This is a combined synopsis/solicitation for commercial items issued by the Department of the Army Corps of Engineers Engineering District Little Rock. The solicitation seeks quotes for the Eglin NICoE Initial Outfitting Project at Eglin Air Force Base in Florida. Quotes are due no later than January 8, 2020 by 1:00pm Central Time. A site visit is scheduled for December 4, 2019 at 9:00am Central Time at the Eglin Air Force Base West Visitors Center. Interested contractors must RSVP by November 29, 2019 with required contact information. The solicitation is set aside for total Service-Disabled Veteran-Owned Small Businesses and has a NAICS code of 337127 for the size standard of 500 employees. More information regarding entrance onto the base will be provided once attendance is confirmed. The solicitation will use simplified acquisition procedures in conjunction with commercial items procedures.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ST
ST
V
SAN
SAN
G
HWR
HW
CW
F
PLUMBING PIPING LEGEND
PLUMBING ABBREVIATIONS PLUMBING FLOOR PLAN SYMBOLS PLUMBING GENERAL NOTES
UNDER SLAB SANITARY DRAIN
UNDER SLAB STORM DRAIN
SANITARY OR WASTE DRAIN
SANITARY VENT
NATURAL GAS (PRESSURE AS INDICATED)
STORM (RAINWATER) DRAIN
DOM HOT WATER RETURN
FIRE PROTECTION PIPING
DOM COLD WATER
DOM HOT WATER
(TEMP 110° OR AS INDICATED)
(TEMP 110° OR AS INDICATED)
DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL
AIR VENT WITH VALVE
WATER HAMMER ARRESTOR
ELBOW - TURNED UP
FLOW INDICATING BALANCE VALVE
PLUG VALVE or GAS COCK
BALL VALVE
BUTTERFLY VALVE
PRESSURE GAUGE WITH COCK
DIRECTION OF FLOW
BRANCH TOP CONNECTION
TEE OUTLET - DOWN
ELBOW - TURNED DOWN
QUICK COUPLING
FLOW METER
DROP OR RISE
CAP OR PLUG
THERMOMETER
PIPE ALIGNMENT GUIDE
REDUCER - ECCENTRIC
REDUCER - CONCENTRIC
FLOOR DRAIN (ROUND)
ROOF DRAIN
FLOOR CLEANOUT or EXTERIOR CLEANOUT
PIPE UNION
PIPE ANCHOR
HOSE BIBB
WALL HYDRANT
CLEANOUT
PRESSURE REGULATOR VALVE FLANGED
FLEXIBLE CONNECTION
MECHANICAL EXPANSION JOINT
BASKET STRAINER
PRESSURE RELIEF VALVE or
STRAINER
SOLENOID VALVE
BALANCING VALVE
ISOLATION VALVE or GATE VALVE
CHECK VALVE
ANGLE VALVE
POINT OF DISCONNECT
POINT OF CONNECTION
DESCRIPTIONDESCRIPTIONSYMBOL SYMBOL
BACKFLOW PREVENTOR (TYPE
AS
INDICATED BY ASSE STANDARD)
TEMP PRESSURE RELIEF VALVE
FLOOR DRAIN (RECTANGULAR)
HEAT TRACED PIPE
(SYSTEM AS INDICATED)
INSTALL ALL PLUMBING IN ACCORDANCE WITH THE 2012 INTERNATIONAL PLUMBING CODE AND REGULATIONS OF ALL AUTHORITIES HAVING JURISDICTION.
TO OBTAIN COMPLETE CONSTRUCTION INFORMATION ALL SPECIFICATIONS AND DRAWINGS (I.E. ARCHITECTURAL, STRUCTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND FIRE PROTECTION) MUST
BE USED JOINTLY.
BRING TO THE ATTENTION OF THE ARCHITECT ANY INFORMATIONAL CONFLICTS WITHIN THE SPECIFICATIONS AND DRAWINGS. THE CONTRACTOR SHALL NOT PROCEED WITH ANY WORK EXCEPT AT HIS OWN RISK UNTIL ALL CONFLICTS ARE RESOLVED AND THE CLARIFYING INFORMATION IS ISSUED TO THE CONTRACTOR BY THE ARCHITECT.
THE CONTRACTOR SHALL VERIFY AND COORDINATE THE LOCATION OF ALL STRUCTURAL MEMBERS BELOW FLOORS FOR ANY CONFLICTS WITH PIPING. THE CONTRACTOR WILL NOTIFY THE
ARCHITECT IMMEDIATELY IF A CONFLICT IS DETERMINED.
INSTALL ALL SANITARY AND STORM DRAINAGE PIPING 3" AND LARGER AT 1/8" PER FOOT SLOPE. INSTALL PIPING SMALLER THAN 3" AT 1/4" PER FOOT SLOPE.
PROVIDE CLEANOUTS WHERE INDICATED ON DRAWINGS AND WHERE REQUIRED BY THE APPLICABLE CODES.
INSTALL ALL SANITARY AND STORM PIPING WHICH TURNS AT A 90° ANGLE AFTER PASSING THROUGH A FLOOR AS TIGHT TO THE UNDERSIDE OF STRUCTURE AS POSSIBLE.
FIRE STOP ALL OPENINGS AROUND PIPES TO MAINTAIN THE REQUIRED FIRE RATING.
COORDINATE ALL PIPING INSTALLED WITH ALL OTHER TRADES (I.E. STRUCTURAL, MECHANICAL, ELECTRICAL AND FIRE PROTECTION) TO INSURE THAT ALL PIPING SYSTEMS ARE INSTALLED ABOVE FINISHED CEILING OR IN A CONCEALED LOCATION. ALL CEILING HEIGHTS ARE INDICATED ON THE ARCHITECTURAL AND/OR INTERIOR DESIGN DRAWINGS. MAINTAIN MINIMUM CLEARANCES REQUIRED
BY THE APPLICABLE CODES THROUGH OUT THE BUILDING.
PROVIDE FREEZE PROTECTION FOR ALL SANITARY TRAPS, WATER PIPING AND PUMPED DISCHARGE PIPING INSTALLED IN UNHEATED AREAS WITH ELECTRIC HEAT TRACE. INCLUDE ALL ACCESSORIES
FOR A COMPLETE SYSTEM, PROVIDE INSULATION AS INDICATED IN THE SPECIFICATION.
PROVIDE TRAP PRIMER VALVES AND DISTRIBUTION UNITS AS REQUIRED TO PROVIDE TRAP SEALS ON ALL FLOOR DRAINS INDICATED FOR TRAP PRIMING. INSTALL TRAP PRIMER VALVE AND
DISTRIBUTION UNITS LEVEL AND LOCATED IN AN ACCESSIBLE LOCATION.
