVANIZED

NOTE: INTERIOR HM DOOR FRAMES TO BE LEVEL 2

EXTERIOR HM DOOR FRAMES TO BE LEVEL 3 GALVANIZED

CARPET

VINYL

TRANSITION

REDUCER

CONCRETE

SLAB CARPET

4"

TYP.

VINYL TRANSITION

REDUCER

CONCRETE

SLAB

4" TYP AT GWB PARTITIONS UON

T Y

P

TYP

2"

WIRE GLASSWIRE GLASS

SEALANT & BACKER ROD ON

BOTH SIDES 3/8" TYP

SEALANT & BACKER ROD ON

BOTH SIDES 3/8" TYPSEALANT & BACKER ROD ON

BOTH SIDES 3/8" TYP

G L

K P

A K

HOLLOW METAL FRAME

HOLLOW METAL FRAME

HOLLOW METAL FRAME

THROUGH BOLT FRAME

ANCHOR

GROUT FILL,

HOLLOW METAL

FRAME

GROUT FILL,

HOLLOW METAL

FRAME

THROUGH BOLT FRAME

ANCHOR

GROUT FILL,

HOLLOW METAL

FRAME

D E

N D

"Z" SHAPED ANCHOR

WELDED TO FRAME

SUPPORT ANGLES

ATTACHED W/

EXPANSION BOLTS

*** Safety Pays ***

*** Support Value Engineering - It Pays ***

NEW YORK DISTRICT

A R

L

IN

G T

O N

V

IR

G

T E

L

F A

X

R

R

E

D w n b y

D e s ig n e d b y

R e v ie w e d b y

D a t e

R e v

C k d b b m it t e d b e n a m t d a t t s c a ie f

A r c h

B r a n

S L

A B s ig n f il e n a w in g c o d s c r ip t io n M a r k

A p p r

M a r k

D a t e

D a t e

A p p r

US Army Corps of Engineers

A

B

D

21 4 5

Sheet reference number:

2 4 51

C

N

T R

IC

T

N

T R

IC

T

J

U L

R K

N

S T

E

B O

R A

T O

R

S T

E

B O

R A

T O

R

8’0 4’ 16’

SCALE:1/8"=1’

A2 �" = 1’-0"

1S-111

IL

D

FOUNDATION AND SLAB PLAN - SOUTH

M A

T C

H L

IN

E

S E

E S

E E

S H

E E

T

S

SHEET NOTES

KEY NOTES

A.

B.

C.

D.

E.

SEE 0S-501 FOR TYPICAL CONCRETE

DETAILS.

SEE STRUCTURAL GENERAL NOTES ON

0S-001 AND 0S-002.

F.

A1

1S-501

T/ CONC EL = 0’-0"

ELEVATIONS STATED ON PLANS ARE

T/CONC SOG. SEE CIVIL FOR MEAN

SEA LEVEL ELEVATION.

A2

1S-501

TYP

TYP TYP

1’- 0"

1’- 0"

2 BAY FOR BRACED FRAME LOCATION

P2

P2

P3

P2

P2

A2

1S-501

A2

1S-501

HS

S

CO

L

HS

S

CO

L

PLACE FTG W/ MAT FDN

F2

P3

F2

T/ WALL FTG EL = [-4’-2"]

G. SEE 1S-131 FOR INFO FOR DESIGN OF

MECH PLATFORM; COLS A.4-3 & A.4-4.

7 STEPPED FTG, SEE A3/0S-501 FOR

DETAIL

A3

1S-501

3 3

A5

1S-501 8

REMOTE CONTROL STATION (RCS).

COORDINATE EXACT LOCATION OF EQUIP

SUPPORT STEEL W/ EQUIP INSTALLER.

LOCAL CONTROL STATION (LCS).

COORDINATE EXACT LOCATION OF EQUIP

SUPPORT STEEL W/ EQUIP INSTALLER.

C4

1S-515

H.

13 LCS & RCS EQUIP SEE C4/1S-515 FOR

STEEL SUPPORT DETAIL

TRENCH 2’-0" WIDE x 6" DEEP (MIN)

SLOPE BOT OF TRENCH TOWARDS EXT

WALL @ 0.5%. SEE B5/0S-502 FOR TYP

DETAIL. PROVIDE 1" x 3/16" STEEL BAR

GRATING W/ BEARING BARS SPACED @

1�" OC & CROSS BARS @ 4" OC TO

COVER TRENCH. PROVIDE OPENINGS IN

GRATING @ PIPE & CABLE

PENETRATIONS. COORD W/ PLUMB AND

EQUIP INSTALLER.

@ DOOR

A3

1S-501

@ DOOR

A5

1S-501@ DOOR

TOP OF EXT WALL FTG EL IS EQUAL TO

THE ADJACENT TOP OF EXT SPREAD

FTG. SEE 0S-601 FOR SIZE AND REINF.

ALL COLUMN PIERS ARE MARK P1 UON.

T/PIER EL IS 0’-0", TYP. SEE PIER

SCHEDULE ON 0S-601 FOR DETAILS AND

ANCHOR BOLT PLACEMENT.

PROVIDE FOR 30 GALLON WATER

HEATER TO BE HUNG FROM ROOF

BEAMS. COORD LOCATION W/ PLUMB.

14 SANITARY LINE. COORD W/ PLUMB FOR

INVERT. SLEEVE WALL, SEE DETAIL

A1/0S-501.

15 WATER LINE. COORD W/ FP FOR

INVERT. SLEEVE WALL, SEE DETAIL

A1/0S-501.

16 CONDUIT. COORD W/ ELEC & FP. SEE

A1/0S-501 FOR SLEEVE.

T/ WALL FTG EL = [-7’-6"]

KEY NOTES

STORM LINE. COORD W/ PLUMB FOR

INVERT. SLEEVE WALL, SEE DETAIL

A1/0S-501.

T/ WALL FTG EL = [-3’-9"] 20

6"

SLAB EDGE, TYP

WALL FTG, TYP

6"

6’-4" 12’-0"

9’-0"

OUTSIDE FACE OF

WALL, TYP

3’-3" 12’-8"

T/ WALL FTG EL = [-7’-1"] 21

T H

A

S E

2’-0"

T/ WALL FTG EL = [-5’-10"]. WALL

FTG SHALL BE 15" THK AND SHALL BE

REINF W/ 5-#5 EA WAY.

F O

U N

D A

T

IO

A N

B2

1S-512

SLAB-ON-GROUND IS 6" THICK

W/ #3 @ 18" OC, EW TOP.

CONTRACTION JOINT.

FOOTINGS DESIGNED FOR 2.5K DL AND

4.5K LL. COORD W/ PRE ENGR BLDG

MFR TO ENSURE SIZE IS ADEQUATE

PRIOR TO CONSTRUCTION.

12" THK MAT EQUIP FDN W/ #5 @ 12"

OC T & B. PAD TO RECEIVE SEARAM

SHIPPING SKID. T/CONC EL = 0’-0". SEE

C5/1S-501 FOR LOCATIONS OF 1" DIA

HILTI HY 150 INJECTION ADHESIVE

ANCHOR W/ 8�" EMBED LOCATIONS TO

BE INSTALLED AFTER SKID IS IN PLACE.

J

L

O P

E R

22 6" WIDE OPNG FOR TRENCH DRAIN.

COORD W/ PLUMB. SEE B5/0S-502 FOR

SLAB REINF.

12" THK MAT EQUIP FDN W/ #5 @ 12"

OC T & B

C1

1S-501

23 THKD SLAB AT LADDER. SEE

C5/0S-502.

7’-0"

12’-4"

12’-4"

24 2" SLAB DEPRESSION. SEE C3/0S-502

FOR DETAIL. SEE ARCH FOR LOCATION.

PROVIDE 3’-0" SQ OPNG IN SLAB FOR

OIL INTERCEPTOR. SEE A5/0S-501 FOR

ADDL INFO. COORD LOCATION AND 4’-3"

DEPTH OF HOLE W/ PLUMB AND MFR

REQMTS.

D E

N D

1’-4"

90’-0"

1’-9"

A B

C

1 2 3 5 6 7

A .4

22’-6" 22’-6" 22’-6" 22’-6"

*** Safety Pays ***

*** Support Value Engineering - It Pays ***

NEW YORK DISTRICT

A R

L

IN

G T

O N

V

IR

G

T E

L

F A

X

R

R

E

D w n b y

D e s ig n e d b y

R e v ie w e d b y

D a t e

R e v

C k d b b m it t e d b e n a m t d a t t s c a ie f

A r c h

B r a n

S L

A B s ig n f il e n a w in g c o d s c r ip t io n M a r k

A p p r

M a r k

D a t e

D a t e

A p p r

US Army Corps of Engineers

A

B

D

21 4 5

Sheet reference number:

2 4 51

C

N

T R

IC

T

N

T R

IC

T

J

U L

R K

N

S T

E

B O

R A

T O

R

S T

E

B O

R A

T O

R Y

N

BLDG

BLDG

Sheet of 195

2’ -6

2’ -6

5’ -0

2’ -6

2’ -6

C10X15.3

3’ -1 1"

2’ -6

3’ -1 1"

5’ -0

5’ -0

9’ -2 /8

9’ -2 /8

F4

F4

F2 F2 F2

F2F2F2

F1

F1

F1

F1

C

X .3

W10X33

W10X33

W

X

C10X15.3

C

X .3

W10X33

W10X33

A2

LOADER LEVEL FRAMING PLAN - NORTH

�" = 1’-0"

M A

T C

H L

IN

E

S E

E S

E E

S H

E E

T

S

1S-112

B U

IL

D

T/STL PL EL = 0’-0"

A.

