Lakehurst, NJ Building 194, W912CF-09-B-0013, W912CF-09-B-0014, and W912CF-09-B-0015
1. In the scope of work, the fiber is called out to be CMR but the 100 pair Cat 3 is Plenum rated.
Is this correct? Should they both be of the same style?
2. There are no teledata outlets shown in room #100. Is this correct?
3. What are the elevations of the Pre-Fab building?
4. Can you supply us architectural drawings for the Pre-Fab building that states what the building is made of or what the interior walls are made of.
5. Where is panel "PP2" located? It is not shown in equipment room # 101.
6. Where are the safety switches 1 & 2 located?