PROVIDE WATER HAMMER ARRESTORS WHERE QUICK CLOSING VALVES ARE UTILIZED. LOCATE ARRESTORS AS PER PDI RECOMMENDATIONS AND IN AN ACCESSIBLE LOCATION.
INSTALL BACKFLOW PREVENTOR ASSEMBLIES IN AN ACCESSIBLE LOCATION AND IN ACCORDANCE WITH THE APPLICABLE CODES. PIPE RELIEF OUTLET DISCHARGE TO NEAREST FLOOR DRAIN.
PROVIDE AIR GAP FITTING AND FUNNEL AS REQUIRED.
IDENTIFY ALL PIPING SYSTEMS, VALVES AND EQUIPMENT AS INDICATED IN THE SPECIFICATION.
INSULATE ALL HORIZONTAL DRAINAGE PIPING AND TRAPS FROM DRAINS RECEIVING CONDENSATE.
INSULATE ALL DOMESTIC WATER PIPING AS INDICATED IN THE SPECIFICATION.
INSULATE WATER SUPPLIES AND DRAINAGE PIPING SERVING ADA LAVATORIES AND SINKS AS PER THE SPECIFICATIONS.
INSULATE ALL HORIZONTAL STORM PIPING AND DRAIN BODIES.
INSTALL VALVES AND ACCESSORIES ON PIPING SERVING EQUIPMENT TO ALLOW SERVICING OR REMOVAL OF EQUIPMENT WITHOUT HAVING TO REMOVE ALL PIPING AND ACCESSORIES.
PROVIDE UNIONS, VACUUM BREAKERS, STRAINERS, ETC. AS REQUIRED ON ALL PIPE CONNECTIONS TO EQUIPMENT AT LOCATIONS INDICATED. MAKE FULLY OPERABLE IN ACCORDANCE WITH ALL
APPLICABLE CODES AND REGULATIONS.
FOR THE EXACT LOCATION OF FIXTURES, FLOOR DRAINS, ROOF DRAINS, STORM LEADERS AND STACKS REFER TO ARCHITECTURAL PLANS AND DETAILS.
FOR SIZES TO INDIVIDUAL PLUMBING FIXTURES SEE THE "FIXTURE CONNECTION SCHEDULE".
FOR ADDITIONAL INFORMATION AND PIPE SIZES SEE DIAGRAMS.
A
L
M
B
C
N
O D
E
P
Q
R
S
F
G
T H
U
V
W
I
K
ABBR ABBREVIATION
ADA AMERICANS WITH DISABILITIES ACT
AFF ABOVE FINISHED FLOOR
AG ABOVE GRADE
AMB AMBIENT
ANSI AMERICAN NATIONAL STANDARDS
INSTITUTE
AP ACCESS PANEL
APPROX APPROXIMATE
LAV LAVATORY
LGT LENGTH
LPG LIQUID PETROLEUM GAS
LWT LEAVING WATER TEMPERATURE
BFP BACKFLOW PREVENTOR
BFV BUTTERFLY VALVE
BHP BRAKE HORSEPOWER
BLV BALANCING VALVE
BTU/H BRITISH THERMAL UNIT PER HOUR
MAX MAXIMUM
MBH 1000 BTU/HR
MIN MINIMUM
MISC MISCELLANEOUS
MTG MOUNTING
NA NOT APPLICABLE
N.C. NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NITROUS OXIDE
N.O. NORMALLY OPEN
NO. NUMBER
NOM NOMINAL
NTS NOT TO SCALE
CAP. CAPACITY
CFM CUBIC FEET PER MINUTE
CI CAST IRON
CO CLEANOUT
COMP COMPRESSOR
COND CONDENSATE
CONT CONTINUATION
CV CHECK VALVE
CW COLD WATER
DF DRINKING FOUNTAIN
DIA DIAMETER
DN DOWN
DOM DOMESTIC
DWH DOMESTIC WATER HEATER
DWG DRAWING
DWS (CHILLED) DRINKING WATER SUPPLY
DWR (CHILLED) DRINKING WATER RETURN
OD OUTSIDE DIAMETER
OFL OVERFLOW
ORD OVERFLOW ROOF DRAIN
OSD OPEN SITE DRAIN
PC PUMPED CONDENSATE
PD PUMPED DISCHARGE (TYPE AS
INDICATED)
PDI PLUMBING DRAINAGE INSTITUTE
PH PHASE (ELECTRICAL)
PPM PARTS PER MILLION
QTY QUANTITY
REF REFERENCE
RD ROOF DRAIN
RL RELOCATED MATERIAL OR EQUIPMENT
RV PRESSURE RELIEF VALVE
RPZ REDUCED PRESSURE ZONE
RO REVERSE OSMOSIS SUPPLY
SAN SANITARY OR WASTE
SCFM STANDARD CUBIC FEET PER MINUTE
SCW SOFTENED COLD WATER
SE SEWAGE EJECTOR
SG SPECIFIC GRAVITY
SK SINK
SH SHOWER
SHW SOFTENED HOT WATER
SP SUMP PUMP
SPEC SPECIFICATION
SQ. FT. SQUARE FEET
SS STAINLESS STEEL
SSD SUB-SOIL DRAINAGE
ST STORM (RAINWATER)
STD STANDARD
STM STEAM
SV SOLENOID VALVE
TEMP TEMPERATURE
TP TRAP PRIMER
TPU TRAP PRIMER UNIT
TPV TEMPERATURE AND PRESSURE
UON UNLESS OTHERWISE NOTED
V SANITARY VENT
VEL VELOCITY
VTR VENT THRU ROOF
W/ WITH
WC WATER CLOSET
WG WATER GAGE
WHA WATER HAMMER ARRESTOR
WH WALL HYDRANT
W/0 WITHOUT
EA EACH
ECO EXTERIOR CLEANOUT
EEW EMERGENCY EYE WASH
EEW/ESH COMBINATION EMERGENCY EYE WASH/
EEW/EFW COMBINATION EMERGENCY EYE WASH/
EFF EFFICIENCY
EFW EMERGENCY FACE WASH
EL ELEVATION
EQ EQUIVALENT
ESH EMERGENCY SHOWER
ET EXPANSION TANK
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATURE
EXP EXPANSION
EXT EXTERNAL
(E) EXISTING MATERIAL OR EQUIPMENT
_°F DEGREES FAHRENHEIT
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FL FLOOR
FPM FEET PER MINUTE
FPS FEET PER SECOND
FS FLOOR SINK
FT FOOT OR FEET
FTD FOOTER DRAINAGE
G NATURAL GAS (PRESSURE AS
INDICATED)
GAL GALLON
GS GAS COCK
HB HOSE BIBB
HG MERCURY
HGT HEIGHT
HP HORSE POWER
HPCW HIGH PRESSURE DOM. COLD WATER
HPHW HIGH PRESSURE DOM. HOT WATER
(TEMP. 110° OR AS INDICATED)
ID INSIDE DIAMETER
IE INVERT ELEVATION
IN. INCHES
KW KILOWATTS
SEE MECHANICAL SYMBOLS, LEGENDS AND EQUIPMENT SCHEDULES FOR ADDITIONAL ABBREVIATIONS. ALL ABBREVIATIONS, SYMBOLS, AND LEGENDS SHOWN ON THIS DRAWINGS ARE NOT NECESSARILY USED.
