This is a combined synopsis/solicitation for commercial items issued by the Department of the Army Corps of Engineers Engineering District Little Rock for the Eglin NICoE Initial Outfitting Project. The solicitation is issued as a request for quote and is set aside for Service-Disabled Veteran-Owned Small Businesses with a size standard of 500 employees and NAICS code 337127. Quotes are due by January 8, 2020 at 1:00pm Central Time. A site visit is tentatively scheduled for December 4, 2019 at 9:00am Central Time at Eglin Air Force Base West Visitors Center. Interested contractors must provide notice of attending to the specified Army Corps of Engineers contact by November 29, 2019 at 11:00am Central Time and include required personal information for base access.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT MANUAL
NICoE Satellite Eglin Air Force Base
Intrepid Fallen Heroes Fund
Eglin Air Force Base, FL
CONSTRUCTION DOCUMENTS SUBMISSION
PROJECT NO.: 10822.000
ISSUE DATE: 4 January 2019
ISSUED FOR: CONSTRUCTION DOCUMENTS
Volume 2
SmithGroup Incorporated 1700 New York Avenue, NW Suite 100 Washington, DC 20006
SmithGroup Intrepid Fallen Heroes Fund Project No. 10822.00 NICoE Satellite, Eglin Air Force Base CONTRACT DOCUMENTS - January 4, 2019
SEALS PAGE 000107 - 1
DOCUMENT 000107 - SEALS PAGE
ARCHITECT
STRUCTURAL ENGINEER
ELECTRICAL ENGINEER
LANDSCAPE ARCHITECT
MECHANICAL/PLUMBING ENGINEER
FIRE PROTECTION ENGINEER
SEALS PAGE 000107 - 2
CIVIL ENGINEER
TECHNOLOGY ENGINEER
END OF DOCUMENT
TABLE OF CONTENTS 000110 - 1
DOCUMENT 000110 - TABLE OF CONTENTS
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
Document 000101 Cover Page Document 000107 Seals Page Document 000110 Table Of Contents
VOLUME 1
DIVISION 01 - GENERAL REQUIREMENTS
Section 011000 Summary Section 012300 Alternates Section 012500 Substitution Procedures Section 012510 Substitution Request Form Section 012600 Contract Modification Procedures Section 012900 Payment Procedures Section 012973 Schedule Of Values Section 013100 Project Management And Coordination Section 013110 Request For Interpretation Section 013200 Construction Progress Documentation Section 013300 Submittal Procedures Section 014000 Quality Requirements Section 014200 Definitions And Reference Standards Section 015000 Temporary Facilities And Controls Section 016000 Product Requirements Section 017300 Execution Section 017419 Construction Waste Management And Disposal Section 017700 Closeout Procedures Section 017823 Operation And Maintenance Data Section 017839 Project Record Documents Section 017900 Demonstration And Training Section 018113 Sustainable Design Requirements Section 018119 Construction Indoor Air Quality Management Section 019113 General Commissioning Requirements
DIVISION 02 - EXISTING CONDITIONS
Not Used
DIVISION 03 - CONCRETE
Section 030513 Common Work Results For Cast-In Place Concrete Slabs Section 033000 Cast-In-Place Concrete Section 033053 Miscellaneous Cast-In-Place Concrete
DIVISION 04 - MASONRY
Section 042000 Unit Masonry
DIVISION 05 - METALS
Section 051200 Structural Steel Framing Section 052100 Steel Joist Framing Section 053100 Steel Decking
TABLE OF CONTENTS 000110 - 2
Section 054000 Cold-Formed Metal Framing Section 055000 Metal Fabrications Section 057500 Decorative Formed Metal
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
Section 061053 Miscellaneous Rough Carpentry Section 061643 Gypsum Sheathing Section 062023 Interior Finish Carpentry Section 064023 Interior Architectural Woodwork
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
Section 071113 Bituminous Dampproofing Section 072100 Thermal Insulation Section 072726 Fluid-Applied Membrane Air Barriers Section 074243 Composite Wall Panels Section 075419 Thermoplastic Polyvinyl-Chloride (PVC) Roofing Section 076200 Sheet Metal Flashing And Trim Section 077113 Pre-Manufactured Metal Coping And Edge Systems Section 077200 Roof Accessories Section 079200 Joint Sealants
DIVISION 08 - OPENINGS
Section 081113 Hollow Metal Doors And Frames Section 081416 Flush Wood Doors Section 083113 Access Doors And Frames Section 084113 Aluminum-Framed Entrances And Storefronts Section 084126 All-Glass Entrances And Storefronts Section 084229 Sliding Automatic Entrances Section 084400 Curtain Walls Section 086300 Metal-Framed Skylights Section 087100 Door Hardware Section 088000 Glazing Section 089000 Louvers And Vents
DIVISION 09 - FINISHES
Section 092216 Non-Structural Metal Framing Section 092900 Gypsum Board Section 093000 Tiling Section 093033 Stone Tiling Section 095113 Acoustical Panel Ceilings Section 095426 Linear Wood Ceilings Section 096513 Resilient Base And Accessories Section 096519 Resilient Tile Flooring Section 096566 Resilient Athletic Flooring Section 096623 Resinous Matrix Terrazzo Flooring Section 096813 Tile Carpeting Section 097413 Wood Veneer Wallcovering Section 098433 Sound-Absorbing Wall Units Section 099113 Exterior Painting Section 099123 Interior Painting
DIVISION 10 - SPECIALTIES
Section 101100 Visual Display Units
TABLE OF CONTENTS 000110 - 3
Section 101419 Dimensional Letter Signage Section 101423 Panel Signage Section 102113 Toilet Compartments Section 102123 Cubicle Curtains And Track Section 102239 Folding Panel Partitions Section 102600 Wall And Door Protection Section 102800 Toilet, Bath, And Laundry Accessories Section 104400 Fire Protection Specialties Section 105126 Plastic Lockers Section 107113 Exterior Sun Control Devices Section 107516 Ground Set Flagpoles
DIVISION 11 - EQUIPMENT
Section 117000 Furniture And Equipment
DIVISION 12 - FURNISHINGS
Section 122413 Roller Window Shades Section 123661 Simulated Stone Countertops Section 124816 Entrance Floor Grilles Section 129300 Site Furnishings
DIVISION 13 - SPECIAL CONSTRUCTION
Section 134900 Radiation Protection
DIVISION 14 - CONVEYING EQUIPMENT
Not Used
VOLUME 2
DIVISION 21 - FIRE SUPPRESSION
Section 210517 Sleeves And Sleeve Seals For Fire-Suppression Piping Section 210523 General-Duty Valves For Water-Based Fire-Suppression Piping Section 210553 Identification For Fire-Suppression Piping And Equipment Section 211313 Wet-Pipe Sprinkler Systems
