This is a combined synopsis and solicitation for an initial outfitting project at the Eglin National Intrepreneurship Center of Excellence (NICoE). The solicitation requests quotes for construction and installation services including fire protection and alarm systems. Quotes are due by January 8, 2020. A mandatory site visit is scheduled for December 4, 2019 at Eglin Air Force Base. The opportunity is set aside for Service-Disabled Veteran-Owned Small Businesses with a NAICS code of 337127 and size standard of 500 employees. The solicitation will use simplified acquisition procedures under FAR Part 13 in conjunction with commercial item procedures under FAR Part 12. More information on base access for the site visit must be provided by interested contractors by November 29, 2019. The solicitation is issued by the Department of the Army Corps of Engineers Engineering District Little Rock.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. SPRINKLER SYSTEM DESIGN CRITERIA:
a. LIGHT HAZARD OCCUPANCY - PATIENT ROOMS, ADMINISTRATIVE AREAS, COMPUTER ROOMS, ETC.
b. ORDINARY HAZARD OCCUPANCY - HOUSEKEEPING, CLEAN/SOILED UTILITIES, LOCKER ROOMS, STORAGE AREAS, MECHANICAL AND ELECTRIC ROOMS AND SIMILAR AREAS WHERE STOCKPILES OF COMBUSTIBLE
MATERIALS DO NOT EXCEED 8'-0".
c. MINIMUM SCHEDULE 40 STEEL PIPING SHALL BE USED.
2. SYSTEM PROTECTION AREA LIMITATIONS:
a. THE MAXIMUM FLOOR AREA ON ANY ONE FLOOR TO BE PROTECTED BY SPRINKLERS SUPPLIED BY ANY ONE SPRINKLER RISER OR COMBINED SYSTEM SHALL BE 52,000 SQ FT FOR LIGHT AND ORDINARY HAZARD.
3. SPRINKLER DESIGN DENSITIES/DEMAND CRITERIA:
a. LIGHT HAZARD - 0.10 GPM PER SQ FT OVER THE HYDRAULICLLY MOST REMOTE 2500 SQ FT.
b. ORDINARY HAZARD GROUP 1 - 0.2 GPM PER SQ FT OVER THE HYDRAULICLLY MOST REMOTE 2500 SQ FT.
c. DESIGN AREA REDUCTIONS ARE NOT PERMITTED.
d. HYDRAULIC CALCULATIONS SHALL INCLUDE A MINIMUM PRESSURE DROP OF 12 PSI ACROSS THE BACKFLOW PREVENTER ASSEMBLY.
e. HOSE STREAM ALLOWANCE SHALL BE 250 GPM FOR LIGHT AND ORDINARY HAZARD.
f. SPRINKLER K-FACTOR SHALL BE MINIMUM 5.6 FOR LIGHT HAZARD AND 8.0 FOR ORDINARY HAZARD.
g. NO DESIGN AREA REDUCTION ASSOCIATED WITH QUICK RESPONSE SPRINKLERS IS PERMITTED.
DESIGN PARAMETERS
TS
WF
NSFIRE PROTECTION PIPING
FIRE HOSE VALVE
FIRE HOSE VALVE IN CABINET
THROUGH THE WALL, FIRE DEPARTMENT CONNECTION
FREE STANDING, FIRE DEPARTMENT CONNECTION
(SIAMESE)
FIRE PUMP TEST HEADER
VALVE SUPERVISORY SWITCH, TAMPER
ALARM CHECK VALVE
DRY PIPE VALVE
DELUGE VALVE
PRE-ACTION VALVE
FLOW SWITCH
(SIAMESE)
BACKFLOW PREVENTER
OS&Y VALVE
CHECK VALVE
INSPECTOR'S TEST CONNECTION
POST INDICATING VALVE
POINT OF DISCONNECT
POINT OF CONNECTION
ELBOW - TURNED DOWN
CAP OR PLUG
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AMBIENT
AMERICAN NATIONAL STANDARDS
APPROXIMATE
BACKFLOW PREVENTER (TYPE AS
INDICATED)
BOTTOM OF PIPE
BRITISH THERMAL UNIT PER HOUR
BALL VALVE
CUBIC FEET PER MINUTE
CAST IRON
COMPRESSOR
CONDENSATE
CONTINUATION
CHECK VALVE
DOWN
DRAWING
EACH
EFFICIENCY
ELEVATION
EXPANSION TANK
ENTERING WATER TEMPERATURE
EXPANSION
EXTERNAL
EXISTING MATERIAL OR EQUIPMENT
NIC NOT IN CONTRACT
NO. NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OD OUTSIDE DIAMETER
ACCESS PANEL
AMERICANS WITH DISABILITIES ACT
ABBREVIATION
BRAKE HORSEPOWER
CAPACITY
DIAMETER
EQUIVALENT
N.C. NORMALLY CLOSED
NA NOT APPLICABLE
N.O. NORMALLY OPEN
DOMESTIC
OS&Y OUTSIDE SCREW AND YOKE
AFF
AFG
AMB
ANSI
APPROX
BFP
BOP
BTU/H
BV
CFM
CI
COMP
COND
CONT
CV
DN
DWG
EA
EFF
EL
ET
EWT
EXP
EXT
(E)
AP
ADA
ABBR
BHP
CAP.
