Attachment 4 - Drawings 06 Mechanical.pdf

PDF 7 MB Posted

Attached to
Eglin NICoE Initial Outfitting Project
Solicitation number
W9127S20Q6000
Issued by

About this file

This is a combined synopsis/solicitation for commercial items issued by the Department of the Army Corps of Engineers Engineering District Little Rock. It is seeking quotes for the Eglin NICoE Initial Outfitting Project, with a total set-aside for Service-Disabled Veteran-Owned Small Businesses. Quotes are due by January 8, 2020 at 1:00pm Central Time. A site visit is tentatively scheduled for December 4, 2019 at 9:00am Central Time at Eglin Air Force Base West Visitors Center. Interested contractors must RSVP for the site visit by November 29, 2019 at 11:00am Central Time and provide contact information for base access. More information regarding entrance onto the base will be provided once attendance is confirmed. The solicitation number is W9127S20Q6000 and will use FAR simplified acquisition procedures in conjunction with commercial items procedures.

View the file

Other files

File Type Posted
Amendment 2 Attachment 2A - Cut Sheets (Salient Features_Specs).pdf PDF
Amendment 2 Attachment 10 - Site Visit Sign-In.pdf PDF
Amendment 2 Attachment 3A - Project Room Contents_25Dec2019.pdf PDF
W9127S20Q6000 AMENDMENT 0002.pdf PDF
Amendment 2 Attachment 1 - Bid Schedule.xlsx XLSX spreadsheet
Amendment 2 Attachment 8 - ESS_Video_Surveillance_VSS (ProjNet ID 8304557).pdf PDF
Amendment 2 Attachment 9 - Sound_Masking_Systems (ProjNet ID 8304607).pdf PDF
Amendment 2 Attachment 11 - ProjNet Questions_Answers.pdf PDF
Amendment 1 Attachment 3 - Project Room Contents.pdf PDF
W9127S20Q6000 Amendment 0001.pdf PDF
Amendment 1 Attachment 1 - Bid Schedule (Amendment 01).xlsx XLSX spreadsheet
Amendment 1 Attachment 2 - Cut Sheets (Salient Features_Specs).pdf PDF
Amendment 1 Attachment 4 - Eglin Invisible Wounds Clinic (IWC)_As-Built Drawings.pdf PDF
Attachment 4 - Drawings Specifications Vol 2.pdf PDF
Attachment 4 - Drawings 01 General.pdf PDF
W9127S20Q6000 - Combined Synopsis Solicitation NICoE - Eglin AFB IO Project.pdf PDF
Attachment 5 - Reuse List.xlsx XLSX spreadsheet
Attachment 7 - IO&T Submittal Examples.pdf PDF
Attachment 6 - DMLSS RPIE List.xls XLS spreadsheet
Attachment 4 - Drawings 02 Civil.pdf PDF
Attachment 1 - Bid Schedule.xlsx XLSX spreadsheet
Attachment 4 - Drawings 09 Fire Protection.pdf PDF
Attachment 4 - Drawings MEDICAL EQUIPMENT.pdf PDF
Attachment 4 - Drawings 08 Fire Alarm.pdf PDF
Attachment 2 - Cut Sheets.pdf PDF
Attachment 4 - Drawings 10 Electrical.pdf PDF
Attachment 4 - Drawings 11 Technology.pdf PDF
Attachment 4 - Drawings 07 Plumbing.pdf PDF
Attachment 4 - Drawings FFE.pdf PDF
Attachment 4 - Drawings 05 Architecture.pdf PDF
Attachment 4 - Drawings FURNITURE.pdf PDF
Attachment 3 - Project Room Contents_15Nov2019.pdf PDF
Attachment 4 - Drawings Specifications Vol 1.pdf PDF
Attachment 4 - Drawings 03 Landscape Arch.pdf PDF
Attachment 4 - Drawings 04 Structure.pdf PDF
Show all 35

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REFERENCE SYMBOLS

MECHANICAL ABBREVIATIONS

A L

M

B

C N

OD

E

P

Q

R

S F

G

T H

U

V

W

I

K

AD ACCESS DOOR

ACFM ABSOLUTE CUBIC FEET PER MINUTE

AFF ABOVE FINISHED FLOOR

AFM AIR FLOW MEASURING DEVICE

AFMS AIR FLOW MOISTURIZING STATION

AHU AIR HANDLING UNIT

AMB AMBIENT

AP ACCESS PANEL

APPROX APPROXIMATE

ASR AUTOMATIC SPRINKLER RISER

LAT LEAVING AIR TEMPERATURE

LBS/HR POUNDS PER HOUR

LGT LENGTH

LP LOW POINT

LRA LOCKED ROTOR AMPERS

LVG LEAVING

LWT LEAVING WATER TEMPERATURE

BFP BACKFLOW PREVENTOR

BHP BRAKE HORSEPOWER

BOD BOTTOM OF DUCT

BOP BOTTOM OF PIPE

BTU(H) BRITISH THERMAL UNIT (PER HOUR)

MAX MAXIMUM

MBH 1000 BTU/HR

MCC MOTOR CONTROL CENTER

MECH MECHANICAL

MER MECHANICAL EQUIPMENT ROOM

MIN MINIMUM

MISC MISCELLANEOUS

MTG MOUNTING

NC NOISE CRITERIA

N.C. NORMALLY CLOSED

NIC NOT IN CONTRACT

NO. NUMBER

N.O. NORMALLY OPEN

NOM NOMINAL

NPSH NET POSITIVE SUCTION HEAD

(NRL) NEW LOCATION OF RELOCATED

MATERIAL OR EQUIPMENT

NTS NOT TO SCALE

CAP. CAPACITY

CDSR CONDENSER

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CI CAST IRON

CO CLEAN OUT

COMP COMPRESSOR

COND CONDENSATE

CONT CONTINUATION

CW COLD WATER

DB DECIBELS

DBA DECIBELS (A-WEIGHTED SCALE)

DBT DRY BULB TEMPERATURE °F

DDC DIRECT DIGITAL DRIVE

DIA DIAMETER

DN DOWN

DP DIFFERENTIAL PRESSURE

DPT DEW POINT TEMPERATURE °F

DWG DRAWING

DX DIRECT EXPANSION

D&T DRIP & TRAP

OA OUTSIDE AIR

OAD OUTSIDE AIR DAMPER

OD OUTSIDE DIAMETER

OFD OVERFLOW DRAIN

OPR OPERATING

OV OUTLET VELOCITY

PD PRESSURE DROP (FEET OF WATER)

PRESS PRESSURE

PRV PRESSURE REGULATING VALVE

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUAREINCH - GUAGE

QTY QUANTITY

RA RETURN/RELIEF AIR

RC ROOF CONDUCTOR

RD ROOF DRAIN

RH RELATIVE HUMIDITY

(RL) RELOCATED MATERIAL OR EQUIPMENT

RLA RUNNING LOAD AMPS

RPM REVOLUTIONS PER MINUTE

RET RETURN

RE REFERENCE

SA SUPPLY AIR

SA SHOCK ABSORBER

SA SOUND ATTENUATOR

SAN SANITARY WASTE

SCFM STANDARD CUBIC FEET PER MINUTE

SD SMOKE DETECTOR

SDP SMOKE DAMPER

SENS SENSIBLE

SF SQUARE FEET

SG SPECIFIC GRAVITY

SL SOUND LINING

SP STATIC PRESSURE (INCHES OF WATER)

SPD SPEED

SPL SOUND POWER LEVEL

SPS STATIC PRESSURE SENSOR

SS STAINLESS STEEL

STM STEAM

TAB TESTING, ADJUSTING AND BALANCING

TEMP TEMPERATURE

TP TOTAL PRESSURE; TRAP PRIMER

TYP TYPICAL

UON UNLESS OTHERWISE NOTED

V VOLTS

VAC VACUUM

VEL VELOCITY

VFD VARIABLE FREQUENCY DRIVE

VTR VENT THRU ROOF

W WATTS

W/ WITH

W/O WITHOUT

WBT WET BULB TEMPERATURE

WDT WIDTH

WG WATER GUAGE

WH WALL HYDRANT

EA EACH; EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EER ENERGY EFFICIENCY RATIO

EFF EFFICIENCY

EGW ETHYLENE GLYCOL WATER SOLUTION

(% GLYCOL BY VOLUME)

EL ELEVATION

ENT ENTERING

EQ EQUIVALENT

ESP EXTERNAL STATIC PRESSURE

EWC ELECTRIC WATER COOLER

EWT ENTERING WATER TEMPERATURE

EXH EXHAUST

EXP EXPANSION

EXT EXTERNAL

(E) EXISTING

F FAHRENHEIT

FD FLOOR DRAIN

FDP FIRE DAMPER

FH FUME HOOD

FLA FULL LOAD AMPERS

FLEX FLEXIBLE CONNECTION

FLR FLOOR

FM FLOW METER

FPM FEET PER MINUTE

FS FLOW SWITCH

FSDP FIRE & SMOKE DAMPER

FT FEET or FOOT

GAL GALLONS

GPM GALLONS PER MINUTE

GR GRAINS

HB HOSE BIBB

HG MERCURY

HGT HEIGHT

HO HUB OUTLET

HP HORSE POWER

HR HOUR

HUM HUMIDIFIER

HZ HERTZ

ID INSIDE DIAMETER

IE INVERT ELEVATION

IFB INTEGRAL FACE AND BY-PASS

IN. INCHES

KW KILOWATTS

SEE MECHANICAL SYMBOLS, LEGENDS AND EQUIPMENT

SCHEDULES FOR ADDITIONAL ABBREVIATIONS. ALL

ABBREVIATIONS, SYMBOLS, AND LEGENDS SHOWN ON

THIS DRAWINGS ARE NOT NECESSARILY USED.

R

UNIT HEATER

OF AIR FLOW 45° OFFSETS

RETURN OR EXHAUST AIR FLOW

SUPPLY OR OUTSIDE AIR FLOW

SIDE WALL SUPPLY DIFFUSER

SIDE WALL RETURN or EXHAUST

GRILLE/REGISTER

PRESSURE REGULATING VALVE, FLANGED

HORIZONTAL FIRE DAMPER

REDUCER - ECCENTRIC

UP or DN

TEE OUTLET - UP

REDUCED PRESSURE BACKFLOW PREVENTOR

AIR VENT

DROP OR RISE

DIRECTION OF FLOW

DIRECTION OF PIPE PITCH

CONNECT OUT OF TOP

FLOW METER

ELBOW - TURNED UP OR RISER CONNECTION

PRESSURE GUAGE WITH COCK

QUICK COUPLING

ELBOW - TURNED DOWN

TEE OUTLET - DOWN

CAP OR PLUG

THERMOMETER

ALIGNMENT GUIDE

PIPE UNION

PIPE ANCHOR

FLOOR DRAIN (ROUND)

ROOF DRAIN (RD)

RUNNING TRAP

CLEANOUT IN FLOOR

REDUCER - CONCENTRIC

HOSE CONNECTION

WALL HYDRANT

STEAM TRAP

CLEANOUT

HOSE BIBB

FLOW INDICATING BALANCE VALVE

ORIFICE PLATE

FLEXIBLE CONNECTION

STRAINER

PRESSURE REDUCING VALVE

SAFETY RELIEF VALVE

VERTICAL DUCT DROP

VERTICAL DUCT RISE

DIRECTION OF FLOW

SMOKE DAMPER

VERTICAL FIRE DAMPER

MECHANICAL FLOOR PLAN SYMBOLS

BUTTERFLY VALVE (ISOLATION OR THROTTLING)

SELF ACTUATING TYPE DIFFERENTIAL PRESSURE

AUTOMATIC FLOW CONTROL VALVE

3-WAY ELECTRIC CONTROL VALVE

BALL VALVE (ISOLATION OR THROTTLING)

PLUG VALVE (ISOLATION OR THROTTLING)

AUTOMATIC DPCV

CONTROL VALVE (DPCV)

SOLENOID VALVE

2-WAY ELECTRIC CONTROL VALVE

3-WAY PNEUMATIC CONTROL VALVE

2-WAY PNEUMATIC CONTROL VALVE

ANGLE VALVE

CHECK VALVE

ISOLATION VALVE

THROTTLING VALVE

AUTOMATIC DAMPER (MOTORIZED)

VOLUME DAMPER (MANUAL)

ROOM THERMOSTAT

SMOKE DETECTOR

FLOW SWITCH

STATIC PRESSURE SENSOR

AIR SYSTEMS

SUPPLY

RETURN

T

PRESSURE REGULATING VALVE, THREADED

FLOOR DRAIN (RECTANGULAR)

SA

RA

TE

GE

SUPPLY AIR

RETURN AIR

GENERAL EXHAUST

TOILET EXHAUST

HVAC & PIPING LEGEND MECHANICAL GENERAL NOTES

(NOTES APPLY TO ALL MECHANICAL DRAWINGS.)