DIVISION 22 - PLUMBING
Section 220513 Common Motor Requirements For Plumbing Equipment Section 220516 Expansion Fittings And Loops For Plumbing Piping Section 220517 Sleeves And Sleeve Seals For Plumbing Piping Section 220518 Escutcheons For Plumbing Piping Section 220519 Meters And Gages For Plumbing Piping Section 220523 General-Duty Valves For Plumbing Piping Section 220529 Hangers And Supports For Plumbing Piping And Equipment Section 220548 Vibration And Seismic Controls For Plumbing Piping And Equipment Section 220553 Identification For Plumbing Piping And Equipment Section 220719 Plumbing Piping Insulation Section 221113 Facility Water Distribution Piping Section 221116 Domestic Water Piping Section 221123 Domestic Water Pumps Section 221313 Facility Sanitary Sewers Section 221316 Sanitary Waste And Vent Piping
TABLE OF CONTENTS 000110 - 4
Section 221319 Sanitary Waste Piping Specialties Section 221413 Facility Storm Drainage Piping Section 221423 Storm Drainage Piping Specialties Section 223400 Fuel-Fired, Domestic-Water Heaters Section 224213.13 Commercial Water Closets Section 224213.16 Commercial Urinals Section 224216.13 Commercial Lavatories Section 224216.16 Commercial Sinks Section 224223 Commercial Showers, Receptors, And Basins Section 224500 Emergency Plumbing Fixtures Section 224716 Pressure Water Coolers
DIVISION 23 - HEATING VENTILATING AND AIR CONDITIONING
Section 230130.51 HVAC Air-distribution System Cleaning Section 230513 Common Motor Requirements for HVAC Equipment Section 230516 Expansion Fittings and Loops for HVAC Piping Section 230517 Sleeves and Sleeve Seals for HVAC Piping Section 230518 Escutcheons for HVAC Piping Section 230519 Meters and Gages for HVAC Piping Section 230523 General-duty valves for HVAC Piping Section 230529 Hangers and Supports for HVAC Piping and Equipment Section 230533 Heat Tracing for HVAC Piping Section 230548 Vibration and Seismic Controls for HVAC Piping and Equipment Section 230548.13 Vibration Controls for HVAC Section 230553 Identification for HVAC Piping and Equipment Section 230593 Testing, Adjusting, and Balancing for HVAC Section 230713 Duct Insulation Section 230716 HVAC Equipment Insulation Section 230719 HVAC Piping Insulation Section 230800 Commissioning of HVAC Section 230900 Instrumentation and Control for HVAC Section 231123 Facility Natural-Gas Piping Section 232113 Hydronic Piping Section 232113.13 Underground Hydronic Piping Section 232116 Hydronic Piping Specialties Section 232123 Hydronic Pumps Section 232300 Refrigerant Piping Section 232500 HVAC Water Treatment Section 233113 Metal Ducts Section 233300 Air Duct Accessories Section 233423 HVAC Power Ventilators Section 233600 Air Terminal Units Section 233713 Diffusers, Registers, and Grilles Section 233723 HVAC Gravity Ventilators Section 234100 Particulate Air Filtration Section 235100 Breechings, Chimneys, and Stacks Section 235216 Condensing Boilers Section 236423 Scroll Water Chillers Section 237313 Modular Indoor Central-Station Air-Handling Units Section 238126 Split System Air-Conditioners Section 238216 Air Coils Section 238219 Fan Coil Units Section 238236 Finned-Tube Radiation Heaters Section 238239.16 Propeller Unit Heaters Section 238239.19 Wall and Ceiling Unit Heaters
TABLE OF CONTENTS 000110 - 5
DIVISION 26 - ELECTRICAL
Section 260519 Low-Voltage Electrical Power Conductors And Cables Section 260523 Control-Voltage Electrical Power Cables Section 260526 Grounding And Bonding For Electrical Systems Section 260529 Hangers And Supports For Electrical Systems Section 260533 Raceway And Boxes For Electrical Systems Section 260543 Underground Ducts And Raceways For Electrical Systems Section 260544 Sleeves And Sleeve Seals For Electrical Raceways And Cabling Section 260553 Identification For Electrical Systems Section 260573 Overcurrent Protective Device Coordination Study Section 260800 Commissioning Of Electrical Systems Section 260923 Lighting Control Devices Section 262200 Low-Voltage Transformers Section 262413 Switchboards Section 262416 Panelboards Section 262713 Electricity Metering Section 262726 Wiring Devices Section 262813 Fuses Section 262913 Enclosed Controllers Section 262923 Variable-Frequency Motor Controllers Section 264113 Lightning Protection For Structures Section 265119 LED Interior Lighting Section 265600 Exterior Lighting
DIVISION 27 - COMMUNICATIONS
Section 270500 Basic Communications Systems Requirements Section 270526 Communications Bonding Section 270528 Interior Communication Pathways Section 270553 Identification And Administration Section 271100 Communication Equipment Rooms Section 271300 Backbone Cabling Requirements Section 271343.53 Television Distribution System Section 271500 Horizontal Cabling Requirements Section 271710 Testing Section 271720 Support And Warranty Section 275223 Nurse Call System
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
Section 280500 Basic Electronic Safety And Security System Requirements Section 281300 Electronic Access Control Section 283111 Digital Addressable Fire-Alarm System
DIVISION 31 - EARTHWORK
Section 310000 Earthwork Section 311100 Clearing and Grubbing Section 313116.13 Chemical Termite Control
TABLE OF CONTENTS 000110 - 6
DIVISION 32 - EXTERIOR IMPROVEMENTS
Section 320119 Field Molded Sealants For Sealing Joints In Rigid Pavements Section 321123 Aggregate Base Courses Section 321213 Bituminous Tack And Prime Coats Section 321216 Hot-Mix Asphalt (HMA) For Roads Section 321313.06 Portland Cement Concrete Pavement For Roads And Site Facilities Section 321619 Concrete Curbs Gutters And Sidewalks Section 321723 Pavement Markings Section 329100 Soil Preparation Section 329210 Turf Grasses Section 329300 Planting
DIVISION 33 - UTILITIES
Section 334000 Storm Drainage Utilities
APPENDICES
Appendix A 33 10 00 Water Piping, Structures And Appurtenances (ASUS) Appendix B 33 30 00 Sanitary Sewer Pipe, Structures And Appurtenances (ASUS) Appendix C EA187121 Soil Management Plan (Terracon Consultants, Inc.)