DIA
EQ
DOM
LIGHT HAZARD SPRINKLER DENSITY CLASSIFICATION
ORDINARY HAZARD 1 SPRINKLER DENSITY CLASSIFICATION
EXISTING ROOM/AREA SPRINKLER SYSTEM TO
REMAIN. NO NEW WORK.
FIRE
FAN COIL UNIT
FLOOR
FEET PER MINUTE
FEET OR FOOT
GALLON
GALLONS PER MINUTE
GATE VALVE
HEIGHT
HORSE POWER
HIGH PRESSURE STEAM
HOUR
DEGREES IN FAHRENHEIT
FEET PER SECOND
GALLONS PER HOUR
GALLONS PER DAY
MERCURY
FIRE HOSE VALVE
FLOW SWITCH
HYDRAULIC GRADE LINE
F
FCU
FL
FPM
FT
GAL
GPM
GV
HGT
HP
HPS
HR
%%U %%U°F
FPS
GPH
GPD
HG
FHV
FS
HGL
INSIDE DIAMETER
INVERT ELEVATION
IN. INCHES
KW KILOWATTS
LGT LENGTH
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH 1000 BTU/HR
MECH MECHANICAL
MIN MINIMUM
MISC MISCELLANEOUS
MTG MOUNTING
IE
ID
WHERE ANY CONFLICT AND/OR DISCREPANCY BETWEEN THESE GENERAL NOTES AND ANY OTHER INFORMATION CONTAINED IN THE CONTRACT DOCUMENTS EXISTS, THE MORE STRINGENT REQUIREMENT SHALL PREVAIL AND BE A REQUIREMENT OF THE WORK. THAT NOTWITHSTANDING, ANY SUCH CONFLICT AND/OR DISCREPANCY SHALL PROMPTLY BE BROUGHT TO THE ATTENTION OF THE OWNER, ARCHITECT AND ENGINEER.
THE TERM “PROVIDE” SHALL MEAN FURNISH, INSTALL AND CONNECT EQUIPMENT/DEVICE FOR A COMPLETE AND OPERATIONAL SYSTEM.
THE TERM “REMOVE” SHALL MEAN DISCONNECT AND CLEAR EQUIPMENT/DEVICE FROM SITE, AS WELL AS MAINTAINING UPSTREAM AND DOWNSTREAM EQUIPMENT/DEVICES AS REQUIRED.
THE CONTRACT DOCUMENTS ARE DIAGRAMMATIC AND INTENDED TO SHOW DESIGN INTENT ONLY.
PROVIDE A COMPLETE HYDRAULICALLY- CALCULATED AUTOMATIC SPRINKLER SYSTEM THROUGHOUT THE BUILDING, INCLUDING BUT NOT LIMITED TO WATERFLOW ALARM SWITCHES, VALVE SUPERVISORY SWITCHES, CHECK VALVES, CONTROL VALVES, PIPING, HANGERS, SPRINKLERS, ALL ASSOCIATED EQUIPMENT, WIRING AND APPURTENANCES, NORMALLY AND CUSTOMARILY REQUIRED, WHETHER INDICATED OR INHERENTLY NECESSARY DUE
TO THE NATURE OF THE WORK, FOR A COMPLETE AND OPERATIONAL SYSTEM.