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

VAV BOX

VAV BOX

OUTSIDE AIR INTAKE

DUCT SYSTEM LOCATION PRESSURE

CLASSIFICATION

(INCH WATER

GAUGE)

REMARKS

FROM TO

FAN DISCHARGE

FAN INLETGRILLE/DIFFUSER

GENERAL EXHAUST

RETURN

SUPPLY

-4

MECHANICAL HVAC NOTES

THROUGH OUT -2

DIFFUSER

OWS OPERATOR WORK STATION

EXHAUST

HHWS HEATING HOT WATER SUPPLY

HHWR HEATING HOT WATER RETURN

CWS CONDENSER WATER SUPPLY

CWR CONDENSER WATER RETURN

HPR (PSIG)

LPR (PSIG)

PS

D

HPS (PSIG)

LPS (PSIG)

CS (PSIG)

PHWS

PHWR

RL

RS

CHWS

CHWR

RHG

CONDENSATE DRAIN

HIGH PRESSURE CONDENSATE RETURN

LOW PRESSURE CONDENSATE RETURN

LOW PRESSURE STEAM

CLEAN STEAM

PUMPED CONDENSATE

HIGH PRESSURE STEAM

PERIMETER HEATING WATER RETURN

PERIMETER HEATING WATER SUPPLY

CHILLED WATER SUPPLY

CHILLED WATER RETURN

REFRIGERANT HOT GAS

REFRIGERANT SUCTION

REFRIGERANT LIQUID

SD

FS

SP

SMOKE/FIRE COMBINATION DAMPER

INSTALL ALL WORK IN ACCORDANCE WITH ALL APPLICABLE UFC CRITERION AND THE FOLLOWING FLORIDA CODES: MECHANICAL CODE, PLUMBING CODE, ENERGY CODE, ELECTRIC CODE AND THE REGULATIONS OF ALL AUTHORITIES HAVING JURISDICTION.

TO OBTAIN ALL CONSTRUCTION INFORMATION, ALL SPECIFICATION AND DRAWINGS (E.G. ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL, ELECTRICAL, PLUMBING AND FIRE PROTECTION MUST BE USED.

BRING TO THE ATTENTION OF THE ARCHITECT/ENGINEER ANY INFORMATIONAL CONFLICTS WITHIN THE SPECIFICATIONS AND DRAWINGS. THE CONTRACTOR(S) SHALL NOT PROCEED WITH ANY WORK, EXCEPT AT ITS OWN RISK, UNTIL ALL CONFLICTS ARE RESOLVED AND THE CLARIFYING INFORMATION IS ISSUED TO THE CONTRACTOR(S) BY THE ARCHITECT/ENGINEER.

COORDINATE DIFFUSER & REGISTER LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS.

COORDINATE ALL WALL MOUNTED DEVICES SUCH AS THERMOSTATS AND CONTROL PANELS WITH ARCHITECTURAL INTERIOR

ELEVATIONS.

ALL DIMENSIONS SHOWN FOR DUCTWORK ARE NET INSIDE DIMENSIONS.

FURNISH AND INSTALL ALL MANUALLY OPERATED VOLUME CONTROL (BALANCING) DAMPERS NECESSARY TO PERFORM THE

BALANCING WORK.

THOUGH SOME OFFSETS & TRANSITIONS ARE SHOWN IN PIPING & SHEET METAL TO HELP INDICATE THE PHYSICAL RELATIONSHIP BETWEEN THEM, IT IS NOT THE INTENT OF THE DRAWINGS TO SHOW ALL PIPING & SHEET METAL OFFSETS & TRANSITIONS REQUIRED.

THE CONTRACTOR SHALL FULLY COORDINATE THE MECHANICAL WORK WITHIN ITSELF & WITH THE WORK OF ALL TRADES TO PROVIDE

COMPLETE & OPERABLE SYSTEMS WITHOUT INTERFERENCES.

DUCT CONSTRUCTION SHALL FOLLOW THE LATEST SMACNA STANDARDS FOR THE SPECIFIC PRESSURE CLASSIFICATIONS INDICATED

BELOW.

BUILDING IS TO BE FULLY SPRINKLERED; SPRINKLER LAYOUT SHALL CONFORM TO NFPA 13. REFLECTED CEILING PLANS SHOW SPRINKLER LAYOUT FOR SOME AREAS. REFER TO SPECIFICATIONS & ARCHITECTURAL DRAWINGS FOR ADDITIONAL LAYOUT

REQUIREMENTS.

PROVIDE DUCT PRESSURE CLASSIFICATIONS AS FOLLOWS:

-2

BCW BOOSTED COLD WATER

SUB-METER FOR COLD WATER, HOT WATER, GAS

HORIZONTAL SMOKE/FIRE COMBINATION DAMPER

TEST PORT

HB

ST

HC

S

M

M

M

AIR VENT WITH VALVE

RD

FD

FD

CO

CO

RISER DESIGNATION (TYPE AS INDICATED)

SECTION NUMBER

DETAIL NUMBER

DRAWING NUMBER WHERE DRAWN

DRAWING NUMBER WHERE DRAWN

E1-1.0

E1-1.0

KEY NOTE

1 DEMO KEY NOTE

GRILLE/DIFFUSER FAN INLET

THESE GENERAL NOTES APPLY TO ALL M SERIES DRAWINGS.

NOT ALL SYMBOLS, ABBREVIATIONS AND NOTES ON THIS SHEET MAY BE USED FOR THIS PROJECT.

PROVIDE OFFSETS AND TRANSITIONS IN DUCTWORK AND PIPING AS REQUIRED TO AVOID INTERFERENCE AT NO

ADDITIONAL COST TO THE OWNER.

VERIFY ALL EQUIPMENT CONNECTIONS WITH MANUFACTURER’S CERTIFIED DRAWINGS. FIELD VERIFY ALL DIMENSIONS BEFORE FABRICATION OF WORK. PROVIDE TRANSITIONS AND MAKE FINAL CONNECTIONS TO

EQUIPMENT, UNLESS OTHERWISE INDICATED.

COORDINATE EXACT LOCATION OF DIFFUSERS, GRILLES AND REGISTERS WITH THE ARCHITECTURAL DRAWINGS

BEFORE INSTALLATION. PROVIDE SYMMETRY WITH THE ROOM LIGHTING SYSTEMS.

VERIFY DIFFUSER, GRILLE AND REGISTER MOUNTING FRAME TYPES WITH THE CEILING TYPES. PROVIDE FRAME TYPE

THAT MATCHES MOUNTING CONFIGURATION.

INSTALL DUCTWORK AS CLOSE AS POSSIBLE TO UNDERSIDE OF BEAMS AND/OR JOISTS.

PROVIDE CONCRETE HOUSEKEEPING PADS FOR FLOOR MOUNTED EQUIPMENT. COORDINATE SIZES AND LOCATION

WITH ALL TRADES.

PROVIDE ACCESS DOORS AND/OR PANELS FOR DUCT MOUNTED FIRE, SMOKE, AND FIRE/SMOKE DAMPERS AND

SMOKE DETECTORS.

PROVIDE ACCESS DOORS AND/OR PANELS IN HARD CEILINGS AND WALLS TO PERMIT SERVICE TO DAMPERS, VALVES, AND CONCEALED EQUIPMENT.

DUCT CONSTRUCTION SHALL COMPLY WITH THE LATEST VERSION OF SMACNA CONSTRUCTION STANDARDS. ALL 90 DEGREE ELBOWS SHALL BE LONG RADIUS TYPE UNLESS SPACE IS LIMITED. SHORT RADIUS AND RECTANGULAR ELBOWS SHALL HAVE TURNING VANES. UNLESS OTHERWISE NOTED FOR BRANCH CONNECTIONS, PROVIDE CONICAL

TAPS FOR ROUND DUCTS AND 45 DEGREE TAPS FOR RECTANGULAR DUCTS.

PROVIDE FLEXIBLE CONNECTIONS BETWEEN DUCTWORK AND ALL FANS AND ALL AIR HANDLING EQUIPMENT.

PAINT FLAT BLACK THE INSIDE OF ALL DUCTWORK VISIBLE THROUGH DIFFUSERS, GRILLES AND REGISTERS.

PROVIDE OPEN END DUCTWORK (OED) WITH 2X2 MESH (1/2"X 1/2") ALUMINUM SCREEN WITH REMOVABLE FRAMES.

ALL DUCT WORK SIZES INDICATED ARE INSIDE CLEAR DIMENSIONS.

CONCENTRATE LOADS AT JOIST AND/OR BEAM LOCATIONS. WHERE CONCENTRATED LOADS DUE TO EQUIPMENT, RISERS, OR SPECIAL DUCT CONSTRUCTION OCCUR AT OTHER LOCATIONS, PROVIDE ADDITIONAL SUPPORT FRAMING

AND/OR ANGLE BRACING.

COORDINATE ALL DOOR UNDER CUTS INDICATED AND AS REQUIRED WHERE RETURN/TRANSFER OPENS ARE NOT

PROVIDED.

PROVIDE RUNOUT PIPING AS SCHEDULED OR AS OTHERWISE INDICATED.

FIRE SAFE PIPE AND DUCTWORK PENETRATIONS AT ALL FIRE RATED AND SMOKE RESISTIVE CONSTRUCTION.

COORDINATE WITH LIFE SAFETY PLANS FOR LOCATIONS. PENETRATION ASSEMBLY TO BE U.L. LISTED.

REFER TO ARCHITECTURAL GENERAL INFORMATION SHEETS FOR MOUNTING HEIGHTS OF DEVICES. WHERE THIS INFORMATION IS NOT PROVIDED, MOUNT ROOM THERMOSTATS AT 48 INCHES AFF AND OCCUPANCY SENSORS AT 84

INCHES AFF UNLESS OTHERWISE INDICATED.

INSTALL ALL EQUIPMENT LEVEL AND PLUMB. PROVIDE BLOCKING AND HARDWARE AS REQUIRED.

INSTALL ALL EQUIPMENT REQUIRING PERIODIC SERVICE NOT LESS THAN 10 FEET FROM ROOF EDGE OR OPENING, UNLESS PROTECTIVE RAILING OR PARAPET OF 42 INCHES AFF OR TIE-OFF POINT. HAS BEEN PROVIDED. VERIFY WITH

OTHER TRADES.

DUCT SYSTEMS SHALL BE BALANCED TO AIR FLOWS INDICATED ON DRAWINGS. FANS SHALL BE FIELD TESTED TO ENSURE COMPLIANCE WITH SCHEDULED FAN PERFORMANCE AND SCHEDULED AIR FLOW AT THE DESIGN STATIC

PRESSURES LISTED.

PROVIDE VOLUME DAMPERS AT ALL BRANCH DUCT TAKEOFFS, AT EACH AIR TERMINAL DEVICE AND WHERE

INDICATED.

WHERE SIZE OF MOTORIZED DAMPER EXCEEDS THE LIMITS OF A SINGLE OPERATOR, PROVIDE MULTIPLE OPERATORS

IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

M.

N.

O.

P.

Q.

R.

S.

T.

U.

V.

W.

X.

Y.

