09R0015 Amnd4-Specs .pdf
PDF 16 MB Posted
- Attached to
- Design-Build Armed Forces Medical Examiner System Facility, Dover Air Force Base, Dover, Delaware
- Solicitation number
- W912BU-09-R-0015
About this file
Amendment No. 0004
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 09R0015-SPECS-AM5.PDF | ||
| 09R0015-Specs-Am3-1.PDF | ||
| 09R0015-Dwgs-Am3.pdf | ||
| 09R0015-Specs-Am3-2.pdf | ||
| 00120 Prop Eval Factors - Attachments.doc | DOC document | |
| 09R0015-SPECS-AM2.PDF | ||
| 09R0015-SPECS-AM1.PDF | ||
| Site_Visit_Attendance_Sheet.pdf | ||
| 09R0015-Specs-VOL2-3.PDF | ||
| 09R0015-Specs-VOL1.PDF | ||
| 09R0015-Specs-VOL2-4.PDF | ||
| 09R0015-Dwgs-2.PDF | ||
| 09R0015-Specs-VOL2-5.PDF | ||
| RFI Example.xls | XLS spreadsheet | |
| 09R0015-Specs-VOL2-2.PDF | ||
| 09R0015-Dwgs-1.PDF | ||
| 09R0015-Specs-VOL2-1.PDF |
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
US ARMY ENGINEER DISTRICT, PHILADELPHIA
POC:MICHELLE L. JOHNSON
WANAMAKER BLDG
100 PENN SQUARE EAST
PHILADELPHIA PA 19107-3390
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
THE PROPOSAL RECEIPT DATE IS EXTENDED TO 2:00 P.M., LOCAL TIME ON JULY 24, 2009.
1. CONTRACT ID CODE PAGE OF PAGES
U 1
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W912BU-09-R-0015
X 9B. DATED (SEE ITEM 11)
3-June-2009
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer x is extended, is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning 0 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required) Design-Build Armed Forces Medical Examiners System Facility, Dover Air Force Base, Dover, Delaware
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
14-July-2009
CODE
US ARMY ENGINEER DISTRICT, PHILADELPHIA
CONTRACTING DIVISION
WANAMAKER BUILDING
100 PENN SQUARE EAST
PHILADELPHIA PA 19107-3390
W912BU 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE E5CTCMLJ
FACILITY CODECODE
EMAIL:TEL:
Amendment No. 0004
Request for Proposals
W912BU-09-R-0015
14. DESCRIPTION OF AMENDMENT (continued)
a. RFIs with RESPONSES: RFIs with responses, annotated Amendment No. 0004 are attached to this amendment.
b. VOLUME 1 OF 2:
(1) Section 01 10 00 STATEMENT OF WORK: Please delete the following pages in this section in their entirety and substitute the revised pages of the same numbers, annotated Amendment No. 0004, attached hereto.
(2) Section 01 33 16 DESIGN AFTER AWARD: Please delete page 21 of this section in its entirety and substitute the revised page of the same number, annotated Amendment No. 0004, attached hereto.
c. VOLUME 2 OF 2:
(1) Appendix H ROOM DATA SHEETS: Please delete the Appendix H issued by Amendment No. 0003 in its entirety. Please utilize the Appendix H included with the advertised project on 3 June 2009 found in the Specs-VOL2-3.pdf file.
(a) Please delete the following pages from that version of Appendix H in their entirety and substitute the revised pages of the same number, annotated Amendment No. 0004, attached hereto.
(b) Please add the new sheet 212.1 to that version of Appendix H.
(2) AGRAM 08-03 for fire protection redundancy, referenced in RFP, provided for your use.
d. Please indicate receipt of this amendment on Standard Form 1442 (SOLICITATION, OFFER, AND AWARD) as Amendment No. 0004. Failure to acknowledge all amendments may be cause for rejection of the bid.
RFP W912BU-09-R-0015
FOR INFORMATION ONLY
REQUESTS FOR INFORMATION with RESPONSES
Solicitation No. W912BU-09-R-0015 7/14/2009
RFI #
Dwg Sheet/Spec Section Comment Response
115 01 10 00
Paragraph 6.6.6.10(13), page 152 thru 157, refers to high density files systems. The total size of the systems (number of carriages, number of shelves per carriage, type of contents, etc.) are not provided. Please provide configuration of the systems so that a total weight can be determined for design of the slab-on-grade.
A thickened slab is indicated in the RFP already and the storage loads are indicated as well. Please price per the RFP.
116 01 10 00
Para. 6.15.1.3 states that overall fire protection design to also be in accordance with the requirements of AGRAM 08-03 for Fire Protection Redundancy. Assume this is a standard or technical directive which has not been included in the Government documents. Also cannot find on the internet. We assume that the requirements of this standard have been incorporated into the RFP. Please provide a copy of this standard or information on where it can be acquired. AGRAM 08-03 included with
Amendment No. 0004
117 01 10 00
Para. 6.15.1.4 specify that the fire protection systems design shall also incorporate the requirements of NFPA 232. This standard addresses other design requirements beyond fire protection systems per se and it is assumed that these requirements shall be applied to spaces such as the Repository and other areas that contain (storage?) of foil wrapped index cards?
Correct, NFPA 232 requirements apply only to the storage of the foil wrapped index cards. Please price per the RFP.
118 01 10 00
Para. 6.15.1.4 specify that the fire protection systems design shall also incorporate the requirements of NFPA 232. This allow for specific methods of storage based on the types of records to be stored as defined in NFPA 232 (i.e. Vital, Important, Archival material, Permanent, Active, Inactive, Unscheduled records). Based on the Type of Records and the resulting method of storage, there are specific requirements for fire ratings, method of operation of shelving, storage volume limitations smoke detection in addition to fire suppression, etc. Please define the type of records per these NFPA 232 definitions.
Please see Amendment No. 0004.
119 01 10 00
Para. 6.15.2.2 Based on the description in this paragraph and the Hazardous Materials/Chemical List In Appendix K, it is assumed that the quantities of Hazardous Materials can be accommodated by treating the entire building as one control area;
no control areas separations would be required and the structure can generally remain non-fire rated. If this is not the case, fire proofing of the structure would be likely to accommodate additional control areas especially those on the second level.
Please confirm.
Addressed in a previous RFI.
120 01 10 00
Para. 6.15.2.6 No information can be found in the Government documentation that indicates the occupancy and construction type of the existing Building 116. This is needed to confirm proper rating of the fire wall at the new/existing building juncture.
Regardless, the possible S-1 occupancy in the new building would drive the fire wall rating to 3 hours vs. 2 (IBC Table 705.4) as stated in the RFP.
The existing building is considered B Use Group and Type 2B construction. We do not see that the new building will become an S-1 use Group since the storage area is less than 10% of the building area.
Please price per the RFP.
Drawing A-01; 01 10
Para. 6.15.2.6 The fire wall is indicated to be a back to back double wall construction. By code including NFPA 221, each individual wall making up this double wall assembly would need its own fire rated opening protective (door) and a vestibule would be created between these doors with thee fire rating wrapping around each side of the vestibule; This is not currently shown. It is assumed the additional doors and vestibule will be required and shall be provided. Please confirm.
There are methods of complying with NFPA 221 that do not require vestibules. Please price per the
RFP.
RFI Answers Page 1 of 3
Appendix "H"
Appendix “H” page 301 Receiving Room (#158) – In the remarks section “Provide refrigerated section for cold storage.” Does this mean to provide a cold box or will the Owner be providing refrigerators in the room for storage? If a cold box is required please provide the size of the box?
Please see Amendment No. 0004.
123 01 10 00
Para. 5.10.4.15 Past experience has included galvanized piping for dry and preaction sprinkler systems. Not indicated in RFP. It is assume that galvanized piping is not required. Please confirm.
Addressed in a previous RFI.
