This solicitation is for construction services for a new 135,000 square foot hangar facility at Minot Air Force Base in North Dakota. The project involves building a hangar, alert crew facility, aircraft maintenance unit, simulator complex, taxiways, and airfield lighting to support helicopter squadron operations and tactical response forces. Sustainability measures are also required. The estimated value is over $36.5 million. The selected contractor will be responsible for all conventional design and construction in accordance with military standards and specifications. The soliciting agency is the Department of the Army Corps of Engineers Omaha District.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Minot JA MIC1 PN QJVF153001 Minot AFB Helo JA_FINAL 05122020.pdf | ||
| HVAC Chiller Justification and Approval - Signed.pdf | ||
| Am_0006.pdf | ||
| Am_0005.pdf | ||
| Am_0004.pdf | ||
| Am_0003.pdf | ||
| Am_0002.pdf | ||
| MIC1 - AM_0002.pdf | ||
| W9128F22R0048 Helo Ops Site Visit 5 May 2022.pdf | ||
| W9128F22R0048_MINOT AFB HELO OPS_SPS Solicitation_Amendment 0001.pdf | ||
| Am_0001_SPECS.pdf | ||
| MIC1 - VOL. 2_Part 2 of 3.pdf | ||
| MIC1 - VOL. 2_Part 3 of 3.pdf | ||
| MIC1 - VOL. 2_Part 1 of 3.pdf | ||
| Site Video 2.zip | ZIP file | |
| Site Photos.zip | ZIP file | |
| W9128F22R0048_SPECS.pdf | ||
| Site Videos 1.zip | ZIP file | |
| VOL1of2_W9128F22R0048_DRAWINGS_20220228.pdf |
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
FA002
F
IR
E A
L A
R M
K E
Y E
D N
O T
E S
M
IN
O T
A F
B N
O R
T H
D A
K O
T A
C O
N S
O L
ID
A T
E D
H E
L O
/T R
F /O
P S
A M
U
A L E
R T
F A
C
IL
IT
Y
P N
Q J V
F (1
(F Y
O M
A H
A D
IS
T
R
IC
T C
A P
IT
O
L A
V E
O M
A H
A N
E
S .L
IN
D
G R
E N
S .L
IN
D
G R
E N
S .L
IN
D
G R
E N
D .O
T T
E R
B Y
/2
/2
W F
R
M
IC
-G
H L N
-H
E L O
T
R F
-M E
.R V
T
KEYED NOTES - FA100 THROUGH FA400 SERIES SHEETS
A1 SLEEPING ROOM SPEAKERS MUST PRODUCE A 520 HZ SIGNAL TEMPORAL THREE (T3) FOR FIRE ALARM AND 520 HZ SIGNAL TEMPORAL FOUR (T4) FOR CARBON MONOXIDE (UFC 3-600-01 SECTIONS 9-18.6.3(b) AND 9-19.3.4).
A2 AUDIBLE NOTIFICATION NOT REQUIRED AS AN AREA NOT OCCUPIED BY PEOPLE ON A REGULAR BASIS (NFPA 72 SECTION 3.3.177 VIA SECTION 18.4.1.4.2; UFC 4-021-01 SECTION 4-6.1.2) AND NOT STIPULATED IN UFC 3-600-01, UFC 4-021-01, OR UFC 4-211-01.
A3 SPEAKERS IN EXIT STAIRS AND EXIT PASSAGEWAYS SHALL BE A SEPARATE ZONE WITHIN THE LARGER ZONE WHICH DOES NOT PROPAGATE EVACUATION MESSAGES. (NFPA 72 SECTION 24.4.8.4.1)
V1 VISUAL NOTIFICATION MUST BE PROVIDED IN NORMALLY UNOCCUPIED SPACES GREATER THAN 900 SF (UFC 3-600-01 SECTION 9-18.6.3(g)).
V2 VISUAL NOTIFICATION MUST BE PROVIDED IN NORMALLY UNOCCUPIED SPACES LESS THAN OR EQUAL TO 900 SF WHEN AMBIENT NOISE IS LOUD ENOUGH TO REQUIRE HEARING PROTECTION (UFC 3-600-01 SECTION 9-18.6.3(g)).
V3 VISUAL NOTIFICATION NOT REQUIRED AS A NORMALLY UNOCCUPIED SPACES LESS THAN OR EQUAL TO 900 SF WITH LOW AMBIENT NOISE (UFC 3-600-01 SECTION 9-18.6.3(g,h)).
V4 VISUAL NOTIFICATION NOT REQUIRED PER NFPA 101 SECTION 9.6.3.5.5.
V6 FIXTURE/CEILING HEIGHT AND CRANE CLEARANCE EXCEEDS 30'-0". PROVIDE WALL-MOUNTED VISUAL NOTIFICATION APPLIANCES. (NFPA 72 SECTION 18.5.5.4.6)
KEYED NOTES - FA100 THROUGH FA400 SERIES SHEETS
1 ELEVATOR FIREFIGHTERS' EMERGENCY OPERATION (FEO) RELAY MODULES TO SEND ELEVATOR TO A GIVEN FLOOR. COORDINATE WITH ELEVATOR SUPPLIER.
2 ELEVATOR ECB SHUNT TRIP CONTROL MODULE.
3 ELEVATOR SHAFT SMOKE DETECTOR. LOCATE PER UFC 3-600-01.
4 SKYLIGHT WELL SHALL BE TREATED AS A "SEPARATE AREA" PER NFPA 72 SECTION 17.6.3.3.1.3. PROVIDE HEAT DETECTOR COVERAGE ACCORDINGLY.
5 PROVIDE WITH A SOUNDER BASE.
6 PROVIDE SMOKE DETECTOR IN EACH SLEEPING ROOM AND SHARED/COMMON SPACE OF A SUITE REGARDLESS OF OCCUPANCY OR THE PRESENCE OF OTHER DETECTION OR PROTECTION SYSTEMS IN THE FACILITY PER
UFC 3-600-01.
7 DASHED LINE INDICATES EXTENT OF DORMITORY. ACTIVATION OF A SMOKE DETECTOR IN ANY OF THE SLEEPING ROOMS SHALL ACTIVATE THE NOTIFICATION APPLIANCES IN ENTIRE AREA (FA/MNS SPEAKERS AND STROBES, BUT NOT "RESPONSE") BUT SHALL NOT ACTIVATE THE BUILDING FIRE ALARM NOTIFICATION APPLIANCES. (UFC 3-600-01 SECTION 9-18.7.5.2; NFPA 101 SECTIONS 9.6.2.10.9 AND 9.6.2.10.10)
8 RECESSED MASS NOTIFICATION SYSTEM LOCAL OPERATING CONSOLE WITH MICROPHONE.
9 SURFACE MASS NOTIFICATION SYSTEM LOCAL OPERATING CONSOLE WITH MICROPHONE.
10 SHOULD THE BATTERY COMPARTMENTS EXTEND GREATER THAN 4 INCHES OUT FROM THE FINISHED WALL, THE BATTERIES SHALL BE LOCATED IN 127 PA/FIRE ALARM ROOM.
12 ROUTE CONDUIT(S) THROUGH THE HANGAR BAY, THEN INTO ROOM 127 PA/FIRE ALARM. COORDINATE FINAL ANTENNA(E) AND LOCATION WITH COR/5 CES FOR EXPOSURE/AIMING. ONE ANTENNA SHOWN ASSUMING COMBINED FIRE ALARM TRANSCEIVER AND BASEWIDE MASS NOTIFICATION RECEIVER; COORDINATE QUANTITY OF ANTENNAE REQUIRED WITH EQUIPMENT INSTALLED.
13 SPACE DEDICATED FOR RSCP AND CSMP BATTERIES AS REQUIRED.
14 SPACE DEDICATED FOR CSMP BATTERIES AS REQUIRED.
15 PROVIDE MONITOR MODULE AND ROUTE UNDERGROUND CIRCUIT PER NFPA 70 ARTICLE 800 TO SUPERVISE POST INDICATOR VALVE TAMPER SWITCH. IF MONITOR MODULE IS LOCATED OUTSIDE, IT SHALL BE
WEATHERPROOF. PIV LOOPS SHALL BE EQUIPPED WITH TVSS.
16 ADDRESSABLE MONITOR MODULES FOR MANUAL STATIONS, RATE-COMPENSATED HEAT DETECTORS, AND OUTPUT/CONTROL MODULES SHALL NOT BE LOCATED IN THE HANGAR BAY PER UFC 4-211-01, PLUS ANY MODULES WHOSE WARRANTY WOULD BE VOIDED BY EXPOSURE TO EXTREME TEMPERATURES. THE HANGAR BAY SHALL BE CONSIDERED AN "OUTDOOR" SPACE FOR EQUIPMENT RATING PURPOSES WHERE TEMPERATURES ABOVE 80°F AND BELOW 32°F MAY BE PRESENT. LOCATE IN A CABINET IN A SPACE CONDITIONED TO BETWEEN 60°F AND 80°F.
19 RELAY MODULE(S) FOR MAIN ACCESS CONTROL SYSTEM (ACS) PANEL (SYSTEM SHOWN ON EY SHEETS). COORDINATE EXACT LOCATION WITH INSTALLED PANEL.
20 RELAY MODULES FOR MAIN LIGHTING CONTROL SYSTEM (LCS) PANEL (SYSTEM SHOWN ON EL SHEETS). COORDINATE EXACT LOCATION WITH INSTALLED PANEL.
21 RELAY MODULE(S) FOR MUTE OVERRIDE OF ROOM LOCAL AUDIO CONTROL(S). COORDINATE EXACT LOCATION WITH INSTALLED DEVICE. ANNOTATION INDICATES THE MUTING ZONE WITH RESPECT TO THE FACP AND
AUDIBLE MESSAGE TRANSMISSION MATRICES.
22 THIS VIEW DOES NOT INCLUDE THE ELEVATED EQUIPMENT MEZZANINE (SEE NESTED CALLOUT FOR CONTENTS OF ELEVATED AREA). ELEMENTS SHOWN WITHIN THE CALLOUT AREA IN THIS VIEW ARE ON GROUND LEVEL.
23 PROVIDE CONTROL MODULE TO CLOSE SMOKE DAMPER (FAIL SAFE IN CLOSED POSITION, SEE MECHANICAL) PER FACP MATRIX (ACTIVATION OF EITHER OF THE AIR TRANSFER SMOKE DETECTORS, ACTIVATION OF A
BUILDING FIRE ALARM, OR LOSS OF POWER SHALL CLOSE THE DAMPER).
24 PROVIDE CONTROL MODULE TO CLOSE FIRE-RATED OVERHEAD COILING DOOR PER FACP MATRIX. COORDINATE WITH SPECIFICATION SECTION 08 33 23.
25 SPEAKERS IN IMMEDIATE VICINITY OF LOC, ACU, OR PUBLIC ADDRESS MICROPHONE SHALL BE A SEPARATELY-WIRED ZONE SUCH THAT WHEN THE LOCAL AUDIO INPUT APPLIANCE IS UTILIZED, THE LOCAL SPEAKERS DO NOT
OPERATE AND CREATE FEEDBACK. (UFC 4-021-01 SECTION 4-6.1)
GAP SHOWN IN COVERAGE IS INTENDED TO REPRESENT THE GENERAL VICINITY OF THE LOC/ACU AND IS NOT INTENDED TO PERMIT A GAP IN AUDIBLE INTELLIGIBILITY.
26 STEADY TONE WATERFLOW INDICATOR. WEATHERPROOF HORN STROBE STAYS ACTIVE UNTIL WATER FLOW STOPS. MOUNT 96" A.F.G.
27 LOCATE SIGN ON HORIZONTAL STEEL MEMBER.
28 PROVIDE A CONTROL MODULE FOR EACH CIRCUIT ASSOCIATED WITH EACH AIR HANDLING OR VENTILATION UNIT.
29 PROVIDE PLACARD NEAR THE RTS AND DISCONNECT SWITCHES INDICATING THE LOCATION OF THE SHUNT TRIP CIRCUIT BREAKERS: "SHUNT TRIP CIRCUIT BREAKERS ARE OPENED UPON DUCT SMOKE DETECTION, OR FIRE ALARM. LOCATION OF CIRCUIT BREAKER IS IN ROOM <###>." <###> SHALL BE REPLACED WITH THE ROOM NUMBER. MINIMUM 2" BLACK TEXT ON WHITE FIELD WITH BLACK BORDER.
