09b0020amend7specs.pdf
PDF 405 KB Posted
- Attached to
- Joint SATCOM Engineering Center, C4ISR Campus, Aberdeen Proving Ground, Harford County, MD
- Solicitation number
- W912BU09B0020
About this file
Amendment No. 0007 - Specs
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 09b0020Amend9.pdf | ||
| 09B0020AMND8specs.PDF | ||
| 09b0020amend8dwgs.pdf | ||
| 09B0020AMEND7DWGS.pdf | ||
| 09b0020Amnd6dwgs.pdf | ||
| 09b0020amnd6spec.pdf | ||
| AMEND5.pdf | ||
| 09b0020amend4.pdf | ||
| 09b0020amnd4dwgs.pdf | ||
| Amnd0003.pdf | ||
| Amendment0002.pdf | ||
| Amnd1dwgs.pdf | ||
| Amnd1.pdf | ||
| 09B0020-DWGS.pdf | ||
| 09B0020-SPECS-VOL1.PDF | ||
| INSTRUCTIONS.pdf | ||
| RFI Example.xls | XLS spreadsheet | |
| 09B0020-SPECS-VOL2.PDF |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
US ARMY ENGINEER DISTRICT, PHILADELPHIA
POC: DENISE DETITTA
WANAMAKER BUILDING
100 PENN SQUARE EAST
PHILADEPHIA PA 19107-3390
JSEC
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
THIS AMENDMENT EXTENDS THE BID OPENING DATE TO AUGUST 26, 2009 AT 2:00 PM, LOCAL TIME AT PLACE OF BID OPENING.
All RFI's must be sent to C4ISR@usace.army.mil for receipt by 4:00 PM, August 14, 2009. RFI's received after the deadline may not receive responses.
1. CONTRACT ID CODE PAGE OF PAGES
J 1
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W912BU-09-B-0020
X 9B. DATED (SEE ITEM 11)
07-Jul-2009
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer X is extended, is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning 0 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required) Joint SATCOM Engineering Center, C4ISR Campus, Aberdeen Proving Ground, MD
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
2. AMENDMENT/MODIFICATION NO.
10A. MOD. OF CONTRACT/ORDER NO.
5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
12-Aug-2009
CODE
4. REQUISITION/PURCHASE REQ. NO.
CODE
US ARMY ENGINEER DIS RICT, PHILADELPHIAT
CONTRACTING DIVISION
WANAMAKER BUILDING
100 PENN SQUARE EAST
PHILADELPHIA PA 19107-3390
W912BU E5CTCDMD7. ADMINISTERED BY (If other than item 6)
CODE FACILITY CODE
EMAIL:TEL:
Amendment No. 0007 Invitation for Bid No.
W912BU-09-B-0020
THIS PAGE LEFT INTENTIONALLY BLANK FOR DUPLEX PRINTING
IFB W912BU-09-B-0020
14. DESCRIPTION OF AMENDMENT (continued)
(a) Requests For Information With Responses: RFIs with responses, annotated Amendment No. 0007 are attached to this amendment.
(b) SPECIFICATIONS:
(1) Please delete the following sections in their entirety and substitute the revised sections of the same numbers, annotated Amendment No. 0007, attached hereto.
01 11 00 SUMMARY OF WORK
05 30 00 STEEL DECKS
10 21 13 TOILET COMPARTMENTS
10 26 13 WALL AND CORNER GUARDS
23 08 00 COMMISSIONING OF HVAC SYSTEMS
26 32 33 UNINTERRUPTIBLE POWER SUPPLY (UPS) SYSTEM ABOVE 15
KVA CAPACITY
(2) Please add the following new section, annotated Amendment No.
0007, attached hereto.
07 42 13 METAL WALL PANELS
(c) CONTRACT DRAWINGS:
(1) Please delete the following drawings and replace with new drawings of the same number with latest revision date of 12 August 2009, attached hereto:
S-02 E-501 E-502 E-903 E-904
(d) Please indicate receipt of this amendment on Standard Form 1442 (SOLICITATION, OFFER, AND AWARD) as Amendment No. 0007. Failure to acknowledge all amendments may be cause for rejection of the bid.
FOR INFORMATION ONLY
REQUESTS FOR INFORMATION with RESPONSES
Solicitation No. W912BU-09-B-0019 8/12/2009
See Amendment No. 0004 for Comments #1 through #115.
RFI
Dwg Sheet/Spec Section Comment Official Response
116 27 10 00 Section 2.3.2.2-How many strands of fiber are required for a "NIPRNET" outlet?
Refer to T-001 for quantities within each outlet. Bid according to IFB.
117 Provide a specification or testing requirements for the high voltage cable.
Refer to Section 33 70 02, paragraph "Field Testing".
Bid according to IFB.
Spec 07 92 Joint Sealants 2.1.4 Acoustical Sealant
SPECS INDICATE: Provide rubber or polymer-based acoustical sealant conforming to ASTM C 919must have a flame spread of 25 or less and a smoke developed rating of 50or less when tested in accordance with ASTM E 84. Acoustical sealant must have a consistency of 250 to 310 when tested in accordance with ASTM D 217,and must remain flexible and adhesive after 500 hours of accelerated weathering as specified in ASTM C 734, and must be non-staining. Where does this apply? Please provide location/detail?
Addressed in Amendment No.
0006.
Detail 1,A- 304, no spec exists.
On detail #1 on A304, they are showing waterproofing at the slab and walls where the access flooring is. Please provide the spec for the waterproofing that is being applied in this area.
Addressed in Amendment No.
0006.
Detail 1,A- 304, no spec exists.
On the same detail 1 on A304 there is an exterior drainage panel- Please provide the spec for the drainage panel
Addressed in Amendment No.