Section 5.12.1.1/ Drawing CP101
Please confirm that the footprint of the building meets all ATFP standoff criteria (UFC 4-010-01 B-1.1, Table B-1) for conventional construction both from the controlled perimeter and to parking and roadways within the controlled perimeter. In order for this requirement to be met there must be continuously controlled access to the loading dock access road per UFC 4- 010-01 B-1.1.3 and B-1.3. Controlled access of the loading dock road is only shown at the south entrance to this road on sheet CP101 of the RFP. Please confirm that access is controlled currently at the north entrance to the loading dock road.
There is access control at the north entry to the loading dock. Please price per the RFP.
Section 6.8.2.8
The vibration analysis requires that all structure supporting laboratory spaces shall be stiffened to limit vibrations to 1000 micro-inches per second with a minimum footfall load of an 185 lb person walking 75 steps per minute in the laboratories and 100 steps per minute in corridors. Please confirm that this requirement is intended to be met for the entire lab area and that there are not areas within the lab space that can be designed to less stringent criteria.
Addressed in a previous RFI.
Section 3.4 and 6.18.5.1
Section 3.4, Item 1a (page 13) indicates that furniture 150 square feet and over will be tenant provided, however, Section
6.18.5.1 item (2), page 247 indicates 110 sf and larger will contain office furniture provided by the government. Which is correct?
Addressed in a previous RFI.
Section 5.3.5.1
Please clarify the format for furniture procurement documentation. Are we to specify a single manufacturer's product that meets the design criteria; specify a preferred product vendor with three alternates that also meet the guidelines or specify a generic product that can be an open bid?
Please see Amendment No. 0004.
Appendix H Page 248drawings QL102
& QL202B
Please clarify - the Lab Plan does not match Room Data Sheets. For example Reagent Prep [C7.01] does not match with respect to doors or fume hood. Unless notified otherwise, we assume Appendix H is correct.
Please see Amendment No. 0004
"QL201B
"Please Confirm / Clarify DCID 6/9 Requirements. DCID 6/9 indicates a range of possible protection levels. The following is our understanding as applicable to this project:
QY101
- the focus is to construct the area in accordance with DCID 6/9 section 3, so as to restrict and detect physical access at the perimeter of these areas by the prescribed electronic monitoring and physical barriers.
QY102 - adjacent spaces (above, below or lateral to the SCIF) are not restricted in use or required to be additionally controlled.
Section 01 10 00
- there are no TEMPEST requirements nor any additional restrictions on the material or labor sources used to construct these areas."
DCID 6/9" Correct statements. Please price per the RFP.
Section 01 10 00 page 16 # 4g. "Please clarify the statement 4g ""Lab Space built to DCID 6/9 Standards.""
Please price per the RFP.
Is the intent that this apply to each individual laboratory space as individually separate SCIFs, or collectively so that groupings of adjacent lab spaces constitute a single SCIF perimeter.
RFI Answers Page 2 of 3
Unless notified otherwise we understand groupings of adjacent lab spaces to constitute a single SCIF perimeter. For example laboratories with a common demising wall do not need to build that wall to meet DCID 6/9 or SCIF standards. "
There are specific rooms refernced on the QY drawings and in the Room Data Sheets that require SCIF Construction. Groupings of SCIF areas is not possible. Please price per the RFP.
CL101
Is the emergency generator is supposed to be within the 33 feet ATFP unobstructive zone. Unless directed otherwise, the generator will be moved outside the ATFP unobstructive zone per the RFP Section 01 10 00, 5.12.1.1 and UFC 4-010-01, 1- 6.1, definition of unobstructive space on page A-5, and Appendix B-1.1.
Emergency generator to be located outside of the 33 foot clear zone.
Please price per the RFP.
Appendix Q, 10.6.2.1
There is a contradiction regarding the location of Panelboards within the building. The Dover AFB local MILCON requires Panelboards to be mounted within an electrical room not in the corridors. RFP Section 01 10 00, 6.12.23.6 allows labs to be powered from panleboards in the cooridor outside the lab. Which method of panelboard installation is required for this project? Unless directed otherwise, the panelboards will be mounted in an electrical room except for panelboards providing power to labs, which will have panelboards mounted in the cooridor outside the lab rooms.
Addressed in a previous comment.
Appendix H, Page 54
100 foot candle requirement exceeds ASHRAE 90.1, 2004 requirement, is this value and other lab rooms illumination values correct? Unless otherwise directed, ASHRAE 90.1, 2004 standards will be used for illumenation values for the lab rooms.
Addressed in a previous comment.
RFP Section 01 10 00, 3.7.14.5
Door size indicated is 36 inches wide and the switchgear will require a larger door. Can a larger door be used to allow the proper size switchgear to be moved for installation and replacment? Unless otherwise directed, the door size will be adjusted to accommodate the switchgear dimensions.
There are a pair of 3'-0" wide doors indicated for the switchgear room on the floor plan. The referenced para is for interior electrical rooms.
Please price per the RFP.
RFP Section 01 10 00, 6.19 (1)
The RFP states, "The contractor will include all devices … to provide a fully functional and operational security system."
What are all devices? Unless otherwise directed, it will be assumed that the devices are the equipment provided by the government as stated in the paragraph in RFP 01 10 00, 6.19. Correct statement. Please price per the RFP.
E04
The estimate power requirement of the building loads, 2,500kVA will require front and back access to the Switchgear. Can the location of the switchgear and room size be modified to accommodate the switchgear to meet NEC 110 requirements?
Unless directed otherwise, it will be assumed the main electrical room size and switchgear location can be changed to meet NEC 110 requirements.
Addressed in a previous comment.
E04
The estimate power requirement of the building loads, 2,500kVA will require the ATS and room 151A to be modified to meet NFPA 70 requirements.Can the ATS and room size be modified to accommodate the ATS to meet NEC 110 requirements?
Unless directed otherwise, it will be assumed room 151A size and ATS location can be changed to meet NEC 110 requirements.
Addressed in a previous comment.
RFI Answers Page 3 of 3
SECTION 01 33 16 Page 21 each room with a voice data outlet, the type of outlet, number of outlets, number of telephones required and type of telephone required.
3.5.8.10. Design of the information systems shall include a layout of the voice/data outlets (including voice only wall phones) on telecommunication floor plan drawing, location of SIPRNET data outlets, and a legend and symbol definition to indicate height above finished floor. Show voice, data, CATV cable/conduit/raceway and cable-tray, and a System Riser Diagram. Show size of conduit and cable type and size on Riser Diagram. Do not show conduit runs between backboard and outlets on the floor plans. Show underground telephone telecommunication distribution conduit and cable with sizing from point of presence to entrance facility of building. Provide calculations showing the signal loss of the CATV system and signal to be provided to the most distant outlet.
3.5.8.11. LEED: Project checklist indicating credits claimed, all required design phase supporting documentation and completed submittals checklist.
3.6. FINAL DESIGN REVIEWS AND CONFERENCES
A final design review and review conference will be held upon completion of final design at the project installation, or – where equipment is available - by video teleconference or a combination thereof, for any design package to receive Government acceptance to allow release of the design package for construction.
For smaller separate design packages, the parties may agree on alternative reviews and conferences (e.g., conference calls and electronic file sharing, etc.) through the Partnering process. The Offeror shall include the final design conference in the project schedule and shall indicate what part of the design work is at 100% completion. The final design conference will be held after the Government has had up to seven (7) calendar days after receipt of the submission to review the final design package and supporting data. For smaller packages, especially those involving only one or a few design disciplines the parties may agree on a shorter period.
3.7. FINAL DESIGN REQUIREMENTS
Final design deliverables for a design package shall consist of 100% complete drawings, specifications, submittal register, design analysis for Government review and acceptance. The 100% design submission shall consist of drawings, specifications, and design analysis and any permits required by the contract for each package submitted. In order to expedite the final design review, prior to the conference, the Offeror shall ensure that the design configuration management data and all review comment resolutions are up-to-date. The Offeror shall also have performed independent technical reviews and back-checks of previous comment resolutions, as required by Section 01 45 04 CONTRACTOR QUALITY CONTROL.