30 IN ACCORDANCE WITH UFC 4-211-01 SECTION C-6.4, FAN SHUTDOWN SHALL BE PERFORMED BY CONTROL MODULE ACTUATING A SHUNT TRIP CIRCUIT BREAKER RATHER THAN BY LOCAL CONTROL MODULE DUE TO THE TEMPERATURE AND HUMIDITY THAT MAY BE EXPERIENCED. CONTROL FOR FIRE ALARM PURPOSES SHALL NOT BE PROVIDED VIA EMCS/DDC. (AT/FP SHUTDOWN OF HVAC EQUIPMENT MAY BE PERFORMED VIA EMCS/DDC
PER UFC 4-211-01 SECTION 3-5.9.1 AND UFC 3-600-01 SECTION 9-18.1.2.2.)
31 PROVIDE DUCT SMOKE DETECTOR AND ASSOCIATED CONTROL MODULE TO SHUT DOWN UNIT UPON DETECTION OF SMOKE.
32 SMOKE DETECTOR FOR DOOR HOLD OPEN (NFPA 72 SECTIONS 17.7.5.6 AND 21.8; NFPA 101 SECTION 7.2.1.8.2(3)).
33 WALL MOUNT TO MAINTAIN PROXIMITY TO DOOR HEADER REQUIRED BY NFPA 72 SECTION 17.7.5.6.
34 IN THIS SPACE, ALL FIRE ALARM SYSTEM,CONTAINMENT SYSTEM, AND MASS NOTIFICATION SYSTEM DEVICES, INFRASTRUCTURE, AND CIRCUITING SHALL BE PROVIDED WITH WATERTIGHT CONDUIT/CONNECTIONS, MINIMUM NEMA 4 JUNCTION BOXES, BACK BOXES, AND ENCLOSURES. THIS INCLUDES ALL DETECTION, INITIATING, AND NOTIFICATION DEVICES. ADDITIONALLY, COORDINATE WITH SHEETS E-100, E-101, AND E-110 FOR
ADDITIONAL ENVIRONMENTAL CONDITION RATINGS.
35 IN THIS SPACE, ROUTE CONDUIT INTO THE BOTTOM OF THE BACKBOX FOR MANUAL FIRE ALARM STATIONS AND FLAME DETECTORS. PROVIDE THE LOW POINT OF THIS CONDUIT WITH A DRAIN. WHERE THE CONDUIT IS IN A HAZARDOUSLY CLASSIFIED AREA, PROVIDE BREATHERS IN ISOLATED PORTIONS OF THE CONDUIT SUCH AS WHERE SEALED OFFS ARE PROVIDED. RATE DRAINS AND BREATHERS FOR THE ELECTRICAL HAZARD CLASSIFICATION IN WHICH THEY ARE INSTALLED, BUT NOT BE LESS THAN NEMA 250 TYPE 4.
36 COORDINATE WITH CU AND CS SHEETS AND SPECIFICATIONS 28 31 76 AND 33 32 16. CONDUIT IN HANGAR OR BURIED SHALL BE IN RGS.
37 CONTAINMENT SYSTEM AUDIBLE AND VISUAL NOTIFICATION DEVICES. COORDINATE WITH AND PROVIDE SIGNAGE IN ACCORDANCE WITH SPECIFICATION 28 31 76.
38 UNDERGROUND CONDUITS FROM CSMP(A) TO TANK, MAY SHARE A COMMON TRENCH WITH POWER CONDUITS (SEE SHEET EP218). PROVIDE TVSS ON CIRCUITS ENTERING AND EXITING THE BUILDING.
39 LOCATE TANK GAUGE AND TEMPERATURE SENSOR INSIDE STORAGE TANK AND LEAK DETECTOR IN THE DOUBLE-WALL INTERSTITIAL SPACE. COORDINATE WITH CU AND CS SHEETS AND SPECIFICATIONS 28 31 76, 33 32 16, AND 33 56 10. CONNECTION SHALL BE BURIED IN RGS. PROVIDE LEAK DETECTION AT ALL INTERSTITIAL SPACE LOW POINTS.
40 WALL MOUNT TO MAINTAIN PROXIMITY TO OBSERVED EQUIPMENT.
41 COORDINATE WITH GAS-FIRED EQUIPMENT LOCATIONS (UFC 3-600-01 SECTION 9-19.2.1). SEE SPECIFICATION 28 31 76 PARAGRAPH "CARBON MONOXIDE DETECTORS" FOR PROXIMITY REQUIREMENTS.
42 PROVIDE ONE CARBON MONOXIDE DETECTOR DOWNSTREAM OF FUEL BURNING EQUIPMENT (UFC 3-600-01 SECTION 9-19.2.2).
43 COORDINATE QUANTITY AND LOCATIONS OF CARBON MONOXIDE DETECTORS IN PROXIMITY TO RADIANT HEATER BURNERS WITH THE SYSTEM INSTALLED. QUANTITY SHOWN IS BASED ON BASIS OF DESIGN LAYOUT AND
EQUIPMENT SHOWN ON THE MECHANICAL SHEETS.
44 PROVIDE SMOKE DETECTOR FOR PROTECTION OF CONTROL PANELS PER NFPA 72.
45 RECESSED COMBINED ADDRESSABLE FIRE ALARM AND MASS NOTIFICATION (ACU) CONTROL PANEL WITH MICROPHONE.
46 ELEVATOR RECALL SMOKE DETECTOR.
47 TAMPER SWITCH FOR SHUTOFF VALVE ON SPRINKLER LINE SUPPLYING HOISTWAY PIT (UFC 3-600-01 SECTION 4-12.4.4.2).
48 TAMPER SWITCH FOR SHUTOFF VALVE AND FLOW SWITCH ON SPRINKLER LINE SUPPLYING ELEVATOR MACHINE ROOM (UFC 3-600-01 SECTION 4-12.4.2.2).
49 TAMPER SWITCH FOR SHUTOFF VALVE AND FLOW SWITCH ON SPRINKLER LINE SUPPLYING TOP OF ELEVATOR HOISTWAY (UFC 3-600-01 SECTION 4-12.4.3.2).
50 PROVIDE SEALOFFS IN HANDHOLE (EXITING HAZARDOUS AREA) PER NFPA 70 SECTIONS 501.15 AND 513.8. SEE ES SHEETS FOR LOCATION.
51 KEY-OPERATED SUPERVISED DISCONNECT SWITCH. REFERENCE SECTION 28 31 76 "SOLENOID DISCONNECT SWITCHES" AND FA500 SERIES SHEETS.
52 HORN AND AMBER STROBE TO INDICATE CONTAINMENT TANK EVACUATION PUMP IS RUNNING. PROVIDE PLACARD STATING "HORN/STROBE INDICATES PUMP IS RUNNING". SEE SHEET EP506.
53 MONITOR TAMPER, FLOW, AND HIGH/LOW SUPERVISORY PRESSURE SWITCHES FOR THE DRY-PIPE SYSTEM SUPPLYING THE 021 BEARCAT STORAGE. VERIFY QUANTITY AND LOCATIONS WITH FIRE PROTECTION SYSTEM
INSTALLER.
55 MONITOR TAMPER AND WATER FLOW SWITCHES AND CONTROL THE SOLENOIDS/CONTROL VALVES FOR HANGAR BAY PRE-ACTION SPRINKLER SYSTEM. VERIFY QUANTITY AND LOCATIONS WITH FIRE PROTECTION SYSTEM
INSTALLER.
56 MONITOR TAMPER AND WATER FLOW SWITCHES FOR WET-PIPE SYSTEMS SUPPLYING THE ADMINISTRATIVE AREAS (NON-HANGAR). VERIFY QUANTITY AND LOCATIONS WITH FIRE PROTECTION SYSTEM INSTALLER.
57 MONITOR TAMPER AND WATER FLOW SWITCHES FOR WET-PIPE SYSTEMS SUPPLYING THE MAINTENANCE SHOP AND SIMULATOR AREAS. VERIFY QUANTITY AND LOCATIONS WITH FIRE PROTECTION SYSTEM INSTALLER.
59 FIRE ALARM MANUAL PULL STATIONS IN THIS SPACE SHALL HAVE CLEAR TAMPER COVER.
60 PROVIDE HYDROGEN DETECTOR ONLY IF UNSEALED BATTERIES ARE PROVIDED.
61 OPTICAL FLAME DETECTOR INHIBIT SWITCH LOCATED INSIDE RSCP. SEE SECTION 28 31 76 AND FA600 SERIES RSCP MATRICES.
62 SHOULD THE BATTERY COMPARTMENTS EXTEND GREATER THAN 4 INCHES OUT FROM THE FINISHED WALL, THE BATTERIES SHALL BE LOCATED IN 116 ELECTRICAL ROOM.
63 ALERT/RESPONSE START/SILENCE/STOP STATIONS. SEE SHEET FA501. LOCATE BOTTOM OF STATIONS APPROXIMATELY 12 INCHES ABOVE COUNTER SURFACE.
64 TEXT SIGN SHALL BE CONSIDERED ASSOCIATED WITH THE ALERT/RESPONSE AREA WITH RESPECT TO THE FIRE ALARM CONTROL PANEL (FACP) MATRIX IN THE FA600 SERIES SHEETS.
65 PROVIDE EARLY WARNING SMOKE DETECTION THROUGH THE VESDA AT THE CEILING LEVEL AND BELOW THE RAISED FLOOR THROUGHOUT THE PROTECTED SPACE.
66 LOCATE CENTERED ALONG WALL.
67 RELAY FOR FLASHING ELEVATOR CAB LIGHT AND AUDIBLE ALARM AT FIREFIGHTER'S SERVICE. COORDINATE WITH ELEVATOR SUPPLIER.
68 RELAY FOR CONSTANT ELEVATOR CAB LIGHT AT FIREFIGHTER'S SERVICE. COORDINATE WITH ELEVATOR SUPPLIER.
69 PUMP CONTROLLER MONITOR MODULES INTERFACE WITH FIRE ALARM CONTROL SYSTEM.
70 NITROGEN GENERATOR MONITOR MODULES INTERFACE WITH FIRE ALARM CONTROL SYSTEM.
71 PROVIDE SUPERVISORY MONITOR MODULE TO REPORT WHETHER THE DISCONNECT IS IN THE CLOSED POSITION PER NFPA 70 SECTION 695.4(B)(3)(e).
72 PROVIDE REMOTE ANNUNCIATOR WITH CONTROL FUNCTIONS THE SAME AS THE MAIN CONTROL PANEL. CONTROL FUNCTIONS MUST BE ACCESSIBLE ONLY BY USER CODE OR SECURED BEHIND A LOCKED PANEL. (UFC
3-600-01 SECTION 9-18.4.3)
73 MONITOR MODULE FOR FLOW SWITCH ON SPRINKLER LINE SUPPLYING ELEVATOR AREA TO MONITOR THE PRESENCE OF OPERATION VOLTAGE. LOSS OF VOLTAGE SHALL CAUSE ACTIVATION OF A SUPERVISORY SIGNAL.
(UFC 3-490-01 SECTION 6-1.2.2).
74 RED AGENT PRE-DISCHARGE STROBE. PROVIDE WITH SIGN SHOWN IN DETAIL 2/FA608.
75 BLUE AGENT DISCHARGE STROBE. PROVIDE WITH SIGN SHOWN IN DETAIL 3/FA608.
76 PROVIDE PRE-DISCHARGE/DISCHARGE AUDIBLE NOTIFICATION WARNING DEVICES ABOVE THE DOOR FOR ROOMS PROTECTED WITH A SPECIAL SUPPRESSION SYSTEM. PROVIDE ON BOTH THE INTERIOR AND EXTERIOR OF THE SPACE. NOTIFICATION SHALL BE INDEPENDENT OF THE FIRE ALARM CONTROL SYSTEM AND IN ADDITION TO THE NOTIFICATION PROVIDED IN THE SPACES TO WHICH THIS KEYED NOTE IS APPLIED IN ACCORDANCE
WITH NFPA 72 SECTIONS 24.4.7.1 AND A.24.4.7.1.
