This is a combined synopsis and solicitation for commercial items issued by the Department of the Army Corps of Engineers Engineering District Little Rock. It requests quotes for the Eglin NICoE Initial Outfitting Project to outfit a new facility on Eglin Air Force Base. Quotes are due by January 8, 2020 at 1:00 PM Central Time. A site visit is scheduled for December 4, 2019 at 9:00 AM Central Time at the Eglin AFB West Visitors Center. This is a total Service-Disabled Veteran-Owned Small Business set-aside with a NAICS code of 337127 and size standard of 500 employees. Interested contractors must RSVP for the site visit by November 29, 2019 at 11:00 AM Central Time and provide contact information for base access. More details are available in the combined synopsis and solicitation attachments.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TECHNOLOGY SYMBOL LIST
SYMBOL: DESCRIPTION: NOTE:
EQUIPMENT
LIST ABBREV.:
C#
W
C#
C#
1.INFORMATION OUTLET (CEILING)SC-IO-C
1.INFORMATION OUTLET (WALL)SC-IO-W
.WALL PHONESC-IO-W
1., 3.INFORMATION OUTLET (FLOOR)SC-IO-F
RI
.INFORMATION OUTLET ROUGH-IN (WALL)SC-RI-W
CSS
CR1 2.CREDENTIAL READER - TYPE 1AC-CR1-W
2.
CONTROLLED SECURITY SCHEME SCHEDULE
IDENTIFIER
DR SECURITY DURESS/PANIC BUTTON (WALL)AC-DR-W .
DR SECURITY DURESS/PANIC BUTTON (SURFACE)AC-DR-S .
EDR ELECTRONIC DOOR RELEASE (WALL)AC-EDR-W .
N/A
WP1 .AUDIO/VISUAL FACEPLATE (WALL) - TYPE 1AV-WP1-W
ND2
D NURSE CALL - DOME LIGHT (WALL)
STAFF ASSIST BUTTON
ND1 .NURSE CALL - MASTER STATION
NC-D-W
NC-ND2-W
NC-ND1-W
TECHNOLOGY ABBREVIATION KEY
ENTRANCE FACILITYEF-#
MAIN CROSS-CONNECTMC-#
TELECOMMUNICATIONS ROOMTR-#
ABOVE FINISHED FLOORAFF
BELOW FINISHED CEILINGBFC
CONDUITC
SIMILARSIM
TYPICALTYP
MOUNTING HEIGHT ABOVE FINISHED FLOOR+#
JUNCTION BOXJ-BOX
ABBR: DESCRIPTION:
UNLESS NOTED OTHERWISEUNO
TECHNOLOGY GENERAL NOTES:
1. ###-### INDICATES GENERAL TECHNOLOGY EQUIPMENT SCHEDULE ITEM LABELED AS
"EQUIPMENT LIST ABBREVIATION"
2. REFER TO GENERAL TECHNOLOGY EQUIPMENT SCHEDULE AND SPECIFICATIONS FOR FULL
DESCRIPTIONS AND MANUFACTURERS OF ALL DEVICES.
TECHNOLOGY MOUNTING SUBSCRIPT KEY:
A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH
H MOUNT ORIENTED HORIZONTALLY
L MOUNT IN CASEWORK
M MOUNT IN MODULAR FURNITURE
S MOUNT IN SURFACE RACEWAY
A SLASH IS USED BETWEEN TWO SUBSCRIPTS, E.G., A/H.
1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR
ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS
ON THIS PAGE FOR ADDITIONAL INFORMATION.
2. CONCEAL ALL CONDUIT IN WALLS, PARTITIONS, ABOVE CEILING, IN FLOOR SLAB, ETC.
UNLESS OTHERWISE INDICATED ON THE PLANS OR IN THE SPECIFICATIONS. CONDUIT IN
MECHANICAL ROOMS AND STORAGE ROOMS WITHOUT CEILINGS MAY BE EXPOSED ON
BUILDING STRUCTURE.
3. BOXES LOCATED ON OPPOSITE SIDES OF NON-RATED WALLS SHALL BE OFFSET A MINIMUM
OF 6" HORIZONTALLY. BOXES ON OPPOSITE SIDES OF FIRE RATED WALLS SHALL BE
OFFSET A MINIMUM OF 24" HORIZONTALLY. "THRU-THE-WALL" BOXES SHALL NOT BE
ALLOWED WITHOUT PRIOR WRITTEN APPROVAL OF THE ARCHITECT/ENGINEER.
4. VERIFY ALL FURNITURE, MODULAR FURNITURE, AND EQUIPMENT LOCATIONS WITH
ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS. PRIOR TO MAKING
THE ACTUAL TELECOMMUNICATIONS INSTALLATION, ADJUST OUTLETS OR CONNECTION
LOCATIONS TO ACCOMMODATE FURNITURE AND/OR EQUIPMENT.
5. TELECOMMUNICATIONS EQUIPMENT SHALL BE MOUNTED TO ALLOW ACCESS TO
ELECTRICAL AND MECHANICAL EQUIPMENT. ALL MOUNTING OF TELECOMMUNICATION
DEVICES ON EQUIPMENT SUPPLIED BY ANOTHER CONTRACTOR SHALL BE APPROVED IN
ADVANCE BY THE OTHER CONTRACTOR.
6. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL
OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE
EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR
SEALED INTO OPENINGS.
7. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL
BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF
THROUGH-PENETRATION FIRESTOPS. REFER TO DIVISION 7 FOR ADDITIONAL INFORMATION
AND REQUIREMENTS SPECIFIC TO FIRESTOPPING.
8. REMOVE AND REINSTALL ALL CEILING TILES AS REQUIRED FOR THE EXECUTION OF
TELECOMMUNICATIONS WORK THAT IS OUTSIDE THE CONTRACT LIMITS OF CONSTRUCTION.
REPLACE CEILING TILES WITH IDENTICAL MATERIAL WHERE DAMAGED BY THIS
CONTRACTOR.
9. FLUSH MOUNT ALL TELECOMMUNICATION OUTLETS AT +18" FROM FLOOR (CENTERLINE
DIMENSION), EXCEPT WHERE OTHERWISE NOTED. OUTLETS MAY BE SURFACE MOUNTED
WHEN CONDUIT IS SPECIFIED EXPOSED.
TECHNOLOGY INSTALLATION NOTES:
GENERAL NOTES:
1. ALL SYMBOLS AND ABBREVIATIONS LISTED MAY NOT BE APPLICABLE TO THIS PROJECT.
REFER TO THE GENERAL TECHNOLOGY EQUIPMENT SCHEDULE FOR MORE COMPLETE
DESCRIPTION AND ITEMS.
2. ALL SYMBOLS AND ABBREVIATIONS REFER TO TECHNOLOGY SHEETS ONLY AS DEFINED ON
THE SHEET INDEX. REFER TO THE GENERAL TECHNOLOGY NOTES FOR ADDITIONAL
INFORMATION.
3. ALL SYMBOLS LISTED ABOVE ARE FOR REFERENCE ONLY. REFER TO PLANS AND LINE TYPE
KEY FOR NEW, EXISTING TO REMAIN AND TO BE REMOVED ITEMS FOR ADDITIONAL
INFORMATION.
TECHNOLOGY SYMBOL NOTES:
1. "C#" INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION. REFER TO
INFORMATION OUTLET SCHEDULE ON T7.1 AND RISER ON 1/T5.1 FOR ADDITIONAL
INFORMATION.
2. REFER TO CONTROLLED SECURITY SCHEME (CSS) TYPE SCHEDULE ON T7.1 AND DOOR
ROUGH-IN DETAIL AT 5/T6.1 FOR ADDITIONAL INFORMATION.
3. INFORMATION OUTLET INSTALLED IN E.C. PROVIDED FLOOR BOX. "C#" INDICATES
INFORMATION OUTLET FACEPLATE CONFIGURATION. REFER TO INFORMATION OUTLET
SCHEDULE ON T7.1 FOR ADDITIONAL INFORMATION. REFER TO THE ELECTRICAL FLOOR
PLANS AND ELECTRICAL EQUIPMENT SCHEDULE FOR ADDITIONAL INFORMATION.
CABLE TRAY, CHANNEL TRAY, BASKET
TRAY
LADDER RACK
WIDTH X HEIGHT
WIDTH X HEIGHT
DIAMETERø C CONDUIT
CONDUIT DOWN
CONDUIT UP OR UP/DOWN
CONDUIT SLEEVE
CONTINUATION
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
NAME
VIEW NAME
1/8" = 1'-0"
T4.1
SIM
DETAIL REFERRED TO BY ELEVATION
SHEET DETAIL IS LOCATED ON
INDICATES SIMILAR DETAIL
REFERENCED IN MULTIPLE LOCATIONS
LEVEL NAME
10' - 0" HEIGHT ABOVE
PROJECT 0' - 0"
1 INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
N
O R HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
NEW WORK BY THIS CONTRACTOR
(DARK SOLID LINE)
NEW WORK UNDERFLOOR OR UNDERGROUND BY THIS CONTRACTOR
(DARK LONG DASHED LINE)
NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN
(LIGHT SOLID LINE)
EXISTING TO BE REMOVED BY THIS CONTRACTOR
(DARK SHORT DASHED LINE)
LINE TYPE KEY:
SECURITY CONTRACTORS.C.
NURSE CALL CONTRACTORN.C.C.
CIVIL CONTRACTORC.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
ELECTRICAL CONTRACTORE.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
CONSTRUCTION MANAGERC.M.
M
A X
20" MAX.
M
A X
20"-25" MAX.
M
A X
M
IN
. 4
M
A X
M
A X
10" MAX. 10"-24" MAX.
ADA GUIDELINES - FRONT ACCESS
ADA STANDARDS FOR ACCESSIBLE DESIGN
INSTALL ABOVE COUNTER
DEVICE AT 44" ABOVE
FINISHED FLOOR.
INSTALL ABOVE COUNTER
DEVICE AT 40" ABOVE
FINISHED FLOOR.