The Offeror shall include the 100% SID and 100% FF&E binders for government approval.
3.7.1. Drawings:
3.7.1.1. Submit drawings complete with all contract requirements incorporated into the documents to provide a 100% design for each package submitted.
Appendix H Page 6
Appendix H Page 14
Appendix H Page 19
Appendix H Page 18
Appendix H Page 22
Appendix H Page 30
Appendix H Page 35
Appendix H Page 56
Appendix H Page 57
Appendix H Page 54
Appendix H Page 59
Appendix H Page 63
Appendix H Page 64
Appendix H Page 66
Appendix H Page 81
Appendix H Page 95
Appendix H Page 105
Appendix H Page 117
UTILIZATION
Hours of Use
8 hours/day
14 hours/day
24 hours/day
Hours of Operation
8 hours/day
14 hours/day
24 hours/day
MECHANICAL
Temperature
72°F ± 2°F (SET)
15 Air Changes/Hour Min.
10Air Changes/Hour Min.
6 Air Changes/Hour Min.
100% Make-up Air
Recirculated Air
Air Pressure Positive
Air Pressure Negative
Humidity
50% ± 20%
Uncontrolled
HOODS (indicate quantity and size)
Chemical Fume Hood
Radioisotope Hood
Laminar Flow Hood
Biological Safety Cabinet
Snorkel
Canopy Hood
Low Slotted Exhaust
LABORATORY EQUIPMENT
Vibration Sensitive
Light Sensitive
Vibration Producing
Heat Producing
Noise Producing
Overhead Service
REMARKS:
KEY PLAN:
PLUMBING
Laboratory Gas (LG)
Laboratory Vacuum (LV)
Laboratory Air (LA)
Compressed Air, 100 psi (A)
Hot Water (HW)
Cold Water (CW)
Pure Water Type III (0.05 MOhm)
Chilled Water (CHW S/R)
Steam/Condensate Return
Carbon Dioxide (C02)
Nitrogen Gas (N2)
Helium (He)
Hydrogen (H)
Oxygen (O2)
Floor Drain (FD)
Floor Sink (FS)
Safety Shower (SS)
Drench Hose (DH)
ELECTRICAL
110V, 20A, 1 Phase
208V, 30A, 1 Phase
208V, 30A, 3 Phase
480V, 100A, 3 Phase
Isolated Ground Outlet
Emergency Power
Phone
Data - Wired
LIGHTING
"In Use" Light
Task Lighting
Lighting Level
100 fc at bench/desk
60 fc at bench/desk
Dimmable
Zoned Lighting
CHEMICALS
Bases
Acids
Solvents
Radioisotopes
Carcinogens/Regulated
Chemical Waste Storage
Biological Storage
Radioisotope Storage
Chemical Storage
ARCHITECTURAL
Floor
VCT (ESD/CR)
VCT
Sheet Vinyl
Epoxy
Carpet
Sealed Concrete
Partitions
GWB, Epoxy Paint
GWB, Paint
Other
Base
Integral w/floor
Ceiling
Open
Acoustic Tile
Gyp Board, Height
Doors
3'-6" x 8'
3' x 8'
Uneven
Vision Panel
Natural Daylight
LABORATORY CASEWORK
ROOM NAME:
SECTION:
CONTACT:
PHONE:
FAX:
E-MAIL:
ROOM ID:
Standard
Eyewash (EW)
Darkenable
Sink
Data - Wireless
Benchtop Material
Casework Material
68°F-75°F ± 2°F (VAR)
Other
Other
Pure Water Type II (1.0 MOhm)
Pure Water Type I (18 MOhm)
Other
Other
Other
Other
Other
Other
Other
Other
Other
UPS Power
Emergency Operation
100% Uptime
Reduced Capability
N/A
Other
DIVISION:
4'-0" x 8'
X
X
X
Locate condensing unit above room; access from service corridor
X
X
X
X
X
X
SHELVING
7'-6" min
WALK-IN -20C FREEZER (LONG TERM STORAGE)
D1.04
D. FORENSIC TOXICOLOGY
65% max
BAS interface for remote monitoring/alarm
All finishes by room manufacturer/card reader
X
X
D1. ADMIN
-20C +/-0.5C
Space Requirements
Amendment No. 0003AFMES Facility at Dover AFB 07.16025.02
Amendment No. 0004
Appendix H Page 96
FD
SHELVING
6A
4'0 8' 16'
ELECTRICAL LEGEND
Duplex Outlet (110 V)
Quadruplex Outlet (110 V)
Specialty Outlet
Communication Outlet
Emergency PowerEP
Uninterruptable PowerUP
PLUMBING LEGEND
AIR Compressed Air CG Cylinder Gas CO2 Carbon Dioxide CHW Chilled Water CW Cold Water EW Eye Wash/Drench Hose FD Floor Drain FS Floor Sink G Gas HCW Hot & Cold Water N2 Nitrogen PW Pure Water VAC Vacuum AR Argon DI Distilled HE Helium CS Cup Sink
FURNISHINGS / EQUIPMENT
1. Chemical Fume Hood
2. Biological Safety Cabinet, UAFI
3. Radioisotope Hood
4. Laminar Flow Cabinet, UAFI
5. Snorkel Exhaust 6A. Fixed Lab Bench 30"Deep (standing height)
7. Fixed Lab Bench (sitting height)
8. Mobile Lab Bench (variable height), UAFI
9. Desk / Write-Up Station, UAFI
10. Wall Cabinet
11. Adjustable Shelves
12. Tall Storage Cabinet
13. Flammable Storage Cabinet
14. Equipment Space
16. Cup Sink
17. Scullery Sink
18. Cylinder Bracket
19. Safety Shower / Eyewash
20. Overhead Service Carrier
21. Pipe Drop Enclosure
22. Glasswasher
23. Autoclave
24. Icemaker, UAFI
25. White Markerboard, UAFI
26. Hook Strip
27. Laboratory Table, UAFI
28. Freezer, UAFI
29. Refrigerator, UAFI
30. PCR Hood, UAFI
15. Laboratory Sink
UAFI : User Agency Furnished and Installed
31. Bone Sanding Hood, UAFI
32. Metro Shelving 5'w x 8'h
6B. Fixed Lab Bench 24"Deep (standing height)
Space Diagram
This diagram is conceptual and is provided only to indicate required furnishings equipment, and general room proportions. The actual room design may change.
NAME
ROOM NUMBER
Amendment No. 0003AFMES Facility at Dover AFB 07.16025.02
WALK-IN -20C FREEZER (LTS)
D1.04A
Amendment No. 0004
Appendix H Page 97
8 hours/day
14 hours/day
24 hours/day
Hours of Operation
8 hours/day
14 hours/day
24 hours/day
MECHANICAL
Temperature
72°F ± 2°F (SET)
15 Air Changes/Hour Min.
10Air Changes/Hour Min.
