This combined synopsis/solicitation is seeking quotes for the Eglin NICoE Initial Outfitting Project. The solicitation is a total Service-Disabled Veteran-Owned Small Business set-aside, issued under NAICS code 337127 with a size standard of 500 employees. Quotes are due no later than January 8, 2020 by 1:00pm Central Time. An optional site visit is scheduled for December 4, 2019 at 9:00am Central Time at the Eglin Air Force Base West Visitors Center. Interested contractors must RSVP for the site visit by November 29, 2019 with required contact information. The solicitation is being conducted using FAR simplified acquisition procedures in conjunction with commercial items procedures. The Army Corps of Engineers Engineering District Little Rock is the issuing agency.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL ABBREVIATIONS
J J
J
M
V
SP
R
CB
VFD
LCP
LRP
FBX
GAP
ET
M
M
C
DT
U
PIPI
U
DT
A-1
PH
D a
LD
OS
SP
VP
TV
XX
PC
C
RP-XXXX
E
K
ATS
TBB
T
TMH
EMH
EHH
EMU
FB
UG
GB
G
PB
SR-X
6-30R
UPS
CT
FLUSH FLOOR BOX ("X" DENOTES TYPE AS SPECIFIED)
REFER TO SPEC SECTION 262726 FOR FURTHER DEVICE DESCRIPTIONS. ALL FLOOR BOX TYPES
ARE TO BE SHALLOW AND FLUSH MOUNTED TO CARPET AND COVERS ARE TO HAVE A BRUSHED
ALUMINUM FINISH. FLOORPORT COVERS WITH CUTOUT TOP ARE TO BE FILLED WITH CARPET TO
MATCH LOCATION OF FLOOR BOX. REFER TO TELECOM DRAWINGS FOR SPECIFIC
REQUIREMENTS OF TELECOMMUNICATIONS BRACKETS.
FB1 - RECTANGULAR, 4-GANG, DUAL TYPE FLUSH FLOOR BOX CONSISTING OF (2) DUPLEX
RECEPTACLES AND RECEPTACLE BRACKETS AND (2) MODULAR TELECOMMUNICATIONS
BRACKETS. MODEL #RFB4-CI-1 WITH FLOORPORT COVER MODEL #FPCTCAL BY LEGRAND
WIREMOLD OR ENGINEER APPROVED EQUAL.
FB2 - RECTANGULAR, 2-GANG, DUAL TYPE FLUSH FLOOR BOX CONSISTING OF (1) DUPLEX
RECEPTACLE AND RECEPTACLE BRACKET AND (1) MODULAR TELECOMMUNICATIONS BRACKET.
MODEL #RFB2-OG WITH FLOORPORT COVER MODEL# FPCTCAL BY LEGRAND WIREMOLD OR
ENGINEER APPROVED EQUAL.
FB3 - ROUND, SINGLE SOURCE TYPE FLUSH FLOOR BOX CONSISTING OF (1) DUPLEX RECEPTACLE
AND RECEPTACLE BRACKET. MODEL #885B WITH BRUSHED ALUMINUM COVER PLATE MODEL #
895TCAL BY LEGRAND WIREMOLD OR ENGINEER APPROVED EQUAL.
CONTACTOR
HAND-OFF-AUTO SELECTOR SWITCH WITH PILOT LIGHT
VARIABLE FREQUENCY DRIVE/VARIABLE FREQUENCY MOTOR CONTROLLER
PACKAGE CONTROL UNIT (PROVIDED BY EQUIPMENT SUPPLIER)
MANUAL MOTOR STARTER WITH PILOT LIGHT AS INDICATED.
PUSHBUTTON STATION
LIGHTING FIXTURE TYPE DESIGNATION - "XX" INDICATES SPECIFIC TYPE
EXIT LIGHT - WALL/CEILING MOUNTED - DIRECTIONAL
ARROWS AS INDICATED SHADING INDICATES ILLUMINATED
FACE
LIGHTING TRACK - "X" DENOTES TYPE
FLUORESCENT LIGHTING FIXTURE - TYPE AS INDICATED
WALL MOUNTED LIGHTING FIXTURE- TYPE AS INDICATED
SITE LIGHTING FIXTURE TYPE AS INDICATED
LIGHTING FIXTURE - TYPE AS INDICATED (LOWERCASE 'LETTER' SUBSCRIPT INDICATES
SWITCH CONTROL, UPPERCASE 'LETTER' SUBSCRIPT INDICATES PHOTOSENSOR CONTROL,
'NUMBER' SUBSCRIPT INDICATES RELAY CONTACTOR CONTROL)
JUNCTION BOX - CEILING OR WALL MOUNTED - INDICATED IN POWER, LIGHTING & FIRE
ALARM SYSTEMS PLANS.
DIRECT CONNECTION TO EQUIPMENT
SINGLE POLE SWITCH (SUBSCRIPT INDICATES FIXTURES CONTROLLED)
DIMMER SWITCH; WHERE SHOWN IN SPACES WITH AN OCCUPANCY SENSOR, DIMMER SHALL
ACT AS OCCUPANCY SENSOR OVERRIDE
DUAL LEVEL SWITCHING - ONE SWITCH CONTROLS OUTER LAMPS
AND ONE SWITCH CONTROLS REMAINING INNER LAMPS.
PASSIVE INFRARED OCCUPANCY SENSOR (WALL/CEILING)
THREE-WAY SWITCH (S3P-THREE-WAY SWITCH WITH PILOT LIGHT)
FUSED SWITCH
DELTA CONNECTION
CPT
PASSIVE INFRARED/ULTRASONIC OCCUPANCY SENSOR (WALL/CEILING, 'NUMBER' SUBSCRIPT
INDICATES LIGHTING RELAY CONTACTOR CONTROLLED)
ELECTRIC INTERLOCK SYSTEM
CONTROL POWER TRANSFORMER
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
PHOTO CELL (UPPERCASE 'LETTER' SUBSCRIPT INDICATES PHOTO CELL CONTROL ZONE)
KEY INTERLOCKING SYSTEM
WYE CONNECTION - SOLID GROUND
SWITCH - SINGLE THROW
ULTRASONIC OCCUPANCY SENSOR (WALL/CEILING)
TELECOMMUNICATIONS BACKBOARD
MOTOR CONTROL CENTER
TELEPHONE MANHOLE
ELECTRIC MANHOLE
FUSE
BUS DUCT PLUG-IN UNIT
GROUND
AUTOMATIC TRANSFER SWITCH
DRAWOUT TYPE, CIRCUIT BREAKER
STATIONARY CIRCUIT BREAKER
LIGHTNING ARRESTOR
DISCONNECT SWITCH, FUSED.
PROVIDE SWITCH AND FUSE AMACITY EQUAL TO OR GREATER THAN FEEDER AMPACITY,
UON
GROUND ROD
DISCONNECT SWITCH, NON-FUSED
PROVIDE SWITCH AMPACITY EQUAL TO OR GREATER THAN FEEDER AMPACITY, UON
STRESS CONE
TRANSFORMER - TYPE AND RATING AS INDICATED
COMBINATION MOTOR STARTER WITH DISCONNECT SWITCH.
PROVIDE SWITCH AND FUSE AMACITY EQUAL TO OR GREATER THAN FEEDER
AMPACITY, UON
PANELBOARD - (FLUSH/SURFACE)
DISTRIBUTION PANELBOARD
CIRCUIT BREAKER IN NEMA 1 ENCLOSURE (FLUSH/SURFACE)
ELECTRIC HANDHOLE
LIGHTING CONTROL PANEL, SURFACE MTD. UON.
LOW VOLTAGE LIGHTING RELAY PANEL, SURFACE MTD. UON
UNINTERRUPTIBLE POWER SUPPLY
SHADING INDICATES FIXTURE [CONNECTED TO CRITICAL BRANCH]
[CONNECTED TO GENERATOR CIRCUIT (SWITCHED)]
[W/FLUORESCENT BATTERY/INVERTER UNIT (SWITCHED)]
SHADING INDICATES FIXTURE [CONNECTED TO LIFE SAFETY BRANCH
(UNSWITCHED)] [W/FLUORESCENT BATTERY/INVERTER UNIT (UNSWITCHED)]
LOW VOLTAGE DIMMING SWITCH WITH ON/OFF AND RAISE/LOWER BUTTONS FOR EACH ZONE
JUNCTION BOX - FLOOR MOUNTED
MOTOR AND CONNECTION
EMERGENCY POWER OFF
SYMBOL INDICATES TO WHICH PANELBOARD INDICATED CIRCUITS IN THE
ROOM ARE TO BE CONNECTED.
CEILING MOUNTED DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W.
SPECIAL PURPOSE RECEPTACLE. TYPE AS INDICATED ON DRAWINGS.
COORDINATE RECEPTACLE TYPE WITH ACTUAL EQUIPMENT PRIOR TO INSTALLATION.
SWITCHED DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W.
EMERGENCY DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W.
(SHADING INDICATING EMERGENCY RECEPTACLE TYPICAL FOR ALL OTHER
RECEPTACLE TYPES)
QUADRUPLEX RECEPTACLE, (2) 20A, 125V, 2P, 3W., FLOOR MTD SERVICE FITTING, FLUSH TYPE
UON
("S" DENOTES SURFACE TYPE)
CEILING MOUNTED QUADRUPLEX ISOLATED GROUND RECEPTACLE, (2)20A, 125V,
2P, 3W, DUPLEX ISOLATED GROUND RECEPTACLES WITH A COMMON FACEPLATE.
SINGLE RECEPTACLE, 20A, 125V, 2P, 3W., FLOOR MTD SERVICE FITTING, FLUSH TYPE UON
("S" DENOTES SURFACE TYPE)
CEILING MOUNTED DUPLEX ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.
CEILING MOUNTED SINGLE ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.
CEILING MOUNTED SINGLE RECEPTACLE, 20A, 125V, 2P, 3W.
SINGLE ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P,
3W. (SLASH INDICATES MOUNTING ABOVE FINISH
COUNTER)
QUADRUPLEX ISOLATED GROUND RECEPTACLE, (2)20A, 125V, 2P, 3W,
DUPLEX ISOLATED GROUND RECEPTACLES WITH A COMMON
FACEPLATE. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)
DUPLEX ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.
(SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)
DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)
SINGLE RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)
RECEPTACLES MOUNTED ABOVE THE CEILING.
QUADRUPLEX RECEPTACLE, (2)20A, 125V, 2P, 3W, DUPLEX RECEPTACLES
WITH A COMMON FACEPLATE. (SLASH INDICATES MOUNTING ABOVE FINISH
COUNTER)
CEILING MOUNTED QUADRUPLEX RECEPTACLE, (2)20A, 125V, 2P, 3W, DUPLEX
RECEPTACLES WITH A COMMON FACEPLATE.