END OF SECTION
Project No. 10822.000 NICoE Satellite, Eglin Air Force Base CONTRACT DOCUMENTS – January 4, 2019
SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING 210517 - 1
SECTION 210517 - SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section includes:
1. Sleeves.
2. Stack-sleeve fittings.
3. Sleeve-seal systems.
4. Sleeve-seal fittings.
5. Grout.
1.3 SUBMITTALS
A. Product Data: For each type of product indicated.
PART 2 - PRODUCTS
2.1 SLEEVES
A. Cast-Iron Wall Pipes: Cast or fabricated of cast or ductile iron and equivalent to ductile-iron pressure pipe, with plain ends and integral waterstop unless otherwise indicated.
B. Galvanized-Steel Wall Pipes: ASTM A 53/A 53M, Schedule 40, with plain ends and welded steel collar; zinc coated.
C. Galvanized-Steel-Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, zinc coated, with plain ends.
D. Galvanized-Steel-Sheet Sleeves: 0.0239-inch (0.6-mm) minimum thickness; round tube closed with welded longitudinal joint.
2.2 SLEEVE-SEAL SYSTEMS
A. Manufacturers: Subject to compliance with requirements, provide products by the following available manufacturers offering products that are comparable to but not limited to the following:
SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING 210517 - 2
1. Advance Products & Systems, Inc.
2. CALPICO, Inc.
3. Metraflex Company (The).
4. Pipeline Seal and Insulator, Inc.
B. Description: Modular sealing-element unit, designed for field assembly, for filling annular space between piping and sleeve.
1. Sealing Elements: EPDM-rubber or NBR interlocking links shaped to fit surface of pipe. Include type and number required for pipe material and size of pipe.
2. Pressure Plates: Carbon steel.
3. Connecting Bolts and Nuts: Stainless steel of length required to secure pressure plates to sealing elements.
2.3 SLEEVE-SEAL FITTINGS
A. Manufacturers: Subject to compliance with requirements, provide products by the following available manufacturers offering products that are comparable to but not limited to the following:
1. Pre-sealed Systems.
B. Description: Manufactured plastic, sleeve-type, waterstop assembly made for imbedding in concrete wall. Unit has plastic or rubber waterstop collar with center opening to match piping OD.
2.4 GROUT
A. Standard: ASTM C 1107/C 1107M, Grade B, post-hardening and volume-adjusting, dry, hydraulic-cement grout.
B. Characteristics: Non-shrink; recommended for interior and exterior applications.
C. Design Mix: 5000-psi (34.5-MPa), 28-day compressive strength.
D. Packaging: Premixed and factory packaged.
PART 3 - EXECUTION
3.1 SLEEVE INSTALLATION
A. Install sleeves for piping passing through penetrations in floors, partitions, roofs, and walls.
B. For sleeves that will have sleeve-seal system installed, select sleeves of size large enough to provide 1-inch (25-mm) annular clear space between piping and concrete slabs and walls.
1. Sleeves are not required for core-drilled holes.
SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING 210517 - 3
C. Install sleeves in concrete floors, concrete roof slabs, and concrete walls as new slabs and walls are constructed.
1. Permanent sleeves are not required for holes in slabs formed by molded-PE or -PP sleeves.
2. Cut sleeves to length for mounting flush with both surfaces.
a. Exception: Extend sleeves installed in floors of mechanical equipment areas or other wet areas 2 inches (50 mm) above finished floor level.
3. Using grout, seal the space outside of sleeves in slabs and walls without sleeve-seal system.
D. Install sleeves for pipes passing through interior partitions.
1. Cut sleeves to length for mounting flush with both surfaces.
2. Install sleeves that are large enough to provide 1/4-inch (6.4-mm) annular clear space between sleeve and pipe or pipe insulation.
3. Seal annular space between sleeve and piping or piping insulation; use joint sealants appropriate for size, depth, and location of joint. Comply with requirements for sealants specified in Division 07 Section "Joint Sealants."
E. Fire-Barrier Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and floors at pipe penetrations. Seal pipe penetrations with firestop materials. Comply with requirements for firestopping specified in Division 07 Section "Penetration Firestopping."
3.2 SLEEVE-SEAL-SYSTEM INSTALLATION
A. Install sleeve-seal systems in sleeves in exterior concrete walls and slabs-on-grade at service piping entries into building.
B. Select type, size, and number of sealing elements required for piping material and size and for sleeve ID or hole size. Position piping in center of sleeve. Center piping in penetration, assemble sleeve-seal system components, and install in annular space between piping and sleeve. Tighten bolts against pressure plates that cause sealing elements to expand and make a watertight seal.