6 Air Changes/Hour Min.
100% Make-up Air
Recirculated Air
Air Pressure Positive
Air Pressure Negative
Humidity
50% ± 20%
Uncontrolled
HOODS (indicate quantity and size)
Chemical Fume Hood
Radioisotope Hood
Laminar Flow Hood
Biological Safety Cabinet
Snorkel
Canopy Hood
Low Slotted Exhaust
LABORATORY EQUIPMENT
Vibration Sensitive
Light Sensitive
Vibration Producing
Heat Producing
Noise Producing
Overhead Service
REMARKS:
KEY PLAN:
PLUMBING
Laboratory Gas (LG)
Laboratory Vacuum (LV)
Laboratory Air (LA)
Compressed Air, 100 psi (A)
Hot Water (HW)
Cold Water (CW)
Pure Water Type III (0.05 MOhm)
Chilled Water (CHW S/R)
Steam/Condensate Return
Carbon Dioxide (C02)
Nitrogen Gas (N2)
Helium (He)
Hydrogen (H)
Oxygen (O2)
Floor Drain (FD)
Floor Sink (FS)
Safety Shower (SS)
Drench Hose (DH)
ELECTRICAL
110V, 20A, 1 Phase
208V, 30A, 1 Phase
208V, 30A, 3 Phase
480V, 100A, 3 Phase
Isolated Ground Outlet
Emergency Power
Phone
Data - Wired
LIGHTING
"In Use" Light
Task Lighting
Lighting Level
100 fc at bench/desk
60 fc at bench/desk
Dimmable
Zoned Lighting
CHEMICALS
Bases
Acids
Solvents
Radioisotopes
Carcinogens/Regulated
Chemical Waste Storage
Biological Storage
Radioisotope Storage
Chemical Storage
ARCHITECTURAL
Floor
VCT (ESD/CR)
VCT
Sheet Vinyl
Epoxy
Carpet
Sealed Concrete
Partitions
GWB, Epoxy Paint
GWB, Paint
Other
Base
Integral w/floor
Ceiling
Open
Acoustic Tile
Gyp Board, Height
Doors
3'-6" x 8'
3' x 8'
Uneven
Vision Panel
Natural Daylight
LABORATORY CASEWORK
ROOM NAME:
SECTION:
CONTACT:
PHONE:
FAX:
E-MAIL:
ROOM ID:
Standard
Eyewash (EW)
Darkenable
Sink
Data - Wireless
Benchtop Material
Casework Material
68°F-75°F ± 2°F (VAR)
Other
Other
Pure Water Type II (1.0 MOhm)
Pure Water Type I (18 MOhm)
Other
Other
Other
Other
Other
Other
Other
Other
Other
UPS Power
Emergency Operation
100% Uptime
Reduced Capability
N/A
Other
DIVISION:
4'-0" x 8'
X
X
X
X
X
X
X
X
X
This space is designated for research and development of new detection techniques in support of the division’s missions, as well as short term or unique missions such as training kit development for the military drug dog program; locate remotely from other laboratories
X
X
X
X
X
X
X
X
X
X
X
2X
4X
X
X
X
X
X
Wire mesh security partition w/i room
X
Lab standard
X
X
X
SPECIAL PROJECTS
D2.01
D. FORENSIC TOXICOLOGY
X
X
Epoxy
Steel
X
X
CCTV monitoring
Controlled substances
Securtiy 24 hour monitored alarm with motion detector/card reader
X
X
D2. RESEARCH / SPECIAL PROJECTS
Space Requirements
Amendment No. 0003AFMES Facility at Dover AFB 07.16025.02
Amendment No. 0004
Appendix H Page 103
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
HCW
PW
EW
CW
CS
AIR
VAC
SS
OUTLETS @ 24" O.C. IN
2 CHANNEL ELEC.
RACEWAY, TYP.
@ PERIMETER WALLS
ONE SPECIALTY OUTLET
PER 15' OF BENCH TYP.
MIN (1) PER LAB
OUTLETS @ 60" O.C.
@ LAB BENCHES
WITH MIN.(1)
SPECIALTY OUTLET
EVERY 10'-0"
WIRE MESH SECURITY
PARTITION AND DOOR
WITHIN ROOM
6A
VAC
FD
4'0 8' 16'
ELECTRICAL LEGEND
Duplex Outlet (110 V)
Quadruplex Outlet (110 V)
Specialty Outlet
Communication Outlet
Emergency PowerEP
Uninterruptable PowerUP
PLUMBING LEGEND
AIR Compressed Air CG Cylinder Gas CO2 Carbon Dioxide CHW Chilled Water CW Cold Water EW Eye Wash/Drench Hose FD Floor Drain FS Floor Sink G Gas HCW Hot & Cold Water N2 Nitrogen PW Pure Water VAC Vacuum AR Argon DI Distilled HE Helium CS Cup Sink
FURNISHINGS / EQUIPMENT
1. Chemical Fume Hood
2. Biological Safety Cabinet, UAFI
3. Radioisotope Hood
4. Laminar Flow Cabinet, UAFI
5. Snorkel Exhaust 6A. Fixed Lab Bench 30"Deep (standing height)
7. Fixed Lab Bench (sitting height)
8. Mobile Lab Bench (variable height), UAFI
9. Desk / Write-Up Station, UAFI
10. Wall Cabinet
11. Adjustable Shelves
12. Tall Storage Cabinet
13. Flammable Storage Cabinet
14. Equipment Space
16. Cup Sink
17. Scullery Sink
18. Cylinder Bracket
19. Safety Shower / Eyewash
20. Overhead Service Carrier
21. Pipe Drop Enclosure
22. Glasswasher
23. Autoclave
24. Icemaker, UAFI
25. White Markerboard, UAFI
26. Hook Strip
27. Laboratory Table, UAFI
28. Freezer, UAFI
29. Refrigerator, UAFI
30. PCR Hood, UAFI
15. Laboratory Sink
UAFI : User Agency Furnished and Installed
31. Bone Sanding Hood, UAFI
32. Metro Shelving 5'w x 8'h
6B. Fixed Lab Bench 24"Deep (standing height)
Space Diagram
This diagram is conceptual and is provided only to indicate required furnishings equipment, and general room proportions. The actual room design may change.
NAME
ROOM NUMBER
Amendment No. 0003AFMES Facility at Dover AFB 07.16025.02
SPECIAL PROJECTS
D2.01A
Amendment No. 0004
Appendix H Page 104
8 hours/day
14 hours/day
24 hours/day
Hours of Operation
8 hours/day
14 hours/day
24 hours/day
MECHANICAL
Temperature
72°F ± 2°F (SET)
15 Air Changes/Hour Min.
10Air Changes/Hour Min.
6 Air Changes/Hour Min.
100% Make-up Air
Recirculated Air
Air Pressure Positive
Air Pressure Negative
Humidity
50% ± 20%
Uncontrolled
HOODS (indicate quantity and size)
Chemical Fume Hood
Radioisotope Hood
Laminar Flow Hood
Biological Safety Cabinet
Snorkel
Canopy Hood
Low Slotted Exhaust
LABORATORY EQUIPMENT
Vibration Sensitive
Light Sensitive
Vibration Producing
Heat Producing
Noise Producing
Overhead Service
REMARKS:
KEY PLAN:
PLUMBING
Laboratory Gas (LG)
Laboratory Vacuum (LV)
Laboratory Air (LA)
Compressed Air, 100 psi (A)
Hot Water (HW)
Cold Water (CW)
Pure Water Type III (0.05 MOhm)
Chilled Water (CHW S/R)
Steam/Condensate Return
Carbon Dioxide (C02)
Nitrogen Gas (N2)
Helium (He)
Hydrogen (H)
Oxygen (O2)
Floor Drain (FD)
Floor Sink (FS)
Safety Shower (SS)
Drench Hose (DH)
ELECTRICAL
110V, 20A, 1 Phase
208V, 30A, 1 Phase
208V, 30A, 3 Phase
480V, 100A, 3 Phase
Isolated Ground Outlet
Emergency Power
Phone
Data - Wired
LIGHTING
"In Use" Light
Task Lighting
Lighting Level
100 fc at bench/desk
60 fc at bench/desk
Dimmable
Zoned Lighting
CHEMICALS
Bases
Acids
Solvents
Radioisotopes
Carcinogens/Regulated
Chemical Waste Storage
Biological Storage
Radioisotope Storage
Chemical Storage
ARCHITECTURAL
Floor
VCT (ESD/CR)
VCT
Sheet Vinyl
Epoxy
Carpet
Sealed Concrete
Partitions
GWB, Epoxy Paint
GWB, Paint
Other
Base
Integral w/floor
Ceiling
Open
Acoustic Tile
Gyp Board, Height
Doors
3'-6" x 8'
3' x 8'
Uneven
Vision Panel
Natural Daylight
LABORATORY CASEWORK
ROOM NAME:
SECTION:
CONTACT:
PHONE:
FAX:
E-MAIL:
ROOM ID:
Standard
Eyewash (EW)
Darkenable
Sink
Data - Wireless
Benchtop Material
Casework Material
68°F-75°F ± 2°F (VAR)
Other
Other
Pure Water Type II (1.0 MOhm)
Pure Water Type I (18 MOhm)
Other
Other
Other
Other
Other
Other
Other
Other
Other
UPS Power
Emergency Operation
100% Uptime
Reduced Capability
N/A
Other
DIVISION:
4'-0" x 8'
X
X
X
X
X
X
X
X
This space is designated for toxicology screening of samples using automated immunoassays