GFI, DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)
ELECTRONIC METERING UNIT
GROUND BUS
GROUND CABLE, SIZE AS INDICATED
PLUG-IN BUSWAY
FEEDER BUSWAY
UNDERGROUND CONDUIT/DUCTBANK
CABLE TRAY
CONDUIT TURNED DOWN
CONDUIT TURNED UP
CONDUIT CAST IN CONCRETE OR BELOW SLAB
CONDUIT RUN CONCEALED IN FINISHED AREAS, EXPOSED IN UNFINISHED
AREAS OR BELOW ACCESS FLOORS
HOMERUN TO PANEL WITH CIRCUIT NUMBER(S) AS INDICATED
GENERATOR ANNUNCIATOR (DERANGEMENT) PANEL
COMBINATION TV OUTLET AND DUPLEX RECEPTACLE ON SINGLE
FACEPLATE
SPEAKER - WALL MTD
PA VOLUME CONTROL
MICROPHONE OUTLET - CEILING MTD
MICROPHONE OUTLET - WALL MTD
MICROPHONE OUTLET - FLOOR MTD
SPEAKER - CEILING MTD
RECORDING OUTLET
COMBINATION VIDEO PROJECTOR OUTLET AND DUPLEX RECEPTACLE
CLOCK OUTLET, W/RECPT AND HANGER
CLOCK OUTLET, MASTER CLOCK
CLOCK OUTLET, ELAPSED TIME
GENERATORG
SURFACE RACEWAY ("X" DENOTES TYPE AS SPECIFIED)
WALLWASH LIGHT FIXTURE,
DEMOLITION WORK
OCCUPANCY SENSOR WALL SWITCH
M
HC HANDICAPPED PUSH BUTTON.
ELECTRICAL LIGHTING SYMBOLS ELECTRICAL POWER SYMBOLS GENERAL NOTES
A B C A B C
P P
PD PD
POWER SERVICE FITTING (FLOOR/WALL) MOUNTED FOR CONNECTION TO FURNITURE
SYSTEM AS SPECIFIED.
COMBINATION POWER AND TELECOMMUNICATIONS FLOOR OR WALL MOUNTED BOX FOR
POWER AND DATA CONNECTION - INDICATED IN POWER & SPECIAL SYSTEMS PLANS.
PROVIDE 1#12 + 1#12N + 1#12G FOR 20A BRANCH CIRCUITING, UON; MAXIMUM OF THREE
CIRCUITS PER CONDUIT; MINIMUM CONDUIT SIZE OF 3/4" C, UON.
PROVIDE A DEDICATED NEUTRAL WIRE FOR EACH BRANCH CIRCUIT.
COORDINATE DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTURAL
DRAWINGS PRIOR TO ROUGH-IN.
PROVIDE FIRE STOPPING FOR CONDUITS AND ELECTRICAL EQUIPMENT FOR FLOOR SLABS,
WALLS AND CEILINGS TO MAINTAIN FIRE RATING.
INSTALL ELECTRICAL WORK IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND
LOCAL BUILDING AND FIRE CODES, IN A NEAT AND WORKMANLIKE MANNER.
LIMIT VOLTAGE DROP TO 2% FOR FEEDERS AND 3% FOR BRANCH CIRCUITS. INCLUDE
DERATING FACTOR FOR ROOF-MOUNTED CONDUITS.
REFER TO ARCH. REFLECTED CEILING PLANS FOR EXACT LOCATION OF CEILING MOUNTED
DEVICES AND LIGHT FIXTURES, UNLESS OTHERWISE INDICATED.
WHERE MULTIPLE SWITCHES, RECEPTACLES, AND OTHER OUTLETS (EXCEPT WALL
PHONES) ARE INDICATED PROVIDE MULTI-GANG BACK BOXES WITH GANG BARRIERS AND A
COMMON FACEPLATE.
WHERE DIFFERENT RECESSED ELECTRICAL DEVICES WITH THE SAME MOUNTING HEIGHTS
ARE INDICATED SIDE-BY-SIDE, MOUNT THE DEVICES SO THAT THERE IS FOUR INCHES
BETWEEN ADJACENT VERTICAL EDGES OF THE FACEPLATES, UON.
WHERE ELECTRICAL DEVICES WITH DIFFERENT MOUNTING HEIGHTS ARE LOCATED IN THE
SAME AREA ALIGN DEVICES VERTICALLY THROUGH THEIR CENTERLINES, UON.
WHERE EXIT SIGNS ARE INDICATED ABOVE DOOR MOUNT AS FOLLOWS, CENTER THE EXIT
SIGN BETWEEN TOP OF DOOR FRAME AND CEILING IF DISTANCE BETWEEN TOP OF DOOR
FRAME AND CEILING IS 24 INCHES OR LESS; OTHERWISE MOUNT BOTTOM OF EXIT SIGN 6
INCHES FROM TOP OF DOOR FRAME, MOUNT OTHER WALL MOUNTED EXIT SIGNS IN THE
SAME AREA AT THE SAME HEIGHT. COORDINATE WITH ARCHITECTURAL DETAILS.
EXIT SIGNS ARE TO BE TYPE "X1", UON.
PROVIDE SEPARATE NEUTRALS FOR DIMMING CIRCUITS.
PROVIDE FEEDERS AND BRANCH CIRCUITS WHICH HAVE AN AMPACITY EQUAL TO OR
GREATER THAN THE CIRCUIT OVERCURRENT PROTECTIVE DEVICE RATING, U.O.N.
FURNITURE LAYOUTS ARE FOR REFERENCE ONLY. COORDINATE THE FINAL LOCATION OF
ELECTRICAL DEVICES AND OUTLETS WITH ARCHITECT, OWNER AND FINAL FURNITURE
PLANS PRIOR TO INSTALLATION.
MOUNT DEVICES FLUSH WITH CONCEALED CONDUIT, EXCEPT AS NOTED ON THE DRAWINGS
AND IN MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS.
THE DRAWINGS REPRESENT ELECTRICAL DESIGN INTENT. THEY ARE DIAGRAMMATIC.
PROVIDE ALL COMPONENTS NECESSARY FOR COMPLETE OPERATING ELECTRICAL
SYSTEMS.
WHEN MORE THAN ONE 20A., 1P., 120 VOLT CIRCUIT FEEDS A SURFACE RACEWAY CONNECT
RECEPTACLES TO ALTERNATE CIRCUITS AS FOLLOWS - U.O.N.
ALL ELECTRICAL WORK SHALL CONFORM TO AND BE IN ACCORDANCE WITH THE LATEST
EDITION OF THE NATIONAL ELECTRIC CODE, NFPA 72 AND VUSBC.
THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC. REFER TO ARCHITECTURAL PLANS,
ELEVATIONS AND DETAILS FOR BUILDING DIMENSIONS AND MOUNTING LOCATIONS OF
ELECTRICAL DEVICES AND EQUIPMENT. REFER TO MECHANICAL AND/OR PLUMBING PLANS
FOR EXACT LOCATIONS OF EQUIPMENT.
MATERIALS AND EQUIPMENT SHALL CONFORM TO AND BE IN ACCORDANCE WITH THE
LATEST APPLICABLE STANDARDS OF THE NATIONAL ELECTRICAL MANUFACTURERS'
ASSOCIATION (NEMA) AND THE AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI). WHERE
STANDARDS HAVE BEEN ESTABLISHED BY THE UNDERWRITERS' LABORATORIES, THE
MATERIALS AND EQUIPMENT SHALL BEAR THE UL LABEL AND SHALL BE LISTED FOR THE
APPLICATION USED.
FURNISH ALL LABOR, MATERIALS, SERVICES AND SKILLED SUPERVISION NECESSARY FOR
THE CONSTRUCTION, ERECTION, INSTALLATION, CONNECTIONS, TESTING AND ADJUSTMENT
OF ALL CIRCUITS AND ELECTRICAL EQUIPMENT SPECIFIED HEREIN OR SHOWN ON THE
DRAWINGS AND ITS DELIVERY TO THE OWNER COMPLETE IN ALL RESPECTS AND READY
FOR USE. ALL ELECTRICAL WORK SHALL BE NEW EXCEPT WHERE SPECIFICALLY NOTED
OTHERWISE.
ALL WORK SHALL BE INSTALLED IN A WORKMANLIKE MANNER IN ACCORDANCE WITH THE
ACCEPTED STANDARDS FOR THE INDUSTRY INVOLVED.
CEILING GRID LAYOUTS, WHERE SHOWN ON THE DRAWINGS, ARE FOR REFERENCE ONLY.
THE EXACT LOCATIONS AND MOUNTING HEIGHTS OF ALL LIGHTING FIXTURES SHALL BE
COORDINATED WITH ARCHITECTURAL REFLECTED CEILING PLANS, ARCHITECTURAL
DETAILS, MECHANICAL AND PLUMBING PLANS, PRIOR TO INSTALLATION OF FIXTURES.
CEILING TYPES SHALL BE AS NOTED ON THE ARCHITECTURAL REFLECTED CEILING PLANS
AND ARCHITECTURAL DETAILS. COORDINATE ALL REQUIRED LIGHTING FIXTURE
ACCESSORIES AND MOUNTING HARDWARE WITH THE CEILING TYPES AS SHOWN ON THE
DRAWINGS PRIOR TO ORDERING AND INSTALLATION OF LIGHTING FIXTURES. THE
CONTRACTOR SHALL PROVIDE ALL FIXTURE ACCESSORIES AND MOUNTING HARDWARE AS
REQUIRED FOR A COMPLETE INSTALLATION OF THE FIXTURES.
CONTRACTOR SHALL VERIFY ALL DOOR SWINGS WITH THE ARCHITECTURAL DRAWINGS
PRIOR TO THE INSTALLATION OF LIGHT SWITCHES. LIGHT SWITCHES SHALL BE INSTALLED
ON THE LOCK SIDE OF DOORS UNLESS PHYSICALLY IMPOSSIBLE TO INSTALL IN THE
LOCATION OR NOTED OTHERWISE ON THE DRAWINGS.
WHERE MULTIPLE LIGHT SWITCHES ARE SHOWN IN ONE LOCATION ON LIGHTING PLANS,
SWITCHES SHALL BE GANGED UNDER A COMMON COVER PLATE. PROVIDE BARRIERS IN
SWITCH BOXES WHERE REQUIRED BY THE LATEST EDITION OF NEC.
FURNITURE LAYOUTS, WHERE SHOWN ON THE DRAWINGS, ARE FOR REFERENCE ONLY.
THE FINAL LOCATION OF ALL ELECTRICAL DEVICES AND OUTLETS SHALL BE COORDINATED
WITH ARCHITECT, OWNER AND FINAL FURNITURE PLANS PRIOR TO INSTALLATION OF ALL
DEVICES AND OUTLETS.
ALL DEVICES SHALL BE FLUSH MOUNTED WITH CONCEALED CONDUIT, EXCEPT AS NOTED
ON THE DRAWINGS AND IN ELECTRICAL EQUIPMENT ROOMS.
