This is a combined synopsis/solicitation for commercial items issued by the Department of the Army Corps of Engineers Engineering District Little Rock. It is seeking quotes for the Eglin NICoE Initial Outfitting Project, with a total set-aside for Service-Disabled Veteran-Owned Small Businesses. Quotes are due by January 8, 2020 at 1:00pm Central Time. A site visit is tentatively scheduled for December 4, 2019 at 9:00am Central Time at Eglin Air Force Base West Visitors Center. Interested contractors must RSVP for the site visit by November 29, 2019 at 11:00am Central Time and provide contact information for base access. More information regarding entrance onto the base will be provided once attendance is confirmed. The solicitation number is W9127S20Q6000 and will use FAR simplified acquisition procedures in conjunction with commercial items procedures.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REFERENCE SYMBOLS
MECHANICAL ABBREVIATIONS
A L
M
B
C N
OD
E
P
Q
R
S F
G
T H
U
V
W
I
K
AD ACCESS DOOR
ACFM ABSOLUTE CUBIC FEET PER MINUTE
AFF ABOVE FINISHED FLOOR
AFM AIR FLOW MEASURING DEVICE
AFMS AIR FLOW MOISTURIZING STATION
AHU AIR HANDLING UNIT
AMB AMBIENT
AP ACCESS PANEL
APPROX APPROXIMATE
ASR AUTOMATIC SPRINKLER RISER
LAT LEAVING AIR TEMPERATURE
LBS/HR POUNDS PER HOUR
LGT LENGTH
LP LOW POINT
LRA LOCKED ROTOR AMPERS
LVG LEAVING
LWT LEAVING WATER TEMPERATURE
BFP BACKFLOW PREVENTOR
BHP BRAKE HORSEPOWER
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BTU(H) BRITISH THERMAL UNIT (PER HOUR)
MAX MAXIMUM
MBH 1000 BTU/HR
MCC MOTOR CONTROL CENTER
MECH MECHANICAL
MER MECHANICAL EQUIPMENT ROOM
MIN MINIMUM
MISC MISCELLANEOUS
MTG MOUNTING
NC NOISE CRITERIA
N.C. NORMALLY CLOSED
NIC NOT IN CONTRACT
NO. NUMBER
N.O. NORMALLY OPEN
NOM NOMINAL
NPSH NET POSITIVE SUCTION HEAD
(NRL) NEW LOCATION OF RELOCATED
MATERIAL OR EQUIPMENT
NTS NOT TO SCALE
CAP. CAPACITY
CDSR CONDENSER
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CI CAST IRON
CO CLEAN OUT
COMP COMPRESSOR
COND CONDENSATE
CONT CONTINUATION
CW COLD WATER
DB DECIBELS
DBA DECIBELS (A-WEIGHTED SCALE)
DBT DRY BULB TEMPERATURE °F
DDC DIRECT DIGITAL DRIVE
DIA DIAMETER
DN DOWN
DP DIFFERENTIAL PRESSURE
DPT DEW POINT TEMPERATURE °F
DWG DRAWING
DX DIRECT EXPANSION
D&T DRIP & TRAP
OA OUTSIDE AIR
OAD OUTSIDE AIR DAMPER
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
OPR OPERATING
OV OUTLET VELOCITY
PD PRESSURE DROP (FEET OF WATER)
PRESS PRESSURE
PRV PRESSURE REGULATING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUAREINCH - GUAGE
QTY QUANTITY
RA RETURN/RELIEF AIR
RC ROOF CONDUCTOR
RD ROOF DRAIN
RH RELATIVE HUMIDITY
(RL) RELOCATED MATERIAL OR EQUIPMENT
RLA RUNNING LOAD AMPS
RPM REVOLUTIONS PER MINUTE
RET RETURN
RE REFERENCE
SA SUPPLY AIR
SA SHOCK ABSORBER
SA SOUND ATTENUATOR
SAN SANITARY WASTE
SCFM STANDARD CUBIC FEET PER MINUTE
SD SMOKE DETECTOR
SDP SMOKE DAMPER
SENS SENSIBLE
SF SQUARE FEET
SG SPECIFIC GRAVITY
SL SOUND LINING
SP STATIC PRESSURE (INCHES OF WATER)
SPD SPEED
SPL SOUND POWER LEVEL
SPS STATIC PRESSURE SENSOR
SS STAINLESS STEEL
STM STEAM
TAB TESTING, ADJUSTING AND BALANCING
TEMP TEMPERATURE
TP TOTAL PRESSURE; TRAP PRIMER
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
V VOLTS
VAC VACUUM
VEL VELOCITY
VFD VARIABLE FREQUENCY DRIVE
VTR VENT THRU ROOF
W WATTS
W/ WITH
W/O WITHOUT
WBT WET BULB TEMPERATURE
WDT WIDTH
WG WATER GUAGE
WH WALL HYDRANT
EA EACH; EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EER ENERGY EFFICIENCY RATIO
EFF EFFICIENCY
EGW ETHYLENE GLYCOL WATER SOLUTION
(% GLYCOL BY VOLUME)
EL ELEVATION
ENT ENTERING
EQ EQUIVALENT
ESP EXTERNAL STATIC PRESSURE
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
EXP EXPANSION
EXT EXTERNAL
(E) EXISTING
F FAHRENHEIT
FD FLOOR DRAIN
FDP FIRE DAMPER
FH FUME HOOD
FLA FULL LOAD AMPERS
FLEX FLEXIBLE CONNECTION
FLR FLOOR
FM FLOW METER
FPM FEET PER MINUTE
FS FLOW SWITCH
FSDP FIRE & SMOKE DAMPER
FT FEET or FOOT
GAL GALLONS
GPM GALLONS PER MINUTE
GR GRAINS
HB HOSE BIBB
HG MERCURY
HGT HEIGHT
HO HUB OUTLET
HP HORSE POWER
HR HOUR
HUM HUMIDIFIER
HZ HERTZ
ID INSIDE DIAMETER
IE INVERT ELEVATION
IFB INTEGRAL FACE AND BY-PASS
IN. INCHES
KW KILOWATTS
SEE MECHANICAL SYMBOLS, LEGENDS AND EQUIPMENT
SCHEDULES FOR ADDITIONAL ABBREVIATIONS. ALL
ABBREVIATIONS, SYMBOLS, AND LEGENDS SHOWN ON
THIS DRAWINGS ARE NOT NECESSARILY USED.
R
UNIT HEATER
OF AIR FLOW 45° OFFSETS
RETURN OR EXHAUST AIR FLOW
SUPPLY OR OUTSIDE AIR FLOW
SIDE WALL SUPPLY DIFFUSER
SIDE WALL RETURN or EXHAUST
GRILLE/REGISTER
PRESSURE REGULATING VALVE, FLANGED
HORIZONTAL FIRE DAMPER
REDUCER - ECCENTRIC
UP or DN
TEE OUTLET - UP
REDUCED PRESSURE BACKFLOW PREVENTOR
AIR VENT
DROP OR RISE
DIRECTION OF FLOW
DIRECTION OF PIPE PITCH
CONNECT OUT OF TOP
FLOW METER
ELBOW - TURNED UP OR RISER CONNECTION
PRESSURE GUAGE WITH COCK
QUICK COUPLING
ELBOW - TURNED DOWN
TEE OUTLET - DOWN
CAP OR PLUG
THERMOMETER
ALIGNMENT GUIDE
PIPE UNION
PIPE ANCHOR
FLOOR DRAIN (ROUND)
ROOF DRAIN (RD)
RUNNING TRAP
CLEANOUT IN FLOOR
REDUCER - CONCENTRIC
HOSE CONNECTION
WALL HYDRANT
STEAM TRAP
CLEANOUT
HOSE BIBB
FLOW INDICATING BALANCE VALVE
ORIFICE PLATE
FLEXIBLE CONNECTION
STRAINER
PRESSURE REDUCING VALVE
SAFETY RELIEF VALVE
VERTICAL DUCT DROP
VERTICAL DUCT RISE
DIRECTION OF FLOW
SMOKE DAMPER
VERTICAL FIRE DAMPER
MECHANICAL FLOOR PLAN SYMBOLS
BUTTERFLY VALVE (ISOLATION OR THROTTLING)
SELF ACTUATING TYPE DIFFERENTIAL PRESSURE
AUTOMATIC FLOW CONTROL VALVE
3-WAY ELECTRIC CONTROL VALVE
BALL VALVE (ISOLATION OR THROTTLING)
PLUG VALVE (ISOLATION OR THROTTLING)
AUTOMATIC DPCV
CONTROL VALVE (DPCV)
SOLENOID VALVE
2-WAY ELECTRIC CONTROL VALVE
3-WAY PNEUMATIC CONTROL VALVE
2-WAY PNEUMATIC CONTROL VALVE
ANGLE VALVE
CHECK VALVE
ISOLATION VALVE
THROTTLING VALVE
AUTOMATIC DAMPER (MOTORIZED)
VOLUME DAMPER (MANUAL)
ROOM THERMOSTAT
SMOKE DETECTOR
FLOW SWITCH
STATIC PRESSURE SENSOR
AIR SYSTEMS
SUPPLY
RETURN
T
PRESSURE REGULATING VALVE, THREADED
FLOOR DRAIN (RECTANGULAR)
SA
RA
TE
GE
SUPPLY AIR
RETURN AIR
GENERAL EXHAUST
TOILET EXHAUST
HVAC & PIPING LEGEND MECHANICAL GENERAL NOTES
(NOTES APPLY TO ALL MECHANICAL DRAWINGS.)
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
VAV BOX
VAV BOX
OUTSIDE AIR INTAKE
DUCT SYSTEM LOCATION PRESSURE
CLASSIFICATION
(INCH WATER
GAUGE)
REMARKS
FROM TO
FAN DISCHARGE
FAN INLETGRILLE/DIFFUSER
GENERAL EXHAUST
RETURN
SUPPLY
-4
MECHANICAL HVAC NOTES
THROUGH OUT -2
DIFFUSER
OWS OPERATOR WORK STATION
EXHAUST
HHWS HEATING HOT WATER SUPPLY
HHWR HEATING HOT WATER RETURN
CWS CONDENSER WATER SUPPLY
CWR CONDENSER WATER RETURN
HPR (PSIG)
LPR (PSIG)
PS
D
HPS (PSIG)
LPS (PSIG)
CS (PSIG)
PHWS
PHWR
RL
RS
CHWS
CHWR
RHG
CONDENSATE DRAIN
HIGH PRESSURE CONDENSATE RETURN
LOW PRESSURE CONDENSATE RETURN
LOW PRESSURE STEAM
CLEAN STEAM
PUMPED CONDENSATE
HIGH PRESSURE STEAM
PERIMETER HEATING WATER RETURN
PERIMETER HEATING WATER SUPPLY
CHILLED WATER SUPPLY
CHILLED WATER RETURN
REFRIGERANT HOT GAS
REFRIGERANT SUCTION
REFRIGERANT LIQUID
SD
FS
SP
SMOKE/FIRE COMBINATION DAMPER
INSTALL ALL WORK IN ACCORDANCE WITH ALL APPLICABLE UFC CRITERION AND THE FOLLOWING FLORIDA CODES: MECHANICAL CODE, PLUMBING CODE, ENERGY CODE, ELECTRIC CODE AND THE REGULATIONS OF ALL AUTHORITIES HAVING JURISDICTION.