SPRINKLER PIPING INDICATED ON THE CONTRACT DOCUMENTS IS SHOWN FOR DESIGN INTENT ONLY AND IS SUBJECT TO THE PRECEDING NOTE. RUN ALL PIPING STRAIGHT AND TIGHT TO THE FACE OF STRUCTURAL MEMBERS AND WALLS, PARALLEL AND AT RIGHT ANGLES TO STRUCTURAL STEEL OR CONCRETE ELEMENTS.
ALL WORK SHALL CONFORM TO THE APPLICABLE PROVISIONS OF THE UNITED FACILITIES CRITERIA, THE EGLIN AIR FORCE BASE ENGINEERING DESIGN MANUAL (APPENDIX 2, EGLIN SPECIFIC FIRE SUPPRESSION REQUIREMENTS), AMENDED CODE REQUIREMENTS OF THE LOCAL AUTHORITY HAVING JURISDICTION, UFC 3-600-01, AND THE REFERENCED EDITIONS OF NFPA 13, 14, 20, 70 AND 72 . WHERE THERE ARE ANY CONFLICTS IN
REQUIREMENTS, THE MOST STRINGENT REQUIREMENTS SHALL BE APPLIED.
VERIFY ALL DIMENSIONS AND CONDITIONS AT JOB SITE PRIOR TO PROCEEDING WITH THE WORK .
COORDINATE ALL WORK AND AVOID ALL CONFLICTS WITH LIGHTING FIXTURES, DIFFUSERS, GRILLS, DUCTS, STRUCTURAL MEMBERS, PIPES AND OTHER OBSTRUCTIONS .
NO STRUCTURAL MEMBERS SHALL BE CUT, DRILLED OR BURNED UNLESS PREVIOUSLY APPROVED BY OWNER. FURTHER, ANY APPROVED CUTTING OR PATCHING OF ANY STRUCTURAL WORK SHALL NOT RESULT IN A REDUCTION OF LOAD-CARRYING AND/OR LOAD-DEFLECTION RATIO. PRIOR TO SUCH WORK, OBTAIN APPROVAL FROM THE OWNER.
ALL WALL AND FLOOR PENETRATIONS SHALL BE CORE-DRILLED. PROVIDE PIPE SLEEVES FOR WALL AND FLOOR PENETRATIONS AS INDICATED IN THE SPECIFICATIONS. ALL PENETRATIONS IN WALLS, CEILINGS AND FLOORS SHALL BE SEALED TO THE FULL THICKNESS OF THE PENETRATION WITH APPROVED FIRESTOPPING MATERIAL OF EQUAL OR GREATER FIRE RESISTANCE. ALL (CORRIDOR, ROOM SEPARATION, AND SLAB-TO-SLAB WALLS SHALL BE CONSIDERED TO BE OF 1-HOUR FIRE RESISTIVE RATED CONSTRUCTION. STAIRWAYS, SHAFT ENCLOSURES, AND FLOOR SLABS SHALL BE CONSIDERED 2-HOUR FIRE RESISTIVE RATED CONSTRUCTION .
ALL DAMAGE TO WALLS, CEILINGS, FLOORS, AND STRUCTURAL MEMBERS FROM THE WORK SHALL BE PATCHED, REPAIRED AND PAINTED WITH NEW MATERIALS TO MATCH ADJACENT WORK, WHETHER SPECIFICALLY NOTED
OR NOT .
AS A MINIMUM, MAINTAIN 6 FT 8 INCH HEAD ROOM CLEARANCE BETWEEN BOTTOM OF SPRINKLER PIPE AND ADJACENT FLOOR, INCLUDING STAIRWELLS .
CONTRACTOR TO PROVIDE CONCEALED PENDENT SPRINKLERS THROUGHOUT THE BUILDING EXCEPT IN SPACES WITHOUT CEILINGS WHERE UPRIGHT BRASS SPRINKLERS SHALL BE PROVIDED. CONTRACTOR TO PROVIDE
BLACK ESCUTCHEON AND BLACK COVER PLATES IN MAIN CORRIDOR/LOBBY IN WOOD CEILINGS.
LOCATE SPRINKLERS ON CENTER OF ACOUSTICAL CEILING TILE.