EXIT LIGHTS SHALL BE CENTERED IN CEILING TILE OF 6" ABOVE DOOR IF WALL MOUNTED.
NOT ALL SYMBOLS AND ABBREVIATIONS ARE NECESSARILY USED ON THIS PROJECT.
ALL FEEDER AND BRANCH CIRCUITS SHALL INCLUDE A CODE SIZED (LARGER WHERE
INDICATED ON THE DRAWINGS) GROUNDING CONDUCTOR.
ALL NEW PANELBOARDS SHALL HAVE A DOUBLE DOOR (DOOR-IN-DOOR) FEATURE, UON.
ALL JUNCTION BOX SHALL BE SINGLE GANG 4X4 SQUARE AND PROVIDE MIN. 3/4" CONDUIT
FROM JUNCTION BOX TO THE COURCE, UON.
COORDINATE ALL WALL MOUNTED DEVICES WITH ARCHITECTURAL DRAWINGS PRIOR TO
ROUGH-IN. SEE DEVICE MOUNTING HEIGHTS ON THIS DRAWING FOR DEVICE MOUNTING
HEIGHTS NOT INDICATED ON ARCHITECTURAL DRAWINGS.
PROVIDE FIRE RATED SEAL ON ALL CONDUITS PENETRATING FIRE RATED WALLS, U.O.N.
REFER TO ARCHITECTURALLY SIGNIFICANT EQUIPMENT BOOK IN THE PROJECT MANUAL
FOR SPECIFIC EQUIPMENT REQUIREMENTS.
DESIGN FOR PET/CT AND MRI SPACES IS BASED ON EQUIPMENT PROVIDED BY GE
(GENERAL ELECTRIC COMPANY).
WHERE SINGLE PHASE CIRCUITS SHARE A COMMON NEUTRAL PROVIDE A MULTI-POLE
CIRCUIT BREAKER AS REQUIRED TO DICONNECT POWER TO ALL PHASE CONDUCTORS
SHARING THE SAME NEUTRAL.
ALL EQUIPMENT SHALL NOT CONTAIN MERCURY, INCLUDING SWITCHES AND OTHER
BUILDING EQUIPMENT. ALL LAMPS FOR LIGHT FIXTURES SHALL MEET THE MERCURY
REQUIREMENTS LISTED ON SHEET E7.01.
REFER TO NEC 392.18 CABLE TRAY INSTALLATION. NO CABLING CAN BE SUPPORTED FROM
THE OUTSIDE OF CABLE TRAY (I.E SIDES AND BOTTOM)
A.
B.
C.
D.
E.
F.
G.
H.
J.
K.
L.
M.
N.
O.
P.
Q.
R.
S.
T.
U.
V.
W.
X.
Y.
Z.
AA.
BB.
CC.
DD.
EE.
FF.
GG.
HH.
JJ.
KK.
LL.
MM.
NN.
OO.
PP.
QQ.
ELTD EMERGENCY LIGHTING TRANSFER DEVICE
ELECTRICAL EQUIPMENT SYMBOLS
ELECTRICAL WIRING SYMBOLS
DISTRIBUTION AND DIAGRAM SYMBOLS
REFERENCE SYMBOLS
SECTION NUMBER
DETAIL NUMBER
DRAWING NUMBER WHERE DRAWN
DRAWING NUMBER WHERE DRAWN
E1-1.0 KEY NOTE
SPECIAL SYSTEM OUTLET SYMBOLS
E1-1.0
M
SINGLE IG RECEPTACLE, 20A, 125V, 2P, 3W., FLOOR MTD SERVICE FITTING, FLUSH TYPE UON
("S" DENOTES SURFACE TYPE)
DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W., FLOOR MTD SERVICE FITTING, FLUSH TYPE UON
("S" DENOTES SURFACE TYPE)
DUPLEX IG RECEPTACLE, 20A, 125V, 2P, 3W., FLOOR MTD SERVICE FITTING, FLUSH TYPE UON
("S" DENOTES SURFACE TYPE)
QUADRUPLEX IG RECEPTACLE, (2) 20A, 125V, 2P, 3W., FLOOR MTD SERVICE FITTING, FLUSH
TYPE UON ("S" DENOTES SURFACE TYPE)
INV BATTERY INVERTER
GB
TGB
GB
TGB
GROUND BAR
TELECOMMUNICATION GROUND BAR
MOUNTING HEIGHTS
MOUNTING HEIGHT NOTES:
1. ALL ELEVATIONS ARE TO CENTER LINE OF DEVICE, UNLESS OTHERWISE NOTED.
2. REFER TO EQUIPMENT ELEVATION DRAWINGS FOR COORDINATION WITH
CASEWORK.
3. MOUNT MANUAL MOTOR STARTER ADJACENT TO OR ON UNIT.
4. REFER TO ARCHITECTURAL A0 SERIES FOR ADDITIONAL ELECTRICAL DEVICE
MOUNTING HEIGHTS AND DEVICE ALIGNMENT RULES.
3Da
OR
THREE-WAY DIMMER SWITCH (SUBSCRIPT INDICATES FIXTURES CONTROLLED)
OCCUPANCY SENSOR OVERRIDE SWITCH
A
1 K a
COMBINATION USB DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W WITH (2) 5VDC, 2.1A USB
CHARGING PORTS
L1D LOW VOLTAGE DIMMING SWITCH WITH ON/OFF AND RAISE/LOWER BUTTONS FOR ONE ZONE
L2D LOW VOLTAGE DIMMING SWITCH WITH ON/OFF AND RAISE/LOWER BUTTONS FOR TWO ZONES
L3D LOW VOLTAGE DIMMING SWITCH WITH ON/OFF AND RAISE/LOWER BUTTONS FOR THREE ZONES
L4D LOW VOLTAGE DIMMING SWITCH WITH ON/OFF AND RAISE/LOWER BUTTONS FOR FOUR ZONES
LC LIGHTING CONTROL TOUCH SCREEN FOR PARTITION ROOM LIGHTING CONTROL.
CS COMBINED DUAL TECHNOLOGY OCCUPANCY SENSOR AND PHOTOSENSOR
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
Pl ot
D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
NTS
1/ 4/
1:
:0
AM SYMBOLS,
ABBREVIATIONS, AND
GENERAL NOTES
E0.1 10822.000
LC, LCP LIGHTING CONTROL PANEL
LP LIGHTING PANEL
LSI LONG-TIME, SHORT-TIME, INSTANTANEOUS
LSIA LONG-TIME, SHORT-TIME,
INSTANTANEOUS,GROUND-FAULT ALARM ONLY
LSIG LONG-TIME, SHORT-TIME,
INSTANTANEOUS,GROUND-FAULT
LTG LIGHTING
LV LOW VOLTAGE (BELOW 50 VOLTS)
(M)
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MECH MECHANICAL
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MOCP MAXIMUM OVERCURRENT PROTECTION
MS MOTORIZED SHADES
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE (OVER 600V LESS THAN 35KV)
MW MICROWAVE
(N)
N NEUTRAL
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NO., NUM. # NUMBER
NTS NOT TO SCALE
(O)
OC ON CENTER
OCPD OVERCURRENT PROTECTION DEVICE
OFCI OWNER FURNISHED, CONTRACTOR INSTALLED
OFOI OWNER FURNISHED, OWNER INSTALLED
OH OVERHEAD
OHE/T OVERHEAD ELECTRIC/TELEPHONE
OPP OPPOSITE
(P)
P POLE
PA PUBLIC ADDRESS
PB PULL BOX
PDP POWER DISTRIBUTION PANEL
PE PHOTO ELECTRIC
PF POWER FACTOR
PH, Ø PHASE
PNL PANEL
PRI PRIMARY
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE
PWR POWER
(Q)
QTY QUANTITY
(R)
R, RE RELOCATE AS SHOWN
RCLP REMOTE CONTROL LIGHTING PANEL
RCPT RECEPTACLE
REF REFRIGERATOR
RF RADIO FREQUENCY
RG RANGE
RH RANGE HOOD
RLA RATED (RUNNING) LOAD AMPS
RM ROOM
RP RECEPTACLE PANELBOARD
RSC RIGID STEEL CONDUIT
(S)
SB SMARTBOARD
SCAN SCANNER
SCH, SCHED SCHEDULE
SEC SECONDARY
SF SQUARE FOOT
SPD SURGE PROTECTIVE DEVICE
SPDT SINGLE POLE DOUBLE THROW
SPEC(S) SPECIFICATION(S)
SPKR SPEAKER
SPST SINGLE POLE SINGLE THROW
STD STANDARD
STV STOVE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
SYM SYMMETRICAL
(T)
TB TERMINAL BLOCK
TBB TELEPHONE BACKBOARD
TC TIME CLOCK
TEL, TELE TELEPHONE
TELECOM TELECOMMUNICATIONS
TP TAMPERPROOF
TT TREATMENT TABLE
TV TELEVISION
TW TECHNOLOGY WALL
TYP TYPICAL
TZ TRAZER UNIT
(U)
UCR UNDER CABINET REFRIGERATOR
UG UNDERGROUND
UGP UNDERGROUND PRIMARY
UGS UNDERGROUND SECONDARY
UGT UNDERGROUND TELEPHONE
UL UNDERWRITER'S LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
(V)
V VOLTS
VA VOLT-AMPERES
VFD VARIABLE FREQUENCY DRIVE/ VARIABLE
FREQUENCY MOTOR CONTROLLER
(W)
W WIRE
W/ WITH
W/D WASHER/DRYER
W/O WITHOUT
WHM WATT HOUR METER
WP WEATHERPROOF
(X)
X REMOVE DEVICE
XFMR TRANSFORMER
(Z)
%Z PERCENT IMPEDANCE
(A)
A AMPERES
AC ALTERNATING CURRENT
AF AMPERE FRAME (BREAKER RATING)
AFC ABOVE FINISHED COUNTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
ARCH ARCHITECT
AT AMPERES TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AWG AMERICAN WIRE GAUGE
(B)
BLDG BUILDING
BRKR, BKR BREAKER
(C)
C CONDUIT
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CLG CEILING
CM COFFEE MAKER
COM, COMM COMMUNICATIONS
COPY COPIER
CP CONTROL PANEL
CPT CONTROL POWER TRANSFORMER
CT CURRENT TRANSFORMER
CTC COLD TREATMENT CONDITIONER
CU COPPER
(D)
DC DIRECT CURRENT
DISC DISCONNECT
DIST DISTRIBUTION
DIV DIVISION
DN DOWN
DP DISTRIBUTION PANEL