X
X
X
X
X
X
X
1X
8X
X
X
X
X
X
X
X
X
X
X
Lab standard
X
X
X
X
IMMUNOASSAY / SCREENING
D3.01
D. FORENSIC TOXICOLOGY
X
X
Epoxy
Steel
X
Supply air hydrocarbon filtration
X
CO, 2 FLOOR DRAINS
View windows from personnel corridor/card reader
X
X
D3. POSTMORTEM / HUMAN PERFORMANCE LAB
Space Requirements
Amendment No. 0003AFMES Facility at Dover AFB 07.16025.02
Amendment No. 0004
Appendix H Page 102
SS
HCW
PW
EW
FD
FD
AIR
VAC
AIR
VAC
AIR
VAC
AIR
VAC
AIR
VAC
HCW
PW
EW
6A
6A
6A
AIR
VAC
AIR
VAC
AIR
VAC
AIR
VAC
AIR
VAC
AIR
VAC
AIR
VAC
AIR
VAC
AIR
VAC
AIR
VAC
AIR
VAC
AIR
VAC
AIR
VAC
AIR
VAC
AIR
VAC
AIR
VAC
OUTLETS @ 24" O.C. IN
2 CHANNEL ELEC.
RACEWAY, TYP.
@ PERIMETER WALLS
ONE SPECIALTY OUTLET
PER 15' OF BENCH TYP.
MIN (1) PER LAB
OUTLETS @ 60" O.C.
@ LAB BENCHES
WITH MIN.(1)
SPECIALTY OUTLET
EVERY 10'-0"
1414 1414
11 6A
29 29
AI
R
VA
C
N
AI
R
VA
C
13 111
6A10 10 15
VAC
AIR
4'0 8' 16'
ELECTRICAL LEGEND
Duplex Outlet (110 V)
Quadruplex Outlet (110 V)
Specialty Outlet
Communication Outlet
Emergency PowerEP
Uninterruptable PowerUP
PLUMBING LEGEND
AIR Compressed Air CG Cylinder Gas CO2 Carbon Dioxide CHW Chilled Water CW Cold Water EW Eye Wash/Drench Hose FD Floor Drain FS Floor Sink G Gas HCW Hot & Cold Water N2 Nitrogen PW Pure Water VAC Vacuum AR Argon DI Distilled HE Helium CS Cup Sink
FURNISHINGS / EQUIPMENT
1. Chemical Fume Hood
2. Biological Safety Cabinet, UAFI
3. Radioisotope Hood
4. Laminar Flow Cabinet, UAFI
5. Snorkel Exhaust 6A. Fixed Lab Bench 30"Deep (standing height)
7. Fixed Lab Bench (sitting height)
8. Mobile Lab Bench (variable height), UAFI
9. Desk / Write-Up Station, UAFI
10. Wall Cabinet
11. Adjustable Shelves
12. Tall Storage Cabinet
13. Flammable Storage Cabinet
14. Equipment Space
16. Cup Sink
17. Scullery Sink
18. Cylinder Bracket
19. Safety Shower / Eyewash
20. Overhead Service Carrier
21. Pipe Drop Enclosure
22. Glasswasher
23. Autoclave
24. Icemaker, UAFI
25. White Markerboard, UAFI
26. Hook Strip
27. Laboratory Table, UAFI
28. Freezer, UAFI
29. Refrigerator, UAFI
30. PCR Hood, UAFI
15. Laboratory Sink
UAFI : User Agency Furnished and Installed
31. Bone Sanding Hood, UAFI
32. Metro Shelving 5'w x 8'h
6B. Fixed Lab Bench 24"Deep (standing height)
Space Diagram
This diagram is conceptual and is provided only to indicate required furnishings equipment, and general room proportions. The actual room design may change.
NAME
ROOM NUMBER
Amendment No. 0003AFMES Facility at Dover AFB 07.16025.02
IMMUNOASSAY / SCREENING
D3.01A
Amendment No. 0004
Appendix H Page 123
8 hours/day
14 hours/day
24 hours/day
Hours of Operation
8 hours/day
14 hours/day
24 hours/day
MECHANICAL
Temperature
72°F ± 2°F (SET)
15 Air Changes/Hour Min.
10Air Changes/Hour Min.
6 Air Changes/Hour Min.
100% Make-up Air
Recirculated Air
Air Pressure Positive
Air Pressure Negative
Humidity
50% ± 20%
Uncontrolled
HOODS (indicate quantity and size)
Chemical Fume Hood
Radioisotope Hood
Laminar Flow Hood
Biological Safety Cabinet
Snorkel
Canopy Hood
Low Slotted Exhaust
LABORATORY EQUIPMENT
Vibration Sensitive
Light Sensitive
Vibration Producing
Heat Producing
Noise Producing
Overhead Service
REMARKS:
KEY PLAN:
PLUMBING
Laboratory Gas (LG)
Laboratory Vacuum (LV)
Laboratory Air (LA)
Compressed Air, 100 psi (A)
Hot Water (HW)
Cold Water (CW)
Pure Water Type III (0.05 MOhm)
Chilled Water (CHW S/R)
Steam/Condensate Return
Carbon Dioxide (C02)
Nitrogen Gas (N2)
Helium (He)
Hydrogen (H)
Oxygen (O2)
Floor Drain (FD)
Floor Sink (FS)
Safety Shower (SS)
Drench Hose (DH)
ELECTRICAL
110V, 20A, 1 Phase
208V, 30A, 1 Phase
208V, 30A, 3 Phase
480V, 100A, 3 Phase
Isolated Ground Outlet
Emergency Power
Phone
Data - Wired
LIGHTING
"In Use" Light
Task Lighting
Lighting Level
100 fc at bench/desk
60 fc at bench/desk
Dimmable
Zoned Lighting
CHEMICALS
Bases
Acids
Solvents
Radioisotopes
Carcinogens/Regulated
Chemical Waste Storage
Biological Storage
Radioisotope Storage
Chemical Storage
ARCHITECTURAL
Floor
VCT (ESD/CR)
VCT
Sheet Vinyl
Epoxy
Carpet
Sealed Concrete
Partitions
GWB, Epoxy Paint
GWB, Paint
Other
Base
Integral w/floor
Ceiling
Open
Acoustic Tile
Gyp Board, Height
Doors
3'-6" x 8'
3' x 8'
Uneven
Vision Panel
Natural Daylight
LABORATORY CASEWORK
ROOM NAME:
SECTION:
CONTACT:
PHONE:
FAX:
E-MAIL:
ROOM ID:
Standard
Eyewash (EW)
Darkenable
Sink
Data - Wireless
Benchtop Material
Casework Material
68°F-75°F ± 2°F (VAR)
Other
Other
Pure Water Type II (1.0 MOhm)
Pure Water Type I (18 MOhm)
Other
Other
Other
Other
Other
Other
Other
Other
Other
UPS Power
Emergency Operation
100% Uptime
Reduced Capability
N/A
Other
DIVISION:
4'-0" x 8'
X
X
X
X
X
X
6X
X
This space is designated for extraction of samples for analysis of accessioned materials
X
X
X
X
X
X
X
X
X
X
2X
6X
X
X
X
X
X
X
X
X
X
Lab standard
X
X
X
EXTRACTION
D3.02
D. FORENSIC TOXICOLOGY
X
X
X
Epoxy
Steel
X
Supply air hydrocarbon filtration
X
Pure, small mol gas manifolds
View windows from personnel corridor/card reader on both entry doors
X
X
D3. POSTMORTEM / HUMAN PERFORMANCE LAB
Space Requirements
Amendment No. 0003AFMES Facility at Dover AFB 07.16025.02
Amendment No. 0004
Appendix H Page 124
113 113
113 113
C W
C S
C W
C S
C W
C S
C W
C S
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
VAC
AIR
N2
5 5
5 5
5 5
5 5
5 5
5 5
5 5
5 521
6A
6A
6A
6A
SS
HCW
PW
EW HCW
PW
EW
AIR
VAC
AIR
VAC
AIR
VAC
AIR
VAC
OUTLETS @ 24" O.C. IN
2 CHANNEL ELEC.
RACEWAY, TYP.