DRAWING NUMBER

PROJECT NUMBER

SCALE

DRAWING TITLE

KEYPLAN

SEALS AND SIGNATURES

ISSUED FOR REV DATE

Cagley & Associates

STRUCTURAL ENGINEERING

6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050

1700 NEW YORK AVE, NW

SUITE 100

WASHINGTON, DC 20006

202.842.2100 www.smithgroup.com

P lo t D at e:

EGLIN AIR FORCE BASE

BUILDING XX

ASH DR, EGLIN AIR FORCE BASE

FLORIDA

32542

IMEG Corporation

ELECTRONIC SECURITY / TELECOMMUNICATIONS

2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906

Baskerville-Donovan, Inc.

CIVIL ENGINEERING

449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340

SmithGroup

MEP-FP ENGINEERING

1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100

NONE

/4

/2

:2

:5

A

M MECHANICAL

ABBREVIATIONS AND

SYMBOLS

M0.1

10822.000

SCHEMATIC DESIGN 8.17.2018

DESIGN DEVELOPMENT 11.08.2018

CONTRACT DOCUMENTS 01.04.2019

CO2

CO2 CO2

CO2

CO2

CO2

CO2

CO2

CO2

CO2

CO2 CO2

CO2

CO2

CO2

T

T T

T

T T

T

T

T

T

TT

TT

T

T

TTT

T

T

T

T T T T

T

T

T

T

T

TT

T

T

T

T

T T

TT

T

T

T

T

T

T

T

T

T T

T

T

T

TT

T

T

T

T

T

T

T

T

T

8.38.6

7.1

6.9 6.5 6.2

5.4

5.2

4.8

4.5

3.6

2.8

2 1

0.2A

0.3A

0.4A

0.7A

0.9A A

A.2

A.9

A.7

B B

D D

D.7

E E

F F

0.5A

6.8 6.4

B2

C C

E.8

DPS

DPS

DPS

M235

M234

M236

M236

M236

DX-1

DX-2

DX-3

DX-4

DX-5/6

FCU-1

UH-1

VAV-1

VAV-2

VAV-3

VAV-4

VAV-5

VAV-6

VAV-7

VAV-8

VAV-9

VAV-10

VAV-11

VAV-12

VAV-13

VAV-14

VAV-15

VAV-16

VAV-17

VAV-18

VAV-19

VAV-20

VAV-21

VAV-22

VAV-23

VAV-24

VAV-25

VAV-26

VAV-27

VAV-28

VAV-29

VAV-30

VAV-31

VAV-32

VAV-33

VAV-34

VAV-35

VAV-36

VAV-37

VAV-38

VAV-39

VAV-40

VAV-41

VAV-42

VAV-43

VAV-44

VAV-45

VAV-46

VAV-47

VAV-48

VAV-49

VAV-50

VAV-51

VAV-52

VAV-53

VAV-54

VAV-55

VAV-56

VAV-57

VAV-58

Calculating...

VAV-1

FCU-1

DX-3

DX-4

UH-1

DX-2

DX-1

VAV-2

VAV-3

VAV-4

VAV-5

VAV-6

VAV-7 VAV-8 VAV-9

VAV-10

VAV-11

VAV-12

VAV-13

VAV-14

VAV-15

VAV-16

VAV-17

VAV-18

VAV-19

VAV-20

VAV-21

VAV-22

VAV-23

VAV-24

VAV-25 VAV-26 VAV-27

VAV-29

VAV-30

VAV-31

VAV-32

VAV-33

VAV-34

VAV-35

VAV-36

VAV-37

VAV-38

VAV-39

VAV-40

VAV-41

VAV-42

VAV-43

VAV-44

VAV-45

VAV-46

VAV-47

VAV-48

VAV-49

VAV-50

VAV-51

VAV-52

VAV-53

VAV-54

VAV-55

VAV-56

VAV-57

VAV-28

DX-5/6

VAV-58

DRAWING NUMBER

PROJECT NUMBER

SCALE

DRAWING TITLE

KEYPLAN

SEALS AND SIGNATURES

ISSUED FOR REV DATE

PLAN

NORTH

Cagley & Associates

STRUCTURAL ENGINEERING

6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050

1700 NEW YORK AVE, NW

SUITE 100

WASHINGTON, DC 20006

202.842.2100 www.smithgroup.com

P lo t D at e:

EGLIN AIR FORCE BASE

BUILDING XX

ASH DR, EGLIN AIR FORCE BASE

FLORIDA

32542

IMEG Corporation

ELECTRONIC SECURITY / TELECOMMUNICATIONS

2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906

Baskerville-Donovan, Inc.

CIVIL ENGINEERING

449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340

SmithGroup

MEP-FP ENGINEERING

1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100

1/8" = 1'-0"

/4

/2

:2

:5

A

M HVAC ZONE LEGEND

M2.1

10822.000

SHEET NOTES

M234 PROVIDE WALL MOUNTED CO2 SENSOR.

TYPICAL THROUGHOUT.

M235 PROVIDE WALL MOUNTED THERMOSTAT.

TYPICAL THROUGHOUT.

M236 PROVIDE DIFFERENTIAL PRESSURE

SENSORS. SEE CONTROL DRAWINGS FOR

ADDITIONAL INFORMATION.

KEYED NOTES

SCALE: 1/8" = 1'-0"

HVAC ZONE LEGEND

SCHEMATIC DESIGN 8.17.2018

T ectonic Cop yright 2007

SS

S

8.38.6

7.1

6.9 6.5 6.2

5.4

5.2

4.8

4.5

3.6

2.8

2 1

0.2A

0.3A

0.4A

0.7A

0.9A A

A.2

A.9

A.7

B

D

D.7

E

F

0.5A

100CFM

S4-1

100CFM

S4-1

100CFM

S4-1

100CFM

S4-1

200CFM

S2-7

175CFM

S2-1

200CFM

S2-1

150CFM

S2-1

100CFM

S1-1

100CFM

S1-1

150CFM

S1-1

150CFM

S1-1

150CFM

S2-2

200CFM

S2-2

150CFM

S2-2

175CFM

S2-1

100CFM

S2-1

150CFM

S2-1

150CFM

S2-2

150CFM

S2-2

150CFM

S2-2

M4.2

6.8 6.4

B2

C

E.8

M227

M231

200CFM

S2-7

200CFM

S2-7

225CFM

S1-3

225CFM

S1-3 450CFM

R1-5

200CFM

S1-2

200CFM

S1-2

400CFM

R1-4

250CFM

S1-3

250CFM

S1-3

250CFM

S1-3

250CFM

R1-3

250CFM

R1-3

250CFM

R1-3

200CFM

S1-2

200CFM

S1-2

200CFM

S1-2

200CFM

R1-2

200CFM

R1-2

200CFM

R1-2

250CFM

R1-3250CFM

S1-3

150CFM

R1-2

150CFM

S1-1 200CFM

S1-2

200CFM

R1-2

100CFM

S3-1

150CFM

R1-2

150CFM

S1-1

200CFM

R1-2

200CFM

S1-2

300CFM

S1-3

200CFM

S1-2

200CFM

S1-2

150CFM

E1-2

150CFM

S1-1

150CFM

R1-2

150CFM

S1-1

150CFM

S1-1

150CFM

R1-2

250CFM

S1-3

250CFM

S1-3

250CFM

R1-3

250CFM

R1-3

50CFM

S3-1

100CFM

S1-1

100CFM

S1-1

200CFM

S1-2

100CFM

R1-1

100CFM

S1-1

250CFM

R1-3

200CFM

R1-2150CFM

S1-1

200CFM

R1-2

200CFM

S1-2

150CFM

R1-2

150CFM

S1-1

150CFM

S1-1

150CFM

S1-1

150CFM

R1-2

150CFM

S1-1

150CFM

R1-2

150CFM

S1-1

150CFM

R1-2

150CFM

S1-1

150CFM

R1-2

100CFM

S1-1

50CFM

S3-1

200CFM

S1-2

150CFM

S1-1

150CFM

S1-1

150CFM

R1-2

200CFM

S1-2

100CFM

R1-1

150CFM

S1-1

150CFM

R1-2

150CFM

S1-1

150CFM

S1-1

300CFM

R1-3

100CFM

S1-1

100CFM

S1-1

100CFM

S1-1

100CFM

R1-1

100CFM

R1-1

100CFM

R1-1

100CFM

R1-1

100CFM

R1-1 100CFM

R1-1

100CFM

S1-1

100CFM

S1-1

100CFM

S1-1

200CFM

S1-2

200CFM

R1-2

200CFM

S1-2

200CFM

R1-2

200CFM

S1-2

200CFM

R1-2

200CFM

S1-2

200CFM

R1-2

100CFM

S1-1

100CFM

R1-1

150CFM

S1-1

150CFM

S1-1

150CFM

R1-2

150CFM

R1-2

150CFM

S1-1

150CFM

E1-2

150CFM

S1-1

150CFM

S1-1

300CFM

S2-4

150CFM

S2-4

300CFM

S2-4

200CFM

S2-4

200CFM

S2-4

100CFM

S2-4

950CFM

R3-1

1000CFM

R3-1 275CFM

S1-3

275CFM

S1-3

275CFM

S1-3

275CFM

S1-3

275CFM

S1-3

275CFM

S1-3

275CFM

S1-3

275CFM

S1-3

300CFM

S1-3

300CFM

S1-3

300CFM

S1-3

300CFM

S1-3

500CFM

R3-1

600CFM

R3-1

200CFM

S2-1

200CFM

S2-1

200CFM

S2-1

100CFM

S1-1

150CFM

S1-1

350CFM

R1-4

400CFM

R1-4

500CFM

R1-5

250CFM

S1-3

250CFM

S1-3

175CFM

R1-2

175CFM

S1-2

175CFM

S1-2

175CFM

R1-2

150CFM

R1-2

150CFM

S1-1 150CFM

R1-2

150CFM

S1-1

100CFM

S1-1

100CFM

R1-1

200CFM

R1-2

100CFM

S1-1

125CFM

S1-1

125CFM

S1-1

250CFM

R1-3

250CFM

S1-3

250CFM

R1-3

125CFM

S1-1

300CFM

R1-3

150CFM

S1-1

1500CFM

R3-2

1500CFM

R3-2

50CFM

S1-1

50CFM

S1-1

50CFM

S3-1100CFM

E1-1

200CFM

S1-2

100CFM

E1-1

100CFM

E1-1

100CFM

E1-1

100CFM

S3-1

200CFM

S1-2

100CFM

E1-1

200CFM

E1-2

100CFM

S1-1

150CFM

E1-2

100CFM

S3-1

350CFM

S1-4

200CFM

R1-2

150CFM

S1-1

300CFM

E1-3

300CFM

E1-3

100CFM

S1-1

100CFM

R1-1

150CFM

E1-2

200CFM

S1-2

200CFM

R1-2

100CFM

E1-1

100CFM

E1-1

100CFM

E1-1

50CFM

S3-1

300CFM

R1-3

100CFM

S1-1

100CFM

S2-5

150CFM

S1-1

100CFM

S2-5

100CFM

S2-6

100CFM

S2-6

200CFM

S2-1

200CFM

R3-3

125CFM

S1-1

100CFM

S1-1

150CFM

R1-2

150CFM

E1-2

150CFM

R1-2

500CFM

R1-5

50CFM

S3-1

50CFM

S3-1

50CFM

S3-1

100CFM

S1-1

100CFM

R1-1

200CFM

E1-2

150CFM

R1-2

100CFM

S2-5

M210

M210

M210

M210

M210

M210

150CFM

E1-3

VESTIBULE

CORR

C301

PUBLIC WAITING

C101

TLT/ SHR

218.2

MECHANICAL

FAMILY WAITING

MAT / PLATFORM

ACCUPUNCTURE-1

341.1-1

SPIRITUAL COUNSELLING

BRAIN LAB

CORR-1

C306-1

COMM

CASE MGMT

PSYCHOLOGIST

ART AND CLAY THERAPY

STORAGE / KILN

338.1

COMM

ELEC

SPEECH THERAPY

VENDING ALCOVE

106.1

NICoE DIR.