BV BALL VALVE
(PRESSURE AS INDICATED)
CA UTILITY COMPRESSED AIR
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GV GATE VALVE
HPHWR HIGH PRESSURE DOM. HOT WATER
RETURN (TEMP. 110° OR AS INDICATED)
HR HOUR
MSB MOP SERVICE BASIN
PRESS. PRESSURE
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH - GAUGE
PV PLUG VALVE
PW PROCESS WATER
TW TEMPERED WATER
TYP TYPICAL
UR URINAL
Y
YD YARD
(TYPE AS INDICATED)
EMERGENCY SHOWER
EMERGENCY FACE WASH
RELIEF VALVE
REFERENCE SYMBOLS
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
O.
P.
Q.
R.
S.
T.
U.
V.
W.
PRESSURE REGULATOR VALVE THREADED
S
HB
RD
FD
FD
CO
CO
RISER DESIGNATION (TYPE AS INDICATED)
SECTION NUMBER
DETAIL NUMBER
DRAWING NUMBER WHERE DRAWN
DRAWING NUMBER WHERE DRAWN
E1-1.0
E1-1.0
KEY NOTE 1 DEMO KEY NOTE
ETP ELECTRONIC TRAP PRIMER
RECIRC RECIRCULATION
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
Pl ot
D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
NONE
1/ 3/
:2
8:
P
M PLUMBING
ABBREVIATIONS
/SYMBOLS/GENERAL
NOTES
P0.1 10822.000
DESIGN DEVELOPMENT 11/08/2018
CONTRACT DOCUMENTS 01/04/2019
8.38.69
8 7.1
6.9 6.5 6.2
6 5.4
5.2
4.8
5 4.5 4 3.6 3 2.8 2 1
0.2A
0.3A
0.4A
0.7A
0.9A A
A.2
A.9
A.7
B B
D D
D.7
E E
F F
0.5A
2"W UP
2"W UP
4" SAN FROM
ABOVE2"W UP
2"W UP
4"W UP
2"W UP
4" SAN FROM
ABOVE
2"W UP
4"W UP
4"W UP
4"W UP
4"W UP
3" SAN FROM
ABOVE
2"W UP
3"W UP
2"W UP
2" V UP
2"V UP
4" UP TO
FCO
3" UP
TO FCO
4" UP
TO FCO
6" SAN
INV. ELEV. 49.5'
SEE CIVIL DWGS
FOR CONT.
C
W GF
6.8 6.4
B2
C C
E.8
2"W UP
2"W UP
4" SAN FROM
ABOVE
4"
2"W UP
2"W UP
2"2"
2"
4"
3" S
AN
4"
2"W UP
2"W UP
4"
2"
2"W UP
2"
6" ST (3,170 SF)
FOR CONT. SEE
CIVIL DWGS.
3"
P101 P102
P103 P104
P105
P106
2"W UP
2"W UP
2" W UP
4" S
AN
2"
2"
2"W UP
2" W UP
2" S
AN
2"W UP
2"V UP
4" SAN
3" W UP
4" ST (960 SF)
FOR CONT. SEE
CIVIL DWGS.
4" ST (1,244 SF)
FOR CONT. SEE
CIVIL DWGS.
8" ST (5,760 SF)
FOR CONT. SEE
CIVIL DWGS.
8" ST (5,100 SF)
FOR CONT. SEE
CIVIL DWGS.
8" ST (5,840 SF)
FOR CONT. SEE
CIVIL DWGS.
8" ST (17,600 SQ)
FOR CONT. SEE
CIVIL DWGS.
2"W UP
2"
2"W UP 2"W UP
2"W UP
4" SAN FROM
ABOVE
3"SAN UP
4"SAN UP
2"W UP
4" UP TO FCO
4" SAN
4" S
AN
4"
S
AN
3" SAN3" SAN
4" SAN4" SAN 4" SAN
4" S
AN
2"W UP
2"W UP
2"W UP 2"W UP
3"W UP
3" W UP
3"
4"
3"
3"
3"
3" W UP
2"W UP
4" SAN FROM
ABOVE
2"W UP
4" SAN FROM
ABOVE
2"W UP
2"
2"
3"
2"
4"
3"
4"
2" W UP
4" UP TO
FCO
4" UP TO
FCO
4" UP TO
FCO
2"V UP
2"V UP
3"W UP
2"
4"
4"
4"W UP
4" SAN
4" SAN4" SAN4" SAN
2"W UP4"
S
AN
6" S
AN
4" SAN
4" SAN3" SAN
4" SAN
4" SAN
INV. ELEV. 52.5'
FURTHERMOST
FIXTURE
2"V UP
2"V UP
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
PLAN
NORTH
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
Pl ot
D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
1/8" = 1'-0"
1/ 3/
:3
2:
P
M UNDERGROUND
PLUMBING PLAN
P2.00 10822.000
GENERAL SHEET NOTES
SHEET KEYNOTES
P101 6" FIRE SERVICE. SEE CIVIL DRAWINGS FOR
CONTINUATION
P102 4" DCW (120 GPM). SEE CIVIL DRAWINGS FOR
CONTINUATION.
P103 4" DCW UP.
P104 6" FIRE WATER UP.
P105 2" NATURAL GAS AT 2 PSI. SEE CIVIL DRAWINGS
FOR CONTINUATION.