TO OBTAIN ALL CONSTRUCTION INFORMATION, ALL SPECIFICATION AND DRAWINGS (E.G. ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL, ELECTRICAL, PLUMBING AND FIRE PROTECTION MUST BE USED.
BRING TO THE ATTENTION OF THE ARCHITECT/ENGINEER ANY INFORMATIONAL CONFLICTS WITHIN THE SPECIFICATIONS AND DRAWINGS. THE CONTRACTOR(S) SHALL NOT PROCEED WITH ANY WORK, EXCEPT AT ITS OWN RISK, UNTIL ALL CONFLICTS ARE RESOLVED AND THE CLARIFYING INFORMATION IS ISSUED TO THE CONTRACTOR(S) BY THE ARCHITECT/ENGINEER.
COORDINATE DIFFUSER & REGISTER LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS.
COORDINATE ALL WALL MOUNTED DEVICES SUCH AS THERMOSTATS AND CONTROL PANELS WITH ARCHITECTURAL INTERIOR
ELEVATIONS.
ALL DIMENSIONS SHOWN FOR DUCTWORK ARE NET INSIDE DIMENSIONS.
FURNISH AND INSTALL ALL MANUALLY OPERATED VOLUME CONTROL (BALANCING) DAMPERS NECESSARY TO PERFORM THE
BALANCING WORK.
THOUGH SOME OFFSETS & TRANSITIONS ARE SHOWN IN PIPING & SHEET METAL TO HELP INDICATE THE PHYSICAL RELATIONSHIP BETWEEN THEM, IT IS NOT THE INTENT OF THE DRAWINGS TO SHOW ALL PIPING & SHEET METAL OFFSETS & TRANSITIONS REQUIRED.
THE CONTRACTOR SHALL FULLY COORDINATE THE MECHANICAL WORK WITHIN ITSELF & WITH THE WORK OF ALL TRADES TO PROVIDE
COMPLETE & OPERABLE SYSTEMS WITHOUT INTERFERENCES.
DUCT CONSTRUCTION SHALL FOLLOW THE LATEST SMACNA STANDARDS FOR THE SPECIFIC PRESSURE CLASSIFICATIONS INDICATED
BELOW.
BUILDING IS TO BE FULLY SPRINKLERED; SPRINKLER LAYOUT SHALL CONFORM TO NFPA 13. REFLECTED CEILING PLANS SHOW SPRINKLER LAYOUT FOR SOME AREAS. REFER TO SPECIFICATIONS & ARCHITECTURAL DRAWINGS FOR ADDITIONAL LAYOUT
REQUIREMENTS.
PROVIDE DUCT PRESSURE CLASSIFICATIONS AS FOLLOWS:
-2
BCW BOOSTED COLD WATER
SUB-METER FOR COLD WATER, HOT WATER, GAS
HORIZONTAL SMOKE/FIRE COMBINATION DAMPER
TEST PORT
HB
ST
HC
S
M
M
M
AIR VENT WITH VALVE
RD
FD
FD
CO
CO
RISER DESIGNATION (TYPE AS INDICATED)
SECTION NUMBER
DETAIL NUMBER
DRAWING NUMBER WHERE DRAWN
DRAWING NUMBER WHERE DRAWN
E1-1.0
E1-1.0
KEY NOTE
1 DEMO KEY NOTE
GRILLE/DIFFUSER FAN INLET
THESE GENERAL NOTES APPLY TO ALL M SERIES DRAWINGS.
NOT ALL SYMBOLS, ABBREVIATIONS AND NOTES ON THIS SHEET MAY BE USED FOR THIS PROJECT.
PROVIDE OFFSETS AND TRANSITIONS IN DUCTWORK AND PIPING AS REQUIRED TO AVOID INTERFERENCE AT NO
ADDITIONAL COST TO THE OWNER.
VERIFY ALL EQUIPMENT CONNECTIONS WITH MANUFACTURER’S CERTIFIED DRAWINGS. FIELD VERIFY ALL DIMENSIONS BEFORE FABRICATION OF WORK. PROVIDE TRANSITIONS AND MAKE FINAL CONNECTIONS TO
EQUIPMENT, UNLESS OTHERWISE INDICATED.
COORDINATE EXACT LOCATION OF DIFFUSERS, GRILLES AND REGISTERS WITH THE ARCHITECTURAL DRAWINGS
BEFORE INSTALLATION. PROVIDE SYMMETRY WITH THE ROOM LIGHTING SYSTEMS.
VERIFY DIFFUSER, GRILLE AND REGISTER MOUNTING FRAME TYPES WITH THE CEILING TYPES. PROVIDE FRAME TYPE
THAT MATCHES MOUNTING CONFIGURATION.
INSTALL DUCTWORK AS CLOSE AS POSSIBLE TO UNDERSIDE OF BEAMS AND/OR JOISTS.
PROVIDE CONCRETE HOUSEKEEPING PADS FOR FLOOR MOUNTED EQUIPMENT. COORDINATE SIZES AND LOCATION
WITH ALL TRADES.
PROVIDE ACCESS DOORS AND/OR PANELS FOR DUCT MOUNTED FIRE, SMOKE, AND FIRE/SMOKE DAMPERS AND
SMOKE DETECTORS.
PROVIDE ACCESS DOORS AND/OR PANELS IN HARD CEILINGS AND WALLS TO PERMIT SERVICE TO DAMPERS, VALVES, AND CONCEALED EQUIPMENT.
DUCT CONSTRUCTION SHALL COMPLY WITH THE LATEST VERSION OF SMACNA CONSTRUCTION STANDARDS. ALL 90 DEGREE ELBOWS SHALL BE LONG RADIUS TYPE UNLESS SPACE IS LIMITED. SHORT RADIUS AND RECTANGULAR ELBOWS SHALL HAVE TURNING VANES. UNLESS OTHERWISE NOTED FOR BRANCH CONNECTIONS, PROVIDE CONICAL
TAPS FOR ROUND DUCTS AND 45 DEGREE TAPS FOR RECTANGULAR DUCTS.
PROVIDE FLEXIBLE CONNECTIONS BETWEEN DUCTWORK AND ALL FANS AND ALL AIR HANDLING EQUIPMENT.
PAINT FLAT BLACK THE INSIDE OF ALL DUCTWORK VISIBLE THROUGH DIFFUSERS, GRILLES AND REGISTERS.
PROVIDE OPEN END DUCTWORK (OED) WITH 2X2 MESH (1/2"X 1/2") ALUMINUM SCREEN WITH REMOVABLE FRAMES.
ALL DUCT WORK SIZES INDICATED ARE INSIDE CLEAR DIMENSIONS.
CONCENTRATE LOADS AT JOIST AND/OR BEAM LOCATIONS. WHERE CONCENTRATED LOADS DUE TO EQUIPMENT, RISERS, OR SPECIAL DUCT CONSTRUCTION OCCUR AT OTHER LOCATIONS, PROVIDE ADDITIONAL SUPPORT FRAMING
AND/OR ANGLE BRACING.
COORDINATE ALL DOOR UNDER CUTS INDICATED AND AS REQUIRED WHERE RETURN/TRANSFER OPENS ARE NOT
PROVIDED.
PROVIDE RUNOUT PIPING AS SCHEDULED OR AS OTHERWISE INDICATED.
FIRE SAFE PIPE AND DUCTWORK PENETRATIONS AT ALL FIRE RATED AND SMOKE RESISTIVE CONSTRUCTION.
COORDINATE WITH LIFE SAFETY PLANS FOR LOCATIONS. PENETRATION ASSEMBLY TO BE U.L. LISTED.
REFER TO ARCHITECTURAL GENERAL INFORMATION SHEETS FOR MOUNTING HEIGHTS OF DEVICES. WHERE THIS INFORMATION IS NOT PROVIDED, MOUNT ROOM THERMOSTATS AT 48 INCHES AFF AND OCCUPANCY SENSORS AT 84
INCHES AFF UNLESS OTHERWISE INDICATED.
INSTALL ALL EQUIPMENT LEVEL AND PLUMB. PROVIDE BLOCKING AND HARDWARE AS REQUIRED.
INSTALL ALL EQUIPMENT REQUIRING PERIODIC SERVICE NOT LESS THAN 10 FEET FROM ROOF EDGE OR OPENING, UNLESS PROTECTIVE RAILING OR PARAPET OF 42 INCHES AFF OR TIE-OFF POINT. HAS BEEN PROVIDED. VERIFY WITH
OTHER TRADES.
DUCT SYSTEMS SHALL BE BALANCED TO AIR FLOWS INDICATED ON DRAWINGS. FANS SHALL BE FIELD TESTED TO ENSURE COMPLIANCE WITH SCHEDULED FAN PERFORMANCE AND SCHEDULED AIR FLOW AT THE DESIGN STATIC
PRESSURES LISTED.
PROVIDE VOLUME DAMPERS AT ALL BRANCH DUCT TAKEOFFS, AT EACH AIR TERMINAL DEVICE AND WHERE
INDICATED.
WHERE SIZE OF MOTORIZED DAMPER EXCEEDS THE LIMITS OF A SINGLE OPERATOR, PROVIDE MULTIPLE OPERATORS
IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
O.
P.
Q.
R.
S.
T.
U.
V.
W.
X.
Y.