B.

C.

SHEET NOTES KEY NOTES

DECK IS 3/8" METAL PLATE. SEE

GENERAL NOTES FOR ADDL INFO.

4 T/AREAWAY WALL, EL 1’-6"

SEE STRUCTURAL GENERAL NOTES

0S-001 AND 0S-002.

FRAMING MEMBERS BTWN COL

LINES ARE EQUALLY SPACED,

UON.

D.

ELEVATIONS STATED ON PLANS ARE

FIN FLR. SEE CIVIL FOR MEAN

SEA LEVEL ELEVATION.

B2

1S-512

A4

1S-512

A1

1S-211

B5

1S-512

A1

1S-210

0 4’ 8’ 12’

SCALE:3/16"=1’

CARRIER MOUNTING PL. SEE A1/1S-311

3 3 3

CHEVRON BRACING, SEE A1/1S-210

TYP

A1

1S-511

A3

1S-512

A1

1S-512

A2

1S-512

A4

1S-511

EL [-2’-0"]

TOC

0’-0"

TOC EL

SIDEWALK, SEE CIVIL.

9 MOMENT CONN TO BE DESIGNED FOR

FACTORED END MOMENT OF 30 FT-K

10 FOOTING STEP, SEE A3/0S-501

6 PLCS ALONG 11

TYP @

14 PLCS

TYP

@ DOOR

A3

1S-512

TYP @ 8 PLCS

ALONG 8

A1

1S-512

A2

1S-512

B5

1S-512

P5

P5

P5

P5

4’ -0

6’ -0

4’ -0

4’ -0

3’ -0

2’ -0

2’ -0

2’ -0

2’ -0

2’ -0

2’ -0

P4

TYP @ DOOR

TYP

T/ WALL FTG EL IS [-6’-0"]

T/ WALL FTG EL IS [-5’-8"]

14 DOMESTIC WATER LINE. COORD W/ PLUMB.

SEE A1/0S-501 FOR SLEEVE DETAIL.

SANITARY LINE, BELOW FTG. COORD W/

PLUMB. SEE A1/0S-501 FOR SLEEVE DETAIL.

15 COMPRESSED AIR PIPE. COORD W/ PLUMB.

SEE A1/0S-501 FOR SLEEVE DETAIL.

T H

A

S E

L L

2’ -6

1’- 0"

P4 0’ -8

P4 -1’ -0

P4 0’ -8

17 T/AREAWAY WALL, EL [-1’-0"]

B2

1S-512

C5x9 DOOR FRAME STEEL, SEE A4/1S-511

BRACED FRAME. SEE C1/1S-510 FOR ADDL

INFO.

18 6" CURB. SEE B5/1S-512

L O

A D

V

A M

A N

P4 -0 8"

P4 -0 8"

P4 -0 8"

P4 -0 8"

P4 -0 8"

P4 -0 8"

C2

1S-510

B1

1S-512

E. SEE DRAWINGS 1S-113 & 1S-114 FOR ADDL

INFO AT THE LOADER LEVEL.

F.

L L

COLUMNS SHALL SIT ON AREAWAY WALL W/

BASE PLATE BP4. SEE 0S-601 FOR ADDL

INFO FOR BASE PLATE AND ANCHOR BOLTS.

J

L

O P

E R

TYP @

EXP JT

JIB CRANE FDN. CRANE TO BE FOUNDATION

MOUNTED DURING WALL PLACEMENT. GC TO

COORDINATE W/ JIB CRANE SUPPLIER & FDN

SHOWN.

T/ PIER ELEVATION IS [-2’-0"], UON.

C3

1S-513

TYP,

11 PLCS

4" EQUIPMENT PAD. COORD W/ MECH, ELEC &

PLUMB FOR SIZE & LOCATION. SEE D5/0S-501

FOR ADDL INFO.

L

22 TYP DIMENSIONS FOR CHANNEL

FRAMING @ STAIR OPNGS.

W8x15, BM TO COL MOMENT CONN TO BE

DESIGNED FOR FACTORED END MOMENT OF 5

K-FT. MC TO BE PROVIDED AT COLUMNS ONLY.

C4

1S-513

TYP @ 8

PLCS

ALONG 8

PIER & FOUNDATION FOR STAIR POST.

COORD LOCATION W/ STAIR MFR.

2’ -0

P4 -0 8"

24 THICKENED SLAB @ STAIR LANDING.

COORD W/ SIDEWALK (CIVIL) AND STAIR

MFR. SEE C5/0S-502

A1

1S-512

6" THICK SOG W/ #3@18" OC, EW TOP. SEE

1S-113 FOR CONTRACTION JOINT LAYOUT.

PROVIDE FLOOR DRAINS, SEE PLUMB AND ARCH

FOR LOCATIONS.

STORM LINE. COORD SLEEVE IN WALL

W/ PLUMB & CIVIL.

25 PROVIDE WT4x9 VERT FRAMING FROM

STEEL PLATE DECK TO DECK FRAMING

ABOVE AT ELEC PANEL LOCATION.

COORD W/ ELEC.

1’-3"

1’-3"

5’-4" 1’-0"

9�"

9�"

FOR CONT OF

WALL FTG

SEE 1S-102

1’-7"

C OF EXP JT

1’-7"

C OF EXP JT

C CANOPY

COLS

1’-3" 5’-3"

10"

6 PLCS

ALONG 9

7’-6"

7’-8"

FOR CONT OF

WALL FTG

SEE 1S-102

26 PIT 2’-0"x2’-0"x2’-0" DEEP. SEE

DETAIL B5/0S-502. GRATING SHALL BE

1" x 3/16" STEEL BAR GALV W/

BEARING BARS SPA @ 1 3/16" OC AND

CROSS BARS @ 4" OC TO COVER

OPNG.

D E

N D

B .1

C C .1

7 8 9 9.3 9.4 9.6 9.7 10 11 1211.3 11.4 11.6 11.77.3 7.4 7.6 7.7

B .3

B .4

B .6

B .7

B

C .1

8’-0" 7’-10" 8’-0"7’-10"3’-9"3’-9" 4’-10" 7’-10" 7’-10"3’-9"3’-9" 4’-10"7’-10" 7’-10"3’-9"3’-9" 4’-10"

14’-5"

2’-7"

100’-0"

B .6

B .1

6’-1"

13.5

8’-8"

29’-2"

A A .5

A .9

*** Safety Pays ***

*** Support Value Engineering - It Pays ***

NEW YORK DISTRICT

A R

L

IN

G T

O N

V

IR

G

T E

L

F A

X

R

R

E

D w n b y

D e s ig n e d b y

R e v ie w e d b y

D a t e

R e v

C k d b b m it t e d b e n a m t d a t t s c a ie f

A r c h

B r a n

S L

A B s ig n f il e n a w in g c o d s c r ip t io n M a r k

A p p r

M a r k

D a t e

D a t e

A p p r

US Army Corps of Engineers

A

B

D

21 4 5

Sheet reference number:

2 4 51

C

N

T R

IC

T

N

T R

IC

T

J

U L

R K

N

S T

E

B O

R A

T O

R

S T

E

B O

R A

T O

R Y

N

BLDG

BLDG

Sheet of 195

W

X

C10X15.3C10X15.3

W

X

C10X15.3

W

X

C

X .3

C

X .3

W10X33

W10X33

C

X .3

C

X .3

C

X .3

C

X .3

C

X .3

C

X .3

W10X33

W10X33

C

X .3

C

X .3

C

X .3

C

X .3

C

X .3

C

X .3

C

X .3

C10X15.3

W

X

W

X8

W

X6

W

X6

W

X8

W

X6

W

X8

W12 X8

W12 X6

W12 X6

W12X87

W12X6

W12X6

W

X4

W

X4

W10 X4

W

X4

C10X15.3

W12X8

W

X6

W

X8

W

X6

W

X6

W

X8

W

X8

W

X6

W

X8

W

X8

W

X6

W

X6

W12X8

W12 X6

W12 X6

W

X4

W

X4

W

X4

W

X4

C10X15.3

W12 X8

W

X6

W

X8

W

X8

W

X6

W

X6

W

X8

W

X8

W

X6

W

X8

W12X87

W

X6

W

X6

W12 X8

W12 X6

W

X6

W

X4

W

X4

W10 X4

W

X4

W

X8

W

X6

W

X8

W10X33

W10X33

W10X33

W10X33

W10X33

W10X33

W

X3

W

X3

W

X3

W10X33

W10X33

W10X33

W10X33

W10X33

W10X33

W

X3

W

X3

HS

S4

X4 X3 /8

HSS

4X4

X3 /8

HS

S4

X4 X1 /4

HS

S4

X4 X1 /4

HS

S4

X4 X1 /4

HS

S4

X4 X1 /4

HS

S4

X4 X1 /4

HS

S4

X4 X1 /4

HS

S4

X4 X3 /8

HSS4X4X3/8

HS

S4

X4 X3 /8

HS

S4

X4 X3 /8

W

X8

C

X .3

F5 F5

F1

F4

F4

F5

F5 F5

F5 F5

F4

F1

F1

F5

W10X45

W

X

W

X

W

X

W10X33

W10X33

W

X

W

X

W

X

W

X

W

X

W10X33

W10X33

W

X

W

X

C

X .3

C10X15.3

C

X .3

W

X

W10X45

W

X

W

X

W10X33 W10X33

W10X33 W10X33

W10X33

W

X

W10X33

W

X

C

X .3

C10X15.3

W

X

W

X

W

X

W

X

W

X

C

X .3

C10X15.3

W

X

W10X45

W

X

W

X

W10X33 W10X33

W10X33 W10X33

W10X33

W

X

W10X33

W

X

W

X

W

X

W

X

C10X15.3

W

X

C

X .3

C

X .3

W10X45

W

X

W

X

W

X

W10X33

W10X33

W

X

W

X

W

X

W

X

W

X

W10X33

W10X33

W

X

W

X

C10X15.3

C

X .3

W

X

W10X45

W

X

W

X

W10X33

W10X33

W10X33 W10X33

W10X33

W

X

W10X33

W

X

W

X

W

X

W

X

C10X15.3

W

X

C

X .3

C

X .3

W10X45

W

X

W

X

W

X

W10X33

W10X33

W

X

W

X

W

X

W

X

W

X

W10X33

W10X33

W

X

C

X .3

C

X .3

C

X .3

C

X .3

C

X .3

C

X .3

C

X

.3

A

T C

H L

IN

E

S E

E S

E E

S H

E E

T

S

1S-113

B U

IL

D

T/STL PL EL = 0’-0"

A.

B.

SHEET NOTES KEY NOTES

SEE STRUCTURAL GENERAL NOTES

0S-001 AND 0S-002.

0 4’ 8’ 12’

SCALE:3/16"=1’

OPNGS AT LOADER LEVEL FRAMING PLAN - NORTH

3/16 " = 1’-0"

OPENING IS 19" NS x 9" EW3

OPENING IS 9" NS x 19" EW4

53113

1 1 1 3

OPENING IS 5’-3" x 5’-3"6

1’-11" 2’-5" 1’-10"

2’-5"

1’-11"

2’-6" 1’-11"

2’-1"

4’-0"

1’-11" 2’-5" 1’-10" 2’-5"

1 1 1 3

2’-1"

4’-0" 1’-11"

1’-11" 2’-6"

13 6 531

1’-11"2’-5" 1’-10"

4’-0"

2’-1"

1’-11"

1 365 3 1

2’-6" 1’-11"1’-11"

OPENING IS 5’-2" NS x 2’-11" EW

N

OPENING IS 3’-2" NS x 4’-0" EW

1’-11"

2’-11"

5’-6"

C. DIMENSIONS SHOWN ARE TO OPNG CL

S E

L

T H

A R

L O

A D

V

E N

IN

A N

OPENING IS 3�" DIA. COORD W/ MECH

FOR LOCATIONS.

11 CONTRACTION JOINT IN SOG, TYP.

D. SEE 1S-112 FOR FRAMING PLAN.

J

L

O P

E R

FOR DIRECTION OF OPENINGS, THE NORTH

DIRECTION IS STATED AS FOLLOW

1 1/2" DIA OPNG. COORD LOCATION W/

PLUMB.

OPNGS FOR BCCP WATERLINE & DISCHARGE

DRAIN. COORD W/ OWNER PROVIDED

EQUIPMENT & PLUMB FOR LOCATION & SIZE.

1’-11"1’-11"

OPENING IS 16" NS x 8" EW

OPENING IS 8" NS x 16" EW

OPENING IS 10" NS x 8" EW

OPENING IS 4" DIA. COORD W/ PLUMB FOR

LOCATION.

D E

N D

.1

C C .1

7 8 9 9.3 9.4 9.6 9.7 10 11 1211.3 11.4 11.6 11.77.3 7.4 7.6 7.7

B .3

B .4

B .6

B .7

B

C .1

8’-0" 7’-10" 8’-0"7’-10"3’-9"3’-9" 4’-10" 7’-10" 7’-10"3’-9"3’-9" 4’-10"7’-10" 7’-10"3’-9"3’-9" 4’-10"

14’-5"

2’-7"

100’-0"

B .6

B .1

6’-1"

13.5

8’-8"

29’-2"

A A .5

A .9

*** Safety Pays ***

*** Support Value Engineering - It Pays ***

NEW YORK DISTRICT

A R

L

IN

G T

O N

V

IR

G

T E

L

F A

X

R

R

E

D w n b y

D e s ig n e d b y

R e v ie w e d b y

D a t e

R e v

C k d b b m it t e d b e n a m t d a t t s c a ie f

A r c h

B r a n

S L

A B s ig n f il e n a w in g c o d s c r ip t io n M a r k

A p p r

M a r k

D a t e

D a t e

A p p r

US Army Corps of Engineers

A

B

D

21 4 5

Sheet reference number:

2 4 51

C

N

T R

IC

T

N

T R

IC

T

J

U L

R K

N

S T

E

B O

R A

T O

R

S T

E

B O

R A

T O

R Y

N

BLDG

BLDG

A

T C

H L

IN

E

S E

E S

E E

S H

E E

T

S

1S-114

B U

IL

D

T/STL PL EL = 0’-0"

A.

SHEET NOTES KEY NOTES

SEE STRUCTURAL GENERAL NOTES

0S-001 AND 0S-002.

0 4’ 8’ 12’

SCALE:3/16"=1’

3/16 " = 1’-0"

REMOTE CONTROL STATION (RCS). COORDINATE EXACT LOCATION

OF EQUIPMENT SUPPORT STEEL W/ EQUIP INSTALLER.

LOCAL CONTROL STATION (LCS). COORDINATE EXACT LOCATION

OF EQUIPMENT SUPPORT STEEL W/ EQUIP INSTALLER.

B1

1S-515

GUN CONTROL PANEL (GCP). COORDINATE EXACT LOCATION

OF EQUIPMENT SUPPORT STEEL W/ EQUIP INSTALLER.

A4

1S-515

4 SEE ELEVATION FOR WALL MOUNTED EQUIPMENT:

BARREL COOLING CONTROL PANEL (BCCP) &

ANTI-ICING JUNCTION BOX.

5 SLIPRING SUPPORT BRACKET.

C1

1S-515

C3

1S-515

A2

1S-515

A1

1S-515

B2

1S-515

1’-1" 1’-3"

1’-23 8"

1’-7"

1’-4" 1’-7"

EP1. COORDINATE EXACT LOCATION OF EQUIP

SUPPORT STEEL W/ EQUIP INSTALLER. SEE 1S-113

FOR LOCATION AND SIZE OF OPENING.

EP2. COORDINATE EXACT LOCATION OF EQUIP

SUPPORT STEEL W/ EQUIP INSTALLER. SEE 1S-113

FOR LOCATION & SIZE OF OPNG.

S E

L

T H

A R

L O

A D

V

Q

U

IP

M E

P P

O

A M

7"

5"

3"

A3

1S-515

B. SEE 1S-112 FOR FRAMING PLAN.

LOADER LEVEL EQUIPMENT SUPPORT FRAMING PLAN

J

L

O P

E R

LOWER ACCUMULATOR (LA). COORDINATE EXACT

LOCATION OF EQUIP SUPPORT STEEL W/ EQUIP INSTALLER.

CENTER LA OVER W10 BEAM BELOW.

9 9

4’-7"

1’-0"

PROVIDE (2) C6x8.2 BETWEEN COLUMNS TO SUPPORT ELEC

PANELS. COORD W/ ELEC MFR FOR ELEVATIONS. WELD

BOTH ENDS OF C6 TO INSIDE OF COL FLANGE W/ 1/4"

FILLET ALL AROUND OR PROVIDE (2) 3/4" DIA BOLTS W/ 1/4"

SHEAR PL

WT4 (SEE 1S-112 FOR SIZE) VERT MEMBER.

GRIND SMOOTH DECK TO RECEIVE 1/4" WELD

ALL AROUND @ BASE. USE VERT SLIP CONN

@ TOP OF WT4 TO UNDERSIDE OF W8.

