MP-501.pdf
PDF 57 KB Posted
- Attached to
- Fort Bragg SATOC
- Solicitation number
- W912DR-14-R-0025
About this file
Dwg
View the file
Other files
| File | Type | Posted |
|---|---|---|
| W912DR-14-R-0025-0003_Amendment_3_FINAL.pdf | ||
| W912DR-14-R-0025-0002_Amendment_2.pdf | ||
| W912DR-14-R-0025-0001_Amendment_1.pdf | ||
| A-001.pdf | ||
| W912DR-14-R-0025_Fort_Bragg_SATOC_Solicitation.pdf | ||
| MP-102.pdf | ||
| E-101.pdf | ||
| Division_1_Fort_Bragg_SATOC_March_2014.pdf | ||
| E-102.pdf | ||
| E-001.pdf | ||
| A-102.pdf | ||
| C-102.pdf | ||
| E-002.pdf | ||
| C-101.pdf | ||
| A-201.pdf | ||
| Contractor_Format_for_RFIs.xlsx | XLSX spreadsheet | |
| S-101.pdf | ||
| A-401.pdf | ||
| A-501.pdf | ||
| A-301.pdf | ||
| G-001.pdf | ||
| A-402.pdf | ||
| MP-001.pdf | ||
| MP-101.pdf | ||
| MP-601.pdf | ||
| A-101.pdf |
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SCALE: NTS
SCALE: NTSSCALE: NTSSCALE: NTS
SCALE: NTS SCALE: NTS
RETURN GRILLE DETAIL FLEXIBLE BRANCH DUCT (CEILING DIFFUSER) DETAIL VERTICAL FIRE DAMPER DETAIL
NO-PRIMER FLOOR DRAIN DETAIL
TYPICAL LOW PRESSURE ROUND DUCT TAKE-OFF DETAIL TYPICAL LOW PRESSURE RECTANGULAR DUCT TAKE-OFF DETAIL
45°
RA PLENUM
(PAINT INSIDE BLACK
IF VISIBLE)
DUCT DROP TO ACTIVE
SECTION OF CRG
(PAINT INSIDE BLACK)
WIDTH OF DUCT DROP
EQUALS LISTED GRILLE
WIDTH
LOW PRESSURE
SUPPLY DUCT
45° TAKE-OFF COLLAR
(TYP OF ALL DIFFUSERS)
VOLUME DAMPER
(TYP OF ALL DIFFUSERS)
FLEXIBLE DUCT
(6'-0" MAX)
STAINLESS
STEEL
STRAP CLAMP
LAY-IN CEILING DIFFUSER
SUPPORT ON ALL SIDES
OF CEILING DIFFUSER
LAY-IN CEILING TILE
CEILING TILE SUPPORT
WALL
2X2X10 GA STEEL
ANGLE BOLTED TO
SLEEVE (TYPICAL)
3/8" UNC THREAD
CUTTING SCREW
6" OC (TYPICAL)
10 GA SLEEVE
(ALL AROUND)
"S" SLIP CONNECTION
ALL FOUR SIDES
HINGED
ACCESS
DOOR
LOCATE
WHERE
ACCESSIBLE
OR WHERE
SHOWN
FIRE
DAMPER
FIRE DAMPER (OUT-OF-
AIRSTREAM TYPE)
NOTE:
SIDE ELEVATION SHOWN. PROVIDE CLEARANCES
AS SPECIFIED IN SMACNA "FIRE DAMPER AND HEAT
STOP GUIDE FOR AIR HANDLING SYSTEMS".
OUTLET
CONNECTION
FLOOR SLAB
WATERPROOFING
MEMBRANE
(WHERE PROVIDED
FOR BY ARCHITECT)
FINISHED FLOOR
DRAIN BODY
SEEPAGE OPENINGS
FLASHING COLLAR
STRAINER HEAD
RECOMMENDATIONS.
INSTALL FLEX DUCT FULLY EXTENDED.
