080310-3 ENGINE MONITORING SYSTEM CABLING REQUIREMENTS.pdf
PDF 73 KB Posted
- Solicitation number
- W912BU-10-R-0033
About this file
MACH-301 080310-3 ENGINE MONITORING SYSTEM CABLING REQUIREMENTS.pdf
View the file
Other files
Show 40 more
Latest 50 of 183 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Acronym Definition AMS Alarm and Monitoring System PDE Port Dredge EnginePDE Port Dredge Engine SDE Starboard Dredge Engine CDE Center Dredge Engine PAE Port Aux Engine SAE S b d A E iSAE Starboard Aux Engine CAE Center Aux Engine HMI Human Machine Interface LOP Lube Oil Pressure LOT Lube Oil Temperature RW1 Raw Water Pressure (before strainer) RW2 Raw Water Pressure (after strainer) FOP Fuel Oil PressureFOP Fuel Oil Pressure JWTI Jacket Water Temp In JWTO Jacket Water Temp Out DI Digital Inputs
CABLE ID CABLE MANUFACTURER PART NUMBER DESCRIPTION FROM TO ESTIMATED LENGTH REQUIRED SENSOR/TRANSDUCER MOUNTING
AMS‐PROFI‐1 BELDEN 3076F Profibus Engine Room Remote I/O Panel Generator Room Remote I/O Panel 20' N/A
AMS‐PROFI‐2 BELDEN 3076F Profibus Engine Room Remote I/O Panel Central Control Station (CCS) 75' N/A AMS‐PROFI‐3 CAT‐5 CCS Dredge Pump Control Panels 50' N/A AMS‐HMI‐7 CAT‐5 Dredge Pump Control Panels Aux Switchgear 25' N/A
AMS‐PDE‐LOP MONROE LS2SJ‐16 Twisted Shielded Pair FWD Engine Room Bulkhead Engine Room Remote I/O Panel 30' Mount DANFOSS MBC5000 series pressure transducer at existing pressure switch location on FWD engine room bulkhead. Provide tubing.
AMS‐PDE‐LOT MONROE LS3SJ‐18 3 Conductor Shielded Existing Thermowell on Engine Engine Room Remote I/O Panel 30' Install new PT1000 RTD in existing thermowell.
AMS‐PDE‐RW1 MONROE LS2SJ‐16 Twisted Shielded Pair Engine Room Port Side Engine Room Remote I/O Panel 45' Mount DANFOSS MBC5000 series pressure transducer at existing local gauges port side engine room. Provide tubing.
Mount DANFOSS MBC5000 series pressure transducer at existing local
AMS‐PDE‐RW2 MONROE LS2SJ‐16 Twisted Shielded Pair Engine Room Port Side Engine Room Remote I/O Panel 45' Mount DANFOSS MBC5000 series pressure transducer at existing local gauges port side engine room. Provide tubing.
AMS‐PDE‐JWTI MONROE LS3SJ‐18 3 Conductor Shielded Existing Thermowell on Engine Engine Room Remote I/O Panel 30' Install new PT1000 RTD in existing thermowell.
AMS‐PDE‐JWTO MONROE LS3SJ‐18 3 Conductor Shielded Existing Thermowell on Engine Engine Room Remote I/O Panel 30' Install new PT1000 RTD in existing thermowell.
Mount DANFOSS MBC5000 series pressure transducer adjacent to local engine panel. Provide tubing to "T" into fuel oil pressure feed to local
AMS‐PDE‐FOP MONROE LS2SJ‐16 Twisted Shielded Pair Adjacent to Local Engine Panel Engine Room Remote I/O Panel 30' engine panel. Provide tubing to T into fuel oil pressure feed to local engine panel.
AMS‐PDE‐RPM MONROE LS2SJ‐16 Twisted Shielded Pair Tach gen on engine Engine Room Remote I/O Panel 50' N/A. Existing tach generator.
AMS‐PDE‐DI GENERAL CBL 356760 8 Conductor 14 AWG Local Engine Panel Engine Room Remote I/O Panel 50' N/A
AMS‐SDE‐LOP MONROE LS2SJ‐16 Twisted Shielded Pair FWD Engine Room Bulkhead Engine Room Remote I/O Panel 30' Mount DANFOSS MBC5000 series pressure transducer at existing pressure switch location on FWD engine room bulkhead. Provide tubing.