DPDT DOUBLE POLE DOUBLE THROW
DPST DOUBLE POLE SINGLE THROW
DW DISHWASHER
DWG DRAWING
(E)
E, EX, EXIST EXISTING
EFC ELECTRIC FAUCET
EG EQUIPMENT GROUND
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM. EMEG EMERGENCY
EMT ELECTRIC METALLIC CONDUIT
ENCL ENCLOSURE
EQ, EQIP EQUIPMENT
ET EXAM TABLE
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXH EXHAUST HOOD
(F)
F FUSE
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FAEP FIRE ALARM EXTENDER PANEL
FC FOOT CANDLE
FDR FEEDER
FL, FLR FLOOR
FLA FULL LOAD AMPS
FLEX FLEXIBLE
FLUOR FLUORESCENT
FT FOOT / FEET (')
(G)
G, GND, GRD GROUND
GD GARBAGE DISPOSAL
GEN GENERATOR
GFI GROUND FAULT INTERRUPTER
GFI GROUND FAULT INTERRUPTER
(H)
H HORIZONTAL MOUNTING
HC HYDROCULATOR
HD HAND DRYER
HH HAND HOLE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HPS HIGH PRESSURE SODIUM
HR HOUR
HT HEIGHT
HTR HEATER
HVAC HEATING VENTILATION AND AIR CONDITIONING
HZ HERTZ
(I)
ICE ICE MAKER
IG ISOLATED GROUND
IN INCH / INCHES (")
INCAND INCANDESCENT
INV INVERTER
(J)
JB, JBOX JUNCTION BOX
(K)
K KEY INTERLOCK
Kcmil 1000 CIRCULAR mils
KV KILOVOLTS (THOUSAND VOLTS)
KVA KILOVOLTS-AMPERES (THOUSAND VOLT-AMPS)
KW KILOWATTS (THOUSAND WATTS)
KWH KILOWATT-HOURS
(L)
L-G LINE TO GROUND
L-L LINE TO LINE
L-N LINE TO NEUTRAL
LA LIGHTNING ARRESTOR
LAN LOCAL AREA NETWORK
ACCESS CONTROL DEVICES 4'-0" AFF
CLOCK OUTLETS 7'-0" AFF
DIMMERS 4'-0" AFF
DISCONNECT SWITCHES 5'-6" AFF
INDIVIDUAL CIRCUIT BREAKERS 5'-6" AFF
INTERCOM 4'-0" AFF
MOTOR STARTERS 5'-6" AFF
PANELBOARDS & CABINETS 6'-0" AFF TO TOP
PUSHBUTTONS 4'-0" AFF
RECEPTACLES 1'-6" AFF
RECEPTACLES ABOVE FINISHED COUNTER 8" AFC
VANITY LIGHT IN TOILET 6" ABOVE THE MIRROR, UON
VOLUME CONTROLS 4'-0" AFF
WALL SWITCHES 4'-0" AFF
TELECOMMUNICATIONS OUTLETS 1'-6" AFF
TELECOMMUNICATIONS OUTLETS - WALL PHONE 4'-0" AFF
TV OUTLETS 5'-0" AFF
NURSE CALL DOME LIGHTS 7'-6" AFF
NURSE CALL STATIONS 4'-0" AFF
PUBLIC RESTROOM WALL SWITCHES 3'-6" AFF
3'-6" AFF
DAILY LIVING SKILLS WALL SWITCHES 4'-0" AFF
SCHEMATIC DESIGN 8.17.2018
DESIGN DEVELOPMENT 11.08.2018
CONTRACT DOCUMENTS 01.04.2019
T
P
P
T
T
P
P P
P
P
T
J
M J J
DIRECT BURIAL WARNING TAPE
12" BELOW GRADE, WORDED
"CAUTION-BURIED ELECTRICAL
LINE BELOW".
FIN. GRADE
WALL OF
TRENCH
#2/0 GROUND
(DELETE GROUND CONDUCTOR IF NOT
REQUIRED BY UTILITY COMPANY
RED
CONCRETE
ENCASEMENT
PLASTIC UTILITIES
DUCT SIZE AND
QUANTITY AS
INDICATED
PVC
SPACER/
SUPPORTS
EARTH FILL
3" 36" MINIMUM
3"
3"
3"
3"
4"
4"
E116
SB
SB
SB
SB
800A
SWITCHBOARD
500KVA TRANSFORMER PROVIDED BY CHELCO,
(25KV PRIMARY, 480Y/277V, 3-PHASE, 4-WIRE SECONDARY)
- CT CABINET, CTs, AND UTILITY METER TO BE INSTALLED BY
BUILDING CONTRACTOR.
- PRIMARY FEEDER PROVIDED/INSTALLED BY CHELCO.
- CONCRETE EQUIPMENT PAD PROVIDED BY GOVERNMENT
(CONCRETE PAD TO INCLUDE SECONDARY CONDUIT ELBOWS
AND CT ELBOWS CAPPED BEYOND PAD)
-TEMPORARY POWER FOR SITE CONSTRUCTION ACTIVITIES TO BE
COORDINATED BETWEEN CONTRACTOR AND CHELCO.
(TYP)
E105
T
WAWA
WA
E104 E106
VIA LCP-5
CH-1
WP
GN1- 1
DP-H- 19
E115
CHILLER
FEEDER
SECONDARY SERVICE
DUCT BANK AND
FEEDER.
FLAG POLE
DROP OFF
70 TOTAL PARKING SPACES
UTILITY YARD
DUMPSTER
ENCLOSURE
SC
SC
SC
SD
SD
SD
SD
SD
SD
E119
LS1- 5
CONCRETE BASES FOR
PARKING LOT LIGHTING
TO BE DESIGNED AND
INSTALLED BY SITE
CONTRACTOR. TYP.
VIA LCP-6
HANDHOLE
30"X48"X24"
E123
E121
E124
E125
LN1- 27
HANDHOLE
E107
DIRECT BURIAL WARNING TAPE
12" BELOW GRADE, WORDED
"CAUTION-BURIED ELECTRICAL
LINE BELOW".
FIN. GRADE
WALL OF
TRENCH
RED
CONCRETE
ENCASEMENT
PLASTIC UTILITIES
DUCT SIZE AND
QUANTITY AS
INDICATED
PVC
SPACER/
SUPPORTS
EARTH FILL
3" 36" MINIMUM
3"
3"
3"
3"
4"
4"
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
PLAN
NORTH
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
Pl ot
D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
As indicated
1/ 4/
1:
:1
AM ELECTRICAL SITE
PLANS
E1.1 10822.000
KEYED NOTES
SHEET NOTES
A. SEE SHEET E0.01 FOR SYMBOLS, ABBREVIATIONS, AND
GENERAL NOTES.
B. SEE SHEET E7.01 FOR LIGHTING FIXTURE SCHEDULE.
C. COORDINATE WITH LOCAL UTILITY FOR ALL SITE SERVICE
REQUIREMENTS.
D. CONTACT LOCAL UTILITY TO IDENTIFY ALL EXISTING
UNDERGROUND UTILITIES.
E. THE LIGHTING CIRCUITING IS DIAGRAMMATIC. PROVIDE SWITCH
LEGS, UNSWITCHED LEGS, PHASE WIRES AND TRAVELLERS AS
NECESSARY.
F. COORDINATE LIGHTING FIXTURE LOCATIONS WITH
ARCHITECTURAL REFLECTED CEILING PLAN AND CIVIL PLANS.
G. LIMIT VOLTAGE DROP TO 3%.
H. COORDINATE EXACT LOCATION OF ALL EQUIPMENT WITH CIVIL
DRAWINGS.
I. SEE ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS AND
MOUNTING HEIGHTS OF FIXTURES.
J. ARCHITECT HAS FINAL APPROVAL OVER ALL FINISHES.
K. ALL FIXTURES WITH AN "E" SUBSCRIPT ARE EXISTING TO
REMAIN. MAINTAIN ALL CIRCUIT CONTINUITY AND PROTECT
FROM DAMAGE DURING CONSTRUCTION.
L. ALL FIXTURES WITH AN "RL" SUBSCRIPT ARE TO BE RELOCATED
PER THE CIVIL DRAWINGS. SEE CIVIL DFRAWINGS FOR EXACT
FIXTURE LOCATIONS. EXTEND ALL CONDUIT AND WIRING TO
NEW LOCATION AND MAINTAIN CIRCUIT CONTINUITY. PROTECT
FROM DAMAGE DURING CONSTRUCTION.
FEEDER SCHEDULE
SCALE: 12" = 1'-0"1 SITE-DUCT BANK 4-WAY W/SPACERS
SCALE: 1" = 20'-0"2 ELECTRICAL SITE PLAN
E104 COORDINATE CHILLER HEATER WITH
MECHANICAL CONTRACTOR AND IN-FIELD
CONDITIONS.
E105 PROVIDE STRAIGHT, ROUND CONCRETE POLE
BASE WITH 24" DIAMETER AND 6" HEIGHT ABOVE
FINISHED GRADE. SEE ELECTRICAL DETAIL SHEET
E6.01. COORDINATE LIGHT POLE-BASE HEIGHT
WITH EXISTING BASE STANDARD. WORK TO BE
COMPLETED BY SITE CONTRACTOR.
E106 JUNCTION BOX FOR CHILLER PIPING FREEZE
PROTECTION HEAT TRACE CONDUCTORS. HEAT
TRACE CONDUCTORS BY DIVISION 23, POWER
CONDUCTORS BY DIVISION 26. HEAT TRACE
POWER CONDUCTORS TO 20A/1P/277V CIRCUIT
BREAKER IN PANEL 'DP1' IN MECHANICAL ROOM.
COORDINATE EXACT LOCATION OF JUNTION BOX
WITH DIVISION 23.
E107 JUNCTION BOX FOR CHILLER FREEZE
PROTECTION HEAT TRACE CONDUCTORS. HEAT
TRACE CONDUCTORS BY DIVISION 23, POWER
CONDUCTORS BY DIVISION 26. HEAT TRACE
POWER CONDUCTORS TO 20A/1P/277V CIRCUIT
BREAKER IN PANEL 'DP1' IN MECHANICAL ROOM.
COORDINATE EXACT LOCATION OF JUNTION BOX
WITH DIVISION 23.
E108 PROVIDE 1-1/2" EMPTY PVC, SCHEDULE #40 WITH
DRAG WIRE FOR 208Y/120 VOLT ANCILLARY
POWER CONNECTIONS IN CHILLER ENCLOSURE.
MINIMUM 24" BELOW GRADE. STUB UP ROUT
CONDUIT AT PANEL 'GN1' IN MECHANICAL ROOM.
E109 PROVIDE 1-1/2" EMPTY PVC, SCHEDULE #40 WITH
DRAG WIRE FOR HEAT TRACE CIRCUITS AND
480Y/277 VOLT ANCILLARY POWER CONNECTIONS
IN CHILLER ENCLOSURE. MINIMUM 24" BELOW
GRADE. STUB UP ROUT CONDUIT AT PANEL 'DP-H'
IN MECHANICAL ROOM.