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
NONE
/4
/2
:2
:5
A
M MECHANICAL
ABBREVIATIONS AND
SYMBOLS
M0.1
10822.000
SCHEMATIC DESIGN 8.17.2018
DESIGN DEVELOPMENT 11.08.2018
CONTRACT DOCUMENTS 01.04.2019
CO2
CO2 CO2
CO2
CO2
CO2
CO2
CO2
CO2
CO2
CO2 CO2
CO2
CO2
CO2
T
T T
T
T T
T
T
T
T
TT
TT
T
T
TTT
T
T
T
T T T T
T
T
T
T
T
TT
T
T
T
T
T T
TT
T
T
T
T
T
T
T
T
T T
T
T
T
TT
T
T
T
T
T
T
T
T
T
8.38.6
7.1
6.9 6.5 6.2
5.4
5.2
4.8
4.5
3.6
2.8
2 1
0.2A
0.3A
0.4A
0.7A
0.9A A
A.2
A.9
A.7
B B
D D
D.7
E E
F F
0.5A
6.8 6.4
B2
C C
E.8
DPS
DPS
DPS
M235
M234
M236
M236
M236
DX-1
DX-2
DX-3
DX-4
DX-5/6
FCU-1
UH-1
VAV-1
VAV-2
VAV-3
VAV-4
VAV-5
VAV-6
VAV-7
VAV-8
VAV-9
VAV-10
VAV-11
VAV-12
VAV-13
VAV-14
VAV-15
VAV-16
VAV-17
VAV-18
VAV-19
VAV-20
VAV-21
VAV-22
VAV-23
VAV-24
VAV-25
VAV-26
VAV-27
VAV-28
VAV-29
VAV-30
VAV-31
VAV-32
VAV-33
VAV-34
VAV-35
VAV-36
VAV-37
VAV-38
VAV-39
VAV-40
VAV-41
VAV-42
VAV-43
VAV-44
VAV-45
VAV-46
VAV-47
VAV-48
VAV-49
VAV-50
VAV-51
VAV-52
VAV-53
VAV-54
VAV-55
VAV-56
VAV-57
VAV-58
Calculating...
VAV-1
FCU-1
DX-3
DX-4
UH-1
DX-2
DX-1
VAV-2
VAV-3
VAV-4
VAV-5
VAV-6
VAV-7 VAV-8 VAV-9
VAV-10
VAV-11
VAV-12
VAV-13
VAV-14
VAV-15
VAV-16
VAV-17
VAV-18
VAV-19
VAV-20
VAV-21
VAV-22
VAV-23
VAV-24
VAV-25 VAV-26 VAV-27
VAV-29
VAV-30
VAV-31
VAV-32
VAV-33
VAV-34
VAV-35
VAV-36
VAV-37
VAV-38
VAV-39
VAV-40
VAV-41
VAV-42
VAV-43
VAV-44
VAV-45
VAV-46
VAV-47
VAV-48
VAV-49
VAV-50
VAV-51
VAV-52
VAV-53
VAV-54
VAV-55
VAV-56
VAV-57
VAV-28
DX-5/6
VAV-58
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
PLAN
NORTH
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
1/8" = 1'-0"
/4
/2
:2
:5
A
M HVAC ZONE LEGEND
M2.1
10822.000
SHEET NOTES
M234 PROVIDE WALL MOUNTED CO2 SENSOR.
TYPICAL THROUGHOUT.
M235 PROVIDE WALL MOUNTED THERMOSTAT.
TYPICAL THROUGHOUT.
M236 PROVIDE DIFFERENTIAL PRESSURE
SENSORS. SEE CONTROL DRAWINGS FOR
ADDITIONAL INFORMATION.
KEYED NOTES
SCALE: 1/8" = 1'-0"
HVAC ZONE LEGEND
SCHEMATIC DESIGN 8.17.2018
T ectonic Cop yright 2007
SS
S
8.38.6
7.1
6.9 6.5 6.2
5.4
5.2
4.8
4.5
3.6
2.8
2 1
0.2A
0.3A
0.4A
0.7A
0.9A A
A.2
A.9
A.7
B
D
D.7
E
F
0.5A
100CFM
S4-1
100CFM
S4-1
100CFM
S4-1
100CFM
S4-1
200CFM
S2-7
175CFM
S2-1
200CFM
S2-1
150CFM
S2-1
100CFM
S1-1
100CFM
S1-1
150CFM
S1-1
150CFM
S1-1
150CFM
S2-2
200CFM
S2-2
150CFM
S2-2
175CFM
S2-1
100CFM
S2-1
150CFM
S2-1
150CFM
S2-2
150CFM
S2-2
150CFM
S2-2
M4.2
6.8 6.4
B2
C
E.8
M227
M231
200CFM
S2-7
200CFM
S2-7
225CFM
S1-3
225CFM
S1-3 450CFM
R1-5
200CFM
S1-2
200CFM
S1-2
400CFM
R1-4
250CFM
S1-3
250CFM
S1-3
250CFM
S1-3
250CFM
R1-3
250CFM
R1-3
250CFM
R1-3
200CFM
S1-2
200CFM
S1-2
200CFM
S1-2
200CFM
R1-2
200CFM
R1-2
200CFM
R1-2
250CFM
R1-3250CFM
S1-3
150CFM
R1-2
150CFM
S1-1 200CFM
S1-2
200CFM
R1-2
100CFM
S3-1
150CFM
R1-2
150CFM
S1-1
200CFM
R1-2
200CFM
S1-2
300CFM
S1-3
200CFM
S1-2
200CFM
S1-2
150CFM
E1-2
150CFM
S1-1
150CFM
R1-2
150CFM
S1-1
150CFM
S1-1
150CFM
R1-2
250CFM
S1-3
250CFM
S1-3
250CFM
R1-3
250CFM
R1-3
50CFM
S3-1
100CFM
S1-1
100CFM
S1-1
200CFM
S1-2
100CFM
R1-1
100CFM
S1-1
250CFM
R1-3
200CFM
R1-2150CFM
S1-1
200CFM
R1-2
200CFM
S1-2
150CFM
R1-2
150CFM
S1-1
150CFM
S1-1
150CFM
S1-1
150CFM
R1-2
150CFM
S1-1
150CFM
R1-2
150CFM
S1-1
150CFM
R1-2
150CFM
S1-1
150CFM
R1-2
100CFM
S1-1
50CFM
S3-1
200CFM
S1-2
150CFM
S1-1
150CFM
S1-1
150CFM
R1-2
200CFM
S1-2
100CFM
R1-1
150CFM
S1-1
150CFM
R1-2
150CFM
S1-1
150CFM
S1-1
300CFM
R1-3
100CFM
S1-1
100CFM
S1-1
100CFM
S1-1
100CFM
R1-1
100CFM
R1-1
100CFM
R1-1
100CFM
R1-1
100CFM
R1-1 100CFM
R1-1
100CFM
S1-1
100CFM
S1-1
100CFM
S1-1
200CFM
S1-2
200CFM
R1-2
200CFM
S1-2
200CFM
R1-2
200CFM
S1-2
200CFM
R1-2
200CFM
S1-2
200CFM
R1-2
100CFM
S1-1
100CFM
R1-1
150CFM
S1-1
150CFM
S1-1
150CFM
R1-2
150CFM
R1-2
150CFM
S1-1
150CFM
E1-2
150CFM
S1-1
150CFM
S1-1
300CFM
S2-4
150CFM
S2-4
300CFM
S2-4
200CFM
S2-4
200CFM
S2-4
100CFM
S2-4
950CFM
R3-1
1000CFM
R3-1 275CFM
S1-3
275CFM
S1-3
275CFM
S1-3
275CFM
S1-3
275CFM
S1-3
275CFM
S1-3
275CFM
S1-3
275CFM
S1-3
300CFM
S1-3
300CFM
S1-3
300CFM
S1-3
300CFM
S1-3
500CFM
R3-1
600CFM
R3-1
200CFM
S2-1
200CFM
S2-1
200CFM
S2-1
100CFM
S1-1
150CFM
S1-1
350CFM
R1-4
400CFM
R1-4
500CFM
R1-5
250CFM
S1-3
250CFM
S1-3
175CFM
R1-2
175CFM
S1-2
175CFM
S1-2
175CFM
R1-2
150CFM
R1-2
150CFM
S1-1 150CFM
R1-2
150CFM
S1-1
100CFM
S1-1
100CFM
R1-1
200CFM
R1-2
100CFM
S1-1
125CFM
S1-1
125CFM
S1-1
250CFM
R1-3
250CFM
S1-3
250CFM
R1-3
125CFM
S1-1
300CFM
R1-3
150CFM
S1-1
1500CFM
R3-2
1500CFM
R3-2
50CFM
S1-1
50CFM
S1-1
50CFM
S3-1100CFM
E1-1
200CFM
S1-2
100CFM
E1-1
100CFM
E1-1
100CFM
E1-1
100CFM
S3-1
200CFM
S1-2
100CFM
E1-1
200CFM
E1-2
100CFM
S1-1
150CFM
E1-2
100CFM
S3-1
350CFM
S1-4
200CFM
R1-2
150CFM
S1-1
300CFM
E1-3
300CFM
E1-3
100CFM
S1-1
100CFM
R1-1
150CFM
E1-2
200CFM
S1-2
200CFM
R1-2
100CFM
E1-1
100CFM
E1-1
100CFM
E1-1
50CFM
S3-1
300CFM
R1-3
100CFM
S1-1
100CFM
S2-5
150CFM
S1-1
100CFM
S2-5
100CFM
S2-6
100CFM
S2-6
200CFM
S2-1
200CFM
R3-3
125CFM
S1-1
100CFM
S1-1
150CFM
R1-2
150CFM
E1-2
150CFM
R1-2
500CFM
R1-5
50CFM
S3-1
50CFM
S3-1
50CFM
S3-1
100CFM
S1-1
100CFM
R1-1
200CFM
E1-2
150CFM
R1-2
100CFM
S2-5
M210
M210
M210
M210
M210
M210
150CFM
E1-3
VESTIBULE
CORR
C301
PUBLIC WAITING
C101
TLT/ SHR
218.2
MECHANICAL
FAMILY WAITING
MAT / PLATFORM
ACCUPUNCTURE-1
341.1-1
SPIRITUAL COUNSELLING
BRAIN LAB
CORR-1
C306-1
COMM
CASE MGMT
PSYCHOLOGIST
ART AND CLAY THERAPY
STORAGE / KILN
338.1
COMM
ELEC
SPEECH THERAPY
VENDING ALCOVE
106.1
NICoE DIR.