AV SUPPLY

HOUSE KEEPING

DAILY LIVING SKILLS

PAT TLT

NEUROPSYCH

333PSYCH TECH

BREAK ALCOVE

106.2

STAFF TLT

CLASSROOM

CLASSROOM

103.1

CORR

C201

CHAPLIN

CASE MGMT

NEUROLOGIST

CHANGING / LOCKER (M)

218 SPEECH THERAPY

DIR. OF CLINICAL SERVICES

MUSIC THERAPY

CORR

C102

RESEARCH SHARED OFFICE

ACCUPUNCTURE-2

341.1-2

ACCUPUNCTURE

341.2

PT GYM-1

200-1

NP PSYCH

STAFF TLT

FEMALE TOILET

MALE TOILET

CORR

DAYROOM

STORAGE / ALCOVE

200.1

CORR

C200

SOIL UTIL

EQPT STOR

MULTI-STATION TREATMENT

RM

OT O/E

PT O/E

PT O/E

OT O/E

RECEPTION

PATIENT INTAKE CUBICLES

300.1

CORR-2

C306-2

MAIN CORRIDOR / LOBBY-1

C100-1

CASE MGMT

CHECK-IN KIOSK

300.2

CLINICAL PHARMACIST

PC MD

BH / SW PROVIDERS

TRANS-CRANIAL MAGNETIC

STIM

ELEC

GROUP THERAPY

CORR-3

C306-3

CORR

C303

GROUP THERAPY

335.1

PSYCH TECH

CORR-1

C302-1

CORR-2

C302-2

HOUSE KEEPING

SOIL UTIL

EXAM

TREATMENT IPMC

EXAM

TREATMENT IPMC

EYE LANE

CORR

C304

FLEX STORAGE

CLEAN UTIL

WORKSTATION PT

TEAM ROOM

EXAM

EXAM

EXAM

CORRIDOR

C305

EXAM

EXAM

EXAM

PAT TLT

CORRIDOR

C300

NCOIC / ADMIN

TRAZER / FATS

NEURO REHAB AREA

CENTRAL PARK

STAFF LOUNGE

PAIN MD

CHIRO TREATMENT

CHIRO TREATMENT

CORR-3

C302-3

MAIN CORRIDOR / LOBBY

C100

MAIN CORRIDOR / LOBBY-3

C100-3

PT GYM-2

200-2

BIO NEUROFEEDBACK

EQPT STOR

BH / SW PROVIDER

BH / SW PROVIDERS

ALCOVE / STORAGE

C303.1

EYE TESTING

GAIT OBS LANE

CHANGING / LOCKER (W)

219TLT / SHR

219.1

TLT/ SHR

218.1

CORR

C202

700CFM

R3-1

100CFM

S2-6

100CFM

S2-6

100CFM

S2-5

100CFM

S2-6

100CFM

S2-6

M227

M227

M231

COPY

109.1

100CFM

S1-1

150CFM

S2-1

150CFM

S2-1

150CFM

R1-2

100CFM

S1-1

50CFM

S1-1

200CFM

S1-2

100CFM

S1-1

DRAWING NUMBER

PROJECT NUMBER

SCALE

DRAWING TITLE

KEYPLAN

SEALS AND SIGNATURES

ISSUED FOR REV DATE

PLAN

NORTH

Cagley & Associates

STRUCTURAL ENGINEERING

6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050

1700 NEW YORK AVE, NW

SUITE 100

WASHINGTON, DC 20006

202.842.2100 www.smithgroup.com

P lo t D at e:

EGLIN AIR FORCE BASE

BUILDING XX

ASH DR, EGLIN AIR FORCE BASE

FLORIDA

32542

IMEG Corporation

ELECTRONIC SECURITY / TELECOMMUNICATIONS

2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906

Baskerville-Donovan, Inc.

CIVIL ENGINEERING

449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340

SmithGroup

MEP-FP ENGINEERING

1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100

1/8" = 1'-0"

/4

/2

:2

:0

A

M GROUND FLOOR AIR

TERMINALS

M2.2

10822.000

SCALE: 1/8" = 1'-0"

GROUND FLOOR AIR TERMINALS

SHEET NOTES

M210 PROVIDE 4' PLENUM WITH 10" NECK .

BLANK OFF 1' ON EACH SIDE OF THE

LINEAR DIFFUSER.

M227 PROVIDE ONE (1) CONTINUOUS LINEAR

DIFFUSER WITH THREE (3) 4' PLENUMS.

BALANCE EACH PLENUM FOR CFM

SHOWN.

M231 PROVIDE ONE (1) CONTINUOUS LINEAR

DIFFUSER WITH TWO (2) 4' PLENUMS.

BALANCE EACH PLENUM FOR CFM

SHOWN.

KEYED NOTES

1. AIR TERMINALS LOCATED IN AREAS WITH A ACOUSTICAL

CEILING TILES SHALL BE COORDINATED WITH THE CEILING

GRID. SEE ARCHITECTURAL PLANS AND DETAILS.

2. AIR TERMINALS LOCATED IN HARD LID DRYWALL CEILINGS

SHALL BE INSTALLED SUCH THAT THE OPENING FOR THE

AIR TERMINAL IS THOUROUGHLY SEALED/MUDDED.

8.38.6

7.1

6.9 6.5 6.2

5.4

5.2

4.8

4.5

3.6

2.8

2 1

0.2A

0.3A

0.4A

0.7A

0.9A A

A.2

A.9

A.7

B B

D D

D.7

E E

F F

0.5A

FCU-1

"x

60"x18"

"x

EV-1

CP-1

EV-2

CP-2

CP-3 EV-3

EV-4 CP-4

"x

M4.1

"x

14"x8"

10"x8"

22"x8"

26"x8"

24"x12"

M4.2

M4.2

24"x14"

16"x8"

30"x8"

M4.2

M4.2

6.8 6.4

B2

C C

E.8

18"x18" 24"x18"

"x

20"x16"

"x

26"x14"

20"x12"20"x16"18"x14"

60"x18"

10"x10"

36"x20"42"x16"

"x

68"x26"

26"x14"

"x

20"x10"

8"x8"

8"x8" 12"x10"

26"x14"

12"x12"

"x

66"x26"

74"x30"

48"x8"

12"x10"

"x

64"x20"

M207

M208

M209

54"x22"

16"x8"

M211

M230

66"x32"

14"x10"

20"x10"

20"x14"

10"x10"

"x

12"x10" 18"x12" 24"x12" 30"x10" 30"x12"

14"x10"

16"x12" 24"x12" 30"x12"

14"x20"

"x

16"x14" 20"x16"

48"x8"

16"x12"

12"x10"

16"x8"

28"x16"

26"x8"26"x6"

12"x10"

8"ø8"x8"

10"x8"

"x

16"x10" 16"x10"

12"x10"

6"x6"

12"x8"

10"x8"

12"x10"

16"x12"10"x10" 10"x8"

"x

16"x8"

6"ø

12"x8"

10"x10"

8"x10"

10"x10"

8"x10"

10"x10"

8"x6" 12"x12"

16"x12"

8"x14"

8"x14"

8"x8"

8"x8"

10"x10"

12"x8"

12"x10"

10"ø

10"x10"

10"x8" 6"x8"

8"x8" 12"x8"

12"x8"

12"x10"

16"x10"

16"x10"

12"x8"

10"ø

8"x6"

8"x6"

50"x22"

12"x10"

10"x12"

12"x10"

14"x12"

18"x10"

"x

"x

28"x16"

18"x16"

"x

10"x8"

10"x8"

12"x8"

8"x8"

12"x12"

20"x10"

10"ø 10"x10"

18"x12"

10"x10"

66"x26"

8"x8"

10"x8"

12"x8"

14"x8" 20"x8" 10"x8"

10"ø

30"x10" 42"x16"

"x

16"x10"

16"x12"

14"x10" 14"x10"

"x

6"x8" 8"x6"

12"x8"

12"x10"

12"x8"

10"x8"

12"x8"

12"x10"

8"x12"

12"x10"

14"x12"

14"x10"

12"x8"

C301

C101

218.2

341.1-1

C306-1

338.1

106.1

106.2

103 103.1

C201

311 309

C102

341.1-2

341.2

200-1

200.1

C200

206205

300.1

C306-2

C100-1

300.2

305307

C306-3

C303

335.1

C302-1

C302-2

350 346

C304

345347348

C305

310 308 306

C300

109.1

C302-3

C100

C100-3

200-2

C303.1

219.1

218.1

C202

C203

"x

"x

12"x8"

8"x6"

22"x12"24"x16"

22"x14"

20"x20"

20"x20"

24"x8"

VAV-4

VAV-6

VAV-57

VAV-25

VAV-24

VAV-26

VAV-27

VAV-29

VAV-28

VAV-23

VAV-21 VAV-22VAV-20

VAV-18

VAV-31

VAV-17VAV-16

VAV-15

VAV-19

VAV-3

VAV-14

VAV-2

VAV-1

VAV-7

VAV-5

VAV-10

VAV-12 VAV-11

VAV-13

VAV-30

VAV-8

VAV-33

VAV-9

VAV-47

VAV-32 VAV-54 VAV-55

VAV-56

VAV-53

VAV-51

VAV-49 VAV-50

VAV-52

VAV-43

VAV-48

VAV-44

VAV-41

VAV-40

VAV-42

VAV-39

VAV-38VAV-37

VAV-36

VAV-35

VAV-34 VAV-46

VAV-45

64"x24"

10"x10"

EV-5 CP-5

EV-6

CP-6

12"x8"

12"x8"

VAV-58

8"ø

10"x8"

16"x10"

30"x10" 32"x12"

"x

VAV-45

DRAWING NUMBER

PROJECT NUMBER

SCALE

DRAWING TITLE

KEYPLAN

SEALS AND SIGNATURES

ISSUED FOR REV DATE

PLAN

NORTH

Cagley & Associates

STRUCTURAL ENGINEERING

6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050

1700 NEW YORK AVE, NW

SUITE 100

WASHINGTON, DC 20006

202.842.2100 www.smithgroup.com

P lo t D at e:

EGLIN AIR FORCE BASE

BUILDING XX

ASH DR, EGLIN AIR FORCE BASE

FLORIDA

32542

IMEG Corporation

ELECTRONIC SECURITY / TELECOMMUNICATIONS

2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906

Baskerville-Donovan, Inc.

CIVIL ENGINEERING

449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340

SmithGroup

MEP-FP ENGINEERING

1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100

1/8" = 1'-0"

/4

/2

:2

:0

A

M GROUND FLOOR

DUCT PLAN

M2.3

10822.000

SHEET NOTES

M207 18"X18" EXHAUST DUCT UP TO EF-3 ON ROOF.

M208 16"X16" EXHAUST DUCT UP TO EF-2 ON ROOF.

M209 16"X16" EXHAUST DUCT UP TO EF-1 ON ROOF.

M211 PROVIDE EMERGENCY SHUTOFF SWITCH FOR

ENTIRE HVAC SYSTEM. INSTALL 48" ABOVE

FINISHED FLOOR. SEE SHEET M8.8 FOR MORE

INFORMATION.

M230 PROVIDE OPEN END DUCT WITH VOLUME DAMPER

FOR RETURN FROM CENTRAL PARK.

SCALE: 1/8" = 1'-0"

GROUND FLOOR DUCT PLAN

KEYED NOTES

1. PROVIDE VOLUME DAMPERS ON ALL DUCT TAKEOFFS

SERVING SUPPLY, EXHAUST AND RETURN AIR TERMINALS.

TYPICAL THROUGHOUT.

2. PROVIDE REMOTE DAMPER OPERATORS FOR ALL AIR

TERMINALS LOCATED IN THE HARD LID AND WOOD CEILING.

3. PROVIDE ALL RECTANGULAR MITERED ELBOWS WITH

TURNING VANES.

4. PROVIDE DUCT PRESSURE READING PORTS BEFORE AND

AFTER DUCT SILENCERS. TYPICAL FOR ALL DUCT SILENCERS.

5. PROVIDE DUCT DP SENSOR LOCATED IN COMPLIANCE WITH

ASHRAE 90.1. STATIC PRESSURE SENSORS SHALL BE PLACED

IN A POSITION SUCH THAT THE CONTROLLER SETPOINT IS NO

GREATER THAN ONE-THIRD THE TOTAL STATIC PRESSURE. IF

THIS RESULTS IN THE SENSOR BEING LOCATED

DOWNSTREAM OF MAJOR DUCT SPLITS, MULTIPLE SENSORS

SHALL BE INSTALLED IN EACH MAJOR BRANCH TO ENSURE

THAT STATIC PRESSURE CAN BE MAINTAINED IN EACH.