D E

N D

.1

C C .1

7 8 9 9.3 9.4 9.6 9.7 10 11 1211.3 11.4 11.6 11.77.3 7.4 7.6 7.7

B .3

B .4

B .6

B .7

B

C .1

8’-0" 7’-10" 8’-0"7’-10"3’-9"3’-9" 4’-10" 7’-10" 7’-10"3’-9"3’-9" 4’-10"7’-10" 7’-10"3’-9"3’-9" 4’-10"

14’-5"

2’-7"

100’-0"

B .6

B .1

6’-1"

13.5

8’-8"

29’-2"

A A .5

A .9

*** Safety Pays ***

*** Support Value Engineering - It Pays ***

NEW YORK DISTRICT

A R

L

IN

G T

O N

V

IR

G

T E

L

F A

X

R

R

E

D w n b y

D e s ig n e d b y

R e v ie w e d b y

D a t e

R e v

C k d b b m it t e d b e n a m t d a t t s c a ie f

A r c h

B r a n

S L

A B s ig n f il e n a w in g c o d s c r ip t io n M a r k

A p p r

M a r k

D a t e

D a t e

A p p r

US Army Corps of Engineers

A

B

D

21 4 5

Sheet reference number:

2 4 51

C

N

T R

IC

T

N

T R

IC

T

J

U L

R K

N

S T

E

B O

R A

T O

R

S T

E

B O

R A

T O

R Y

N

BLDG

BLDG

B.4

B.6

7.6

L

L

OPEN

A1 A3

SECTION

A3

1S-311

1S-311

CARRIER MOUNTING PLATE PLAN

1’ 2’0 6"

SCALE:1-1/2"=1’

1 1/2" = 1’-0" 1 1/2" = 1’-0"

2" 2’-

4"

1 8

D

IA

2"

W10 BEAM, SEE PLAN

5’- 4"

W10x45

W10x45

W10x45

W10x45

OPEN

C A

R R

IE

U N

T

A

A N

3/8" PLATE

3/8" PLATE

B3 1 1/2" = 1’-0"

B3

1S-311

SECTION - TYP 7 PLCS

1/4

W10 BEAM, SEE PLAN

W10 BEAM, SEE PLAN

W10 BEAM, SEE PLAN

W10 BEAM, SEE PLAN

C MOUNTL

EDGE OF PL ON THE C

OF BEAM, TYP ALL SIDES

L

EDGE OF PLATE @ BM CL

3/8" PLATE

B U

IL

D

S E

L

T H

A R

NOTE: ALL W10x45 RADIAL BEAMS SHALL BE WELDED AT JOINTS

W/ BEAMS & CIRCULAR ROLLED PLATES. WEB & FLANGE JOINTS

SHALL BE 1/4" FILLET WELDED ALONG LENGTH OF CONNECTION.

J

L

O P

E R

1’-8

" IN

SID

E D

IA

E Q

SURFACE B

A.

SHEET NOTES

CENTERLINES OF 1’-8" DIA HOLE

AND 3’-0" DIA MACHINED AREA

(SURFACE B) SHALL BE LOCATED

WITH RESPECT TO THE

VERTICAL CENTERLINE OF THE

MOUNT ABOVE TO THE

DIMENSIONS SHOWN +/- 0.25".

B.

C.

C3

SECTION

1 1/2" = 1’-0"

SURFACE B

SURFACE A

(SEE 1S-312)

.9

.0

SEE NOTE C

C3

1S-311

C MOUNT ABOVE

U

O V

E

3’-0" DIA (SURFACE B)

2" PLATE

ADJUST THE ELEVATION OF THE

2" PLATE BY SHIMMING BETWEEN

THE PLATE AND THE SUPPORT

STRUCTURE PRIOR TO WELDING.

FINAL ELEVATION TO BE

DETERMINED SUCH THAT

SURFACE B CAN BE ACHIEVED

TO THE DIMENSION SHOWN.

SHIIMS SHALL BE POSITIONED

NEXT TO EACH OTHER WITH NO

GAPS.

NOTE: AT TURRETS 1 & 2, PROVIDE REMOVABLE 1/4"

PLATE TO COVER OPENING. OVERLAP OPNG BY 1" FOR

BOLTED ATTACHMENT. NO MACHINING OF SURFACE B

REQUIRED AT TURRETS 1 &2.

D E

N D

MACHINE "SURFACE B & C"

(LOADER FOUNDATION AND

FOUNDATIONS

FOR LOWER HOIST DRIVE, HOIST

TUBE AND STRIKEDOWN TUBE)

IN THE SAME PLANE ON LOADER

PLATE. THESE FOUNDATION

SURFACES MUST HAVE A 125

FINISH AND BE PARALLEL TO THE

STAND FOUNDATION SURFACE

WITHIN 0.002" IN 12". MINIMUM

BEARING AREA OF 50 PERCENT.

NONBEARING AREAS IN ANY

60 DEGREE SECTOR SHALL BE

LIMITED TO A MAXIMUM OF 10

PERCENT OF TOTAL FOUNDATION

BEARING AREA.

KEY NOTES

2 GRAPHIC REPRESENTATION OF

THE FOUNDATIONS FOR THE

LOWER HOIST DRIVE, HOIST

TUBE AND STRIKEDOWN TUBE.

SURFACE C. SURFACE C DEFINES

AREA REQUIRING MACHINING FOR

TURRET 3 ONLY. COORDINATE

EXACT EXTENT WITH EQUIPMENT

INSTALLER.

2’-5 2"

1 8

2’-5

8" DIA

3/8" OUTSIDE

PLATE

W10 BEAM,

SEE PLAN

3"x5/8" PLATE (T & B)

W10 BEAM

T/ STL PL LOADER LVL

EL SEE PLAN

T/ STL PL LOADER LVL

EL SEE PLAN

W10 BEAM BEYOND,

SEE PLAN

2’-11

8" OUTSIDE DIA

1’-8" INSIDE DIA

1 8

O U T S

ID

E

D

IA

E Q

3’-0" DIA (SURFACE B)

PL 2"x5’-0�"x6’-5�"

2" PLATE

*** Safety Pays ***

*** Support Value Engineering - It Pays ***

NEW YORK DISTRICT

A R

L

IN

G T

O N

V

IR

G

T E

L

F A

X

R

R

E

D w n b y

D e s ig n e d b y

R e v ie w e d b y

D a t e

R e v

C k d b b m it t e d b e n a m t d a t t s c a ie f

A r c h

B r a n

S L

A B s ig n f il e n a w in g c o d s c r ip t io n M a r k

A p p r

M a r k

D a t e

D a t e

A p p r

US Army Corps of Engineers

A

B

D

21 4 5

Sheet reference number:

2 4 51

C

N

T R

IC

T

N

T R

IC

T

J

U L

R K

N

S T

E

B O

R A

T O

R

S T

E

B O

R A

T O

R Y

4"

7.3 7.4 7.6 7.7

B.3

B.4

B.6

B.7

U N

T L

C MOUNT

L

1S-312

A1 1" = 1’-0"

A51S-312

A5

SECTION

1" = 1’-0"

B5

1S-312

B5

C MOUNTL

U N

T L

B4

1S-312

B4

SECTION

2" = 1’-0"

2" = 1’-0"

TOP LOADER RING AND PLATE DETAIL

2’0

SCALE:2"=1’-0"

1’

3’-9"

2’-5"

4’-10" 3’-9"

1�" PLATE

(RING)

4" TYP

1/2" PLATE

3’-5�" REF

W18 BEAM, SEE PLAN,

TYP

1/2" PL

1�" PL

NOTE: TOP PL OMITTED

FOR CLARITY

T/STL PL @ DECK LVL

EL SEE PLAN

1/4

CONT

PLAN DETAIL

D

S E

L

T H

A R

B U

IL

D

T

A D

A

A N

NOTE: AT TURRETS 1 & 2, ADAPTER PLATES SHALL BE PLACED

ON LOADER RING FOR VARIOUS GUNMOUNTS TO COVER OPNGS. SEE

1S-313 FOR ADAPTER PLATE FOR TURRET 1. ADAPTER PLATE FOR

TURRET 2 SHALL BE PROVIDED BY OWNER.

INSIDE DIA

OUTSIDE DIA

8’ -5

OUTS

IDE

DIA

IN

S

ID

J

L

O P

E R

2’0 1’

SCALE:1"=1’-0"

SURFACE A

SURFACE A

IS

H E

D

T H

IC

K N

E S

S

S

T E

B.

A.

SHEET NOTES

2’-2 2" 1’-0"

4"

OPNG IN STEEL DECK

AT TURRET #1 ONLY

OPNG IN STEEL DECK

AT TURRET #1 ONLY

1’-5"

D E

N D

CONTRACTOR SHALL DETERMINE THE INITIAL THICKNESS REQUIRED TO PROVIDE ADEQUATE MACHINING ALLOWANCE SO

THAT FINAL MINIMUM THICKNESS IS ACHIEVED.

STAND FOUNDATION "SURFACE A" MUST BE LEVEL WITH RESPECT TO GRAVITY WITHIN 3 MINUTES OF ANGLE WITH A SURFACE FINISH OF 125 AND A MINIMUM BEARING AREA OF 75 PERCENT. NONBEARING AREAS IN ANY 60 DEGREE SECTOR SHALL BE LIMITED TO A MAXIMUM OF 5 PERCENT OF THE TOTAL FOUNDATION BEARING AREA.

C. MACHINING OF SURFACE A IS REQUIRED FOR ALL TURRETS.

W12 COL, SEE PLAN

1/2" PLATE

3/4" PLATE

1/2" PLATE

4"

4"1’-10�"

6"11"

STAND

MOUNTING

SURFACE

*** Safety Pays ***

*** Support Value Engineering - It Pays ***

NEW YORK DISTRICT

A R

L

IN

G T

O N

V

IR

G

T E

L

F A

X

R

R

E

D w n b y

D e s ig n e d b y

R e v ie w e d b y

D a t e

R e v

C k d b b m it t e d b e n a m t d a t t s c a ie f

A r c h

B r a n

S L

A B s ig n f il e n a w in g c o d s c r ip t io n M a r k

A p p r

M a r k

D a t e

D a t e

A p p r

US Army Corps of Engineers

A

B

D

21 4 5

Sheet reference number:

2 4 51

C

N

T R

IC

T

N

T R

IC

T

J

U L

R K

N

S T

E

B O

R A

T O

R

S T

E

B O

R A

T O

R Y

7.3 7.7

B.3

B.7

U N

T L

C MOUNT

L

1S-313

A1 1" = 1’-0"

C

IW

A P

T

A

A N

B4

1S-513

CIWS ADAPTER PLATE PLAN

3’-11 2"

M C x .8

C x .2

C x .2

M C x

.8

MC13x31.8

MC13x31.8

C6x8.2

C6x8.2

M C x .8

B1

1S-513

11" 4’-0"

11"2’-1"

B U

IL

D

S E

L

T H

A R

T/ ADAPTER PL & T/ OF GRATING EL 9’-4�"

A.