EXTEND FLEX DUCT 12" BEYOND
ALL FLEX DUCT CONNECTIONS SHALL
BE COATED WITH A LIQUID SEALER
IN ACCORDANCE WITH MANUFACTURER
BELL MOUTH
CONNECTION
CLAMP
INSULATION
FLEXIBLE
ROUND
DUCT
45° ANGLE ON SHEET
METAL TRIM PIECE TO
RETAIN ACOUSTICAL
LINING ONLY
DUCT
SEALANT
CONNECTOR BEFORE BEND.
HAND DAMPER
W/ LOCKING DEVICE
1.
2.
3.
ACOUSTICAL LINING
WHERE INDICATED
MAIN LOW
PRESSURE DUCT
NOTES:
HAND DAMPER
W/ LOCKING DEVICE
MAIN SUPPLY
AIR DUCT
BRANCH DUCT
AIR FLOW
EQUALS WIDTH OF BRANCH DUCT UP TO 12".
12" FOR ALL BRANCH DUCTS LARGER THAN 12".
SCALE: NTS
INLINE FAN DETAIL
DISCHARGE
THRUST RESTRAIN
FLEXIBLE CONNECTION
FAN
INTAKE
THREADED ROD
(4 REQ'D)
TURNBUCKLE (4 REQ'D)
VIBRATION ISOLATOR
(4 REQ'D)
BRACKET
(4 REQ'D)
SCALE: NTS
AHU-1 & AHU-2 DUCTWORK DETAIL
AHU-1
AHU-2
18"x14"
"x
14"x14"
FLEX
CONNECTION
RETURN
PLENUM
FLEX
CONNECTION
FLEX
CONNECTIONREFRIGERANT LINES
TO CONDENSING UNITS
HP-1 & HP-2
ROUTE 3/4" CONDENSATE FROM AHU-1
& AHU-2 TO MECH ROOM FLOOR DRAIN
180 DEGREE BEND
DRAW THRU TYPE AHU
2" AIR GAP
FLOOR DRAIN FLOOR
IPS COPPER ADAPTER
CLEAN-OUT PLUG (TYP)
PAN WATER LEVEL
DRIP PAN
C
A
B
NOTES:
1. ALLOW SUFFICIENT SPACE BELOW DRAIN PAN FOR TRAP.
2. MANUALLY PRIME TRAP BEFORE START-UP TO FORM INITIAL DRAIN SEAL.
A = EQUAL TO OR LARGER THAN
THE PLENIUM NEGATIVE STATIC
PRESSURE AT DESIGN OPERATING
CONDITIONS
B = A/2 + 1-1/2" * (MIN.)
C = A + B
SEE CIVIL
DWGS. FOR
PAD.
SERVICE PORT
LIQUID LINE
SOLENOID
VALVE
SIGHT GLASS
DRIER BI-FLOW
FILTER
SCALE: NTS
CONDENSING UNIT DETAIL
SCALE: NTS
CONDENSATE DRAIN DETAIL
FLEX
CONNECTION
NOTE:
1. SUPPORT UNIT AS PER MANUFACTURER'S RECOMMENDATIONS.
SEAL AT
CORNERS
D
C
B
A
2 3 4 5
R e v
Sheet
Sheet reference number:
A p p r.
D a te
D e s c ri p ti o n
M a rk
D a te
D e s ig n f ile n o
D e s ig n e d b y
D w n b y
C k d b y
R e v ie w e d b y
S u b m itt e d b y
C h ie f, D ra w in g c o d e
F ile n a m e
P lo t s c a le
P lo t d a te of
B U
IL
D
IN
G
E
Baltimore District of Engineers US Army Corps
S U
B M
IS
S
IO
N
-2
-0
S
U B
M
IS
S
IO
N
-2
-0
N O
S C
A L E
-3
-0
M P
-5 .d w g
-3
-0
T S
C
T S
C K
L P
M E
C H
A N
IC
A
L
P L U
M B
IN
G
D E
T A
IL
S
MP-501
16 21
File details come from the government source that posted it. Updated .