6. IN ADDITION TO HANGERS AND SUPPORTS FOR DUCTWORK,

PIPING AND EQUIPMENT, PROVIDE SEISMIC RESTRAINTS IN

CONFORMANCE WITH ASCE/SEI 07 – 10. FOR ADDITIONAL

INFORMATION, SEE SPECIFICATIONS, STRUCTURAL

DRAWINGS AND CHAPTER 13 OF ASCE/SEI 07–10.

7. DO NOT PROVIDE VAV BOXES WITH AN 120V INTEGRAL

ELECTRICAL TRANSFORMER. COORDINATE WITH THE

ELECTRICAL TRADE.

Room Schedule Number Name

337 PSYCHOLOGIST

338 ART AND CLAY THERAPY

338.1 STORAGE / KILN

339 CASE MGMT

340 PAT TLT

341.1-1 ACCUPUNCTURE-1

341.1-2 ACCUPUNCTURE-2

341.2 ACCUPUNCTURE

342 BRAIN LAB

343 EYE LANE

344 TREATMENT IPMC

344 EYE TESTING

345 EXAM

346 TREATMENT IPMC

347 EXAM

348 EXAM

349 EXAM

350 EXAM

351 TRANS-CRANIAL MAGNETIC STIM

359 CORR

C100 MAIN CORRIDOR / LOBBY

C100-1 MAIN CORRIDOR / LOBBY-1

C100-3 MAIN CORRIDOR / LOBBY-3

C101 PUBLIC WAITING

C102 CORR

C200 CORR

C201 CORR

C202 CORR

C203 Space

C204 Space

C300 CORRIDOR

C301 CORR

C302-1 CORR-1

C302-2 CORR-2

C302-3 CORR-3

C303 CORR

C303.1 ALCOVE / STORAGE

C304 CORR

C305 CORRIDOR

C306-1 CORR-1

C306-2 CORR-2

C306-3 CORR-3

Room Schedule Number Name

219.1 TLT / SHR

220 MECHANICAL

300 RECEPTION

300.1 PATIENT INTAKE CUBICLES

300.2 CHECK-IN KIOSK

301 CHAPLIN

302 SPIRITUAL COUNSELLING

303 CASE MGMT

304 TEAM ROOM

305 CLINICAL PHARMACIST

306 EXAM

307 PC MD

308 EXAM

309 NEUROLOGIST

310 EXAM

311 CASE MGMT

312 MUSIC THERAPY

313 PAT TLT

314 STAFF LOUNGE

315 CLEAN UTIL

316 PAIN MD

317 FLEX STORAGE

318 STAFF TLT

319 CHIRO TREATMENT

320 HOUSE KEEPING

321 CHIRO TREATMENT

322 SOIL UTIL

323 BIO NEUROFEEDBACK

324 COMM

325 EQPT STOR

326 BH / SW PROVIDERS

327 BH / SW PROVIDERS

329 BH / SW PROVIDER

330 ELEC

331 PSYCH TECH

332 PSYCH TECH

333 NEUROPSYCH

334 STAFF TLT

335 GROUP THERAPY

335.1 GROUP THERAPY

336 NP PSYCH

Room Schedule Number Name

100 VESTIBULE

101 FAMILY WAITING

102 CENTRAL PARK

103 CLASSROOM

103.1 CLASSROOM

104 AV SUPPLY

105 DAYROOM

106.1 VENDING ALCOVE

106.2 BREAK ALCOVE

107 FEMALE TOILET

108 MALE TOILET

109 NCOIC / ADMIN

109.1 COPY

110 DIR. OF CLINICAL SERVICES

111 RESEARCH SHARED OFFICE

112 NICoE DIR.

113 HOUSE KEEPING

114 ELEC

200-1 PT GYM-1

200-2 PT GYM-2

200.1 STORAGE / ALCOVE

201 WORKSTATION PT

202 NEURO REHAB AREA

203 MAT / PLATFORM

204 GAIT OBS LANE

205 EQPT STOR

206 SOIL UTIL

207 PT O/E

208 PT O/E

209 TRAZER / FATS

210 SPEECH THERAPY

211 COMM

212 DAILY LIVING SKILLS

213 OT O/E

214 SPEECH THERAPY

215 OT O/E

217 MULTI-STATION TREATMENT RM

218 CHANGING / LOCKER (M)

218.1 TLT/ SHR

218.2 TLT/ SHR

219 CHANGING / LOCKER (W)

SCHEMATIC DESIGN 8.17.2018

7.1

6.9 6.5 6.2

5.4

5.2

4.8

4.5

3.6

2.8

2 1

0.2A

0.3A

0.4A

0.7A

0.9A A

A.2

A.9

A.7

B B

D D

D.7

E E

F F

0.5A

ALP-2

ALP-1

CU-3

CU-1 CU-2

EF-1

EF-4

EF-3

PROVIDE PVC BOILER INTAKE

AND STAINLESS STEEL

EXHAUST.

PROVIDE PVC BOILER INTAKE

AND STAINLESS STEEL

EXHAUST.

ARCHITECTURAL

LOUVERED

PENTHOUSE

ALP-3

CU-4

PROVIDE PVC INTAKE AND

EXHAUST FOR DWH-1.

AIR COOLED

CONDENSING UNIT FOR

DX COOLING FAN COILS

(TYP.)

6.8 6.4

B2

C C

E.8

EF-2

M221

M214

M214

M214

M214

M228

M228

M229

M229

M228

M239

M239

54"x30"

CU-6 CU-5

AIR COOLED

CONDENSING UNIT FOR

DX COOLING FAN COILS

(TYP.)

AIR COOLED

CONDENSING UNIT FOR

DX COOLING FAN COILS

(TYP.)

ROOF HATCH

54"x32"

DRAWING NUMBER

PROJECT NUMBER

SCALE

DRAWING TITLE

KEYPLAN

SEALS AND SIGNATURES

ISSUED FOR REV DATE

PLAN

NORTH

Cagley & Associates

STRUCTURAL ENGINEERING

6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050

1700 NEW YORK AVE, NW

SUITE 100

WASHINGTON, DC 20006

202.842.2100 www.smithgroup.com

P lo t D at e:

EGLIN AIR FORCE BASE

BUILDING XX

ASH DR, EGLIN AIR FORCE BASE

FLORIDA

32542

IMEG Corporation

ELECTRONIC SECURITY / TELECOMMUNICATIONS

2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906

Baskerville-Donovan, Inc.

CIVIL ENGINEERING

449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340

SmithGroup

MEP-FP ENGINEERING

1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100

1/8" = 1'-0"

/4

/2

:2

:1

A

M ROOF PLAN

M2.4

10822.000

SHEET NOTES

M214 PROVIDE EXHAUST FAN WITH MOTORIZED

CONTROL DAMPER THAT MEETS THE

LEAKAGE REQUIREMENTS OUTLINED IN

UFC 4-010-01, PARAGRAPH B-4.3.1

M221 PROVIDE 20"X20" DUCT FROM ALP-3 INTO

THE MECHANICAL ROOM. PROVIDE AND

INSTALL MOTORIZED CONTROL DAMPER

IN THE DUCTWORK. PROVIDE OPEN END

DUCT WITH MESH SCREEN INTO THE

MECHANICAL ROOM.

M228 PROVIDE AND INSTALL SEISMICALLY

RATED ARCHITECTURAL LOUVERED

PENTHOUSE; SEE STRUCTURAL

DRAWINGS, SPEC SECTION 233723 AND

SECTION 230548 FOR ADDITIONAL

INFORMATION.

M229 FOR ALL BOILER FLUE EXHAUST,

MAINTAIN A MINIMUM DISTANCE OF 15

FEET FROM ANY OUTSIDE AIR INTAKE

PER IMC.

M239 PROVIDE 3' ROOF CURB

SCALE: 1/8" = 1'-0"

ROOF PLAN

KEYED NOTES

1. IN ADDITION TO HANGERS AND SUPPORTS FOR DUCTWORK,

PIPING AND EQUIPMENT, PROVIDE SEISMIC RESTRAINTS IN

CONFORMANCE WITH ASCE/SEI 07 – 10. FOR ADDITIONAL

INFORMATION, SEE SPECIFICATIONS, STRUCTURAL DRAWINGS

AND CHAPTER 13 OF ASCE/SEI 07–10.

SCHEMATIC DESIGN 8.17.2018

7.1

6.9 6.5 6.2

5.4

5.2

4.8

4.5

3.6

2.8

2 1

0.2A

0.3A

0.4A

0.7A

0.9A A

A.2

A.9

A.7

B B

D D

D.7

E E

F F

0.5A

FCU-1

C H

W R

C H

W S

BELOW GRADE

BELOW

GRADE

4" CHWS/R PIPING TO CH-1 IN

CHILLER UTILITY

ENCLOSURE.

SEE BELOW.

4" CHWS/R PIPING DOWN

THROUGH SLAB TO CH-1

FTR-2B

FTR-2

FTR-1

FTR-1B

EV-2

EV-1

CP-1

CP-2

CP-3

CP-4

EV-4

EV-3

M4.1

M4.2

M4.2

1 1/4" HHWR

1 1/4" HHWS

1" HHWR

1" HHWS

1" HHWS

1" HHWR

/4

H H

W R

/4

H H

W S

1 1/4" HHWR

1 1/4" HHWS

3/4" HHWS

3/4" HHWR

3/4" HHWR

3/4" HHWS

1" HHWS

1" HHWR

M4.2

M4.2

6.8 6.4

B2

C C

E.8

3/4" HHWS

3/4" HHWS

3/4" HHWR

/4

H H

W R

/4

H H

W S

M302

M302

M302

M216

M216

M216

M216

M219

M303

M303

VAV-4

VAV-6

VAV-57

VAV-25

VAV-24 VAV-26

VAV-27

VAV-29

VAV-28 VAV-28

VAV-19

VAV-20 VAV-22 VAV-21 VAV-23

VAV-31

VAV-3

VAV-15

VAV-16 VAV-17

VAV-18

VAV-14

VAV-2

VAV-5

VAV-1

VAV-7

VAV-10

VAV-12 VAV-11

VAV-8

VAV-9

VAV-33

VAV-30

VAV-13

VAV-32

VAV-54 VAV-55

VAV-56

VAV-53

VAV-51

VAV-47

VAV-49

VAV-50

VAV-34

VAV-46

VAV-35

VAV-36

VAV-37

VAV-38 VAV-39

VAV-42

VAV-45

VAV-40

VAV-41

VAV-44

VAV-43

VAV-48

VAV-52

3/4" HHWS

3/4" HHWR

1" HHWR

1" HHWS

1 1/2" HHWR

1 1/2" HHWS

3/4" HHWS

3/4" HHWR

3/4" HHWR

1 1/4" HHWS

1 1/4" HHWR

1" HHWR

1" HHWS3/4" HHWS

3/4" HHWR

3/4" HHWS

3/4" HHWR

3/4" HHWR

3/4" HHWS 2" HHWS

2" HHWR

1" HHWR

1" HHWS

3/4" HHWS

3/4" HHWR

2 1/2" HHWS

2 1/2" HHWR

1 1/4" HHWS

1 1/4" HHWR

1 1/2" HHWS

1 1/2" HHWR

3" HHWR

3" HHWS

1" HHWR

VESTIBULE

CORR

C301

PUBLIC WAITING

C101

TLT/ SHR

218.2

MECHANICAL

FAMILY WAITING

MAT / PLATFORM

ACCUPUNCTURE-1

341.1-1

SPIRITUAL COUNSELLING

BRAIN LAB

CORR-1

C306-1

COMM

CASE MGMT

PSYCHOLOGIST

ART AND CLAY THERAPY

STORAGE / KILN

338.1

COMM

ELEC

SPEECH THERAPY

VENDING ALCOVE

106.1

NICoE DIR.