SHEET NOTES

KEY NOTES

B.

J

L

O P

E R

10’-10"

1 TYP

CONTRACTOR SHALL DETERMINE THE

INITIAL THICKNESS REQUIRED TO

PROVIDE ADEQUATE MACHINING

ALLOWANCE SO THAT FINAL MINIMUM

THICKNESS IS ACHIEVED.

3" MINIMUM

THICKNESS OF

CIWS ADAPTER

PLATE

1 3/16" DIA BOLT HOLES FOR 1"

DIA BOLTS FOR ATTACHMENT OF

THE SHIPPING SKID TO THE

ADAPTER RING. BOLTS SHALL BE

SUPPLIED AND INSTALLED BY

OWNER DURING GUN INSTALLATION.

2"

10" 2’-1" 1’-3" 5’-0" 1’-3"

3 HSS BELOW. SEE B1/1S-513 FOR

ADDL INFO.

4 MAINTENANCE RAIL FOR SUPPORT

OF THE COMPONENT REMOVAL

EXTENSION SET (CRES).

7’-11"

7’-11"

M C x .8

M C x

.8

3’-7

2"

3"

3"

GRATING SHALL BE REMOVABLE IN

THIS LOCATION.

4’-7"

C4

1S-501

2"

2"

C4

1S-501

2"

3’-1 2"

2’-2"

2"

GRATING SHALL BE 1 1/2" x 3/16"

GALV STEEL W/ BEARING BARS

SPACED AT 1 3/16" OC AND

CROSS BARS SPACED AT 4" OC.

MC13x31.8

M C x

.8

MC13x31.8

10" 1’-4�"

2"

TOP SURFACE OF PLATE SHALL BE

LEVEL WITH RESPECT TO GRAVITY

WITHIN 3 MINUTES OF ANGLE WITH

A SURFACE FINISH OF 125 AND A

MINIMUM BEARING AREA OF 75

PERCENT. NONBEARING AREAS IN

ANY 60 DEGREE SECTOR SHALL BE

LIMITED TO A MAXIMUM OF 5

PERCENT OF THE TOTAL

FOUNDATION BEARING AREA. THE

BOTTOM SURFACE OF THE

ADAPTER PLATE MUST BE

MACHINED TO THE SAME FLATNESS

REQUIREMENT AS SURFACE A (ON

1S-312).

A D

D E

N D

*** Safety Pays ***

*** Support Value Engineering - It Pays ***

NEW YORK DISTRICT

A R

L

IN

G T

O N

V

IR

G

T E

L

F A

X

R

R

E

D w n b y

D e s ig n e d b y

R e v ie w e d b y

D a t e

R e v

C k d b b m it t e d b e n a m t d a t t s c a ie f

A r c h

B r a n

S L

A B s ig n f il e n a w in g c o d s c r ip t io n M a r k

A p p r

M a r k

D a t e

D a t e

A p p r

US Army Corps of Engineers

A

B

D

21 4 5

Sheet reference number:

2 4 51

C

N

T R

IC

T

N

T R

IC

T

J

U L

R K

N

S T

E

B O

R A

T O

R

S T

E

B O

R A

T O

R Y

L

IN

G T

O N

V

IR

G

T E

L

F A

X

R

R

E

D w n b y

D e s ig n e d b y

R e v ie w e d b y

D a t e

R e v

C k d b b m it t e d b e n a m t d a t t s c a ie f

A r c h

B r a n

S L

A B s ig n f il e n a w in g c o d s c r ip t io n M a r k

*** Safety Pays ***

*** Support Value Engineering - It Pays ***

A p p r

M a r k

D a t e

D a t e

A p p r

US Army Corps of Engineers

A

B

D

21 4 5

Sheet reference number:

2 4 51

C

NEW YORK DISTRICT

N

T R

IC

T

N

T R

IC

T

J

U L

R K

N

S T

E

B O

R A

T O

R

S T

E

B O

R A

T O

R Y

N

BLDG

BLDG

Sheet of 195

6 8 10 12

B .1

C .1

C

7 9 11

B

B .6

.1

.1

CORRIDOR

MECH

EMERG

SHOWER

ELEC

LOADER ROOM 1

LOADER ROOM 3

LOADER ROOM 2

OFFICE

8’0 4’ 16’

SCALE:1/8"=1’

M A

T C

H L

IN

E

S E

E S

E E

P

SHEET NOTES

KEY NOTES

D N

A.

1P-111

A1 SCALE = �" = 1’-0"

1" AIR 1" AIR

1" AIR

2" CW

2" AIR1" AIR

GAS METER

4 4 4

2" CW

77 7

AIR DRYER LOCATED ON WALL.

2" AIR

FOR GENERAL NOTES, SYMBOLS AND

ABBREVIATIONS REFER TO SHEET P-001.

1" AIR

UP & DN

1" AIR

UP & DN

1" AIR

UP & DN

2"

1�" GAS TO

BOILER (TYP.

OF 2)

1�"

INCOMING GAS LINE

1�" 1�"

1�"

GCO-1

3"FS-1

3"FS-1

3"FS-1

3"FS-1

3"FS-1

10 10

1" AIR

INSTALL ALL PIPING SYSTEM CONCEALED

IN WALL AND CEILING SPACES/OR CLOSE

TO STRUCTURAL ELEMENTS. UNLESS

OTHERWISE INDICATED.

B.

C.ALL PIPING SYSTEM SHALL BE

COORDINATED WITH OTHER TRADES

PRIOR TO INSTALLATION.

D.ALL PIPING SHALL BE SUPPORTED IN SUCH

MANNER AS TO ELIMINATE SWAY AND

VIBRATIONS.

2"

3"

3"

3"

6"

3" BACKFLOW

PREVENTER

3" INCOMING WATER

SERVICE LINE

6" SANITARY WASTE 13

2" VENT TROUGH THE WALL

3"3"

2"CW

AIR COMPRESSOR

AND TANK (AC-1)

15 ETP-1, ELECTRONIC TRAP PRIMER

GAS SHUT- OFF VALVE & REGULATOR

WITH VENT TROUGH THE WALL (TYP)

16 BACKWATER VALVE

AIR PRESSURE REDUCING VALVE ABOVE

G T

B L

H

F.F.E. 0.00’ F.F.E. -2.00’

NFWH-1

NFWH-1

2"PD

2"PD

2"V

1"

1"

2"V

2" VENT FROM BELOW

2"DP, DISCHARGE PUMP FROM BELOW

1" CW SUPPLY FROM BELOW

B.C.C.P. BY OTHERS

INCOMING DOMESTIC WATER LINE. 2’-6" MIN. BELOW

FINISHED GRADE. SEE CIVIL DRAWINGS FOR

CONTINUATION.

GAS LINE. SEE CIVIL DRAWINGS FOR CONTINUATION.

HVAC EQUIPMENT. REFER TO MECHANICAL DRAWINGS

FOR DETAILS.

COMPRESSED AIR LINE DOWN TO SUPPLY WEAPON

SYSTEM IN LOADER ROOMS.

1�"COMPRESSED AIR PIPE DOWN TO BELOW SLAB.

�" WATER LINE DOWN SUPPLY TO WATER TANK

1" COMPRESSED AIR LINES TERMINALS WITH QUICK

DISCONNECTS AND EMERGENCY SHUT- OFF VALVES

6" SANITARY WASTE. FOR CONT. SEE CIVIL DRAWINGS.

2" (PD) SUMP PUMP DISCHARGE SHALL BE INSTALLED

BELOW FLOOR SLAB AND CONNECTED TO 4" SANITARY

LINE. PROVIDE A BACKWATER VALVE BEFORE CONNECTION.

1" CW SHALL RUN ABOVE TIGHT TO STRUCTURE.

1"CW DOWN TO BARREL COOLING CONTROL PANEL.

PROVIDE FLEXIBLE PIPES TO CONNECTION, USE PANEL

FITTINGS BETWEEN FLEXIBLE PIPES AND THE PANEL.

2" VENT PIPE FROM SUMP PUMP PIT SHALL RUN ABOVE

TIGHT TO THE STRUCTURE OF LOADER LEVEL THROUGH

THE WALL, TERMINATE THE PIPE OPENING DOWN.

PLUMBING- BLDG 3349 LOADER LEVEL- PARTIAL FLOOR PLAN

23 1�" B.C.C.P. DRAIN LINE DOWN TO SPILL ON FLOOR DRAIN

LOCATED ON MAGAZINE ROOM 2, MAGAZINE LEVEL.

P L

U M

B

IN

G B

U

IL

D

L

O A

D

V E

L P

A R

T

O

24 FLEXIBLE HOSE ASSEMBLY FOR WATER SUPPLY FROM

B.C.C.P. TO THE GUN. FOR CONNECTIONS MUST BE USED

THE ASSEMBLY FITTINGS ( TO BE SUPPLIED BY OTHERS)

25 DRAIN LINE FROM THE GUN SHALL BE DIRECTED TO

FLOOR DRAIN LOCATED BELOW FLOOR IN MAGAZINE

ROOM 2. UNLESS OTHERWISE INDICATED.