E110 PROVIDE 1-1/2" EMPTY PVC, SCHEDULE #40 WITH
DRAG WIRE FOR HVAC CONTROLS WIRING IN
CHILLER ENCLOSURE. MINIMUM 24" BELOW
GRADE.
E111 PROVIDE 1-1/2" EMPTY PVC, SCHEDULE #40 WITH
DRAG WIRE FOR CHILLER ENCLOSURE LIGHTING
CIRCUIT FROM PANEL 'LN1'. MINIMUM 24" BELOW
GRADE. SEE SHEET E3.01.
E112 STUB-UP 1-1/2" EMT ALONG WALL IN MECHANICAL
ROOM NEAR HINGE SIDE OF DOOR. SEE
ELECTRICAL POWER PLAN E2.1 FOR
CONTINUATION.
E115 SWITCH FOR UTILITY YARD LIGHTING. PROVIDE IN
NEMA 4X ENCLOSURE
E116 STUB-UP 1-1/2" PVC OR RGS FOR HVAC CONTROL
WIRING (BY DIVISION 23). EXACT COORDINATE
EXACT LOCATION WITH DIVISION 23.
E119 STUB-UP 3-1/2" RGS.
E120 PROVIDE 3-1/2" EMPTY PVC, SCHEDULE #40 WITH
DRAG WIRE FOR CHILLER. MINIMUM 24" BELOW
GRADE. SEE SHEET E7.0 FOR FEEDER SIZE.
E121 CONDUIT STUB-UP 6" FOR CHILLER POWER TO BE
ROUTED TO MAIN SWITCHBOARD IN ELEC RM 111.
E123 PROVIDE 1" EMPTY PVC SCHEDULE #40 WITH
DRAG WIRE. ROUTE PVC MINIMUM 24" BELOW
GRADE
E124 STUB UP 1" EMT CONDUIT.
E125 STUB UP 1-1/2" EMT CONDUIT
SCALE: 12" = 1'-0"3 SITE-DUCT BANK 4-WAY W/SPACERS - COMMUNICATION
SCHEMATIC DESIGN 8.17.2018
LC
T
FB
FB2
FB3
FB3FB3
FB2
FB2 FB2 FB2
FB2FB2
FB2
FB
FB
FB
FB
FB
FB
FB
FB
FB
FB
FB1
M
FB2
FB2
FB1 FB1
8.38.6
7.1
6.9 6.5 6.2
5.4
5.2
4.8
4.5
3.6
2.8
2 1
0.2A
0.3A
0.4A
0.7A
0.9A A
A.2
A.9
A.7
B B
D D
D.7
E
F F
0.5A
RS2
RS1-2
RS1-1
LS1
RN1-2
RN1-1
LN1
800A SWBD
EF102
(TYP)
EF107
EF123EF123
EF123
EF104
EF116
EF108
EF108
EF108
EF108
6.8 6.4
B2
C C
E.8
EF120
EF101
RN2
EF118
EF107
EF108
EF124
EF108
EF108
EF105
EF110
HH
EF117
EF117
EF118
E1.1
EF123EF123
HH
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
PLAN
NORTH
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
Pl ot
D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
1/8" = 1'-0"
1/ 7/
:3
8:
P
M FOUNDATION POWER
PLAN
E2.0 10822.000
KEYED NOTES
SHEET NOTES
A. SEE SHEET E0.01 FOR SYMBOLS, ABBREVIATIONS, AND
GENERAL NOTES.
B. COORDINATE WITH LOCAL UTILITY FOR ALL SITE SERVICE
REQUIREMENTS.
C. CONTACT LOCAL UTILITY TO DENTIFY ALL EXISTING
UNDERGROUND UTILITIES.
D. COORDINATE EXACT LOCATION OF ALL EQUIPMENT WITH CIVIL
DRAWINGS.
E. THIS SHEET IS ISSUED FOR FOUNDATION AND STEEL
CONSTRUCTION. DESIGN OF ITEMS NOT PERTAINING TO THIS
ISSUE SHOULD NOT BE CONSIDERED FINAL AND MAY CHANGE
IN FUTURE ISSUES WITHOUT BEING CLOUDED. ITEMS
PERTAINING TO FOUNDATION AND STEEL CONSTRUCTION
WHICH CHANGE IN THE FUTURE SHALL BE CLOUDED.
XX
EF101 (1) 1" CONDUIT (RN1-208/120V) FROM THE MAIN
ELECTRICAL ROOM WITH DRAG WIRE UNDER
SLAB TO BUILDING EXTERIOR FOR FUTURE
EXTERIOR CIRCUITS.
EF102 (1) 1" CONDUITS (LN1-480/277V) FROM THE MAIN
ELECTRICAL ROOM WITH DRAG WIRE UNDER
SLAB TO BUILDING EXTERIOR FOR FUTURE
EXTERIOR CIRCUITS.
EF104 (1) 1" CONDUIT (LS1-480/277V) FROM THE SOUTH
ELECTRICAL ROOM WITH DRAG WIRE UNDER
SLAB TO EXTERIOR BUILDING FOR FUTURE
EXTERIOR CIRCUITS,
EF105 (1) 1" CONDUIT (RS1-208/120V) FROM THE SOUTH
ELECTRICAL ROOM WITH DRAG WIRE UNDER
SLAB TO EXTERIOR BUILDING FOR FUTURE
EXTERIOR CIRCUITS.
EF107 (1) 3/4" CONDUIT FOR POWER AND (1) 1 1/4"
CONDUIT FOR TELE/COMM TO CONNECT TO
DUAL SUPPLY FLUSH MOUNTED FLOOR BOX.
ROUTE CONDUIT TO PANEL 'RN1-1' ELECTRICAL
ROOM. COORDINATE EXACT LOCATION OF
FLOOR BOX WITH ARCHITECTURAL DRAWINGS.
EF108 (1) 3/4" CONDUIT FOR POWER TO PANEL 'GN1' IN
MECHANICAL ROOM. COORDINATE EXACT
LOCATIONS OF FLOOR BOXES WITH
ARCHITECTURAL DRAWINGS.
EF110 (1) 3/4" CONDUIT FOR POWER AND (1) 1 1/4"
CONDUIT FOR TELE/COMM RUN IN SLAB AND UP
INTO HALF WALL OF GYM DESK. ROUTE
CONDUIT TO THE NEAREST WALL. COORDINATE
EXACT LOCATION OF DESK WITH
ARCHITECTURAL DRAWINGS.
EF116 (4) FOUR 4" SCHEDULE 40 PVC CONDUITS WITH
DRAG WIRE TO TELECOMMUNICATIONS ROOM
FROM MANHOLE. COORDINATE WITH TELECOM
DRAWINGS AND COORDINATE WITH CIVIL
DRAWINGS FOR LOCATION OF MANHOLE.
EF117 (1) 3/4" CONDUIT FOR POWER TO CONNECT TO
SINGLE SERVICE FLUSH MOUNTED FLOOR BOX.
ROUTE CONDUIT TO PANEL 'RS1-2' IN SOUTH
ELECTRICAL ROOM. COORDINATE EXACT
FLOORBOX LOCATIONS WITH ARCHITECTURAL
DRAWINGS.
EF118 (1) 1" PVC (2) #12 AND #12G FOR FIXTURE TYPE
'SB'/'SC'. REFER TO SPEC SECTION TO
TRANSITION FROM EMT WITHIN THE BUILDING
TO PVC OUTSIDE THE BUILDING. SEE SHEET
E1.1.
EF120 COORDINATE TERMINATION OF UNDERGROUND
DUCTBANK WITH LOCATION OF SWITCHBOARD
CONDUIT ENTRY.
EF123 (1) 3/4" CONDUIT FOR POWER TO PANEL 'RN2' IN
ELECTRICAL ROOM. COORDINATE EXACT
LOCATIONS OF FLOOR BOXES WITH
ARCHITECTURAL DRAWINGS.
EF124 (1) 3/4" CONDUIT FOR POWER TO PANEL 'GN1' IN
MECHANICAL ROOM AND (1) 1 1/4" CONDUIT
STUB UP TO CLOSEST WALL CAVITY.
COORDINATE EXACT LOCATIONS OF FLOOR
BOXES WITH ARCHITECTURAL DRAWINGS.
SCHEMATIC DESIGN 8.17.2018
FB
J
FB2
FB3
FB3FB3
J M
J M
M
M
J
J J
J
J
J
M
J
J
J
J
J
J
J
J
J
M
M
M
M
M
M M
MM
FB2
FB2 FB2
J
FB2
FB2FB2
FB2
M
J JJ J
JJ J J J
FB
FB
FB
FB
FB
FB
FB
FB
FB
FB
FB1
M J
J
J
FB2
FB2
M
M
M
J
J
J
M
J
J
FB1 FB1
M
8.38.6
7.1
6.9 6.5 6.2
5.4
5.2
4.8
4.5
3.6
2.8
2 1
0.2A
0.3A
0.4A
0.7A
0.9A A
A.2
A.9
A.7
B B
D D
D.7
E E
F F
0.5A
B-2
B-1
CWP-2
CWP-1
HWP-2
HWP-1 VF
D
VF
D
VF
D
VF
D
WP
AHU LIGHTS
AHU RECEPTACLES
HWRP-1
ETP-1
DWH-1
VF
D
VF
DSF-1
SF-2
UNISTRUT
SUPPORT
VF
D
VF
D
RF-1
RF-2
ERW-1
UNISTRUT
SUPPORT
UH-1
UH-2
COPY
FCU-1
E202
E202
E218
E218E218
E209
E209
E209
E209
E209
E209
E209
WP
WP
WP
WP
WP
WP
WP
WP
WP
E212
E212
EV-2
CP-2
E250
EV-1
CP-1
E250
E22640-3
EV-3CP-3
EV-4 CP-4
E250
E250
DP-H GN1
(TYP)
E252
E225E225
E225E225
E247E247
E244
(TYP)
E237
WP
BMS
RN1-2
RN1-1
RS1-1
RS1-2
RS2
RN2
TO CHILLER
AHU-1
6.8 6.4
B2
C C
E.8
RP-1EWC
TV
REFMW
PR
COPY
E219
TV 60" AFF
EWC
REF
14-30R
REF
MW
STV,14-50R
PR
EWC
E219
L6-30R
TV 60" AFF
E235
E235
E235
TV
E235 E249
E249
TV
E219
PR
E239
PR
E212
E212
E212E212
E244
CM
EXH
T-GN1 30KVA
CLG MNTD.