CONTRACTOR TO PROTECT THE SPRINKLER SYSTEM IN ACCORDANCE WITH SEISMIC CRITERIA FOUND IN ASCE 7.1 AND NFPA 13.
DO NOT ROUTE SPRINKLER PIPING DIRECTLY OVER ELECTRICAL PANELS OR EQUIPMENT. DO NOT ROUTE SPRINKLER PIPING THROUGH ELECTRICAL ROOMS; BRANCH LINES SHOULD TERMINATE IN ELECTRICAL ROOMS.
FIRE SUPPRESSION SYSTEMS INSPECTOR'S TEST VALVES SHALL NOT BE MOUNTED ANY HIGHER THAN 72 INCHES ABOVE FINISHED FLOOR.
ALL CHECK VALVES OVER 2 INCHES MUST HAVE A COVER PLATE FOR MAINTENANCE WITHOUT REMOVING THE CHECK VALVE ASSEMBLY FROM THE PIPING SYSTEM.
WHEN PIPE THREAD SEALANT IS USED, USE A NON-PETROLEUM BASED PRODUCT. OIL RESIDUALS HAVE BEEN FOUND ON HEADS FROM THE OIL SEPARATING FROMT THE BASE OF THE THREAD SEALANT.
THE INSPECTOR'S TEST VALVE SHALL BE LOCATED IN THE MOST HYDRAULICALLY REMOTE PORTION OF THE BUILDING.
A
B
C
D
E
F
G
H
I
K
L
M
N
P
PRESS. PRESSURE
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH - GAUGE
REF REFERENCE
RL RELOCATED MATERIAL OR EQUIPMENT
RPM REVOLUTIONS PER MINUTE
SCFM STANDARD CUBIC FEET PER MINUTE
SE SEWAGE EJECTOR
SF SQUARE FEET
SG SPECIFIC GRAVITY
SS STAINLESS STEEL
STM STEAM
TEMP TEMPERATURE
TYP TYPICAL
VEL VELOCITY
W/ WITH
WG WATER GAUGE
W/0 WITHOUT
PH PHASE (ELECTRICAL)
PPM PARTS PER MILLION
SPEC SPECIFICATION
SQ. FT. SQUARE FEET
STD STANDARD
UON UNLESS OTHERWISE NOTED
V VOLT
YD YARD
SPRINKLER/ STANDPIPE
SPRINKLERSPR
SPR/STP
TAMPER SWITCHTS
O
R
S
T
U
V
W
Y
REFERENCE SYMBOLS
FIRE PROTECTION GENERAL NOTESFIRE PROTECTION FLOOR PLAN SYMBOLSFIRE PROTECTION ABBREVIATIONS
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
O.
P.
Q.
R.
S.
T.
U.
RISER DESIGNATION (TYPE AS INDICATED)
SECTION NUMBER
DETAIL NUMBER
DRAWING NUMBER WHERE DRAWN
DRAWING NUMBER WHERE DRAWN
E1-1.0
E1-1.0
KEY NOTE 1 DEMO KEY NOTE
PRESSURE GAUGE
SECTION VIEWS
KEYED NOTES
FLOW TEST AND SITE INFORMATION
ROOF
EL +14' - 0"
T.O. BRICK
EL +16' - 0"
ROOF PLAN
14'-0"
FP206FP206
ROOF
14' - 0"
H.P. ROOF DECK - WEST
18' - 0"
T.O. CURTAIN WALL
18' - 8"
T.O. BRICK
16' - 0"
AA.7 A.2A.9 0.9A
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
Pl ot
D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
As indicated
1/ 4/
2:
:2
PM FIRE PROTECTION
ABBREVIATIONS AND
SYMBOLS
FP0.1
10822.000
SCALE: 3/16" = 1'-0"
CENTRAL PARK SPRINKLER SECTION
FP206 PROVIDE INTERMEDIATE TEMPERATURE-RATED HORIZONTAL SIDEWALL SPRINKLERS TO PROTECT SKYLIGHT. EXACT LOCATION OF SIDEWALL SPRINKLER SHALL BE COORDINATED WITH
ARCHITECTURAL PLANS.
