This document outlines the requirements for a sound masking system installation project. The project involves installing sound masking speakers, amplifiers, a noise generator, wiring and other components in a medical facility to provide acoustic privacy. Key specifications include the components must be non-proprietary, utilize current operating systems, and integrate with the facility's paging and notification systems. The system must meet standards for open office acoustics and be compatible with existing IT infrastructure. Installers must have 5 years experience and be able to train facility staff. Quotes are due by January 8, 2020 with the project taking place at Eglin Air Force Base. The solicitation is set aside for Service-Disabled Veteran-Owned Small Businesses.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FOR OFFICIAL USE ONLY
(October 2018)
DHA PERFORMANCE STANDARDS
FOR
SECTION 27 51 19
SOUND MASKING SYSTEMS
10/18
TABLE OF CONTENTS
GENERAL
1.1 REFERENCES
2.1 DESCRIPTION & MATERIALS
3.1 SUBMITTALS
3.2 PERFORMANCE VERIFICATION AND ACCEPTANCE TESTING
3.2.1 Qualifications of Installers and Inspectors
3.2.2 Inspections and Tests to be Performed
3.3 WARRANTY
3.4 OPERATIONS AND MAINTENANCE (O & M)
GENERAL
This Performance Specification (PS) specifies the installation and quality of sound masking systems.
Note: A typical sound masking system consists of a network of speakers and amplifiers connected to a noise generator to raise the ambient noise level of a space to minimize audible distraction and provide privacy by masking intrusive speech. The noise generator typically provides pink noise, centered on the frequency of human speech, making indirect speech unintelligible. Real property, including raceway, cable tray, junction boxes, etc. are addressed in their respective UFGS sections and not included in this specification.
1.1 REFERENCES
Contractor must comply with the following:
1.1.1 United Facilities Criteria (UFC)
A. UFC 1-200-01 General Building Requirements B. UFC 3-501-01 Electrical Engineering C. UFC 4-010-06 Cybersecurity
1.1.2 Military Standard
A. Reserved for future
1.1.3 Military Health Services Standards
A. Defense Health Agency Standards
1. Building Control Systems Categorization Memorandum
2. Cyber Security Controls for Physically Isolated Systems
3. Cyber Security Controls for Medical Community of Interest (MEDCOI)
B. Department of Defense Standards
1. Department of Defense Instruction (DoDI) Number 8500.01
2. Department of Defense Instruction (DoDI) Number 8510.01
1.1.4 Other Standards
A. ASTM E1374-06 – Standard Guide for Open Office Acoustics and Applicable ASTM Standards
B. ASTM E1573-09 – Standard Test Method for Evaluating Masking Sound in Open Office Using A-Weighted and One-Third Octave Band Sound Pressure Levels C. ASTM E1130-08 – Standard Test Method for Objective Measurement of Speech Privacy in Open Offices Using Articulation Index D. ASTM E1041-85 – Standard Guide for Measurement of Masking Sound in Open Offices.
E. ANSI S1.4 American National Standard Specification for Sound Level Meters F. ANSI S1.6 American National Standard Specification for Preferred Frequencies and Band Numbers for Acoustical Measurements G. ANSI S1.11 American National Standard Specification for Octave-Band and Fractional-Octave-Band Analog and Digital Filters H. ANSI 709.1 / ISO / IEC standards for open platform.
I. UL 2043 Approved for use in air handling spaces J. [UL 2572 Standard for Mass Notification Systems] K. UL 60065 Approved for use as Audio/Video Equipment L. UL 1480 Approved for use as speakers for use in fire alarm, emergency, and commercial and professional use M. NFPA 101 Life Safety Code N. NFPA 72 Fire Alarm and Signaling Code O. ADA American Disabilities Act
2.1 DESCRIPTION & MATERIALS
2.1.1 General
A. Materials used must be suitable for the environment in which they are installed and UL listed.
B. Sound masking system speakers and amplifiers must be non-proprietary.
C. [Utilize the most current approved version of Windows operating systems at the time of initial testing or as specifically approved for workstations and servers. Entire network must be supervised, monitored, patched, maintained, and life-cycled. Coordinate with Government to establish a plan of action for approval and dissemination of required Information Assurance Vulnerability Alert (IAVA) patches as well as software and security updates. Locate server in computer room (room code CMP01).] D. Disable any unused communications ports and protocols such that they can be reactivated by the government at a later date. Where Bluetooth functions are available, disable the Bluetooth functionality on delivery. The Bluetooth functionality must be able to be turned on after installation and review with the Cybersecurity Representative.