0006.
spec 07 92 00 joint sealants 2.1.4 Acoustical Sealant
SPECS INDICATE: Provide rubber or polymer-based acoustical sealant conforming to ASTM C 919must have a flame spread of 25 or less and a smoke developed rating of 50or less when tested in accordance with ASTM E 84. Acoustical sealant must have a consistency of 250 to 310 when tested in accordance with ASTM D 217,and must remain flexible and adhesive after 500 hours of accelerated weathering as specified in ASTM C 734, and must be non-staining. Where does this apply? Please provide location/detail?
Addressed in Amendment No.
0006.
A-605 / A-
The partition head of wall detail “A” on 1/A-605 indicate that drywall goes 6” above ceiling and metal framing goes to the deck. The Head Condition and Default Partition in the Legend on A-605 says B32 is to go 6” above highest adjacent ceiling. Please advise what wall types go 6” above ceiling and what wall types go to the deck. Similarly, detail 2/A-301 shows the wall dividing rooms T.01 and T.06 not going to the deck.
Drawing A-105 near column line 20 indicates this wall as 5S-U / ---, a full height partition as indicated on 1/A-605. Please advise what wall type goes there.
Addressed in Amendment No.
0006.
A-303, Detail 2 Please provide specification for 3/8" drainage board referenced on the detail.
Addressed in Amendment No.
0006.
A-601, A132, and 09 29 00 Section 3.4.1
The paint spec section requires surfaces with eggshell, semi gloss or gloss paint to receive level 5 drywall finish. Many rooms in the finish plans call for paints P1-P4 which would then require level 5 drywall finish. Level 5 finishes are normally reserved for walls with critical natural lighting conditions or "wall wash" lighting fixtures. Neither of these conditions appear to be present. Please verify if Level 5 finishes are required.
Addressed in Amendment No.
0006.
09 29 00 Sections 1.1 and 2.1.5
Exterior Gypsum sheathing references ASTM numbers C79, C1396 and C1177. gypsum sheathing does not comply with all of these ASTM numbers. A sheathing product like Densglass gold does comply with these requirements. Please confirm that Densglass Gold sheathing is to be used on the project.
Specifications do not require a specific proprietary product be used. Bid per
IFB.
126 A-605
The partition head condition on A-605 does not indicated "fire track" to allow for roof movement on rated floor to deck partitions. Is fire track required for rated floor to deck partitions? Please advise.
Addressed in Amendment No.
Para 1.2.6 Spec Section 26 42 14
Para 1.2.6 of Spec Section 26 42 14 lists the number of magnesium anodes to be installed with fire hydrants, along pipe under concrete slabs, on valves, on metallic pipe component or section and on connectors or change in direction devices. This section seems to apply to installing anodes on metallic pipe/fittings installed in a non-metallic piping system. Are the same number of anodes required for each identified item plus addtional anodes to protect the metallic main run of pipe, if the main run of pipe is metallic and bonded? or can these items be protected by inclusion in a magnesium anode cathodic protection system designed for the metallic main run pipe and these items? Refer to note #3 on ES-101.
Para 1.2.6 Spec Section 26 42 14
Para 1.2.6 of Spec Section 26 42 14 lists the number of magnesium anodes to be installed with fire hydrants, along pipe under concrete slabs, on valves, on metallic pipe component or section and on connectors or change in direction devices. Are there any soil resistivity survey test results available to assist in the design of cathodic protection systems for other items not included in the referenced listing, such as for the gas main and main run of metallic water pipe?
Soil Resistivity tests are not available. Refer to Section 26 42 14 for requirements in this regard.
Also,refer to note #3 on ES- 101 for pipes requiring cathodic protection.
RFI Replies - Page 1
Para 2.2.16 Spec Section 26 42 14
Para 2.2.16 of Spec Section 26 42 14 describes permanent reference electrodes. Are permanent reference electrodes to be installed at all test stations or only along pipe under concrete slabs as described in Part 1.2.6.c of Spec Section 26 42 14
Required under concrete slabs per IFB.
130 E-501
Transformer TU-1 feeds Panels MCPP-1, MCPP-2, and MCPP-3. These Panels are 120/208V 3P4W. The feeders to these Panels are 3P3W with GND. The Panel overcurrent devices are 800A, 1000A, AND 1200A respectively. Please review Feeders Sizes from Transformer TU
Confirmed feeder sizes. Bid per IFB
E-501 & E-
Panel "MCPP-3" is shown on the Single Line Diagram as an 1200A panel and 800A on the Panel Schedule. Which is correct?
Addressed in Amendment No.
132 E-909 Panel "RP-X7" does not appear on the Single Line Diagram. Please Advise Addressed in Amendment No.
0004.
133 E-910 Panel "RP-3" does not appear on the Single Line Diagram. Please Advise.
Addressed in Amendment No.
134 E-502 The following Panel are shown on the Single Line Diagram but are not detailed in the panel schedules; "PP-7","PP-10, "PP-11" Please Advise.
Addressed in Amendment No.
0004.
135 FA-101 Is there a Fire Alarm Plan for the second floor of the TSL Lab?
Addressed in Amendment No.
0006.
E-104 & E-
On Drawing E-104 Transformer "TR3" is located in Room SU.21 and on Drawing E-105 Transformer "TR3" is located in Room T.02. Which location is correct?
137 E-103 On Drawing E-103, Key Note number 5 says to see enlargement of the CSL-UPS room (Rm CS.02) for additional electrical requirements. Where is this enlargement located?
Addressed in Amendment No.
0004.
138 E-105
Panel "LP-7", located in TSL High Bay (Room T.08), does not appear on the Single Line Diagram or in the Panel Schedules. Could you clarify the size of this Panel and where this Panel is fed from?
There is no LP-7. Bid per
IFB
139 E-104 Panel "CP-7" appears in two locations in SSL. (Room S.01) Which location is correct?
Addressed in Amendment No.
0004.