112AV SUPPLY

HOUSE KEEPING

DAILY LIVING SKILLS

PAT TLT

NEUROPSYCH

PSYCH TECH

BREAK ALCOVE

106.2

STAFF TLT

CLASSROOM

CLASSROOM

103.1

CORR

C201

CHAPLIN

CASE MGMT

NEUROLOGIST

CHANGING / LOCKER (M)

SPEECH THERAPY

DIR. OF CLINICAL SERVICES

MUSIC THERAPY

CORR

C102

RESEARCH SHARED OFFICE

ACCUPUNCTURE-2

341.1-2

ACCUPUNCTURE

341.2

PT GYM-1

200-1

NP PSYCH

STAFF TLT

FEMALE TOILET

MALE TOILET

CORR

DAYROOM

STORAGE / ALCOVE

200.1

CORR

C200

SOIL UTIL

EQPT STOR

MULTI-STATION TREATMENT

RM

OT O/E

PT O/E

PT O/E

OT O/E

RECEPTION

PATIENT INTAKE CUBICLES

300.1

CORR-2

C306-2

MAIN CORRIDOR / LOBBY-1

C100-1

CASE MGMT

CHECK-IN KIOSK

300.2

CLINICAL PHARMACIST

PC MD

BH / SW PROVIDERS

TRANS-CRANIAL MAGNETIC

STIM

ELEC

GROUP THERAPY

CORR-3

C306-3

CORR

C303

GROUP THERAPY

335.1

PSYCH TECH

CORR-1

C302-1

CORR-2

C302-2

HOUSE KEEPING

SOIL UTIL

EXAM

TREATMENT IPMC

EXAM

TREATMENT IPMC

EYE LANE

CORR

C304

FLEX STORAGE

CLEAN UTIL

WORKSTATION PT

TEAM ROOM

EXAM

EXAM

EXAM

CORRIDOR

C305

EXAM

EXAM

EXAM

PAT TLT

CORRIDOR

C300

COPY

109.1

NCOIC / ADMIN

TRAZER / FATS

NEURO REHAB AREA

CENTRAL PARK

STAFF LOUNGE

PAIN MD

CHIRO TREATMENT

CHIRO TREATMENT

CORR-3

C302-3

MAIN CORRIDOR / LOBBY

C100

MAIN CORRIDOR / LOBBY-3

C100-3

PT GYM-2

200-2

BIO NEUROFEEDBACK

EQPT STOR

BH / SW PROVIDER

BH / SW PROVIDERS

ALCOVE / STORAGE

C303.1

EYE TESTING

GAIT OBS LANE

CHANGING / LOCKER (W)

TLT / SHR

219.1

TLT/ SHR

218.1

CORR

C202

Space

C203

1" HHWR

1" HHWS

1" HHWR

1" HHWS

1" HHWR

1" HHWR

EV-6

EV-5

CP-6

CP-5

M216

M216

VAV-58

1" HHWS

1" HHWR

3/4" HHWS

3/4" HHWR

1 1/4" HHWS

1 1/4" HHWR

3/4" HHWS

3/4" HHWS

1" HHWS

1" HHWR

E

F

4" CHWS/R PIPING

DOWN THRU SLAB

CH-1

4" CHWS/R PIPING

TO MECHANICAL

ROOM

M304

DRAWING NUMBER

PROJECT NUMBER

SCALE

DRAWING TITLE

KEYPLAN

SEALS AND SIGNATURES

ISSUED FOR REV DATE

PLAN

NORTH

Cagley & Associates

STRUCTURAL ENGINEERING

6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050

1700 NEW YORK AVE, NW

SUITE 100

WASHINGTON, DC 20006

202.842.2100 www.smithgroup.com

P lo t D at e:

EGLIN AIR FORCE BASE

BUILDING XX

ASH DR, EGLIN AIR FORCE BASE

FLORIDA

32542

IMEG Corporation

ELECTRONIC SECURITY / TELECOMMUNICATIONS

2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906

Baskerville-Donovan, Inc.

CIVIL ENGINEERING

449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340

SmithGroup

MEP-FP ENGINEERING

1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100

1/8" = 1'-0"

/4

/2

:2

:2

A

M GROUND FLOOR

HVAC PIPING PLAN

M3.1

10822.000

SCALE: 1/8" = 1'-0"

GROUND FLOOR HVAC PIPING PLAN

SHEET NOTES

SCALE: 1/8" = 1'-0"

UTILITY YARD

1. PROVIDE MINIMUM 3/4" CONNECTION TO ALL VAV BOXES.

2. PROVIDE STATIC PRESSURE SENSORS ON CHW & HHW

PIPING SUCH THAT THE CONTROLLER SETPOINT IS NO

GREATER THAN ONE-THIRD THE TOTAL DESIGN PUMP STATIC

PRESSURE. IF THIS RESULTS IN THE SENSOR BEING LOCATED

DOWNSTREAM OF MAJOR PIPE SPLITS, MULTIPLE SENSORS

SHALL BE INSTALLED IN EACH MAJOR BRANCH TO ENSURE

THAT SUFFICIENT DIFFERENTIAL PRESSURE CAN BE

MAINTAINED IN EACH BRANCH.

3. IN ADDITION TO HANGERS AND SUPPORTS FOR DUCTWORK,

PIPING AND EQUIPMENT, PROVIDE SEISMIC RESTRAINTS IN

CONFORMANCE WITH ASCE/SEI 07 – 10. FOR ADDITIONAL

INFORMATION, SEE SPECIFICATIONS, STRUCTURAL

DRAWINGS AND CHAPTER 13 OF ASCE/SEI 07–10.

KEYED NOTES

M216 PROVIDE WALL MOUNTED DX FAN COIL

UNIT.CONNECT TO CORRESPONDING AIR

COOLED CONDENSING UNIT LOCATED ON

THE ROOF. PROVIDE A CONDENSATE PUMP

FOR EACH FAN COIL. RUN 1" CONDENSATE

LINE TO NEAREST JC AND SPILL OVER

SINK.

M219 INSTALL TW0-WAY CONTROL VALVE HERE.

SEE DETAIL ON M6 SERIES FOR MORE

INFORMATION.

M302 PROVIDE BLANK OFF PANELS AT EACH END

AND BETWEEN EACH SECTIONS OF THE

FIN TUBE RADIATORS. SEE DETAIL 2 ON

SHEET M6.3 FOR ADDITIONAL

INFORMATION.

M303 3/4" HHWS & HHWR DOWN TO FTR.

M304 PROVIDE HEAT TRACE ON ALL PIPING

ABOVE GRADE. MINIMUM POWER DENSITY

8W/LF. COORDINATE WITH ELECTRICAL.

SCHEMATIC DESIGN 8.17.2018

2 1

A.2

B

HWRP-1

UH-1

500 GAL. CHILLED

WATER BUFFER

TANK

AS-1

ET-2 ET-1

74"x30"

UH-2

S-1

66"x32"

M4.2

M4.2

M4.2

M4.2

M225

TYP. FOR 2

M207

M226

M226

B-1

B-2

PVC EXHAUST

UP THRU ROOF

M222M224

M223

M223

M224

54"X32" OUTSIDE AIR

DUCT UP TO ALP-1

66"X26" RELIEF AIR

DUCT UP TO ALP-2

CWP-2

CWP-1

HWP-2

HWP-1

AHU-1

AS-2

C

S-2

M224

M237

M237

M238

20x20 DUCT TO ALP-1

CONTROL PANELS

DWH-1

2 1

A.2

B

UH-2

UH-1

500 GAL. CHILLED

WATER BUFFER

TANK

ET-1ET-2

AHU-1

AS-2

AS-1

H H

W R

H H

W R

C H

W R

H H

W S

H H

W R

C H

W R

C H

W S

HWRP-1

M4.2

M4.2

4" CHWS/R

PIPING DOWN

THROUGH

SLAB TO CH-1

M4.2

M4.2

HWP-1

HWP-2

CWP-1

CWP-2

M226

M226

B-1

B-2

C H

W R

M220

M218

C

SEE M3.1 FOR

CONTINUATION

M218

2 1/2" HHWS

3" HHWR

M238

M240

M241

CONTROL PANELS

DRAWING NUMBER

PROJECT NUMBER

SCALE

DRAWING TITLE

KEYPLAN

SEALS AND SIGNATURES

ISSUED FOR REV DATE

PLAN

NORTH

Cagley & Associates

STRUCTURAL ENGINEERING

6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050

1700 NEW YORK AVE, NW

SUITE 100

WASHINGTON, DC 20006

202.842.2100 www.smithgroup.com

P lo t D at e:

EGLIN AIR FORCE BASE

BUILDING XX

ASH DR, EGLIN AIR FORCE BASE

FLORIDA

32542

IMEG Corporation

ELECTRONIC SECURITY / TELECOMMUNICATIONS

2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906

Baskerville-Donovan, Inc.

CIVIL ENGINEERING

449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340

SmithGroup

MEP-FP ENGINEERING

1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100

1/4" = 1'-0"

/4

/2

:2

:2

A

M MECHANICAL ROOM

ENLARGED PIPING

AND DUCT PLANS

M4.1

10822.000

SCALE: 1/4" = 1'-0"

MECHANICAL ROOM ENLARGED DUCT PLAN

SCALE: 1/4" = 1'-0"

MECHANICAL ROOM ENLARGED PIPING PLAN

SHEET NOTES

1. PROVIDE VOLUME DAMPERS ON ALL DUCT TAKEOFFS SERVING

SUPPLY, EXHAUST AND RETURN AIR TERMINALS. TYPICAL

THROUGHOUT.

2. PROVIDE REMOTE DAMPER OPERATORS FOR ALL AIR TERMINALS

LOCATED IN THE WOOD CEILING.

3. PROVIDE ALL RECTANGULAR MITERED ELBOWS WITH TURNING

VANES.

4. PROVIDE DUCT PRESSURE READING PORTS BEFORE AND AFTER

DUCT SILENCERS. TYPICAL FOR ALL DUCT SILENCERS.

5. PROVIDE DUCT DP SENSOR LOCATED IN COMPLIANCE WITH

ASHRAE 90.1. STATIC PRESSURE SENSORS SHALL BE PLACED IN

A POSITION SUCH THAT THE CONTROLLER SETPOINT IS NO

GREATER THAN ONE-THIRD THE TOTAL STATIC PRESSURE. IF

THIS RESULTS IN THE SENSOR BEING LOCATED DOWNSTREAM

OF MAJOR DUCT SPLITS, MULTIPLE SENSORS SHALL BE

INSTALLED IN EACH MAJOR BRANCH TO ENSURE THAT STATIC

PRESSURE CAN BE MAINTAINED IN EACH.

6. IN ADDITION TO HANGERS AND SUPPORTS FOR DUCTWORK,

PIPING AND EQUIPMENT, PROVIDE SEISMIC RESTRAINTS IN

CONFORMANCE WITH ASCE/SEI 07 – 10. FOR ADDITIONAL

INFORMATION, SEE SPECIFICATIONS, STRUCTURAL DRAWINGS

AND CHAPTER 13 OF ASCE/SEI 07–10.

KEYED NOTES

M207 18"X18" EXHAUST DUCT UP TO EF-3 ON

ROOF.

M218 PROVIDE DP SENSOR. SEE CONTROLS

DRAWINGS.

M220 PROVIDE TWO-WAY BYPASS CONTROL

VALVE.

M222 PROVIDE PVC INTAKE FOR DOMESTIC

WATER HEATER. RUN DUCT UP THRU ROOF

AND TERMINATE WITH GOOSENECK.

M223 PROVIDE PVC AIR INTAKE FOR BOILER.

INTAKE TO BE SIZED BY BOILER

MANUFACTURER. RUN DUCT UP THRU

ROOF AND TERMINATE WITH GOOSENECK.

M224 INSULATE OUTSIDE AIR INTAKE, LOCATED

INSIDE THE MECHANICAL ROOM, WITH 2"

INSULATION. PROVIDE ALUMINUM JACKET.

M225 CHEMICAL SHOT FEEDER.

M226 PROVIDE EMERGENCY SHUTOFF SWITCH

FOR BOILERS. INSTALL 48" ABOVE

FINISHED FLOOR. SEE SHEET M8.4 FOR

MORE INFORMATION.