3.3 SLEEVE-SEAL-FITTING INSTALLATION
A. Install sleeve-seal fittings in new walls and slabs as they are constructed.
B. Assemble fitting components of length to be flush with both surfaces of concrete slabs and walls. Position waterstop flange to be centered in concrete slab or wall.
C. Secure nailing flanges to concrete forms.
D. Using grout, seal the space around outside of sleeve-seal fittings.
3.4 SLEEVE AND SLEEVE-SEAL SCHEDULE
A. Use sleeves and sleeve seals for the following piping-penetration applications:
1. Interior Partitions:
a. Piping: Galvanized-steel-sheet sleeves.
SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING 210517 - 4
GENERAL-DUTY VALVES FOR WATER-BASED FIRE-SUPPRESSION PIPING 210523 - 1
SECTION 210523 - GENERAL-DUTY VALVES FOR WATER-BASED FIRE-SUPPRESSION PIPING
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Two-piece ball valves with indicators.
2. Check valves.
3. Bronze OS&Y gate valves.
4. Iron OS&Y gate valves.
5. NRS gate valves.
6. Indicator posts.
7. Trim and drain valves.
1.3 DEFINITIONS
A. NBR: Acrylonitrile-butadiene, Buna-N, or nitrile rubber.
B. NRS: Nonrising stem.
C. OS&Y: Outside screw and yoke.
D. SBR: Styrene-butadiene rubber.
1.4 ACTION SUBMITTALS
A. Product Data: For each type of valve.
1.5 DELIVERY, STORAGE, AND HANDLING
A. Prepare valves for shipping as follows:
1. Protect internal parts against rust and corrosion.
2. Protect threads, flange faces, and weld ends.
3. Set valves open to minimize exposure of functional surfaces.
B. Use the following precautions during storage:
1. Maintain valve end protection.
2. Store valves indoors and maintain at higher than ambient dew point temperature. If outdoor storage is necessary, store valves off the ground in watertight enclosures.
GENERAL-DUTY VALVES FOR WATER-BASED FIRE-SUPPRESSION PIPING 210523 - 2
C. Use sling to handle large valves; rig sling to avoid damage to exposed parts. Do not use operating handles or stems as lifting or rigging points.
D. Protect flanges and specialties from moisture and dirt.
PART 2 - PRODUCTS
2.1 GENERAL REQUIREMENTS FOR VALVES
A. UL Listed: Valves shall be listed in UL's "Online Certifications Directory" under the headings listed below and shall bear UL mark:
1. Main Level: HAMV - Fire Main Equipment.
a. Level 1: HCBZ - Indicator Posts, Gate Valve.
b. Level 1: HLOT - Valves.
1) Level 3: HLUG - Ball Valves, System Control.
2) Level 3: HMER - Check Valves.
3) Level 3: HMRZ - Gate Valves.
2. Main Level: VDGT - Sprinkler System & Water Spray System Devices.
a. Level 1: VQGU - Valves, Trim and Drain.
B. FM Global Approved: Valves shall be listed in its "Approval Guide," under the headings listed below:
1. Automated Sprinkler Systems:
a. Indicator posts.
b. Valves.
1) Gate valves.
2) Check valves.
a) Single check valves.
3) Miscellaneous valves.
C. Source Limitations for Valves: Obtain valves for each valve type from single manufacturer.
D. ASME Compliance:
1. ASME B16.1 for flanges on iron valves.
2. ASME B1.20.1 for threads for threaded-end valves.
3. ASME B31.9 for building services piping valves.
E. AWWA Compliance: Comply with AWWA C606 for grooved-end connections.
F. NFPA Compliance: Comply with NFPA 24 for valves.
G. Valve Pressure Ratings: Not less than the minimum pressure rating indicated or higher as required by system pressures.
H. Valve Sizes: Same as upstream piping unless otherwise indicated.
I. Valve Actuator Types:
GENERAL-DUTY VALVES FOR WATER-BASED FIRE-SUPPRESSION PIPING 210523 - 3
1. Worm-gear actuator with handwheel for quarter-turn valves, except for trim and drain valves.
2. Handwheel: For other than quarter-turn trim and drain valves.
3. Handlever: For quarter-turn trim and drain valves NPS 2 (DN 50) and smaller.
2.2 TWO-PIECE BALL VALVES WITH INDICATORS
A. Manufacturers: Subject to compliance with requirements, provide products by the following available manufacturers offering products that are comparable to but not limited to the following:
1. NIBCO INC.
2. Victaulic Company.
B. Description:
1. UL 1091, except with ball instead of disc and FM Global standard for indicating valves (ball type), Class Number 1112.
2. Minimum Pressure Rating: 175 psig (1200 kPa).
3. Body Design: Two piece.
4. Body Material: Forged brass or bronze.
5. Port Size: Full or standard.
6. Seats: PTFE.
7. Stem: Bronze or stainless steel.
8. Ball: Chrome-plated brass.
9. Actuator: Worm gear or traveling nut.
10. Supervisory Switch: Internal or external.
11. End Connections for Valves NPS 1 (DN 25) through NPS 2 (DN 50): Threaded ends.
12. End Connections for Valves NPS 2-1/2 (DN 65): Grooved ends.
2.3 CHECK VALVES
A. Manufacturers: Subject to compliance with requirements, provide products by the following available manufacturers offering products that are comparable to but not limited to the following:
1. Anvil International, Inc.
2. Fire Protection Products, Inc.
3. Fivalco Inc.
4. Globe Fire Sprinkler Corporation.
5. Kennedy Valve; a division of McWane, Inc.
6. Matco-Norca.
7. Mueller Co.; Water Products Division.
8. NIBCO INC.
9. Reliable Automatic Sprinkler Co., Inc.
10. Shurjoint Piping Products.
11. Tyco Fire & Building Products LP.
12. United Brass Works, Inc.
13. Venus Fire Protection Ltd.
14. Victaulic Company.
15. Viking Corporation.
http://www.specagent.com/LookUp/?uid=123456917201&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917202&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917213&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917214&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917215&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917216&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917217&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917218&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917219&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917220&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917221&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917222&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917223&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917224&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917225&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917226&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917227&mf=&src=wd
GENERAL-DUTY VALVES FOR WATER-BASED FIRE-SUPPRESSION PIPING 210523 - 4
16. Watts Water Technologies, Inc.
17. Wilson & Cousins Inc.
B. Description:
1. Standard: UL 312 and FM Global standard for swing check valves, Class Number
1210.