INSTALL DEVICE AT 18"
ABOVE FINISHED FLOOR.
ADA GUIDELINES - SIDE ACCESS
INSTALL DEVICE AT 44"
ABOVE FINISHED FLOOR.
INSTALL DEVICE AT 42"
ABOVE FINISHED FLOOR.
SUGGESTED MATRIX OF RESPONSIBILITY
ITEM: SHOWN ON:
FURNISHED
BY:
INSTALLED
BY: NOTES:
TECHNOLOGY ROUGH-IN, REFER TO
GENERAL TECHNOLOGY EQUIPMENT
SCHEDULE AND SPECIFICATIONS FOR
DEFINITION
T-SERIES E.C. E.C. 3. 4.
INFORMATION OUTLET FACEPLATES,
JACKS, AND TERMINATIONS
T-SERIES T.C. T.C.
CONDUIT SLEEVES (WHEN SHOWN ON
DRAWINGS)
T-SERIES E.C. E.C.
CONDUIT SLEEVES (NOT SHOWN BUT
REQUIRED FOR PROPER INSTALLATION
OF SYSTEM)
N/A T.C. T.C. 2. 4.
TELECOMMUNICATION SYSTEMS
ROUGH-IN
T-SERIES E.C. E.C. 1.
TELECOMMUNICATION EQUIPMENT,
CABLING, AND TERMINATIONS
T-SERIES T.C. T.C.
NURSE CALL ROUGH-IN T-SERIES N.C.C. E.C.
NURSE CALL EQUIPMENT, CABLING,
AND TERMINATIONS
T-SERIES N.C.C.
CABLE TRAY (INCLUDING WIRE BASKET
TRAY) REFER TO SPECIFICATION
SECTION 27 05 28 FOR DEFINITION
T-SERIES E.C. E.C.
LADDER RACK T-SERIES T.C. T.C. 5.
GROUNDING LUGS ON TECHNOLOGY
EQUIPMENT
T-SERIES T.C. E.C. 6.
BONDING SYSTEM FOR TECHNOLOGY
SYSTEM, REFER TO SPECIFICATION
SECTION 27 05 26 FOR DEFINITION
T-SERIES E.C. E.C. 7. 8.
CONNECTION OF TECHNOLOGY
BONDING SYSTEM TO THE ELECTRICAL
GROUND SYSTEM
T-SERIES E.C. E.C.
LINE VOLTAGE POWER (+120V OR
GREATER)
E-SERIES E.C. E.C.
LINE VOLTAGE POWER (NOT SHOWN
BUT REQUIRED FOR PROPER
INSTALLATION OF SYSTEM)
N/A T.C. E.C. 2. 4.
LINE VOLTAGE POWER FOR DOOR
HARDWARE POWER SUPPLIES
ARCH SPEC E.C. E.C.
LOW VOLTAGE CABLING FOR
TECHNOLOGY SYSTEMS
T-SERIES T.C. T.C.
CABLE HANGERS AND SUPPORTS OR
OTHER CABLE ROUTING METHODS
(OTHER THAN CONDUIT AND CABLE
TRAY)
T-SERIES T.C. T.C. 5.
TECHNOLOGY SERVICE ENTRANCE
CONDUITS, HANDHOLES, AND
MANHOLES
T-SERIES E.C. E.C.
FLOOR BOX (ROUGH-IN) T & E SERIES E.C. E.C.
SUGGESTED MATRIX OF RESPONSIBILITY NOTES
1. LOCATIONS OF TELECOMMUNICATIONS ROUGH-INS SHALL BE INDICATED BY THE INFORMATION
OUTLET SYMBOLS ON THE DRAWINGS. REFER TO THE TECHNOLOGY SYMBOL LIST FOR
ADDITIONAL INFORMATION.
2. BASED ON THE INHERENT DIFFERENCES IN PRODUCTS FROM VARIOUS MANUFACTURERS, ALL
REQUIRED EQUIPMENT MAY NOT BE SHOWN ON THE DRAWINGS FOR ALL ACCEPTABLE
MANUFACTURERS.
3. INCLUDES BACKBOXES AND CONDUIT REQUIRED FOR THE TECHNOLOGY SYSTEMS
INSTALLATION. THE E.C. SHALL BASE THE BID ON THE BASIS OF DESIGN SHOWN ON THE
CONTRACT DOCUMENTS.
4. ALL CHANGES TO THE SLEEVES, BACKBOXES, CONDUITS, AND POWER REQUIRED BECAUSE OF
THE T.C.'S SELECTION OF AN ALTERNATE ACCEPTABLE MANUFACTURER OR FROM SYSTEM
CONFIGURATIONS THAT ARE LEFT TO THE CHOICE OF THE CONTRACTOR SHALL BE INCLUDED
IN THE T.C.'S BID. THIS BID SHALL INCLUDE INSTALLATION BY A LICENSED ELECTRICIAN.
5. UNLESS TRADE RULES DICTATE OTHERWISE.
6. FURNISHED AS PART OF THE EQUIPMENT WHEN POSSIBLE, OR FURNISHED TO THE E.C. FOR
INSTALLATION IN THE FIELD.
7. INCLUDES ALL CONDUCTORS, GROUND BARS, AND TERMINATIONS FOR THE COMPLETE
BONDING SYSTEM REQUIRED BY THE SPECIFICATIONS.
8. REFER TO ELECTRICAL DRAWINGS FOR LOCATIONS OF PANELS AND SWITCHBOARDS SHOWN
IN THE TECHNOLOGY BONDING RISER DIAGRAM AND TYPICAL TELECOM ROOM BONDING FLOW
DIAGRAM.
TELECOM ROOM REFERENCES
TELECOM ROOM
DETAIL / SHEET
REFERENCE
FLOOR PLAN
REFERENCE ARCH ROOM NUMBER
TR-1 1/T4.1 T2.1 324
TR-2 4/T4.1 T2.1 211
I O W A
S E
D
PROFESS IONA
14628
L
IC
E N
L E
N G
I N E
E R
Jeffrey A.
Carpenter
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
As indicated
/1
/2
:5 :0
P
M TECHNOLOGY
ABBREVIATIONS AND
SYMBOLS
T0.1
10822.000
TECHNOLOGY SHEET INDEX
T0.1 TECHNOLOGY ABBREVIATIONS AND SYMBOLS
T2.1 GROUND FLOOR PLAN - TECHNOLOGY
T4.1 ENLARGED PLANS - TECHNOLOGY
T5.1 RISER DIAGRAMS - TECHNOLOGY
T6.1 DETAILS - TECHNOLOGY
T7.1 SCHEDULES - TECHNOLOGY
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE
THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
2882 106TH STREET
DES MOINES, IA 50322
515.334.9906 FAX: 515.334.9908
www.imegcorp.com
18003094.00
Contract Documents 01.04.2019
C
C
C2-WAP
W
W
C 2C
C
W
C2-WAP
C2
C2-WAP
C2-WAP
C2-WAP
C2-WAP
C2-WAP
C2-WAP
C2-WAP
C2-WAP
C2-WAP
C2-WAP
C2-WAP
C2-WAP
C2-WAP
C2-WAPC2-WAP
C
C
C 2C
RI
C2
C
C
C
C
C2
C2
C2
C
C 2C
C
C
C
C2C2
C2 C2
C2
C2
C2-WAP
C2-WAP
C
C
C
C
C
C 2 C
C
C 2 C
C2
C
C2
C
C
C
C
C
C
C2
C
C
C2
C
C
C
C2 C
C2 C2
C2
W
C4
C2
C2C2
C2 C2 C2
C2 C2 C2
RI
C -T
V
C -T
V
C
C
C -T
V
RI
C -T
V
C -T
V
RI
CR1
CSS
C
C
CSS
CR1
CR1
C S
S
C R
CR1
C R
CR1
C R
C R
CR1
CR1
C S
S
C S
S
CSS
CSS
CSS
C S
S
CSS
C S
S
CSS
C S
S
CSS CSS
CSS
W P
W P
W P
W P
W P
E D
R
D D
DD
D D
D
D
D
D
D D
D
D
D
D D
D
DD
D
ND2 ND2
ND2
N D
N D
N
D
ND2
ND2
N D
ND2
ND2ND2ND2
ND2
ND2
N D
N D
ND2
ND2
ND2
N D
N
D
N D
ND2ND2ND2
ND2 ND2 ND2
ND2
ND2
N D
D
D D
N D
D
N D
N D
D
DR
DRDR
DR
DR
DR
DR
DR
D
C
C
C
C2 C2
C
C2
C2
C2C2
C
DR
DR
DR
DR
DR
DR DR DR
DR
C2 DR
DR
DR
DR
DR
DR
DR
DR
DR
DR
DR
DR
DRDRDR
DR DR DR
DR
DR
W P
C -T
V
DR
DR
DR
DR
DR
DR
C
W P
C -T
V
DR
DRDR
DR
DR DR
DR
W P
WP1W
P
C -T
V
C1-TV
C -T
V
C2
C2DR
C2
W P
C
- T
V
C2
C
C
DR
W P
W
P
C -T
V C
-T
V
C
C
C2
C2
C
W P
W
P
C
C1
C
C
C
C
C1
C -T
V
W P
C
CR1 CR1
CR1
C
W P
W P
C
W P
W P
W P
W P
W P
C -T
V
W P
W
P
W P
W
P
W P
N D
ND2
ND2
D
DR
C R
C2
C1
C1
C
C
W P
1 W P
WP1
W P
W P
W P
C
W P
C2
W
123456789
B
C
D
E
F
A
A.7
A.2
6.97.1 6.26.5 5.4 4.5 3.6 2.8
D.7
5.2 4.88.6 8.3 6.8 6.4
0.9A
0.2A
0.3A
0.4A
0.5A
0.6A
E.8
B2
A.9
0.7A
MECHANICAL
ELEC
TLT/ SHR
218.2
CHANGING / LOCKER (M)
CHANGING / LOCKER (W)
VESTIBULE
COMM
PUBLIC WAITING
C101
SOIL UTIL
WORKSTATION PT
TLT/ SHR
218.1
CORRIDOR
C300
CORR
C301
CORR
C305
CORR
C304
CORR
C302
CORR
C306
CORR
C201
CORR
C200
CORR
C202
MAT / PLATFORM
PT GYM
GAIT OBS LANE
CORR
C303
NEURO REHAB AREA
FAMILY WAITING
CENTRAL PARK
TREATMENT IPMC
DAYROOM
SOIL UTIL
CASE MGMT
CLEAN UTIL
CORR
C102.1
EYE TESTING
EXAM
SCALE
C306.1PAT TLT
STAFF TLT
EXAM
GROUP THERAPY
TEAM ROOM
EXAM
HOUSEKEEPING
PAT TLT
BRAIN LAB
ELEC
TRANS-CRANIAL MAGNETIC STIM
COMM
ACUPUNCTURE
341.1
SPIRITUAL COUNSELLING
NP PSYCH
NEUROPSYCH
ACUPUNCTURE
341.2
BH / SW PROVIDERS
BH / SW PROVIDERS
PSYCHOLOGIST
CHIRO TREATMENT
CASE MGMT
STAFF LOUNGE
EXAM
MUSIC THERAPY
CHIRO TREATMENT
RECEPTION
PTNT INTAKE CUBICLES
300.1
CASE MGMT
ART AND CLAY THERAPY
MALE TOILET
FEMALE TOILET
HOUSEKEEPING
MULTI-STATION TREATMENT RM
PT O/E
PT O/E
DAILY LIVING SKILLS
BREAK ALCOVE
105.1
RESEARCH SHARED OFFICE
NCOIC / ADMIN
NICoE DIR.