M237 PROVIDE STAINLESS STEEL BOILER

EXHAUST SIZED BY BOILER

MANUFACTURER. PVC BOILER EXHAUST IS

ACCEPTABLE IF ALLOWED BY THE BOILER

MANUFACTURER.

M238 BOILER COOLDOWN. SEE DETAIL FOR

MORE INFORMATION.

M240 COORDINATE PIPING LOCATION WITH

ELECTRICAL CONTRACTOR. TYPICAL

THROUGHOUT.

M241 COORDINATE THE DEPTH OF THE

CONDENSATE TRAP WITH THE

STRUCTURAL CONTRACTOR.

SEE M2.3 FOR

CONTINUATION.

SEE M2.3 FOR

CONTINUATION.

2-1/2" HHWS & HHWR TO BUILDING.

SEE M3.1 FOR CONTINUATION.

A.2 A.9A.7 B

ALP-2 ALP-1

UH-1 UH-2

HWRP-1

30"x54"

PROVIDE MOTORIZED

DAMPER

AHU-1

EMERGENCY

SHUTOFF

SWITCH

B2 C

M401

M402

66"x32"

74"x30"

32"x54"

A.2A.9 A.7B

ALP-3

30"x74"

66"x32"

DWH-1 B-2 B-1 HWP-1 HWP-2 CWP-1 CWP-2 ET-1

EF-4

AS-1

4" CHWS/R TO CHILLER

AS-2 ETP-1

CHEMICAL

SHOT FEEDER

500 GAL. CHILLED

WATER BUFFER

TANK

B2C

2 1

HWRP-1

B-1

74"x30"

EMERGENCY

SHUTOFF SWITCH AS-2

ALP-2

AHU-1

54"x30"

PROVIDE STAINLESS STEEL BOILER EXHAUST.

PVC BOILER EXHAUST IS ACCEPTABLE IF IT IS

ALLOWED BY THE BOILER MANUFACTURER.

EXHAUST TO BE SIZED BY BOILER

MANUFACTURER.

TERMINATE MINIMUM 6'-0" ABOVE ROOF LEVEL.

PROVIDE MINIMUM 3 GUY WIRES.

PROVDE RAIN CAP.

PVC BOILER OUTSIDE AIR INTAKE. INTAKE TO BE SIZED BY BOILER MANUFACTURER.

TERMINATE MINIMUM 3'-0" ABOVE ROOF LEVEL.

PROVIDE HORIZONTAL TERMINATION WITH BIRDSCREEN.

32"x66"

2 1

ALP-1

30"x74"

DWH-1

AHU-1

PVC DWH EXHAUST.

TERMINATE MINIMUM 6'-0" ABOVE ROOF LEVEL.

PROVIDE MINIMUM 3 GUY WIRES.

PROVIDE RAIN CAP.

PVC DWH OUTSIDE AIR INTAKE.

TERMINATE MINIMUM 3'-0" ABOVE ROOF LEVEL.

PROVIDE HORIZONTAL TERMINATION WITH BIRDSCREEN.

54"x32"

DRAWING NUMBER

PROJECT NUMBER

SCALE

DRAWING TITLE

KEYPLAN

SEALS AND SIGNATURES

ISSUED FOR REV DATE

PLAN

NORTH

Cagley & Associates

STRUCTURAL ENGINEERING

6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050

1700 NEW YORK AVE, NW

SUITE 100

WASHINGTON, DC 20006

202.842.2100 www.smithgroup.com

P lo t D at e:

EGLIN AIR FORCE BASE

BUILDING XX

ASH DR, EGLIN AIR FORCE BASE

FLORIDA

32542

IMEG Corporation

ELECTRONIC SECURITY / TELECOMMUNICATIONS

2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906

Baskerville-Donovan, Inc.

CIVIL ENGINEERING

449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340

SmithGroup

MEP-FP ENGINEERING

1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100

1/4" = 1'-0"

/4

/2

:2

:2

A

M MECHANICAL ROOM

SECTIONS

M4.2

10822.000

SCALE: 1/4" = 1'-0"

MECHANICAL ROOM SECTION 1

SCALE: 1/4" = 1'-0"

MECHANICAL ROOM SECTION 2

SCALE: 1/4" = 1'-0"

MECHANICAL ROOM SECTION 3

SCALE: 1/4" = 1'-0"

MECHANICAL ROOM SECTION 4

SHEET NOTES

M401 DUCT SIZE 12X54 FOR MINIMUM OUTSIDE

AIR INTAKE. PROVIDE CONTROL DAMPER.

M402 DUCT SIZE 20X54 FOR OUTSIDE AIR

INTAKE DURING ECONOMIZER MODE.

PROVIDE CONTROL DAMPER.

KEYED NOTES

M401 DUCT SIZE 12X54 FOR MINIMUM OUTSIDE

AIR INTAKE. PROVIDE CONTROL DAMPER.

M402 DUCT SIZE 20X54 FOR OUTSIDE AIR

INTAKE DURING ECONOMIZER MODE.

PROVIDE CONTROL DAMPER.

VFD

HWP-1

HWP-2 (STBY)

B-1

AS-1

ET-1

HHWR

H H

W S

H H

W S

H H

W R

FLOW METER

TYPICAL

2-WAY CONTROL VALVE

TYPICAL

TEMPERATURE SENSOR

(TYPICAL)

M

M

T

T

T

T

T

T

VFD

PROVIDE CONDENSATE

DRAIN KIT ASSEMBLY

PROVIDE PH NEUTRALIZING KIT

WITHOUT PUMP

SPILL OVER NEAREST

FLOOR DRAIN

BOILER RELIEF

VALVE

BOILER RELIEF

VALVE

BOILER RELIEF COOLDOWN MODULE

BASIS OF DESIGN: CEMLINE

SPILL OVER NEAREST

FLOOR DRAIN

1" CONDENSATE

1" CONDENSATE

1-1/4" BOILER RELIEF

1-1/4" BOILER RELIEF

3" 3"

3"

3"

3"

AHU-1

HEATING COIL

HEATING COIL

HWRP-1

MECHANICAL ROOM

HHWS HHWS HHWS

HHWR HHWR HHWR

M

3" 3"

3"

3"

3"3"

3"

3"

TEST PORT

(TYPICAL)

FLEXIBLE

CONNECTION (TYP.)

FM

FM

1 1/2"

M501

M502

M502

B-2

1 1/2"

M503

UH-1

UH-2

CWP-1

CWP-2 (STBY)

AS-2

ET-2

TEMPERATURE SENSOR

(TYPICAL)

T

T

VFD

CH-1

BUFFER

TANK

500 GAL

VFD

FS

T

T

MECHANICAL ROOMUTILITY ENCLOSURE UNDERGROUND

4"

4"

4"

4"

4"

AHU-1

COOLING COIL

COOLING COIL

4"

4"

4" 4"

CHWS

C H

W S

C H

W R

C H

W R

DP

FLOW METER

FLEXIBLE

CONNECTION (TYP.)

STRAINER

M

FM

4"

M501

M504

EMERGENCY

CONNECTION

DRAWING NUMBER

PROJECT NUMBER

SCALE

DRAWING TITLE

KEYPLAN

SEALS AND SIGNATURES

ISSUED FOR REV DATE

Cagley & Associates

STRUCTURAL ENGINEERING

6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050

1700 NEW YORK AVE, NW

SUITE 100

WASHINGTON, DC 20006

202.842.2100 www.smithgroup.com

P lo t D at e:

EGLIN AIR FORCE BASE

BUILDING XX

ASH DR, EGLIN AIR FORCE BASE

FLORIDA

32542

IMEG Corporation

ELECTRONIC SECURITY / TELECOMMUNICATIONS

2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906

Baskerville-Donovan, Inc.

CIVIL ENGINEERING

449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340

SmithGroup

MEP-FP ENGINEERING

1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100

NONE

/4

/2

:2

:2

A

M HOT WATER AND

CHILLED WATER

PIPING DIAGRAM

M5.1

10822.000

SCALE: NONE

HOT WATER SYSTEM DIAGRAM

SHEET NOTES

1. PROVIDE ONE CHEMICAL SHOT FEEDER FOR THE CHILLED

WATER SYSTEM AND ONE CHEMICAL SHOT FEEDER FOR THE

HOT WATER SYSTEM.

SCALE: NONE

CHILLED WATER SYSTEM PIPING DIAGRAM

KEYED NOTES

M501 PROVIDE HIGH PERFORMANCE

SEGMENTED BALL VALVE WITH A TURN

DOWN RATIO OF 300:1 FOR FLOW BYPASS.

BASIS OF DESIGN VSI, SERIES V.

BUTTERFLY VALVES ARE NOT ACCEPTABLE

FOR FLOW BYPASS.

M502 INSTALL BOILERS ON SPRING TYPE

VIBRATION ISOLATOR.

M503 SELECT VALVE FOR A 5PSI DROP AT

20GPM.

M504 SELECT VALVE FOR 5PSI DROP AT MINIMUM

CHILLER FLOW AS REQUIRED BY

MANUFACTURER.

M

RETURN WATER

MANUAL

AIR

VENT

UNION

(TYPICAL)

PRESSURE

GAUGE

(TYPICAL)

THERMOMETER

(TYPICAL)

2 WAY CONTROL VALVE

SUPPLY WATER

AUTOMATIC FLOW

CONTROL VALVE OR

CIRCUIT SETTER

ISOLATION

VALVE

ISOLATION

VALVECOOLING

COIL STRAINER3/4" DRAIN VALVE

W/ HOSE END

CONNECTION

TEST PORT

(TYPICAL)

M

BYPASS. SEE M5.1

FOR MORE

INFORMATION.

M

RETURN WATER

MANUA

L

AIR

VENT

UNION

(TYPICAL)

PRESSURE

GAUGE

(TYPICAL)

THERMOMETER

(TYPICAL)

2 WAY

CONTROL

VALVE

SUPPLY WATER

AUTOMATIC

FLOW

CONTROL

VALVE

ISOLATION

VALVE

ISOLATION

VALVE

STRAINER3/4" DRAIN VALVE

W/ HOSE END

CONNECTION

FREEZ

E

PUMP

HEATING

COIL

TEST PORT

(TYPICAL)

M

RETURN WATER

MANUAL

AIR VENT

UNION

(TYPICAL)

PRESSURE

GAUGE

(TYPICAL)

THERMOMETER

(TYPICAL)

3 WAY

CONTROL

VALVE

SUPPLY WATER

AUTOMATIC

FLOW

CONTROL

VALVE

ISOLATION

VALVE

ISOLATION

VALVE

STRAINER3/4" DRAIN VALVE

W/ HOSE END

CONNECTION

HEATING

COIL

TEST PORT

(TYPICAL)

NOTES:

1. SEE SCHEDULES FOR VAV BOXES THAT WILL BE PROVIDED WITH 3-WAY CONTROL VALVES.

M

RETURN WATER

MANUAL

AIR VENT

UNION

(TYPICAL)

PRESSURE

GAUGE

(TYPICAL)

THERMOMETER

(TYPICAL)

2 WAY

CONTROL

VALVE

SUPPLY WATER

AUTOMATIC

FLOW

CONTROL

VALVE

ISOLATION

VALVE

ISOLATION

VALVEHEATING

COIL STRAINER3/4" DRAIN VALVE

W/ HOSE END

CONNECTION

TEST PORT

(TYPICAL)

FS

STRAINER

TEST PLUG (TYP.)

EVAPORATOR

TEST PLUG (TYP.)

ISOLATION VALVES

TEST PLUG (TYP.)

MANUAL AIR VENT

THERMOMETER (TYP.)

NOTE:

FLOW SWITCH

DRAIN VALVES WITH

HOSE END CONNECTIONS

FLEXIBLE

CONNECTION

(TYPICAL)

1. IN AREAS SUBJECT TO FREEZING CONDITIONS, ALL

VALVES, PIPING, STRAINERS, FLOW SWITCHES, FLEXIBLE

CONNECTIONS, ETC.

OUTSIDE OF BUILDING SHALL BE WRAPPED BY

ELECTRIC HEAT TRACE UNDER INSULATION

BALANCING

VALVE

PRESSURE GAUGE

(TYP.)