E. Directional Effect: People in covered spaces under calibration conditions cannot determine source of Masking sound.
F. Provide surge protection for sound masking system components. Integral surge protection devices listed in UL 1449.
G. Provide cabling and other appurtenances in accordance with the manufacturer’s recommendations.
H. Coordinate with Medical Treatment Facility (MTF) IT department for currently installed servers, switches, PCs and other similar hardware components. Where no manufacturer’s requirements conflict, provide hardware components to be fully compatible with those currently installed in the MTF.
I. System and other appurtenances must not have an anticipated end of system support in the next [18] [___] months. Systems being phased out are not acceptable.
J. [Integrate with paging system to provide sound masking and paging over the same speakers.] K. Sound masking system must mute during fire alarm and mass notification system signaling. [Provide UL 2572 listed system to interface with the fire alarm and mass notification systems.]
2.1.2 Noise Generator
A. Octave bands from 100Hz to 8000Hz.
B. Spectrum adjustments must meet acoustical preferred curve.
C. Filters for one-third Octave Bands: Adjustable from 10 dB of boost to 10 dB of cut at each center frequency.
D. Output octave bands must be from 30 to 4000 Hz.
E. Auxiliary Inputs: Able to accept two, high-level, auxiliary signals such as music and telephone paging as well as general paging.
F. Mounting: Mount with common rack with paging and music system headend equipment.
G. Central volume control and EQ control for zones and units for paging and audio.
2.1.3 Wire
A. UTP cable complying with manufacturer’s requirements; listed and labeled for environmental air plenums where cable is indicated in plenum spaces and is not indicated to be a in a raceway.
B. Minimum 18 gauge, stranded, non-shielded, and UL listed.
2.1.4 Masking Speaker Assemblies
A. Power Rating: [10] [___] Watts Root Mean Squared (RMS) B. Frequency Response: Within +/- [1] [2] [3] [___]dB from 50-15,000 Hz C. Pressure Sensitivity: SPL - at 1 Watt/m - 90 dB D. Assemblies installed in air-handling spaces must comply with NFPA 70 requirements for rate of heat-release and rate of smoke-release characteristics. Tests for these requirements must be according to UL 2043.
2.1.5 Component Mounting Racks
A. Configuration: Comply with CEA-310-E. Factory fabricated units designed for interchangeable mounting and enclosure of Standard 19-inch relay rack modules.
B. Mounting Provisions: Equipped for freestanding floor mounting.
C. Cabinet: Factory-Finished steel with component mounting rails and prewired plug strips for component power connections. Full front and rear doors with continuous hinges, handles, and cylindrical keyed locks.
2.1.6 Central Volume Control
A. The Central Volume Control unit must operate as a central volume control from which universal volume adjustments can be made remotely for a minimum of [150][___] total speakers.
2.1.7 Remote Volume Control
A. Volume adjustment: A rotating switch accompanied by a wall mountable plate and is adjusted by rotating the dial from 0 to 10.
B. Each remote central volume remote control unit is solid state and consists of a CMOS/MSI digital random sequence noise generator, electronic amplifier, and filter for active spectrum shaping and is equipped with a 10-step volume control, an additional continuous volume control, and the central volume remote adjustment control (as previously described above). Range of sound level: 41-86 dBA. Additionally contained is a continuous and completely separate volume control for paging/music.
3.1 SUBMITTALS
3.1.1 Submittals required for government review
A. Submittal requirements are outlined in [Division 01] [PWS SOW] [___].
B. [Submit the following for government review in addition to the submittal requirements in the [PWS SOW] [Division 1]
C. [Product Literature that includes manufacturers’ installation instructions, sizing, options, utility requirements and accessories being provided.] D. [Warranty information.]
E. [Contact Information for Repair Technician or Emergency Repair Company] F. [Qualifications of installers and inspectors.] G. [Specification Compliance Document] H.
3.2 PERFORMANCE VERIFICATION AND ACCEPTANCE TESTING
Install sound masking systems in accordance with manufacturer’s instructions. Demonstrate system is in operating condition in accordance with manufacturers’ specifications, and meets performance requirements stated in referenced criteria. Perform final verification and acceptance testing after facility construction is complete. If portions of the system were tested before final construction completion, retest system communications and functionality after completion of facility construction.
3.2.1 Qualifications of Company, Lead Installers, and Inspectors A. Company specializing in installing the products specified in this section with minimum 5 years of documented experience.