DIR. OF OPERATIONS
AV SUPPLY
CLASSROOM
103.1
CHAPLAIN
CLASSROOM
EYE LANE
EXAM
PSYCH TECH
PSYCH TECH
STAFF TLT
SPEECH THERAPY - OFFICE
OT O/E
TRAZER / FATS
SPEECH THERAPY - TESTING
OT O/E
NEUROLOGIST
PC MD
CLINICAL PHARMACIST
EXAM
EXAM
PAIN MD
NUTRITIONIST
GROUP THERAPY
335.1
BIO NEUROFEEDBACK
FLEX STORAGE
VENDING ALCOVE
106.1
CORR
C102
STORAGE / KILN
338.1
TLT / SHR
219.1
BH / SW PROVIDER
4A
4B
5.
8.
318 349 34
EQPT STOR
EXAM
EQPT STOR
8.
8.
219.1
C
2A
C102
103 10
7B
C
0A
217A
C100A
C
C100B
STORAGE / ALCOVE
200.1
C100
ALCOVE / STORAGE
C303.1
MAIN CORRIDOR / LOBBY
C100
C102.1
3.
T4.1
T4.1
TR-1
TR-2
SC-CT-1 (TYP)
SC-CT-1 (TYP)
+108"
+108"
+108"
CABLING ON THIS SIDE TO TR-1
CABLING ON THIS SIDE TO TR-2
CABLING ON THIS SIDE TO TR-1
CABLING ON THIS SIDE TO TR-2
PRINTER
PYXIS
MACHINE
PRINTER
AC-DRK-1 1
12"x4"
"x
"x
12"x4"12"x4"
+60"+60"
+60"
+60"
+60"
+60"
+60" +60"
+60" +60"
+60" +60"
+60"
+60"
+60"+60"
+60" +60"
+60" +60"
+60" +60"
+60"
+60"
+60"
+60"
+60"
+60"
+60"
+60"
+108"
AC-DRK-1
+60" +60"
12"x4"
"x
"x
"x
12"x4"
12"x4"
"x
"x
12"x4"
+48"
+48"
+48"
+48"
+48"
+48"
+48"
+48"
+48"
+48"
+48"
+48" +48"
+48"
+48"
+48"
+48"
+48"
+48"
+48"
+48"
+48"
+48"
+48" +48"
+48" +48"
+48"
+48"+42" +48"
+48"
+48"
+48"
+48" +48"
WALL MOUNTED
WIRELESS
DURESS BUTTON
AV-VPS-1
AV-PRO-MNT-1
AV-PRO-1
HANDHOLE AND CONDUIT DUCTBANK
ROUTED INTO BUILDING. REFER TO
ELECTRICAL DRAWINGS FOR ADDITIONAL
INFORMATION.
BUILDING CONTRACTOR TO ROUTE AND
TERMINATE 24 SM FIBER INTO BUILDING.
FIBER AND SLACK COIL WILL BE PROVIDED
BY BASE CONTRACTOR AND LEFT AT
HANDHOLE FOR INSTALLATION. REFER TO
1/T5.1 FOR ADDITIONAL INFORMATION
I O W A
S E
D
PROFESS IONA
14628
L
IC
E N
L E
N G
I N E
E R
Jeffrey A.
Carpenter
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
1/8" = 1'-0"
/1
/2
:5 :0
P
M GROUND FLOOR
PLAN - TECHNOLOGY
T2.1
10822.000
N
O R HT
1/8" = 1'-0"1
GROUND FLOOR PLAN - TECHNOLOGY
GENERAL SHEET NOTES :
1. CONTRACTOR TO PROVIDE A 15' SLACK COIL
AT THE NEAREST SUPPORT ABOVE EVERY
ROOM CONTAINING ONLY ONE INFORMATION
OUTLET LOCATION TO ALLOW FOR CABLING
TO BE RE-ROUTED TO THE OTHER SIDE OF
THE ROOM AT A LATER DATE BY THE OWNER.
KEYNOTES:
1. PROVIDE (2) 1" CONDUITS DOWN COLUMN FOR
ROUTING OF LOW VOLTAGE CABLING FROM
ABOVE CEILING, INTO MILLWORK, AND
THROUGH MILLWORK TO TERMINATION
LOCATION.
2. INSTALL INFORMATION OUTLET IN MILLWORK.
ROUTE CABLING THROUGH MILLWORK AND
THROUGH CONDUIT STUB UP IN FLOOR. REFER
TO ELECTRICAL DRAWINGS FOR ADDITIONAL
PATHWAY INFORMATION.
3. PROVIDE HDMI CABLE FROM WALL PLATE TO
HDMI EQUALIZER MOUNTED AT PROJECTOR.
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE
THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
2882 106TH STREET
DES MOINES, IA 50322
515.334.9906 FAX: 515.334.9908
www.imegcorp.com
W
W
NC-NCP-1 AC-SCP-1
SC-GND-1
SC-TTB
(TYP)
T4.1
SC-ER-1
SC-VWM-1
(TYP)
(TYP)
NOTES:
1. REFER TO 2/T4.1 FOR PATHWAY PLAN.
TV-TVT-4
SC-FDC-1
(PROVIDE WALL
MOUNT BRACKET)
NOTES:
1. PLACE ALL EQUIPMENT IN ITS DESIGNATED RACK AS DEFINED BY THIS LAYOUT UNLESS
OTHERWISE NOTED. ALL EQUIPMENT IS SIZED (BY RACK UNITS) ACCORDING TO THE
BASIS OF DESIGN MANUFACTURER AND ARE THE MINIMUM REQUIREMENTS.
COORDINATE WITH THE OWNER AND THE ENGINEER FOR ANY CHANGES PRIOR TO
MODIFICATION OF THIS LAYOUT. REFER TO THE TECHNOLOGY EQUIPMENT SCHEDULE
ON T7.1 AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
2. ALL EMPTY SPACES ARE FOR OWNER SUPPLIED EQUIPMENT (HUBS, SWITCHES, PATCH
PANELS, ETC.) UNLESS OTHERWISE NOTED.
SC-MPP-1
SC-HWM-1
SC-FDC-1
SC-VWM-1
SC-ER-1
(TYP)
(TYP)
(TYP)
(TYP)
SC-LR-1
(TYP)1
"x
"x
"x
12"x2"
12"x2"
(4) 4" CONDUIT SLEEVES
(2) 3" CONDUITS ROUTED TO
TR-2 OVERHEAD IN CEILING
SPACE FOR FIBER AND
COPPER BACKBONE CABLING
SC-GND-1
SC-TTB
T4.1
NOTES:
1. REFER TO 5/T4.1 FOR PATHWAY PLAN.
AC-SCP-1
SC-VWM-1
SC-ER-1
TV-TVT-4
SC-LR-1
(TYP)
"x
"x
"x
12"x2"
12"x2"
(4) 4" CONDUIT
SLEEVES
(2) 3" CONDUITS ROUTED TO TR-1
OVERHEAD IN CEILING SPACE FOR
FIBER AND COPPER BACKBONE
CABLING
NOTES:
1. PLACE ALL EQUIPMENT IN ITS DESIGNATED RACK AS DEFINED BY THIS LAYOUT UNLESS
OTHERWISE NOTED. ALL EQUIPMENT IS SIZED (BY RACK UNITS) ACCORDING TO THE
BASIS OF DESIGN MANUFACTURER AND ARE THE MINIMUM REQUIREMENTS. COORDINATE
WITH THE OWNER AND THE ENGINEER FOR ANY CHANGES PRIOR TO MODIFICATION OF
THIS LAYOUT. REFER TO THE TECHNOLOGY EQUIPMENT SCHEDULE ON T7.1 AND
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
2. ALL EMPTY SPACES ARE FOR OWNER SUPPLIED EQUIPMENT (HUBS, SWITCHES, PATCH
PANELS, ETC.) UNLESS OTHERWISE NOTED.
SC-MPP-1
SC-HWM-1
SC-FDC-1
SC-VWM-1
SC-ER-1
(TYP)
(TYP)
(TYP)
(TYP)
I O W A
S E
D
PROFESS IONA
14628
L
IC
E N
L E
N G
I N E
E R
Jeffrey A.