AV SUPPLY
HOUSE KEEPING
DAILY LIVING SKILLS
PAT TLT
NEUROPSYCH
333PSYCH TECH
BREAK ALCOVE
106.2
STAFF TLT
CLASSROOM
CLASSROOM
103.1
CORR
C201
CHAPLIN
CASE MGMT
NEUROLOGIST
CHANGING / LOCKER (M)
218 SPEECH THERAPY
DIR. OF CLINICAL SERVICES
MUSIC THERAPY
CORR
C102
RESEARCH SHARED OFFICE
ACCUPUNCTURE-2
341.1-2
ACCUPUNCTURE
341.2
PT GYM-1
200-1
NP PSYCH
STAFF TLT
FEMALE TOILET
MALE TOILET
CORR
DAYROOM
STORAGE / ALCOVE
200.1
CORR
C200
SOIL UTIL
EQPT STOR
MULTI-STATION TREATMENT
RM
OT O/E
PT O/E
PT O/E
OT O/E
RECEPTION
PATIENT INTAKE CUBICLES
300.1
CORR-2
C306-2
MAIN CORRIDOR / LOBBY-1
C100-1
CASE MGMT
CHECK-IN KIOSK
300.2
CLINICAL PHARMACIST
PC MD
BH / SW PROVIDERS
TRANS-CRANIAL MAGNETIC
STIM
ELEC
GROUP THERAPY
CORR-3
C306-3
CORR
C303
GROUP THERAPY
335.1
PSYCH TECH
CORR-1
C302-1
CORR-2
C302-2
HOUSE KEEPING
SOIL UTIL
EXAM
TREATMENT IPMC
EXAM
TREATMENT IPMC
EYE LANE
CORR
C304
FLEX STORAGE
CLEAN UTIL
WORKSTATION PT
TEAM ROOM
EXAM
EXAM
EXAM
CORRIDOR
C305
EXAM
EXAM
EXAM
PAT TLT
CORRIDOR
C300
NCOIC / ADMIN
TRAZER / FATS
NEURO REHAB AREA
CENTRAL PARK
STAFF LOUNGE
PAIN MD
CHIRO TREATMENT
CHIRO TREATMENT
CORR-3
C302-3
MAIN CORRIDOR / LOBBY
C100
MAIN CORRIDOR / LOBBY-3
C100-3
PT GYM-2
200-2
BIO NEUROFEEDBACK
EQPT STOR
BH / SW PROVIDER
BH / SW PROVIDERS
ALCOVE / STORAGE
C303.1
EYE TESTING
GAIT OBS LANE
CHANGING / LOCKER (W)
219TLT / SHR
219.1
TLT/ SHR
218.1
CORR
C202
700CFM
R3-1
100CFM
S2-6
100CFM
S2-6
100CFM
S2-5
100CFM
S2-6
100CFM
S2-6
M227
M227
M231
COPY
109.1
100CFM
S1-1
150CFM
S2-1
150CFM
S2-1
150CFM
R1-2
100CFM
S1-1
50CFM
S1-1
200CFM
S1-2
100CFM
S1-1
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
PLAN
NORTH
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
1/8" = 1'-0"
/4
/2
:2
:0
A
M GROUND FLOOR AIR
TERMINALS
M2.2
10822.000
SCALE: 1/8" = 1'-0"
GROUND FLOOR AIR TERMINALS
SHEET NOTES
M210 PROVIDE 4' PLENUM WITH 10" NECK .
BLANK OFF 1' ON EACH SIDE OF THE
LINEAR DIFFUSER.
M227 PROVIDE ONE (1) CONTINUOUS LINEAR
DIFFUSER WITH THREE (3) 4' PLENUMS.
BALANCE EACH PLENUM FOR CFM
SHOWN.
M231 PROVIDE ONE (1) CONTINUOUS LINEAR
DIFFUSER WITH TWO (2) 4' PLENUMS.
BALANCE EACH PLENUM FOR CFM
SHOWN.
KEYED NOTES
1. AIR TERMINALS LOCATED IN AREAS WITH A ACOUSTICAL
CEILING TILES SHALL BE COORDINATED WITH THE CEILING
GRID. SEE ARCHITECTURAL PLANS AND DETAILS.
2. AIR TERMINALS LOCATED IN HARD LID DRYWALL CEILINGS
SHALL BE INSTALLED SUCH THAT THE OPENING FOR THE
AIR TERMINAL IS THOUROUGHLY SEALED/MUDDED.
8.38.6
7.1
6.9 6.5 6.2
5.4
5.2
4.8
4.5
3.6
2.8
2 1
0.2A
0.3A
0.4A
0.7A
0.9A A
A.2
A.9
A.7
B B
D D
D.7
E E
F F
0.5A
FCU-1
"x
60"x18"
"x
EV-1
CP-1
EV-2
CP-2
CP-3 EV-3
EV-4 CP-4
"x
M4.1
"x
14"x8"
10"x8"
22"x8"
26"x8"
24"x12"
M4.2
M4.2
24"x14"
16"x8"
30"x8"
M4.2
M4.2
6.8 6.4
B2
C C
E.8
18"x18" 24"x18"
"x
20"x16"
"x
26"x14"
20"x12"20"x16"18"x14"
60"x18"
10"x10"
36"x20"42"x16"
"x
68"x26"
26"x14"
"x
20"x10"
8"x8"
8"x8" 12"x10"
26"x14"
12"x12"
"x
66"x26"
74"x30"
48"x8"
12"x10"
"x
64"x20"
M207
M208
M209
54"x22"
16"x8"
M211
M230
66"x32"
14"x10"
20"x10"
20"x14"
10"x10"
"x
12"x10" 18"x12" 24"x12" 30"x10" 30"x12"
14"x10"
16"x12" 24"x12" 30"x12"
14"x20"
"x
16"x14" 20"x16"
48"x8"
16"x12"
12"x10"
16"x8"
28"x16"
26"x8"26"x6"
12"x10"
8"ø8"x8"
10"x8"
"x
16"x10" 16"x10"
12"x10"
6"x6"
12"x8"
10"x8"
12"x10"
16"x12"10"x10" 10"x8"
"x
16"x8"
6"ø
12"x8"
10"x10"
8"x10"
10"x10"
8"x10"
10"x10"
8"x6" 12"x12"
16"x12"
8"x14"
8"x14"
8"x8"
8"x8"
10"x10"
12"x8"
12"x10"
10"ø
10"x10"
10"x8" 6"x8"
8"x8" 12"x8"
12"x8"
12"x10"
16"x10"
16"x10"
12"x8"
10"ø
8"x6"
8"x6"
50"x22"
12"x10"
10"x12"
12"x10"
14"x12"
18"x10"
"x
"x
28"x16"
18"x16"
"x
10"x8"
10"x8"
12"x8"
8"x8"
12"x12"
20"x10"
10"ø 10"x10"
18"x12"
10"x10"
66"x26"
8"x8"
10"x8"
12"x8"
14"x8" 20"x8" 10"x8"
10"ø
30"x10" 42"x16"
"x
16"x10"
16"x12"
14"x10" 14"x10"
"x
6"x8" 8"x6"
12"x8"
12"x10"
12"x8"
10"x8"
12"x8"
12"x10"
8"x12"
12"x10"
14"x12"
14"x10"
12"x8"
C301
C101
218.2
341.1-1
C306-1
338.1
106.1
106.2
103 103.1
C201
311 309
C102
341.1-2
341.2
200-1
200.1
C200
206205
300.1
C306-2
C100-1
300.2
305307
C306-3
C303
335.1
C302-1
C302-2
350 346
C304
345347348
C305
310 308 306
C300
109.1
C302-3
C100
C100-3
200-2
C303.1
219.1
218.1
C202
C203
"x
"x
12"x8"
8"x6"
22"x12"24"x16"
22"x14"
20"x20"
20"x20"
24"x8"
VAV-4
VAV-6
VAV-57
VAV-25
VAV-24
VAV-26
VAV-27
VAV-29
VAV-28
VAV-23
VAV-21 VAV-22VAV-20
VAV-18
VAV-31
VAV-17VAV-16
VAV-15
VAV-19
VAV-3
VAV-14
VAV-2
VAV-1
VAV-7
VAV-5
VAV-10
VAV-12 VAV-11
VAV-13
VAV-30
VAV-8
VAV-33
VAV-9
VAV-47
VAV-32 VAV-54 VAV-55
VAV-56
VAV-53
VAV-51
VAV-49 VAV-50
VAV-52
VAV-43
VAV-48
VAV-44
VAV-41
VAV-40
VAV-42
VAV-39
VAV-38VAV-37
VAV-36
VAV-35
VAV-34 VAV-46
VAV-45
64"x24"
10"x10"
EV-5 CP-5
EV-6
CP-6
12"x8"
12"x8"
VAV-58
8"ø
10"x8"
16"x10"
30"x10" 32"x12"
"x
VAV-45
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
PLAN
NORTH
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
1/8" = 1'-0"
/4
/2
:2
:0
A
M GROUND FLOOR
DUCT PLAN
M2.3
10822.000
SHEET NOTES
M207 18"X18" EXHAUST DUCT UP TO EF-3 ON ROOF.
M208 16"X16" EXHAUST DUCT UP TO EF-2 ON ROOF.
M209 16"X16" EXHAUST DUCT UP TO EF-1 ON ROOF.
M211 PROVIDE EMERGENCY SHUTOFF SWITCH FOR
ENTIRE HVAC SYSTEM. INSTALL 48" ABOVE
FINISHED FLOOR. SEE SHEET M8.8 FOR MORE
INFORMATION.
M230 PROVIDE OPEN END DUCT WITH VOLUME DAMPER
FOR RETURN FROM CENTRAL PARK.
SCALE: 1/8" = 1'-0"
GROUND FLOOR DUCT PLAN
KEYED NOTES
1. PROVIDE VOLUME DAMPERS ON ALL DUCT TAKEOFFS
SERVING SUPPLY, EXHAUST AND RETURN AIR TERMINALS.
TYPICAL THROUGHOUT.
2. PROVIDE REMOTE DAMPER OPERATORS FOR ALL AIR
TERMINALS LOCATED IN THE HARD LID AND WOOD CEILING.
3. PROVIDE ALL RECTANGULAR MITERED ELBOWS WITH
TURNING VANES.
4. PROVIDE DUCT PRESSURE READING PORTS BEFORE AND
AFTER DUCT SILENCERS. TYPICAL FOR ALL DUCT SILENCERS.
5. PROVIDE DUCT DP SENSOR LOCATED IN COMPLIANCE WITH
ASHRAE 90.1. STATIC PRESSURE SENSORS SHALL BE PLACED
IN A POSITION SUCH THAT THE CONTROLLER SETPOINT IS NO
GREATER THAN ONE-THIRD THE TOTAL STATIC PRESSURE. IF
THIS RESULTS IN THE SENSOR BEING LOCATED
DOWNSTREAM OF MAJOR DUCT SPLITS, MULTIPLE SENSORS
SHALL BE INSTALLED IN EACH MAJOR BRANCH TO ENSURE
THAT STATIC PRESSURE CAN BE MAINTAINED IN EACH.
6. IN ADDITION TO HANGERS AND SUPPORTS FOR DUCTWORK,
PIPING AND EQUIPMENT, PROVIDE SEISMIC RESTRAINTS IN
CONFORMANCE WITH ASCE/SEI 07 – 10. FOR ADDITIONAL
INFORMATION, SEE SPECIFICATIONS, STRUCTURAL
DRAWINGS AND CHAPTER 13 OF ASCE/SEI 07–10.
7. DO NOT PROVIDE VAV BOXES WITH AN 120V INTEGRAL
ELECTRICAL TRANSFORMER. COORDINATE WITH THE
ELECTRICAL TRADE.
