Attachment 4 - Drawings 08 Fire Alarm.pdf

PDF 750 KB Posted

Attached to
Eglin NICoE Initial Outfitting Project
Solicitation number
W9127S20Q6000
Issued by

About this file

This is a combined synopsis and solicitation for a construction project. The U.S. Army Corps of Engineers seeks to outfit the Eglin Neuroscience Center of Excellence Initial Outfitting Project at Eglin Air Force Base in Florida. Interested Service-Disabled Veteran-Owned Small Businesses must submit quotes by January 8th for work including mechanical, electrical, and fire protection systems. A site visit is scheduled for December 4th, and notice of intent to attend is due by November 29th. The NAICS code is 337127 and size standard is 500 employees. This procurement will follow simplified acquisition procedures under FAR Part 13 for commercial items under FAR Part 12.

The solicitation provides contact information for the site visit and requests contractor data for base access. Additional details on entrance to the base will be provided to confirmed attendees. The document and incorporated provisions and clauses reflect updates from Federal Acquisition Circular 2019-06.

View the file

Other files

File Type Posted
Amendment 2 Attachment 10 - Site Visit Sign-In.pdf PDF
Amendment 2 Attachment 3A - Project Room Contents_25Dec2019.pdf PDF
Amendment 2 Attachment 2A - Cut Sheets (Salient Features_Specs).pdf PDF
Amendment 2 Attachment 9 - Sound_Masking_Systems (ProjNet ID 8304607).pdf PDF
Amendment 2 Attachment 11 - ProjNet Questions_Answers.pdf PDF
W9127S20Q6000 AMENDMENT 0002.pdf PDF
Amendment 2 Attachment 1 - Bid Schedule.xlsx XLSX spreadsheet
Amendment 2 Attachment 8 - ESS_Video_Surveillance_VSS (ProjNet ID 8304557).pdf PDF
Amendment 1 Attachment 2 - Cut Sheets (Salient Features_Specs).pdf PDF
Amendment 1 Attachment 3 - Project Room Contents.pdf PDF
W9127S20Q6000 Amendment 0001.pdf PDF
Amendment 1 Attachment 1 - Bid Schedule (Amendment 01).xlsx XLSX spreadsheet
Amendment 1 Attachment 4 - Eglin Invisible Wounds Clinic (IWC)_As-Built Drawings.pdf PDF
Attachment 1 - Bid Schedule.xlsx XLSX spreadsheet
Attachment 4 - Drawings 06 Mechanical.pdf PDF
Attachment 4 - Drawings 09 Fire Protection.pdf PDF
Attachment 4 - Drawings MEDICAL EQUIPMENT.pdf PDF
Attachment 2 - Cut Sheets.pdf PDF
Attachment 4 - Drawings 10 Electrical.pdf PDF
Attachment 4 - Drawings Specifications Vol 2.pdf PDF
Attachment 4 - Drawings 01 General.pdf PDF
W9127S20Q6000 - Combined Synopsis Solicitation NICoE - Eglin AFB IO Project.pdf PDF
Attachment 5 - Reuse List.xlsx XLSX spreadsheet
Attachment 7 - IO&T Submittal Examples.pdf PDF
Attachment 6 - DMLSS RPIE List.xls XLS spreadsheet
Attachment 4 - Drawings 02 Civil.pdf PDF
Attachment 3 - Project Room Contents_15Nov2019.pdf PDF
Attachment 4 - Drawings Specifications Vol 1.pdf PDF
Attachment 4 - Drawings 03 Landscape Arch.pdf PDF
Attachment 4 - Drawings 04 Structure.pdf PDF
Attachment 4 - Drawings 11 Technology.pdf PDF
Attachment 4 - Drawings 07 Plumbing.pdf PDF
Attachment 4 - Drawings FFE.pdf PDF
Attachment 4 - Drawings 05 Architecture.pdf PDF
Attachment 4 - Drawings FURNITURE.pdf PDF
Show all 35

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LOW VOLTAGE (BELOW 50 VOLTS)

L-L L-N

LTG

LV

LIGHTING

LINE TO LINE

LINE TO NEUTRAL

1000 CIRCULAR mils

KILOVOLTS (THOUSAND VOLTS)

KILOWATTS (THOUSAND WATTS)

LIGHTNING ARRESTOR

LOCAL AREA NETWORK

KILOVOLTS-AMPERES (THOUSAND VOLT-AMPS)

ISOLATED GROUND

KWH

LAN

LA

KW

KVA

Kcmil

KV

KILOWATT-HOURS

INCAND

KEY INTERLOCK

JUNCTION BOX

INCH/INCHES (")

INCANDESCENT

GROUND FAULT INTERRUPTER

HAND-OFF-AUTOMATIC

HIGH PRESSURE SODIUM

HEATING VENTILATION AND AIR CONDITIONING

HERTZ

HVAC

HZ

HTR

HR

HT

HPS

HOA

HP

HEATER

HEIGHT

HORSEPOWER

HOUR

GFI

G, GND, GRD

GEN

FLUOR

FL, FLR

GROUND

GENERATOR

FOOT/FEET (')