140 08 44 10 Spec does not specify whether curtainwall, storefronts and Windows require Blast Resistance. Please verify. Addressed in Amendment 4
141 08 81 00 Spec does not specify whether glazing should be Blast Resistant. Please verify. Addressed in Amendment 4
142 A-601
"SC1 - The finish schedule specifies Sealed Concrete with Chemical Hardener. The specified manufacturer is Perfect Polish. Perfect Polish is a contractor not a manufacturer. Is there a specification general contractors can use to get competitive bids? Can you clarify if the chemical hardener is being considered as the sealing agent or is the concrete to be treated with a hardener and then sealed with a topical sealer? There is nothing listed in the Division 3 or Division 9 specifications.
NOTE: CPT - Concrete Polishing Technologies www.cptonline.biz is the parent company for Perfect Polish (Polishing Contractor) www.perfectpolishonline.com, Concrete Polishing Solutions (Distributor of Equipment and Supplies) www.go2cps.com and International Polished Concrete Institute www.ipcionline.org"
Addressed in Amendment 4, spec section 03 31 00
Door numbers V.01A, V.02A and L.01A are listed as MTL Insulated Doors. Please confirm that they are aluminum storefront.
Doors are metal insulated.
Bid per the IFB
A-602; 08 11 03-4, 2.2
On the Door Schedule ( A-602 ), there is a number of doors listed ad MTL INSUL. Are those doors insulated steel door systems based on the Specs, page 4, item 2.2? Can you please confirm what type of door material they are?
Doors are Metal Insulated per the IFB
145 CU-101
Reference Note 16 on CU-101. This note requires the Contractor to hire BGE to furnish and install the new gas lines for the project. BGE will not give construction costs until an Application for service is received. Has the Governement made the Application to BGE? We will not be able to get Construction costs from BGE in time to include in our bid. Please delete this requirement (the Contractor is to include trenching and backfill only) or specify an allowance to be included in the Contractor's bid for BGE's portion of the work.
Addressed in Amendment No
Please confirm the delivery location for the bid as: US Army Engineer District, Philadelphia; Contracting Division; Wanamaker Building; 100 Penn Square; Philadelphia PA 19107-3390. The address is correct
147 A-601
It is stated that, "Polishing shall be a dry diamond method with a machine capable of a grinding pressure of 675 or more. The grinder shall be connected to a vacuum system with HEPA filtration." A vacuum that has HEPA filtration only means that it will filter particulate debris that it "actually collects" to the HEPA specification. There are no vacuums currently on the market for grinding concrete that has the ability to "lift and contain" the heavy particulate generated during the initial grinding stages of the polishing process. To help reduce possible silica exposure to workers and other trades from the initial grinding stages can a contractor use a wet method for the initial grinding, then switch to a dry method at which point the available vacuum systems on the market are able to lift and contain the particulate debris? See Amendment No. 0004
It is stated, "The system shall be capable of meeting the following performance requirements: Floor Flatness: 45 Minimum." Floor Flatness is dictated by the contractor placing and finishing the concrete. Small aggregate exposure has been specified as the desired cut. Aggregate placement will vary in depth from one place to the next throughout the slab. These two variables are going to affect the finished floor flatness of the polished surface. To what extent is the polishing contractor going to be held to a 45 minimum floor flatness and a uniform exposure of small aggregate? See Amendment No. 0004
230800 Item 1.8
The Commissioning Specialist did not develop the commissioning specifications and incorporate them into the construction documents in accordance with LEED NC 2.2 EA Pr 1 scope item 2. Will the project still be able to achieve EA Pr 1 compliance?
RFI Replies - Page 2
230800 Item 1.3.2;
013329 LEED
Scorecard
230800 page 2 item 1.3.2 indicates that Contractor shall provide documentation that Cx work meets LEED EA Credit 3, Enhanced Cx. However, this is not possible due to hiring CxA after design process is completed, and this credit is marked as “No” in the LEED NC
2.2 checklist of specification section 013329. Please clarify.
230800 Item 3.3
Indicates the entire TAB report shall be included in the final Commissioning Report.
This is not normal practice and the TAB report can be very large. Can the TAB Verification Report be included while the full TAB report is left as a separate document?
230800 Item 1.3.2
Items states that "Formal LEED certification is not required. It also states "Provide documentation for as many LEED credits as possible to support LEED silver certification of the project". Please clarify whether or not project is pursuing LEED certification and why LEED credit documentation is required if project is not seeking LEED certification?
Numerous questions were identified in amendment 4 about BG&E and the gas line installation. All were answered with a reference to that same amendment. No additional information relating to the gas line installation could be found in amendment 4. Please clarify. Addressed in Amendment No.
154 Bid Form A revised bid form was referenced in Amendment 4, but no new form could be found in the pdf posted on the website. Please issue this form.
Addressed in Amendment No.
Spec 07 42 13 1.8
"We have been receiving messages that the siding manufactures and installers are indicating that they will not provide a ""no dollar limit ""warranty on the metal siding. Recently, the Consolidated Facility Project being bid at APG with similar siding initially had a similar warranty and was subsequently changed in an addendum #3 to a more standard warranty. 1.8 WARRANTIES The Contractor shall provide a weathertight material and workmanship warranty for the metal wall panel system installation for a period of 10 years and to include a manufacturer's 10 year warranty against cracking, peeling, or delamination of the color finish and corrosion of the base metal, and 10 year warranty against the corrosion of fasteners caused by ordinary wear and tear by the elements. The warranties shall start upon final acceptance of the work or the date the Government takes possession, whichever is earlier. Please revise the warranty to be consistant with that provided for the Consolidated North Project.
Addressed in Amendment No.
Spec 07 42 13 Please provide a spec for the horizonal metal siding. Type 4 .
Addressed in Amendment No.
spec 08 44
The exposed aluminum finishes section 2.5.3 call out four different coatings. Which one is required?
Addressed in Amendment No.
158 General Please confirm if there is any GFCI material or equipment covered under this contract.
If there is, provide details of the material or equipment.
No GFCI equipment. Bid per
IFB.