Room Schedule Number Name
337 PSYCHOLOGIST
338 ART AND CLAY THERAPY
338.1 STORAGE / KILN
339 CASE MGMT
340 PAT TLT
341.1-1 ACCUPUNCTURE-1
341.1-2 ACCUPUNCTURE-2
341.2 ACCUPUNCTURE
342 BRAIN LAB
343 EYE LANE
344 TREATMENT IPMC
344 EYE TESTING
345 EXAM
346 TREATMENT IPMC
347 EXAM
348 EXAM
349 EXAM
350 EXAM
351 TRANS-CRANIAL MAGNETIC STIM
359 CORR
C100 MAIN CORRIDOR / LOBBY
C100-1 MAIN CORRIDOR / LOBBY-1
C100-3 MAIN CORRIDOR / LOBBY-3
C101 PUBLIC WAITING
C102 CORR
C200 CORR
C201 CORR
C202 CORR
C203 Space
C204 Space
C300 CORRIDOR
C301 CORR
C302-1 CORR-1
C302-2 CORR-2
C302-3 CORR-3
C303 CORR
C303.1 ALCOVE / STORAGE
C304 CORR
C305 CORRIDOR
C306-1 CORR-1
C306-2 CORR-2
C306-3 CORR-3
Room Schedule Number Name
219.1 TLT / SHR
220 MECHANICAL
300 RECEPTION
300.1 PATIENT INTAKE CUBICLES
300.2 CHECK-IN KIOSK
301 CHAPLIN
302 SPIRITUAL COUNSELLING
303 CASE MGMT
304 TEAM ROOM
305 CLINICAL PHARMACIST
306 EXAM
307 PC MD
308 EXAM
309 NEUROLOGIST
310 EXAM
311 CASE MGMT
312 MUSIC THERAPY
313 PAT TLT
314 STAFF LOUNGE
315 CLEAN UTIL
316 PAIN MD
317 FLEX STORAGE
318 STAFF TLT
319 CHIRO TREATMENT
320 HOUSE KEEPING
321 CHIRO TREATMENT
322 SOIL UTIL
323 BIO NEUROFEEDBACK
324 COMM
325 EQPT STOR
326 BH / SW PROVIDERS
327 BH / SW PROVIDERS
329 BH / SW PROVIDER
330 ELEC
331 PSYCH TECH
332 PSYCH TECH
333 NEUROPSYCH
334 STAFF TLT
335 GROUP THERAPY
335.1 GROUP THERAPY
336 NP PSYCH
Room Schedule Number Name
100 VESTIBULE
101 FAMILY WAITING
102 CENTRAL PARK
103 CLASSROOM
103.1 CLASSROOM
104 AV SUPPLY
105 DAYROOM
106.1 VENDING ALCOVE
106.2 BREAK ALCOVE
107 FEMALE TOILET
108 MALE TOILET
109 NCOIC / ADMIN
109.1 COPY
110 DIR. OF CLINICAL SERVICES
111 RESEARCH SHARED OFFICE
112 NICoE DIR.
113 HOUSE KEEPING
114 ELEC
200-1 PT GYM-1
200-2 PT GYM-2
200.1 STORAGE / ALCOVE
201 WORKSTATION PT
202 NEURO REHAB AREA
203 MAT / PLATFORM
204 GAIT OBS LANE
205 EQPT STOR
206 SOIL UTIL
207 PT O/E
208 PT O/E
209 TRAZER / FATS
210 SPEECH THERAPY
211 COMM
212 DAILY LIVING SKILLS
213 OT O/E
214 SPEECH THERAPY
215 OT O/E
217 MULTI-STATION TREATMENT RM
218 CHANGING / LOCKER (M)
218.1 TLT/ SHR
218.2 TLT/ SHR
219 CHANGING / LOCKER (W)
SCHEMATIC DESIGN 8.17.2018
7.1
6.9 6.5 6.2
5.4
5.2
4.8
4.5
3.6
2.8
2 1
0.2A
0.3A
0.4A
0.7A
0.9A A
A.2
A.9
A.7
B B
D D
D.7
E E
F F
0.5A
ALP-2
ALP-1
CU-3
CU-1 CU-2
EF-1
EF-4
EF-3
PROVIDE PVC BOILER INTAKE
AND STAINLESS STEEL
EXHAUST.
PROVIDE PVC BOILER INTAKE
AND STAINLESS STEEL
EXHAUST.
ARCHITECTURAL
LOUVERED
PENTHOUSE
ALP-3
CU-4
PROVIDE PVC INTAKE AND
EXHAUST FOR DWH-1.
AIR COOLED
CONDENSING UNIT FOR
DX COOLING FAN COILS
(TYP.)
6.8 6.4
B2
C C
E.8
EF-2
M221
M214
M214
M214
M214
M228
M228
M229
M229
M228
M239
M239
54"x30"
CU-6 CU-5
AIR COOLED
CONDENSING UNIT FOR
DX COOLING FAN COILS
(TYP.)
AIR COOLED
CONDENSING UNIT FOR
DX COOLING FAN COILS
(TYP.)
ROOF HATCH
54"x32"
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
PLAN
NORTH
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
1/8" = 1'-0"
/4
/2
:2
:1
A
M ROOF PLAN
M2.4
10822.000
SHEET NOTES
M214 PROVIDE EXHAUST FAN WITH MOTORIZED
CONTROL DAMPER THAT MEETS THE
LEAKAGE REQUIREMENTS OUTLINED IN
UFC 4-010-01, PARAGRAPH B-4.3.1
M221 PROVIDE 20"X20" DUCT FROM ALP-3 INTO
THE MECHANICAL ROOM. PROVIDE AND
INSTALL MOTORIZED CONTROL DAMPER
IN THE DUCTWORK. PROVIDE OPEN END
DUCT WITH MESH SCREEN INTO THE
MECHANICAL ROOM.
M228 PROVIDE AND INSTALL SEISMICALLY
RATED ARCHITECTURAL LOUVERED
PENTHOUSE; SEE STRUCTURAL
DRAWINGS, SPEC SECTION 233723 AND
SECTION 230548 FOR ADDITIONAL
INFORMATION.
M229 FOR ALL BOILER FLUE EXHAUST,
MAINTAIN A MINIMUM DISTANCE OF 15
FEET FROM ANY OUTSIDE AIR INTAKE
PER IMC.
M239 PROVIDE 3' ROOF CURB
SCALE: 1/8" = 1'-0"
ROOF PLAN
KEYED NOTES
1. IN ADDITION TO HANGERS AND SUPPORTS FOR DUCTWORK,
PIPING AND EQUIPMENT, PROVIDE SEISMIC RESTRAINTS IN
CONFORMANCE WITH ASCE/SEI 07 – 10. FOR ADDITIONAL
INFORMATION, SEE SPECIFICATIONS, STRUCTURAL DRAWINGS
AND CHAPTER 13 OF ASCE/SEI 07–10.
SCHEMATIC DESIGN 8.17.2018
7.1
6.9 6.5 6.2
5.4
5.2
4.8
4.5
3.6
2.8
2 1
0.2A
0.3A
0.4A
0.7A
0.9A A
A.2
A.9
A.7
B B
D D
D.7
E E
F F
0.5A
FCU-1
C H
W R
C H
W S
BELOW GRADE
BELOW
GRADE
4" CHWS/R PIPING TO CH-1 IN
CHILLER UTILITY
ENCLOSURE.
SEE BELOW.
4" CHWS/R PIPING DOWN
THROUGH SLAB TO CH-1
FTR-2B
FTR-2
FTR-1
FTR-1B
EV-2
EV-1
CP-1
CP-2
CP-3
CP-4
EV-4
EV-3
M4.1
M4.2
M4.2
1 1/4" HHWR
1 1/4" HHWS
1" HHWR
1" HHWS
1" HHWS
1" HHWR
/4
H H
W R
/4
H H
W S
1 1/4" HHWR
1 1/4" HHWS
3/4" HHWS
3/4" HHWR
3/4" HHWR
3/4" HHWS
1" HHWS
1" HHWR
M4.2
M4.2
6.8 6.4
B2
C C
E.8
3/4" HHWS
3/4" HHWS
3/4" HHWR
/4
H H
W R
/4
H H
W S
M302
M302
M302
M216
M216
M216
M216
M219
M303
M303
VAV-4
VAV-6
VAV-57
VAV-25
VAV-24 VAV-26
VAV-27
VAV-29
VAV-28 VAV-28
VAV-19
VAV-20 VAV-22 VAV-21 VAV-23
VAV-31
VAV-3
VAV-15
VAV-16 VAV-17
VAV-18
VAV-14
VAV-2
VAV-5
VAV-1
VAV-7
VAV-10
VAV-12 VAV-11
VAV-8
VAV-9
VAV-33
VAV-30
VAV-13
VAV-32
VAV-54 VAV-55
VAV-56
VAV-53
VAV-51
VAV-47
VAV-49
VAV-50
VAV-34
VAV-46
VAV-35
VAV-36
VAV-37
VAV-38 VAV-39
VAV-42
VAV-45
VAV-40
VAV-41
VAV-44
VAV-43
VAV-48
VAV-52
3/4" HHWS
3/4" HHWR
1" HHWR
1" HHWS
1 1/2" HHWR
1 1/2" HHWS
3/4" HHWS
3/4" HHWR
3/4" HHWR
1 1/4" HHWS
1 1/4" HHWR
1" HHWR
1" HHWS3/4" HHWS
3/4" HHWR
3/4" HHWS
3/4" HHWR
3/4" HHWR
3/4" HHWS 2" HHWS
2" HHWR
1" HHWR
1" HHWS
3/4" HHWS
3/4" HHWR
2 1/2" HHWS
2 1/2" HHWR
1 1/4" HHWS
1 1/4" HHWR
1 1/2" HHWS
1 1/2" HHWR
3" HHWR
3" HHWS
1" HHWR
VESTIBULE
CORR
C301
PUBLIC WAITING
C101
TLT/ SHR
218.2
MECHANICAL
FAMILY WAITING
MAT / PLATFORM
ACCUPUNCTURE-1
341.1-1
SPIRITUAL COUNSELLING
BRAIN LAB
CORR-1
C306-1
COMM
CASE MGMT
PSYCHOLOGIST
ART AND CLAY THERAPY
STORAGE / KILN
338.1
COMM
ELEC
SPEECH THERAPY
VENDING ALCOVE
106.1
NICoE DIR.