@ PERIMETER WALLS
ONE SPECIALTY OUTLET
PER 15' OF BENCH TYP.
MIN (1) PER LAB
OUTLETS @ 60" O.C.
@ LAB BENCHES
WITH MIN.(1)
SPECIALTY OUTLET
EVERY 10'-0"
8 20 11 8 20 11 8 20 11 8 20 11
13 CW
CS
CW
CS
28 29 29 6A 29 29 28 28
AIR
VAC
N2
AI
R
VA
C
N
AI
R
VA
C
N
AI
R
VA
C
N
AI
R
VA
C
N
AIR
VAC
N2
4'0 8' 16'
ELECTRICAL LEGEND
Duplex Outlet (110 V)
Quadruplex Outlet (110 V)
Specialty Outlet
Communication Outlet
Emergency PowerEP
Uninterruptable PowerUP
PLUMBING LEGEND
AIR Compressed Air CG Cylinder Gas CO2 Carbon Dioxide CHW Chilled Water CW Cold Water EW Eye Wash/Drench Hose FD Floor Drain FS Floor Sink G Gas HCW Hot & Cold Water N2 Nitrogen PW Pure Water VAC Vacuum AR Argon DI Distilled HE Helium CS Cup Sink
FURNISHINGS / EQUIPMENT
1. Chemical Fume Hood
2. Biological Safety Cabinet, UAFI
3. Radioisotope Hood
4. Laminar Flow Cabinet, UAFI
5. Snorkel Exhaust 6A. Fixed Lab Bench 30"Deep (standing height)
7. Fixed Lab Bench (sitting height)
8. Mobile Lab Bench (variable height), UAFI
9. Desk / Write-Up Station, UAFI
10. Wall Cabinet
11. Adjustable Shelves
12. Tall Storage Cabinet
13. Flammable Storage Cabinet
14. Equipment Space
16. Cup Sink
17. Scullery Sink
18. Cylinder Bracket
19. Safety Shower / Eyewash
20. Overhead Service Carrier
21. Pipe Drop Enclosure
22. Glasswasher
23. Autoclave
24. Icemaker, UAFI
25. White Markerboard, UAFI
26. Hook Strip
27. Laboratory Table, UAFI
28. Freezer, UAFI
29. Refrigerator, UAFI
30. PCR Hood, UAFI
15. Laboratory Sink
UAFI : User Agency Furnished and Installed
31. Bone Sanding Hood, UAFI
32. Metro Shelving 5'w x 8'h
6B. Fixed Lab Bench 24"Deep (standing height)
Space Diagram
This diagram is conceptual and is provided only to indicate required furnishings equipment, and general room proportions. The actual room design may change.
NAME
ROOM NUMBER
Amendment No. 0003AFMES Facility at Dover AFB 07.16025.02
EXTRACTION
D3.02A
Amendment No. 0004
Appendix H Page 125
8 hours/day
14 hours/day
24 hours/day
Hours of Operation
8 hours/day
14 hours/day
24 hours/day
MECHANICAL
Temperature
72°F ± 2°F (SET)
15 Air Changes/Hour Min.
10Air Changes/Hour Min.
6 Air Changes/Hour Min.
100% Make-up Air
Recirculated Air
Air Pressure Positive
Air Pressure Negative
Humidity
50% ± 20%
Uncontrolled
HOODS (indicate quantity and size)
Chemical Fume Hood
Radioisotope Hood
Laminar Flow Hood
Biological Safety Cabinet
Snorkel
Canopy Hood
Low Slotted Exhaust
LABORATORY EQUIPMENT
Vibration Sensitive
Light Sensitive
Vibration Producing
Heat Producing
Noise Producing
Overhead Service
REMARKS:
KEY PLAN:
PLUMBING
Laboratory Gas (LG)
Laboratory Vacuum (LV)
Laboratory Air (LA)
Compressed Air, 100 psi (A)
Hot Water (HW)
Cold Water (CW)
Pure Water Type III (0.05 MOhm)
Chilled Water (CHW S/R)
Steam/Condensate Return
Carbon Dioxide (C02)
Nitrogen Gas (N2)
Helium (He)
Hydrogen (H)
Oxygen (O2)
Floor Drain (FD)
Floor Sink (FS)
Safety Shower (SS)
Drench Hose (DH)
ELECTRICAL
110V, 20A, 1 Phase
208V, 30A, 1 Phase
208V, 30A, 3 Phase
480V, 100A, 3 Phase
Isolated Ground Outlet
Emergency Power
Phone
Data - Wired
LIGHTING
"In Use" Light
Task Lighting
Lighting Level
100 fc at bench/desk
60 fc at bench/desk
Dimmable
Zoned Lighting
CHEMICALS
Bases
Acids
Solvents
Radioisotopes
Carcinogens/Regulated
Chemical Waste Storage
Biological Storage
Radioisotope Storage
Chemical Storage
ARCHITECTURAL
Floor
VCT (ESD/CR)
VCT
Sheet Vinyl
Epoxy
Carpet
Sealed Concrete
Partitions
GWB, Epoxy Paint
GWB, Paint
Other
Base
Integral w/floor
Ceiling
Open
Acoustic Tile
Gyp Board, Height
Doors
3'-6" x 8'
3' x 8'
Uneven
Vision Panel
Natural Daylight
LABORATORY CASEWORK
ROOM NAME:
SECTION:
CONTACT:
PHONE:
FAX:
E-MAIL:
ROOM ID:
Standard
Eyewash (EW)
Darkenable
Sink
Data - Wireless
Benchtop Material
Casework Material
68°F-75°F ± 2°F (VAR)
Other
Other
Pure Water Type II (1.0 MOhm)
Pure Water Type I (18 MOhm)
Other
Other
Other
Other
Other
Other
Other
Other
Other
UPS Power
Emergency Operation
100% Uptime
Reduced Capability
N/A
Other
DIVISION:
4'-0" x 8'
X
X
X
X
X
To airlock
Airlock to corridor
X
X
X
X
This space is designated for automated analysis of samples using GC/MS and LC/MS instruments
X
X
X
X
X
X
X
X
X
2X
8X
X
X
X
X
X
X
Lab standard
X
X
X
INSTRUMENT
D3.03
D. FORENSIC TOXICOLOGY
X
X
Epoxy
Steel
X
Supp;y air hydrocarbon filtration
X
Pure, small mol gas manifolds, Argon
View windows from personnel corridor/card reader
X
X
D3. POSTMORTEM / HUMAN PERFORMANCE LAB
Space Requirements
Amendment No. 0003AFMES Facility at Dover AFB 07.16025.02
Amendment No. 0004
Appendix H Page 126
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
AIR
N2
HE
AR
8 8 8 8 8 8 8 8 8
8 8 8 8 8 8
14 14
AIR
VAC
AIR
VAC
6A
AIR
VAC
6A
OUTLETS @ 24" O.C. IN
2 CHANNEL ELEC.
RACEWAY, TYP.
@ PERIMETER WALLS
ONE SPECIALTY OUTLET
PER 15' OF BENCH TYP.