FLUORESCENT

FLOOR

CATV

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

FIRE ALARM ANNUNCIATOR PANEL

ELECTRIC, ELECTRICAL

ELECTRIC METALLIC CONDUIT

EQUIPMENT GROUND

EWC

FAAP

FLA

FDR

EWH

FA

FULL LOAD AMPS

FEEDER

FIRE ALARM

FUSE

ELEC

EQ, EQUIP

EM, EMERG

EMT

ELEV

ENCL

EG

EQUIPMENT

ELEVATOR

EMERGENCY

ENCLOSURE

DISTRIBUTION PANEL

DOUBLE POLE SINGLE THROW

DOUBLE POLE DOUBLE THROW

CONTROL POWER TRANSFORMER

CURRENT TRANSFORMER

DPDT

DWG

DPST

DIST

DISC

DC

DP

DN

DRAWING

DISTRIBUTION

DIRECT CURRENT

DISCONNECT

DOWN

CPT

CU

CT

COM, COMM

CKT

CLG

COPPER

COMMUNICATIONS

CIRCUIT

CEILING

CABLE TELEVISION

AMERICAN WIRE GAUGE

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AUTOMATIC TRANSFER SWITCH

AMPERE INTERRUPTING CAPACITY

ALTERNATING CURRENT

ABOVE FINISHED COUNTER

AWG

CB

BLDG

BRKR, BKR

CIRCUIT BREAKER

CONDUIT

BUILDING

BREAKER

AUTO

AUX

ARCH

AT

ATS

ALT

AFG

AIC

AFC

AFF

AC

AF

AUXILIARY

ALTERNATE

ARCHITECT

AUTOMATIC

AMPERES TRIP

AMPERE FRAME (BREAKER RATING)

MTG

MV

MH

MOCP

MTD

MLO

MIN

MISC

MECH

MCC

MFR

MCA

MCB

MOUNTING

MEDIUM VOLTAGE (OVER 600V LESS THAN 35KV)

MINIMUM CIRCUIT AMPACITY

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAXIMUM OVERCURRENT PROTECTION

MOUNTED

MISCELLANEOUS

MAIN LUGS ONLY

MINIMUM

MANHOLE

MANUFACTURER

MECHANICAL

FIRE ALARM CONTROL PANELFACP

FIRE ALARM EXTENDER PANELFAEP

AIR HANDLING UNITAHU

CCTV CLOSED CIRCUIT TELEVISION

CP CONTROL PANEL

FLEX FLEXIBLE

HAND HOLEHH

LIGHTING CONTROL PANELLC, LCP

LIGHTING PANEL

L-G LINE TO GROUND

MTS MANUAL TRANSFER SWITCH

AMPERESA

C

F

EXISTINGE, EX, EXIST

FT

IN

IG

JB, JBOX

K

LP

FOOT CANDELFC

DIV DIVISION

FIRE ALARM ABBREVIATIONS

A M

B

C

D

E

F

G

H

I

J

K

L

N

NO., NUM, #

NTS

NC

NEMA

NO

NIC

NEC

N

NOT TO SCALE

NUMBER

NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION

NORMALLY CLOSED

NORMALLY OPEN

NOT IN CONTRACT

NEUTRAL

NATIONAL ELECTRIC

CODE

O

OCPD

OC

OVERCURRENT PROTECTION DEVICE

ON CENTER

OPP

OHE/T

OH

OFOI

OFCI

OPPOSITE

OWNER FURNISHED, CONTRACTOR INSTALLED

OWNER FURNISHED, OWNER INSTALLED

OVERHEAD ELECTRIC/TELEPHONE

OVERHEAD

P

PRI

PWR

PT

PVC

PA

PH, ∅

PF

PNL

PE

PB

P

POTENTIAL TRANSFORMER

POLYVINYL CHLORIDE

POWER

PUBLIC ADDRESS

PANEL

PRIMARY

PULL BOX

POWER FACTOR

PHOTO ELECTRIC

PHASE

POLE

PDP POWER DISTRIBUTION PANEL

Q

QTY QUANTITY

R

RCLP

RM

RP

REF

RCPT

RSC

RLA

RF

R, RE

RIGID STEEL CONDUIT

RATED (RUNNING) LOAD AMPS

RECEPTACLE PANELBOARD

ROOM

RADIO FREQUENCY

RECEPTACLE

REFRIGERATOR

RELOCATE AS SHOWN

REMOTE CONTROL LIGHTING PANEL

S

SPST

SWBD

SYM

STD

SW

SPEC(S)

SPDT

SPKR

SF

SEC

SINGLE POLE SINGLE THROW

SINGLE POLE DOUBLE THROW

SYMMETRICAL

SWITCHBOARD

STANDARD

SWITCH

SECONDARY

SQUARE FOOT

SPECIFICATION(S)

SPEAKER

SCH, SCHED SCHEDULE

SWGR SWITCHGEAR

T

TYP

TV

TP

TEL,TELE

TELECOM

TC

TELECOMMUNICATIONS

TYPICAL

TELEVISION

TAMPERPROOF

TIME CLOCK

TELEPHONE

TB TERMINAL BLOCK

TBB TELEPHONE BACKBOARD

U

UPS

UL

UON

UG

UGS

UGT

UGP UNDERGROUND PRIMARY

UNDERGROUND SECONDARY

UNDERGROUND TELEPHONE

UNDERWRITER'S LABORATORY

UNLESS OTHERWISE NOTED

UNINTERRUPTIBLE POWER SUPPLY

UNDERGROUND

V

VFD

VA

V VOLTS

VARIABLE FREQUENCY DRIVE

VOLT-AMPERES

W

WP

WHM

W/ W/O

W

WATT HOUR METER

WEATHERPROOF

WITHOUT

WITH

WIRE

X X

XFMR TRANSFORMER

REMOVE DEVICE

Z

% Z PERCENT IMPEDANCE

FIRE ALARM SYMBOLS GENERAL NOTES

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

M.