112AV SUPPLY
HOUSE KEEPING
DAILY LIVING SKILLS
PAT TLT
NEUROPSYCH
PSYCH TECH
BREAK ALCOVE
106.2
STAFF TLT
CLASSROOM
CLASSROOM
103.1
CORR
C201
CHAPLIN
CASE MGMT
NEUROLOGIST
CHANGING / LOCKER (M)
SPEECH THERAPY
DIR. OF CLINICAL SERVICES
MUSIC THERAPY
CORR
C102
RESEARCH SHARED OFFICE
ACCUPUNCTURE-2
341.1-2
ACCUPUNCTURE
341.2
PT GYM-1
200-1
NP PSYCH
STAFF TLT
FEMALE TOILET
MALE TOILET
CORR
DAYROOM
STORAGE / ALCOVE
200.1
CORR
C200
SOIL UTIL
EQPT STOR
MULTI-STATION TREATMENT
RM
OT O/E
PT O/E
PT O/E
OT O/E
RECEPTION
PATIENT INTAKE CUBICLES
300.1
CORR-2
C306-2
MAIN CORRIDOR / LOBBY-1
C100-1
CASE MGMT
CHECK-IN KIOSK
300.2
CLINICAL PHARMACIST
PC MD
BH / SW PROVIDERS
TRANS-CRANIAL MAGNETIC
STIM
ELEC
GROUP THERAPY
CORR-3
C306-3
CORR
C303
GROUP THERAPY
335.1
PSYCH TECH
CORR-1
C302-1
CORR-2
C302-2
HOUSE KEEPING
SOIL UTIL
EXAM
TREATMENT IPMC
EXAM
TREATMENT IPMC
EYE LANE
CORR
C304
FLEX STORAGE
CLEAN UTIL
WORKSTATION PT
TEAM ROOM
EXAM
EXAM
EXAM
CORRIDOR
C305
EXAM
EXAM
EXAM
PAT TLT
CORRIDOR
C300
COPY
109.1
NCOIC / ADMIN
TRAZER / FATS
NEURO REHAB AREA
CENTRAL PARK
STAFF LOUNGE
PAIN MD
CHIRO TREATMENT
CHIRO TREATMENT
CORR-3
C302-3
MAIN CORRIDOR / LOBBY
C100
MAIN CORRIDOR / LOBBY-3
C100-3
PT GYM-2
200-2
BIO NEUROFEEDBACK
EQPT STOR
BH / SW PROVIDER
BH / SW PROVIDERS
ALCOVE / STORAGE
C303.1
EYE TESTING
GAIT OBS LANE
CHANGING / LOCKER (W)
TLT / SHR
219.1
TLT/ SHR
218.1
CORR
C202
Space
C203
1" HHWR
1" HHWS
1" HHWR
1" HHWS
1" HHWR
1" HHWR
EV-6
EV-5
CP-6
CP-5
M216
M216
VAV-58
1" HHWS
1" HHWR
3/4" HHWS
3/4" HHWR
1 1/4" HHWS
1 1/4" HHWR
3/4" HHWS
3/4" HHWS
1" HHWS
1" HHWR
E
F
4" CHWS/R PIPING
DOWN THRU SLAB
CH-1
4" CHWS/R PIPING
TO MECHANICAL
ROOM
M304
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
PLAN
NORTH
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
1/8" = 1'-0"
/4
/2
:2
:2
A
M GROUND FLOOR
HVAC PIPING PLAN
M3.1
10822.000
SCALE: 1/8" = 1'-0"
GROUND FLOOR HVAC PIPING PLAN
SHEET NOTES
SCALE: 1/8" = 1'-0"
UTILITY YARD
1. PROVIDE MINIMUM 3/4" CONNECTION TO ALL VAV BOXES.
2. PROVIDE STATIC PRESSURE SENSORS ON CHW & HHW
PIPING SUCH THAT THE CONTROLLER SETPOINT IS NO
GREATER THAN ONE-THIRD THE TOTAL DESIGN PUMP STATIC
PRESSURE. IF THIS RESULTS IN THE SENSOR BEING LOCATED
DOWNSTREAM OF MAJOR PIPE SPLITS, MULTIPLE SENSORS
SHALL BE INSTALLED IN EACH MAJOR BRANCH TO ENSURE
THAT SUFFICIENT DIFFERENTIAL PRESSURE CAN BE
MAINTAINED IN EACH BRANCH.
3. IN ADDITION TO HANGERS AND SUPPORTS FOR DUCTWORK,
PIPING AND EQUIPMENT, PROVIDE SEISMIC RESTRAINTS IN
CONFORMANCE WITH ASCE/SEI 07 – 10. FOR ADDITIONAL
INFORMATION, SEE SPECIFICATIONS, STRUCTURAL
DRAWINGS AND CHAPTER 13 OF ASCE/SEI 07–10.
KEYED NOTES
M216 PROVIDE WALL MOUNTED DX FAN COIL
UNIT.CONNECT TO CORRESPONDING AIR
COOLED CONDENSING UNIT LOCATED ON
THE ROOF. PROVIDE A CONDENSATE PUMP
FOR EACH FAN COIL. RUN 1" CONDENSATE
LINE TO NEAREST JC AND SPILL OVER
SINK.
M219 INSTALL TW0-WAY CONTROL VALVE HERE.
SEE DETAIL ON M6 SERIES FOR MORE
INFORMATION.
M302 PROVIDE BLANK OFF PANELS AT EACH END
AND BETWEEN EACH SECTIONS OF THE
FIN TUBE RADIATORS. SEE DETAIL 2 ON
SHEET M6.3 FOR ADDITIONAL
INFORMATION.
M303 3/4" HHWS & HHWR DOWN TO FTR.
M304 PROVIDE HEAT TRACE ON ALL PIPING
ABOVE GRADE. MINIMUM POWER DENSITY
8W/LF. COORDINATE WITH ELECTRICAL.
SCHEMATIC DESIGN 8.17.2018
2 1
A.2
B
HWRP-1
UH-1
500 GAL. CHILLED
WATER BUFFER
TANK
AS-1
ET-2 ET-1
74"x30"
UH-2
S-1
66"x32"
M4.2
M4.2
M4.2
M4.2
M225
TYP. FOR 2
M207
M226
M226
B-1
B-2
PVC EXHAUST
UP THRU ROOF
M222M224
M223
M223
M224
54"X32" OUTSIDE AIR
DUCT UP TO ALP-1
66"X26" RELIEF AIR
DUCT UP TO ALP-2
CWP-2
CWP-1
HWP-2
HWP-1
AHU-1
AS-2
C
S-2
M224
M237
M237
M238
20x20 DUCT TO ALP-1
CONTROL PANELS
DWH-1
2 1
A.2
B
UH-2
UH-1
500 GAL. CHILLED
WATER BUFFER
TANK
ET-1ET-2
AHU-1
AS-2
AS-1
H H
W R
H H
W R
C H
W R
H H
W S
H H
W R
C H
W R
C H
W S
HWRP-1
M4.2
M4.2
4" CHWS/R
PIPING DOWN
THROUGH
SLAB TO CH-1
M4.2
M4.2
HWP-1
HWP-2
CWP-1
CWP-2
M226
M226
B-1
B-2
C H
W R
M220
M218
C
SEE M3.1 FOR
CONTINUATION
M218
2 1/2" HHWS
3" HHWR
M238
M240
M241
CONTROL PANELS
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
PLAN
NORTH
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
1/4" = 1'-0"
/4
/2
:2
:2
A
M MECHANICAL ROOM
ENLARGED PIPING
AND DUCT PLANS
M4.1
10822.000
SCALE: 1/4" = 1'-0"
MECHANICAL ROOM ENLARGED DUCT PLAN
SCALE: 1/4" = 1'-0"
MECHANICAL ROOM ENLARGED PIPING PLAN
SHEET NOTES
1. PROVIDE VOLUME DAMPERS ON ALL DUCT TAKEOFFS SERVING
SUPPLY, EXHAUST AND RETURN AIR TERMINALS. TYPICAL
THROUGHOUT.
2. PROVIDE REMOTE DAMPER OPERATORS FOR ALL AIR TERMINALS
LOCATED IN THE WOOD CEILING.
3. PROVIDE ALL RECTANGULAR MITERED ELBOWS WITH TURNING
VANES.
4. PROVIDE DUCT PRESSURE READING PORTS BEFORE AND AFTER
DUCT SILENCERS. TYPICAL FOR ALL DUCT SILENCERS.
5. PROVIDE DUCT DP SENSOR LOCATED IN COMPLIANCE WITH
ASHRAE 90.1. STATIC PRESSURE SENSORS SHALL BE PLACED IN
A POSITION SUCH THAT THE CONTROLLER SETPOINT IS NO
GREATER THAN ONE-THIRD THE TOTAL STATIC PRESSURE. IF
THIS RESULTS IN THE SENSOR BEING LOCATED DOWNSTREAM
OF MAJOR DUCT SPLITS, MULTIPLE SENSORS SHALL BE
INSTALLED IN EACH MAJOR BRANCH TO ENSURE THAT STATIC
PRESSURE CAN BE MAINTAINED IN EACH.
6. IN ADDITION TO HANGERS AND SUPPORTS FOR DUCTWORK,
PIPING AND EQUIPMENT, PROVIDE SEISMIC RESTRAINTS IN
CONFORMANCE WITH ASCE/SEI 07 – 10. FOR ADDITIONAL
INFORMATION, SEE SPECIFICATIONS, STRUCTURAL DRAWINGS
AND CHAPTER 13 OF ASCE/SEI 07–10.
KEYED NOTES
M207 18"X18" EXHAUST DUCT UP TO EF-3 ON
ROOF.
M218 PROVIDE DP SENSOR. SEE CONTROLS
DRAWINGS.
M220 PROVIDE TWO-WAY BYPASS CONTROL
VALVE.
M222 PROVIDE PVC INTAKE FOR DOMESTIC
WATER HEATER. RUN DUCT UP THRU ROOF
AND TERMINATE WITH GOOSENECK.
M223 PROVIDE PVC AIR INTAKE FOR BOILER.
INTAKE TO BE SIZED BY BOILER
MANUFACTURER. RUN DUCT UP THRU
ROOF AND TERMINATE WITH GOOSENECK.
M224 INSULATE OUTSIDE AIR INTAKE, LOCATED
INSIDE THE MECHANICAL ROOM, WITH 2"
INSULATION. PROVIDE ALUMINUM JACKET.
M225 CHEMICAL SHOT FEEDER.
M226 PROVIDE EMERGENCY SHUTOFF SWITCH
FOR BOILERS. INSTALL 48" ABOVE
FINISHED FLOOR. SEE SHEET M8.4 FOR
MORE INFORMATION.
M237 PROVIDE STAINLESS STEEL BOILER
EXHAUST SIZED BY BOILER
MANUFACTURER. PVC BOILER EXHAUST IS
ACCEPTABLE IF ALLOWED BY THE BOILER
MANUFACTURER.
M238 BOILER COOLDOWN. SEE DETAIL FOR
MORE INFORMATION.
M240 COORDINATE PIPING LOCATION WITH
ELECTRICAL CONTRACTOR. TYPICAL
THROUGHOUT.