Carpenter
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
As indicated
/1
/2
:5 :0
P
M ENLARGED PLANS -
TECHNOLOGY
T4.1
10822.000
N
O R HT
1/4" = 1'-0"1
TECHNOLOGY ROOM 324 LAYOUT - TR-1
1" = 1'-0"3
EQUIPMENT RACK ELEVATION - TR-1
N
O R HT
1/4" = 1'-0"2
TECHNOLOGY ROOM 324 PATHWAY - TR-1
N
O R HT
1/4" = 1'-0"4
TECHNOLOGY ROOM 211 LAYOUT - TR-2
N
O R HT
1/4" = 1'-0"5
TECHNOLOGY ROOM 211 PATHWAY - TR-2
1" = 1'-0"6
EQUIPMENT RACK ELEVATION - TR-2
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE
THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
2882 106TH STREET
DES MOINES, IA 50322
515.334.9906 FAX: 515.334.9908
www.imegcorp.com
SC-MPP-1
OWNER
PROVIDED
EQUIPMENT
SC-FDC-1
SC-MPP-1
OWNER
PROVIDED
EQUIPMENT
SC-FDC-1
SC-FDC-1
AC-SCP-1
AC-DRK-1 AC-DRK-1 AC-DR-S
TV-TVT-4
TV-TVT-4
OWNER
PROVIDED PC
OWNER
PROVIDED
TELEVISION
GROUND
FLOOR
TELECOMMUNICATIONS ROOM (TR-1)
TELECOMMUNICATIONS ROOM (TR-2)
NOTES:
1. THIS RISER IS DIAGRAMMATIC AND MAY NOT SHOW ACTUAL ROUTING OR QUANTITIES
OF MATERIALS SHOWN. THIS RISER IS SHOWN FOR CLARIFICATION OF CONNECTION(S),
LOCATIONS AND CABLE TYPE. ALL INFORMATION OUTLETS ARE TYPICAL OF THE
OUTLETS IN THE AREA SHOWN. REFER TO FLOOR PLANS FOR MORE SPECIFIC ROUTING
INFORMATION. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
2. REFER TO FLOOR PLANS FOR QUANTITY OF CABLES AND JACKS TO BE INSTALLED AT
EACH INFORMATION OUTLET.
3. ALL CABLING SHALL BE 23 GAUGE, 4-PAIR, CATEGORY 6, UNSHIELDED TWISTED PAIR
CABLE UNLESS OTHERWISE NOTED. REFER TO SPECIFICATIONS SECTION 27 15 00 FOR
ADDITIONAL INFORMATION.
CEILING SPACE
4 4
C#-WAP
C#
C#
W
KEYNOTES:
1. REFER TO PLANS FOR QUANTITY OF CABLES AND JACKS TO BE INSTALLED AT EACH
INFORMATION OUTLET. REFER TO THE INFORMATION OUTLET SCHEDULE ON T7.1 FOR
ADDITIONAL INFORMATION. REFER TO ELECTRICAL FLOOR PLANS AND ELECTRICAL
EQUIPMENT SCHEDULE FOR ADDITIONAL INFORMATION.
2. RACK OR CABINET AS DEFINED ON THE TELECOM ROOM LAYOUT. REFER TO THE
TELECOM ROOM REFERENCES MATRIX ON THE COVERPAGE FOR LOCATION.
3. RJ-45 TO RJ45 CATEGORY 6 UTP PATCH CORDS PROVIDED BY CONTRACTOR AND
INSTALLED BY OWNER. REFER TO SPECIFICATIONS.
4. REFER TO COVER SHEET AND FLOOR PLANS FOR TELECOMMUNICATIONS ROOM
LOCATIONS.
5. 24 STRAND SINGLE MODE FIBER COILED IN HANDHOLE BY OWNER TO BE ROUTED INSIDE
AND TERMINATED BY CONTRACTOR. COORDINATE WITH 96 CS/SCXP PRIOR TO
COMMENCING THIS WORK.
6. 24 STRAND SINGLE MODE FIBER.
7. FIBER PATCH CORDS FURNISHED BY CONTRACTOR AND INSTALLED BY OWNER.
C#-WAP
C#
C#
W
WALL MOUNTED
5 X-BUS
+14 VDC
CAT6
CAT6
CAT6
CONSOLE
CIRCUIT
NC-NCP-1
ND2
D
D
D
NOTES:
1. THIS RISER IS DIAGRAMMATIC AND MAY NOT SHOW ACTUAL ROUTING OR QUANTITIES OF MATERIALS SHOWN. THIS RISER IS SHOWN
FOR CLARIFICATION OF CONNECTION(S), LOCATIONS AND CABLE TYPE. ALL INFORMATION OUTLETS ARE TYPICAL OF THE OUTLETS IN THE AREA SHOWN. REFER TO FLOOR PLANS FOR MORE SPECIFIC ROUTING INFORMATION. REFER TO SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS. REFER TO FLOOR PLANS FOR QUANTITY OF DEVICES.
2. POWER FOR CONTROL DEVICES AND LOCAL CONSOLES TO BE PROVIDED IN LOCATIONS AS PER MANUFACTURER'S REQUIREMENTS.
ND2
ND2
ND1
(TYP)
(TYP)
(TYP)
(TYP)
DOOR ROUGH-IN DIAGRAM
(SINGLE DOORS)
NOTES:
1. DOOR # DESIGNATES THE ACCESS CONTROL SCHEME AT EACH DOOR LOCATION. REFER TO T7.1 FOR
REQUIREMENTS.
2. THIS RISER IS DIAGRAMMATIC AND NOT INTENDED TO SHOW ACTUAL ROUTING OR QUANTITIES OF MATERIALS
SHOWN. THIS RISER IS SHOWN FOR CLARIFICATION OF CONNECTION LOCATIONS AND CABLE TYPE. THIS RISER WILL NOT REPLICATE ALL DOOR CONFIGURATIONS. REFER TO SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS.
3. REFER TO ARCHITECTURAL DRAWING FOR DETAILS.
4. POWER FOR THE DOOR HARDWARE WILL COME FROM THE ACCESS CONTROL PANEL.
KEYNOTES:
1. MOUNT AC-SCP-1 ACCORDING TO MANUFACTURER SPECIFICATIONS. REFER TO SPECIFICATION SECTION 28 13 00
FOR ADDITIONAL INFORMATION.
2. ELECTRIC DOOR STRIKE BY OTHERS. CONTRACTOR SHALL PROVIDE 18AWG 2-CONDUCTOR NON-SHIELDED
WIRING AND TERMINATIONS FROM DOOR STRIKE TO SECURITY CONTROLLER.
3. DOOR CONTACT SWITCH AND CABLE. CONTRACTOR SHALL PROVIDE 18AWG 2-CONDUCTOR WIRING FROM
CONTACT SWITCH TO SECURITY CONTROLLER.
4. PROVIDE POWER AS REQUIRED BY MANUFACTURER.
5. TYPICAL WIRELESS DURESS. PROVIDE QUANTITY AS SHOWN ON FLOOR PLANS.
6. PROGRAM EMERGENCY DURESS TO LOCK-DOWN ACCESS CONTROLLED DOORS.
7. CARD READER CABLING. CONTRACTOR SHALL PROVIDE 18AWG 9-CONDUCTOR SHIELDED WIRING AND
TERMINATIONS FROM DOOR STRIKE TO SECURITY CONTROLLER.
8. ELECTRONIC DOOR HARDWARE POWER CABLING. CONTRACTOR SHALL PROVIDE 18AWG 2-CONDUCTOR NON-
SHIELDED WIRING AND TERMINATIONS FROM DOOR STRIKE TO SECURITY CONTROLLER.
9. EMERGENCY DURESS CABLING. CONTRACTOR SHALL PROVIDE 18AWG 2-CONDUCTOR NON-SHIELDED WIRING
AND TERMINATIONS FROM DOOR STRIKE TO SECURITY CONTROLLER.
OWNER
NETWORK
TO HOSPITAL
SERVER
ROOM
CARD READER
AT 48" AFF
A
F F
CONNECT ACCESS CONTROL
PANEL TO FIRE ALARM
CONTROL PANEL VIA AN
ADDRESSABLE RELAY
CR1
EDR 6
PROVIDE CONNECTION TO BUILDING
SERVICE SINGLE MODE FIBER FOR
NOTIFICATIONS TO BE ROUTED TO
CENTRAL SECURITY OFFICE
INTERCONNECT PANELS PER
MANUFACTURER RECOMMENDATION
9 8
REQUEST TO EXIT
CONNECTION (TYP)
NOTES:
1. THIS RISER IS DIAGRAMMATIC AND MAY NOT SHOW
ACTUAL ROUTING OR QUANTITIES OF MATERIALS
SHOWN. THIS RISER IS SHOWN FOR CLARIFICATION OF
CONNECTION(S), LOCATIONS AND CABLE TYPE. ALL
INFORMATION OUTLETS ARE TYPICAL OF THE OUTLETS IN
THE AREA SHOWN. REFER TO DRAWINGS FOR ACTUAL
QUANTITIES OF INFORMATION OUTLETS AND MORE
SPECIFIC ROUTING INFORMATION. REFER TO
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
2. SERVICE PROVIDER TO PROVIDE CATV SYSTEM.
3. ALL CROSS-CONNECTIONS BY SERVICE PROVIDER.
KEYNOTES:
1. RG-6 HORIZONTAL CABLE RUNS FROM
TELECOMMUNICATIONS ROOMS TO OUTLET LOCATIONS
FURNISHED AND INSTALLED BY CONTRACTOR. REFER TO
SPECIFICATIONS FOR CABLE REQUIREMENTS.
2. REFER TO DRAWINGS FOR QUANTITY OF LOCATIONS AND
QUANTITY OF CABLES AND JACKS TO BE INSTALLED AT
EACH INFORMATION OUTLET LOCATION.
3. CONTRACTOR FURNISHED AND INSTALLED RG-11 COAX
CABLE.
4. INCOMING SERVICE CABLE BY SERVICE PROVIDER.
COORDINATE EXACT LOCATION WITH SERVICE
PROVIDER.