N.

O.

P.

Q.

R.

S.

T.

U.

V.

W.

X.

Y.

Z.

J J JUNCTION BOX (RECESSED/SURFACE) FOR FIRE ALARM SYSTEMS PLANS.

F

SD

BT/BR

TS

WF

AP

DH

PS

FACP

FAAP

FACP

FAAP

EVAC

MAGNETIC DOOR HOLD OPEN DEVICE

HI / LOW AIR PRESSURE SWITCH, FOR CONNECTION ONLY

VALVE SUPERVISORY (TAMPER) SWITCH, FOR CONNECTION ONLY

WATER FLOW SWITCH, FOR CONNECTION ONLY

CARBON MONOXIDE DETECTOR

SMOKE DETECTOR FOR ELEVATOR RECALL

SMOKE DETECTOR FOR ACTIVATION OF SMOKE DAMPER, FOR CONNECTION ONLY

SMOKE DETECTOR - CEILING OR SURFACE MOUNTED

ALARM PRESSURE SWITCH, FOR CONNECTION ONLY

NOTIFICATION APPLIANCE POWER EXTENDER PANEL

STROBE - WALL MOUNTED

STROBE - CEILING MOUNTED

FIRE FIGHTER'S TELEPHONE

FIRE ALARM ANNUNCIATOR PANEL AND LOCAL OPERATING CONSOLE (FLUSH/SURFACE)

FIRE ALARM REMOTE CONTROL PANEL (FLUSH/SURFACE)

MANUAL FIRE ALARM PULL STATION

VOICE EVACUATION PANEL

FA/MASS NOTIFICATION SPEAKER WITH STROBE - WALL MOUNTED

FA/MASS NOTIFICATION SPEAKER - WALL MOUNTED

FA/MASS NOTIFICATION SPEAKER WITH STROBE - CEILING MOUNTED

FARPFARP FIRE ALARM SYSTEM CONTROL PANEL (FLUSH/SURFACE)

DACT DIGITAL ALARM COMMUNICATOR TRANSMITTER

FI FAULT ISOLATION MODULE

SPD SURGE PROTECTIVE DEVICE

NAC

PB

EN

ELECTRICAL PULL BOX, FOR CONNECTION ONLY

NEMA 1 ENCLOSURE CABINET

GF GENERATOR FAULT CONNECTION

GR GENERATOR RUNNING CONNECTION

WHERE ANY CONFLICT AND/OR DISCREPANCY BETWEEN THESE GENERAL NOTES AND ANY OTHER INFORMATION CONTAINED IN THE CONTRACT DOCUMENTS EXISTS, THE MORE STRINGENT REQUIREMENT SHALL PREVAIL AND BE A REQUIREMENT OF THE WORK. THAT NOTWITHSTANDING, ANY SUCH CONFLICT AND/OR DISCREPANCY SHALL PROMPTLY BE BROUGHT TO THE ATTENTION OF THE OWNER, ARCHITECT AND ENGINEER

THE WORK INCLUDES, BUT IS NOT LIMITED TO DESIGNING AND PROVIDING A COMPLETELY SUPERVISED, MULTIPLEXED, INTELLIGENT, ANALOG, ADDRESSABLE COMBINED FIRE ALARM AND DETECTION/MASS NOTIFICATION SYSTEM. THE WORK SHALL INCLUDE, BUT NOT BE LIMITED TO, ALL WIRING, RACEWAYS, PULL BOXES, TERMINAL CABINETS, OUTLET AND MOUNTING BOXES, CONTROL EQUIPMENT, ALARM AND SUPERVISORY SIGNALS, INITIATING DEVICES, ALARM NOTIFICATION APPLIANCES, NOTIFICATION ALARM PANELS, INTERFACE EQUIPMENT, AND ALL OTHER ACCESSORIES AND MISCELLANEOUS ITEMS INCLUDING SOFTWARE, SYSTEM PROGRAMMING, TEST AND CONSTRUCTION PERMITS REQUIRED FOR A COMPLETE OPERATING SYSTEM NORMALLY AND CUSTOMARILY REQUIRED, WHETHER INDICATED OR INHERENTLY NECESSARY DUE TO THE NATURE OF THE WORK. THE WORK SHALL BE LISTED FOR THE INTENDED PURPOSE BY A NATIONAL RECOGNIZED TESTING LABORATORY.

ALL WORK SHALL CONFORM TO THE APPLICABLE PROVISIONS OF THE EGLIN AIR FORCE BASE ENGINEERING DESIGN MANUAL, AMENDED CODE REQUIREMENTS OF THE LOCAL AUTHORITY HAVING JURISDICTION, UFC 3-600-01, UFC 4-021-01, AND THE

REFERENCED EDITIONS OF NFPA 13, 14, 20, 70 AND 72 .

THE TERM "PROVIDE" SHALL MEAN FURNISH, INSTALL AND CONNECT EQUIPMENT/DEVICE FOR A COMPLETE AND OPERATIONAL SYSTEM.