Spec Section 23 08 00
Spec Section 23 08 00 item 1.3.2 states that for new construction to provide documentation that meets the LEED enhanced commissioning credit. The LEED checklist shows enhanced commissioning as a NO for the credit. Please confirm that LEED Enhanced Commissioning is not required for the JSEC project.
Addressed in Amendment No.
0007.
160 RFIs
Several RFIs that were submitted are indicated to have answers in Amendment 4, but are not answered in the document.. Will all questions be addressed in a subsequent Amendment?
Addressed in Amendment No.
161 CS-103
The sheet G-1 issue with amendment 4 indicated tha CS-103 was newly issued, but it was not included in the drawings posted in the .website
Addressed in Amendment No.
162 S-02
There are apparent references to other foundations, QRSO (2ea) and GSC-52, that are on this drawi ng. No details have been provided. Are these foundations to be included in the scope of work of this contract?
Addressed in Amendment No.
163 CS-101
Reference is made on the drawing to note 5 for construction details according to the Antennae Foundation package just north of the parking lot adjacent to Raritan Road.
No information was found in Amendment 4 for this location. Please clarify.
Addressed in Amendment No.
164 SB 601
No reinforcing steel details are provided for the 2.4 M Antennae Pad shown on this drawing. Please provide.
Refer to Amendment No. 004, CP-301.
Specs 01 78 00 and 02 50
In Amendment 04, section "DESCRIPTION OF AMENDMENT", #87) references deleting sections 10 50 00 TEMPORARY CONSTRUCTION and 01 78 00 CLOSEOUT SUBMITTALS and substitut-ing revised sections, however, revised sections are not included in attached documents.
Please provide.
Addressed in Amendment No.
166 01 33 29
In Section 1.3.2 Contractor Responsibilities, Bid Option 1:"The Contractor shall submit the project for formal USGBC certification for a rating of silver. All Costs in connection with taking the project from a Silver Certifiable rating (Base Bid) to a Silver Certified rating shall be included in the cost of Option - Bid item 3 "LEED Silver Certification". Where can we locate the new bid form that reflects these changes?
Addressed in Amendment No.
02 41 00 Demolition
Will existing loose furnishings and equipment be removed prior to contractors demolition process?
Yes. Clarified in Amendment No. 0007
07 22 00 Roof & Deck Insulation
To what extent is 5/8" Glas-Mat boarding required at roof system? Specs outline thermal in para. 3.3. and protection board para. in 3.4.2.1.
Addressed in Amendment No.
07 22 00 Roof & Deck Insulation
What is pitch required fro crickets? Spec 2.1.3 outlines 1/4"/1'-0" Drawing A-301 outlines 1/2"/1'-0".
Plans and specs both call for a 1/4" per foot slope. Bid per documents.
RFI Replies - Page 3
170 Wage Scale
Wage Scales were reissued as part of amendment #4 to include Schedules for Sewer and Water Line Construction Projects, Heavy Construction Projects and Building Construction. Please advise which schedule of prevailing wages applies to the various construction items for this project or are we to only reference the Building Construction type wage scale.
Addressed in Amendment No.
0006, Secton 00815
RFI Replies - Page 4
SECTION 01 11 00
SUMMARY OF WORK
PART 1 GENERAL
1.1 WORK COVERED BY CONTRACT DOCUMENTS
1.1.1 Project Description
The work includes construction of an approximately 99,147 square foot facility for the Joint SATCOM Engineering Center (JSEC) and all related site and utility work. This project is part of Command, Control, Communications, Computers, Intelligence, Surveillance, and Reconnaissance (C4ISR) and Base Realignment and Closure (BRAC) DoD initiatives.
The single story structure houses four laboratories, an administrative area, and support spaces served by a major east-west corridor that traverses the length of the building. A secondary north-south corridor links support spaces to the labs and provides access to hardstands sited to the south of the building required for antenna locations and building access.
Parking is provided on the east and west sides of the building, while access and deliveries are accommodated from the north. Other site elements include, hardstands, walkways, landscaping, security fencing, utilities, and storm water management.
Work also includes demolition of existing abandoned Building 3070 B located on the project site. Building, site and utility demolition and removal and some utility salvage is required.
A LEED certifiable rating of Silver is being pursued for this project.
Option 1 is the effort required to take the project from LEED Silver Certifiable, to LEED Silver Certified. This facility has been designed in accordance with UFC 4-010-01: DoD Minimum Antiterrorism Standards for Buildings.
1.1.2 Location
The work shall be located at the Aberdeen Proving Ground (APG) in the location shown on the contract drawings.
1.2 OCCUPANCY OF PREMISES
Building #3070-A on the project site scheduled for demolition under this contract is abandoned. The Contracting Officer shall be notified 48 hours prior to start of demolitions work
1.3 EXISTING WORK
In addition to "FAR 52.236-9, Protection of Existing Vegetation, Structures, Equipment, Utilities, and Improvements":
a. Remove or alter existing work in such a manner as to prevent injury or damage to any portions of the existing work which remain.
SECTION 01 11 00 Page 1
b. Repair or replace portions of existing work which have been altered during construction operations to match existing or adjoining work, as approved by the Contracting Officer. At the completion of operations, existing work shall be in a condition equal to or better than that which existed before new work started.
1.4 LOCATION OF UNDERGROUND FACILITIES
Obtain digging permits prior to start of excavation. Scan the construction site with electromagnetic or sonic equipment, and mark the surface of the ground or paved surface where existing underground utilities are discovered. Verify the elevations of existing piping, utilities, and any type of underground obstruction not indicated to be specified or removed but indicated or discovered during scanning in locations to be traversed by piping, ducts, and other work to be conducted or installed. Verify elevations before installing new work closer than nearest manhole or other structure at which an adjustment in grade can be made.
1.4.1 Notification Prior to Excavation
Notify the Contracting Officer at least 48 hours prior to starting excavation work.