P106 2" NATURAL GAS UP
A. SEE SHEET P0.1 FOR SYMBOLS, ABBREVIATIONS AND GENERAL NOTES.
8 7.1
7 6.9 6.5 6.2
6 5.4
5.2
4.8
5 4.5 4 3.6
2.8 2 1
0.2A
0.3A
0.4A
0.7A
0.9A A
A.2
A.9
A.7
B B
D D
D.7
E E
F F
0.5A
FCO
FCO
FCO
4"VTR
4"VTR
4" ST UP
TO RD-1
4" ST UP
TO RD-1
3" ST UP
TO RD-1
3" ST
3" ST
4" ST UP
TO RD-14" ST UP
TO RD-1
4" ST UP
TO RD-1
ST
ST
ST
4" ST UP
TO RD-1
ST
4" ST DN INTO
SCUPPER BOX
(1,244 SF)
65 GPM
4" ST UP
TO RD-1
4" ST UP
TO RD-1
FCO
HWCWHWCW
HW
H W
HW
CW
CW
H W
C W
H W
C W
H W
C W
CW
HW
CW
HW
HWR
HW
CW
HWR HWR
CW
CW
HW
H W
CW
C W
HWR
HW
CW
TP-1
TP-1
2" CW TO DWH-1
1"CW MAKE-UP LINE W/ PRZ-BFP
FOR MECH EQUIP. SEE MECH
DWGS
C W
C W
CW
HW
2"V
FROM
BELOW
H W G
G G
G
G
G
1 1/2"
C W
CW
C W
6.8 6.4
B2
C C
E.8
SH-1A
SH-1A
WC-1A
SK-1A
SK-1A
SK-1A
LA
V-
1A
LA
V-
1A
LA
V-
1A
LA
V-
1A
FD-1
UR
-1
W C-
1A
W C-
W C-
W C-
1A
UR
-1
A
LAV-2A
WC-1A
MSB-1 FD-1
EW-1
SK-2A
SK-1A
SK-1A
SK-1A
SK-1A
SK-1A
SK-1A
SK-1A
LA
V-
2A
FD-1
WC-1A
FD-1
LAV-2A
EWC-1
SK-2A W/
DISPOSAL
SK-1A
SK-1A
SK-1A
SK-1A
LAV-2A
WC-1A
SK-1A
SK-1A
SK-1A
SK-1A
LAV-2A WC-1A
WC-1A
LAV-2A
SK-1A
FCO
2"V DN
4"VTR
4"FCO
GAS REGULATOR
& METER BY
UTILITY COMPANY
6" FIRE WATER
FROM BELOW
4" CW FROM
BELOW
P301
HW
HWR
BALANCING
ASSEMBLY
2" V FROM
BELOW
ST
C W
HW
CW CW
H W
HW
H W
R
CW
C W
C W
CW C
W
HWR
H W
H W
C W
ST
P302
CW HW HW CW
H W
CW
ELEC
COMM
STAFF LOUNGE
CLEAN UTIL
MUSIC THERAPY
RECEPTION
CORR
C303
NP PSYCH
CORR
C302
MAIN CORRIDOR / LOBBY
C100
CHANGING / LOCKER (W)
COMM
MECHANICAL
ELEC
DAILY LIVING SKILLS
DIR. OF OPERATIONS
RESEARCH SHARED OFFICE
NICoE DIR.
NCOIC / ADMIN
CLASSROOM
103.1
CENTRAL PARK
MAIN CORRIDOR / LOBBY
C100
FAMILY WAITING
VESTIBULE
PT GYM
200 NEURO REHAB AREA
WH-1
WH-1
WH-1
WH-1
WH-1
WH-1
FEMALE TOILET
HOUSEKEEPING
MALE TOILET
PAT TLT
CHANGING / LOCKER (M)
DWH-1
FD-2
FD-2
FD-2FD-2
FD-2
RP-1
CW
ET
P-
ET-1
SK-2A
SDB-1
CORR
C200
H W
C W
SK-2A
1 1/2"
EWC-1
CORR
C301
CORR
C304
CORRIDOR
C300
CORR
C306
P207
HWR BALANCING
ASSEMBLY
2" V FROM
BELOW
FD-1
6" ST
8" ST
6" ST
6" ST
CO
CO
6" ST
6" ST
ST
4" ST
4"ST UP
TO RD-1
CHIRO TREATMENT
CHIRO TREATMENT
BH / SW PROVIDERS
BH / SW PROVIDER
SK-1A
4" ST
4" ST DN INTO
SCUPPER BOX
(960 SF) 50 GPM
6" ST DN INTO
SCUPPER BOX
(3,170 SF)
165 GPM
6" ST DN INTO
SCUPPER BOX
(3,250 SF)
167 GPM
8" ST DN INTO
SCUPPER BOX
(5,840 SF)
304 GPM
8" ST DN INTO
SCUPPER BOX
(5,100 SF)
266 GPM
8" ST DN INTO
SCUPPER BOX
(5,760 SF)
300 GPM
6" ST
6" ST
8" ST
8" ST
8" ST
CO
CO
CO
STAFF TLT
NEUROPSYCH
PSYCH TECH
PSYCH TECH
GROUP THERAPY
335.1
PSYCHOLOGIST
ART AND CLAY THERAPY
BH / SW PROVIDERS
EQPT STOR
BIO NEUROFEEDBACK
TRANS-CRANIAL MAGNETIC STIM
GROUP THERAPY
TREATMENT IPMC
NUTRITIONIST
EXAM
EXAM
EYE TESTING
PAIN MD
EXAM
FLEX STORAGE
EXAM
EXAM
TEAM ROOM
EXAM
EXAM
EXAM
PAT TLT
CASE MGMT
NEUROLOGIST
PC MD
307 CLINICAL PHARMACIST
CASE MGMT
BRAIN LAB
SPIRITUAL COUNSELLING
ACUPUNCTURE
341.2
STORAGE / KILN
338.1
ALCOVE / STORAGE
C303.1
CASE MGMT
EYE LANE
OT O/E
OT O/E
MULTI-STATION TREATMENT RM
217 PT O/E
PT O/E
PT GYM
EQPT STOR
SOIL UTIL
TLT / SHR
219.1
TLT/ SHR
218.2
TLT/ SHR
218.1
AV SUPPLY
CORR
C202
CORR
C202
TRAZER / FATS
SPEECH THERAPY - OFFICE
6" ST
8" ST8" ST
DAYROOM
SPEECH THERAPY - TESTING
CO
SK-1A
WC-1A
LAV-2A
HOUSEKEEPING
STAFF TLT
EW-1MSB-1
FCO
FCO
FCO
ICE MAKER
(EXIST)
REF/FRZ
W/ICE MAKER
REF/FRZ
W/ICE MAKER
4"VTR
V
V
V
V V
V
V
V
V
V V
V
V
V
V
VV
V
V
V
V
V V
V
V
V
V
V
V
3" V
V
V
HW
OSD-1
2" HW
2" H
W
WH-1
4" ST UP
TO RD-1
REF/FRZ
W/ICE MAKER
SOIL UTIL
CORR
C102
EWC-1
SH-1A
FD-1
4" ST(OF) UP
TO RD-2
4" ST(OF) UP
TO RD-2
6" ST
8" ST
6" ST
6" ST
8" ST(OF)
18" ABOVE FINISH
GRADE. (5560 SF)
290 GPM
OFD
HW
MANIFOLD
RECIRC.