77 "CARP" AND "VESDA" SHALL BE CONSIDERED COMPONENTS OF THE "CLEAN AGENT EXTINGUISHING SYSTEM" (CAES).
78 CLEAN AGENT SAFING/DISCONNECT SWITCH. PROVIDE IN ENCLOSURE AND PROVIDE IDENTIFICATION PER SECTION 21 22 00.00 40.
79 PROVIDE PRE-DISCHARGE/DISCHARGE VISUAL NOTIFICATION WARNING DEVICES ABOVE THE DOOR FOR ROOMS PROTECTED WITH A SPECIAL SUPPRESSION SYSTEM. PROVIDE ON BOTH THE INTERIOR AND EXTERIOR OF THE SPACE. NOTIFICATION SHALL BE INDEPENDENT OF THE FIRE ALARM CONTROL SYSTEM AND IN ADDITION TO THE NOTIFICATION PROVIDED IN THE SPACES TO WHICH THIS KEYED NOTE IS APPLIED IN ACCORDANCE
WITH NFPA 72 SECTIONS 24.4.7.1 AND A.24.4.7.1.
80 AMBER "ALERT" ELEVATED SMOKE LEVELS STROBE. PROVIDE WITH SIGN SHOWN IN DETAIL 1/FA608.
81 MONITOR THE ELEVATOR SHUNT TRIP CONTROL MODULE FOR THE PRESENCE OF OPERATING VOLTAGE IN ACCORDANCE WITH NFPA 72 SECTION 21.4.4.
82 PROVIDE RELAYS FOR SHUTDOWN OF USER-PROVIDED RACK-MOUNTED UNINTERRUPTIBLE POWER SUPPLIES IN ACCORDANCE WITH NFPA 75 SECTION 11.4.7. LABEL THE RELAYS' INTENDED USE.
83 MONITOR ELECTRICAL POWER SUPPLYING THE N1SLT SHUNT TRIP DEVICE PER NFPA 75 SECTION 9.2.5.
84 LOCATE FIRE ALARM MAPS ABOVE ANNUNCIATOR.
85 PROVIDE CONTROL MODULE TO CLOSE SMOKE DAMPER (FAIL SAFE IN CLOSED POSITION, SEE MECHANICAL) PER CAES MATRIX (CLEAN AGENT RELEASE OR LOSS OF POWER SHALL CLOSE THE DAMPER).
86 COORDINATE ANTENNA(E) SYSTEM GROUNDING WITH EG SHEETS.
87 WHERE SHOWN ADJACENT TO EACH OTHER, THE "WP" ANNOTATION SHALL APPLY TO BOTH DEVICES.
96 COORDINATE WALL EQUIPMENT TO BE INSTALLED IN THE FOLLOWING ORDER FROM LEFT TO RIGHT: LIGHT SWITCH(ES), CLEAN AGENT RELEASING STATION, CLEAN AGENT ABORT STATION, VESDA PANEL.
97 LOCATE DOCUMENT STORAGE CABINET (SECTION 28 31 76) ON THIS WALL.
98 MONITOR MODULE AT CIRCUIT SUPPLYING A GIVEN TEXT SIGN BATTERY CHARGER. (TYPICAL)
99 CONTAINMENT TANK EVACUATION PUMP CONTROL PANEL PUMP RUNNING MONITORING MODULES. SEE SHEET EP506.
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
A
M
G E
N E
R A
L R
E V
IS
IO
N S
/3
/2
A
M
G E
N E
R A
L R
E V
IS
IO
N S
/1
/2
F F
F
CR
CR
CR
CR
CR
CR
CR
CR
CR
CR
CR
CR
CR
CR
CR
CR
CR
CR
CR
CR
CR
CR
CR
CR CR
CR
CR
CR
F
IR
IR
IR
IR
IR
D
IR
IR
IR
IR
IR
V R
C M
C M
C M
P
H
T
T
C M
C M
M M
F
R T
S
GOVT OVERSIGHT
SITE MGR
VESTIBULE
093A
TELECOM
JANITOR
CORRIDOR
086B
PLANS/SCHED/MOC
INFO CTR/CAMS
TOILET
093C
TOILET
093D
TOILET
093E
BREAK ROOM
ELEC
SIM STORAGE
130A
AIR
COMPRESSOR
050B
CORRIDOR
SIMULATOR
TOILET
093F
WP
WP
WP WP
WP
WP
WP WP
WP
WP
WP WP WP
WPWP
WP
WP
WP
WP WP WP
WP
WP
WP WP
WP
WP
WP
WP
WP
W P
W P
WP
WP
HVU-050
SUPPLY
WPWPWPWPWP
31 34 3738 40 42
B
G
J
P
S
U
Z
V
T
M
X
H
F
N
C
E
N.5
BB
H.8
A
K
AA
3628 30
Y
R
W
L
Q
32 33
D
Q.1
K.8
G.3
V.5
4 4
MAINTENANCE
HANGAR
MAINTENANCE
HANGAR
/2 x
"x
"x
/2 x
≈1/2 "x" ≈"x" ≈"x" ≈1/2 "x" ≈1/2 "x" ≈"x" ≈"x" ≈1/2 "x"
≈"x" ≈"x" ≈"x" ≈"x" ≈1/2 "x"
DRAFT CURTAIN DRAFT CURTAIN
E Q
E
Q
FA401
DRAFT CURTAIN
LOC
H V
U -0
H V
U -0
A
H V
U -0
34 35 34 35
CSMP(H)
HE40
F A
R P
S
F A
R P
S
59 59
AMU
H
H
N1SLT
(CARP)
N1SL
FA501
VESTIBULE
093G
F A
R P
S
W P
C S
M P
(H
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
FA114
F
IR
E A
L A
R M
I N
IT
IA
T
IO
N A
N D
C O
N T
R O
L P
L A
N F
IR
S
T F
L O
O R
A
R E
A D
M
IN
O T
A F
B N
O R
T H
D A
K O
T A
C O
N S
O L
ID
A T
E D
H E
L O
/T R
F /O
P S
A M
U
A L E
R T
F A
C
IL
IT
Y
P N
Q J V
F (1
(F Y
O M
A H
A D
IS
T
R
IC
T C
A P
IT
O
L A
V E
O M
A H
A N
E
S .L
IN
D
G R
E N
S .L
IN
D
G R
E N
S .L
IN
D
G R
E N
D .O
T T
E R
B Y
/2
/2
W F
R
M
IC
-G
H L N
-H
E L O
T
R F
-M E
.R V
T
1/8" = 1'-0"FA114
FIRST FLOOR PLAN - FIRE ALARM:
INITIATION DEVICES AND CONTROL EQUIPMENT - AREA D
PLAN NORTH
8'0 4' 16'
KEYPLAN - FIRST FLOOR
"D"
FOR SUPPLEMENTAL LEGEND AND GENERAL NOTES, SEE SHEET FA001.
FOR KEYED NOTES, SEE SHEET FA002.
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
A
M
G E
N E
R A
L R
E V
IS
IO
N S
/3
/2
A
M
G E
N E
R A
L R
E V
IS
IO
N S
/1
/2
FA/MNS ANTENNA
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
FA130
C O
M P
O S
IT
E
F
IR
E A
L A
R M
P L A
N R
O O
F
M
IN
O T
A F
B N
O R
T H
D A
K O
T A
C O
N S
O L
ID
A T
E D
H E
L O
/T R
F /O
P S
A M
U
A L E
R T
F A
C
IL
IT
Y
P N
Q J V
F (1
(F Y
O M
A H
A D
IS
T
R
IC
T C
A P
IT
O
L A
V E
O M
A H
A N
E
S .L
IN
D
G R
E N
S .L
IN
D
G R
E N
S .L
IN
D
G R
E N
D .O
T T
E R
B Y
/2
/2
W F
R
M
IC
-G
H L N
-H
E L O
T
R F
-M E
.R V
T
1/32" = 1'-0"FA130
1 COMPOSITE ROOF PLAN - FIRE ALARM: BASE BID
1/32" = 1'-0"FA130
1A COMPOSITE ROOF PLAN - FIRE ALARM: BID OPTION
PLAN NORTH
8'0 4' 16'
KEYPLAN - ROOF
"A" "B" "C" "D" "E"
"F"
"G"
"H"
FOR SUPPLEMENTAL LEGEND AND GENERAL NOTES, SEE SHEET FA001.
FOR KEYED NOTES, SEE SHEET FA002.
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
A
M
G E
N E
R A
L R
E V
IS
IO
N S
/1
/2
W
F
P
T
T
KP
R
E A
C T
IO
N
(0
K P R
E A
C T
IO
N
(0
H
OFDIS(050)OFDIS(060)
M
M
M
TM
F
M
W F
P
P
T
T
C M
KP
R
E A
C T
IO
N
(0
H
H
OFDIS(030)
M
M
M
T
T
T M
P
H
T
M
P
H
T
CASS
M
P
H
T
FPC070
ELECTRICAL
FIRE
SUPPRESSION
EQUIPMENT
S1MLF
F A
A
F A
M A
P
MODULE
CABINET
FIRE PUMP
FP-070
JOCKEY PUMP
JP-070
WET-PIPE SYSTEM
MAINTENANCE AREA
050 PREACTION
WATER RISERS
NITROGEN
GENERATOR
NG-070A
OS&Y
TS
BYPASS
TS
BYPASS
TS
BACKFLOW
PREVENTER
TS
BACKFLOW
PREVENTER
TS
BACKFLOW
PREVENTER TEST
TS
OS&Y
TS
CV
PS
FSTS
070 FDC
TS
CV
PS
TS
TS
050 PREACTION
WATER RISER
CV
PS
TS
CV
PS
TS
N
E
F A
R P
S F
A R
P S
F A
R P
S
RSCP070
JPCP
L
L
H
040 FDC
TS
BYPASS
TS
BYPASS
TS
OS&Y
TS
(TYP)
(TYP)
NITROGEN
GENERATOR
NG-070B
CV
PS
TS
CV
PS
060 PREACTION
WATER RISERS
TS
CV
PS
TS
OS&Y
TSOS&Y
TS
OS&Y
TS
FIRE
SUPPRESSION
EQUIPMENT
TELECOM
HALL
S1GLF
FPC040
F A
A
F A
M A
P
MODULE
CABINET
OS&Y
TS
OS&Y
TS
BYPASS
TS
BYPASS
TS
FIRE PUMP
FP-040
JOCKEY PUMP
JP-040
BACKFLOW
PREVENTER
TS
BACKFLOW
PREVENTER
TS
BACKFLOW
PREVENTER TEST
TS
TS
TS
TS
FS
FS
DRY-PIPE SYSTEM
BEARCAT STORAGE
WET-PIPE SYSTEM
1ST FLOOR ADMIN
030 PREACTION
WATER RISERS
PS
CV
NITROGEN GENERATOR
NG-040
TS
PS
CVTS
50 53 56
GG
51 5554
HH
52 55.8
GG.8
JPCP
F A
R P
S F
A R
P S
F A
R P
S
DISPATCH
115A
RSCP040
ELECTRICAL
HVU-03051
L
L
H
H
H
BYPASS
TS
BYPASS
TS
WET-PIPE SYSTEM
2ND FLOOR ADMIN 56
(TYP)
(TYP)
PS
CVTS
OS&Y
TS
OS&Y
TS
OS&Y
TS
ELECTRICAL
220A
50 51
X
W
F A
R P
S F
A R
P S
F A
R P
S
HS2GLF
PA/FIRE ALARM
S G
L F
7 R
A C
K A
P
A /F
A
TS
S
T
R
FARPS
F A
T
FARPSFARPS
H
57 57.1
FARPS FARPS
ELECTRICAL
200A
H
FARPS
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
FA400
E N
L A
R G
E D
F
IR
E A
L A
R M
P L A
N S
M
IN
O T
A F
B N
O R
T H
D A
K O
T A
C O
N S
O L
ID
A T
E D
H E
L O
/T R
F /O
P S
A M
U
A L E
R T
F A
C
IL
IT
Y
P N
Q J V
F (1
(F Y
O M
A H
A D
IS
T
R
IC
T C
A P
IT
O
L A
V E
O M
A H
A N
E
S .L
IN
D
G R
E N
S .L
IN
D
G R
E N
S .L
IN
D
G R
E N
D .O
T T
E R
B Y
/2
/2
W F
R
M
IC
-G
H L N
-H
E L O
T
R F
-M E
.R V
T
3/8" = 1'-0"FA400
ENLARGED FIRE ALARM PLAN
070/080 UTILITIES (INITIATION)
3/8" = 1'-0"FA400
2 ENLARGED FIRE ALARM PLAN - 040/117/118 UTILITIES (INITIATION)
3/8" = 1'-0"FA400
ENLARGED FIRE ALARM PLAN
220A ELECTRICAL (INITIATION)
3/8" = 1'-0"FA400
ENLARGED FIRE ALARM PLAN
127 PA/FIRE ALARM (INITIATION)
PLAN NORTH
0 2' 4' 6'FOR SUPPLEMENTAL LEGEND, GENERAL NOTES, AND KEYED NOTES, SEE SHEET FA001.