TO DRAIN

TO DRAIN

ISOLATION VALVES (TYP)

QUICK FILL BYPASS

VERTICAL EXPANSION TANK

LINE SIZE AIR SEPARATOR

THREADED HOSE CONNECTION

3/4"

HIGH CAPACITY AUTOMATIC AIR VENT

PIPE TO DRAIN

PIPE TO DRAIN

12" MIN.

PRESS. REG. VALVE

PRESSURE GAGE

NORMALLY OPEN ISOLATION VALVE

(REMOVE HANDLE)

EQUIVALENT LINE SIZE PER DWGS.

1" PIPE SIZE MINIMUM-INSTALL TEE

IN VERTICAL.

EQUIVALENT LINE SIZE PER

DRAWINGS- 1" PIPE SIZE MINIMUM

CW MAKE-UP FROM

WATER MAKE-UP UNIT

SIDE OF MAIN CONNECTION

ONLY. (TOP & BOTTOM

CONNECTION NOT ALLOWED.)

TO PUMP SUCTION

HIGH CAPACITY

AUTOMATIC AIR VENT

LINE SIZED TO FULL

TANK CONNECTION

SIZE

LINE SIZED TO FULL

TANK CONNECTION

SIZE

PRESSURE GAGE &

GAGE COCK

CAPPED SIDE TEE CONNECTION FOR MULTIPLE

TANKS WHERE MULTIPLE EXPANSION TANKS ARE

REQUIRED. CONNECT TO SIDE TEE AT THIS POINT -

CONNECTION LINE SIZE TO BE FULL TANK

CONNECTION SIZE.

PRE CHARGE AIR

CONNECTION. TANK

CONNECTION LOCATIONS AND

ARRANGEMENT MAY VARY BY

MANUFACTURER.

FROM SYSTEM

STRAINER

ISOLATION VALVE

UNION

CHECK VALVE

(CABINET UNIT HEATERS SIMILAR)

UNION (TYPICAL) HHWS

HHWR

1/2" ALL THREAD

TO STRUCTURE

2-WAY CONTROL

VALVE

STAINER

3/4" DRAIN VALVE W/

HOSE END CONNECTION

VIBRATION

ISOLATOR

AUTOMATIC FLOW

CONTROL VALVE

M

ISOLATION VALVE

ISOLATION VALVEBALL VALVE

MANUAL

AIR VENT

UNIT

HEATER

TEST PORT

(TYPICAL)

ISOLATION VALVE

ISOLATION VALVE

FLOW METER

THROTTLING VALVE

SEE SPECS

2.

1.

NOTES:

STRAINER

1/4" BALL VALVE (TYP.)

CHECK VALVE

PRESSURE GAGE

UNION OR FLANGE

TYPE CONNECTION

IN-LINE PUMP

AND MOTOR

PROVIDE INCREASERS AS

REQUIRED-REFER TO

PROJECT PLANS FOR PIPE

SIZE REQUIREMENTS

SUPPORT PUMP AND PIPING FROM SUITABLE VIBRATION ISOLATION

SUPPORTS. REFER TO SPECIFICATIONS.

PIPING SHALL BE INSTALLED SUCH THAT PUMP MAY BE COMPLETELY REMOVED

WITHOUTDISMANTLING PIPE OR FITTINGS, AND WITHOUT FORCING OR SPRINGING THE

PIPING.

DRAWING NUMBER

PROJECT NUMBER

SCALE

DRAWING TITLE

KEYPLAN

SEALS AND SIGNATURES

ISSUED FOR REV DATE

Cagley & Associates

STRUCTURAL ENGINEERING

6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050

1700 NEW YORK AVE, NW

SUITE 100

WASHINGTON, DC 20006

202.842.2100 www.smithgroup.com

P lo t D at e:

EGLIN AIR FORCE BASE

BUILDING XX

ASH DR, EGLIN AIR FORCE BASE

FLORIDA

32542

IMEG Corporation

ELECTRONIC SECURITY / TELECOMMUNICATIONS

2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906

Baskerville-Donovan, Inc.

CIVIL ENGINEERING

449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340

SmithGroup

MEP-FP ENGINEERING

1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100

NONE

/4

/2

:2

:2

A

M MECHANICAL

DETAILS - PIPING

M6.1

10822.000

SCALE: NONE

CHILLED WATER COIL 2-WAY CONTROL VALVE

SCALE: NONE

HOT WATER HEATING COIL 2-WAY CONTROL VALVE W/ FREEZE PUMP

SCALE: NONE

HOT WATER HEATING COIL 3-WAY CONTROL VALVE

SCALE: NONE

HOT WATER HEATING COIL 2-WAY CONTROL VALVE

SCALE: NONE

WATER PIPING CONNECTIONS TO AIR COOLED CHILLER

SCALE: NONE

DIAPHRAGM EXPANSION TANK AND AIR SEPARATOR - VERTICAL TANK

SCALE: NONE

HORIZONTAL HOT WATER UNIT HEATER

SCALE: NONE

IN-LINE PUMP

SCHEMATIC DESIGN 8.17.2018

VANE

VANE

NOTE:

1. THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.

R SHALL

EQUAL

OR BE

GREATER

THAN W.

R SHALL

EQUAL

OR BE

GREATER

THAN

1/3W.

R SHALL

EQUAL

OR BE

GREATER

THAN

1/6W.

STANDARD RADIUS OR

LONG RADIUS ELBOW

SHORT RADIUS ELBOW

WITH ONE VANE

SHORT RADIUS ELBOW

WITH TWO VANES

W

R

R

2/3W

1/ 3W

W W

1/2W

1/ 3W

1/6W

R

NOTE:

1.

2.

3.

4.

ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.

WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE

REGARDLESS OF W DIMENSION.

ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] MAXIMUM

SPACE BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.

WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL BE DOUBLE

VANE TYPE.

W

W1

FLEXIBLE DUCT SIZE

SAME AS DIFFUSER

INLET. 5'-0" MAX LENGTH

12"

CEILING

SUPPORT SADDLE

FROM STRUCTURE

VOLUME DAMPER

W/ LOCKING

QUAD

SHEET METAL

SADDLE

CONICAL OUTLET

BRANCH DUCT

USE RIGID ELBOWS FOR

CHANGE OF DIRECTION

GREATER THAN 45°.

SEE SPECIFICATIONS FOR

CLAMPS

AND SEALANT (TYP.)

TYPICAL

DIFFUSER OR

REGISTER IN

LAY-IN CLG.

THERMAL

INSULATION

SEE SPECIFICATIONS

NOTES:

1. PROVIDE PREFABRICATED ROOF CURB WITH TIE DOWN POINTS. SECURE

ROOF CURB WITH RUST RESISTANT BOLTS.

2. SECURE TO CURB WITH MINIMUM 3/8" CADMIUM PLATED SELF-TAPPING

SCREWS NOT OVER 12" ON CENTER.

3. PROVIDE ROOF OPENING TO ALLOW FOR THE INSTALLATION OF THE

RELIEF AIR DUCT ONLY.

4. PROVIDE ALUMINUM CURB WITH 2" INSULATION.

5. PROVIDE ALUMINUM PENTHOUSE WITH 1" INSULATION.

6. PROVIDE MINIMUM 3/8" DIA. BOLTS 3" FROM CORNERS AND 12" MAX C-C.

7. PROVIDE 4" RIGID INSULATION AROUND THE DUCT OPENING AND

THROUGHOUT THE INTERIOR OF THE CURB.

8. PROVIDE ADDITIONAL VERTICAL SUPPORTS 24" MAX C-C.

PROVIDE CURB WITH EXTENDED SILL BASE TO ACCOMMODATE THE

INSTALLATION OF THE VERTICAL SUPPORTS.

STEEL DECK

SEE NOTE 2

ARCHITECTURAL LOUVERED

PENTHOUSE

SEE NOTE 3

SEE NOTE 6

INSULATION

PROVIDE STEEL ANGLES

ON ALL FOUR SIDES OF THE CURB

SEE STRUCTURAL DRAWINGS

RELIEF DUCT ENDS HERE

PROVIDE STEEL ANGLES

ON ALL FOUR SIDES OF

THE ROOF OPENING

SEE STRUCTURAL DRAWINGS

RELIEF AIR

DUCT

SEE NOTE 7

SEE NOTE 8

SEE NOTE 8

3' M

IN

NOTE:

1.

2.

DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.

DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR

MULTI-BLADE DAMPERS & ROUND DAMPERS.

INSULATION SEE

SPECIFICATION

DAMPER BLADE

1/8"

CLEARANCE

ALL AROUND

OUTSIDE END BEARING

INSIDE END BEARING

HANDLE WITH

LOCKING

QUADRANT

INSULATION

STAND-OFF

1/2" ROUND ROD PIN

DUCT

STIFFEN BLADE

AS REQUIRED

SIDE ELEVATION SECTION

AIR SPLIT DUCT TAKE-OFF PLAN

VIEW

BRANCH DUCT TAKE-OFF PLAN VIEW

SUPPLY REGISTER

OR BRANCH DUCT

TURNING VANES

MAIN

SUPPLY

DUCT

SEE FLOOR PLAN FOR

SPLIT DIMENSION

PROVIDE

VOLUME

DAMPER

PROVIDE VOLUME

DAMPER

1/4 W OR 6"

MAIN SUPPLY

DUCT

W

AIR

FLOW

AIR

FLOW

A

IR

F

LO

W

A

IR

F

LO

W

AIR

FLOW

SEE CONTROLS AND

PIPING DETAIL

PROVIDE DUCT TRANSITION

AS REQUIRED TO MATCH

DUCT CONNECTIONS WITH

UNIT OUTLET DIMENSIONS

SAME DIAMETER AS BOX INLET

SCHEDULE FOR INLET SIZE)

(SEE VAV TERMINAL UNIT

2D MIN.

CONICAL BELLMOUTH FITTING,

VAV BOX

HEATING COIL

CLEARANCE

MIN. 36"

M A

IN

S

U P

P

LY

A

IR

D U

C T

D

VD VOLUME DAMPER

5D MAX.

HHWS AND HHWR

SEE NEW WORK

PIPING PLANS

SEE CONTROLS AND

PIPING DETAIL

PROVIDE DUCT TRANSITION

AS REQUIRED TO MATCH

DUCT CONNECTIONS WITH

UNIT OUTLET DIMENSIONS

1. 36" CLEARANCE REQUIRED FOR VAV BOXES WITH REHEAT.

NOTE:

2D MIN.

VAV BOX

HEATING COIL

CLEARANCE

MIN. 36"

M A

IN

S

U P

P

LY

A

IR

D U

C T

D

VD VOLUME DAMPER

5D MAX.

HHWS AND HHWR

SEE PIPING PLANS

SEE DUCT PLANS

FOR SIZES

THIS DUCT CONNECTION SHALL MATCH THE

INLET SIZE OF THE VAV BOX

DO NOT PROVIDE DUCT CONNECTION

SMALLER OR LARGER THAN THE NECK OF THE VAV BOX

NOTE:

1. DUCT CONNECTION TO THE VAV BOX SHALL BE THE

SAME SIZE AS THE NECK OF THE BOX. 2. DUCT CONNECTION TO VAV BOX SHALL BE SAME SIZE AS NECK OF THE BOX.

MAIN EXHAUST OR RETURN

PLAN VIEW

PROVIDE VOLUME DAMPER

AT EACH BRANCH DUCT

1/4W OR 4" MIN.

BRANCH DUCT

VD

W

AIR

FLOW AIR

FLOW

ROOF

CONDUIT

PREFABRICATED CURB

(SEE SPECIFICATIONS)

& TYPICAL FAN CURB

DETAIL

PROVIDE 1/2" MESH

BIRDSCREEN AND

DISCONNECT SWITCH

SCREEN AREA SHALL

BE 125% OF DUCT AREA

OR ROOF OPENING

MOTORIZED DAMPER

INSTALL IN EXHAUST DUCTWORK BELOW

ROOF OR DUCT OPENING

VIBRATION

ISOLATOR

NOTES:

1. PROVIDE PREFABRICATED ROOF CURB WITH TIE DOWN POINTS. SECURE ROOF CURB WITH RUST RESISTANT BOLTS.

2. SECURE CURB…