1.5 PERMITS
The permits listed below have been obtained by the Government or are in the approval process and may require additional action by the Contractor to become complete. After final approvals by the respective state agencies are received, the Government will furnish approval letters and permits to the Contracting Officer who will furnish the Contractor all such permits before or during construction. The Contractor shall abide by all permit requirements. No earth disturbance can occur until permits in subparagraphs a, b and c, below are received from MDE.
a. Erosion and Sedimentation (E&S) Control Plan: The E&S control plans were submitted to the Maryland Department of the Environment (MDE).
Permit number is: MDE # - 09-SF-0314.
b. Stormwater Management (SWM) Plan: The (SWM) Plans were submitted to the Maryland Department of the Environment. Permit number is: MDE # -
09-SF-0314.
c. Notice of Intent (NOI) to comply with the General Permit for construction activities in accordance with EPA's National Pollution Discharge Elimination System (NPDES) stormwater management program: The NOI form has been completed and is under review by MDE. Upon the issuance of the Notice to Proceed to the Contractor, a Transfer of Authority form will be prepared by the COE project designer and routed through the Contracting Officer to the Contractor. The Contractor shall return the signed Transfer of Authority form to the COE designer through the Contracting Officer who shall forward it to MDE. At completion of the construction contract the Contractor shall complete a Notice of Termination (NOT) form and furnish it to MDE through the Contracting Officer notifying that agency of the end of construction.
d. Forest Conservation (FC) Plan: A Forest Conservation plan has been coordinated with the DIO, APG. APG is responsible for any reforestation and aforestation.
SECTION 01 11 00 Page 2
1.9 FAA HEIGHT RESTRICTION
Contractors shall file for an FAA permit and Notice to Airmen (NOTAM) through the FAA for any crane/obstacle above 100 feet in height. The average timeframe for permit process is 30 days.
PART 2 PRODUCTS
Not used.
PART 3 EXECUTION
Not used.
SECTION 01 11 00 Page 3
-- End of Section --
SECTION 01 11 00 Page 4
SECTION 05 30 00
STEEL DECKS
PART 1 GENERAL
The work reqired herein is the responsibility of the pre-engineered framing system manufacturer requirements specified in Section 13 34 19 and shall be thouroughly coordinated with that section.
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
AISC 360 (2005) Specification for Structural Steel Buildings, with Commentary
AMERICAN IRON AND STEEL INSTITUTE (AISI)
AISI SG-913 (1991) LRFD Cold-formed Steel Design Manual
AISI SG03-3 (2002) Cold-Formed Steel Design Manual Set
AMERICAN WELDING SOCIETY (AWS)
AWS D1.1/D1.1M (2008) Structural Welding Code - Steel
AWS D1.3/D1.3M (2008) Structural Welding Code - Sheet Steel
ASTM INTERNATIONAL (ASTM)
ASTM A 1008/A 1008M (2008a) Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy and High-Strength Low-Alloy with Improved Formability, Solution Hardened, and Bake Hardened
ASTM A 108 (2007) Standard Specification for Steel Bar, Carbon and Alloy, Cold-Finished
ASTM A 123/A 123M (2008) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A 36/A 36M (2008) Standard Specification for Carbon Structural Steel
ASTM A 570/A 570M (1998) Standard Specification for Steel, Sheet and Strip, Carbon, Hot-Rolled
ASTM A 653/A 653M (2008) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or
SECTION 05 30 00 Page 1
Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A 780 (2001; R 2006) Standard Practice for Repair of Damaged and Uncoated Areas of Hot-Dip Galvanized Coatings
ASTM A 792/A 792M (2008) Standard Specification for Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process
FM GLOBAL (FM)
FM DS 1-28 (2002) Design Wind Loads
FM P7825 (2005) Approval Guide
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2007; AMD 1 2008) National Electrical Code - 2008 Edition
STEEL DECK INSTITUTE (SDI)
SDI 30 (2001) Design Manual for Composite Decks, Form Decks, and Roof Decks
SDI DDMO3 (3rd Edition) Diaphragm Design Manual
SDI DDP (1987; R 2000) Deck Damage and Penetrations
SDI MOC2 (2006) Manual of Construction with Steel Deck
THE SOCIETY FOR PROTECTIVE COATINGS (SSPC)
SSPC Paint 20 (2002; E 2004) Paint Specification No. 20 Zinc-Rich Coating Type I Inorganic and Type II Organic
U.S. DEPARTMENT OF DEFENSE (DOD)
UFC 3-310-01 Load Assumptions for Buildings
UNDERWRITERS LABORATORIES (UL)
UL 209 (2005; Rev thru May 2007) Cellular Metal Floor Raceways and Fittings
UL 580 (2006) Tests for Uplift Resistance of Roof Assemblies
UL Bld Mat Dir (2008) Building Materials Directory
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office
SECTION 05 30 00 Page 2 that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Fabrication Drawings; G, DO
Metal Floor Deck Units; G, DO
Cant Strips; G, DO
Ridge and Valley Plates; G, DO
Metal Closure Strips; G, DO
SD-03 Product Data
Accessories; G, DO
Deck Units; G, DO
Galvanizing Repair Paint; G, DO
Joint Sealant Material; G, DO
Mechanical Fasteners; G, DO
Metal Floor Deck Units; G, DO
Piston Tool Operator; G, DO
Repair Paint; G, DO
Sound Absorbing Material; G, DO
Welder Qualifications; G, DO
Welding Equipment; G, DO
Welding Rods and Accessories; G, DO
SD-04 Samples
Metal Roof Deck Unitsv
Flexible Closure Strips; G, DO
Accessories; G, DO
SD-05 Design Data
Deck Units; G, DO
Submit manufacturer's design calculations, or applicable published literature for the structural properties of the proposed deck units.