MIN (1) PER LAB
OUTLETS @ 60" O.C.
@ LAB BENCHES
WITH MIN.(1)
SPECIALTY OUTLET
EVERY 10'-0"
VESTIBULE
D3.03
D3. POSTMORTEM / HUMAN
PERFORMANCE LAB
VESTIBULE
D3.03
D3. POSTMORTEM / HUMAN
PERFORMANCE LAB
20 11 20 11 20 11 20 11 20 11
20 11 20 11 20 11
HCW
EW
PW
AIR
VAC
12 1212
4'0 8' 16'
ELECTRICAL LEGEND
Duplex Outlet (110 V)
Quadruplex Outlet (110 V)
Specialty Outlet
Communication Outlet
Emergency PowerEP
Uninterruptable PowerUP
PLUMBING LEGEND
AIR Compressed Air CG Cylinder Gas CO2 Carbon Dioxide CHW Chilled Water CW Cold Water EW Eye Wash/Drench Hose FD Floor Drain FS Floor Sink G Gas HCW Hot & Cold Water N2 Nitrogen PW Pure Water VAC Vacuum AR Argon DI Distilled HE Helium CS Cup Sink
FURNISHINGS / EQUIPMENT
1. Chemical Fume Hood
2. Biological Safety Cabinet, UAFI
3. Radioisotope Hood
4. Laminar Flow Cabinet, UAFI
5. Snorkel Exhaust 6A. Fixed Lab Bench 30"Deep (standing height)
7. Fixed Lab Bench (sitting height)
8. Mobile Lab Bench (variable height), UAFI
9. Desk / Write-Up Station, UAFI
10. Wall Cabinet
11. Adjustable Shelves
12. Tall Storage Cabinet
13. Flammable Storage Cabinet
14. Equipment Space
16. Cup Sink
17. Scullery Sink
18. Cylinder Bracket
19. Safety Shower / Eyewash
20. Overhead Service Carrier
21. Pipe Drop Enclosure
22. Glasswasher
23. Autoclave
24. Icemaker, UAFI
25. White Markerboard, UAFI
26. Hook Strip
27. Laboratory Table, UAFI
28. Freezer, UAFI
29. Refrigerator, UAFI
30. PCR Hood, UAFI
15. Laboratory Sink
UAFI : User Agency Furnished and Installed
31. Bone Sanding Hood, UAFI
32. Metro Shelving 5'w x 8'h
6B. Fixed Lab Bench 24"Deep (standing height)
Space Diagram
This diagram is conceptual and is provided only to indicate required furnishings equipment, and general room proportions. The actual room design may change.
NAME
ROOM NUMBER
Amendment No. 0003AFMES Facility at Dover AFB 07.16025.02
INSTRUMENT
D3.03A
Amendment No. 0004
Appendix H Page 127
8 hours/day
14 hours/day
24 hours/day
Hours of Operation
8 hours/day
14 hours/day
24 hours/day
MECHANICAL
Temperature
72°F ± 2°F (SET)
15 Air Changes/Hour Min.
10Air Changes/Hour Min.
6 Air Changes/Hour Min.
100% Make-up Air
Recirculated Air
Air Pressure Positive
Air Pressure Negative
Humidity
50% ± 20%
Uncontrolled
HOODS (indicate quantity and size)
Chemical Fume Hood
Radioisotope Hood
Laminar Flow Hood
Biological Safety Cabinet
Snorkel
Canopy Hood
Low Slotted Exhaust
LABORATORY EQUIPMENT
Vibration Sensitive
Light Sensitive
Vibration Producing
Heat Producing
Noise Producing
Overhead Service
REMARKS:
KEY PLAN:
PLUMBING
Laboratory Gas (LG)
Laboratory Vacuum (LV)
Laboratory Air (LA)
Compressed Air, 100 psi (A)
Hot Water (HW)
Cold Water (CW)
Pure Water Type III (0.05 MOhm)
Chilled Water (CHW S/R)
Steam/Condensate Return
Carbon Dioxide (C02)
Nitrogen Gas (N2)
Helium (He)
Hydrogen (H)
Oxygen (O2)
Floor Drain (FD)
Floor Sink (FS)
Safety Shower (SS)
Drench Hose (DH)
ELECTRICAL
110V, 20A, 1 Phase
208V, 30A, 1 Phase
208V, 30A, 3 Phase
480V, 100A, 3 Phase
Isolated Ground Outlet
Emergency Power
Phone
Data - Wired
LIGHTING
"In Use" Light
Task Lighting
Lighting Level
100 fc at bench/desk
60 fc at bench/desk
Dimmable
Zoned Lighting
CHEMICALS
Bases
Acids
Solvents
Radioisotopes
Carcinogens/Regulated
Chemical Waste Storage
Biological Storage
Radioisotope Storage
Chemical Storage
ARCHITECTURAL
Floor
VCT (ESD/CR)
VCT
Sheet Vinyl
Epoxy
Carpet
Sealed Concrete
Partitions
GWB, Epoxy Paint
GWB, Paint
Other
Base
Integral w/floor
Ceiling
Open
Acoustic Tile
Gyp Board, Height
Doors
3'-6" x 8'
3' x 8'
Uneven
Vision Panel
Natural Daylight
LABORATORY CASEWORK
ROOM NAME:
SECTION:
CONTACT:
PHONE:
FAX:
E-MAIL:
ROOM ID:
Standard
Eyewash (EW)
Darkenable
Sink
Data - Wireless
Benchtop Material
Casework Material
68°F-75°F ± 2°F (VAR)
Other
Other
Pure Water Type II (1.0 MOhm)
Pure Water Type I (18 MOhm)
Other
Other
Other
Other
Other
Other
Other
Other
Other
UPS Power
Emergency Operation
100% Uptime
Reduced Capability
N/A
Other
DIVISION:
4'-0" x 8'
X
X
X
X
X
To airlock
Airlock to corridor
X
X
X
This space is designated for preparation and toxicology screening of samples for volatile compounds using automated analyzers
X
X
X
X
X
X
X
X
X
1X
7X
X
X
X
X
X
X
Lab standard
X
X
X
VOLATILE ANALYSIS
D3.04
D. FORENSIC TOXICOLOGY
X
X
Epoxy
Steel
X
Supp;y air hydrocarbon filtration
X
Pure, small mol gas manifolds, CO alarm hard-wired outside chemical fume hood
View windows from personnel corridor/card reader
X
X
D3. POSTMORTEM / HUMAN PERFORMANCE LAB
Space Requirements
Amendment No. 0003AFMES Facility at Dover AFB 07.16025.02
Amendment No. 0004
Appendix H Page 128
OUTLETS @ 24" O.C. IN
2 CHANNEL ELEC.
RACEWAY, TYP.
@ PERIMETER WALLS
ONE SPECIALTY OUTLET
PER 15' OF BENCH TYP.