TR-2
C#-TV
C#-TV
TR-1
C#-TV
C#-TV
NOTES:
1. THIS FLOW DIAGRAM IS DIAGRAMMATIC AND MAY NOT SHOW ACTUAL ROUTING OR QUANTITIES OF
MATERIALS SHOWN. THIS DIAGRAM IS SHOWN FOR CLARIFICATION OF CONNECTION LOCATIONS AND CABLE TYPE. REFER TO FLOOR PLANS FOR MORE SPECIFIC ROUTING AND QUANTITY INFORMATION.
REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
VGA, HDMI, USB, AUDIO CABLE
(1) 1 1/4" CONDUIT,
POPULATE WITH VGA,
HDMI, USB, AND AUDIO
CABLES
HDMI CABLE
WP1
WP1
REFER TO ARCHITECTURAL DRAWINGS
FOR MOUNTING HEIGHT AND LOCATION
I O W A
S E
D
PROFESS IONA
14628
L
IC
E N
L E
N G
I N E
E R
Jeffrey A.
Carpenter
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
12" = 1'-0"
/1
/2
:5 :0
P
M RISER DIAGRAMS -
TECHNOLOGY
T5.1
10822.000
NO SCALE1
FIBER AND COPPER RISER DIAGRAM
NO SCALE2
NURSE CALL CONTROL MODULE WIRING DIAGRAM
NO SCALE3
ACCESS CONTROL/DURESS RISER DIAGRAM
NO SCALE4
CATV RISER DIAGRAM
NO SCALE5
PC TO TV/MONITOR CONNECTION DIAGRAM
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE
THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
2882 106TH STREET
DES MOINES, IA 50322
515.334.9906 FAX: 515.334.9908
www.imegcorp.com
SC-GND-1
NEAREST
ELECTRICAL
PANEL
METALLIC
CONDUITS
AND SLEEVES
EQUIPMENT
RACK(S)
BUILDING
STEEL
CABLE TRAY
(CONTINUOUS
BOND)
LADDER RACK
(CONTINUOUS
BOND)
SC-GND-1 SC-GND-1
MOLDED POLYESTER -
FIBERGLASS INSULATOR
COPPER GROUND CONDUCTOR
FROM BUILDING SERVICE GROUND.
REFER TO SPECIFICATIONS FOR
DETAILS
TWO HOLE COMPRESSION LUG
NOTES:
1. REFER TO TECHNOLOGY EQUIPMENT SCHEDULE SC-GND-1 FOR WIDTH REQUIREMENTS.
2. REFER TO 2/T6.1 FOR TELECOMMUNICATIONS ROOM BONDING CONNECTION DIAGRAM.
COPPER BONDING CONDUCTOR TO
EQUIPMENT RACKS, CABLE TRAYS &
METALLIC SLEEVES. REFER TO
SPECIFICATIONS FOR DETAILS
BARE COPPER GROUND BAR,
INSULATORS, BRACKETS AND
BONDING PROVIDED BY E.C.
REFER TO TECHNOLOGY
EQUIPMENT SCHEDULE SC-GND-1
5/16" Ø
(TYP)
7/16" Ø
(TYP)
TO ELECTRICAL ENTRANCE FACILITY.
REFER TO 3/T6.1 FOR
TELECOMMUNICATIONS BONDING RISER
DIAGRAM FOR CONTINUATION AND
ADDITIONAL INFORMATION. THIS
CONNECTION ONLY HAPPENS IN THE
TR-1. REFER TO THE COVER SHEET AND
THE FLOOR PLANS FOR TR-1 LOCATION
TELECOMMUNICATIONS BONDING
BACKBONE (TBB). REFER TO 3/T6.1 FOR
TELECOMMUNICATIONS BONDING RISER
DIAGRAM
TELECOMMUNICATIONS
BONDING JUMPER (TBJ)
TELECOMMUNICATIONS ROOM (TR-#), (TYP)
NOTES:
1. THIS FLOW DIAGRAM IS DIAGRAMMATIC AND MAY NOT SHOW ACTUAL ROUTING OR QUANTITIES OF
MATERIALS SHOWN. THIS DIAGRAM IS SHOWN FOR CLARIFICATION OF CONNECTION LOCATIONS
AND CABLE TYPE. REFER TO FLOOR PLANS FOR MORE SPECIFIC ROUTING AND QUANTITY
INFORMATION. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
2. ALL CONDUCTORS IN THE TELECOMMUNICATIONS SYSTEM SHALL BE 3/0 AWG COPPER (GREEN OR
MARKED WITH A DISTINCTIVE GREEN COLOR) UNLESS CONDUCTOR DISTANCE IS LESS THAN 66
FEET. REFER TO 3/T6.1 BONDING CONDUCTOR SIZING SCHEDULE FOR SIZING CRITERIA FOR
CONDUCTORS LESS THAN 66 FEET IN LENGTH. REFER TO SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS..
3. ALL BONDING CONDUCTORS AND BONDING JUMPERS SHALL BE CONNECTED BY COMPRESSION
LUGS, EXOTHERMIC WELDING, OR IRREVERSIBLE COMMUNICATIONS BONDING CONDUCTORS TO
EQUIPMENT. WHERE NECESSARY REMOVE PAINT AND/OR USE PAINT-PIERCING WASHERS TO
PROVIDE PROPER ELECTRICAL BOND AT ALL CONNECTIONS.
4. BONDING TO PAINT TREATED SURFACES SHALL UTILIZE PANT PIERCING LUGS.
5. REFER TO THE TELECOMMUNICATIONS BONDING BUS BAR DETAIL ON 1/T6.1 FOR ADDITIONAL
INFORMATION FOR THE SC-GND-1.
KEYNOTES:
1. REFER TO T0.1 FOR TELECOMMUNICATIONS ROOM NUMBERS AND LOCATIONS.
TELECOMMUNICATIONS
BONDING JUMPER (TBJ)
CONDUCTOR
LENGTH IN FEET
BONDING CONDUCTOR SIZING SCHEDULE
MINIMUM ACCEPTABLE
SIZE - AWG
LESS THAN 13' 6
14' - 20' 4
21' - 26' 3
27' - 33' 2
34' - 41' 1
42' - 52' 1/0
53' - 66' 2/0
3/0
NOTES:
1. THIS RISER IS DIAGRAMMATIC AND MAY NOT SHOW ACTUAL ROUTING OR
QUANTITIES OF MATERIALS SHOWN. THIS RISER IS SHOWN FOR
CLARIFICATION OF CONNECTION LOCATIONS AND CABLE TYPE. REFER TO
FLOOR PLANS FOR SPECIFIC ROUTING AND QUANTITY INFORMATION.
REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
2. ALL CONDUCTORS IN THE TELECOMMUNICATIONS BONDING SYSTEM
SHALL BE MINIMUM SIZE OF 3/0 AWG PLENUM RATED COPPER
CONDUCTORS (GREEN OR MARKED WITH A DISTINCTIVE GREEN COLOR)
UNLESS CONDUCTOR LENGTH IS LESS THAN 66 FEET. REFER TO BONDING
CONDUCTOR SIZING SCHEDULE FOR SIZING CRITERIA FOR CONDUCTORS.
3. BONDING CONDUCTORS AND BONDING JUMPERS SHALL BE CONNECTED
BY EXOTHERMIC WELDING, LISTED PRESSURE CONNECTORS, LISTED
CLAMPS OR OTHER LISTED MEANS. SOLDER IS NOT AN ACCEPTABLE
MEANS OF CONNECTION. SHEET METAL SCREWS SHALL NOT BE USED TO
CONNECT COMMUNICATIONS BONDING CONDUCTORS TO EQUIPMENT.
4. REFER TO 2/T6.1 FOR TELECOMMUNICATIONS ROOM BONDING
CONNECTION DIAGRAM.
5. REFER TO T0.1 FOR TELECOMMUNICATIONS ROOM REFERENCES.
GROUND
FLOOR
EXISTING ELECTRICAL
ENTRANCE FACILITY
EXISTING GROUNDING ELECTRODE
CONDUCTOR. COORDINATE
CONNECTION WITH ELECTRICAL
CONTRACTOR
EXISTING ELECTRICAL
GROUNDING
ELECTRODE SYSTEM
TELECOMMUNICATIONS
BONDING BACKBONE
(TBB) (TYP)
BONDING CONDUCTOR FOR TELECOMMUNICATIONS (BCT). BCT SHALL
BE AT LEAST THE SAME SIZE AS THE TBB OR LARGER. REFER TO
BONDING CONDUCTOR SIZING SCHEDULE FOR SIZING REQUIREMENTS.
THIS CONNECTION OCCURS IN THE TR-1 ROOM ONLY
TR-1 TR-2
67' - 84'
REFER TO
ARCHITECTURAL
PLANS FOR WALL
CONSTRUCTION
SINGLE GANG PLASTER
RING TO COME WITHIN 1/8"
OF FINAL SURFACE
STUD
1 1/4" EMT CONDUIT. REFER
TO DETAIL NOTES FOR
ADDITIONAL REQUIREMENTS
NYLON BUSHING
J-HOOK
NOTES:
1. 1 1/4" EMT CONDUIT SHALL STUB UP TO NEAREST ACCESSIBLE CEILING AND TERMINATE ORIENTED
HORIZONTALLY AT THE HEIGHT OF THE ASSOCIATED CABLE TRAY OR J-HOOK ROUTE. CONDUIT RUN SHALL NOT CONTAIN MORE THAN 180 DEGREES OF BEND BETWEEN ACCESSIBLE JUNCTION BOXES OR
BETWEEN JUNCTION BOX AND END OF CONDUIT.
2. WHERE CONDUIT STUB IS LOCATED IN A ROOM WITH AN ACCESSIBLE CEILING AND IS NOT REQUIRED TO RUN TO CABLE ROUTE LOCATED OUTSIDE THE ROOM, STUB MUST TERMINATE ABOVE THE ACCESSIBLE CEILING WITH A 90-DEGREE BEND AT THE TOP ORIENTED IN TO THE ROOM AT THE HEIGHT OF THE
ASSOCIATED CABLE TRAY OR J-HOOK ROUTE IN THE ROOM.