PROVIDE ALL NECESSARY PERMITS, INSPECTIONS AND FINAL SYSTEM ACCEPTANCE FROM THE AUTHORITY HAVING JURISDICTION (AHJ).

COORDINATE ALL WORK AND AVOID ALL CONFLICTS WITH LIGHTING FIXTURES, DIFFUSERS, GRILLS, DUCTS, STRUCTURAL MEMBERS, PIPES AND OTHER OBSTRUCTIONS

ALL FIRE ALARM CIRCUITS SHALL BE SUPERVISED AS FOLLOWS DETAILED IN SPECIFICATION IN ACCORDANCE WITH EGLIN DESIGN MANUAL.

SUBJECT TO ANY INFORMATION CONTAINED IN THE CONTRACT DOCUMENTS, MOUNT ALL VISUAL WARNING STROBE/AUDIBLE NOTIFICATION APPLIANCES TO ACHIEVE MAXIMUM AUDIBILITY AND VISIBILITY IN ACCORDANCE WITH CURRENT ADAAG GUIDELINES.

PROVIDE CARE IN LOCATING VISUAL WARNING STROBE APPLIANCES TO INSURE VISIBILITY AND AVOID OBSTRUCTIONS. PROVIDE MINIMUM INTELLIGIBLITY CRITERIA THROUGHOUT THE BUILDING IN ACCORDANCE WITH CHAPTER 24.

SUBJECT TO ANY CODE RESTRICTION AND/OR REQUIREMENT; PROVIDE ELECTRICAL METALLIC TUBING (EMT), UNLESS OTHERWISE NOTED.

IN AREAS WITHOUT CEILINGS, CONDUIT SHALL BE INSTALLED AS UNOBTRUSIVELY AS POSSIBLE, AS CLOSE AS POSSIBLE TO FLOOR/CEILING SLAB AND PARALLEL AND AT RIGHT ANGLES TO STRUCTURAL STEEL OR CONCRETE.

CONCEAL ALL CONDUIT ABOVE SUSPENDED CEILINGS AND BEHIND WALLS. CONDUIT MAY BE SURFACE MOUNTED IN UNFINISHED AREAS , UNLESS OTHERWISE NOTED.

EXPOSED CONDUIT SHALL BE PAINTED TO MATCH ADJACENT FINISH.

COORDINATE LOCATION OF AUTOMATIC SPRINKLER FLOW AND VALVE SUPERVISORY SWITCHES PRIOR TO CONDUIT ROUGH-IN TO ENSURE ACCESSIBILITY AND MINIMIZE LENGTH OF FLEXIBLE CONDUIT RUNS NECESSARY TO MAKE CONNECTIONS.

ALL WALL AND FLOOR PENETRATIONS SHALL BE CORE-DRILLED WITH MASONRY TYPE CORE BIT. AFTER CONDUIT INSTALLATION, ALL PENETRATIONS IN WALLS, CEILINGS AND FLOORS SHALL BE SEALED TO THE FULL THICKNESS OF THE PENETRATION WITH

APPROVED FIRESTOPPING MATERIAL OF EQUAL OR GREATER FIRE RESISTANCE.

ELECTRICAL BOXES SHALL BE PROVIDED AS FOLLOWS: I) EXPOSED WORK - CAST METAL BELL TYPE BOXES WITH THREADED HUB, EXCEPT WHERE FACTORY BOXES ARE PROVIDED; AND II) CONCEALED WORK - BOXES MAY BE STAMPED STEEL BOXES.

PROVIDE TERMINAL CABINETS OF SOLID WALL CONSTRUCTION WITH NO FACTORY CONDUIT KNOCK OUTS.

PROVIDE COMPRESSION TYPE STEEL FITTINGS AND CONNECTORS FOR BOTH EXPOSED AND CONCEALED CONDUITS INCLUDING RISERS UP TO 2 INCHES IN DIAMETER.

CONDUIT & RISERS: I) PROVIDE ¾ INCH MINIMUM EMT TRADE SIZE CONDUIT, UNLESS OTHERWISE NOTED; II) VERTICAL RISERS SHALL BE ONE INCH DIAMETER EMT MINIMUM.

PROVIDE WIRING CONDUCTORS AS INDICATED BELOW:

INITIATING - NO. 18/2 AWG, TSP

SIGNALING - NO. 18/2 AWG, TSP W/ DRAIN WIRE

NOTIFICATION APPLIANCES - 14/2 AWG

CONTROL - 16/2 AWG

120 VAC POWER - 12/2 AWG, WITH NO 12 AWG E.G., 600 VAC INSULATED

ALL DAMAGE TO WALLS, CEILINGS, FLOORS, AND STRUCTURAL MEMBERS FROM THE WORK SHALL BE PATCHED, REPAIRED AND PAINTED WITH NEW MATERIALS TO MATCH ADJACENT WORK, WHETHER SPECIFICALLY NOTED OR NOT.

LOCATE FIRE ALARM DEVICES INSTALLED IN ACOUSTICAL TILE CEILINGS IN THE CENTER OF THE TILE. MOUNT WALL MOUNTED DEVICES 84 INCHES ABOVE FINISHED FLOOR AT CENTER OF DEVICE. SECONDARY POWER SHALL BE PROVIDED FOR 72 HOURS OF

STANDBY AND 10 MINUTES OF ALARM.