SCHEMATIC DESIGN 8.17.2018
DESIGN DEVELOPMENT 11.08.2018
CONTRACT DOCUMENTS 01.04.2019
FP0.1
OH-1
OH-1
OH-1
OH-1
OH-1
OH-1
FP201
FP202
FP204
FP206FP206 FP207
TLT/ SHR
218.2
CHANGING / LOCKER (M)
CHANGING / LOCKER (W)
VESTIBULE
MECHANICAL
ELEC
SOIL UTIL
TREATMENT IPMC
DAYROOM
COMM
SOIL UTIL
NEUROLOGIST
PUBLIC WAITING
C101
WORKSTATION PT
201PT GYM
CORRIDOR
C300
CORR
C200
TLT/ SHR
218.1
CORR
C302
CORR
C305
CORR
C304
CORR
C306
CORR
C303
CORR
C301
CORR
C201
CORR
C202
CASE MGMT
MAT / PLATFORM
GAIT OBS LANE
EQPT STOR
PC MD
CLEAN UTIL
NEURO REHAB AREA
CORR
C102.1
FAMILY WAITING
CENTRAL PARK
MAIN CORRIDOR / LOBBY
C100
NUTRITIONIST
EYE TESTING
SPEECH THERAPY - TESTING
SPEECH THERAPY - OFFICE
EXAM
SCALE
C306.1
PAT TLT
STAFF TLT
EXAM
CLINICAL PHARMACIST
GROUP THERAPY
TEAM ROOM
PSYCH TECH
EXAM
HOUSEKEEPING
PAT TLT
PSYCH TECH
FLEX STORAGE
BRAIN LAB
ELEC
TRANS-CRANIAL MAGNETIC STIM
COMM
ACUPUNCTURE
341.1
SPIRITUAL COUNSELLING
NP PSYCH
NEUROPSYCH
ACUPUNCTURE
341.2
BH / SW PROVIDERS
BH / SW PROVIDERS
PAIN MD
PSYCHOLOGIST
CHIRO TREATMENT
CASE MGMT
STAFF LOUNGE
EXAM
EXAM
BH / SW PROVIDER
MUSIC THERAPY
CHIRO TREATMENT
RECEPTION
PTNT INTAKE CUBICLES
300.1
CASE MGMT
ART AND CLAY THERAPY
MALE TOILET
FEMALE TOILET
HOUSEKEEPING
MULTI-STATION TREATMENT RM
PT O/E
OT O/E
TRAZER / FATS
COPY
109.1
OT O/E
DAILY LIVING SKILLS
EXAM
BREAK ALCOVE
105.1
RESEARCH SHARED OFFICE
NCOIC / ADMIN
NICoE DIR.
DIR. OF OPERATIONS
AV SUPPLY
CLASSROOM
103.1
CHAPLAIN
VENDING ALCOVE
106.1
EXAM
EYE LANE
EXAM
STAFF TLT
CLASSROOM
CORR
C102
BIO NEUROFEEDBACK
GROUP THERAPY
335.1
STORAGE / KILN
338.1
CHECK-IN KIOSK
300.2
STORAGE / ALCOVE
200.1
EQPT STOR
OH-1
PT O/E
OH-1
OH-1
TLT / SHR
219.1
123456789
B
C
D
E
F
A
0.4A
A.7
A.2
6.2 5.46.97.1 6.5 4.5 3.3 2.8
0.5A
0.2A
D.7
5.2
0.3A
8.6 8.3 6.8 6.4
4.8
A.9
0.7A
0.9A
B.2
E.8
FP209
ZCA
FP205
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
PLAN
NORTH
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
Pl ot
D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
1/8" = 1'-0"
1/ 4/
2:
:3
PM GROUND FLOOR FIRE
PROTECTION PLAN
FP2.1
10822.000
SCALE: 1/8" = 1'-0"1 FIRE PROTECTION PLAN
GENERAL SHEET NOTES
A. SEE SHEET FP0.1 FIRE PROTECTION ABBREVIATIONS AND
SYMBOLS FOR ADDITIONAL INFORMATION.
B. ALL AREAS INDICATED BY DIAGONAL-DOWN HATCHING ARE TO
BE PROTECTED AS ORDINARY HAZARD GROUP 1 PER NFPA 13.
ALL OTHER AREAS ARE TO BE PROTECTED PER LIGHT HAZRD
REQUIREMENTS.