2. Minimum Pressure Rating: 175 psig (1200 kPa).
3. Type: Single swing check.
4. Body Material: Cast iron, ductile iron, or bronze.
5. Clapper: Bronze, ductile iron, or stainless steel with elastomeric seal.
6. Clapper Seat: Brass, bronze, or stainless steel.
7. Hinge Shaft: Bronze or stainless steel.
8. Hinge Spring: Stainless steel.
9. End Connections: Flanged, grooved, or threaded.
10. Cover plates: Required for check valves greater than 2” for maintenance.
2.4 TRIM AND DRAIN VALVES
A. Ball Valves:
1. Manufacturers: Subject to compliance with requirements, provide products by the following available manufacturers offering products that are comparable to but not limited to the following:
a. Conbraco Industries, Inc.; Apollo Valves.
b. Fire-End & Croker Corporation.
c. Fire Protection Products, Inc.
d. Flowserve.
e. FNW; Ferguson Enterprises, Inc.
f. Jomar International, LTD.
g. Kitz Corporation.
h. Legend Valve.
i. Metso Automation USA Inc.
j. Milwaukee Valve Company.
k. NIBCO INC.
l. Potter Roemer.
m. Red-White Valve Corporation.
n. Tyco Fire & Building Products LP.
o. Victaulic Company.
p. Watts Water Technologies, Inc.
2. Description:
a. Pressure Rating: 175 psig (1200 kPa.
b. Body Design: Two piece.
c. Body Material: Forged brass or bronze.
d. Port size: Full or standard.
e. Seats: PTFE.
f. Stem: Bronze or stainless steel.
g. Ball: Chrome-plated brass.
h. Actuator: Handlever.
http://www.specagent.com/LookUp/?uid=123456917228&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917229&mf=&src=wd http://www.specagent.com/LookUp/?ulid=9233&mf=04&mf=95&src=wd&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917252&mf=&src=wd http://www.specagent.com/LookUp/?uid=12345917254&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917253&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917255&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917256&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917257&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917258&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917259&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917260&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917261&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917262&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917263&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917264&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917265&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917266&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917267&mf=&src=wd
GENERAL-DUTY VALVES FOR WATER-BASED FIRE-SUPPRESSION PIPING 210523 - 5
i. End Connections for Valves NPS 1 (DN 25) through NPS 2-1/2 (DN 65):
Threaded ends.
j. End Connections for Valves NPS 1-1/4 and NPS 2-1/2 (DN 32 and DN 65):
Grooved ends.
B. Angle Valves:
1. Manufacturers: Subject to compliance with requirements, provide products by the following available manufacturers offering products that are comparable to but not limited to the following:
a. Fire Protection Products, Inc.
b. NIBCO INC.
c. United Brass Works, Inc.
2. Description:
a. Pressure Rating: 175 psig (1200 kPa).
b. Body Material: Brass or bronze.
c. Ends: Threaded.
d. Stem: Bronze.
e. Disc: Bronze.
f. Packing: Asbestos free.
g. Handwheel: Malleable iron, bronze, or aluminum.
C. Globe Valves:
1. Manufacturers: Subject to compliance with requirements, provide products by the following available manufacturers offering products that are comparable to but not limited to the following:
a. NIBCO INC.
b. United Brass Works, Inc.
2. Description:
a. Pressure Rating: 175 psig (1200 kPa)
b. Body Material: Bronze with integral seat and screw-in bonnet.
c. Ends: Threaded.
d. Stem: Bronze.
e. Disc Holder and Nut: Bronze.
f. Disc Seat: Nitrile.
g. Packing: Asbestos free.
h. Handwheel: Malleable iron, bronze, or aluminum.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine valve interior for cleanliness, freedom from foreign matter, and corrosion.
Remove special packing materials, such as blocks, used to prevent disc movement during shipping and handling.
B. Operate valves in positions from fully open to fully closed. Examine guides and seats made accessible by such operations.
http://www.specagent.com/LookUp/?uid=123456917268&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917269&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917270&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917271&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456917272&mf=&src=wd
GENERAL-DUTY VALVES FOR WATER-BASED FIRE-SUPPRESSION PIPING 210523 - 6
C. Examine threads on valve and mating pipe for form and cleanliness.
D. Examine mating flange faces for conditions that might cause leakage. Check bolting for proper size, length, and material. Verify that gasket is of proper size, that its material composition is suitable for service, and that it is free from defects and damage.
E. Do not attempt to repair defective valves; replace with new valves.
3.2 GENERAL REQUIREMENTS FOR VALVE INSTALLATION
A. Comply with requirements in the following Sections for specific valve installation requirements and applications:
1. Section 211313 "Wet-Pipe Sprinkler Systems" for application of valves in wet-pipe, fire-suppression sprinkler systems.
B. Install listed fire-protection shutoff valves supervised-open, located to control sources of water supply except from fire-department connections. Install permanent identification signs indicating portion of system controlled by each valve.
C. Install valves having threaded connections with unions at each piece of equipment arranged to allow easy access, service, maintenance, and equipment removal without system shutdown. Provide separate support where necessary.
D. Install valves in horizontal piping with stem at or above the pipe center.
E. Install valves in position to allow full stem movement.
F. Install valve tags. Comply with requirements in Section 210553 "Identification for Fire- Suppression Piping and Equipment" for valve tags and schedules and signs on surfaces concealing valves; and the NFPA standard applying to the piping system in which valves are installed. Install permanent identification signs indicating the portion of system controlled by each valve.