SEE EP400 SERIES SHEETS FOR MORE COMPREHENSIVE VIEWS REGARDING THE USE OF WALL SPACE IN THE ELECTRICAL ROOMS.
3/8" = 1'-0"FA400
ENLARGED FIRE ALARM PLAN
200A ELECTRICAL (INITIATION)
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
A
M
G E
N E
R A
L R
E V
IS
IO
N S
/3
/2
A
M
G E
N E
R A
L R
E V
IS
IO
N S
/1
/2
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
FA610
R
IS
E R
D
IA
G R
A M
N O
T E
S F
IR
E
A L A
R M
A N
D A
S S
O C
IA
T
E D
S Y
S T
E M
S
M
IN
O T
A F
B N
O R
T H
D A
K O
T A
C O
N S
O L
ID
A T
E D
H E
L O
/T R
F /O
P S
A M
U
A L E
R T
F A
C
IL
IT
Y
P N
Q J V
F (1
(F Y
O M
A H
A D
IS
T
R
IC
T C
A P
IT
O
L A
V E
O M
A H
A N
E
S .L
IN
D
G R
E N
S .L
IN
D
G R
E N
S .L
IN
D
G R
E N
D .O
T T
E R
B Y
/2
/2
W F
R
M
IC
-G
H L N
-H
E L O
T
R F
-M E
.R V
T
KEYED NOTES - FA610 SERIES RISER DIAGRAM
1 CONNECT TO 120 VAC, 20 AMP DEDICATED POWER CIRCUIT FROM FIRE ALARM POWER PANELS (S##LF#). TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) IS TO BE PROVIDED ON PANELS
SERVING FIRE ALARM CIRCUITS. SEE ELECTRICAL (EP) SHEETS FOR POWER PANEL AND LOCATION. FIRE PROTECTION EQUIPMENT SHALL BE SUPPLIED FROM POWER DISTRIBUTION EQUIPMENT
DESIGNATED AS DEDICATED TO FIRE PROTECTION/LIFE SAFETY.
2 PROVIDE GROUND PER NFPA 70.
3 RADIO ANTENNA. SEE FA500 SERIES FOR DETAIL AND SPECIFICATION 28 31 76 FOR ADDITIONAL REQUIREMENTS. ONE ANTENNA SHOWN ASSUMING COMBINED FIRE ALARM TRANSCEIVER AND BASEWIDE MASS NOTIFICATION RECEIVER; COORDINATE QUANTITY OF ANTENNAE REQUIRED WITH EQUIPMENT INSTALLED.
4 SINGLE SWITCH SHALL DISABLE ALL CONTROL VALVES ASSOCIATED WITH A CONTINUOUS HANGAR SPACE (I.E., 030, 050, OR 060).
5 COMBINED FACP/ACU TO BE CONSIDERED GENERIC. PROVIDE REMOTE PANELS, EQUIPMENT, AND DEVICES AS REQUIRED FOR COMPLETE AND USABLE SYSTEM.
6 PROVIDE MONITOR MODULE AND ROUTE UNDERGROUND CIRCUIT PER NFPA 70 ARTICLE 800. IF MONITOR MODULE IS LOCATED OUTSIDE, IT SHALL BE WEATHERPROOF; PROVIDE IN EXPLOSIONPROOF ENCLOSURE WHERE REQUIRED BY SHEET E-101. LOOPS FOR EXTERIOR EQUIPMENT SHALL BE EQUIPPED WITH TVSS.
7 INTELLIGENT, ADDRESSABLE FIRE ALARM CONTROL PANEL (PORTION OF COMBINATION FIRE ALARM/MASS NOTIFICATION CONTROL PANEL WITH INTEGRATED AUTONOMOUS CONTROL UNIT).
8 INTELLIGENT, ADDRESSABLE MASS NOTIFICATION CONTROL PANEL WITH INTEGRATED AUTONOMOUS CONTROL UNIT (PORTION OF COMBINATION FIRE ALARM/MASS NOTIFICATION CONTROL
PANEL WITH INTEGRATED AUTONOMOUS CONTROL UNIT).
9 INTELLIGENT, ADDRESSABLE RELEASING SERVICE CONTROL PANEL (RSCP) FOR ALL FOAM/WATER AND PREACTION SYSTEMS DETECTION AND RELEASING FUNCTIONS. DO NOT PROVIDE
OPENINGS OR CONDUIT ENTRY INTO THE TOP OF THE RSCP.
10 KEY-OPERATED SUPERVISED DISCONNECT SWITCH. REFERENCE SPECIFICATION 28 31 76 PARAGRAPH "SOLENOID DISCONNECT SWITCHES".
11 SEE SPECIFICATION 28 31 76 PARAGRAPH "OPTICAL FLAME DETECTOR INHIBIT SWITCH".
12 REFERENCE SPECIFICATION 28 31 76 PARAGRAPH "RADIO TRANSMITTER AND INTERFACE PANELS".
13 HVAC SHUTDOWN SWITCH (EPO).
14 CABINET MOUNTED METAL OXIDE VARISTOR (MOV) BASED SURGE PROTECTION DEVICE (SPD) AT THE PANEL POWER INPUT. THE DEVICE SHALL SUPPLEMENT THE SPD INTEGRAL TO THE PANEL.
THE DEVICE SHALL BE UL 1449 LISTED (3RD EDITION) AND SHALL SATISFY THE REQUIREMENTS OF IEEE C62.41.
15 MONITOR FOR FAILURE, PRESSURE, AND EXTENDED DURATION, IN ADDITION TO PROPERTIES AS REQUIRED BY OTHER ELEMENTS OF THIS CONTRACT.
16 MONITOR FOR DISCONNECT IN THE OPEN POSITION, IN ADDITION TO PROPERTIES AS REQUIRED BY OTHER ELEMENTS OF THIS CONTRACT.
17 MONITOR FOR LOSS OF PHASE/POWER FAILURE AND TROUBLE SIGNALS, IN ADDITION TO PROPERTIES AS REQUIRED BY OTHER ELEMENTS OF THIS CONTRACT.
18 MONITOR FOR PUMP RUNNING, LOSS OF PHASE/POWER FAILURE, LOW RESERVOIR, AND TROUBLE SIGNALS, IN ADDITION TO PROPERTIES AS REQUIRED BY OTHER ELEMENTS OF THIS CONTRACT.
19 TYPICAL. SEE PLANS AND COORDINATE WITH SYSTEM INSTALLER FOR FINAL QUANTITY.
GENERAL NOTES - FA610 SERIES RISER DIAGRAM
1 RISER IS A DIAGRAMMATIC REPRESENTATION OF THE FIRE ALARM/MASS NOTIFICATION SYSTEM AND IS NOT CONSIDERED COMPLETE. SEE FIRE ALARM/MASS NOTIFICATION PLANS FOR
LOCATIONS OF INITIATING DEVICES AND INTENT OF COVERAGE FOR NOTIFICATION APPLIANCES. PROVIDE DEVICES FOR A COMPLETE FUNCTIONAL SYSTEM NOT LIMITED TO ADDRESSABLE MONITOR MODULES FOR ALL DEVICES THAT DO NOT HAVE ADDRESS AND CONTROL MODULES TO CONTROL AUXILIARY FUNCTIONS.
2 PROVIDE A SINGLE FACP "SYSTEM" FOR ALL DETECTION ALARM FUNCTIONS IN THE FACILITY WHICH ARE NOT PART OF THE PREACTION FIRE SUPPRESSION SYSTEMS. THE FACP MUST BE FULLY COMPATIBLE WITH THE BASE FIRE ALARM RECEIVING SYSTEM WITHOUT FIELD MODIFICATIONS TO ANY SYSTEM HARDWARE OR SOFTWARE.
3 THE FIRE ALARM SYSTEM IS SHOWN WITH ITS OWN CONTROL PANEL. HOWEVER, IT IS PERMITTED FOR A SINGLE COMBINED FA/MNS CONTROL PANEL TO BE PROVIDED WHICH MEETS THE
FUNCTIONAL REQUIREMENTS OF BOTH SYSTEMS.
4 CONTRACTOR TO VERIFY QUANTITY AND LOCATIONS OF TAMPER SWITCHES, WATER FLOW SWITCHES, PRESSURE SWITCHES, SOLENOIDS, CONTROL ACTUATORS, ETC., AND THEIR RESPECTIVE MONITOR AND CONTROL MODULES WITH FIRE PROTECTION SYSTEM INSTALLER AND EXISTING CONDITIONS.
5 REFER TO FIRE ALARM/MASS NOTIFICATION SYSTEM FLOOR PLANS AND SPECIFICATIONS FOR PRELIMINARY QUANTITY AND LOCATIONS OF INDICATION AND NOTIFICATION DEVICES AND REMOTE
LOCAL OPERATING CONSOLES.
6 REFER TO THE FIRE ALARM AND MASS NOTIFICATION SPECIFICATIONS FOR ADDITIONAL INTERFACE REQUIREMENTS BETWEEN THE FIRE ALARM AND MASS NOTIFICATION SYSTEMS.
7 SEE OTHER FA SHEETS AND SPECIFICATION 28 31 76 FOR ADDITIONAL FIRE ALARM, MASS NOTIFICATION, RESPONSE, AND CONTAINMENT SYSTEM NOTES.
8 SEE FA600 SERIES SHEETS FOR FIRE ALARM AND RELEASING SERVICE CONTROL PANEL MATRICES.
9 RISER DEVICES SHOWN WITH SEPARATE MONITOR MODULES FOR INDIVIDUAL ADDRESSABILITY. WHERE DEVICES INSTALLED ARE INDIVIDUALLY ADDRESSABLE, REDUNDANT MONITORING
MODULE MAY BE OMITTED.
10 COMMUNICATION FUNCTIONALITY BETWEEN RELEASING SERVICE CONTROL PANEL AND BUILDING FIRE ALARM CONTROL PANEL/AUTONOMOUS CONTROL UNIT THROUGH DRY CONTACT/ADDRESSABLE MODULES ONLY TO ACCOMPLISH ACTIVATION OF OCCUPANT FIRE ALARM NOTIFICATION, COMMON SIGNAL TRANSMISSION, AND POINT IDENTIFICATION IN ACCORDANCE
WITH UFC 4-211-01 SECTION 3-6.19.2.
11 MAXIMUM NUMBER OF NOTIFICATION DEVICES PER CIRCUIT SHALL BE IN ACCORDANCE WITH THE CONTROL PANEL LIMITATIONS. CONDUCTOR INTEGRITY MONITORING IS REQUIRED.