WATER METER REMOTE READER ON EXTERIOR WALL.

1�" COMPRESSED AIR PIPE BELOW GRADE

FOR CONTINUATION REFER TO CIVIL

DRAWINGS.

1�" HIGHER PRESSURE AIR (175 PSIG) LINE UP TO

SUPPLY MK-45 EQUIPMENT. (100 cfm)

1" MAKE-UP WATER TO

MECHANICAL EQUIPMENT

3" REDUCED PRESSURE ZONE BACK FLOW PREVENTER

SHALL BE INSTALLED AT 24" HEIGHT FROM THE F.F.E.

1�" CW

3"FS-1

3" WASTE DOWN AND 2" VENT UP.

THE TEMPERED WATER BLENDING SYSTEM, FULLY

ASSEMBLY

EMERGENCY SHOWER EYEWASH ASSEMBLY

2"V UP & DOWN

27 2’X2’ PIT WITH AUTOMATIC FLOAT DRAIN VALVE INSTALLED

AT THE BASE OF COMPRESSED AIR PIPING; PROVIDE �"

SINK.

FLEXIBLE HOSE TO DISCHARGE WATER OVER THE FLOOR

A D

D E

N D

J

U L

THROUGH AUTOMATIC FLOAT DRAIN VALVE.

2" WATER METER WITH REMOTE READER

T C

H L

IN

E

S E

E S

E E

P

8’0 4’ 16’

SCALE:1/8"=1’

SHEET NOTES

D N

B L

H

1P-112

A1

6" SANITARY PIPING

BELOW GRADE

FOR CONTINUATION

SEE CIVIL DRAWING.

GCO-1

3"FS-1

4"FS-1

3"FS-1

3"FS-1

4"

6"

4"

4"

4"

4"

4"

3"

2"

1/2"

1"AIR

1"AIR

1"AIR1"AIR

1"AIR1"AIR

1"AIR

A.

FOR GENERAL NOTES, SYMBOLS AND

ABBREVIATIONS REFER TO SHEET P-001.

INSTALL ALL PIPING SYSTEM CONCEALED

IN WALL AND CEILING SPACES/OR CLOSE

TO STRUCTURAL ELEMENTS. UNLESS

OTHERWISE INDICATED.

B.

C.ALL PIPING SYSTEM SHALL BE

COORDINATED WITH OTHER TRADES

PRIOR TO INSTALLATION.

D.ALL PIPING SHALL BE SUPPORTED IN SUCH

MANNER AS TO ELIMINATE SWAY AND

VIBRATIONS.

OIL INTERCEPTOR FOR SERVICE AREAS

WALL HUNG ELECTRIC WATER HEATER.

(EWH-1).

2"

1" AIR

2"CW

3"

SCALE = 1/8 " = 1’-0"

2"V

FCO-1

3" FD-1

TPY.

P-2 P-1P-1P-2 P-6

1/2" P-3

P-5 P-4

RECESS TRENCH DRAIN

F.F.E. 0.00’

NFWH-1

NFWH-1

PLUMBING - BLDG,-3349 LOADER LEVEL PARTIAL FLOOR PLAN

P L

U M

B

IN

G B

U

IL

D

L

O A

D

V E

L P

A R

T

O

2" VENT

THROUGH

THE WALL AT

(10’ HEIGHT)

3/4"

3/4"

3/4"

3/4"

4"FS-1

FCO-1

4"

3"

3"

1" COMPRESSED AIR LINE UP.

1" COMPRESSED AIR LINE ABOVE CLOSE

TO STRUCTURE ELEMENTS.

TRENCH 2’ WIDE X 6" DEEP, SLOPE

FORWARD EXTERIOR WALL .5%. SEE

STRUCTURAL DRAWING FOR DETAILS.

1" COMPRESSED AIR TERMINALS LINE DOWN

TO 5’ HIGH FROM FLOOR. PROVIDE

QUICK DISCONNECT AND SHUT- OFF

VALVES.

A D

D E

N D

J

U L

A R

L

IN

G T

O N

V

IR

G

T E

L

F A

X

R

R

E

D w n b y

D e s ig n e d b y

R e v ie w e d b y

D a t e

R e v

C k d b b m it t e d b e n a m t d a t t s c a ie f

A r c h

B r a n

S L

A B s ig n f il e n a w in g c o d s c r ip t io n M a r k

*** Safety Pays ***

*** Support Value Engineering - It Pays ***

A p p r

M a r k

D a t e

D a t e

A p p r

US Army Corps of Engineers

A

B

D

21 4 5

Sheet reference number:

2 4 51

C

NEW YORK DISTRICT

N

T R

IC

T

N

T R

IC

T

J

U L

R K

N

S T

E

B O

R A

T O

R

S T

E

B O

R A

T O

R Y

N

BLDG

BLDG

Sheet of 195

A B

C

1 2 3 5 6 7

A .4

WORKROOM

COPY/WORKROOM

BREAK 136

JC

TOILET/SHOWER

TOILET

TR

GUN WORKROOM

LOCATIONSYMBOL DESCRIPTION

4"/4" 100

MINIMUM

VOLUME

(GALLONS)

CONNECTION

SIZES

INLET/OUTLET

CAPACITY

FLOW

(GPM)

OIL-WATER SEPARATOR 100GUN WORKRM.

REMARKSPHASEGPM

TDH

VOLTS HERTZ

(FEET)

RPM

90 20 1750 208 60

LOCATION HPSYMBOL

1SP-1 1

DUPLEX SUMP PUMP SCHEDULE

SERVICE

FOUNDATION; AREA DRAINS & WATER TANK WATER TANK RM.

30 20 3600 208 601WATER TANK RM.

40 20 3500 208 601WP-1 WATER TANK RM.BARRIL COOLING CONTROL PANEL

AMTROL,BASE MOUNTED 1X1

4X5 GTU. END

SUCTION CENTRIFUGAL PUMP.

1.5

SEP-1 FLOOR DRAINS & FLOOR SINK .5 STANCOR DUPLEX OIL MINDER SYSTEM MODEL

SE-100-OM

DUPLEX BELOW GRADE; WEIL MODEL No. 1413

P-701

WHA-1

WHA-2

SYMBOL

FIXTURE UNIT

RATING

1 - 11

12 - 32

1/2"

3/4"

MODEL NO. REMARKS

2"61 - 113WHA-3

SERIES NO.75000

SERIES NO.75002

SERIES NO.75004

CONNECTION SIZE

TO SUPPLY PIPE KNOWN ACCEPTABLE SOURCE

PRECISION PLUMBING

PRODUCT (PPP inc)

PRECISION PLUMBING

PRODUCT (PPP inc)

PRECISION PLUMBING

PRODUCT (PPP inc)

WATER HAMMER ARRESTER SCHEDULE

WALL RECESS TYPE

STAINLESS STEEL WITH GARBAGE DISPOSER

MOP SINK (CORNER TYPE BASIN)

WITH VACUUM BREAKER AND KEY

ACCESS PANEL

LOCATED INSIDE TOILET RM PIPE CHASE WITH

NON FREEZE (EXTERIOR) KEY TYPE WITH

VACUUM BREAKER

PRESSURE ASSISTED TANK, 1.0 GPF, ELONGATED BOWL,

ADA HEIGHT, VITREOUS CHINA, FLOOR MOUNTED.

VITREOUS CHINA, WITH REAR OVERFLOW AND 4" CENTER

FAUCET HOLES. PROVIDED FOR CONCEALED ARMS.

WITH INSTANT TANKLESS ELECTRIC WATER HEATER

FLOOR DRAIN, ADJUSTABLE SHOWEER HEAD 2.5 GPM

BARRIER FREE SINGLE TYPE. WALL MOUNTED

MOTOR ELECTRICAL DATA

FS-1 FLOOR SINK

SERVICE DESCRIPTION AND OPTIONS

FD-1 FLOOR DRAIN

WASTE TRAP VENT

JOSAM SERIES 49000

SYMBOL

WITH DEEP SEAL TRAP, SEDIMENT BUCKET & ACID RESISTING GRATE AND BODY

KNOWN ACCEPTABLE SOURCE

DRAIN SCHEDULE

3" OR 4" 3" OR 4"

3" OR 4" 3" OR 4"

2"

2"

AREA DRAIN 3" OR 4" -AD-1 BODY W/STRAINER, CLAMP DEVICEJOSAM SERIES 30200-AD

JOSAM SERIES 30000-A

-TD-1 TRENCH DRAIN 4"

- JOSAM SERIES 76000 6" WIDE, RECTANGULAR, MODULAR

SHOWER DRAIN, WITH TRAP PRIMER IN TOILET ROOMS, DRAINS IN MAGAZINE RMS.

WITH ROUND FANNELS SERIES F52&F53

CONN. SIZE PRESS. DROP

(PSI)(GPM)

WATTS SERIES 909

MODEL NO. REMARK

103"

MAX. FLOW RATE

LOCATION

MECHANICAL ROOM

REDUCED PRESSURE PRINCIPLE TYPE-CAST IRON

KNOWN ACCEPTABLE SOURCE

FIRST FLOOR MAIN

BACKFLOW PREVENTER SCHEDULE

OIL INTERCEPTOR AND SEPARATOR SCHEDULE

OWS-1

WATTS SERIES 90910 REDUCED PRESSURE PRINCIPLE TYPE-CAST IRON 100

WAREHOUSE

AREA

2 1/2"

REMARKS

KISTNER CONCRETE PRODUCTS INC. OS-OS100

WASTE VENT CW HW

HB-1

4" 2"

SYMBOL

3"

WALL HYDRANT

HOSE BIBB

REMARKSTRAPDESCRIPTION

1/2"1/2"1 1/2"1 1/2"

1/2"1/2"1 1/2"

3/4"

1/2"

ETP-1 ELECTRONIC TRAP PRIMER 3/4"

P-5 1 1/2" 1 1/2" 1/2"ELEC. WATER COOLER

P-1

NFWH-1

1/2"1/2"1 1/2"1 1/2"

MOP SINK

KITCHEN SINK (Single Comp.)