SD-07 Certificates
SECTION 05 30 00 Page 3
Welding Procedures; G, DO
Fire Safety; G, DO
Wind Storm Resistance; G, DO
1.3 QUALITY ASSURANCE
1.3.1 Deck Units
Furnish deck units and accessory products from a manufacturer regularly engaged in manufacture of steel decking. These products shall be the responsibility of the the pre-engineered framing system manufacturer. As such, the pre-engineered framing system manufacturer is required to make selections from items enclosed in [brackets] located throughout this section of the specifications and include selected items in submittals for approval. Some items indicated herein may not be required based on selections made by manufacturer. Provide a 2 sq ft. sample of decking material and each accessory to be used. Provide manufacturer's certificates attesting that the decking material meets the specified requirements.
1.3.2 Certification of Piston Tool Operator
Manufacturer's certificate attesting that the operators are authorized to use the low velocity piston tool.
1.3.3 Qualifications for Welding Work
Follows Welding Procedures in accordance with AWS D1.1/D1.1M. Test specimens shall be made in the presence of Contracting Officer and shall be tested by an approved testing laboratory at the Contractor's expense.
Submit qualified Welder Qualifications in accordance with AWS D1.1/D1.1M, or under an equivalent approved qualification test. Perform tests on test pieces in positions and with clearances equivalent to those actually encountered. If a test weld fails to meet requirements, perform an immediate retest of two test welds until each test weld passes. Failure in the immediate retest will require the welder be retested after further practice or training, performing a complete set of test welds.
Submit manufacturer's catalog data for Welding Equipment and Welding Rods and Accessories.
1.3.4 Regulatory Requirements
1.3.4.1 Fire Safety
Test roof deck as a part of a roof deck construction assembly of the type used for this project, listing as fire classified in the UL Bld Mat Dir, or listing as Class I construction in the FM P7825, and so labeled.
1.3.4.2 Wind Storm Resistance
Provide roof construction assembly capable of withstanding an uplift pressure of 90 pounds per square foot when tested in accordance with the uplift pressure test described in the FM DS 1-28 or as described in UL 580 and in general compliance with UFC 3-310-01.
SECTION 05 30 00 Page 4
1.3.5 Fabrication Drawings
Show type and location of units, location and sequence of connections, bearing on supports, methods of anchoring, attachment of accessories, adjusting plate details, size and location of holes to be cut and reinforcement to be provided, the manufacturer's erection instructions and other pertinent details.
1.4 DELIVERY, STORAGE, AND HANDLING
Deliver deck units to the site in a dry and undamaged condition. Store and handle steel deck in a manner to protect it from corrosion, deformation, and other types of damage. Do not use decking for storage or as working platform until units have been fastened into position. Exercise care not to damage material or overload decking during construction. Must not exceed the design live load. The maximum uniform distributed storage load.
Stack decking on platforms or pallets and cover with weathertight ventilated covering. Elevate one end during storage to provide drainage.
Maintain deck finish at all times to prevent formation of rust. Repair deck finish using touch-up paint. Replace damaged material.
1.5 DESIGN REQUIREMENTS FOR ROOF DECKS
1.5.1 Properties of Sections
Properties of metal roof deck sections must comply with engineering design width as limited by the provisions of AISI SG-913.
1.5.2 Allowable Loads
Indicate total uniform dead and live load for detailing purposes.
PART 2 PRODUCTS
2.1 MATERIALS
2.1.1 Steel Sheet
Flat rolled carbon steel sheets of structural quality, thickness not less than indicated, meeting the requirements of AISI SG03-3, except as modified herein.
2.1.2 Steel Coating
ASTM A 653/A 653M designation G90 galvanized, or ASTM A 792/A 792M designation AZ55, aluminum-zinc alloy. Apply coating to both sides of sheet. Conform to UL 209 for coating on decking provided as wire raceways.
2.1.3 Mixes
2.1.3.1 Galvanizing Repair Paint for Floor Decks
Provide a high-zinc-dust content paint for regalvanizing welds in galvanized steel conforming to ASTM A 780.
2.1.4 Galvanized Steel Angles for Roof Decks
Provide hot-rolled carbon steel angles conforming to ASTM A 36/A 36M, merchant quality, Grade Designation SAE/AISI 1023 or SAE/AISI 1025, and
SECTION 05 30 00 Page 5 hot-dip galvanized in accordance with ASTM A 123/A 123M.
2.1.5 Joint Sealant Material for Roof Decks
Provide a nonskinning, gun-grade, bulk compound material as recommended by the manufacturer.
2.1.6 Galvanizing Repair Paint for Roof Decks
Provide a high zinc-dust content paint for regalvanizing welds in galvanized steel and shall conform to ASTM A 780.
2.1.7 [Enter Appropriate Subpart Title Here]2.2 ACCESSORIES
Provide accessories of same material as deck, unless specified otherwise.
Provide manufacturer's standard type accessories, as specified.
2.2.1 Adjusting Plates
Provide adjusting plates, or segments of deck units, of same thickness and configuration as deck units in locations too narrow to accommodate full size units. Provide factory cut plates of predetermined size where possible.
2.2.2 End Closures
Fabricated of sheet metal by the deck manufacturer. Provide end closures minimum 0.028 inch thick to close open ends at exposed edges of floors, parapets, end walls, eaves, and openings through deck.
2.2.3 Partition Closures
Provide closures for closing voids above interior walls and partitions that are perpendicular to the direction of the configurations. Provide rubber, plastic, or sheet steel closures above typical partitions. Provide sheet steel closures above fire-resistant interior walls and partitions located on both sides of wall or partition.
2.2.4 Closure Plates for Composite Deck
Support and retain concrete at each floor level. Provide edge closures at all edges of the slab of sufficient strength and stiffness to support the wet concrete. Provide metal closures for all openings in composite steel deck 1/4 inch and over.
2.2.5 Sheet Metal Collar
Where deck is cut for passage of pipes, ducts, columns, etc., and deck is to remain exposed, provide a neatly cut sheet metal collar to cover edges of deck. Do not cut deck until after installation of supplemental supports.
2.2.6 Cover Plates
Sheet metal to close panel edge and end conditions, and where panels change direction or butt. Polyethylene-coated, self-adhesive, 2 inch wide joint tape may be provided in lieu of cover plates on flat-surfaced decking butt joints.