SYSTEM
RM
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
PLAN
NORTH
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
Pl ot
D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
1/8" = 1'-0"
1/ 3/
:2
9:
P
M GROUND FLOOR
PLUMBING PLAN
P2.01 10822.000
GENERAL SHEET NOTES
SHEET KEYNOTES
P301 1-1/4" GAS AT 30 PSI FROM BELOW. 1-1/2"
GAS AT 2 PSI TO BLDG. GAS METER &
REGULATOR BY LOCAL GAS UTILITY
COMPANY (OKALOOSA). FOR CONT. SEE
CIVIL DWGS.
P302 2" CW DN FOR TEMPORARY IRRIGATION
SYSTEM BY IRRIGATION CONTRACTOR.
A. SEE SHEET P0.1 FOR SYMBOLS, ABBREVIATIONS AND GENERAL NOTES.
8 7.1
7 6.9 6.5 6.2
6 5.4
5.2
4.8
5 4.5 4 3.6 3 2.8 2 1
0.2A
0.3A
0.4A
0.7A
0.9A A
A.2
A.9
A.7
B B
D D
D.7
E E
F F
0.5A
4"VTR
4"VTR 4"VTR
3" RD-1
(200 SF)
10 GPM
4" RD-1
(2,780 SF)
145 GPM
4" RD-1
(1,244 SF)
65 GPM
4" RD-1
(2,550 SF)
133 GPM
4" RD-1
(3,250 SF)
167 GPM 4" RD-1
(3,170 SF)
165 GPM
4" RD-1
(960 SF)
50 GPM
6.8 6.4
B2
C C
E.8
6" RD-1
(2,920 SF)
152 GPM
4"VTR
RD-1
RD-1 RD-1
RD-1 RD-1
RD-1
RD-1
RD-1
RD-1RD-1
6" RD-1
(2,920 SF)
152 GPM
4" RD-1
(2,780 SF)
145 GPM
4" RD-1
(2,550 SF)
133 GPM
RD-1
RD-2RD-2
4" RD-2
(2,780 SF)
145 GPM
4" RD-2
(2,780 SF)
145 GPM
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
PLAN
NORTH
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
Pl ot
D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
1/8" = 1'-0"
1/ 3/
:2
9:
P
M ROOF PLUMBING
PLAN
P2.02 10822.000
GENERAL SHEET NOTES
SHEET KEYNOTES
A. SEE SHEET P0.1 FOR SYMBOLS, ABBREVIATIONS AND GENERAL NOTES.
RETURN FROM BUILDINGMIXED OUTLET
H. EPOXY COATED STRUT
RETURN TO COLD WATER FEED
OF HOT WATER SOURCE (WATER HEATER)
COLD SUPPLY INLETHOT SUPPLY INLET
B. THERMOMETER
A. FULL PORT BALL VALVE
D. CHECK VALVE
E. RECIRCULATION PUMP (RP-1)
F. CIRCUIT SETTING BALANCING VALVE
G. STOP AND CHECK VALVE
C. LAWLER 800 SERIES VALVERP-1
A
B
C
D
E
F
D
G G
H
ROOF
GROUND FLOOR
SK
-2
A
HW
CW
DAILY LIVING SKILLS
CW CW CW
W C-
1A
UR
-1
UR
-1
A
MALE TOILET
LA
V-
1A
LA
V-
1A
HWR
HW
CW
HWR
HW
CW
HWR HWR
CW CW
HW
FEMALE TOILET
SK-1A
HW
CW
MULTI-STATION
TREATMENT RM
HWR
HW
CW
HWR
HW
CW
HWR
HW
CW
HWR
HW
HWR
HW
CW
HW
CWHW
CW
HW HW HW HW
1/2"3/4"1 1/2"
HWR BALANCING ASSEMBLY
SET @ 1.0 GPM
SEE 3/ P5.02
3/4"
3/4" 1 1/2" 1"
3/4"
ROOF
GROUND FLOOR
HWR
HW
CW
HWR
HW
CW
WH-1
PRESSURE GAUGE
2" FOR CW IRRIGATION.
SEE LANDSCAPE DWG FOR CONT.
1 4" NEW DOMESTIC WATER SERVICE
SEE CIVIL DWGS FOR CONT.
2" REDUCED PRESSURE
BACKFLOW PREVENTER ASSE 1013.
RUN DRAIN TO THE NEAREST FLOOR DRAIN.
EXPANSION
TANK ET-1
HW
R
DW
H-
2" @ 140°
SEE DETAIL 2
THIS SHEET
TO FD-2TO FD-2 TO FD-2 TO FD-2 TO FD-2
ETP-1
ELECTRONIC TRAP PRIMER (ETP-1)
SEE SCHEDULE ON SHEET P7.014
RUN TO THE NEAREST FLOOR DRAIN
1-1/4" REDUCED PRESSURE
BACKFLOW PREVENTER
ASSE 1013. RUN DRAIN TO
THE NEAREST FLOOR DRAIN.