AMS‐SDE‐LOT MONROE LS3SJ‐18 3 Conductor Shielded Existing Thermowell on Engine Engine Room Remote I/O Panel 30' Install new PT1000 RTD in existing thermowell.
AMS‐SDE‐RW1 MONROE LS2SJ‐16 Twisted Shielded Pair Engine Room Port Side Engine Room Remote I/O Panel 45' Mount DANFOSS MBC5000 series pressure transducer at existing local gauges port side engine room. Provide tubing.
Mount DANFOSS MBC5000 series pressure transducer at existing local
AMS‐SDE‐RW2 MONROE LS2SJ‐16 Twisted Shielded Pair Engine Room Port Side Engine Room Remote I/O Panel 45' Mount DANFOSS MBC5000 series pressure transducer at existing local gauges port side engine room. Provide tubing.
AMS‐SDE‐JWTI MONROE LS3SJ‐18 3 Conductor Shielded Existing Thermowell on Engine Engine Room Remote I/O Panel 30' Install new PT1000 RTD in existing thermowell.
AMS‐SDE‐JWTO MONROE LS3SJ‐18 3 Conductor Shielded Existing Thermowell on Engine Engine Room Remote I/O Panel 30' Install new PT1000 RTD in existing thermowell.
Mount DANFOSS MBC5000 series pressure transducer adjacent to local engine panel. Provide tubing to "T" into fuel oil pressure feed to local
AMS‐SDE‐FOP MONROE LS2SJ‐16 Twisted Shielded Pair Adjacent to Local Engine Panel Engine Room Remote I/O Panel 30' engine panel. Provide tubing to T into fuel oil pressure feed to local engine panel.
AMS‐SDE‐RPM MONROE LS2SJ‐16 Twisted Shielded Pair Tach gen on engine Engine Room Remote I/O Panel 50' N/A. Existing tach generator.
AMS‐SDE‐DI GENERAL CBL 356760 8 Conductor 14 AWG Local Engine Panel Engine Room Remote I/O Panel 50' N/A
AMS‐CDE‐LOP MONROE LS2SJ‐16 Twisted Shielded Pair FWD Engine Room Bulkhead Engine Room Remote I/O Panel 20' Mount DANFOSS MBC5000 series pressure transducer at existing pressure switch location on FWD engine room bulkhead. Provide tubing.
AMS‐CDE‐LOT MONROE LS3SJ‐18 3 Conductor Shielded Existing Thermowell on Engine Engine Room Remote I/O Panel 20' Install new PT1000 RTD in existing thermowell.
AMS‐CDE‐RW1 MONROE LS2SJ‐16 Twisted Shielded Pair Engine Room Port Side Engine Room Remote I/O Panel 20' Mount DANFOSS MBC5000 series pressure transducer at existing local gauges port side engine room. Provide tubing.
Mount DANFOSS MBC5000 series pressure transducer at existing local
AMS‐CDE‐RW2 MONROE LS2SJ‐16 Twisted Shielded Pair Engine Room Port Side Engine Room Remote I/O Panel 20' Mount DANFOSS MBC5000 series pressure transducer at existing local gauges port side engine room. Provide tubing.
AMS‐CDE‐JWTI MONROE LS3SJ‐18 3 Conductor Shielded Existing Thermowell on Engine Engine Room Remote I/O Panel 20' Install new PT1000 RTD in existing thermowell.
AMS‐CDE‐JWTO MONROE LS3SJ‐18 3 Conductor Shielded Existing Thermowell on Engine Engine Room Remote I/O Panel 20' Install new PT1000 RTD in existing thermowellAMS‐CDE‐JWTO MONROE LS3SJ‐18 3 Conductor Shielded Existing Thermowell on Engine Engine Room Remote I/O Panel 20 Install new PT1000 RTD in existing thermowell.
AMS‐CDE‐FOP MONROE LS2SJ‐16 Twisted Shielded Pair Adjacent to Local Engine Panel Engine Room Remote I/O Panel 20'
Mount DANFOSS MBC5000 series pressure transducer adjacent to local engine panel. Provide tubing to "T" into fuel oil pressure feed to local engine panel.