PROVIDE ALL EQUIPMENT IN ACCORDANCE WITH SEISMIC CRITERIA FOUND IN NFPA 72.

FIRE ALARM DEVICES SHALL BE WHITE IN COLOR AND READ 'ALERT' WITH AMBER STROBES (IN VISIBLE NOTIFICATION APPLIANCES).

INSTALL BUILDING TRANSCEIVER TOP OF PANEL ENCLOSURE NO HIGHER THAN 60 INCHES ABOVE FINISHED FLOOR.

INSTALL FIRE ALARM CONTROL PANEL TOP OF PANEL ENCLOSURE NO HIGHER THAN 70 INCHES ABOVE FINISHED FLOOR.

SPEAKERS IN PATIENT-SENSITIVE AREAS INDICATED BY VERTICAL HATCHING ARE TO BE ON DEDICATED CIRCUIT WITH MANUAL ON/OFF BROADCASTING FOR USE BY THE FIRE DEPARTMENT VIA ISOLATED SELECTOR SWITCH AT THE VOICE EVACUATION PANEL. SPEAKERS ON DEDICATED CIRCUIT FOR PATIENT-SENSITIVE AREAS SHALL INITIATE ALL VOICE MESSAGES WITHOUT OUTPUT OF TEMPORAL-THREE ALARM, SYNCHRONIZED WITH OTHER SPEAKER CIRCUIT.SPEAKERS ON DEDICATED CIRCUIT ARE TO

BE TAPPED AT 1/8 WATT IN THESE PATIENT-SENSITIVE AREAS.

FIRE FIGHTER'S TELEPHONE JACK

BATT BATTERY CABINET

FA

FA, FA

REFERENCE SYMBOLS

SECTION NUMBER

DETAIL NUMBER

DRAWING NUMBER WHERE DRAWN

DRAWING NUMBER WHERE DRAWN

E1-1.0

E1-1.0

KEY NOTE

ER

SMOKE DETECTOR FOR RETURN AIR PLENUM APPLICATIONRA

DUCT SMOKE DETECTOR REMOTE TEST STATION

AI FIRE ALARM ADDRESSABLE INTERFACE MODULE (INPUT)

AR FIRE ALARM ADDRESSABLE RELAY (OUTPUT)

FATC FIRE ALARM TERMINAL CABINET

AMP FIRE ALARM AMPLIFIER PANEL

ZONE # FIRE ALARM ZONE IDENTIFICATION NUMBER

FIRE ALARM ZONE BOUNDARY

BT/BR,

SMOKE DETECTOR HVAC DUCT TYPE

RF MONACO BT-XM RADIO FREQUENCY COMMUNICATION TRANSMITTER

LOC LOCAL OPERATING CONSOLE

SMOKE DETECTOR BEAM TYPE

MINIMUM INELIGIBILITY BOUNDARY

FIRE ALARM SEQUENCE OF OPERATIONS

NOTES:

1. THE USE OF THE MICROPHONE SHALL NOT INITIATE ANY SIGNALS UNLESS THE FIRE ALARM SIGNAL HAS BEEN ACTIVATED.

2. PROVIDE THE FOLLOWING MESSAGES AND PROVIDE 5 ADDITIONAL SPACES TO BE PROGRAMED AT A LATER DATE.

3. MASS NOTIFICATION MESSAGES SHALL TAKE PRIORITY AND OVERRIDE FIRE ALARM MESSAGES.

4. CLEAR/WHITE STROBE SHALL NOT ACTIVATE WHEN AMBER STROBES ARE IN OPERATION.

5. SPEAKERS ON DEDICATED CIRCUIT FOR PATIENT-SENSITIVE AREAS (EXAM ROOMS, PROVIDER OFFICES, THERAPY SPACES, ETC.) SHALL INITIATE ALL VOICE MESSAGES WITHOUT TEMPORAL-THREE TONE ALARM, SYNCRONIZED WITH OTHER SPEAKER CIRCUIT. SPEAKERS ON DEDICATED CIRCUIT ARE TO BE TAPPED AT 1/8 WATT IN THESE SENSITIVE AREAS.

ALL CLEAR

PRE-ANNOUNCEMENT SOUND – DING-DONG – PERCUSSIVE PAIRS OF 700 AND 570 HZ TONES EACH DAMPED TO ZERO (ONE CYCLE)

ANNOUNCEMENT: VOICE – DONNA (REPEAT TWO CYCLES) – THE EMERGENCY HAS BEEN RESOLVED; RETURN TO NORMAL OPERATIONS

TEST

RE-TEST SOUND – NOAA STANDARD ALERT TONE - 1050 HZ (8 SECONDS)

ANNOUNCEMENT: VOICE – TOM – TEST, TEST, TEST, THIS IS AN EMERGENCY NOTIFICATION AUDIO SYSTEM TEST; YOU MAY CONTINUE NORMAL OPERATIONS, TEST, TEST, TEST.