2"
3/4"
CW
CW CW
115° 115° 115° 115° 115° 115° 115° 115°
CW
CW
CW
1-1/4" CW MAKE-UP LINE
FOR MECH EQUIPMENT
SEE MECH DWGS
1 1/4" 3/4"
BFP
4"
3"
3"
2 1/2"
2"
GROUND FLOOR
ROOF
GROUND FLOOR
HWR
CW
115°
HW
CW
HW 115° HW 115°
HW HW
CW
HW 115°
HW
CW
HW
SK-1A
CW
HW
SK-1A SK-1A
CW
HW
1/2" 1/2"
HW 115°HW 115°
HW
EXAM
EYE LANE
HW
CW
1/2" 1/2" 1/2" 1/2"
CW
3/4"
HW
CW
HW
CWCW
HW
HWR
B
B
3/4"3/4"1"3/4"1 1/2"2"2"3/4"2"1"2"2"1"2"1" 2"
2" 1"
2" 1" 2 1/2" 2 1/2"2"
2"
1" 3/4"
1" 2 1/2" 3/4" 1" 2" 2" 1" 2"
2"
1 1/4"
HWR BALANCING ASSEMBLY
SET @ 1.0 GPM
SEE 3/ P5.02
SK-1A SK-1A
CW CW
CW
HW HW
CW
HW HW
OT O/E
OT O/E
1/2" 1/2"
3/4" 1/2"
BFP
TO
IC
E M
AK
ER
IN
R
EF
/F
RZ
R
1/2"
FILTRINE MODEL
TMS2-0.5 FILTER
DUAL CHECK BFP
ASSE 1024, WATTS
SERIES 7
CW
HW
MSB-1
EW-1
3/4"
HOUSE KEEPING
TMV
1/2"
CW
HW
WH-1
3/4"
CW
CW
3/4"
CW
CW HW
SDB-1
FOR CLOTH WASHER
DAILY LIVING SKILL
3/4"
HW
W C-
1A
W C-
W C-
1/2" 3/4"
LA
V-
1A
LA
V-
1A
CW HW
CW
CW
HW
LAV-2A
1/2"
CW
WC-1A
1 1/2"
CW HW
TLT/SHR
219.1
SH-1A3/4" 3/4"
SK
-1
A
HW
CW
PT GYM
3/4"
BFP
TO
E
XI
ST
IC
E
M
AK
ER
1/2"
FILTRINE MODEL
TMS2-0.5 FILTER
DUAL CHECK BFP
ASSE 1024, WATTS
SERIES 7
HW
CW
HW
CW
CW
HW
SOIL UTIL
SK
-1
A
EW
C-
3/4" 1/2"
1/2"
CORR
C200
CW
HW
HWR
2"
2"
LAV-2A
SK
-2 A
CW CW
CW HW
HW
CW
HW HW
1/2"
TLT/SHR
218.1
DAYROOM
CW
CW
1 1/2"
WC-1A BFP
TO
IC
E M
AK
ER
IN
R
EF
/F
RZ
R
1/2"
FILTRINE MODEL
TMS2-0.5 FILTER
DUAL CHECK BFP
ASSE 1024, WATTS
SERIES 7
3/4"
EW
C-
CW
1/2"
CORR
C102
CW
CW HW
TLT/SHR
218.1
SH-1A
3/4" 3/4"
CW HW
TLT/SHR
218.2
SH-1A
3/4"3/4"
LAV-2A
CW
HW
1/2" 1/2"
WC-1A
CW
1-1/2"
TLT/SHR
218.2
HWR
CASE MGMT
CW
HW
1/2" 1/2"
HW
CW
CAP FOR FUTURE
SK-1A
CW
HW
1/2" 1/2"
EXAM
CLINICAL
PHARMACIST
CW
HW
1/2"
CAP FOR FUTURE
SK-1A
CW
HW
1/2" 1/2"
EXAM
PC MD
CW
HW
1/2"
CAP FOR FUTURE
1/2"
SK-1A
CW
HW
1/2" 1/2"
EXAM
NEUROLOGIST
CW
HW
1/2"
CAP FOR FUTURE
1/2"
CW
HW
1 1/2" 1/2"
W C-
1A
1 1/2"
LA
V-
2A
PAT TLT
CASE MGMT
CW
HW
1/2"
CAP FOR FUTURE
1/2"
EW
C-
CW
1/2"
CORR
C301
SK
-2
A W
DI
SP
OS
ERHW
CW
STAFF LOUNGE
BFP
TO
IC
E M
AK
ER
IN
R
EF
/F
RZ
R
1/2"
FILTRINE MODEL
TMS2-0.5 FILTER
DUAL CHECK BFP
ASSE 1024, WATTS
SERIES 7
3/4"
CW
HW
SK-1A
1/2" 1/2"
CW
HW
SK-1A
1/2" 1/2"
CW
HW
SK-1A
1/2" 1/2"
TREATMENT IPMC
EXAM
EXAM
EXAM
SK-1A
CW
HW
1/2" 1/2"
ACCUPUNCTURE
341.2
CW
HW
HW 115°
HW
CW
CW
HW
SK-1A
1/2" 1/2"
CW
HW
SK-1A
1/2" 1/2"
CW
HW
SK-1A
1/2" 1/2"
CW
HW
SK-1A
1/2" 1/2"
TRANS-CRANIAL
MAGNETICSTIM
EXAM
SOIL UTIL
322PAT TLT
CW
HW
1 1/2"
1/2"
W C-
1A
1 1/2"
LA
V-
2A
HW 115°
HW
CW
C
GROUND FLOOR
HW 115°
HW
CW
C
ROOF
ROOF
GROUND FLOOR
ROOF
CW
HW
SK-1A
1/2" 1/2"
BIO
NEUROFEEDBACK
CW
HW
SK-1A
1/2" 1/2"
CHIRO
TREATMENT
CHIRO
TREATMENT
CW
HW
LAV-2A
1/2" 1/2"
STAFF TLT
WC-1A
CW
1-1/2"
CW
HW
3/4" 3/4"
HOUSEKEEPING
WH-1
CW
3/4"
HW 115°
HW
CW
HW 115°
HW
CW
CW
HW
SK-2A
3/4" 3/4"
ART AND CLAY
THERAPY
WH-1
CW
3/4"
CW
HW
LAV-2A
1/2"
CW
1-1/2"
STAFF TLT
HW
115°HW
CW
WC-1AMSB-1
EW-1
TMV
1/2"
1-1/2"
1-1/2"2"2"2"
CW
CW
CW CW
HW
HWHW
1-1/2"
1-1/2"
2"3/4"
2"2"2"2"
1/2"
2" 2" 2"
3/4"
2"
2"
3/4"
HW
CW CW
WH-1
CW
3/4"
NEAR
COLUMN
D/9
CW
2"2"
3/4" 3/4"3/4"3/4"
B
GROUND FLOOR
ROOF
ROOF
GROUND FLOOR
GROUND FLOOR
ROOF
ROOF
GROUND FLOOR
6"
2"
V
SK-1A
EXAM
2"
V
NEUROLOGIST
ROUGH-IN
BOX FOR THE
FUTURE SINK
4"
V
PAT TLT
CO
LAV-2A
WC-1A
1-1/2"
2"
V
CASE MGMT
ROUGH-IN
BOX FOR THE
FUTURE SINK
2"
V
SK-2A
W/DISPOSAL
STAFF
LOUNGE
CO 2"
V
FCO
CORR
C301 4"
2"
V
PC MD
ROUGH-IN
BOX FOR THE
FUTURE SINK
FCO