CM
E244
BMS
BMS
E258
TLT/ SHR
218.2
CHANGING / LOCKER (M)
CHANGING / LOCKER (W)
VESTIBULE
MECHANICAL
ELEC
SOIL UTIL
TREATMENT IPMC
DAYROOM
COMM
SOIL UTIL
NEUROLOGIST
PUBLIC WAITING
C101
WORKSTATION PT
PT GYM
CORRIDOR
C300
CORR
C200
TLT/ SHR
218.1
CORR
C302
CORR
C305
CORR
C304
CORR
C306
CORR
C303
CORR
C301
CORR
C201
CORR
C202
CASE MGMT
MAT / PLATFORM
GAIT OBS LANE
EQPT STOR
PC MD
CLEAN UTIL
NEURO REHAB AREA
CORR
C102.1
FAMILY WAITING
CENTRAL PARK
MAIN CORRIDOR / LOBBY
C100
NUTRITIONIST
EYE TESTING
SPEECH THERAPY - TESTING
SPEECH THERAPY - OFFICE
EXAM
SCALE
C306.1
PAT TLT
STAFF TLT
EXAM
CLINICAL PHARMACIST
GROUP THERAPY
TEAM ROOM
PSYCH TECH
EXAM
HOUSEKEEPING
PAT TLT
PSYCH TECH
FLEX STORAGE
BRAIN LAB
ELEC
TRANS-CRANIAL MAGNETIC STIM
COMM
ACUPUNCTURE
341.1
SPIRITUAL COUNSELLING
NP PSYCH
NEUROPSYCH
ACUPUNCTURE
341.2
BH / SW PROVIDERS
BH / SW PROVIDERS
PAIN MD
PSYCHOLOGIST
CHIRO TREATMENT
CASE MGMT
STAFF LOUNGE
EXAM
EXAM
BH / SW PROVIDER
MUSIC THERAPY
CHIRO TREATMENT
RECEPTION
PTNT INTAKE CUBICLES
300.1
CASE MGMT
ART AND CLAY THERAPY
TLT / SHR
219.1
MALE TOILET
FEMALE TOILET
HOUSEKEEPING
MULTI-STATION TREATMENT RM
PT O/E
OT O/E
PT O/E
208 TRAZER / FATS
COPY
109.1
OT O/E
DAILY LIVING SKILLS
EXAM
BREAK ALCOVE
105.1
RESEARCH SHARED OFFICE
NCOIC / ADMIN
NICoE DIR.
DIR. OF OPERATIONS
AV SUPPLY
CLASSROOM
103.1
CHAPLAIN
VENDING ALCOVE
106.1
EXAM
EYE LANE
EXAM
CLASSROOM
CORR
C102
BIO NEUROFEEDBACK
GROUP THERAPY
335.1
STORAGE / KILN
338.1
CHECK-IN KIOSK
300.2
STORAGE / ALCOVE
200.1
E5.1
E5.1
E212E212
E235 TV
PR
PR
TV 60" AFF TV 60" AFF
TV 60" AFF
TV 60" AFF
TV 60" AFF
TV 60" AFF
PR
PR
MW
TV 60" AFF
PR
PR
PR
PR
PR
TV 60" AFF
TV 60" AFF
PR PR
PR
PR
PR
PR
RN2- 14
RS1-1- 35
RS1-1- 33
RS1-1- 29
RS1-1- 31
RN2- 12
GN1- 30
GN1- 34
GN1- 32
RN1-2- 18
RN2- 16
GN1- 15
GN1- 16
GN1- 13
GN1- 14
GN1- 11
GN1- 12
GN1- 5
GN1- 6
CP-6
E250E250
RS1-2- 2 RS1-2- 4RS1-2- 12 RS1-2- 5
RN1-1- 41
RN1-1- 38 RN1-1- 39
RS1-2- 37
RS1-2- 39
RS1-2- 41
RS1-1- 3
RS1-1- 19
RS1-1- 5
RS1-1- 10
RS1-1- 21
RS1-1- 14
RS1-1- 15
RS1-1- 20 RS2- 20 RS2- 27 RS1-1- 23
RS2- 35
COPY
RS1-2- 34
RS2- 13
RS1-2- 21RS1-2- 8
RS1-2- 27
RS1-2- 10
RS1-2- 15
RS1-2- 6
RS1-2- 7
RS1-2- 30
RS2- 16
RS1-2- 19
E255
RS1-2- 23
RS1-2- 22
RS2- 19
RS2- 21
RS2- 23
RS1-1- 4
RS1-1- 6
RS1-1- 32
RS1-1- 8
RS1-1- 2
RS2- 26
RN1-1- 20
RN1-1- 5
RN1-1- 3 RN1-1- 2 RN1-1- 1
RN1-1- 4
RN1-1- 10
RN1-2- 31
RN1-1- 12
RN1-1- 11
RN1-2- 32
RN1-2- 4
RN1-1- 24
RN1-2- 34
RN1-2- 25
RN1-2- 2
RN1-2- 1,3,5
RN2- 18
RN1-2- 36
RN1-1- 26
RN2- 15
GN1- 10
GN1- 31,33
GN1- 4
RN1-2- 8
RN1-1- 9
RN1-1- 6
RN1-2- 14
RN1-2- 11
RN1-2- 24
GN1- 42
GN1- 8
GN1- 22
RN2- 13 GN1- 7
GN1- 23
RN2- 17
RN1-2- 6
RN2- 27
RN2- 19
RS1-2- 9
RS1-1- 25
RS1-2- 35
RS1-2- 28
RS1-2- 13
RS1-1- 11
RS1-1- 13
RS1-1- 9
GN1- 18 GN1- 20 GN1- 19 GN1- 17 GN1- 9 GN1- 3
RN2- 20
RN1-2- 33
RN1-2- 7,9
RN1-1- 36
RN1-1- 34
RS2- 25
RS2- 24
LS1- 25,27,29
40-3
(TYP)
E249
GN1- 21
GN1- 2
CP-5EV-5
EV-6
RS1-2- 11
RS1-2- 17
RS1-2- 36
ALCOVE / STORAGE
C303.1
STAFF TLT
EQPT STOR
RN1-2- 12
GN1- 35
GN1- 38
RS2- 41RS2- 38
RN2- 25
RN2- 24
RN1-1- 33
TV 60" AFF
RN1-1- 35
RN1-1- 7
RS2- 22 (TYP)
E259
RN2- 26
GN1- 39
DAMPER
GN1- 29
RN2- 11
GN1- 41
RS1-2- 20
RS1-1- 41
RN1-1- 13
RN2- 35
RN1-1- 15
RN1-1- 8
KILN
PR
E260
E261
E262
E262
RN1-1- 14
RN1-1- 16
RN1-2- 22
RS1-2- 3
RS1-1- 7
RS1-1- 17
RN2- 7
RS1-1- 30
RS2- 11
RS2- 32
GN1- 24
RS1-2- 14
RS1-2- 33
RS2- 18
RS2- 12RS2- 15
PR
RN2- 21,23
RN1-2- 10
RN1-2- 20
RN1-1- 23
RN1-1- 21
RN1-1- 17
RN1-1- 18
RN1-1- 19
RN1-1- 22
RS1-1- 22
RS1-2- 18
RS2- 17
RS2- 14
RS1-2- 29
RS1-2- 16
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
PLAN
NORTH
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
Pl ot
D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
1/8" = 1'-0"
1/ 4/
1:
:3
AM GROUND FLOOR
POWER PLAN
E2.1 10822.000
SHEET NOTES
A. SEE DWG. E0.01 FOR ABBREVIATIONS, SYMBOLS, GENENRAL
NOTES AND DEVICE MOUNTING HEIGHT OF WALL MOUNTED
DEVICES, UON.
B. COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT
AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,
CONTROL POWER AND OTHER POWER REQUIREMENTS WITH
DIV 22 AND 23.
C. SEE MECHANICAL EQUIPMENT SCHEDULE ON E7 SERIES FOR
ASSOCIATED OVERCURRENT DEVICES, DISCONNECT
SWITCHES, STARTERS AND WIRES.
D. THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF
EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT
INSTALLER PRIOR TO ROUGH-IN.
E. COORDINATE MECHANICAL EQUIPMENT LOCATIONS AND
POWER REQUIREMENTS WITH MECHANICAL DRAWINGS.
F. SEE DRAWING E5.01 FOR POWER RISER DIAGRAMS.
G. ALL BRANCH CIRCUIT WIRING SHALL BE 2#12+1#12G IN
3/4"C,UON.
H. COORDINATE ELECTRICAL STARTER AND OVER CURRENT
PROTECTION WITH MECHANICAL EQUIPMENT
MANUFACTURER.
I. VOLTAGE DROP FOR ALL BRANCH CIRCUIT WIRING SHALL
LESS THAN 3%.
J. PROVIDE 20A/120V NORMAL POWER CIRCUITS TO VAV BOXES.
SEE "M" SERIES DRAWINGS FOR VAV BOX LOCATIONS.
K. ALL RECEPTACLES IN LOUNGES, WAITING AREAS AND PUBLIC
SPACES SHALL BE TAMPERPROOF TYPE.
L. CONTRACTOR SHALL COORDINATE AND FIELD VERIFY
REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL
EQUIPMENT AND PROVIDE NEUTRAL CONDUCTOR AS
NECESSARY.
M. COORDINATE THE LOCATION OF ALL DISCONNECT SWITCHES,
MANUAL MOTOR STARTERS AND VFDS WITH MECHANICAL
CONTRACTOR.
N. COORDINATE ALL TV MOUNTING HEIGHTS WITH
ARCHITECTURAL DRAWINGS.
O. RECEPTACLES ABOVE COUNTER SHALL BE MOUNTED
HORIZONTALLY.
P. PROVIDE A COMPLETE LIGHTNING PROTECTION SYSTEM (UL
MASTER LABEL). SEE SPECIFICATION 264113.
Q. COORDINATE ALL ROOF MOUNTED ELEMENTS, INCLUDING
THE LIGHTNING PROTECTION SYSTEM, WITH THE ROOF
INSTALLER, PRIOR TO PERFORMING ANY ROOF SYSTEM
PENETRATIONS.
KEYED NOTESXX
E202 JUNCTION BOX FOR AUTOMATIC SLIDING DOORS
TO BE LOCATED ABOVE CEILING.
E209 JUNCTION BOX FOR VAV BOX TERMINAL
CONNECTIONS TO BE LOCATED ABOVE CEILING.
LOW VOLTAGE WIRING TO CONNECT JUNCTION
BOX TO NO MORE THAN (8) VAV BOXES.
E212 RECEPTACLES AT DESK TO BE FED FROM ABOVE.
CONDUIT TO RUN DOWN COLUMN AND INTO DESK.
E218 RECEPTACLE COVER PLATE TO MATCH FINISH.
MATCH RECEPTACLE COLOR TO COVER PLATE.
E219 POWER FOR ELECTRIC WATER COOLER TO BE
INSTALLED PER MANUFACTURER'S
SPECIFICATIONS.
E225 VFD PROVIDE UNDER DIVISION 26. COORDINATE
WALL MOUNT LOCATION OF VFD WITH
MECHANICAL CONTRACTOR. PROVIDER UNISTRUT
SUPPORT WHERE REQUIRED. COORDINATE PIPE
ROUTING WITH OTHER TRADES SUCH THAT PIPING
IS NOT LOCATED DIRECTLY OVER THE VFDS.