12 PROVIDE ADDITIONAL SIGNALING LINE, NOTIFICATION APPLIANCE, AND INITIATING DEVICE CIRCUITS AND REMOTE POWER SUPPLIES AS REQUIRED SUCH THAT VOLTAGE DROP DOES NOT EXCEED THE MAXIMUM ALLOWED BY THE MANUFACTURER PER CIRCUIT. ADDITIONAL NOTIFICATION CIRCUITS AND ADDITIONAL POWER SUPPLIES MAY BE REQUIRED DEPENDING ON EQUIPMENT PROVIDED. SMOKE DETECTORS SHALL BE PROVIDED ABOVE REMOTE POWER SUPPLIES AND CONNECTED TO FACP INITIATING DEVICE LOOP. PROVIDE ADDITIONAL SLC, NAC, AND IDC CIRCUITS AS REQUIRED FOR THE QUANTITY OF DEVICES SHOWN AND REQUIRED, AND SUCH THAT VOLTAGE DROP DOES NOT EXCEED THE MAXIMUM ALLOWED BY THE MANUFACTURER AND SECTION 28 31
76 PER CIRCUIT.
13 PROVIDE CLASS B NOTIFICATION APPLIANCE CIRCUITS ROUTED BACK TO THE PANEL WITH SEPARATE AUDIBLE AND VISUAL CIRCUITS FOR SILENCE FEATURE. SEPARATE CIRCUITS SHALL ALSO
BE PROVIDED TO DISTINGUISH INTERIOR AND EXTERIOR NOTIFICATION APPLIANCES.
14 PROVIDE SMOKE DETECTORS TO PROTECT FIRE ALARM/MASS NOTIFICATION PANEL, RELEASING SERVICE CONTROL PANEL, CONTAINMENT SYSTEM MONITORING PANEL, FIRE ALARM
TRANSCEIVER, BIG VOICE RECEIVER, AND ANY REMOTE NOTIFICATION POWER SUPPLIES.
15 COMBINE MISCELLANEOUS COMPONENTS IN COMMON ENCLOSURES TO PROVIDE A CLEAN INSTALLATION. WHERE AN AUXILIARY BATTERY SUPPLY IS REQUIRED AND CANNOT BE RECESSED
WITHIN THE WALL, LOCATE IT REMOTELY IN A CONDITIONED, NORMALLY UNOCCUPIED AREA.
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
A
M
G E
N E
R A
L R
E V
IS
IO
N S
/3
/2
A
M
G E
N E
R A
L R
E V
IS
IO
N S
/1
/2
FIRE ALARM
CONTROL PANEL
(FACP)
A D
M
IN
IS
T
R A
T
IV
E A
R E
A S
B
E A
R C
A T
(N
O N
-H A
N G
A R
B A
Y
A M
U A
N D
S
IM
U L A
T O
R A
R E
S
N
-H A
N G
A R
B A
Y
A
L E
R T
H A
N G
A R
B A
Y
M
A
IN
T E
N A
N C
E H
A N
G A
R B
A Y
F
S
T O
R A
G E
H A
N G
A R
B A
Y
TSTS FS
M
021A DRY-PIPE SYSTEM, BEARCAT
STORAGE RISER
TSTS FS
040 WET-PIPE SYSTEM, 1ST FLOOR
ADMINISTRATIVE RISER
TSTS FS
040 WET-PIPE SYSTEM, 2ND FLOOR
ADMINISTRATIVE RISER
TSTS FS
070 WET-PIPE SYSTEM, AMU AREA
(NON-HANGAR) RISER
TS PS
040 PREACTION SYSTEM
030 ALERT HANGAR BAY RISER
TS PS
070 PREACTION SYSTEM
050 MAINTENANCE HANGAR BAY RISER
TS PS
070 PREACTION SYSTEM
060 STORAGE HANGAR BAY RISER
TS
OS&Y
C
V 040 FIRE SUPPRESSION ROOM
030 ALERT PREACTION SPRINKLER SYSTEM RISER
C
V 070 FIRE SUPPRESSION ROOM
050 MAINTENANCE PREACTION SPRINKLER SYSTEM RISER
C
V 070 FIRE SUPPRESSION ROOM
060 STORAGE PREACTION SPRINKLER SYSTEM RISER
TS
T R
A N
S C
E
IV
E R
D O
O R
B A
T T
E R
Y A
R E
A S
S
E E
K E
Y E
D
N
T E
S A
P P
L
IE
D T
O D
E T
E C
T O
R S
FFFF H
MM
MMM
MMM
MMM
MMM
MMM
MMM
M
M
M
NGEN
EXT. DUR.
M
PS
NGEN
M
ISO
ISO
ISO
ISO
ISO
ISO
ISO
ISO
ISO
ISO
ISO
ISO
ISO
ISO
ISO
ISO
ISO
ISO
ISO
ISO
ISO
ISO
RTS
D
N O
N -H
A N
G A
R A
R E
A S
T
Y P
RTS
D
H V
U -0
RTS
D
RTS
D
RTS
D
H V
U -0
H V
U -0
A
H V
U -0
TS
040 FIRE SUPPRESSION ROOM
POST INDICATOR VALVE
TS
TVSS
070 FIRE SUPPRESSION ROOM
POST INDICATOR VALVE
M
MTVSS
TS
OS&Y
TS
OS&Y
ISO
ISO
TS
M M M M M M M M M M M M
M
E N
T R
A N
C E
O S
Y
TS
M
B Y
P A
S S
T
Y P
TS
M
B A
C K
F L
P R
E V
E N
T E
R
T Y
P
TS
M
B A
C K
F L
E V
E N
T E
R T
E S
T
TS
M
M
IS
C
O S
Y
T
Y P
TS
M
F
D C
TS
M
F
D C
070 FIRE SUPPRESSION ROOM
VALVE MONITORING
ISO
ISO
TS
M
E N
T R
A N
C
Y
TS
M
B Y
P A
S S
T
Y P
TS
M
B A
C K
F L
E
V E
N T
(T
Y P
TS
M
B A
C K
F L
E V
E N
T
S T
TS
M
M
IS
C
O S
(T
P
040 FIRE SUPPRESSION ROOM
VALVE MONITORING
TS
M
B E
A R
C
Y -P
IP
E
R
IS
E R
M M
A D
M
IN
A R
E A
S A
N D
B E
A R
C
N -H
A N
G A
R B
A Y
A M
U A
N D
S
IM
U L A
T O
R A
R E
N
-H A
N G
A R
B A
Y
M
A
L E
R T
H A
N G
A R
B A
Y
M
M
A
IN
T E
N A
N C
E H
A N
G A
R B
A Y
M
S
T O
R A
G E
H A
N G
A R
B A
Y
ABOVE CONTROL PANELS AND REMOTE POWER SUPPLIES
ISO
ISO
M
F
IR
S T
F L
O
L
B B
Y
M
S E
C O
N D
F L O
B
B Y
M
M A
C H
IN
E
R O
O M
M
H O
IS
T
W A
Y
FS
M
FS
M M M M
TS TS TS
H O
IS
T
W A
Y
IT
H
U T
O F
F V
A L V
E
M A
C H
IN
E
R O
M
U
T O
F F
V A
L V
E
T O
P O
F H
O
IS
T W
U
T O
F F
V A
L V
E
T O
P O
F S
H A
R
IN
K
L E
R
M A
C H
IN
E
R O
M
R
IN
K
L E
R
ELEVATOR
MONITORING
M
F L
O W
S W
IT
C
H L
O
V O
L T
A G
E
T Y
P
M
S H
U N
T T
R
IP
D E
V
IC
S S
O F
V O
L T
A G
E
T Y
P
COMMON FIRE ALARM SIGNAL R
COMMON SUPERVISORY SIGNAL R
COMMON TROUBLE SIGNAL R
WATERFLOW R
CARBON MONOXIDE DETECTED R
FIRE WATER AREA LOW
TEMPERATURE SUPERVISORY SIGNAL
R
SUPERVISORY SIGNAL
MASS NOTIFICATION SYSTEM ACTIVE
R
SUPERVISORY SIGNAL - FA NAC
INTERRUPTED FOR MNS ANNOUNCEMENT
R
MASS NOTIFICATION PANEL TROUBLE R
FIRE PUMP RUNNING R
FIRE PROTECTION SYSTEM
PUMP POWER FAILURE
R
CLEAN AGENT EXTINGUISHING
SYSTEM RELEASE
R
SIGNALS TO
TRANSCEIVER
PRIMARY RECALL
FIRST FLOOR
R
PRIMARY RECALL
SECOND FLOOR
R
FIREFIGHTER'S SERVICE
FLASHING LIGHT/AUDIBLE
R
FIREFIGHTER'S SERVICE
CONSTANT LIGHT
R
SIGNALS TO ELEVATOR
CONTROLLER
OVERRIDE EGRESS DELAY DOORS R
OVERRIDE ACCESS CONTROL DOORS
FIRE ALARM EVACUATION
R
OVERRIDE ACCESS CONTROL DOORS
ALERT/RESPONSE EVENT
R
SIGNALS TO ACCESS
CONTROL SYSTEM
FIRE PUMP START SIGNAL: FPC040 R
FIRE PUMP START SIGNAL: FPC070 R
CM
CLOSE SMOKE DAMPERS IN RATED WALLS
ADMINISTRATIVE, ALERT, AND BEARCAT AREAS (TYP)
CM
CLOSE SMOKE DAMPERS IN RATED WALLS
AMU, STORAGE, AND MAINTENANCE HANGAR AREAS (TYP)
CM
CLOSE FIRE-RATED OVERHEAD COILING DOORS
AMU, STORAGE, AND MAINTENANCE HANGAR AREAS (TYP)
CM
CLOSE FIRE-RATED OVERHEAD COILING DOORS
ADMINISTRATIVE, ALERT, AND BEARCAT AREAS (TYP)
CM
SHUT DOWN AIR HANDING UNIT/HEATING AND VENTILATING
UNIT ASSOCIATED WITH RESPECTIVE DUCT SMOKE DETECTOR
R
RELEASE MAGNETICALLY HELD DOORS
ADMINISTRATIVE, ALERT, AND BEARCAT AREAS (TYP)
RELEASE MAGNETICALLY HELD DOORS
AMU, STORAGE, AND MAINTENANCE HANGAR AREAS (TYP)
R
HVAC SHUTDOWN AND DAMPER CLOSURE
(TYP BY AREA IDENTIFIED IN MATRIX)
R
SHUTDOWN AHU COLLOCATED WITH
GAS-FIRED EQUIPMENT (TYP)
R
FIRE WATER AREA LOW
TEMPERATURE SUPERVISORY SIGNAL
R
SENSITIVE ELECTRONICS AREA HIGH
TEMPERATURE SUPERVISORY SIGNAL
R
HYDROGEN DETECTOR SUPERVISORY SIGNAL R
CONTAINMENT SYSTEM SUPERVISORY SIGNAL R
CONTAINMENT SYSTEM FULL R
CONTAINMENT SYSTEM LEAK DETECTED R
CONTAINMENT SYSTEM UNDERGROUND
STORAGE TANK LOW TEMPERATURE
R
CONTAINMENT SYSTEM TROUBLE SIGNAL R
SIGNALS TO
DDC SYSTEM
MISCELLANEOUS
SIGNALS
AMU R
1ST ADMIN (TYP) R
2ND ADMIN (TYP) R
2ND ALERT (TYP) R
MUTE SIGNAL TO A/V
SPEAKER CONTROLS
EGRESS LIGHTING HOLD ON R
"RESPONSE" INITIATING ACTION R
SIGNALS TO LIGHTING
CONTROL SYSTEM
CMELEVATOR ENCLOSED CIRCUIT BREAKER
CMHVU-030 CIRCUIT BREAKERS (TYP)
CMHVU-050 CIRCUIT BREAKERS (TYP)