AMS CDE RPM MONROE LS2SJ 16 T i d Shi ld d P i T h i E i R R I/O P l 20' N/A E i i hAMS‐CDE‐RPM MONROE LS2SJ‐16 Twisted Shielded Pair Tach gen on engine Engine Room Remote I/O Panel 20' N/A. Existing tach generator.
AMS‐CDE‐DI GENERAL CBL 356760 8 Conductor 14 AWG Local Engine Panel Engine Room Remote I/O Panel 20' N/A
Mount DANFOSS MBC5000 series pressure transducer at existing pressure AMS‐PAE‐LOP MONROE LS2SJ‐16 Twisted Shielded Pair FWD Engine Room Bulkhead Engine Room Remote I/O Panel 30' p g p switch location on FWD engine room bulkhead. Provide tubing.
AMS‐PAE‐LOT MONROE LS3SJ‐18 3 Conductor Shielded Existing Thermowell on Engine Engine Room Remote I/O Panel 30' Install new PT1000 RTD in existing thermowell.
Mount DANFOSS MBC5000 series pressure transducer at existing local
AMS‐PAE‐RW1 MONROE LS2SJ‐16 Twisted Shielded Pair Engine Room Port Side Engine Room Remote I/O Panel 45' Mount DANFOSS MBC5000 series pressure transducer at existing local gauges port side engine room. Provide tubing.
AMS‐PAE‐RW2 MONROE LS2SJ‐16 Twisted Shielded Pair Engine Room Port Side Engine Room Remote I/O Panel 45' Mount DANFOSS MBC5000 series pressure transducer at existing local gauges port side engine room. Provide tubing.
AMS‐PAE‐JWTI MONROE LS3SJ‐18 3 Conductor Shielded Existing Thermowell on Engine Engine Room Remote I/O Panel 30' Install new PT1000 RTD in existing thermowell.
AMS‐PAE‐JWTO MONROE LS3SJ‐18 3 Conductor Shielded Existing Thermowell on Engine Engine Room Remote I/O Panel 30' Install new PT1000 RTD in existing thermowell.AMS PAE JWTO MONROE LS3SJ 18 3 Conductor Shielded Existing Thermowell on Engine Engine Room Remote I/O Panel 30 Install new PT1000 RTD in existing thermowell.
AMS‐PAE‐FOP MONROE LS2SJ‐16 Twisted Shielded Pair Adjacent to Local Engine Panel Engine Room Remote I/O Panel 30'
Mount DANFOSS MBC5000 series pressure transducer adjacent to local engine panel. Provide tubing to "T" into fuel oil pressure feed to local engine panel.
AMS PAE RPM MONROE LS2SJ 16 T i t d Shi ld d P i T h i E i R R t I/O P l 50' N/A E i ti t h tAMS‐PAE‐RPM MONROE LS2SJ‐16 Twisted Shielded Pair Tach gen on engine Engine Room Remote I/O Panel 50' N/A. Existing tach generator.
AMS‐PAE‐DI GENERAL CBL 356760 8 Conductor 14 AWG Local Engine Panel Engine Room Remote I/O Panel 50' N/A
Mount DANFOSS MBC5000 series pressure transducer at existing pressure AMS‐SAE‐LOP MONROE LS2SJ‐16 Twisted Shielded Pair FWD Engine Room Bulkhead Engine Room Remote I/O Panel 30' p g p switch location on FWD engine room bulkhead. Provide tubing.
AMS‐SAE‐LOT MONROE LS3SJ‐18 3 Conductor Shielded Existing Thermowell on Engine Engine Room Remote I/O Panel 30' Install new PT1000 RTD in existing thermowell.
Mount DANFOSS MBC5000 series pressure transducer at existing local
AMS‐SAE‐RW1 MONROE LS2SJ‐16 Twisted Shielded Pair Engine Room Port Side Engine Room Remote I/O Panel 45' Mount DANFOSS MBC5000 series pressure transducer at existing local gauges port side engine room. Provide tubing.
AMS‐SAE‐RW2 MONROE LS2SJ‐16 Twisted Shielded Pair Engine Room Port Side Engine Room Remote I/O Panel 45' Mount DANFOSS MBC5000 series pressure transducer at existing local gauges port side engine room. Provide tubing.
AMS‐SAE‐JWTI MONROE LS3SJ‐18 3 Conductor Shielded Existing Thermowell on Engine Engine Room Remote I/O Panel 30' Install new PT1000 RTD in existing thermowell.