E226 EXHAUST HOOD RECEPTACLE TO BE MOUNTED IN
THE CABINET OVER THE RANGE. CONSULT
MANUFACTURER'S INSTALLATION INSTRUCTIONS.
E235 TV RECEPTACLE TO BE MOUNTED AT 60" AFF AND
CENTERED BEHIND TV. COORDINATE WITH
TELECOM TO INSTALL DEVICES SIDE BY SIDE.
ALLIGN 18" RECEPTACLE WITH CENTERED 60"
RECEPTACLE TO BE CENTERED BENEATH TV.
E237 BMS JUNCTION BOXES SHALL BE MOUNTED AT
3'-8" AND 5'-8" AND ARE TO BE CENTERED BEHIND
EACH PANEL. COORDINATE WITH MECHANICAL
DRAWINGS.
E239 PROVIDE STAINLESS STEEL RECEPTACLE COVER
PLATE WITH GREY RECEPTACLE.
E244 EMERGENCY POWER OFF (EPO) SWITCH (BY
DIVISION 23) FOR BOILER POWER EMERGENCY
SHUT-DOWN. PROVIDE BACK BOX FOR EPO 300MM
FROM DOOR. PROVIDE 3/4" CONDUIT AND 120V
WIRING (MINIMUM 2-#12) FROM EPO SWITCH TO
BOILER CONTROL PANEL. COORDINATE EXACT
LOCATION WITH BOILER INSTALLER PRIOR TO
ROUGH-IN. SHUNT TRIP BREAKERS SHOWN IN
PANEL SCHEDULES. WIRE EACH EPO SUCH THAT
ONCE EITHER EPO IS PRESSED, BOTH B-1 AND B-2
SHUTS DOWN.
E247 CIRCUIT REQUIRES MULTIPLE JUNCTION BOXES
FOR AHU COMPARTMENTS. PROVIDE CONDUIT AS
REQUIRED. COORDINATE WITH DIVISION 23.
E249 PROVIDE STAINLESS STEEL RECEPTACLE COVER
PLATE WITH GREY RECEPTACLE. MOUNT
RECEPTACLE HORIZONTALLY IN FLOOR BASE.
REFER TO ARCHITECTURAL ELEVATIONS FOR
MOUNTING DETAIL.
E250 EVAPORATOR POWER FED FROM CONDENSER
UNIT ON ROOF. REFER TO MECHANICAL
EQUIPMENT SCHEDULE ON E7.0 FOR CIRCUITING
AND CONDUIT INFORMATION. COORDINATE WITH
MECHANICAL DRAWINGS.
E252 J-BOX TO PROVIDE POWER TO URINAL AND
LAVATORY SENSORS IN MENS RESTROOM. J-BOX
TO POWER LAVATORY SENSORS IN LADIES ROOM.
COORDINATE WITH PLUMBING DRAWINGS.
E255 COORDINATE THE MOUNTING HEIGHT WITH
MANUFACTURER/INSTALLER PRIOR TO ROUGH-IN.
E258 JUNCTION BOX FOR ELECTRIC TRAP PRIMER.
COORDINATE EXACT LOCATION WITH TRAP
PRIMER INSTALLER PRIOR TO ROUGH-IN.
E259 PROVIDE RECESSED OR SEMI-RECESSED BOX
WITHIN BRICK FOR EXTERIOR WET LOCATION
RECEPTACLES WITH "IN-USE" COVERS.
E260 COORDINATE CONNECTION WITH FINAL BMS
LOCATION WITH CONTROLS CONTRACTOR AS
DIRECTED BY THE BASE.
E261 COORDINATE WITH FURNISHED MOTORIZED
PROJECTION SCREEN PROVIDED BY THE BASE.
E262 PROVIDE ENGRAVED FACEPLATE WITH RED
LETTERS READING "C-ARM ONLY"
30 4#10 + 1#10 G, 3/4" C 40-3 3#8 + 1#10 G, 3/4" C
X FEEDER SCHEDULE
SCHEMATIC DESIGN 8.17.2018
M
M
M
M
J
8.38.6
7.1
6.9 6.5 6.2
5.4
5.2
4.8
4.5
3.6
2.8
2 1
0.2A
0.3A
0.4A
0.7A
0.9A A
A.2
A.9
A.7
B B
D D
D.7
E E
F F
0.5A
WP
WP
E221
E221
E254
E254
6.8 6.4
B2
C C
E.8
CU-1
E251
CU-2
E251
CU-3 CU-4
E251 E251
EF-4
EF-3
EF-2
EF-1
CU-6
E251
CU-5
E251
WP
E221
GN1- 40
DAMPER
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
PLAN
NORTH
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
Pl ot
D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
1/8" = 1'-0"
1/ 4/
1:
:3
AM ROOF POWER PLAN
E2.2 10822.000
KEYED NOTES
E221 GENERAL PURPOSE RECEPTACLE MOUNTED ON
UNISTRUT FRAME.
E251 CONDENSER UNIT TO CIRCUIT TO AND FEED
EVAPORATOR UNIT WITHIN THE BUILDING. REFER
TO MECHANICAL EQUIPMENT SCHEDULES ON
E7.0 FOR CIRCUITNG AND CONDUIT
INFORMATION. COORDINATE WITH MECHANICAL
DRAWINGS.
E254 CIRCUIT CONTINUES TO ELECTRICAL ROOM
BELOW.
SHEET NOTES
A. SEE DWG. E0.01 FOR ABBREVIATIONS, SYMBOLS, GENENRAL
NOTES AND DEVICE MOUNTING HEIGHT OF WALL MOUNTED
DEVICES, UON.
B. COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT
AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,
CONTROL POWER AND OTHER POWER REQUIREMENTS WITH
DIV 22 AND 23.
C. SEE MECHANICAL EQUIPMENT SCHEDULE ON E7 SERIES FOR
ASSOCIATED OVERCURRENT DEVICES, DISCONNECT
SWITCHES, STARTERS AND WIRES.
D. THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF
EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT
INSTALLER PRIOR TO ROUGH-IN.
E. COORDINATE MECHANICAL EQUIPMENT LOCATIONS AND
POWER REQUIREMENTS WITH MECHANICAL DRAWINGS.
F. SEE DRAWING E5.01 FOR POWER RISER DIAGRAMS.
G. ALL BRANCH CIRCUIT WIRING SHALL BE 2#12+1#12G IN
3/4"C,UON.
H. COORDINATE ELECTRICAL STARTER AND OVER CURRENT
PROTECTION WITH MECHANICAL EQUIPMENT
MANUFACTURER.
I. VOLTAGE DROP FOR ALL BRANCH CIRCUIT WIRING SHALL
LESS THAN 3%.
J. PROVIDE 20A/120V NORMAL POWER CIRCUITS TO VAV BOXES,
MAXIMUM TEN (10) VAV BOXES PER 20A CIRCUIT. SEE "M"
SERIES DRAWINGS FOR VAV BOX LOCATIONS.
K. ALL RECEPTACLES IN LOUNGES, WAITING AREAS AND PUBLIC
SPACES SHALL BE TAMPERPROOF TYPE.
L. CONTRACTOR SHALL COORDINATE AND FIELD VERIFY
REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL
EQUIPMENT AND PROVIDE NEUTRAL CONDUCTOR AS
NECESSARY.
M. COORDINATE THE LOCATION OF ALL DISCONNECT SWITCHES,
MANUAL MOTOR STARTERS AND VFDS WITH MECHANICAL
CONTRACTOR.
N. COORDINATE ALL TV MOUNTING HEIGHTS WITH
ARCHITECTURAL DRAWINGS.
O. RECEPTACLES ABOVE COUNTER SHALL BE MOUNTED
HORIZONTALLY.
P. PROVIDE A COMPLETE LIGHTNING PROTECTION SYSTEM (UL
MASTER LABEL). SEE SPECIFICATION 264113.
Q. COORDINATE ALL ROOF MOUNTED ELEMENTS, INCLUDING
THE LIGHTNING PROTECTION SYSTEM, WITH THE ROOF
INSTALLER, PRIOR TO PERFORMING ANY ROOF SYSTEM
PENETRATIONS.