B. Provide written Specification Compliance Document that the system and products submitted meet or exceed all requirements stated in this specification and referenced criteria as installed or that declares any omissions to the specification and referenced criteria compliance.
3.2.2 Inspections and Tests to be Performed
A. Demonstrate functionality of interfaces to other systems and networks required.
B. Engage a factory authorized service representative to train Owner’s maintenance personnel to adjust, operate, and maintain equipment and schedules.
C. Demonstrate implementation of cyber-security controls in accordance with DoDI 8510.
3.3 WARRANTY
3.3.1 Minimum Requirements
A. Warranty requirements are outlined in [Division 01] [PWS SOW] [___].
3.4 OPERATIONS AND MAINTENANCE (O & M)
3.4.1 Provide the following to the final owner
A. Provide O & M data for all FFE-LVS as outlined in [Division 01] [PWS SOW] [___].
B. Provide testing, certification and documentation 30 days prior to training sessions.
C. Train designated staff in the operation and maintenance of the provided system. Provide two training sessions for system users and two training sessions for maintenance personnel scheduled to accommodate shift work. [Eleven months after the system is installed, provide a refresher course for each group of trainees.] Provide video of the training with the O & M data.
--End of Section--
| 1.1 REFERENCES |
| 1.1.1 United Facilities Criteria (UFC) |
| A. UFC 1-200-01 General Building Requirements |
| B. UFC 3-501-01 Electrical Engineering |
| C. UFC 4-010-06 Cybersecurity |
| 1.1.2 Military Standard |
| A. Reserved for future |
| 1.1.3 Military Health Services Standards |
| A. Defense Health Agency Standards |
| 1. Building Control Systems Categorization Memorandum |
| 2. Cyber Security Controls for Physically Isolated Systems |
| 3. Cyber Security Controls for Medical Community of Interest (MEDCOI) |
| B. Department of Defense Standards |
| 1. Department of Defense Instruction (DoDI) Number 8500.01 |
| 2. Department of Defense Instruction (DoDI) Number 8510.01 |
| 1.1.4 Other Standards |
| A. ASTM E1374-06 – Standard Guide for Open Office Acoustics and Applicable ASTM Standards |
| B. ASTM E1573-09 – Standard Test Method for Evaluating Masking Sound in Open Office Using A-Weighted and One-Third Octave Band Sound Pressure Levels |
| C. ASTM E1130-08 – Standard Test Method for Objective Measurement of Speech Privacy in Open Offices Using Articulation Index |
| D. ASTM E1041-85 – Standard Guide for Measurement of Masking Sound in Open Offices. |
| E. ANSI S1.4 American National Standard Specification for Sound Level Meters |
| F. ANSI S1.6 American National Standard Specification for Preferred Frequencies and Band Numbers for Acoustical Measurements |
| G. ANSI S1.11 American National Standard Specification for Octave-Band and Fractional-Octave-Band Analog and Digital Filters |
| H. ANSI 709.1 / ISO / IEC standards for open platform. |
| I. UL 2043 Approved for use in air handling spaces |
| J. [UL 2572 Standard for Mass Notification Systems] |
| K. UL 60065 Approved for use as Audio/Video Equipment |
| L. UL 1480 Approved for use as speakers for use in fire alarm, emergency, and commercial and professional use |
| M. NFPA 101 Life Safety Code |
| N. NFPA 72 Fire Alarm and Signaling Code |
| O. ADA American Disabilities Act |
| PART 2 - |
| 2.1 DESCRIPTION & MATERIALS |
| 2.1.1 General |
| A. Materials used must be suitable for the environment in which they are installed and UL listed. |
| B. Sound masking system speakers and amplifiers must be non-proprietary. |
| C. [Utilize the most current approved version of Windows operating systems at the time of initial testing or as specifically approved for workstations and servers. Entire network must be supervised, monitored, patched, maintained, and life-cycled. C... |
| D. Disable any unused communications ports and protocols such that they can be reactivated by the government at a later date. Where Bluetooth functions are available, disable the Bluetooth functionality on delivery. The Bluetooth functionality must ... |
| E. Directional Effect: People in covered spaces under calibration conditions cannot determine source of Masking sound. |
| F. Provide surge protection for sound masking system components. Integral surge protection devices listed in UL 1449. |
| G. Provide cabling and other appurtenances in accordance with the manufacturer’s recommendations. |
| H. Coordinate with Medical Treatment Facility (MTF) IT department for currently installed servers, switches, PCs and other similar hardware components. Where no manufacturer’s requirements conflict, provide hardware components to be fully compatible ... |