AMS‐SAE‐JWTO MONROE LS3SJ‐18 3 Conductor Shielded Existing Thermowell on Engine Engine Room Remote I/O Panel 30' Install new PT1000 RTD in existing thermowell.AMS SAE JWTO MONROE LS3SJ 18 3 Conductor Shielded Existing Thermowell on Engine Engine Room Remote I/O Panel 30 Install new PT1000 RTD in existing thermowell.
AMS‐SAE‐FOP MONROE LS2SJ‐16 Twisted Shielded Pair Adjacent to Local Engine Panel Engine Room Remote I/O Panel 30'
Mount DANFOSS MBC5000 series pressure transducer adjacent to local engine panel. Provide tubing to "T" into fuel oil pressure feed to local engine panel.
AMS SAE RPM MONROE LS2SJ 16 Twisted Shielded Pair Tach gen on engine Engine Room Remote I/O Panel 50' N/A Existing tach generatorAMS‐SAE‐RPM MONROE LS2SJ‐16 Twisted Shielded Pair Tach gen on engine Engine Room Remote I/O Panel 50' N/A. Existing tach generator.
AMS‐SAE‐DI GENERAL CBL 356760 8 Conductor 14 AWG Local Engine Panel Engine Room Remote I/O Panel 50' N/A
Mount DANFOSS MBC5000 series pressure transducer at existing pressure AMS‐CAE‐LOP MONROE LS2SJ‐16 Twisted Shielded Pair FWD Engine Room Bulkhead Engine Room Remote I/O Panel 20' switch location on FWD engine room bulkhead. Provide tubing.
AMS‐CAE‐LOT MONROE LS3SJ‐18 3 Conductor Shielded Existing Thermowell on Engine Engine Room Remote I/O Panel 20' Install new PT1000 RTD in existing thermowell.
Mount DANFOSS MBC5000 series pressure transducer at existing local
AMS‐CAE‐RW1 MONROE LS2SJ‐16 Twisted Shielded Pair Engine Room Port Side Engine Room Remote I/O Panel 20' gauges port side engine room. Provide tubing.
AMS‐CAE‐RW2 MONROE LS2SJ‐16 Twisted Shielded Pair Engine Room Port Side Engine Room Remote I/O Panel 20' gauges port side engine room. Provide tubing.
AMS‐CAE‐JWTI MONROE LS3SJ‐18 3 Conductor Shielded Existing Thermowell on Engine Engine Room Remote I/O Panel 20' Install new PT1000 RTD in existing thermowellAMS‐CAE‐JWTI MONROE LS3SJ‐18 3 Conductor Shielded Existing Thermowell on Engine Engine Room Remote I/O Panel 20 Install new PT1000 RTD in existing thermowell.
AMS‐CAE‐JWTO MONROE LS3SJ‐18 3 Conductor Shielded Existing Thermowell on Engine Engine Room Remote I/O Panel 20' Install new PT1000 RTD in existing thermowell.
Mount DANFOSS MBC5000 series pressure transducer adjacent to local i l P id bi "T" i f l il f d l l AMS‐CAE‐FOP MONROE LS2SJ‐16 Twisted Shielded Pair Adjacent to Local Engine Panel Engine Room Remote I/O Panel 20' engine panel. Provide tubing to "T" into fuel oil pressure feed to local engine panel.
AMS‐CAE‐RPM MONROE LS2SJ‐16 Twisted Shielded Pair Tach gen on engine Engine Room Remote I/O Panel 20' N/A. Existing tach generator.
AMS‐CAE‐DI GENERAL CBL 356760 8 Conductor 14 AWG Local Engine Panel Engine Room Remote I/O Panel 20' N/Ag g / / AMS‐CPU‐PWR GENERAL CBL 279220 3 Conductor 10 AWG CCS Ships Service UPS 50' N/A
AMS‐RER‐PWR GENERAL CBL 279220 3 Conductor 10 AWG Engine Room Remote I/O Panel Dredge System UPS 30' N/A Generator Room Remote I/O
AMS‐RGR‐PWR GENERAL CBL 279220 3 Conductor 10 AWG Generator Room Remote I/O Panel Ships Service UPS 20' N/A
File details come from the government source that posted it. Updated .