KEYED NOTESXX
SCHEMATIC DESIGN 8.17.2018
DT
CS
CS
CS
DT
DT
DT
DT
DT
DT
DT
DTDT
DT
DT
DT
DT
DTDT
DTDT
DTDT
DTDT
DT
DT
DT
DT
DTDT
DT
PHPHPH
DT
DT
DT
DT
L2D
OS
L4D
DT
LDp
L1D
L1 D
L1 D
L1 D
L2 D
L1 D
DT
DT
DT DT
DT
DT
L1D
DT
OS
OS
OS
L2D
L1 D
L1 D
L2D
OS
OS
L1D L1D
L1D
L1D L1D OS L1D L1D
L1D
L1 D
OS
L1D L1D
L1D L1D
L1 D
L3 D
L1D
L1D L1D
L1D
L1 D
L1 D
OS
L1D L2D
OS
OS
OS
OS
L1D L1D
L4D
L1 D
LDm LDk LDn
L1 D
L1 D
Dh
OS
L1D
OS
OS
L1 D
L1D
L2 D
OS
OS
DT
L1D
DT DT DT
L2DL2D
L2D L2D L2D
DT DT
DT
DT
L1D
L2D
DTDTDT
L1D L1D L1D L1D
DT
DT
DT
DT
L2D
DT
DT
DT
DT
DT
L1 D
DT
L1 D
L1D
L2D
L1 D
DT
L2DL2D
DT
DT
DT
DT
DT
DT
DTDTDTDT
DT
DT
DT
DT
DT
DT
CSCS
LC
PS
OS
OS
DT
OS
DT
DT
DTDT
8.38.6
7.1
6.9 6.5 6.2
5.4
5.2
4.8
4.5
3.6
2.8
2 1
0.2A
0.3A
0.4A
0.7A
0.9A A
A.2
A.9
A.7
B B
D D
D.7
E E
F F
0.5A
6.8 6.4
B2
C C
E.8
(TYP)
FA
(TYP)
FD (TYP)
FA
FE
(TYP)
FH
WA
(TYP)
FH
(TYP)
FH
(TYP)
FE
(TYP)
FC
X
X
X
XX
X
X
X
X
WA
(TYP)
FE
X
X
X
WA WA
LA10A LA10A
LA10A LA10A
FF
LC2
LC2
LC2
AA
LC LC
(TYP)
AB
X
X
LA6B LA8B
LA6B LA8B
LA6B LA8B
(TYP)
AB
(TYP)
AB
X
(TYP)
FE
X
(TYP)
FE
X
X
LB10
LB10
LB10
LB10
(TYP)
FC
(TYP)
FH
(TYP)
FH
(TYP)
AB
(TYP)
AB
X
X
X
LC
(TYP)
AB
LA8A LA8A
LA8A LA8A
X
(TYP)
FC
(TYP)
FF
(TYP)
FA
(TYP)
FI
X1
X
(TYP)
FC
(TYP)
FC
(TYP)
FC
(TYP)
FC
(TYP)
FC
(TYP)
FC
X
(TYP)
FC
(TYP)
FC
(TYP)
LD
LD
LA10A LA10A
LA10A LA10A
WB
WB
LA10B
(TYP)
E314
(TYP)
FC
(TYP)
FD
(TYP)
FC
(TYP)
E306
(TYP)
E313
(TYP)
E306
(TYP)
FD
(TYP)
FD
VIA LCP-1
VIA LCP-2
n
(TYP)
E313
(TYP)
FE
(TYP)
FC
LC2
AA
(TYP)
FC
(TYP)
FB
(TYP)
FC
(TYP)
FD
(TYP)
FC
FF
FF (TYP)
FD
(TYP)
FD
(TYP)
FC
(TYP)
FC
(TYP)
E313
5 k
5 k 5 k
5 k
5 k 5 k
5 k
5 k
5 k
5 k
5 k
5 k
5 k
5 k
5 k
5 k
5 k
5 k
5 k
5 k 5 k
5 p 5 p
5 p5 p
5 p 5 p
E318 6 m
6 m 6 m 6 m 6 m 6 m
6 m
6 m
6 m6 m6 m6 m
6 m
6 m
6 m
6 m
6 m
6 m
6 m
6 m
6 m 6 m 6 m 6 m
6 m
6 m
6 m
6 m
6 m
6 6
66 m6 m6 m
6 6
6 m a a b a a b b b b b b b b b a a a a a a a a a
E315
WA
2 2
11 n 1 n 1 n 1 n 1 n
1 n
1 n
1 n 1 n 1 n 1 n 1 n
1 n
1 n
1 n
1 n
(TYP)
FD
4 g 4 g 4 g
4 g
4 f4 f
Z 4 d Z 4 dZ
4 e4 e
Y 4 d Y 4 d
Y(TYP)
E317
(TYP)
AB
4 h
4 h
4 h
4 e4 e
W 4 d W 4 dW
2 2
(TYP)
FC
(TYP)
FC
LC2
AA
(TYP)
FC
(TYP)
FE
5 k
5 k
5 k
5 k
5 k
5 k
VIA LCP-3
VIA LCP-4
(TYP)
FC
(TYP)
FC
(TYP)
FC
E303
(TYP)
FC
E303
LD
(TYP)
FE
(TYP)
FE
(TYP)
AB
E257
E257E257
E257 E257
E257E257
(TYP)
FC
(TYP)
FC
(TYP)
AD
(TYP)
FE
(TYP)
FC
E303
LC
(TYP)
FE(TYP)
FD
AB
AB
a a b b
(TYP)
FD
AB
(TYP)
FC
a a b
TLT/ SHR
218.2
CHANGING / LOCKER (M)
CHANGING / LOCKER (W)
VESTIBULE
MECHANICAL
ELEC
SOIL UTIL
TREATMENT IPMC
DAYROOM
COMM
SOIL UTIL
NEUROLOGIST
PUBLIC WAITING
C101
WORKSTATION PT
PT GYM
CORRIDOR
C300
CORR
C200
TLT/ SHR
218.1
CORR
C302
CORR
C305
CORR
C304
CORR
C306
CORR
C303
CORR
C301
CORR
C201
CORR
C202
CASE MGMT
MAT / PLATFORM
GAIT OBS LANE
EQPT STOR
PC MD
CLEAN UTIL
NEURO REHAB AREA
CORR
C102.1
FAMILY WAITING
CENTRAL PARK
MAIN CORRIDOR / LOBBY
C100
NUTRITIONIST
EYE TESTING
SPEECH THERAPY - TESTING
SPEECH THERAPY - OFFICE
EXAM
SCALE
C306.1
PAT TLT
STAFF TLT
EXAM
CLINICAL PHARMACIST
GROUP THERAPY
TEAM ROOM
PSYCH TECH
EXAM
HOUSEKEEPING
PAT TLT
PSYCH TECH
FLEX STORAGE
BRAIN LAB
ELEC
TRANS-CRANIAL MAGNETIC STIM
COMM
ACUPUNCTURE
341.1
SPIRITUAL COUNSELLING
NP PSYCH
NEUROPSYCH
ACUPUNCTURE
341.2
BH / SW PROVIDERS
PAIN MD
PSYCHOLOGIST
CHIRO TREATMENT
CASE MGMT
STAFF LOUNGE
EXAM
EXAM
BH / SW PROVIDER
MUSIC THERAPY
CHIRO TREATMENT
RECEPTION
PTNT INTAKE CUBICLES
300.1
CASE MGMT
ART AND CLAY THERAPY
TLT / SHR
219.1
MALE TOILET
FEMALE TOILET
HOUSEKEEPING
MULTI-STATION TREATMENT RM
PT O/E
OT O/E
PT O/E
TRAZER / FATS
COPY
109.1
OT O/E
DAILY LIVING SKILLS
EXAM
BREAK ALCOVE
105.1
RESEARCH SHARED OFFICE
NCOIC / ADMIN
NICoE DIR.
DIR. OF OPERATIONS
AV SUPPLY
CLASSROOM
103.1
CHAPLAIN
VENDING ALCOVE
106.1
EXAM
EYE LANE
EXAM
STAFF TLT
CLASSROOM
CORR
C102
BIO NEUROFEEDBACK
GROUP THERAPY
335.1
STORAGE / KILN
338.1
CHECK-IN KIOSK
300.2
STORAGE / ALCOVE
200.1
EQPT STOR
FF
a,b a,b a,b a,b a,b
ALCOVE / STORAGE
C303.1 d,e,f,g
(TYP)
E313 a,b
LC2
(TYP)
AA
AB
a a b
(TYP)
FC
FF
BH / SW PROVIDERS
LS1- 7
LS1- 10
E323
(TYP)
FE
LS1- 4
(TYP)
FD
(TYP)
FD
(TYP)
FD
LS1- 8
LS1- 2
LS1- 9
LS1- 6
LC2
AA
(TYP)
FD
(TYP)
FD
(TYP)
FD
(TYP)
FD
AB
FF
FF
LN1- 2
(TYP)
FD
AC
AA
FF
LN1- 5
(TYP)
FE
LN1- 4
LN1- 1
FF
(TYP)
FC
ABAB
AB AB
(TYP)
FC
LN1- 3
4 g
4 g4 g4 g
LD
(TYP)
FC
a,ba,b aa bb aa a a b b a a a a a,b b a a a a b
AB
a, b a, b b b a a a, b, c
(TYP)
FC
U1 z z
4 e 4 e 4 e 4 e 4 f 4 f d,e,f,g
ABb ABb a,ba,b b AB a,b b b a a c c
(TYP)
FC
(TYP)
AB
(TYP)
FC
AC
AA
AC
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
PLAN
NORTH
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
Pl ot
D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
1/8" = 1'-0"
1/ 4/
1:
:4
AM GROUND FLOOR
LIGHTING PLAN
E3.1 10822.000
KEYED NOTES
SHEET NOTES
A. SEE DWG. E0.01 FOR ABBREVIATIONS, SYMBOLS, GENERAL
NOTES AND DEVICE MOUNTING HEIGHT OF WALL MOUNTED
DEVICES, U.O.N.
B. COORDINATE ALL WALL MOUNTED WIRING DEVICE LOCATIONS
WITH ARCHITECTURAL ELEVATIONS. REFER TO ARCH.
REFLECTED CEILING PLANS FOR EXACT LOCATION OF LIGHT
FIXTURES AND OTHER CEILING MOUNTED DEVICES.
COORDINATE FIXTURES WITH ARCHITECTURAL CEILING AND
WALL TYPES.
C. WHERE INDICATD ON PLANS, CEILING MOUNTED OCCUPANCY
SENSORS SHALL BE DUAL TECHNOLOGY AND SHALL HAVE 360
DEGREES OF COVERAGE. PROVIDE nLIGHT TYPE nCM-9/10 PDT OR APPROVED EQUAL. CONNECT TO nLIGHT TYPE nPP-16
POWER PACKS OR APPROVED EQUAL WITH LOW VOLTAGE
WIRING. PROVIDE NUMBER OF POWER PACKS RECOMMENDED
BY MANUFACTURER. COORDINATE COMPATABILITY WITH
LIGHTING CONTACTORS OR INDICATED SWITCHES. REFER TO
MANUFACTURER WIRING DIAGRAMS.
D. OCCUPANCY SENSORS TO CONTROL ALL LIGHTS IN ROOM, UON.
E. PROVIDE SEPARATE NEUTRALS FOR DIMMING CIRCUITS.
F. THE LIGHTING CIRCUITING IS DIAGRAMMATIC, PROVIDE SWITCH
LEGS. UNSWITCHED PHASE WIRES AND TRAVELERS AS
NECESSARY.
G. REFER TO DRAWING E7.01 FOR LIGHTING FIXTURE SCHEDULE.
H. ALL BRANCH CIRCUIT WIRING SHALL BE 2#12+1#12G IN 3/4"C,
UON. LIMIT THE VOLTAGE DROP TO 3% FOR ALL LIGHTING
BRANCH CIRCUITS.
I. REFER TO ASSOCIATED POWER PLAN AND E2 SERIES FOR
PANELBOARD LOCATIONS.
J. COORDINATE LIGHTING FIXTURE LOCATIONS WITH MECHANICAL
EQUIPMENT, DUCTWORK AND PIPING PRIOR TO INSTALLATION.
K. ALL EMERGENCY LIGHTS ARE DESIGNATED WITH SOLID CIRCLE
IN CENTER OF FIXTURE SYMBOL. PROVIDE AVERAGE OF 1 FC OF
EMERGENCY LIGHTING ALONG THE EGRESS PATH. EACH
EGRESS LIGHT AND EXIT LIGHT SHALL BE PROVDED WITH AN
INTEGRAL EMERGENCY POWER BATTERY PACK. COORDINATE
CIRCUITING WITH LIGHTING CONTROL SCHEDULE ON E7.1.
L. PROVIDE AN INTEGRAL BATTERY PACK FOR EACH LIGHT
FIXTURE DESIGNATED AS EMERGENCY. CONTRACTOR SHALL
PROVIDE UNSWITCHED NORMAL SENSE FEED TO FIXTURES AND
COORDINATE EXACT WIRING REQUIREMENTS WITH
FIXTURE/BATTERY/LIGHTING CONTROLS MANUFACTURER.
M. EXIT SIGNS SHALL NOT BE SWITCHED WITH ADJACENT
EMERGNECY LIGHTING FIXTURES.
N.…