G. Install check valve in each water-supply connection.
IDENTIFICATION FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT 210553 - 1
SECTION 210553 - IDENTIFICATION FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Equipment labels.
2. Warning signs and labels.
3. Pipe labels.
4. Stencils.
5. Valve tags.
6. Warning tags.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Samples: For color, letter style, and graphic representation required for each identification material and device.
C. Equipment-Label Schedule: Include a listing of all equipment to be labeled and the proposed content for each label.
D. Valve Schedules: Valve numbering scheme.
PART 2 - PRODUCTS
2.1 EQUIPMENT LABELS
A. Metal Labels for Equipment:
1. Manufacturers: Subject to compliance with requirements, provide products by the following available manufacturers offering products that are comparable to but not limited to the following:
a. Brady Corporation.
b. Brimar Industries, Inc.
c. Carlton Industries, LP.
d. Champion America.
e. Craftmark.
f. emedco.
g. Kolbi Pipe Marker Co.
h. LEM Products Inc.
i. Marking Services Inc.
http://www.specagent.com/LookUp/?uid=123456934653&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934654&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934660&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934655&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934656&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934661&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934657&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934662&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934658&mf=&src=wd
CONTRACT DOCUMENTS – January 4, 2019
IDENTIFICATION FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT 210553 - 2
j. Seton Identification Products.
2. Material and Thickness: stainless steel, 0.025 inch (0.64 mm), aluminum, 0.032 inch
(0.8 mm) or anodized aluminum, 0.032 inch (0.8 mm) thick, with predrilled holes for attachment hardware.
3. Letter Color: Black, Blue, or White.
4. Background Color: Red or White.
5. Minimum Label Size: Length and width vary for required label content, but not less than 2-1/2 by 3/4 inch (64 by 19 mm).
6. Minimum Letter Size: 1/4 inch (6.4 mm) for name of units if viewing distance is less than 24 inches (600 mm), 1/2 inch (13 mm) for viewing distances up to 72 inches (1830 mm), and proportionately larger lettering for greater viewing distances.
Include secondary lettering two-thirds to three-fourths the size of principal lettering.
7. Fasteners: Stainless-steel rivets or self-tapping screws.
8. Adhesive: Contact-type permanent adhesive, compatible with label and with substrate.
B. Plastic Labels for Equipment:
1. Manufacturers: Subject to compliance with requirements, provide products by the following available manufacturers offering products that are comparable to but not limited to the following:
a. Brady Corporation.
b. Brimar Industries, Inc.
c. Carlton Industries, LP.
d. Champion America.
e. Craftmark.
f. emedco.
g. Kolbi Pipe Marker Co.
h. LEM Products Inc.
i. Marking Services Inc.
j. Seton Identification Products.
2. Material and Thickness: Multilayer, multicolor, plastic labels for mechanical engraving, 1/16-inch (1.6 mm) 1/8 inch (3.2 mm) thick, with predrilled holes for attachment hardware.
3. Letter Color: White.
4. Background Color: Red.
5. Maximum Temperature: Able to withstand temperatures up to 160 deg F (71 deg C).
http://www.specagent.com/LookUp/?uid=123456934659&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934663&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934664&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934665&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934666&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934667&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934668&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934669&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934670&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934671&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934672&mf=&src=wd
IDENTIFICATION FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT 210553 - 3
6. Minimum Label Size: Length and width vary for required label content, but not less than 2-1/2 by 3/4 inch (64 by 19 mm).
7. Minimum Letter Size: 1/4 inch (6.4 mm) for name of units if viewing distance is less than 24 inches (600 mm), 1/2 inch (13 mm) for viewing distances up to 72 inches (1830 mm), and proportionately larger lettering for greater viewing distances.
Include secondary lettering two-thirds to three-fourths the size of principal lettering.
8. Fasteners: Stainless-steel rivets or self-tapping screws.
9. Adhesive: Contact-type permanent adhesive, compatible with label and with substrate.
C. Label Content: Include equipment's Drawing designation or unique equipment number, drawing numbers where equipment is indicated (plans, details, and schedules), and the Specification Section number and title where equipment is specified.
D. Equipment-Label Schedule: For each item of equipment to be labeled on 8-1/2-by-11-inch (A4) bond paper. Tabulate equipment identification number and identify Drawing numbers where equipment is indicated (plans, details, and schedules), and the Specification Section number and title where equipment is specified. Equipment schedule shall be included in operation and maintenance data.
2.2 WARNING SIGNS AND LABELS
A. Manufacturers: Subject to compliance with requirements, provide products by the following available manufacturers offering products that are comparable to but not limited to the following:
1. Brady Corporation.
2. Brimar Industries, Inc.
3. Carlton Industries, LP.
4. Champion America.
5. Craftmark.
6. Emedco, Inc.
7. LEM Products Inc.
8. Marking Services Inc.
9. National Marker Company.
10. Seton Identification Products.
11. Stranco, Inc.
B. Material and Thickness: Multilayer, multicolor, plastic labels for mechanical engraving, 1/16 inch (1.6 mm) to 1/8 inch (3.2 mm) thick, with predrilled holes for attachment hardware.
C. Letter Color: White.
D. Background Color: Red.
http://www.specagent.com/LookUp/?uid=123456934673&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934674&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934675&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934676&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934677&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934678&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934679&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934682&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934683&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934681&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934684&mf=&src=wd
CONTRACT DOCUMENTS – January 4, 2019
IDENTIFICATION FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT 210553 - 4
E. Maximum Temperature: Able to withstand temperatures up to 160 deg F (71 deg C).
F. Minimum Label Size: Length and width vary for required label content, but not less than 2- 1/2 by 3/4 inch (64 by 19 mm).