C. CONTRACTOR TO PROVIDE PENDENT SPRINKLERS, CONCEALED
WITH WHITE COVER PLATES, THROUGHOUT THE BUILDING
EXCEPT IN SPACES WITHOUT CEILINGS WHERE UPRIGHT BRASS
SPRINKLERS SHALL BE PROVIDED. CONTRACTOR TO PROVIDE
BLACK ESCUTCHEON AND BLACK COVER PLATES IN MAIN
CORRIDOR/LOBBY IN WOOD CEILINGS AS INDICATED BY
HORIZONTAL LINE HATCHING.
D. SPRINKLER CONTRACTOR TO AVOID ROUTING WET-PIPE OVER
VAVS OR ELECTRONIC EQUIPMENT/PANELS.
E. CONTRACTOR TO PROVIDE ELECTRONIC SUPERVISION OF
INDOOR FIRE BACKFLOW PREVENTER.
F. PROVIDE A BOX AND A COPY OF ALL FIRE SUPPRESSION O&M'S
NEAR RISER, MOUNTED TO A WALL.
SHEET KEYNOTES
FP201 LOCATION OF INCOMING 6-INCH FIRE
SERVICE LINE. CIVIL CONTRACTOR IS
RESPONSIBLE FOR COORDINATING ALL
PIPING LOCATED OUTSIDE OF THE
BUILDING. REFER TO CIVIL DRAWINGS
FOR EXACT LOCATION OF INCOMING
SERVICE.
FP202 PROVIDE AND INSTALL NEW 6-INCH
DOUBLE CHECK DETECTOR BACKFLOW
PREVENTER ASSEMBLY.
FP204 PROVIDE NEW THROUGH-THE-WALL
SIAMESE FIRE DEPARTMENT
CONNECTION (FDC) AND CHECK VALVE
WITH AN AUTOMATIC BALL DRIP. REFER
TO ARCHITECTURAL EXTERIOR
ELEVATION DRAWINGS FOR EXACT
LOCATION.
FP205 INSTALL ZONE CONTROL ASSEMBLY IN
THE VERTICAL RISER. ZONE CONTROL
ASSEMBLY SHALL CONSIST OF A
PRESSURE RELIEF VALVE, CHECK VALVE,
VALVE SUPERVISORY SWITCH, WATER
FLOW SWITCH, PRESSURE GAUGE, AND
INSPECTOR'S TEST AND MAIN DRAIN.
FP206 PROVIDE INTERMEDIATE
TEMPERATURE-RATED HORIZONTAL
SIDEWALL SPRINKLERS TO PROTECT
SKYLIGHT. EXACT LOCATION OF
SIDEWALL SPRINKLER SHALL BE
COORDINATED WITH ARCHITECTURAL
PLANS.
FP207 REFER TO ARCHITECTURAL REFLECTED
CEILING PLAN FOR DIRECTION ON
PLACEMENT OF SPRINKLERS IN AREA
INDICATED BY VERTICAL LINE HATCHING.
FP209 PROVIDE BLACK COVER PLATES IN
WOOD CEILINGS IN MAIN
CORRIDOR/LOBBY AS INDICATED BY
HORIZONTAL LINE HATCHING.
SCHEMATIC DESIGN 8.17.2018
DESIGN DEVELOPMENT 11.08.2018
CONTRACT DOCUMENTS 01.04.2019
| FP0-1 - FIRE PROTECTION ABBREVIATIONS AND SYMBOLS |
| Sheets |
| FA0.1 - FIRE ALARM ABBREVIATIONS AND SYMBOLS |
| FA2.1 - GROUND FLOOR FIRE ALARM SYSTEMS PLAN |
| FP0.1 - FIRE PROTECTION ABBREVIATIONS AND SYMBOLS |
| FP2.1 - GROUND FLOOR FIRE PROTECTION PLAN |
| FP2-1 - GROUND FLOOR FIRE PROTECTION PLAN |
| Sheets |
| FA0.1 - FIRE ALARM ABBREVIATIONS AND SYMBOLS |
| FA2.1 - GROUND FLOOR FIRE ALARM SYSTEMS PLAN |
| FP0.1 - FIRE PROTECTION ABBREVIATIONS AND SYMBOLS |
| FP2.1 - GROUND FLOOR FIRE PROTECTION PLAN |
File details come from the government source that posted it. Updated .