M241 COORDINATE THE DEPTH OF THE
CONDENSATE TRAP WITH THE
STRUCTURAL CONTRACTOR.
SEE M2.3 FOR
CONTINUATION.
SEE M2.3 FOR
CONTINUATION.
2-1/2" HHWS & HHWR TO BUILDING.
SEE M3.1 FOR CONTINUATION.
A.2 A.9A.7 B
ALP-2 ALP-1
UH-1 UH-2
HWRP-1
30"x54"
PROVIDE MOTORIZED
DAMPER
AHU-1
EMERGENCY
SHUTOFF
SWITCH
B2 C
M401
M402
66"x32"
74"x30"
32"x54"
A.2A.9 A.7B
ALP-3
30"x74"
66"x32"
DWH-1 B-2 B-1 HWP-1 HWP-2 CWP-1 CWP-2 ET-1
EF-4
AS-1
4" CHWS/R TO CHILLER
AS-2 ETP-1
CHEMICAL
SHOT FEEDER
500 GAL. CHILLED
WATER BUFFER
TANK
B2C
2 1
HWRP-1
B-1
74"x30"
EMERGENCY
SHUTOFF SWITCH AS-2
ALP-2
AHU-1
54"x30"
PROVIDE STAINLESS STEEL BOILER EXHAUST.
PVC BOILER EXHAUST IS ACCEPTABLE IF IT IS
ALLOWED BY THE BOILER MANUFACTURER.
EXHAUST TO BE SIZED BY BOILER
MANUFACTURER.
TERMINATE MINIMUM 6'-0" ABOVE ROOF LEVEL.
PROVIDE MINIMUM 3 GUY WIRES.
PROVDE RAIN CAP.
PVC BOILER OUTSIDE AIR INTAKE. INTAKE TO BE SIZED BY BOILER MANUFACTURER.
TERMINATE MINIMUM 3'-0" ABOVE ROOF LEVEL.
PROVIDE HORIZONTAL TERMINATION WITH BIRDSCREEN.
32"x66"
2 1
ALP-1
30"x74"
DWH-1
AHU-1
PVC DWH EXHAUST.
TERMINATE MINIMUM 6'-0" ABOVE ROOF LEVEL.
PROVIDE MINIMUM 3 GUY WIRES.
PROVIDE RAIN CAP.
PVC DWH OUTSIDE AIR INTAKE.
TERMINATE MINIMUM 3'-0" ABOVE ROOF LEVEL.
PROVIDE HORIZONTAL TERMINATION WITH BIRDSCREEN.
54"x32"
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
PLAN
NORTH
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
1/4" = 1'-0"
/4
/2
:2
:2
A
M MECHANICAL ROOM
SECTIONS
M4.2
10822.000
SCALE: 1/4" = 1'-0"
MECHANICAL ROOM SECTION 1
SCALE: 1/4" = 1'-0"
MECHANICAL ROOM SECTION 2
SCALE: 1/4" = 1'-0"
MECHANICAL ROOM SECTION 3
SCALE: 1/4" = 1'-0"
MECHANICAL ROOM SECTION 4
SHEET NOTES
M401 DUCT SIZE 12X54 FOR MINIMUM OUTSIDE
AIR INTAKE. PROVIDE CONTROL DAMPER.
M402 DUCT SIZE 20X54 FOR OUTSIDE AIR
INTAKE DURING ECONOMIZER MODE.
PROVIDE CONTROL DAMPER.
KEYED NOTES
M401 DUCT SIZE 12X54 FOR MINIMUM OUTSIDE
AIR INTAKE. PROVIDE CONTROL DAMPER.
M402 DUCT SIZE 20X54 FOR OUTSIDE AIR
INTAKE DURING ECONOMIZER MODE.
PROVIDE CONTROL DAMPER.
VFD
HWP-1
HWP-2 (STBY)
B-1
AS-1
ET-1
HHWR
H H
W S
H H
W S
H H
W R
FLOW METER
TYPICAL
2-WAY CONTROL VALVE
TYPICAL
TEMPERATURE SENSOR
(TYPICAL)
M
M
T
T
T
T
T
T
VFD
PROVIDE CONDENSATE
DRAIN KIT ASSEMBLY
PROVIDE PH NEUTRALIZING KIT
WITHOUT PUMP
SPILL OVER NEAREST
FLOOR DRAIN
BOILER RELIEF
VALVE
BOILER RELIEF
VALVE
BOILER RELIEF COOLDOWN MODULE
BASIS OF DESIGN: CEMLINE
SPILL OVER NEAREST
FLOOR DRAIN
1" CONDENSATE
1" CONDENSATE
1-1/4" BOILER RELIEF
1-1/4" BOILER RELIEF
3" 3"
3"
3"
3"
AHU-1
HEATING COIL
HEATING COIL
HWRP-1
MECHANICAL ROOM
HHWS HHWS HHWS
HHWR HHWR HHWR
M
3" 3"
3"
3"
3"3"
3"
3"
TEST PORT
(TYPICAL)
FLEXIBLE
CONNECTION (TYP.)
FM
FM
1 1/2"
M501
M502
M502
B-2
1 1/2"
M503
UH-1
UH-2
CWP-1
CWP-2 (STBY)
AS-2
ET-2
TEMPERATURE SENSOR
(TYPICAL)
T
T
VFD
CH-1
BUFFER
TANK
500 GAL
VFD
FS
T
T
MECHANICAL ROOMUTILITY ENCLOSURE UNDERGROUND
4"
4"
4"
4"
4"
AHU-1
COOLING COIL
COOLING COIL
4"
4"
4" 4"
CHWS
C H
W S
C H
W R
C H
W R
DP
FLOW METER
FLEXIBLE
CONNECTION (TYP.)
STRAINER
M
FM
4"
M501
M504
EMERGENCY
CONNECTION
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
NONE
/4
/2
:2
:2
A
M HOT WATER AND
CHILLED WATER
PIPING DIAGRAM
M5.1
10822.000
SCALE: NONE
HOT WATER SYSTEM DIAGRAM
SHEET NOTES
1. PROVIDE ONE CHEMICAL SHOT FEEDER FOR THE CHILLED
WATER SYSTEM AND ONE CHEMICAL SHOT FEEDER FOR THE
HOT WATER SYSTEM.
SCALE: NONE
CHILLED WATER SYSTEM PIPING DIAGRAM
KEYED NOTES
M501 PROVIDE HIGH PERFORMANCE
SEGMENTED BALL VALVE WITH A TURN
DOWN RATIO OF 300:1 FOR FLOW BYPASS.
BASIS OF DESIGN VSI, SERIES V.
BUTTERFLY VALVES ARE NOT ACCEPTABLE
FOR FLOW BYPASS.
M502 INSTALL BOILERS ON SPRING TYPE
VIBRATION ISOLATOR.
M503 SELECT VALVE FOR A 5PSI DROP AT
20GPM.
M504 SELECT VALVE FOR 5PSI DROP AT MINIMUM
CHILLER FLOW AS REQUIRED BY
MANUFACTURER.
M
RETURN WATER
MANUAL
AIR
VENT
UNION
(TYPICAL)
PRESSURE
GAUGE
(TYPICAL)
THERMOMETER
(TYPICAL)
2 WAY CONTROL VALVE
SUPPLY WATER
AUTOMATIC FLOW
CONTROL VALVE OR
CIRCUIT SETTER
ISOLATION
VALVE
ISOLATION
VALVECOOLING
COIL STRAINER3/4" DRAIN VALVE
W/ HOSE END
CONNECTION
TEST PORT
(TYPICAL)
M
BYPASS. SEE M5.1
FOR MORE
INFORMATION.
M
RETURN WATER
MANUA
L
AIR
VENT
UNION
(TYPICAL)
PRESSURE
GAUGE
(TYPICAL)
THERMOMETER
(TYPICAL)
2 WAY
CONTROL
VALVE
SUPPLY WATER
AUTOMATIC
FLOW
CONTROL
VALVE
ISOLATION
VALVE
ISOLATION
VALVE
STRAINER3/4" DRAIN VALVE
W/ HOSE END
CONNECTION
FREEZ
E
PUMP
HEATING
COIL
TEST PORT
(TYPICAL)
M
RETURN WATER
MANUAL
AIR VENT
UNION
(TYPICAL)
PRESSURE
GAUGE
(TYPICAL)
THERMOMETER
(TYPICAL)
3 WAY
CONTROL
VALVE
SUPPLY WATER
AUTOMATIC
FLOW
CONTROL
VALVE
ISOLATION
VALVE
ISOLATION
VALVE
STRAINER3/4" DRAIN VALVE
W/ HOSE END
CONNECTION
HEATING
COIL
TEST PORT
(TYPICAL)
NOTES:
1. SEE SCHEDULES FOR VAV BOXES THAT WILL BE PROVIDED WITH 3-WAY CONTROL VALVES.
M
RETURN WATER
MANUAL
AIR VENT
UNION
(TYPICAL)
PRESSURE
GAUGE
(TYPICAL)
THERMOMETER
(TYPICAL)
2 WAY
CONTROL
VALVE
SUPPLY WATER
AUTOMATIC
FLOW
CONTROL
VALVE
ISOLATION
VALVE
ISOLATION
VALVEHEATING
COIL STRAINER3/4" DRAIN VALVE
W/ HOSE END
CONNECTION
TEST PORT
(TYPICAL)
FS
STRAINER
TEST PLUG (TYP.)
EVAPORATOR
TEST PLUG (TYP.)
ISOLATION VALVES
TEST PLUG (TYP.)
MANUAL AIR VENT
THERMOMETER (TYP.)
NOTE:
FLOW SWITCH
DRAIN VALVES WITH
HOSE END CONNECTIONS
FLEXIBLE
CONNECTION
(TYPICAL)
1. IN AREAS SUBJECT TO FREEZING CONDITIONS, ALL
VALVES, PIPING, STRAINERS, FLOW SWITCHES, FLEXIBLE
CONNECTIONS, ETC.
OUTSIDE OF BUILDING SHALL BE WRAPPED BY
ELECTRIC HEAT TRACE UNDER INSULATION
BALANCING
VALVE
PRESSURE GAUGE
(TYP.)
TO DRAIN
TO DRAIN
ISOLATION VALVES (TYP)
QUICK FILL BYPASS
VERTICAL EXPANSION TANK
LINE SIZE AIR SEPARATOR
THREADED HOSE CONNECTION
3/4"
HIGH CAPACITY AUTOMATIC AIR VENT
PIPE TO DRAIN
PIPE TO DRAIN
12" MIN.
PRESS. REG. VALVE
PRESSURE GAGE
NORMALLY OPEN ISOLATION VALVE
(REMOVE HANDLE)
EQUIVALENT LINE SIZE PER DWGS.
1" PIPE SIZE MINIMUM-INSTALL TEE
IN VERTICAL.