INTERNAL

3/4"ATP-1 AUTOMATIC TRAP PRIMER

P-4

P-3

P-2 1 1/2"

1 1/2"

3"

1 1/2"

PLUMBING FIXTURE CONNECTION SCHEDULE

LOCATION

VOLTS PHASEHERTZ

NOMINAL ENT.

STORAGE

(GALS)

WATER

DEG. F

LVG

WATER

DEG. F

SYMBOL

JANITOR CLOSED 20 208

REMARK

EWH-2

RECOVERY GPM

@ 56 RISE

ELECTRIC WATER HEATER SCHEDULE

REMARKS

AC-1

LOCATIONSYMBOL

FIRST FLOOR

DESIGN BASIC

MAKE AND MODEL TYPE

CAPACITY

acfm

WORKING

PRESSURE

PSIG

175 3600

MOTOR

SPEED

RPM VOLTS PHASEHERTZHP

MOTOR ELECTRICAL DATA

30 208 60 3

RPM FLA

94.1

MOTOR

EFFICIENCY

RATING

DISCH.

CONN.

(INCH)

2 NPT

DIMENSION (INCHES)

62"L X 35"W X 37"H

WEIGHT

(LBS)

RECEIVER

CAPACITY

3. MANUFACTURER SHALL SELECT COMPARABLE AIR DRYER.

AIR COMPRESSOR SCHEDULE

WATER CLOSET (ADA) (FT)

NOTES: 1. STAINLESS STEEL CONTROL TUBING. 2. UNIT WITH LOW NOISE LEVEL SOUND ATTENUATING ENCLOSURE.

EWS-1 EMERGENCY EYEWASH/SHOWER 1 1/4"

1/2"

LAVATORY (ADA WALL HUNG)

40 360JANITOR CLOSET 30 208EWH-1 12 120

GARDNER DENVER MODEL

EBE99Q MODULATED CONTROL

ELECTRA-SAVER II

ROTARY SCREW AIR

COMPRESSOR

120 GALLONS ASME

CODED AIR RECEIVER

(TANK MOUNT ONLY)

PROVIDE WITH HOUSEKEEPING PAD; COMPRESSOR WITH SOUND ENCLOSURE;

HORIZONTAL RECEIVER PACKAGE INCLUDES PRESSURE GAUGE, SAFETY RELIEF

VALVE, BALL VALVE AND ELECTRONIC DRAIN VALVE.

P-6 1 1/2" 1/2"SHOWER 2" 2 1/2"

40 360208EWH-3 85EMERG.SH.RM

12 120 LOCHINVAR MODEL No. JRK020H, MOUNTED ON PLATFORM

LOCHINVAR MODEL No. JRK031H, MOUNTED ON PLATFORM

REMARKS

WT-1

LOCATIONSYMBOL

DESIGN BASIC

MAKE AND MODEL TYPE

DIAM.

45 28

WATER TANK SCHEDULE

WATER TANK

ROOM

HASON WATER TANKS, EXPOLY

LINING #0291

VERTICAL

CAPACITY

GALLONS

ADHESION

PRESSURE

850 PSI

HEAT

RESISTANCE

TANK SIZE

HIGH

NOTES: 1. ABRASIVE RESISTANCE: 75.3 MILIGRAMS LOSS AVERAGE 2. FLEXIBILITY; 1/2" INCH BEND ZUHR CONICAL MANDEL- 10 mil film

MATERIAL TANK TO BE ONE PIECE MOLDED OF HIGH DENSITY

POLYETHYLENE COLOR NATURAL TANK REQUIREDS 100% BOTTON

SUPPORT. PIPING & VALVES MUST HAVE ITS OWN SUPPORT.

119 119GAL/6HRS HAWS, STANDARD SYSTEM No. 8780 POLAR UNITS

*** Safety Pays ***

*** Support Value Engineering - It Pays ***

NEW YORK DISTRICT

A R

L

IN

G T

O N

V

IR

G

T E

L

F A

X

R

R

E

D w n b y

D e s ig n e d b y

R e v ie w e d b y

D a t e

R e v

C k d b b m it t e d b e n a m t d a t t s c a ie f

A r c h

B r a n

S L

A B s ig n f il e n a w in g c o d s c r ip t io n M a r k

A p p r

M a r k

D a t e

D a t e

A p p r

US Army Corps of Engineers

A

B

D

21 4 5

Sheet reference number:

2 4 51

C

N

T R

IC

T

N

T R

IC

T

J

U L

R K

N

S T

E

B O

R A

T O

R

S T

E

B O

R A

T O

R Y

Sheet of 195

B

D C

P L

U M

B

IN

G

S C

H E

D U

L E

S

A D

D E

N D

J

U L

HANDHOLE

#3 TIES AS SHOWN

O .C

SEE NOTE-1

1’- L A P

4" CLR.

A1 SCALE: NONE

SITE LIGHTING POLE BASE

1.

DETAIL NOTES:

BASE DIMENSION INDICATED ARE MINIMUM REQUIREMENTS, INCREASE

AS REQUIRED TO SUITE APPROVED POLE SPECIFICATIONS.

CONTRACTOR SHALL SUBMIT BASE STRUCTURAL AND POLE WIND

RESISTANCE CALCULATIONS THAT DEPICT ACTUAL INSTALLED

CONDITION.

PIER PLAN

ANCHOR BOLTS PER

MANUFACTURER REQUIREMENT

6#5 VERTICAL

FINISHED GRADE

2" NON-SHRINK GROUT

BOND POLE AND BASE

WITH #6AWG BARE COPPER

CONDUCTOR

GROUND ROD

CONDUIT BRANCH CIRCUIT

24"3

A.

KEY NOTES

SHEET NOTES

REFER TO SHEET NO. 1E-801 LIGHTING

FIXTURE SCHEDULE FOR DESIGNATED

FIXTURE TYPE SPECIFICATIONS.

B.

THE CONTRACTOR SHALL BE RESPONSIBLE

FOR NOTIFICATION AND COORDINATION WITH

THE ELECTRIC UTILITY, SUSSEX RURAL

ELECTRIC COOPERATIVE (SREC), AND

TELECOMMUNICATION SERVICE PROVIDER

CHUGACH INDUSTRIES. REFER TO UTILITY

NOTES ON CIVIL SHEET NO. C-001.

A4 1E-001

E L

E C

T R

IC

A N

1" = 30’-0"

OVERALL SITE PLAN

D P

M B

H Z

O V

E R

A L

L

30’0 15’ 60’

SCALE: 1" = 30’-0"

TM4

1E-001

A1

3353-PPL2:8

TM4

TYPICAL

3 - #8AWG IN 1" CONDUIT.

PROVIDE UTILITY STANDARD 150W HIGH

PRESSURE SODIUM AREA LIGHT FIXTURE

MOUNTED ON UTILITY POLE. COORDINATE

WITH SREC, UTILITY SHALL INSTALL FIXTURE

AND TERMINATE POWER CONNECTION.

FIXTURE SHALL HAVE FULL CUT-OFF

OPTICAL DISTRIBUTION FOR DARK SKY

COMPLIANCE AND INTEGRAL PHOTOCELL

CONTROL.

TYPICAL FOR TYPE

TM4 POLE BASE

NEW

BUILDING

#3353

PUMP

ROOM

3 APPROXIMATE LOCATION OF PANEL

3353-PPL2, REFER TO DETAIL B2/2E-202.

C. REFER TO CIVIL UTILITY DRAWINGS FOR

ADDITIONAL UNDERGROUND

TELECOMMUNICATION AND ELECTRICAL

POWER DUCTBANK REQUIREMENTS.

4 EXTEND 2- 4" CONDUITS TO TR 134, SEE

DETAIL A2/1ET-111.

5 2-4" CONDUITS UNDERGROUND

COMMUNICATION LINE TO UTILITY POLE.

6 300kVA UTILITY TRANSFORMER PROVIDED

BY SREC.

7 750kVA UTILITY TRANSFORMER PROVIDED

BY SREC.

(5) 4" CONDUITS

3349-208V-F

(6) 4" CONDUITS

3349-440V-F

8 150kVA UTILITY TRANSFORMER PROVIDED

BY SREC.

9 EXTEND TO TR COMMUNICATION EQUIPMENT

CABINET AT WORKSTATIONS 202, SEE

DETAIL A2/2ET-102.

10 (3) 4" CONDUITS 3353-208V-F

A D

D E

N D

OVERHEAD ELECTRIC

AND COMMUNICATION

SERVICES BY

OTHERS

3/4" FIRE ALARM CONDUIT

(2) 2" POWER CONDUIT

FIRE PUMP-208V-F

TRANSITION FROM OVERHEAD TO

UNDERGROUND FEEDERS - TERMINATE

UNDERGROUND WORK AS DIRECTED BY

SREC UTILITY.