4"
2"
V
SK-1A
EXAM
2"
V
CLINICAL
PHARMACIST
ROUGH-IN
BOX FOR THE
FUTURE SINK
2"
V
SK-1A
EXAM
2"
V
CASE MGMT
ROUGH-IN
BOX FOR THE
FUTURE SINK
2"
V
SK-1A
EXAM
2"
V
SK-1A
TREATMENT
IPMC
2"
V
SK-1A
EXAM
2"
V
SK-1A
EXAM
2"
V
SK-1A
EXAM
V
STAFF
TLT 318
CO
LAV-2A
WC-1A
1-1/2"
4"
3"
4"
FCO
MSB-1
HOUSEKEEPING
SAN
SAN
4"
2"
V
SK-1A
EYE LANE
2"
V
SK-1A
ACCUPUNCTURE
341.2
V
CO
LAV-2A
WC-1A
1-1/2"
4" PAT TLT
SANSANSAN SAN
SAN
SANSAN
SAN
SAN
SAN
4"4"4"
2"
V
SK-1A
TRANS-CRANIAL
MAGNETICSTIM
2"
V
SK-1A
EXAM
3"
2"
V
SK-1A
SOILED
UTILITY
2"
V
SK-1A
BIO-NEURO
FEEDBACK
2"
V
SK-1A
CHIRO
TREATMENT
2"
V
SK-1A
CHIRO
TREATMENT
3"
FCO
SAN SAN
3" 3" 3"4" 4" 4" 4"
SAN SAN
2"
V
SK-2A
ART AND CLAY
THERAPY
V
CO
LAV-2A
WC-1A
1-1/2"
4"
FCO
SAN SAN
4" 4"
STAFF
TLT 334
4"
FCO
V
FD-1
TO TP
4"
SAN
3"
FD-1
TO TP
2"
V
LAV-2A
SH-1A
3" 2"
4" V
WC-1A
4"
SAN
3" 3"
2"
V
LAV-2A
SH-1A SH-1AFD-1
TO TP
V
4"
V
WC-1A
SAN
4"
SAN
2"
V
LAV-2A
4"
V
WC-1A 2"
V
CORR
C102
A
GROUND FLOOR
ROOF
GROUND FLOOR
ROOF
SAN
4"
V W
C- 1A
4"
MALE & FEMALE TLT
107&108
TLT/SHR
219.1
TLT/SHR
218.2
TLT/SHR
218.1
2"
LA
V-
1A
2"
V LA
V-
1A
LA
V-
1A
LA
V-
1A
3"
2"
V
SK-2A
DAYROOM
FD-1
TO TP
V
2"
V
SOIL UTIL
SK-1A
EWC-1
2"
V
LAV-1A
2"
V
SK-1A
B
W C-
1A
V W
C-
UR
-1
V W
C-
UR
-1
A
4" FCO 2"
V
SDB-1
MSB-1
FD-1
TO TP
DAILY LIVING
SKILLS
HOUSEKEEPIG
SAN
VV
FD-1
TO TP
V
2"
V
SK-1A
2"
V
SK-1A
OSD-1
V
DRAIN FROM
ICE MAKER
FD-2
TO TP
V
FD-2
TO TP
V
4" FCOFD-2
TO TP
V
FD-2
TO TP
V
FD-2
TO TP
V
2"
V
SK-2A
DRAIN FROM
DISHWASHER
4" 4"
A
4"
SANSAN
4"4" 2"2"2"2"
MECHANICAL
MULTI-STATION
TREATMENT RM
FEMALE
TOILET
MALE TOILET
EWC-1
V
2"
2" 2" V 2" V
2" V 3" V
2" V
2" V 2" V
2" V 44
2" V 2" V 2" V 2" V
2" V2" V
2" V 2" V
2" V
2" V
2" V 2" V 2" V 2" V 2" V 2" V
2" V 2" V
2" V
2" V 2" V
2" V
2" V
2" V2" V2" V2" V2" V2" V2" V2" V
2" V2" V2" V3" V
SAN
SAN
SAN
SAN SANSAN SANSANSAN
3" V
2" V
2" V 2" V
2" V 2" V 2" V 2" V 2" V 2" V 2" V 2" V 2" V 2" V 2" V 2" V 2" V
2" V 2" V
2" V
3" V3" V
2" V2" V2" V2" V2" V2" V2" V2" V2" V2" V2" V2" V
3" V
2" V2" V2" V
2" V 2" V
3" V
2" V 2" V2" V2" V 3" V
2" V
3" V
PT GYM
DAILY LIVING SKILLS
PT O/E
PT O/E
2" V
2" V
2" V
4" VTR
W/4" SURESEAL
VENT-GUARD
4" VTR
W/4" SURESEAL
VENT-GUARD
4" VTR
W/4" SURESEAL
VENT-GUARD
4" VTR
W/4" SURESEAL
VENT-GUARD
FFE 54.50
FFE 54.50
FFE 54.50
6" SAN (155 DFU)
INV ELEV 49.50
SEE CIVIL FOR
CONTINUATION
4" 4"
4"4"4" 6"6" 4"4"4"
4"
2" 4"
4"
4" 4" 4"
3"
3"3"3"3" 4"3" 2"3"4"
TP FOR FD-1
IN TOILET ROOMS
WATER SAVER TYPE
BY J.R.SMITH 2698
HWR BRANCH
BALL VALVE
BALANCING VALVE: (FLOW
INDICATING BALANCING
VALVE OR SELF
CONTAINED FLOW
REGULATION VALVE)
UNION
BALL VALVE
HWR WATER
RETURN MAIN
CHECK VALVE
THERMOSTAT
ENLARGED PIPING FOR
THERMOSTAT WELL
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
Pl ot
D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
NONE
1/ 3/
:2
9:
P
M DOMESTIC WATER,
SANITARY WASTE &
VENT RISER
DIAGRAMS
P5.01 10822.000
SCALE: NOT TO SCALE1 DOMESTIC WATER RISER DIAGRAM
SCALE: NONE2 MANIFOLD RECIRCULATION SYSTEM- TMV LAWLER MODEL 802 MS
SCALE: NOT TO SCALE4 SANITARY WASTE & VENT RISER DIAGRAM
SCALE: NOT TO SCALE3 HWR BALANCING ASSEMBLY
GROUND FLOOR
ROOF
GROUND FLOOR
ROOF
GROUND FLOOR
ROOF
GROUND FLOOR
ROOF
1-1/4" GAS SERVICE @ 30 PSI
FROM LOCAL GAS UTILITY
(OKALOOSA). SEE CIVIL DWG
FOR CONTINUATION
GAS REGULATOR & METER
PROVIDED BY THE LOCAL
UTILITY COMPANY (OKALOOSA)
DWH-1
399 CFH
14" W.C. MAX.