EQUIVALENT LINE SIZE PER
DRAWINGS- 1" PIPE SIZE MINIMUM
CW MAKE-UP FROM
WATER MAKE-UP UNIT
SIDE OF MAIN CONNECTION
ONLY. (TOP & BOTTOM
CONNECTION NOT ALLOWED.)
TO PUMP SUCTION
HIGH CAPACITY
AUTOMATIC AIR VENT
LINE SIZED TO FULL
TANK CONNECTION
SIZE
LINE SIZED TO FULL
TANK CONNECTION
SIZE
PRESSURE GAGE &
GAGE COCK
CAPPED SIDE TEE CONNECTION FOR MULTIPLE
TANKS WHERE MULTIPLE EXPANSION TANKS ARE
REQUIRED. CONNECT TO SIDE TEE AT THIS POINT -
CONNECTION LINE SIZE TO BE FULL TANK
CONNECTION SIZE.
PRE CHARGE AIR
CONNECTION. TANK
CONNECTION LOCATIONS AND
ARRANGEMENT MAY VARY BY
MANUFACTURER.
FROM SYSTEM
STRAINER
ISOLATION VALVE
UNION
CHECK VALVE
(CABINET UNIT HEATERS SIMILAR)
UNION (TYPICAL) HHWS
HHWR
1/2" ALL THREAD
TO STRUCTURE
2-WAY CONTROL
VALVE
STAINER
3/4" DRAIN VALVE W/
HOSE END CONNECTION
VIBRATION
ISOLATOR
AUTOMATIC FLOW
CONTROL VALVE
M
ISOLATION VALVE
ISOLATION VALVEBALL VALVE
MANUAL
AIR VENT
UNIT
HEATER
TEST PORT
(TYPICAL)
ISOLATION VALVE
ISOLATION VALVE
FLOW METER
THROTTLING VALVE
SEE SPECS
2.
1.
NOTES:
STRAINER
1/4" BALL VALVE (TYP.)
CHECK VALVE
PRESSURE GAGE
UNION OR FLANGE
TYPE CONNECTION
IN-LINE PUMP
AND MOTOR
PROVIDE INCREASERS AS
REQUIRED-REFER TO
PROJECT PLANS FOR PIPE
SIZE REQUIREMENTS
SUPPORT PUMP AND PIPING FROM SUITABLE VIBRATION ISOLATION
SUPPORTS. REFER TO SPECIFICATIONS.
PIPING SHALL BE INSTALLED SUCH THAT PUMP MAY BE COMPLETELY REMOVED
WITHOUTDISMANTLING PIPE OR FITTINGS, AND WITHOUT FORCING OR SPRINGING THE
PIPING.
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
NONE
/4
/2
:2
:2
A
M MECHANICAL
DETAILS - PIPING
M6.1
10822.000
SCALE: NONE
CHILLED WATER COIL 2-WAY CONTROL VALVE
SCALE: NONE
HOT WATER HEATING COIL 2-WAY CONTROL VALVE W/ FREEZE PUMP
SCALE: NONE
HOT WATER HEATING COIL 3-WAY CONTROL VALVE
SCALE: NONE
HOT WATER HEATING COIL 2-WAY CONTROL VALVE
SCALE: NONE
WATER PIPING CONNECTIONS TO AIR COOLED CHILLER
SCALE: NONE
DIAPHRAGM EXPANSION TANK AND AIR SEPARATOR - VERTICAL TANK
SCALE: NONE
HORIZONTAL HOT WATER UNIT HEATER
SCALE: NONE
IN-LINE PUMP
SCHEMATIC DESIGN 8.17.2018
VANE
VANE
NOTE:
1. THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.
R SHALL
EQUAL
OR BE
GREATER
THAN W.
R SHALL
EQUAL
OR BE
GREATER
THAN
1/3W.
R SHALL
EQUAL
OR BE
GREATER
THAN
1/6W.
STANDARD RADIUS OR
LONG RADIUS ELBOW
SHORT RADIUS ELBOW
WITH ONE VANE
SHORT RADIUS ELBOW
WITH TWO VANES
W
R
R
2/3W
1/ 3W
W W
1/2W
1/ 3W
1/6W
R
NOTE:
1.
2.
3.
4.
ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.
WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE
REGARDLESS OF W DIMENSION.
ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] MAXIMUM
SPACE BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.
WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL BE DOUBLE
VANE TYPE.
W
W1
FLEXIBLE DUCT SIZE
SAME AS DIFFUSER
INLET. 5'-0" MAX LENGTH
12"
CEILING
SUPPORT SADDLE
FROM STRUCTURE
VOLUME DAMPER
W/ LOCKING
QUAD
SHEET METAL
SADDLE
CONICAL OUTLET
BRANCH DUCT
USE RIGID ELBOWS FOR
CHANGE OF DIRECTION
GREATER THAN 45°.
SEE SPECIFICATIONS FOR
CLAMPS
AND SEALANT (TYP.)
TYPICAL
DIFFUSER OR
REGISTER IN
LAY-IN CLG.
THERMAL
INSULATION
SEE SPECIFICATIONS
NOTES:
1. PROVIDE PREFABRICATED ROOF CURB WITH TIE DOWN POINTS. SECURE
ROOF CURB WITH RUST RESISTANT BOLTS.
2. SECURE TO CURB WITH MINIMUM 3/8" CADMIUM PLATED SELF-TAPPING
SCREWS NOT OVER 12" ON CENTER.
3. PROVIDE ROOF OPENING TO ALLOW FOR THE INSTALLATION OF THE
RELIEF AIR DUCT ONLY.
4. PROVIDE ALUMINUM CURB WITH 2" INSULATION.
5. PROVIDE ALUMINUM PENTHOUSE WITH 1" INSULATION.
6. PROVIDE MINIMUM 3/8" DIA. BOLTS 3" FROM CORNERS AND 12" MAX C-C.
7. PROVIDE 4" RIGID INSULATION AROUND THE DUCT OPENING AND
THROUGHOUT THE INTERIOR OF THE CURB.
8. PROVIDE ADDITIONAL VERTICAL SUPPORTS 24" MAX C-C.
PROVIDE CURB WITH EXTENDED SILL BASE TO ACCOMMODATE THE
INSTALLATION OF THE VERTICAL SUPPORTS.
STEEL DECK
SEE NOTE 2
ARCHITECTURAL LOUVERED
PENTHOUSE
SEE NOTE 3
SEE NOTE 6
INSULATION
PROVIDE STEEL ANGLES
ON ALL FOUR SIDES OF THE CURB
SEE STRUCTURAL DRAWINGS
RELIEF DUCT ENDS HERE
PROVIDE STEEL ANGLES
ON ALL FOUR SIDES OF
THE ROOF OPENING
SEE STRUCTURAL DRAWINGS
RELIEF AIR
DUCT
SEE NOTE 7
SEE NOTE 8
SEE NOTE 8
3' M
IN
NOTE:
1.
2.
DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR
MULTI-BLADE DAMPERS & ROUND DAMPERS.
INSULATION SEE
SPECIFICATION
DAMPER BLADE
1/8"
CLEARANCE
ALL AROUND
OUTSIDE END BEARING
INSIDE END BEARING
HANDLE WITH
LOCKING
QUADRANT
INSULATION
STAND-OFF
1/2" ROUND ROD PIN
DUCT
STIFFEN BLADE
AS REQUIRED
SIDE ELEVATION SECTION
AIR SPLIT DUCT TAKE-OFF PLAN
VIEW
BRANCH DUCT TAKE-OFF PLAN VIEW
SUPPLY REGISTER
OR BRANCH DUCT
TURNING VANES
MAIN
SUPPLY
DUCT
SEE FLOOR PLAN FOR
SPLIT DIMENSION
PROVIDE
VOLUME
DAMPER
PROVIDE VOLUME
DAMPER
1/4 W OR 6"
MAIN SUPPLY
DUCT
W
AIR
FLOW
AIR
FLOW
A
IR
F
LO
W
A
IR
F
LO
W
AIR
FLOW
SEE CONTROLS AND
PIPING DETAIL
PROVIDE DUCT TRANSITION
AS REQUIRED TO MATCH
DUCT CONNECTIONS WITH
UNIT OUTLET DIMENSIONS
SAME DIAMETER AS BOX INLET
SCHEDULE FOR INLET SIZE)
(SEE VAV TERMINAL UNIT
2D MIN.
CONICAL BELLMOUTH FITTING,
VAV BOX
HEATING COIL
CLEARANCE
MIN. 36"
M A
IN
S
U P
P
LY
A
IR
D U
C T
D
VD VOLUME DAMPER
5D MAX.
HHWS AND HHWR
SEE NEW WORK
PIPING PLANS
SEE CONTROLS AND
PIPING DETAIL
PROVIDE DUCT TRANSITION
AS REQUIRED TO MATCH
DUCT CONNECTIONS WITH
UNIT OUTLET DIMENSIONS
1. 36" CLEARANCE REQUIRED FOR VAV BOXES WITH REHEAT.
NOTE:
2D MIN.
VAV BOX
HEATING COIL
CLEARANCE
MIN. 36"
M A
IN
S
U P
P
LY
A
IR
D U
C T
D
VD VOLUME DAMPER
5D MAX.
HHWS AND HHWR
SEE PIPING PLANS
SEE DUCT PLANS
FOR SIZES
THIS DUCT CONNECTION SHALL MATCH THE
INLET SIZE OF THE VAV BOX
DO NOT PROVIDE DUCT CONNECTION
SMALLER OR LARGER THAN THE NECK OF THE VAV BOX
NOTE:
1. DUCT CONNECTION TO THE VAV BOX SHALL BE THE
SAME SIZE AS THE NECK OF THE BOX. 2. DUCT CONNECTION TO VAV BOX SHALL BE SAME SIZE AS NECK OF THE BOX.
MAIN EXHAUST OR RETURN
PLAN VIEW
PROVIDE VOLUME DAMPER
AT EACH BRANCH DUCT
1/4W OR 4" MIN.
BRANCH DUCT
VD
W
AIR
FLOW AIR
FLOW
ROOF
CONDUIT
PREFABRICATED CURB
(SEE SPECIFICATIONS)
& TYPICAL FAN CURB
DETAIL
PROVIDE 1/2" MESH
BIRDSCREEN AND
DISCONNECT SWITCH
SCREEN AREA SHALL
BE 125% OF DUCT AREA
OR ROOF OPENING
MOTORIZED DAMPER
INSTALL IN EXHAUST DUCTWORK BELOW
ROOF OR DUCT OPENING
VIBRATION
ISOLATOR
NOTES:
1. PROVIDE PREFABRICATED ROOF CURB WITH TIE DOWN POINTS. SECURE ROOF CURB WITH RUST RESISTANT BOLTS.
2. SECURE CURB…