MIN (1) PER LAB
HCW
PW
EW
CW
CS
AIR
VAC
AIR
VAC
6A
HE
AIR
N2
HE
AIR
N2
HE
AIR
N2
HE
AIR
N2
12 12
AIR
VAC
N2
4'0 8' 16'
ELECTRICAL LEGEND
Duplex Outlet (110 V)
Quadruplex Outlet (110 V)
Specialty Outlet
Communication Outlet
Emergency PowerEP
Uninterruptable PowerUP
PLUMBING LEGEND
AIR Compressed Air CG Cylinder Gas CO2 Carbon Dioxide CHW Chilled Water CW Cold Water EW Eye Wash/Drench Hose FD Floor Drain FS Floor Sink G Gas HCW Hot & Cold Water N2 Nitrogen PW Pure Water VAC Vacuum AR Argon DI Distilled HE Helium CS Cup Sink
FURNISHINGS / EQUIPMENT
1. Chemical Fume Hood
2. Biological Safety Cabinet, UAFI
3. Radioisotope Hood
4. Laminar Flow Cabinet, UAFI
5. Snorkel Exhaust 6A. Fixed Lab Bench 30"Deep (standing height)
7. Fixed Lab Bench (sitting height)
8. Mobile Lab Bench (variable height), UAFI
9. Desk / Write-Up Station, UAFI
10. Wall Cabinet
11. Adjustable Shelves
12. Tall Storage Cabinet
13. Flammable Storage Cabinet
14. Equipment Space
16. Cup Sink
17. Scullery Sink
18. Cylinder Bracket
19. Safety Shower / Eyewash
20. Overhead Service Carrier
21. Pipe Drop Enclosure
22. Glasswasher
23. Autoclave
24. Icemaker, UAFI
25. White Markerboard, UAFI
26. Hook Strip
27. Laboratory Table, UAFI
28. Freezer, UAFI
29. Refrigerator, UAFI
30. PCR Hood, UAFI
15. Laboratory Sink
UAFI : User Agency Furnished and Installed
31. Bone Sanding Hood, UAFI
32. Metro Shelving 5'w x 8'h
6B. Fixed Lab Bench 24"Deep (standing height)
Space Diagram
This diagram is conceptual and is provided only to indicate required furnishings equipment, and general room proportions. The actual room design may change.
NAME
ROOM NUMBER
Amendment No. 0003AFMES Facility at Dover AFB 07.16025.02
VOLATILE ANALYSIS
D3.04A
Amendment No. 0004
Appendix H Page 129
8 hours/day
14 hours/day
24 hours/day
Hours of Operation
8 hours/day
14 hours/day
24 hours/day
MECHANICAL
Temperature
72°F ± 2°F (SET)
15 Air Changes/Hour Min.
10Air Changes/Hour Min.
6 Air Changes/Hour Min.
100% Make-up Air
Recirculated Air
Air Pressure Positive
Air Pressure Negative
Humidity
50% ± 20%
Uncontrolled
HOODS (indicate quantity and size)
Chemical Fume Hood
Radioisotope Hood
Laminar Flow Hood
Biological Safety Cabinet
Snorkel
Canopy Hood
Low Slotted Exhaust
LABORATORY EQUIPMENT
Vibration Sensitive
Light Sensitive
Vibration Producing
Heat Producing
Noise Producing
Overhead Service
REMARKS:
KEY PLAN:
PLUMBING
Laboratory Gas (LG)
Laboratory Vacuum (LV)
Laboratory Air (LA)
Compressed Air, 100 psi (A)
Hot Water (HW)
Cold Water (CW)
Pure Water Type III (0.05 MOhm)
Chilled Water (CHW S/R)
Steam/Condensate Return
Carbon Dioxide (C02)
Nitrogen Gas (N2)
Helium (He)
Hydrogen (H)
Oxygen (O2)
Floor Drain (FD)
Floor Sink (FS)
Safety Shower (SS)
Drench Hose (DH)
ELECTRICAL
110V, 20A, 1 Phase
208V, 30A, 1 Phase
208V, 30A, 3 Phase
480V, 100A, 3 Phase
Isolated Ground Outlet
Emergency Power
Phone
Data - Wired
LIGHTING
"In Use" Light
Task Lighting
Lighting Level
100 fc at bench/desk
60 fc at bench/desk
Dimmable
Zoned Lighting
CHEMICALS
Bases
Acids
Solvents
Radioisotopes
Carcinogens/Regulated
Chemical Waste Storage
Biological Storage
Radioisotope Storage
Chemical Storage
ARCHITECTURAL
Floor
VCT (ESD/CR)
VCT
Sheet Vinyl
Epoxy
Carpet
Sealed Concrete
Partitions
GWB, Epoxy Paint
GWB, Paint
Other
Base
Integral w/floor
Ceiling
Open
Acoustic Tile
Gyp Board, Height
Doors
3'-6" x 8'
3' x 8'
Uneven
Vision Panel
Natural Daylight
LABORATORY CASEWORK
ROOM NAME:
SECTION:
CONTACT:
PHONE:
FAX:
E-MAIL:
ROOM ID:
Standard
Eyewash (EW)
Darkenable
Sink
Data - Wireless
Benchtop Material
Casework Material
68°F-75°F ± 2°F (VAR)
Other
Other
Pure Water Type II (1.0 MOhm)
Pure Water Type I (18 MOhm)
Other
Other
Other
Other
Other
Other
Other
Other
Other
UPS Power
Emergency Operation
100% Uptime
Reduced Capability
N/A
Other
DIVISION:
4'-0" x 8'
X
X
X
X
X
X
X
This space is designated for automated immunoassay screening of samples using TDX analyzers
X
X
X
X
X
X
X
X
1X
6X
X
X
X
X
X
Lab standard
X
X
X
EIA ROOM
D3.05
D. FORENSIC TOXICOLOGY
X
X
Epoxy
Steel
X
Supp;y air hydrocarbon filtration
X
View windows from personnel corridor/card reader
X
X
D3. POSTMORTEM / HUMAN PERFORMANCE LAB
Space Requirements
Amendment No. 0003AFMES Facility at Dover AFB 07.16025.02
Amendment No. 0004
Appendix H Page 130
HCW
PW
EW
OUTLETS @ 24" O.C. IN
2 CHANNEL ELEC.
RACEWAY, TYP.
@ PERIMETER WALLS
ONE SPECIALTY OUTLET
PER 15' OF BENCH TYP.
MIN (1) PER LAB
6A
6A
VAC
AIR
N2
VAC
AIR
N2
CW
CS
AIR
VAC
N2
4'0 8' 16'
ELECTRICAL LEGEND
Duplex Outlet (110 V)
Quadruplex Outlet (110 V)
Specialty Outlet
Communication Outlet
Emergency PowerEP
Uninterruptable PowerUP
PLUMBING LEGEND
AIR Compressed Air CG Cylinder Gas CO2 Carbon Dioxide CHW Chilled Water CW Cold Water EW Eye Wash/Drench Hose FD Floor Drain FS Floor Sink G Gas HCW Hot & Cold Water N2 Nitrogen PW Pure Water VAC Vacuum AR Argon DI Distilled HE Helium CS Cup Sink
FURNISHINGS / EQUIPMENT
1. Chemical Fume Hood
2. Biological Safety Cabinet, UAFI
3. Radioisotope Hood
4. Laminar Flow Cabinet, UAFI
5. Snorkel Exhaust 6A. Fixed Lab Bench 30"Deep (standing height)
7. Fixed Lab Bench (sitting height)
8. Mobile Lab Bench (variable height), UAFI
9. Desk / Write-Up Station, UAFI
10. Wall Cabinet
11. Adjustable Shelves
12. Tall Storage Cabinet
13. Flammable Storage Cabinet
14. Equipment Space
16. Cup Sink
17. Scullery Sink
18. Cylinder Bracket
19. Safety Shower / Eyewash
20. Overhead Service Carrier
21. Pipe Drop Enclosure
22. Glasswasher
23. Autoclave
24. Icemaker, UAFI
25. White Markerboard, UAFI
26. Hook Strip
27. Laboratory Table, UAFI
28. Freezer, UAFI
29. Refrigerator, UAFI
30. PCR Hood, UAFI
15. Laboratory Sink
UAFI : User Agency Furnished and Installed
31. Bone Sanding Hood, UAFI
32. Metro Shelving 5'w x 8'h
6B. Fixed Lab Bench 24"Deep (standing height)
Space Diagram
This diagram is conceptual and is provided only to indicate required furnishings equipment, and general room proportions. The actual room design may change.
NAME
ROOM NUMBER
Amendment No. 0003AFMES Facility at Dover AFB 07.16025.02
EIA ROOM
D3.05A
Amendment No. 0004
Appendix H Page 131
8 hours/day
14 hours/day
24 hours/day
Hours of Operation
8 hours/day
14 hours/day
24 hours/day
MECHANICAL
Temperature
72°F ± 2°F (SET)
15 Air Changes/Hour Min.
10Air Changes/Hour Min.
6 Air…