G. Minimum Letter Size: 1/4 inch (6.4 mm) for name of units if viewing distance is less than 24 inches (600 mm), 1/2 inch (13 mm) for viewing distances up to 72 inches (1830 mm), and proportionately larger lettering for greater viewing distances. Include secondary lettering two-thirds to three-fourths the size of principal lettering.
H. Fasteners: Stainless-steel rivets or self-tapping screws.
I. Adhesive: Contact-type permanent adhesive, compatible with label and with substrate.
J. Label Content: Include caution and warning information, plus emergency notification instructions.
2.3 PIPE LABELS
A. Manufacturers: Subject to compliance with requirements, provide products by the following available manufacturers offering products that are comparable to but not limited to the following:
1. ActionCraft Products, Inc.; a division of Industrial Test Equipment Co., Inc.
2. Brady Corporation.
3. Brimar Industries, Inc.
4. Carlton Industries, LP.
5. Champion America.
6. Craftmark.
7. Emedco, Inc.
8. Kolbi Pipe Marker Co.
9. LEM Products Inc.
10. Marking Services Inc.
11. Seon Identification Products.
B. General Requirements for Manufactured Pipe Labels: Preprinted, color-coded, with lettering indicating service and showing flow direction according to MIL-STD-101.
C. Pretensioned Pipe Labels: Precoiled, semirigid plastic formed to partially cover circumference of pipe and to attach to pipe without fasteners or adhesive.
D. Self-adhesive Pipe Labels: Printed plastic with contact-type, permanent-adhesive backing.
E. Pipe-Label Contents: Include identification of piping service using same designations or abbreviations as used on Drawings, pipe size, and an arrow indicating flow direction.
1. Flow-Direction Arrows: Integral with piping-system service lettering to accommodate both directions or as separate unit on each pipe label to indicate flow direction.
2. Lettering Size: At least 3/4 inch (18 mm) for pipe sizes less than 4 inches, and at least 2 inches (50 mm) for pipe sizes 4 inches and larger.
http://www.specagent.com/LookUp/?uid=123456934716&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934706&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934707&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934708&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934709&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934710&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934712&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934714&mf=&src=wd
CONTRACT DOCUMENTS – January 4, 2019
IDENTIFICATION FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT 210553 - 5
F. Pipe-Label Colors:
1. Background Color: Red No. 11105.
2. Letter Color: Black or White.
2.4 STENCILS
A. Stencils for Piping:
1. Manufacturers: Subject to compliance with requirements, provide products by the following available manufacturers offering products that are comparable to but not limited to the following:
a. Brimar Industries, Inc.
b. Carlton Industries, LP.
c. Champion America.
d. Craftmark.
e. Kolbi Pipe Marker Co.
f. Marking Services Inc.
2. Lettering Size:
a. For pipe sizes 4 inches and larger: At least 2 inches (51 mm) in height and visible from at least two sides when viewed from the floor.
b. For pipe sizes less than 4 inches: At least ¾ inch (19 mm) and visible from the floor.
3. Stencil Material: Aluminum.
4. Stencil Paint: White, exterior, gloss, alkyd enamel or acrylic enamel. Paint may be in pressurized spray-can form.
5. Identification Paint: White, exterior, alkyd enamel or acrylic enamel. Paint may be in pressurized spray-can form.
2.5 VALVE TAGS
A. Manufacturers: Subject to compliance with requirements, provide products by the following available manufacturers offering products that are comparable to but not limited to the following:
1. ActionCraft Products, Inc.
2. Brady Corporation.
3. Brimar Industries, Inc.
4. Carlton Industries, LP.
5. Champion America.
6. Craftmark.
7. Emedco, Inc.
8. Kolbi Pipe Marker Co.
9. LEM Products Inc.
10. Marking Services Inc.
11. Seton Identification Products.
http://www.specagent.com/LookUp/?uid=123456934717&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934718&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934719&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934720&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934721&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934722&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934723&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934724&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934725&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934726&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934727&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934728&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934730&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934731&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934732&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934733&mf=&src=wd
CONTRACT DOCUMENTS – January 4, 2019
IDENTIFICATION FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT 210553 - 6
B. Description: Engraved with 1/4-inch (6.4-mm) letters for piping-system abbreviation and 1/2-inch (13-mm) numbers.
1. Tag Material: Brass, 0.032 inch (0.8 mm), stainless steel, 0.025 inch (0.64 mm), aluminum, 0.032 inch (0.8 mm), or anodized aluminum, 0.032 inch (0.8 mm) thick, with predrilled holes for attachment hardware.
2. Fasteners: Brass wire-link chain, beaded chain, or S-hook.
3. Valve-Tag Color: Safety Red.
4. Letter Color: White.
C. Valve Schedules: For each piping system, on 8-1/2-by-11-inch (A4) bond paper. Tabulate valve number, piping system, system abbreviation (as shown on valve tag), location of valve (room or space), normal-operating position (open, closed, or modulating), and variations for identification. Mark valves for emergency shutoff and similar special uses.
1. Valve-tag schedule shall be included in operation and maintenance data.
2.6 WARNING TAGS
A. Manufacturers: Subject to compliance with requirements, provide products by the following available manufacturers offering products that are comparable to but not limited to the following:
1. Brady Corporation.
2. Brimar Industries, Inc.
3. Carlton Industries, LP.
4. Champion America.
5. Craftmark.
6. Emedco, Inc.
7. Kolbi Pipe Marker Co.
8. LEM Products Inc.
9. Marking Services Inc.
10. Seton Identification Products.
B. Description: Preprinted or partially preprinted, accident-prevention tags, of plasticized card stock with matte finish suitable for writing.
1. Size: 3 by 5-1/4 inches (75 by 133 mm) minimum
2. Fasteners: Brass grommet and wire or Reinforced grommet and wire or string.
3. Nomenclature: Large-size primary caption such as "DANGER," "CAUTION," or "DO
NOT OPERATE."