UNDERGROUND ELECTRIC TO

TRANSFORMERS

FUTURE

BUILDING

#3350

(2) 4" COMMUNICATION CONDUIT

(3) 4" ELECTRIC CONDUIT

FEEDER 3353-208V-F

(2) 4" COMMUNICATION CONDUIT

FEEDER 3350-208V-F

(4) 4" ELECTRIC CONDUIT

FEEDER 3350-440V-F

A R

L

IN

G T

O N

V

IR

G

T E

L

F A

X

R

R

E

D w n b y

D e s ig n e d b y

R e v ie w e d b y

D a t e

R e v

C k d b b m it t e d b e n a m t d a t t s c a ie f

A r c h

B r a n

S L

A B s ig n f il e n a w in g c o d s c r ip t io n M a r k

*** Safety Pays ***

*** Support Value Engineering - It Pays ***

A p p r

M a r k

D a t e

D a t e

A p p r

US Army Corps of Engineers

A

B

D

21 4 5

Sheet reference number:

2 4 51

C

NEW YORK DISTRICT

N

T R

IC

T

N

T R

IC

T

J

U L

R K

N

S T

E

B O

R A

T O

R

S T

E

B O

R A

T O

R Y

N

BLDG

BLDG

Sheet of 195

EXISTING CONCRETE PAD

TO REMAIN

#3352

EL. 965.61

NEW

BUILDING

#3349

F.F. 965.90

A1

MAGAZINE LEVEL FLOOR PLAN

8’0 4’ 16’

SCALE:1/8"=1’

SHEET NOTES

KEY NOTES

A.

1E-102

110 113

WATER

TANK

MAGAZINE

ROOM 1

MAGAZINE

ROOM 2

STORAGE

MAGAZINE

ROOM 3

AREA WAY

REFER TO SHEET NO. 1E-801 FOR

LIGHTING FIXTURE TYPE SPECIFICATIONS.

B. ALL POWER AND LIGHTING BRANCH

CIRCUITRY LOCATED AT MAGAZINE LEVEL

INTERIOR ROOMS SHALL BE RATED

SUITABLE FOR APPLICATION IN CLASS-1,

DIVISION-2 ENVIRONMENTS WITH

EXPLOSIVE VAPORS PRESENT.

1/8 " = 1’-0"

TYPICAL

TYPICAL

INSTALL WALL MOUNTED LIGHT FIXTURE AS

HIGH AS POSSIBLE BELOW MECHANICAL

DUCTWORK, (APPROXIMATELY 7’-0" ABOVE

FINISHED FLOOR).

INSTALL PENDANT/SURFACE MOUNTED

LIGHT FIXTURE TO CEILING STRUCTURE AS

HIGH AS POSSIBLE, (APPROXIMATELY 7’-9"

ABOVE FINISHED FLOOR).

TYPICAL

OVERHEAD METAL TRACK SYSTEM FOR

GUN SYSTEM EQUIPMENT PROVIDED BY

OTHERS. MAGAZINE ROOMS 110 AND 111

WILL BE SIMILAR BUT CONFIGURATION WILL

VARY FOR DIFFERENT WEAPON SYSTEM.

LIGHTING FIXTURE LAYOUT IS SHOWN

DIAGRAMMATIC, COORDINATE EXACT FIXTURE

PLACEMENT TO MAXIMIZE LIGHTING

UNIFORMITY WITHIN THE SPACE TO SUIT

WEAPON SYSTEM AND OTHER BUILDING

COMPONENTS.

B U

IL

D

F

L O

A N

M A

G A

Z

V E

IG

H T

IN

G

EXTEND TO LIGHT SWITCH LOCATED AT

TOP OF SPIRAL STAIRS, REFER TO LOADER

LEVEL LIGHTING PLAN.

M B

D P

H Z

A D

D E

N D

WALL MOUNT LIGHT TYPE AT 84" AFF.

1 1

TYPICAL

*** Safety Pays ***

*** Support Value Engineering - It Pays ***

NEW YORK DISTRICT

A R

L

IN

G T

O N

V

IR

G

T E

L

F A

X

R

R

E

D w n b y

D e s ig n e d b y

R e v ie w e d b y

D a t e

R e v

C k d b b m it t e d b e n a m t d a t t s c a ie f

A r c h

B r a n

S L

A B s ig n f il e n a w in g c o d s c r ip t io n M a r k

A p p r

M a r k

D a t e

D a t e

A p p r

US Army Corps of Engineers

A

B

D

21 4 5

Sheet reference number:

2 4 51

C

N

T R

IC

T

N

T R

IC

T

J

U L

R K

N

S T

E

B O

R A

T O

R

S T

E

B O

R A

T O

R Y

N

BLDG

BLDG

Sheet of 195

EX3

FL2

FL2 FL2

FL2 FL2

FL2

EX3

FL2

FL2

FL2

FL2

EX3

PPL3: 1 PPL2: 1 PPL1: 1

3E

J

E

3E

J J

E

FL2FL2

FL2A

FL2A

FL6

FL6

FL6

FL6

FL6

FL6 FL6

FL6

FL6 FL6

FL6 FL6

FL6A

FL6A

FL6A

FL6A

FL6A

FL6A FL6A

FL6A

FL6A

E

E

E

E

3E

E

E

WP1

WP1

WP1

WP1

6 8 10 12

B .1

C .1

C

7 9 11

4 4 4

5 5 5 5

M A

T C

H L

IN

E

S E

E S

E E

1E-111

L O

A D

V

U T

H T

II

N

G

A2

8’0 4’ 16’

SCALE:1/8"=1’

SHEET NOTES

KEY NOTES

E

139 142

WORK ROOM

CORRIDOR

TOILET

TOILET/SHOWER

JC

OFFICE

OFFICE

OFFICE 129

OFFICE

CORRIDOR

COPY/

WORKROOM

TR

BREAK

GUN WORKROOM

A. REFER TO SHEET NO. 3E-801 FOR

LIGHTING FIXTURE TYPE SPECIFICATIONS.

B U

IL

D

F

L O

A N

PPL4B:2

PPL4B:4

PPL4B

A

98.3

A .4

A4

PARTIAL - MECHANICAL ACCESS PLAN

1/8 " = 1’-0"

LOADER LEVEL FLOOR PLAN

1/8 " = 1’-0"

SURFACE MOUNT LIGHT FIXTURE TO

OVERHANG STRUCTURE, REFER TO

ARCHITECTURE.

WALL MOUNTED LIGHT FIXTURE @ 8’-0"

AFF.

WALL MOUNTED LIGHT FIXTURE @ 14’-0"

AFF.

M B

H Z

D P

CONNECT TO RECEPTACLE BRANCH

CIRCUIT 3349- PPL4A:26, REFER TO

DETAIL B4/1E-211.

PROVIDE BI-LEVEL OCCUPANCY SENSOR

WALL SWITCH. LIGHT FIXTURES SHALL

HAVE ELECTRONIC BI-LEVEL BALLAST.

PROVIDE BI-LEVEL WALL SWITCHES. LIGHT

FIXTURES SHALL HAVE ELECTRONIC

BI-LEVEL BALLASTS.

PPL4B:8

TYPICAL

PENDANT MOUNT FIXTURE - PROVIDE CORD

AND PLUG WITH RECEPTACLE PLUG FOR

QUICK DISCONNECTING MEANS.

PPL4B:10

A D

D E

N D

*** Safety Pays ***

*** Support Value Engineering - It Pays ***

NEW YORK DISTRICT

A R

L

IN

G T

O N

V

IR

G

T E

L

F A

X

R

R

E

D w n b y

D e s ig n e d b y

R e v ie w e d b y

D a t e

R e v

C k d b b m it t e d b e n a m t d a t t s c a ie f

A r c h

B r a n

S L

A B s ig n f il e n a w in g c o d s c r ip t io n M a r k

A p p r

M a r k

D a t e

D a t e

A p p r

US Army Corps of Engineers

A

B

D

21 4 5

Sheet reference number:

2 4 51

C

N

T R

IC

T

N

T R

IC

T

J

U L

R K

N

S T

E

B O

R A

T O

R

S T

E

B O

R A

T O

R Y

N

BLDG

BLDG

Sheet of 195

O S

A B

C 1 2 3 5 66 7 7

FL4 FL4

M A

T C

H L

IN

E

S E

E S

E E

1E-112

A2 �" = 1’-0"

LOADER LEVEL FLOOR PLAN

8’0 4’ 16’

SCALE:1/8"=1’

L O

A D

V

R T

H T

IN

G

SHEET NOTES

KEY NOTES

E

LOADER ROOM 1

LOADER ROOM 2

LOADER ROOM 3 125

MECH

ELEC

B U

IL

D

F

L O

A N

A. REFER TO SHEET NO. 3E-801 FOR

LIGHTING FIXTURE TYPE SPECIFICATIONS.

B.

INSTALL PENDANT/SURFACE MOUNTED

LIGHT FIXTURE TO CEILING STRUCTURE AS

HIGH AS POSSIBLE, (APPROXIMATELY 7’-6"

ABOVE FINISHED FLOOR).

ALL POWER AND LIGHTING BRANCH

CIRCUITRY LOCATED AT LOADER ROOMS

120, 121, AND 123 SHALL BE RATED

SUITABLE FOR…

This is the start of the file's text. The full file is on GovTribe.