FIRE

ALERT SOUND – NFPA TEMPORAL 3 (T-3) - 422-775HZ UPWARD SWEEP OVER 850 MS FOR THREE-PULSES EACH SEPARATED BY 1 SECOND FOLLOWED BY A 1.5 SECOND DELAY (REPEAT 2 CYCLES) A FIRE EMERGENCY HAS OCCURRED; PLEASE LEAVE THE BUILDING BY THE NEAREST EXIT AND REPORT TO YOUR ASSEMBLY LOCATION

FIRE ALARM RISER DIAGRAM

GROUND FLOOR

ROOF

ELECTRICAL CLOSET 114 ELECTRICAL CLOSET 330

FACP

NAC

AMP

SPD

BATT

ACU

FATCFI JJ120 VAC 120 VACSPD

NAC

AMP

FIF

WF

AIAR

AHU

SD

TS

AI

FA/MASS NOTIFICATION SPEAKER - CEILING MOUNTED

WP WP WP

WP

F

RF

ACU AUTONOMOUS CONTROL UNIT

LOC

MAIN VESTIBULE/

SOUTH EXIT

(X2)FACP

PATIENT-SENSITIVE AREAS

DRAWING NUMBER

PROJECT NUMBER

SCALE

DRAWING TITLE

KEYPLAN

SEALS AND SIGNATURES

ISSUED FOR REV DATE

Cagley & Associates

STRUCTURAL ENGINEERING

6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050

1700 NEW YORK AVE, NW

SUITE 100

WASHINGTON, DC 20006

202.842.2100 www.smithgroup.com

Pl ot

D at e:

EGLIN AIR FORCE BASE

BUILDING XX

ASH DR, EGLIN AIR FORCE BASE

FLORIDA

32542

IMEG Corporation

ELECTRONIC SECURITY / TELECOMMUNICATIONS

2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906

Baskerville-Donovan, Inc.

CIVIL ENGINEERING

449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340

SmithGroup

MEP-FP ENGINEERING

1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100

1 : 1

1/ 4/

2:

:2

PM FIRE ALARM

ABBREVIATIONS AND

SYMBOLS

FA0.1

10822.000

13 MASS NOTIFICATION ACTIVE

13 MANUAL MASS NOTIFICATION MESSAGE WHEN FIRE ALARM IS ACTIVATED

12 MANUAL MASS NOTIFICATION MESSAGE

11 NOTIFICATION APPLIANCE CIRCUIT SHORT

10 SLC/INITIATING DEVICE CIRCUIT FAULT

9 GROUND FAULT

8 OPEN CIRCUIT

7 FIRE ALARM SYSTEM LOW BATTERY

6 FIRE ALARM AC POWER FAIL

5 SPRINKLER VALVE SUPERVISORY SWITCH

4 SPRINKLER WATERFLOW SWITCH

3 DUCT MOUNTED SMOKE DETECTOR @ AHU (RETURN) FOR AHUS

2 SMOKE DETECTORS ‐ SPOT TYPE

1 MANUAL PULL STATION

AL

AR

M A N N U N

CI

AT

IO

N

F

AC

P

AN

D

RE

M O

TE

A N N U N

CI

AT

O R

BY

D

EV

IC

E

TR

O U

BL

E

AN

N U N

CI

AT

IO

N

F

AC

P

AN

D

RE

M O

RE

A N N U N

CI

AT

O R

BY

D

EV

IC

E

SU

PE

RV

IS

O

RY

A N N U N

CI

AT

IO

N

F

AC

P

AN

D

RE

M O

TE

A N N U N

CI

AT

O R

PA

N

EL

TR

AN

SM

IT

S

IG

N

AL

T O S U

PE

RV

IS

IN

G S

TA

TI

O N

RE

CO

RD

A N D

PR

IN

T

CH

AN

G E O F

SY

ST

EM

S

ST

AT

U S

AN

N U N

CI

AT

E

AS

SO

CI

AT

ED

IN

FO

RM

AT

IO

N O N A

LL

R

EM

O

TE

F

AA

CP

S

BR

O

AD

CA

ST

P

RE

‐R

EC

O

RD

ED

F

IR

E

AL

AR

M E M

ER

G

EN

CY

E

VA

CT

U

AT

IO

N M

ES

SA

G E

TH

RO

U G H

AU

DI

BL

E

SP

EA

KE

RS

AC

TI

VA

TE

C

LE

AR

(A

LE

RT

) V

IS

IB

LE

N O

TI

FI

CA

TI

O N D

EV

IC

ES

SH

U T‐

DO

W N O N

LY

T

HE

A

SS

O

CI

AT

ED

A

HU

A N D

IN

DI

CA

TE

A T

RE

M O

TE

S

TA

TI

O N

M U

TE

A

LL

P U

BL

IC

A

DD

RE

SS

/S O U N D

SY

ST

EM

S

IN

IT

IA

TE

S

EC

U

RI

TY

L O

CK

R

EL

EA

SE

BR

O

AD

CA

ST

M

AS

S N O

TI

FI

CA

TI

O N M

ES

SA

G E

TH

RO

U G H

AU

DI

BL

E

SP

EA

KE

RS

AC

TI

VA

TE

A M

BE

R

VI

SI

BL

E N O

TI

FI

CA

TI

O N D

EV

IC

ES

SYSTEM INPUT SY

ST

EM

O U

TP

U T

A B C D E F G H I J K L M

SCHEMATIC DESIGN 8.17.2018

DESIGN DEVELOPMENT 11.08.2018

CONTRACT DOCUMENTS 01.04.2019

DA

CT

FA

CP

NA

C

AM

P

BA

TT

SP

D

J

AC

U

F

NA

C

AM

P

SP

D

J

F

F

F

FI

FA

TC

AR

AR

F

F

F

AI AI

WF TS

F

FI

LOC

LCD

LO

C

RF

AR

0.7A

0.9A

A.9

A.7

15 15

FA

1515 15

FA209

FA209

FA209

FA209

FA203

FA215

FA207

FA203

FA208

FA215

B2

E.8

FA209

FA209

FA211

FA211

FA218

FA209FA209

FA209

FA

TLT/ SHR

218.2

CHANGING / LOCKER (M)