3. ALL STUBS MUST BE FITTED WITH A NYLON BUSHING ON EACH END OF THE CONDUIT.
4. INSTALLING CONTRACTOR SHALL FURNISH AND INSTALL FIRESTOP MATERIALS FOR TECHNOLOGY
ROUGH-INS PER PROJECT REQUIREMENTS. REFER TO SPECIFICATIONS FOR FIRESTOP REQUIREMENTS.
NOTES:
1. CONFIGURATIONS SHOWN IN THE DETAIL ABOVE ARE DIAGRAMMATIC, INTENDED TO DESCRIBE THE CONTROLLED SECURITY SCHEME ROUGH-IN
REQUIREMENTS OF THE DOORS. DETAILS ABOVE MAY NOT ACCURATELY REPRESENT DOOR SIZE, DOOR SWING, DOOR HARDWARE, OR DOOR FUNCTIONALITY. REFER TO ARCHITECTURAL DOOR HARDWARE SCHEDULE, DOOR HARDWARE GROUPS AND DOOR HARDWARE SPECIFICATIONS
FOR COMPLETE INFORMATION. MIRROR THE DETAIL AS REQUIRED.
2. ROUGH IN SHOWN IN THE DETAIL ABOVE REPRESENTS THE MINIMUM REQUIREMENTS FOR ALL CONTROLLED SECURITY SYSTEM DEVICES AND CABLING UNLESS OTHERWISE NOTED. COORDINATE EXACT REQUIREMENTS WITH SELECTED DOOR MATERIALS, DOOR HARDWARE, AND
CONTROLLED SECURITY DEVICES AND CABLING PRIOR TO INSTALLATION.
3. ALL CABLING IN WALLS AND WHERE EXPOSED ON VERTICAL SURFACES SHALL BE INSTALLED IN EMT CONDUIT OR SURFACE MOUNT RACEWAY.
CABLING ROUTED HORIZONTALLY ABOVE THE ACCESSIBLE CEILING MAY BE INSTALLED FREE-AIR CABLING PROPERLY RATED FOR THE CEILING
ENVIRONMENT.
4. THE ELECTRICAL OR SECURITY CONTRACTOR SHALL NOT MODIFY ANY FIRE RATED DOOR AND/OR DOOR FRAME. REFER TO THE ARCHITECTURAL DOOR SCHEDULE, DOOR HARDWARE SCHEDULE, AND DOOR HARDWARE SPECIFICATION FOR ADDITIONAL INFORMATION. MODIFICATION TO ANY FIRE RATED DOOR AND/OR FRAME WILL REQUIRE A RE-CERTIFICATION OF THE DOOR AND FRAME WITH THE LOCAL AUTHORITY HAVING
JURISDICTION (AHJ).
5. INSTALLING CONTRACTOR SHALL FURNISH AND INSTALL FIRESTOP MATERIALS FOR ALL CONTROLLED SECURITY SCHEME ROUGH-INS PER PROJECT REQUIREMENTS. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
6. REFER TO THE ACCESS CONTROL/DURESS RISER DIAGRAM ON T5.1 FOR CABLING REQUIREMENTS AND THE CONTROLLED SECURITY SCHEME
SCHEDULE ON T7.1 FOR ADDITIONAL INFORMATION.
7. INSTALLATION SHALL INCLUDE ALL POWER REQUIRED FOR SYSTEM OPERATION INCLUDING +120VAC ORIGINATING AT ACCESS CONTROL PANEL.
REFER TO THE SUGGESTED MATRIX OF SCOPE RESPONSIBILITY FOR ADDITIONAL INFORMATION.
KEYNOTES:
1. PROVIDE JUNCTION BOXES IN THE DOOR FRAME WHERE SHOWN ON THIS DETAIL. ROUGH-IN SHALL BE PROVIDED WHETHER THE CURRENT
SECURITY SCHEME UTILIZES THEM OR NOT. ALL CONDUITS SHALL BE EMT CONDUIT UNLESS OTHERWISE NOTED. FLEXIBLE CONDUIT OF ANY TYPE WILL NOT BE ACCEPTED. COORDINATE INSTALLATION WITH ON-SITE DOOR FRAME INSTALLATION CONTRACTOR.
2. ALL DOOR POSITION SWITCHES ARE REQUIRED TO BE RECESSED UNLESS OTHERWISE NOTED. ELECTRIC HINGE MONITORS ARE NOT AN
ACCEPTABLE REPLACEMENT FOR THE RECESSED DOOR POSITION SWITCH.
3. DOUBLE GANG BACKBOX WITH SINGLE GANG PLASTER RING. REFER TO FLOOR PLAN(S) FOR ACTUAL CREDENTIAL READER TYPE AND ROUGH-IN
LOCATIONS.
4. CONDUIT SHALL ROUTE FROM THE CREDENTIAL READER TO THE SECURE SIDE OF THE DOOR. CONDUIT SHALL ROUTE A MINIMUM OF 12" FROM THE
JUNCTION BOX. PROVIDE A NYLON BUSHING ON CONDUIT END.
5. MOUNT A MINIMUM 4" SQUARE 2-1/8" DEEP JUNCTION BOX WITH BLANK COVER PLATE ON THE SECURE SIDE OF THE DOOR ABOVE ACCESSIBLE CEILING. INSTALLING CONTRACTOR SHALL SIZE THE JUNCTION BOXES PER SYSTEM INSTALLATION REQUIREMENTS AND APPLICABLE CODES.
MAINTAIN ACCESS TO THE JUNCTION BOX.
6. PROVIDE A HORIZONTALLY MOUNTED SINGLE GANG BACKBOX FOR THE REQUEST TO EXIT SENSOR. REFER TO THE CONTROLLED SECURITY SCHEME
SCHEDULE ON T7.1 FOR DOORS THAT REQUIRE THIS ROUGH-IN.
7. CONDUIT SHALL ROUTE A MINIMUM OF 12" FROM THE JUNCTION BOX. PROVIDE A NYLON BUSHING ON CONDUIT END.
8. CONDUIT INSTALLED IN PERMANENT MULLIONS ONLY. REFER TO THE ARCHITECTURAL DOOR SCHEDULE AND DOOR HARDWARE GROUPS FOR
LOCATIONS THAT REQUIRE THIS ROUGH-IN. PROVIDE A NYLON BUSHING ON THE CONDUIT END.
DOOR FRAME ROUGH-IN DIAGRAM
(ALL SINGLE DOORS)
DOOR FRAME ROUGH-IN DIAGRAM
(ALL DOUBLE DOORS WITH OR WITHOUT MULLION)
FINISHED ACCESSIBLE
CEILING
MINIMUM 3/4" EMT CONDUIT
TO ABOVE THE
ACCESSIBLE CEILING
FINISHED FLOOR
CREDENTIAL READER
ROUGH-IN 3
DOOR CONTACT
ROUGH-IN
MINIMUM 1" EMT
CONDUIT
REQUEST TO
EXIT DEVICE
ROUGH-IN
1/2" EMT CONDUIT
MINIMUM (TYP.)
MINIMUM 1" EMT
CONDUIT
MINIMUM 3/4" EMT
CONDUIT TO ABOVE THE
ACCESSIBLE CEILING
CREDENTIAL READER
ROUGH-IN 3
REQUEST TO
EXIT DEVICE
ROUGH-IN
DOOR CONTACT
ROUGH-IN
5 5
4" 4" 4"
7 7
I O W A
S E
D
PROFESS IONA
14628
L
IC
E N
L E
N G
I N E
E R
Jeffrey A.
Carpenter
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
As indicated
/1
/2
:5 :0
P
M DETAILS -
TECHNOLOGY
T6.1
10822.000
NO SCALE1
TELECOMMUNICATIONS BONDING BUS BAR DETAIL
NO SCALE2
TELECOMMUNICATIONS
ROOM BONDING CONNECTION DIAGRAM
NO SCALE3
TELECOMMUNICATIONS BONDING RISER DIAGRAM
NO SCALE4
TECHNOLOGY ROUGH-IN MOUNTING DETAIL
NO SCALE5
CONTROLLED SECURITY SCHEME DOOR ROUGH-IN DETAIL
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE
THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
2882 106TH STREET
DES MOINES, IA 50322
515.334.9906 FAX: 515.334.9908
www.imegcorp.com
PAIR 2
PAIR 3
WG WOG O
ANSI/TIA/EIA T568A
PIN/PAIR ASSIGNMENT
PAIR 1 PAIR 4
BL WBL WBR BR
1 32 4 5 6 7 8
2-Port Faceplate
IDENTIFICATION
IDENTIFICATION
IDENTIFICATION
IDENTIFICATION
1 2
4-Port Faceplate
REFER TO SPECIFICATIONS FOR
IDENTIFICATION REQUIREMENTS (TYP.)
NUMBER INDICATES
FACEPLATE POSITION (TYP.)
I O W A
S E
D
PROFESS IONA
14628
L
IC
E N
L E
N G
I N E
E R
Jeffrey A.
Carpenter
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
12" = 1'-0"
/1
/2
:5 :0
P
M SCHEDULES -
TECHNOLOGY
T7.1
10822.000
THE EQUIPMENT LIST ABBREVIATIONS AND THE GENERAL TECHNOLOGY EQUIPMENT SCHEDULE ARE FOR THE CONVENIENCE OF THE CONTRACTOR. EACH CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF QUANTITIES AND SHALL FURNISH ALL MATERIAL REQUIRED, WHETHER SPECIFIED OR NOT, TO PRODUCE A SATISFACTORY WORKING SYSTEM.
CATALOG NUMBERS ARE NOT TO BE CONSIDERED COMPLETE BUT ARE GIVEN ONLY TO AID THE CONTRACTOR IN THE SEARCH FOR MATERIAL. NO MATERIAL SHALL BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. EACH CONTRACTOR SHALL FIRST READ THE COMPLETE DESCRIPTION OF THE MATERIAL ON THESE DRAWINGS AND SPECIFICATIONS.
THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN. "STANDARD COLOR" INDICATES FACTORY FINISH AVAILABLE AT NO ADDITIONAL CHARGE.
GENERAL TECHNOLOGY EQUIPMENT SCHEDULE
EQUIPMENT LIST
ABBREVIATION EQUIPMENT LIST DESCRIPTION
EQUIPMENT LIST
MANUFACTURER AND MODEL
SC-VWM-1 VERTICAL WIRE MANAGER, REFER TO SC-ER-1 FOR ADDITIONAL INFORMATION. PANDUIT
WMPV45E
ORTRONICS
SYSTIMAX
SC-WP-W WALL MOUNTED INFORMATION OUTLET CONTAINING (1) RJ-45 JACK FOR VOICE AT +54" AFF FOR WALL HUNG PHONE. PROVIDE
WITH STAINLESS STEEL FACEPLATE, MATING LUGS.
INSTALL INFORMATION OUTLET IN A 4" SQUARE BACKBOX WITH A SINGLE GANG PLASTER RING. INSTALL A 1 1/4" EMT CONDUIT
ABOVE ACCESSIBLE CEILING.
HUBBELL
P630S1G
BELDEN
SYSTIMAX
SIEMON
HUBBELL/MOHAWK
ORTRONICS
MOLEX
LEVITON
TV-TVT-4 4-PORT DIRECTIONAL COUPLER/TAP. 5-1000 MHZ FREQUENCY RANGE, RF SHIELDING, DIE CAST HOUSING, ISOLATION OUTPUTS
AND THRU-LINE LOSSES WILL VARY. REFER TO 4/T5.1 FOR ADDITIONAL INFORMATION.
VALUES ARE PROVIDED PER CONTRACTOR REQUIREMENTS/DESIGN.
BLONDER TONGUE
SRT-4
RL DRAKE
CHANNEL MASTER
THE EQUIPMENT LIST ABBREVIATIONS AND THE GENERAL TECHNOLOGY EQUIPMENT SCHEDULE ARE FOR THE CONVENIENCE OF THE CONTRACTOR. EACH CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF QUANTITIES AND SHALL FURNISH ALL MATERIAL REQUIRED, WHETHER SPECIFIED OR NOT, TO PRODUCE A SATISFACTORY WORKING SYSTEM.
CATALOG NUMBERS ARE NOT TO BE CONSIDERED COMPLETE BUT ARE GIVEN ONLY TO AID THE CONTRACTOR IN THE SEARCH FOR MATERIAL. NO MATERIAL SHALL BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. EACH CONTRACTOR SHALL FIRST READ THE COMPLETE DESCRIPTION OF THE MATERIAL ON THESE DRAWINGS AND SPECIFICATIONS.
THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN. "STANDARD COLOR" INDICATES FACTORY FINISH AVAILABLE AT NO ADDITIONAL CHARGE.
GENERAL TECHNOLOGY EQUIPMENT SCHEDULE
EQUIPMENT LIST
ABBREVIATION EQUIPMENT LIST DESCRIPTION
EQUIPMENT LIST
MANUFACTURER AND MODEL
AC-CR1-W CARD READER. PROVIDED AS INTEGRAL PART OF SECURITY MANAGEMENT SYSTEM. REFER TO CONTROLLED SECURITY SCHEME (CSS) TYPE SCHEDULE ON T7.1 FOR ADDITIONAL INFORMATION. CARD READERS SHOWN ON PLANS TO IDENTIFY INTENDED MOUNTING LOCATION. REFER TO SPECIFICATION SECTION 28 13 00 FOR COMPLETE INFORMATION.
IDENTIV
uTRUST SCRAMBLEPAD
AC-DR-S ACCESS CONTROL DURESS/PANIC BUTTON, SURFACE MOUNT. INVONICS
EN1235D
AC-DRK-1 WIRELESS HIGH POWER DURESS BUTTON RECIVER/KEYPAD, PROVIDES 2 WAY, SUPERVISED COMMUNICATION USING 900 MHZ FREQUENCY HOPPING SPREAD SPECTRUM, SUPPORTS UP TO 32 WIRELESS ZONES, RECIEVER SHALL PROVIDE AUDIBLE ALARM UPON RECEIPT OF DURESS CONDITION FROM ANY TRANSMITTER. RECEIVER SHALL DISPLAY ORIGINATING ZONE AND NAME INFORMATION OF SIGNALING TRANSMITTER. PROVIDE WITH BLUE LIGHT TO VISUALLY
INDICATE ALARM CONDITION.
ADVANTOR
INFRATOUCH
INNOVONICS
EN4232MR
AC-EDR-W WALL MOUNTED ELECTRIC DOOR SWITCH. MOMENTARY PUSH BUTTON. 1" GUARD RING. CONTACTS RATED AT 4 AMPS AT 28VDC. MOUNT UNDER COUNTER TOP AND PROVIDE ROUGH-IN/PATHWAY AT NEAREST WALL TO ABOVE CEILING FOR ROUTING
OF CABLING.
ASSA ABLOY
TS-18
AC-SCP-1 ACCESS CONTROL SECURITY PANEL, REFER TO SPECIFICATION SECTION 28 13 00 FOR COMPLETE INFORMATION. OWNERS EXISTING SMS WORKSTATION AT THE MONITORING FACILITY SHALL BE USED FOR ADMINISTRATION AND MAINTENANCE.
IDENTIV
HIRSCH MX-8
AV-PRO-1 VIDEO PROJECTOR, 1920X1200 PIXELS RESOLUTION, 16:10 ASPECT RATIO, 5200 LUMENS, 20000:1 CONTRAST RATIO, 20000 HOURS LIFE AT HALF LUMINANCE. 1-CHIP DLP LASER DIODE. (2) HDMI IN, (1) DIGITAL LINK IN, (1) LAN IN, (2) COMPUTER IN, (1) SERIAL IN, (1) DVI-D IN, (2) AUDIO IN, (1) VIDEO IN, (1) VARIABLE AUDIO OUT. DIMENSIONS (WXHXD) : 19 5/8˝ x 6 5/8˝*5 x 19 3/8˝.
AUDIO INPUT, FREQUENCY RESPONSE: 20 HZ - 20 KHZ @ +0.5DB. POWER SUPPLY: INPUT: 100-240 VAC, 50-60 HZ OUTPUT: 24 VDC, 1.25A.
PANASONIC
PT-RZ570
CHRISTIE
AV-PRO-MNT-1 CEILING MOUNTED PROJECTOR MOUNT. POLE MOUNT WITH UNIVERSAL HBU BRACKET, ROLL, PITCH AND YAW ADJUSTMENTS (ROLL: +3°, PITCH: +15°, YAW: 360°), 25 lbs WEIGHT CAPACITY, COMPACT DESIGN, OVERALL DIMENSION(HXWXD) :1.8" x 4.4" x 5.1".
CHIEF
RSMAU
PREMIER
PEERLESS
AV-VPS-1 PROJECTION SCREEN, ELECTRIC 69"(H) X 110"(W) CEILING RECESSED, ELECTRICALLY OPERATED WITH QUICK CONNECT MALE CONNECTOR ON THE MOTOR. TENSIONING SYSTEM PROVIDES AN EXTRA FLAT SURFACE FOR OPTIMUM IMAGE QUALITY WITH HEAVY DUTY ALUMINUM EXTRUDED PLENUM ENCLOSURE. PROVIDE WITH BUILT-IN LOW VOLTAGE MOTOR CONTROL, SILENT
MOTOR OPTION. PROVIDE AND INSTALL ALL CONTROL CABLING AND PROGRAM AS REQUIRED.
PROVIDE WITH HD PROGRESSIVE 0.9 SCREEN MATERIAL.
DA-LITE
TENSIONED ADVANTAGE
ELECTROL
DRAPER
STEWART
AV-WP1-W PASSIVE WALLPLATE, CEILING MOUNT OR WALL MOUNT, (1) 3.5 mm STEREO AUDIO CONNECTOR, (1) VGA, AND (1) HDMI.
INSTALL INFORMATION OUTLET IN A 5" SQUARE BACKBOX WITH A SINGLE GANG PLASTER RING. INSTALL A (1) 1 1/4" EMT CONDUIT AND (1) 1" EMT CONDUIT TO ABOVE ACCESSIBLE CEILING. CABLE ROUTING FROM CONDUIT STUB TO NEAREST CABLE
TRAY SHALL BE VIA J-HOOK WIRE-WAY, REFER TO 4/T6.1 FOR ADDITIONAL INFORMATION.
CABLE WALLPLATES TOGETHER WITH USB, VGA, HDMI CABLE AND SHIELDED AUDIO CABLE. USED TO CONNECT PERSONAL COMPUTER VIDEO AND AUDIO (IF REQUIRED) TO DISPLAY DEVICE. REFER TO 5/T5.1 FOR CONNECTION DIAGRAM.
C2G
PN 39707
NC-D-W NURSE CALL SINGLE COMPARTMENT DOME LIGHT, WALL MOUNT ABOVE DOOR. REFER TO SPECIFICATION SECTION 27 52 23. SIMPLEX
EZ CARE
WEST-COM
NC-NCP-1 NURSE CALL CONTROL PANEL, WALL MOUNT. REFER TO SPECIFICATION SECTION 27 52 23 AND 2/T5.1 FOR RISER DIAGRAM. SIMPLEX
EZ CARE
WEST-COM
NC-ND1-W NURSE CALL MASTER STATION. DESK MOUNT. MICROPROCESSOR BASED WITH VISUAL AND AUDIBLE INDICATION OF PATIENT, NURSE ASSIST, STAFF ASSIST AND ALL EMERGENCY CALLS. REFER TO SPECIFICATION SECTION 27 52 23.
SIMPLEX
EZ CARE
WEST-COM
NC-ND2-W NURSE CALL PULL CORD INITIATION STATION WITH TONE AND VISUAL INDICATION FROM MASTER STATION ND1. REFER TO
SPECIFICATION SECTION 27 52 23.