CMHVU-050A CIRCUIT BREAKERS (TYP)
CMHVU-060 CIRCUIT BREAKERS (TYP)
SIGNALS TO SHUNT
TRIP MODULES
PUBLIC
ADDRESS
(PA) SYSTEM
BATTERY
BACKUP
MOV
R
PUBLIC ADDRESS MESSAGE: NON-ALERT / NON-RESPONSE
GENERAL BUILDING NOTIFICATION
R
PUBLIC ADDRESS MESSAGE: ALERT / RESPONSE
SIGNALS TO FACP INDICATING
THE TYPE OF MESSAGEPUBLIC ADDRESS MESSAGE: NON-ALERT / NON-RESPONSE
MAINTENANCE AND HANGARS
R
PUBLIC ADDRESS MESSAGE: NON-ALERT / NON-RESPONSE
ADMINISTRATIVE
R
AUDIO SIGNALS TO ACU
SIGNAL TO BASE MASS NOTIFICATION SYSTEM R
1 2
CM
E Q
U
IP
M E
N T
S H
U T
D O
W N
T
ISO
021A RISER ROOM
LOW TEMPERATURE MONITORING
040 FIRE SUPPRESSION ROOM
LOW TEMPERATURE MONITORING
ISO
ISO
ISO
M
M
M
L
L
L
T
T
070 FIRE SUPPRESSION ROOM
LOW TEMPERATURE MONITORING
ISO
ISO
M
M
L
L
T
T
ISO
TEXT SIGN BATTERY CHARGER SUPPLY
CIRCUIT VOLTAGE MONITORING (TYP)
ISO
M
ACU LOC
LOC
BATTERY
BACKUP
BATTERY
BACKUP
MOV
MOV
MASS NOTIFICATION
SYSTEM
AUTONOMOUS
CONTROL UNIT
(ACU)
REMOTE LOCAL OPERATING
CONSOLE (TYP)
EPO
EPO
M
FIRE PUMP
CONTROLLER
FPC070
M
M
M
FIRE PUMP
CONTROLLER
FPC040
M
M
M
JOCKEY PUMP
CONTROLLER
JPCP070 M
JOCKEY PUMP
CONTROLLER
JPCP040 M
FPC070
DISCONNECT
M
FPC040
DISCONNECT
M
ISO
N1SLT SHUNT TRIP DEVICE
LOSS OF VOLTAGE MONITORING
ISO
M
ISO
ISO M
T
M H
T H
T
M H
T
M H
HIGH TEMPERATURE
MONITORING
E
C
IV
IS
P
L E
C O
M
/F A
ISO
ISO M
T
M H
T H
T
M H
T
M
E
C
L E
C O
M
E C
B
IM
C O
M
ISO
ISO
T
M H
T
M H
T
M H
L E
C O
M
E C
IS
P
A T
C H
ISO
ISO
T
M H
T
M H
T
M H
L E
C O
M
E
C
E
C
M
M
M
M
070 NITROGEN
GENERATOR
NGEN-070A
M
M
M
PS
NGEN
040 NITROGEN
GENERATOR
NGEN-040
M
M
M
PS
NGEN
021 NITROGEN
GENERATOR
NGEN-021A
M
M
M
PS
NGEN
R E
S E
T
S
IL
E N
C E
A C
K N
O W
L E
D G
E
SIGNALS FROM
RSCP040
SIGNALS FROM
RSCP070
SIGNALS FROM
CSMP
SIGNALS FROM
CAES
H
TVSS
070 FIRE SUPPRESSION ROOM
WATERFLOW INDICATOR
C
M
H
TVSS
040 FIRE SUPPRESSION ROOM
WATERFLOW INDICATOR
C
M
INTERIOR COMBINED FIRE ALARM/MASS
NOTIFICATION VISUAL NOTIFICATION DEVICES
AREAS NOT DESIGNATED AS DWELLING UNIT
C C
CC
C
M
TVSS
EXTERIOR FIRE ALARM VISUAL
NOTIFICATION DEVICES
C C
M
INTERIOR COMBINED FIRE ALARM/MASS
NOTIFICATION VISUAL NOTIFICATION DEVICES
DWELLING UNIT
C C
CC
C
M
INTERIOR ALERT/RESPONSE
VISUAL NOTIFICATION DEVICES
G G
GG
C
M
TEXT TEXT
LED NOTIFICATION TEXT SIGNS (TYP)
ALL OTHER SIGNS
C
M
TEXT TEXT
LED NOTIFICATION TEXT SIGNS (TYP)
SIGNS DESIGNATED AS "ALERT"
C
M
WP
WP
BATT BATT
BATT BATT
WP WP
S F
S F
EXTERIOR AUDIBLE NOTIFICATION DEVICES
PUBLIC SIDE (TYP)
INTERIOR AUDIBLE NOTIFICATION DEVICES
SEPARATE ZONES AS IDENTIFIED ON PLANS,
MATRICES, AND SPECIFICATIONS (TYP)
TVSS
C
M
C
M
WP WP
EXTERIOR AUDIBLE NOTIFICATION DEVICES
APRON SIDE (TYP)
TVSS
C
M
GRAPHICAL
ANNUNCIATOR
MAP (TYP)
LCD
ANNUNCIATOR
PANEL (TYP)
SIGNALS FROM
BVR
SIGNALS FROM
PA SYSTEM
ALERT / RESPONSE NOTIFICATION
START/SILENCE/STOP STATIONS
MISO
ISO
R0
M
R1
M
R2
AUDIO SIGNALS
FROM PA SYSTEM
H
HIGH TEMPERATURE
MONITORING
HIGH TEMPERATURE
MONITORING
HIGH TEMPERATURE
MONITORING
M M M
S L
E E
P
IN
G A
R E
A S
COCOCO
B O
IL
E
R R
O O
M A
JA
C E
N T
A R
E A
S
G A
S -F
U E
L E
D E
Q U
IP
M
E N
T
M M M
S L
E E
P
IN
G A
R E
A S
D O
O R
H O
L D
O P
E N
S A
D M
IN
IT
R A
T
IV
E A
N D
D O
R M
A R
E A
S
D O
O R
H O
L D
O P
E N
S A
M U
A N
D M
A
IN
T E
N A
N C
E H
A N
G A
R
FIRE ALARM
CONTROL PANEL
(FACP)
CONTINUED FROM
BOTTOM LEFT
SIGNALS FROM INPUT DEVICES
(SEE FA630 AND EY SHEETS)
LA
LIGHTNING
ARRESTER
FIRE ALARM
TRANSCEIVER
(FAT)
ANTENNA
SIGNALS FROM
RSCP040
SIGNALS FROM
RSCP070
SIGNALS FROM
FACP
BATTERY
BACKUP
MOV
1 2
CONTINUED ON
TOP RIGHT
070 NITROGEN
GENERATOR
NGEN-070B
M
M
M
PS
NGEN
AUDIO SIGNALS TO ACU
R
R
MESSAGE TYPE
SIGNALS TO FACP
STAR-SPANGLED
BANNER
REVEILLER
OTHER MESSAGES
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
FA611
R
IS
E R
D
IA
G R
A M
F
IR
E A
L A
R M
M
A S
S N
O T
IF
IC
A T
IO
N
A
N D
P
A R
T
IA
L
P U
B L
IC
A D
D R
E S
S S
Y S
T E
M S
M
IN
O T
A F
B N
O R
T H
D A
K O
T A
C O
N S
O L
ID
A T
E D
H E
L O
/T R
F /O
P S
A M
U
A L E
R T
F A
C
IL
IT
Y
P N
Q J V
F (1
(F Y
O M
A H
A D
IS
T
R
IC
T C
A P
IT
O
L A
V E
O M
A H
A N
E
S .L
IN
D
G R
E N
S .L
IN
D
G R
E N
S .L
IN
D
G R
E N
D .O
T T
E R
B Y
/2
/2
W F
R
M
IC
-G
H L N
-H
E L O
T
R F
-M E
.R V
T M
A R
K D
E S
C R
IP
T
IO
N
D A
T E
A
M
G E
N E
R A
L R
E V
IS
IO
N S
/3
/2
A
M
G E
N E
R A
L R
E V
IS
IO
N S
/1
/2
FOAM SUPPRESSION AND ASSOCIATED SUPPORT ELEMENTS REMOVED.
ADDITIONAL PREACTION ZONES ADDED.
VISUAL SYSTEM INPUTS
ABPUBLIC ADDRESS: ANY INPUT LOCATION
MODE: ALERT/RESPONSE FROM 119A OPS DESK1
V
IS
U A
L N
O T
IF
IC
A T
A
N S
M
IS
S
IO
N T
Y P
E S
A N
D Z
O N
E S
MODE: ALL OTHERS AT ANY LOCATION
3 3
MASS NOTIFICATION: PRE-RECORDED MESSAGE
BASEWIDE MNS: 127 PA/FIRE ALARM - STAR-SPANGLED BANNER OR REVEILLE
FIRE ALARM
SMOKE DETECTOR IN DORMITORY AREA71
R E
S P
O N
S E
S Y
S T
E M
S T
R O
B E
S
C O
M B
IN
E
D F
IR
E
A L A
R M
/M A
S S
N O
T
IF
IC
A
T
IO
N S
Y S
T E
M
A L E
R T
S
T R
O B
E S
A
L E
R T
D O
R M
NON-TEXT
VISUAL
NOTIFICATION
APPLIANCES
AA AC AD AE
LED TEXT
SIGNS
(SEE
LEGEND)
BBBA BC
NOTIFICATION INITIATION DUE TO HANGAR BAY (INCLUDING PASSTHROUGH FROM RELEASING SERVICES)
74 74
ACU: 126 ARMS VAULT LOBBY41
42 ANY LOC
BASEWIDE MNS: 127 PA/FIRE ALARM - ALL OTHER MESSAGES
RESPONSE NON-LIVE SIGNAL
KLAXON AUDIBLE SIGNAL BY PUSHBUTTON STATION61
A L L O
T H
E R
S
IG
N S
D E
S
IG
N A
T E
D O
N P
L A
N S
A S
A
L E
R T
(S
E E
F A
S
E R
IE
S
S H
E E
T K
E Y
E D
N O
T E
A P
P L
IC
A T
IO
N
RELEASING SERVICE
81 818181
C O
M B
IN
E
D F
IR
E
A L A
R M
/M A
S S
N O
T
IF
IC
A
T
IO
N S
Y S
T E
M
A L E
R T
S
T R
O B
E S
A
L L O
T H
E R
A R
E A
S
ACU: 126 ARMS VAULT LOBBY51
52 ANY LOC
BASEWIDE MNS: 127 PA/FIRE ALARM - ALL OTHER MESSAGES
MASS NOTIFICATION: LIVE MESSAGE
ABAA AC AD AE BBBA BC
ABAA AC AD AE BBBA BC
ABAA AC AD AE BBBA BC
ABAA AC AD AE BBBA BC
ABAA AC AD AE BBBA BC
ABAA AC AD AE BBBA BC
73 737373ALL OTHER NOTIFICATION TYPES
DTR
DTDT
DT
EH EH
EE
E DT
R
AP AP
AP
DT
APAP
DT
AP
ALAL
AL
AL AL
AL
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
FA620
V
IS
U A
L N
O T
IF
IC
A T
IO
N
Z O
N E
S D
IS
T
R
IB
U T
IO
N
M A
T R
IX
M
IN
O T
A F
B N
O R
T H
D A
K O
T A
C O
N S
O L
ID
A T
E D
H E
L O
/T R
F /O
P S
A M
U
A L E
R T
F A
C
IL
IT
Y
P N
Q J V
F (1
(F Y
O M
A H
A D
IS
T
R
IC
T C
A P
IT
O
L A
V E
O M
A H
A N
E
S .L
IN
D
G R
E N
S .L
IN
D
G R
E N
S .L
IN
D
G R
E N
D .O
T T
E R
B Y
/2
/2
W F
R
M
IC
-G
H L N
-H
E L O
T
R F
-M E
.R V
T
LED TEXT SIGN MESSAGE LEGEND
DT DISPLAY DATE AND TIME IF NO OTHER OPERATION.