CHANGING / LOCKER (W)

VESTIBULE

MECHANICAL

ELEC

SOIL UTIL

COMM

PUBLIC WAITING

C101

WORKSTATION PT

PT GYM

CORRIDOR

C300

CORR

C200

TLT/ SHR

218.1

CORR

C302

CORR

C305

CORR

C304

CORR

C306

CORR

C303

CORR

C301

CORR

C201

MAT / PLATFORM

EQPT STOR

CLEAN UTIL

NEURO REHAB AREA

CORR

C102.1

FAMILY WAITING

CENTRAL PARK

MAIN CORRIDOR / LOBBY

C100

PAT TLT

ELEC

COMM

NP PSYCH

BH / SW PROVIDERS

BH / SW PROVIDERS

STAFF LOUNGE

MUSIC THERAPY

RECEPTION

PTNT INTAKE CUBICLES

300.1

MALE TOILET

FEMALE TOILET

HOUSEKEEPING

DAILY LIVING SKILLS

RESEARCH SHARED OFFICE

NCOIC / ADMIN

NICoE DIR.

DIR. OF OPERATIONS

112AV SUPPLY

CLASSROOM

103.1

FA206

FA218FA222

FA216

FA219

PSYCHOLOGIST

BH / SW PROVIDER

STAFF TLT

GROUP THERAPY

335.1

GROUP THERAPY

TRANS-CRANIAL MAGNETIC STIM

BIO NEUROFEEDBACK

CASE MGMT

EXAM

350 NUTRITIONIST

352SOIL UTIL

HOUSEKEEPING

STAFF TLT

318 EXAM

349 EYE TESTING

TREATMENT IPMC

EYE LANE

TRAZER / FATS

OT O/E

213 SPEECH THERAPY - OFFICE

SPEECH THERAPY - TESTING

PT O/E

208PT O/E

MULTI-STATION TREATMENT RM

STORAGE / ALCOVE

200.1

DAYROOM

VENDING ALCOVE

106.1

BREAK ALCOVE

105.1

CASE MGMT

NEUROLOGIST

PC MD

CLINICAL PHARMACIST

CASE MGMT

PAIN MD

CHIRO TREATMENT

CHIRO TREATMENT

EXAM

EXAM

EXAM

EXAM

345EXAM

EXAM

348 TEAM ROOM

304 SPIRITUAL COUNSELLING

CHAPLAIN

SCALE

C306.1

FLEX STORAGE

PAT TLT

STORAGE / KILN

338.1

ART AND CLAY THERAPY

PSYCH TECH

PSYCH TECH

NEUROPSYCH

EQPT STOR

BRAIN LAB

ACUPUNCTURE

341.2

ACUPUNCTURE

341.1

OT O/E

FA209

FA219

ALCOVE / STORAGE

C303.1

GAIT OBS LANE

CORR

C102

TLT / SHR

219.1

123456789

B

C

D

E

F

A

0.4A

A.7

A.2

6.2 5.46.97.1 6.5 4.5 3.3 2.8

0.5A

0.2A

D.7

5.2

0.3A

8.6 8.3 6.8 6.4

4.8

A.9

0.7A

0.9A

B.2

E.8

FA207

FA22515

FA225

FA204

FA205

FA226

CLASSROOM

DRAWING NUMBER

PROJECT NUMBER

SCALE

DRAWING TITLE

KEYPLAN

SEALS AND SIGNATURES

ISSUED FOR REV DATE

PLAN

NORTH

Cagley & Associates

STRUCTURAL ENGINEERING

6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050

1700 NEW YORK AVE, NW

SUITE 100

WASHINGTON, DC 20006

202.842.2100 www.smithgroup.com

Pl ot

D at e:

EGLIN AIR FORCE BASE

BUILDING XX

ASH DR, EGLIN AIR FORCE BASE

FLORIDA

32542

IMEG Corporation

ELECTRONIC SECURITY / TELECOMMUNICATIONS

2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906

Baskerville-Donovan, Inc.

CIVIL ENGINEERING

449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340

SmithGroup

MEP-FP ENGINEERING

1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100

1/8" = 1'-0"

1/ 4/

2:

:2

PM GROUND FLOOR FIRE

ALARM SYSTEMS

PLAN

FA2.1

10822.000

KEYED NOTES

SHEET NOTES

A. SEE FA0.1 FOR FIRE ALARM AND DETECTION ABBREVIATIONS,

SYMBOLS, AND GENERAL NOTES.

B. SPEAKERS IN AREAS INDICATED BY VERTICAL HATCHING ARE

TO BE ON DEDICATED CIRCUIT WITH MANUAL ON/OFF

BROADCASTING BY FIRE DEPARTMENT VIA ISOLATED

SELECTOR SWITCH AT THE VOICE EVACUATION PANEL. THESE

SPEAKERS SHALL SKIP INITIAL TEMPORAL-THREE ALARM AND

INTIATE NOTIFICATION WITH START OF VOICE MESSAGE.