Fabricate cover plates for abutting floor deck units from the specified
SECTION 05 30 00 Page 6 structural-quality steel sheets not less than nominalthick before galvanizing. Provide 6 inch wide cover plates and form to match the contour of the floor deck units.
2.2.7 Roof Sump Pans
Sump pans must be provided for roof drains and must be minimum 0.075 inch thick steel, flat type. Shape sump pans to meet roof slope by the supplier or by a sheet metal specialist. Provide bearing flanges of sump pans to overlap steel deck a minimum of 3 inch. Shape, size, and reinforce the opening in bottom of the sump pan to receive roof drain.
2.2.8 Column Closures
Sheet metal, minimum 0.0358 inch thick or metal rib lath.
2.2.9 Access Hole Covers
Sheet metal, minimum 0.0474 inch thick.
2.2.10 Hanger
Provide clips or loops for utility systems and suspended ceilings of one or more of the following types:
a. Lip tabs or integral tabs where noncellular decking or flat plate of cellular section is 0.0474 inch thick or more, and a structural concrete fill is used over deck.
b. Slots or holes punched in decking for installation of pigtails.
c. Tabs driven from top side of decking and arranged so as not to pierce electrical cells.
d. Decking manufacturer's standard as approved by the Contracting Officer.
2.2.11 Shear Connectors
Provide shear connectors as headed stud type, ASTM A 108, Grade 1015 or 1020, cold finished carbon steel with dimensions complying with AISC 360 and strap type, ASTM A 570/A 570M, Grade D, hot-rolled carbon steel.
2.2.12 Mechanical Fasteners
Provide mechanical fasteners, such as powder actuated or pneumatically driven fasteners, for anchoring the deck to structural supports and adjoining units that are designed to meet the loads indicated. Provide positive locking-type fasteners standard with the Steel Deck Institute and the steel deck manufacturer, as approved by the Contracting Officer.
2.2.13 Miscellaneous Accessories
Furnish the manufacturer's standard accessories to complete the deck installation. Furnish metal accessories of the same material as the deck and with the minimum design thickness as follows: saddles, 0.0474 inch;
welding washers, 0.0598 inch cant strip, 0.0295 inch other metal accessories, 0.0358 inch unless otherwise indicated. Accessories must include but not be limited to saddles, welding washers, fasteners, cant strips, butt cover plates, underlapping sleeves, and ridge and valley
SECTION 05 30 00 Page 7 plates.
2.3 FABRICATION
Furnish one sample of each type of Metal Floor Deck Units used to illustrate the actual cross section dimensions and configuration.
Furnish sample of Metal Roof Deck Units used to illustrate actual cross section dimensions and configurations.
2.3.1 Deck Units
2.3.1.1 Cellular Metal Floor Deck Units
Provide decking as wire raceways conforming to NFPA 70. Fabricate units from the specified structural-quality steel sheets. Provide nominal thickness of the steel sheets, before galvanizing, a minimum 18-gage for the upper element of the floor deck unit, and a minimum 16-gage for the lower element of the floor deck unit.
Provide sufficient welds, forming the steel sheets into the cellular floor deck unit, to develop the full horizontal shear at the plane where the steel sheets are joined.
Cellular metal floor deck units must be fluted section cells combined on a flat plate having interlocking type sidelaps. Provide depth, width of unit, number of cells per unit, and width of cells as follows:
DEPTH WIDTH OF UNIT NUMBER OF CELLS WIDTH OF CELLS
MINIMUM NOMINAL PER UNIT NOMINAL
(inch) (inch) (inch)
1-1/2 24 4 3-5/8
1-1/2 24 2 9-5/8
1-1/2 12 1 9-5/8
3 24 3 5-5/8
3 24 2 9-5/8
3 12 1 9-5/8
4-1/2 24 4 2-5/8
4-1/2 24 2 9-5/8
4-1/2 12 1 9-5/8
6 24 2 9-5/8
6 12 1 9-5/8
7-1/2 24 2 9-5/8
7-1/2 12 1 9-5/8
SECTION 05 30 00 Page 8
Cellular metal floor deck units must be fluted section cells combined with a matching fluted bottom section having interlocking type sidelaps.
Provide depth, width of unit, number of cells per unit, and width of cells as follows:
DEPTH WIDTH OF UNIT NUMBER OF CELLS WIDTH OF CELLS
MINIMUM NOMINAL PER UNIT NOMINAL
(inch) (inch) _______________ (inch)
3 24 4 3-5/8
3 12 1 9-5/8
6 24 3 5-5/8
Conform to SDI 30 for deck units. Conform to ASTM A 653/A 653M, SQ, Grade 230, Grade 33; ASTM A 1008/A 1008M Coated Carbon Steel Sheets, Grade C, 228 mPa, 33, 000 psi minimum yield strength; or ASTM A 792/A 792M Coated Steel Sheets, Grade 33 for formed cellular and non-cellular decking and accessories. Use panels of maximum possible lengths to minimize end laps.
Fabricate deck units in lengths to span 3 or more supports with flush, telescoped, or nested 2 inch laps at ends, and interlocking, or nested side laps, unless otherwise indicated. Deck with cross-sectional configuration differing from the units indicated may be used, provided that the properties of the proposed units, determined in accordance with AISI SG03-3, are equal to or greater than the properties of the units indicated and that the material will fit the space provided without requiring revisions to adjacent materials or systems. Factory apply a standard, phosphatized and painted, baked-on enamel finish to underside of steel decking.
2.3.2 Open Beam, Metal Floor Deck Units
Fabricate open beam metal floor deck units of the specified structural-quality steel sheets. Provide nominal thickness of the steel sheets before galvanizing of minimum 18-gage.