SIMPLEX
EZ CARE
WEST-COM
SC-CT-1 CABLE TRAY, WIRE MESH TYPE, 4" LOADING DEPTH, 12" WIDTH, COMPLETE WITH ALL FITTINGS AND MOUNTING HARDWARE.
PROVIDE TRAPEZE SUPPORT WITH PLASTIC RETAINER. CUTTING OF THE MESH CABLE TRAY SHALL BE DONE WITH OFFSET BOLT CUTTERS ONLY. 10' MAXIMUM SUPPORT SPAN. EITHER SPLICE WASHERS OR TERMINAL GROUND SUPPORT AND JUMPER WIRE SHALL BE USED TO ATTAIN GROUNDING CONTINUITY THROUGHOUT. Z-BRACKETS SHALL BE USED FOR WALL MOUNTED APPLICATIONS. REFER TO MANUFACTURERS INSTALLATION INSTRUCTIONS AND SPECIFICATION SECTION 27 05 28 FOR
ADDITIONAL INFORMATION.
COOPER B-LINE
FLEXTRAY FT 4x12x10
MONO-SYSTEMS
CABLOFIL
SC-ER-1 EQUIPMENT RACK, 84" HIGH, STANDARD 19" MOUNTING SPACE, 4" WIDE x 6" DEEP UPRIGHTS FEATURING PASS-THRU HOLES ON FRONT AND SIDES FOR CABLE MANAGEMENT. PROVIDE TWO PER RACK, MODULAR D-RINGS ON FRONT OF VERTICAL ORGANIZERS. TOP CENTER WATERFALL, TOP CHANNEL PATHWAY FOR LADDER RACK, PROVIDES (45) 1.75" MOUNTING SPACES.
CHATSWORTH
46353-703
ORTRONICS
HOMACO INC.
HUBBELL
SC-FDC-1 OPTICAL FIBER DISTRIBUTION CABINET, HIGH DENSITY, MINIMUM 24 FIBER CAPACITY, PROVIDE WITH CLAMP AND GROUNDING KIT, COUPLING PANELS, LC CONNECTORS, COUPLINGS AND JUMPERS. REQUIRES (2) 1.75" MOUNTING SPACES. PROVIDE
HARDWARE TO MOUNT (1) SC-FDC-1 IN SC-ER-1 AND (1) SC-FDC-1 ON THE WALL.
CORNING
CCH
ORTRONICS
THE SIEMON COMPANY
SYSTIMAX COMPANY
SC-GND-1 WALL MOUNT GROUND BAR. 4" H X 12" L X 1/4" D COPPER, ELECTRICALLY ISOLATED BY INSULATIOS INTEGRAL TO MOUNTING BRACKETS. PROVIDE UNIT CONFIGURED WITH SIXTEEN (16) SETS OF 5/16" HOLES SPACED 5/8" ON CENTER TO ACCOMMODATE "A" SPACED TWO-HOLE COMPRESSION LUGS AND THREE (3) SETS OF 7/16" HOLES SPACED 1" ON CENTER TO ACCOMMODATE "C" SPACED TWO-HOLE COMPRESSION LUGS. ANSI/EIA/TIA-607 AND BICSI COMPLIANT. UL LISTED. REFER TO 1/T6.1 FOR
ADDITIONAL INFORMATION.
CHATSWORTH PRODUCTS
40153-012
PANDUIT
ERICO
HARGER
SC-HWM-1 HORIZONTAL WIRE MANAGEMENT, SINGLE-SIDED, 3.5"H x 19" W x 8.2" D, PROVIDE WITH COVER. REQUIRES (2) 1.75" MOUNTING
SPACE.
CHATSWORTH
35441-702
ORTRONICS
SYSTIMAX
SC-IO-C INFORMATION OUTLET, SURFACE MOUNT, 2-PORT AS INDICATED ON DRAWINGS AND INFORMATION OUTLET SCHEDULE. REFER
TO INFORMATION OUTLET SCHEDULE ON T7.1 FOR PIN CONFIGURATION INFORMATION.
" # " INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION AS INDICATED ON THE DRAWINGS. REFER TO INFORMATION
OUTLET SCHEDULE ON T7.1 FOR ADDITIONAL INFORMATION.
INSTALL INFORMATION OUTLET IN A 4" SQUARE BACKBOX WITH A SINGLE GANG PLASTER RING. MOUNT TO CLOSEST STRUCTURE ELEMENTS (EX. COLUMN). INSTALL A DELUXE CORD GRIP FOR STRAIN RELIEF ON UTP CABLE. PROVIDE 20' COIL OF UTP CABLE AT WIRELESS OUTLET LOCATION. INSTALL A 1 1/4" EMT CONDUIT 6" BEYOND BOX AND TERMINATE WITH NYLON BUSHING. PROVIDE REMOVABLE BLANK INSERTS FOR UNUSED PORTS. ROUTE CABLE TO NEAREST CABLE TRAY VIA J-HOOK
WIREWAY.
COVERPLATE:
HUBBELL
IBS2 SERIES
JACK(CAT 6):
HXJ6 SERIES
BELDEN/CDT
SYSTIMAX
SIEMON
HUBBELL/MOHAWK
BERK-TEK ORTRONICS
MOLEX
LEVITON NEXTLAN
PANDUIT
SC-IO-F INFORMATION OUTLET, FLOORBOX OR POKE-THROUGH MOUNT, 4-PORT COVERPLATE AS INDICATED ON DRAWINGS, REFER TO
INFORMATION OUTLET SCHEDULE ON SHEET T7.1 FOR PIN CONFIGURATION.
" # " INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION AS INDICATED ON THE PLANS. REFER TO INFORMATION
OUTLET SCHEDULE.
INSTALL INFORMATION OUTLET IN E.C. PROVIDED FLOORBOX. PROVIDE ADAPTER PLATE FOR 106-TYPE FACEPLATE WHERE REQUIRED. COORDINATE ADDITIONAL MOUNTING REQUIREMENTS WITH E.C. PROVIDE REMOVABLE BLANK INSERTS FOR UNUSED PORTS (PANDUIT CMB OR APPROVED EQUAL). ROUTE CONDUIT TO NEAREST STUD WALL AND ROUTE TO ABOVE
ACCESSIBLE CEILING.
REFER TO ELECTRICAL SPECIFICATION FOR FLOORBOX AND ROUGH-IN DESCRIPTION.
CABLE ROUTING FROM CONDUIT STUB TO NEAREST CABLE TRAY SHALL BE VIA J HOOK WIREWAY, REFER TO 4/T6.1 FOR
ADDITIONAL INFORMATION.
COVERPLATE:
HUBBELL
IPF SERIES
JACK(CAT 6):
HXJ6 SERIES
F-CONNECTOR:
SFF SERIES
BELDEN/CDT
SYSTIMAX
SIEMON
HUBBELL/MOHAWK
BERK-TEK ORTRONICS
MOLEX
LEVITON NEXTLAN
PANDUIT
SC-IO-W INFORMATION OUTLET, ANGLED WALL MOUNT, 1, 2 OR 4-PORT COVERPLATE AS INDICATED ON DRAWINGS, REFER TO
INFORMATION OUTLET SCHEDULE ON SHEET T7.1 FOR PIN CONFIGURATION.
" # " INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION AS INDICATED ON THE PLANS. REFER TO INFORMATION
OUTLET SCHEDULE ON T7.1.
" TV "INDICATES TELEVISION SERVICE OUTLET. CABLE OUTLET WITH RATED RG-6, 75 OHM COAX CABLE. TERMINATE ON F-STYLE
CONNECTOR. INSTALL IN 1-PORT COVER PLATE.
INSTALL INFORMATION OUTLET IN A 5" SQUARE BACKBOX WITH A SINGLE GANG PLASTER RING. INSTALL A 1 1/4" EMT CONDUIT TO ABOVE ACCESSIBLE CEILING. CABLE ROUTING FROM CONDUIT STUB TO NEAREST CABLE TRAY SHALL BE VIA J-HOOK
WIREWAY, REFER TO 4/T6.1 FOR ADDITIONAL INFORMATION.
COVERPLATE:
HUBBELL
AFP SERIES
JACK(CAT 6):
HXJ6 SERIES
F-CONNECTOR:
SFF SERIES
BELDEN/CDT
SYSTIMAX
SIEMON
HUBBELL/MOHAWK
BERK-TEK ORTRONICS
MOLEX
LEVITON NEXTLAN
PANDUIT
SC-LR-1 LADDER RACK, 12" W TUBULAR STEEL CONSTRUCTION, RUST RESISTANT ENAMEL FINISH, GRAY IN COLOR. REMOVE SHARP BURRS FROM LADDER RACK AND REPAINT ALL AREAS THAT HAVE BEEN FIELD MODIFIED, CUT OR EXPOSED. U.L. LISTED.
CHATSWORTH
10250-112
HUBBELL
MONO-SYSTEMS
CABLOFIL
SC-MPP-1 MODULAR PATCH PANEL, 48 MODULAR RJ-45 TERMINATIONS, MOUNTS DIRECTLY TO EIA/TIA STANDARD 19" RELAY RACK, PORT IDENTIFICATION NUMBERS, PROVIDED WITH COLOR CODING AND LABEL HOLDER KITS, U.L. LISTED. REQUIRES (2) 1.75"
MOUNTING SPACES.
HUBBELL
HP648 SERIES
BELDEN/CDT
SYSTIMAX
SIEMON
HUBBELL/MOHAWK
BERK-TEK ORTRONICS
MOLEX
LEVITON NEXTLAN
PANDUIT
SC-RI-W TECHNOLOGY ROUGH-IN, FLUSH MOUNT ON WALL OR AS NOTED IN PLANS, ALL TECHNOLOGY ROUGH-INS SHALL HAVE (1) 4" SQUARE BACKBOX WITH SINGLE GANG PLASTER RING, APPROPRIATE…