SPEAKERS ON SEPARATE CIRCUIT ARE TO BE TAPPED AT

LOWEST WATTAGE.

FA203 PROVIDE NEW NOTIFICATION APPLIANCE

POWER EXTENDER (NAC) PANEL AND

AMPLIFIER (AMP) PANEL TO POWER FIRE

ALARM DEVICES.

FA204 PROVIDE NEW FIRE ALARM ANNUNCIATOR

PANEL (LCD TYPE) AND LOCAL OPERATING

CONSOLE (LOC) IN ENTRANCE VESTIBULE.

FA205 PROVIDE AND INSTALL NEW LOCAL

OPERATING CONSOLE (LOC) FOR

OPERATION OF BUILDING MASS

NOTIFICATION SYSTEM.

FA206 PROVIDE AND INSTALL NEW ADDRESSABLE

INTERFACE MODULE TO MONITOR VALVE

SUPERVISORY SWITCH.

FA207 PROVIDE AND INSTALL NEW COMBINATION

VOICE EVACUATION FIRE ALARM CONTROL

PANEL (FACP) AND AUTONOMOUS CONTROL

UNIT (ACU) FOR FIRE ALARM AND MASS

NOTIFICATION THROUGH OUT BUILDING IN

ELECTRICAL ROOM. FIRE ALARM SYSTEM

SHALL BE A SIMPLEX SYSTEM.

FA208 PROVIDE A DIGITAL ALARM COMMUNICATOR

TRANSMITTER.

FA209 PROVIDE NEW WEATHERPROOF DEVICE.

FA211 PROVIDE AND INSTALL NEW ADDRESSABLE

RELAY FOR AUTOMATIC SHUT DOWN OF

AHU MOTOR UPON ACTIVATION OF

ASSOCIATED SMOKE DETECTOR WITHIN 36

INCHES OF AHU CONTROL CIRCUIT.

PROVIDE REMOTE TEST STATION

INDICATING LIGHT. REFER TO MECHANICAL

PLANS FOR EXACT LOCATION OF AHU.

FA215 PROVIDE AND INSTALL ELECTRICAL

JUNCTION BOX CONTAINING TERMINATION

OF TWO (2) 120 VAC/20 AMP POWER CIRCUIT

FROM BUILDING EMERGENCY ELECTRICAL

DISTRIBUTION PANEL TO PROVIDE PRIMARY

POWER FOR FIRE ALARM PANEL

EQUIPMENT. LABEL ASSOCIATED CIRCUIT

BREAKERS "FIRE ALARM CIRCUIT CONTROL."

ELECTRICAL JUNCTION BOX PROVIDED

UNDER ELECTRICAL SECTION. REFERENCE

ELECTRICAL SHEETS FOR PANEL SCHEDULE

AND LOCATIONS OF EMERGENCY POWER

DISTRIBUTION PANELS.

FA216 PROVIDE AND INSTALL NEW ADDRESSABLE

INTERFACE MODULE TO MONITOR WATER

FLOW SWITCH.

FA218 PROVIDE AND INSTALL NEW HVAC DUCT

TYPE SMOKE DETECTOR ON THE SUPPLY

SIDE OF AHU UNIT. CONTRACTOR TO REFER

TO MECHANICAL PLANS FOR EXACT

LOCATION OF AHU UNIT.

FA219 INSTALL FIRE ALARM DEVICE ON MULLION.

ALL FIRE ALARM WIRING IS TO BE RUN

INSIDE MULLION.

FA222 PROVIDE NEW MONACO BT-XM MASS

NOTIFICATION TRANSCEIVER FOR

COMMUNICATION WITHIN THE BUILDING.

FA225 PROVIDE SURGE SUPPRESSOR ON ALL 120

VOLT CIRCUITS TO CONTROL PANELS,

TRANSMITTERS, AMPLIFIER PANELS, AND

BOOSTER PANELS.

FA226 PROVIDE ADDRESSABLE RELAY WITHIN 3

FEET OF DOOR CONTROL PANEL TO

RELEASE DOORS UPON UPON ACTIVATION

OF THE FIRE ALARM SYSTEM.

PATIENT-SENSITIVE AREAS

GRAPHIC LEGEND

SCHEMATIC DESIGN 8.17.2018

DESIGN DEVELOPMENT 11.08.2018

CONTRACT DOCUMENTS 01.04.2019

FA0-1 - FIRE ALARM ABBREVIATIONS AND SYMBOLS
Sheets
FA0.1 - FIRE ALARM ABBREVIATIONS AND SYMBOLS
FA2.1 - GROUND FLOOR FIRE ALARM SYSTEMS PLAN
FP0.1 - FIRE PROTECTION ABBREVIATIONS AND SYMBOLS
FP2.1 - GROUND FLOOR FIRE PROTECTION PLAN
FA2-1 - GROUND FLOOR FIRE ALARM SYSTEMS PLAN
Sheets
FA0.1 - FIRE ALARM ABBREVIATIONS AND SYMBOLS
FA2.1 - GROUND FLOOR FIRE ALARM SYSTEMS PLAN
FP0.1 - FIRE PROTECTION ABBREVIATIONS AND SYMBOLS
FP2.1 - GROUND FLOOR FIRE PROTECTION PLAN

File details come from the government source that posted it. Updated .