R DISPLAY "RESPONSE".
AP DISPLAY "ANNOUNCEMENT" FOLLOWED BY THE TEXT VERSION OF THE PRE-RECORDED MESSAGE.
AL DISPLAY "ANNOUNCEMENT".
E DISPLAY "EVACUATE" FOLLOWED BY "PLEASE LEAVE THE BUILDING BY THE NEAREST EXIT".
EH DISPLAY "EVACUATE" FOLLOWED BY "DO NOT EXIT THROUGH THE HANGAR BAY".
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
A
M
G E
N E
R A
L R
E V
IS
IO
N S
/3
/2
A
M
G E
N E
R A
L R
E V
IS
IO
N S
/1
/2
FOAM BEACONS AND ASSOCIATED CONTACTORS REMOVED.
"BVR" NOMENCLATURE REVISED TO "BASEWIDE MNS".3
EXISTING VISUAL NOTIFICATION:
LED TEXT SIGN MESSAGES
ABPUBLIC ADDRESS: ANY INPUT LOCATION
MODE: ALERT/RESPONSE FROM 119A OPS DESK1
2 MODE: ALL OTHERS AT ANY LOCATION
3 3
MASS NOTIFICATION: PRE-RECORDED MESSAGE
BASEWIDE MNS: 127 PA/FIRE ALARM - STAR-SPANGLED BANNER OR REVEILLE
FIRE ALARM
SMOKE DETECTOR IN DORMITORY AREA71
M O
D E
A
L E
R T
/R E
S P
O N
S E
F R
O M
A
O P
S D
E S
K P
U B
D
R E
S S
A
N Y
I N
P U
C A
T
IO
N
AA AC
CBCA CC
ABAA AC
ABAA AC
NOTIFICATION INITIATION DUE TO HANGAR BAY
(INCLUDING PASSTHROUGH FROM RELEASING SERVICES)
73 73
ACU: 126 ARMS VAULT LOBBY41
42 ANY LOC
ABAA AC
BASEWIDE MNS: 127 PA/FIRE ALARM - ALL OTHER MESSAGES
RESPONSE NON-LIVE SIGNAL
KLAXON AUDIBLE SIGNAL BY PUSHBUTTON STATION61
ABAA AC
A N
Y L
O C
A
N Y
O T
H E
R L
O C
W H
E N
E X
IS
T
IN
G
M E
S S
A G
E I S
F R
O M
A L
O C
RELEASING SERVICE
81 81
ABAA AC
M O
D E
A
L L O
T H
E R
S A
T A
N Y
L O
C A
T
IO
N
ACU: 126 ARMS VAULT LOBBY51
52 ANY LOC
ABAA AC
BASEWIDE MNS: 127 PA/FIRE ALARM
MASS NOTIFICATION: LIVE MESSAGE
NEW VISUAL NOTIFICATION:
LED TEXT SIGN MESSAGES
BBBA BC
BBBA BC
BBBA BC
BBBA BC
BBBA BC
BBBA BC
BBBA BC
B
A S
E W
ID
E
M N
S P
A /F
IR
E
A L A
R M
S
T A
R -S
P A
N G
L E
D B
A N
N E
R O
R R
E V
E
IL
L E
BD
B A
S E
W
ID
E M
N S
P
A /F
IR
E
A L A
R M
A
L L O
T H
E R
M E
S S
A G
E S
BE
A C
U A
R M
S V
A U
L T
L O
B B
Y
CD
A N
Y O
T H
E R
L O
C
B A
S E
W
ID
E M
N S
P
A /F
IR
E
A L A
R M
A C
U A
R M
S V
A U
L T
L O
B B
Y
DBDA
EBEA EC
FBFA FC FD
CBCA CCBD BE CD DBDA EBEA EC FBFA FC FD
CBCA CCBD BE CD DBDA EBEA EC FBFA FC FD
CBCA CCBD BE CD DBDA EBEA EC FBFA FC FD
CBCA CCBD BE CD DBDA EBEA EC FBFA FC FD
CBCA CCBD BE CD DBDA EBEA EC FBFA FC FD
CBCA CCBD BE CD DBDA EBEA EC FBFA FC FD
K L A
X O
N A
U D
IB
L E
S
IG
N A
L B
Y P
U S
H B
U T
T O
N S
T A
T
IO
N
S M
O K
E D
E T
E C
T O
R I N
D O
R M
IT
O
R Y
A R
E A
N O
T
IF
IC
A
T
IO
N I N
IT
IA
T
IO
N D
U E
T O
H A
N G
A R
B A
Y
IN
C
L U
D
IN
G P
A S
S T
H R
O U
G H
F R
O M
R E
L E
A S
IN
G
S E
R V
IC
E
S
MASS NOTIF.:
PRE-RECORDED
MESSAGE
MASS NOTIF.:
LIVE
MESSAGE
R E
S P
O N
N
-L
IV
IG
N A
L
FIRE
ALARM
RELEASING
SERVICE
EXISTING VISUAL NOTIFICATION:
NON-TEXT VISUAL NOTIFICATION
APPLIANCES
ABPUBLIC ADDRESS: ANY INPUT LOCATION
MODE: ALERT/RESPONSE FROM 119A OPS DESK1
2 MODE: ALL OTHERS AT ANY LOCATION
3 3
MASS NOTIFICATION: PRE-RECORDED MESSAGE
BASEWIDE MNS: 127 PA/FIRE ALARM - STAR-SPANGLED BANNER OR REVEILLE
FIRE ALARM
SMOKE DETECTOR IN DORMITORY AREA71
M O
D E
A
L E
R T
/R E
S P
O N
S E
F R
O M
A
O P
S D
E S
K P
U B
D
R E
S S
A
N Y
I N
P U
C A
T
IO
N
AA AC
CBCA CC
ABAA AC
ABAA AC
NOTIFICATION INITIATION DUE TO HANGAR BAY
(INCLUDING PASSTHROUGH FROM RELEASING SERVICES)
73 73
ACU: 126 ARMS VAULT LOBBY41
42 ANY LOC
ABAA AC
BASEWIDE MNS: 127 PA/FIRE ALARM - ALL OTHER MESSAGES
RESPONSE NON-LIVE SIGNAL
KLAXON AUDIBLE SIGNAL BY PUSHBUTTON STATION61
ABAA AC
A N
Y L
O C
A
N Y
O T
H E
R L
O C
W H
E N
E X
IS
T
IN
G
M E
S S
A G
E I S
F R
O M
A L
O C
RELEASING SERVICE
81 81
ABAA AC
M O
D E
A
L L O
T H
E R
S A
T A
N Y
L O
C A
T
IO
N
ACU: 126 ARMS VAULT LOBBY51
52 ANY LOC
ABAA AC
BASEWIDE MNS: 127 PA/FIRE ALARM
MASS NOTIFICATION: LIVE MESSAGE
NEW VISUAL NOTIFICATION:
NON-TEXT VISUAL
NOTIFICATION APPLIANCES
BBBA BC
BBBA BC
BBBA BC
BBBA BC
BBBA BC
BBBA BC
BBBA BC
B A
S E
W
ID
E M
N S
P
A /F
IR
E
A L A
R M
S
T A
R -S
P A
N G
L E
D B
A N
N E
R O
R R
E V
E
IL
L E
BD
B A
S E
W
ID
E M
N S
P
A /F
IR
E
A L A
R M
A
L L O
T H
E R
M E
S S
A G
E S
BE
A
C U
A
R M
S V
A U
L T
L O
B B
Y
CD
A N
Y O
T H
E R
L O
C
B A
S E
W
ID
E M
N S
P
A /F
IR
E
A L A
R M
A C
U A
R M
S V
A U
L T
L O
B B
Y
DBDA
EBEA EC
FBFA FC FD
CBCA CCBD BE CD DBDA EBEA EC FBFA FC FD
CBCA CCBD BE CD DBDA EBEA EC FBFA FC FD
CBCA CCBD BE CD DBDA EBEA EC FBFA FC FD
CBCA CCBD BE CD DBDA EBEA EC FBFA FC FD
CBCA CCBD BE CD DBDA EBEA EC FBFA FC FD
CBCA CCBD BE CD DBDA EBEA EC FBFA FC FD
K L A
X O
N A
U D
IB
L E
S
IG
N A
L B
Y P
U S
H B
U T
T O
N S
T A
T
IO
N
S M
O K
E D
E T
E C
T O
R I N
D O
R M
IT
O
R Y
A R
E A
N O
T
IF
IC
A
T
IO
N I N
IT
IA
T
IO
N D
U E
T O
H A
N G
A R
B A
Y
IN
C
L U
D
IN
G P
A S
S T
H R
O U
G H
F R
O M
R E
L E
A S
IN
G
S E
R V
IC
E
S
MASS NOTIF.:
PRE-RECORDED
MESSAGE
MASS NOTIF.:
LIVE
MESSAGE
R E
S P
O N
N
-L
IV
IG
N A
L
FIRE
ALARM
RELEASING
SERVICE
I I I I I I I I I
SS
S
S S
S
S
S S S
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I I I I I I I I
SS S S S S
S
S
S
S
S
SS S
S
S S S
S
S
S S
S S
S S
S S
S S
S S
S S
S& S& S& S& S& S&
S&
S&
S&
S&
S&
S&
S&
S&
ALL OTHER NOTIFICATION TYPES
74 74747474747474
ED
ED
ED
ED
ED
ED
ED
ED
ED
ED
ED
ED
ED
ED
A L L O
T H
E R
N O
T
IF
IC
A
T
IO
N T
Y P
E S
A L L O
T H
E R
N O
T
IF
IC
A
T
IO
N T
Y P
E S
ALL OTHER NOTIFICATION TYPES
74 74 74 74 74 74 74 74
I S S S S S S I S&
S
S
S
S
S
S
S&
I
S
S
AE AE AE AE AE AE E N N N
TN TN E TN TN EN
N
N
N
N
N
N
T
T
T
N E
E
E
E
N
N
E
E
E
E
N N N N AN
N N N
AN
AN N N N
N N N
N N N
N N N
N N N
N N N
AN
AN
AN
EE
E
NN
N
E
E
E
NN
N
E E
E
T
T
T
T
T
T
E
E
E
T
T
T
T
T
T
E
E
E
TE
TE
TE
T
T
N
N
T
T
I
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
FA621
V
IS
U A
L N
O T
IF
IC
A T
IO
N
T R
A N
S M
IS
S
IO
N
P R
IO
R
IT
Y
M A
T R
IC
E
S
M
IN
O T
A F
B N
O R
T H
D A
K O
T A
C O
N S
O L
ID
A T
E D
H E
L O
/T R
F /O
P S
A M
U
A L E
R T
F A
C
IL
IT
Y
P N
Q J V
F (1
(F Y
O M
A H
A D
IS
T
R
IC
T C
A P
IT
O
L A
V E
O M
A H
A N
E
S .L
IN
D
G R
E N
S .L
IN
D
G R
E N
S .L
IN
D
G R
E N
D .O
T T
E R
B Y
/2
/2
W F
R
M
IC
-G
H L N
-H
E L O
T
R F
-M E
.R V
T
VISUAL NOTIFICATION PRIORITY NOTES:
1. GENERALLY, THE VISUAL NOTIFICATION SYSTEMS ARE EITHER INDEPENDENT AND DO NOT REQUIRE OVERRIDING, OR ARE SHARED AND NOTIFICATION PERSISTS FOR THE DURATION OF ALL ASSOCIATED INITIATING ACTIONS. THE EXCEPTION
TO THIS IS THE LED TEXT SIGNS DESCRIBED BELOW.
LED TEXT SIGN PRIORITY NOTES:
1. THE GENERAL HIERARCHY IS AS FOLLOWS:
a. FIRE ALARM
b. ALERT / RESPONSE PUBLIC ADDRESS LIVE MESSAGE
- CAPABLE OF OVERRIDING FIRE ALARM TEXT SIGN MESSAGE FOR UP TO 60 SECONDS.
c. ALERT / RESPONSE PUBLIC ADDRESS KLAXON ALARM
- CAPABLE OF OVERRIDING FIRE ALARM TEXT SIGN MESSAGE FOR UP TO 60 SECONDS.
d. BUILDING MASS NOTIFICATION: LIVE MESSAGES AND PRE-RECORDED MESSAGES
- CAPABLE OF OVERRIDING FIRE ALARM TEXT SIGN MESSAGE FOR UP TO 60 SECONDS.