4. Color: Safety Yellow background with black lettering.
PART 3 - EXECUTION
3.1 PREPARATION
A. Clean piping and equipment surfaces of incompatible primers, paints, and encapsulates, as well as dirt, oil, grease, release agents, and other substances that could impair bond of identification devices.
http://www.specagent.com/LookUp/?uid=123456934753&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934754&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934755&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934756&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934757&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934758&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934759&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934760&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934761&mf=&src=wd http://www.specagent.com/LookUp/?uid=123456934762&mf=&src=wd
CONTRACT DOCUMENTS – January 4, 2019
IDENTIFICATION FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT 210553 - 7
3.2 GENERAL INSTALLATION REQUIREMENTS
A. Coordinate installation of identifying devices with completion of covering and painting of surfaces where devices are to be installed.
B. Coordinate installation of identifying devices with locations of access panels and doors.
C. Install identifying devices before installing acoustical ceilings and similar concealment.
3.3 EQUIPMENT LABEL INSTALLATION
A. Install or permanently fasten labels on each major item of mechanical equipment.
B. Locate equipment labels where accessible and visible.
3.4 PIPE LABEL INSTALLATION
A. Stenciled Pipe-Label Option: Stenciled labels may be provided instead of manufactured pipe labels, at Installer's option. Install stenciled pipe labels, complying with ASME A13.1, with painted, color-coded bands or rectangles on each piping system.
1. Identification Paint: Use for contrasting background.
2. Stencil Paint: Use for pipe marking.
B. Pipe-Label Locations: Locate pipe labels where piping is exposed or above accessible ceilings in finished spaces; machine rooms; accessible maintenance spaces such as shafts, tunnels, and plenums; and exterior exposed locations as follows:
1. Near each valve and control device.
2. Near each branch connection excluding short takeoffs. Where flow pattern is not obvious, mark each pipe at branch.
3. Near penetrations and on both sides of through walls, floors, ceilings, and inaccessible enclosures.
4. At access doors, manholes, and similar access points that permit a view of concealed piping.
5. Near major equipment items and other points of origination and termination.
6. Spaced at maximum intervals of 50 feet (15 m) along each run. Reduce intervals to
25 feet (7.6 m) in areas of congested piping and equipment.
7. On piping above removable acoustical ceilings. Omit intermediately spaced labels.
C. Directional Flow Arrows: Arrows shall be used to indicate direction of flow in pipes including pipes where flow is allowed in both directions.
3.5 VALVE-TAG INSTALLATION
A. Install tags on valves and control devices in fire-suppression piping systems. List tagged valves in a valve-tag schedule.
B. Valve-Tag Application Schedule: Tag valves according to size, shape, and with captions similar to those indicated in "Valve-Tag Size and Shape" Subparagraph below:
1. Valve-Tag Size and Shape:
CONTRACT DOCUMENTS – January 4, 2019
IDENTIFICATION FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT 210553 - 8
a. Wet-Pipe Sprinkler System: 1-1/2 inches (38 mm) or 2 inches (50 mm), round or square.
3.6 WARNING-TAG INSTALLATION
A. Write required message on, and attach warning tags to, equipment and other items where required.
WET-PIPE SPRINKLER SYSTEMS 211313 - 1
v.03/11
SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS
1.1 SUMMARY
A. This section includes the design and provision of the wet-pipe sprinkler fire suppression system for the project.
B. Section Includes:
1. Pipes, fittings, and specialties.
2. Fire-protection valves.
3. Fire-department connections.
4. Sprinklers.
5. Alarm devices.
6. Pressure gages.
1.2 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.3 DEFINITIONS
A. Standard-Pressure Sprinkler Piping: Wet-pipe sprinkler system piping designed to operate at working pressure of 175 psig maximum.
1.4 PERFORMANCE REQUIREMENTS
A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure.
B. Delegated Design: Design sprinkler system(s), including comprehensive engineering analysis by a qualified professional engineer, using performance requirements and design criteria indicated.
1. Available fire-hydrant flow test records indicate the following conditions:
a. Date:
b. Time:
c. Performed by:
d. Location of Residual Fire Hydrant R:
e. Location of Flow Fire Hydrant F:
f. Static Pressure at Residual Fire Hydrant R:
g. Measured Flow at Flow Fire Hydrant F:
h. Residual Pressure at Residual Fire Hydrant R:
C. Sprinkler system design shall be approved by authorities having jurisdiction.
1. Margin of Safety for Available Water Flow and Pressure: 10 percent or 5 psi, whichever is higher, including losses through water-service piping, valves, and backflow preventers.
2. Sprinkler Occupancy Hazard Classifications: Light Hazard for offices, waiting areas, exam rooms, administrative areas, etc., and Ordinary Hazard Group 1 for storage areas, mechanical and electric rooms, soiled utility spaces, and similar areas.
WET-PIPE SPRINKLER SYSTEMS 211313 - 2
1.5 SUBMITTALS
A. Product Data: For each type of product indicated. Include rated capacities, operating characteristics, electrical characteristics, and furnished specialties and accessories.
B. LEED Submittal:
1. Product Data for Credit EQ 4.1: For solvent cements and adhesive primers, including printed statement of
VOC content and chemical components.
C. Shop Drawings: For wet-pipe sprinkler systems. Include plans, elevations, sections, details, hydrant flow test results and attachments to other work.
1. Wiring Diagrams: For power, signal, and control wiring.
D. Delegated-Design Submittal: For sprinkler systems indicated to comply with performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation.
E. Qualification Data: For qualified Installer.
F. Approved Sprinkler Piping Drawings: Working plans, prepared according to NFPA 13 and UFC 3-600-01, that have been approved by authorities having jurisdiction, including hydraulic calculations if applicable. Contractor shall perform hydraulic calculations in accordance with UFC 3-600-01.
G. Fire-hydrant flow test report.
H. Field Test Reports and Certificates: Indicate and interpret test results for compliance with performance requirements and as described in NFPA 13. Include "Contractor's Material and Test Certificate for Aboveground Piping."
I. Field quality-control reports.
J. Operation and Maintenance Data: For sprinkler…