Provide open beam metal floor deck units with a fluted section having interlocking type sidelaps. Provide depth, width of unit, number of flutes per unit, and width of flutes as follows:
DEPTH WIDTH OF UNIT NUMBER OF CELLS WIDTH OF CELLS
MINIMUM NOMINAL PER UNIT NOMINAL
(inch) (inch) _______________ (inch)
1-1/2 24 4 3-5/8
1-1/2 24 2 9-5/8
1-1/2 12 1 9-5/8
3 24 3 5-5/8
3 24 2 9-5/8
3 12 1 9-5/8
4-1/2 24 2 9-5/8
4-1/2 12 2 2-5/8
SECTION 05 30 00 Page 9
DEPTH WIDTH OF UNIT NUMBER OF CELLS WIDTH OF CELLS
MINIMUM NOMINAL PER UNIT NOMINAL
(inch) (inch) _______________ (inch)
4-1/2 12 1 9-5/8
6 24 2 9-5/8
6 12 1 9-5/8
7-1/2 24 2 9-5/8
7-1/2 12 1 9-5/8
2.3.3 Length of Floor Deck Units
Provide floor deck units of sufficient length to span three or more spacings where possible.
2.3.4 Roof Deck
Conform to ASTM A 792/A 792M or ASTM A 1008/A 1008M for deck used in conjunction with insulation and built-up roofing. Fabricate roof deck units of the steel design thickness required by the design drawings and galvanized or zinc-coated in conformance with ASTM A 653/A 653M, G90 coating class or aluminum-zinc coated in accordance with ASTM A 792/A 792M Coating Designation AZ55.
2.3.4.1 Cant Strips for Roof Decks
Fabricate cant strips from the specified commercial-quality steel sheets not less than nominal 0.0359 inch thick before galvanizing. Bend strips to form a 45-degree cant not less than 5 inch wide, with top and bottom flanges a minimum 3 inch wide. Length of strips 10 feet.
2.3.4.2 Ridge and Valley Plates for Roof Decks
Fabricate plates from the specified structural-quality steel sheets, not less than nominal 0.0359 inch thick before galvanizing. Provide plates of minimum 4-1/2 inch wide and bent to provide tight fitting closures at ridges and valleys. Provide a minimum length of ridge and valley plates of 10 feet.
2.3.4.3 Metal Closure Strips for Roof Decks
Fabricate strips from the specified commercial-quality steel sheets not less than nominal 0.0359 inch thick before galvanizing. Provide strips from the configuration required to provide tight-fitting closures at open ends and sides of steel roof decking.
2.3.5 Form Deck
Conform to ASTM A 653/A 653M or ASTM A 1008 for deck used as formwork for concrete. Fabricate form deck of 0.015inch design thickness or thicker steel. Paint with one coat of manufacture's standard paint.
SECTION 05 30 00 Page 10
2.3.6 Composite Deck
Conform to ASTM A 653/A 653M or ASTM A 1008/A 1008M for composite deck assembly. Fabricate deck used as the tension reinforcing in composite deck if 0.0295. Zinc-coat in conformance with ASTM A 653/A 653M.
In addition to resisting shear, provide devices to resist vertical separation between the steel deck and the concrete. Provide one of the following types of shear devices:
a. Mechanically fixed shear devices such as embossments, holes, or welded buttons.
b. Mechanically fixed shear devices such as inverted, triangular-shaped ribs.
2.3.7 [Enter Appropriate Subpart Title Here]2.3.8 Touch-Up Paint
Provide touch-up paint for shop-painted units of the same type used for the shop painting, and touch-up paint for zinc-coated units of an approved galvanizing repair paint with a high-zinc dust content. Touch-up welds with paint conforming to SSPC Paint 20 in accordance with ASTM A 780.
Maintain finish of deck units and accessories by using touch-up paint whenever necessary to prevent the formation of rust.
For floor decking installation, wire brush, clean, and touchup paint the scarred areas on the top and bottom surfaces of the metal floor decking and on the surface of supporting steel members. Include welds, weld scars, bruises, and rust spots for scarred areas. Touched up the galvanized surfaces with galvanizing repair paint. Touch up the painted surfaces with paint for the repair of painted surfaces.
After roof decking installation, wire brush, clean, and touchup paint the scarred areas on top and bottom surfaces of metal roof decking. The scarred areas include welds, weld scars, bruises, and rust spots. Touchup galvanized surfaces with galvanizing repair paint. Touchup painted surfaces with repair paint of painted surfaces.
PART 3 EXECUTION
3.1 EXAMINATION
Prior to installation of decking units and accessories, examine worksite to verify that as-built structure will permit installation of decking system without modification.
3.2 INSTALLATION
Install steel deck units in accordance with SDI 30, or SDI DDMO3 and approved shop drawings. Place units on structural supports, properly adjusted, leveled, and aligned at right angles to supports before permanently securing in place. Damaged deck and accessories including material which is permanently stained or contaminated, deformed, or with burned holes shall not be installed. Extend deck units over three or more supports unless absolutely impractical. Report inaccuracies in alignment or leveling to the Contracting Officer and make necessary corrections before permanently anchoring deck units. Locate deck ends over supports only. Ends of floor deck may be lapped or butted. Do not use unanchored deck units as a work or storage platform. Do not fill unanchored deck with
SECTION 05 30 00 Page 11 concrete. Permanently anchor units placed by the end of each working day.
Do not support suspended ceilings, light fixtures, ducts, utilities, or other loads by steel deck unless indicated. Distribute loads by appropriate means to prevent damage. Prepare shoring in position before concrete placement begins in composite or form deck. Size cellular decking provided as electrical raceways to accommodate indicated wiring systems.
Chip off burrs and eliminate sharp edges which may damage wiring. Mesh decking panels accurately and place in accordance with UL 209. Neatly fit acoustical material into the rib voids.
3.2.1 Attachment
Immediately after placement and alignment, and after correcting inaccuracies, permanently fasten steel deck units to structural supports and to adjacent deck units by welding with normal5/8 inch diameter puddle welds or fastened with screws, powder-actuated fasteners, or pneumatically driven fasteners in accordance with…