| I. System and other appurtenances must not have an anticipated end of system support in the next [18] [___] months. Systems being phased out are not acceptable. |
| J. [Integrate with paging system to provide sound masking and paging over the same speakers.] |
| K. Sound masking system must mute during fire alarm and mass notification system signaling. [Provide UL 2572 listed system to interface with the fire alarm and mass notification systems.] |
| 2.1.2 Noise Generator |
| A. Octave bands from 100Hz to 8000Hz. |
| B. Spectrum adjustments must meet acoustical preferred curve. |
| C. Filters for one-third Octave Bands: Adjustable from 10 dB of boost to 10 dB of cut at each center frequency. |
| D. Output octave bands must be from 30 to 4000 Hz. |
| E. Auxiliary Inputs: Able to accept two, high-level, auxiliary signals such as music and telephone paging as well as general paging. |
| F. Mounting: Mount with common rack with paging and music system headend equipment. |
| G. Central volume control and EQ control for zones and units for paging and audio. |
| 2.1.3 Wire |
| A. UTP cable complying with manufacturer’s requirements; listed and labeled for environmental air plenums where cable is indicated in plenum spaces and is not indicated to be a in a raceway. |
| B. Minimum 18 gauge, stranded, non-shielded, and UL listed. |
| 2.1.4 Masking Speaker Assemblies |
| A. Power Rating: [10] [___] Watts Root Mean Squared (RMS) |
| B. Frequency Response: Within +/- [1] [2] [3] [___]dB from 50-15,000 Hz |
| C. Pressure Sensitivity: SPL - at 1 Watt/m - 90 dB |
| D. Assemblies installed in air-handling spaces must comply with NFPA 70 requirements for rate of heat-release and rate of smoke-release characteristics. Tests for these requirements must be according to UL 2043. |
| 2.1.5 Component Mounting Racks |
| A. Configuration: Comply with CEA-310-E. Factory fabricated units designed for interchangeable mounting and enclosure of Standard 19-inch relay rack modules. |
| B. Mounting Provisions: Equipped for freestanding floor mounting. |
| C. Cabinet: Factory-Finished steel with component mounting rails and prewired plug strips for component power connections. Full front and rear doors with continuous hinges, handles, and cylindrical keyed locks. |
| 2.1.6 Central Volume Control |
| A. The Central Volume Control unit must operate as a central volume control from which universal volume adjustments can be made remotely for a minimum of [150][___] total speakers. |
| 2.1.7 Remote Volume Control |
| A. Volume adjustment: A rotating switch accompanied by a wall mountable plate and is adjusted by rotating the dial from 0 to 10. |
| B. Each remote central volume remote control unit is solid state and consists of a CMOS/MSI digital random sequence noise generator, electronic amplifier, and filter for active spectrum shaping and is equipped with a 10-step volume control, an additio... |
| PART 3 - |
| 3.1 Submittals |
| 3.1.1 Submittals required for government review |
| A. Submittal requirements are outlined in [Division 01] [PWS SOW] [___]. |
| B. [Submit the following for government review in addition to the submittal requirements in the [PWS SOW] [Division 1] [___]. |
| C. [Product Literature that includes manufacturers’ installation instructions, sizing, options, utility requirements and accessories being provided.] |
| D. [Warranty information.] |
| E. [Contact Information for Repair Technician or Emergency Repair Company] |
| F. [Qualifications of installers and inspectors.] |
| G. [Specification Compliance Document] |
| H. |
| 3.2 PERFORMANCE VERIFICATION AND ACCEPTANCE TESTING |
| 3.2.1 Qualifications of Company, Lead Installers, and Inspectors |
| A. Company specializing in installing the products specified in this section with minimum 5 years of documented experience. |
| B. Provide written Specification Compliance Document that the system and products submitted meet or exceed all requirements stated in this specification and referenced criteria as installed or that declares any omissions to the specification and refer... |
| 3.2.2 Inspections and Tests to be Performed |
| A. Demonstrate functionality of interfaces to other systems and networks required. |
| B. Engage a factory authorized service representative to train Owner’s maintenance personnel to adjust, operate, and maintain equipment and schedules. |
| C. Demonstrate implementation of cyber-security controls in accordance with DoDI 8510. |
| 3.3 WARRANTY |
| 3.3.1 Minimum Requirements |
| 3.4 OPERATIONS AND MAINTENANCE (O & M) |
| 3.4.1 Provide the following to the final owner |