- CAPABLE OF OVERRIDING ALERT / RESPONSE KLAXON TEXT MESSAGE FOR UP TO 60 SECONDS.
- NOT CAPABLE OF OVERRIDING ALERT / RESPONSE PUBLIC ADDRESS LIVE MESSAGE.
- ACU MESSAGES SHALL TAKE PRIORITY OVER LOC MESSAGES.
- ONE LOC SHALL NOT OVERRIDE A DIFFERENT LOC WHILE ORIGINAL MESSAGE IS IN PROGRESS.
e. BASE-WIDE MASS NOTIFICATION
- STAR-SPANGLED BANNER AND REVEILLE SHALL NOT TRANSMIT THROUGH BUILDING TEXT SIGN MESSAGE
SYSTEM.
NON-ALERT / NON-RESPONSE PUBLIC ADDRESS SHALL NOT CHANGE THE TEXT SIGN MESSAGE.
2. LIVE MESSAGES WITHIN A HIERARCHY LEVEL SHALL TAKE PRIORITY OVER PRE-RECORDED MESSAGES.
3. AUDIBLE NOTIFICATION OVERRIDES SHALL NOT INTERRUPT ANY VISUAL NOTIFICATION UNLESS STATED EXPLICITLY IN
VISUAL NOTIFICATION SEQUENCE OF OPERATIONS.
4. TEXT SIGN MESSAGE SYSTEM SHALL PRODUCE THE MESSAGE SPECIFIC TO THE "ALERT" ZONE TEXT SIGNS WHEN
IDENTIFIED BY THE FA600 AND FA620 SERIES MATRICES.
5. TABLE ON THIS SHEET IS GENERIC. SEE "VISUAL NOTIFICATION ZONES DISTRIBUTION MATRIX" FOR SUBZONES WITHIN TRANSMISSION ZONES THAT DO NOT DISTRIBUTE MESSAGES FROM SPECIFIC SOURCES ON A SUBZONE-SPECIFIC BASIS.
WHERE A MESSAGE TYPE IS ACTIVATED BUT DOES NOT APPLY TO A GIVEN ZONE OR SUBZONE, THE INITIATION OF A NON- APPLICABLE MESSAGE SHALL NOT INTERRUPT AN EXISTING APPLICABLE MESSAGE NOR SHALL IT PRECLUDE THE
INITIATION OF A NEW APPLICABLE MESSAGE TO THE ZONE IN QUESTION.
6. MASS NOTIFICATION SYSTEM MESSAGES SHALL AUTOMATICALLY END AFTER 10 MINUTES IF NOT ENDED MANUALLY (UFC
4-021-01 SECTION 4-4.2).
VISUAL NOTIFICATION PRIORITY LEGEND
NOT APPLICABLE.
E EXISTING VISUAL NOTIFICATION / TEXT DISPLAY MESSAGE HAS PRIORITY AND SHALL NOT BE OVERRIDDEN.
N NEW VISUAL NOTIFICATION / TEXT DISPLAY MESSAGE HAS PRIORITY AND SHALL OVERRIDE EXISTING MESSAGE.
T EXISTING VISUAL NOTIFICATION / TEXT DISPLAY MESSAGE HAS PRIORITY, BUT SHALL BE TEMPORARILY OVERRIDDEN FOR THE LESSER OF 60 SECONDS OR THE
CONCLUSION OF THE NEW MESSAGE.
I EXISTING AND NEW VISUAL NOTIFICATIONS MAY OPERATE SIMULTANEOUSLY (NOTIFICATIONS ARE OF INDEPENDENT SYSTEMS).
S EXISTING AND NEW VISUAL NOTIFICATIONS MAY OPERATE SIMULTANEOUSLY (NOTIFICATIONS UTILIZE THE SAME SYSTEM). VISUAL NOTIFICATION SHALL NOT DEACTIVATE UNTIL ALL INDICATORS FROM ASSOCIATED SYSTEMS HAVE CEASED OR THE SYSTEM IS SILENCED/RESET (SEE FACP MATRIX).
& UPON CONCLUSION OF NON-DORM AREA ALARM, THE NON-DORM AREA VISUAL NOTIFICATIONS SHALL EXTINGUISH. THE DORM AREA VISUAL NOTIFICATIONS
SHALL CONTINUE.
AE FOR TEXT SIGNS DESIGNATED AS "ALERT" ON THE PLANS, THIS ENTRY SHALL BE CONSIDERED "E".
FOR ALL OTHER TEXT SIGNS, THIS ENTRY SHALL BE CONSIDERED "N".
AN FOR TEXT SIGNS DESIGNATED AS "ALERT" ON THE PLANS, THIS ENTRY SHALL BE CONSIDERED "N".
FOR ALL OTHER TEXT SIGNS, THIS ENTRY SHALL BE CONSIDERED "E".
TE FOR TEXT SIGNS DESIGNATED AS "ALERT" ON THE PLANS, THIS ENTRY SHALL BE CONSIDERED "T".
FOR ALL OTHER TEXT SIGNS, THIS ENTRY SHALL BE CONSIDERED "E".
TN FOR TEXT SIGNS DESIGNATED AS "ALERT" ON THE PLANS, THIS ENTRY SHALL BE CONSIDERED "T".
FOR ALL OTHER TEXT SIGNS, THIS ENTRY SHALL BE CONSIDERED "N".
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
A
M
G E
N E
R A
L R
E V
IS
IO
N S
/3
/2
A
M
G E
N E
R A
L R
E V
IS
IO
N S
/1
/2
"BVR" NOMENCLATURE REVISED TO "BASEWIDE MNS".3
FOAM RELEASE FUNCTIONS REMOVED.2
3/4"x10' GROUND ROD
3/4"x10' GROUND ROD WITH TEST WELL
MGB
GROUND BARGB
TMGB
TGB
AIRCRAFT GROUNDING POINT, SEE DETAIL 7/EG502. "#-##" IS THE GROUND POINT IDENTIFIER DESCRIBED IN DETAIL 7/EG502. WHERE "BO" PREPENDS THE IDENTIFIER, DO NOT INCLUDE WHEN
PAINTING; THIS IS A DESIGN DESIGNATOR ONLY REPRESENTING "BID OPTION".
MAIN GROUND BAR
TELECOMMUNICATIONS MAIN GROUND BAR
TELECOMMUNICATIONS GROUND BAR
LIGHTNING PROTECTION ROOF MAIN CONDUCTORRC
LIGHTNING PROTECTION DOWN CONDUCTORDC
COUNTERPOISE GROUND LOOPG
AIR TERMINAL, 60" MINIMUM HEIGHT
AIR TERMINAL, 24" MINIMUM HEIGHT
AIR TERMINAL, 12" MINIMUM HEIGHT
PER UFC 3-575-01, BOND ANY METALLIC BODY WITHIN 10 FEET OF A DOWNCONDUCTOR TO THE LIGHTNING PROTECTION SYSTEM INSIDE HAZARDOUS AREAS. REFER TO E-100 SERIES FOR HAZARDOUS
AREA CLASSIFICATIONS.
DC
CGB CONTINUOUS GROUND BAR
EGB ELECTRICAL GROUND BAR
BONDING CONDUCTORS
AGB ANTENNA GROUND BAR
SUPPLEMENTAL LIGHTNING PROTECTION
AND GROUNDING LEGEND
GROUND BARS, SEE EG502 FOR SIZES BASED ON THE FOLLOWING DESIGNATIONS:
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
EG001
G R
O U
N D
IN
G
/L
IG
H T
N
IN
G P
R O
T E
C T
O N
N O
T E
S A
N D
S U
P P
L E
M E
N T
A L L
E G
E N
D
M
IN
O T
A F
B N
O R
T H
D A
K O
T A
C O
N S
O L
ID
A T
E D
H E
L O
/T R
F /O
P S
A M
U
A L E
R T
F A
C
IL
IT
Y
P N
Q J V
F (1
(F Y
O M
A H
A D
IS
T
R
IC
T C
A P
IT
O
L A
V E
O M
A H
A N
E
S .L
IN
D
G R
E N
S .L
IN
D
G R
E N
S .L
IN
D
G R
E N
M .M c N
A M
A R
A
/2
/2
W F
R
M
IC
-G
H L N
-H
E L O
T
R F
-M E
.R V
T
# KEYED NOTES - EG100 THROUGH EG400 SERIES SHEETS
1 SEE DETAIL 1/EG501.
2 SEE DETAIL 2/EG501.
3 AIR TERMINAL ON EXHAUST EQUIPMENT SERVING HAZARDOUS AREAS SHALL EXTEND MINIMUM 60 INCHES ABOVE EQUIPMENT PER UFC 3-575-01 PARAGRAPH
3-2.1. COORDINATE EXACT LOCATION WITH EQUIPMENT.
4 TO ARMAG COUNTERPOISE, SEE SHEETS EG600.
5 PER UFC 3-575-01, BOND FRAME OF DOOR IN/ALONG HAZARDOUS AREA WITH MINIMUM #6 AWG TO NEAREST COLUMN AND PROVIDE A FLEXIBLE BRAID BETWEEN DOOR AND DOOR FRAME. AT DOUBLE DOORS, PROVIDE A FLEXIBLE BRAID BETWEEN EACH DOOR AND DOOR FRAME.
6 BOND LADDER IN/ALONG HAZARDOUS AREA WITH MINIMUM #6 AWG TO NEAREST COLUMN.
7 BOND ROOF HATCH.
8 BOND LADDER.
9 BOND TUBULAR DAYLIGHTING DEVICE.
10 SKYLIGHT. LOCATE AIR TERMINALS AT TOP OF FEATURE
11 BOND MECHANICAL EQUIPMENT.
12 TO ESD FLOORING, SEE 9/EG502. SEE EG600 FOR CONDUCTOR SIZE.
13 2"x12"GROUND BAR FOR TELECOMMUNICATIONS ENCLOSURE. CONDUIT TO TMGB SHALL BE ROUTED IN CONDUIT.
14 TO TMGB. SEE EG600 FOR CONDUCTOR SIZE.
15 TO RAISED FLOOR. SEE EG600 FOR CONDUCTOR SIZE. SEE 3/EG503 FOR BONDING REQUIREMENTS.
16 TO MGB. SEE EG600 FOR CONDUCTOR SIZE.
17 SERVICE TRANSFORMER GROUND RODS (ONE FOR PRIMARY COMPARTMENT, ONE FOR SECONDARY COMPARTMENT). SEE SITE PLAN FOR LOCATION.
GROUNDING SHALL BE SEPARATE FROM BOLLARDS GROUNDING SYSTEM. SEE SECTION 26 12 19.10 SUBPART "GROUNDING" AND ES503 FOR REQUIREMENTS.
18 GENERATOR GROUND RODS AND GROUND RING. SEE SITE PLAN FOR LOCATION.
19 PROVIDE SEALOFF FOR EACH CONDUIT AT HAZARDOUS BOUNDARY.
20 ROOF ANTENNA CONDUITS/WEATHERHEADS. BOND TO LIGHTNING PROTECTION SYSTEM.
21 APPROXIMATE LOCATION OF FIRE ALARM TRANSCEIVER/MASS NOTIFICATION RECEIVER ANTENNA. BOND MAST/WEATHERHEAD TO LIGHTNING PROTECTION
SYSTEM. COORDINATE WITH FIRE ALARM INSTALLER FOR ANTENNA QUANTITY AND LOCATION.
22 CONDUITS FOR ANTENNA(E) GROUND CONDUCTORS. COORDINATE LOCATION WITH SPLIT SYSTEM CONDENSING UNIT SERVING 127 PA/FIRE ALARM LOCATED…