SET TEMP
TO 140 DEG F
INSIDE TANK
B-1
750 CFH
14" W.C. MAX
G
G
1-1/2"
G
3/4"
PRESSURE
REGULATOR
BY PLUMBING
CONTRACTOR
G
1-1/4"
G
1"
PRESSURE
REGULATOR
BY PLUMBING
CONTRACTOR
B-2
750 CFH
14" W.C. MAX
1"
G
1"
PRESSURE
REGULATOR
BY PLUMBING
CONTRACTOR
TOTAL FEET OF PIPING FROM GAS METER TO THE
MOST REMOTE OUTLET (DWH-1) = 100 FEET
2015 IFGC TABLE 402.4(5). INLET PRESSURE = 2 PSI,
PRESSURE DROP = 1.0 PSI AND S.G. 0.60
6" 8"
ST
4" RD-1
(2,780 SQ FT)
145 GPM
CO
ST
6"
4"
4"
ST
8"
S/S SCUPPER
BOX. SEE ARCH
DWGS FOR DETAIL
ST
GROUND FLOOR
ROOF
GROUND FLOOR
ROOF
ST
4"
4"
ST
4" RD-1
(1,244 SQ FT)
65 GPM
ST
4" (65 GPM)
ST
S/S SCUPPER
BOX. SEE ARCH
DWGS FOR DETAIL
A
4" ST
(1,244 SQ FT)
65 GPM
SEE CIVIL DWG
FOR CONT.
ST
4"
4"
ST
4" RD-1
(960 SQ FT)
50 GPM
ST
4" (50 GPM)
ST
S/S SCUPPER
BOX. SEE ARCH
DWGS FOR DETAIL
A
4" ST
(960 SQ FT)
50 GPM
SEE CIVIL DWG
FOR CONT.
ST
6"
6"
ST
ST
6" (165 GPM)
ST
S/S SCUPPER
BOX. SEE ARCH
DWGS FOR DETAIL
6" ST
(3,170 SQ FT)
165 GPM
SEE CIVIL DWG
FOR CONT.
4" RD-1
(3,170 SQ FT)
165 GPM
CO
ST
6"
4" 4"
ST
6"
ST
ST
6" (167 GPM)
ST
S/S SCUPPER
BOX. SEE ARCH
DWGS FOR DETAIL
6" ST
(3,250 SQ FT)
167 GPM
SEE CIVIL DWG
FOR CONT.
4" RD-1
(3,250 SQ FT)
167 GPM
CO
ST
6"
4"
ST
6"8"
ST
4" RD-1
(2,920 SQ FT)
152 GPM
CO
ST
6"
4"4"
4" RD-1
(2,920 SQ FT)
152 GPM
ST
8"
8" (304 GPM)
S/S SCUPPER
BOX. SEE ARCH
DWGS FOR DETAIL
8" ST
(5,840 SQ FT)
304 GPM.
SEE CIVIL DWG
FOR CONT.
ST
ST
6"8"
ST
4" RD-1
(2,550 SQ FT)
133 GPM
CO
ST
6"
4"4"
ST
8"
S/S SCUPPER
BOX. SEE ARCH
DWGS FOR DETAIL
ST
4" RD-1
(2,550 SQ FT)
133 GPM
8" (300 GPM)
ST
8" ST
(5,760 SQ FT)
300 GPM
SEE CIVIL DWG
FOR CONT.
B
CO
ST
3" RD-1
(200 SQ FT)
10 GPM
4"
ST
ST
8"
3"6"
6"
4" RD-1
(2,780 SQ FT)
145 GPM
1-1/2"
G
G
1-1/2"
M
1-1/4"
G
2" PSIG PRESSURE
8" (304 GPM)
ST
8" ST
(5,100 SQ FT)
266 GPM.
SEE CIVIL DWG
FOR CONT.
8" (266 GPM)
8" (266 GPM)
ST
B
6"
B
B
B
8"
OFD
4" RD-2
(2,780 SQ FT)
145 GPM
CO
ST(OF)
6"
4"
4"
ST
(O
F)
8" ST(OF)
5560 SQ FT
290 GPM)
8" ST(OF)
SPILL ON GRADE
THRU DOWNSPOUT
NOZZLE ZURN MODEL
Z199-DC
CO
ST(OF)
8"
6"
6"
4" RD-2
(2,780 SQ FT)
145 GPM
6"
ST(OF)
ST(OF)
8"
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
Pl ot
D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
12" = 1'-0"
1/ 3/
:2
9:
P
M STORM WATER AND
GAS RISER DIAGRAM
P5.02 10822.000
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
Cagley & Associates
STRUCTURAL ENGINEERING
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
1700 NEW YORK AVE, NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
Pl ot
D at e:
EGLIN AIR FORCE BASE
BUILDING XX
ASH DR, EGLIN AIR FORCE BASE
FLORIDA
32542
IMEG Corporation
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Baskerville-Donovan, Inc.
CIVIL ENGINEERING
449 W Main Street Pensacola, Florida 32502 850.438.9661 Engineering Business: EB-0000340
SmithGroup
MEP-FP ENGINEERING
1700 New York Ave, Suite 100 Washington, D.C. 20006 202.842.2100
1/ 3/
:3
0:
P
M PLUMBING
SCHEDULES
P7.01 10822.000
NICoE PLUMBING FIXTURE SCHEDULE
FIXTURE
DESIGNATION DESCRIPTION
INDIRECT
WASTE WASTE
COLD
WATER
HOT
WATER
VENT
PIPE FLOW/CAPACITY BASIS OF DESIGN REMARKS
EW-1 EYE WASH 1 1/2" 1/2" ATTACHED TO SPEAKMAN SERVICE SINK FAUCET, SPEAKMAN SEF-9000-TW WITH HOT & COLD WATER, AND THERMOSTATIC MIXING
VALVE
EWC-1 ELECTRIC WATER COOLER WITH BFS 1 1/2" 1/2" 1 1/2" WATER COOLER WITH BOTTLE FILLING STATION: ELKAY LZSTL8WSLK WITH FILTER AND CARRIER: WATTS: CA-431-1 ADA, PROVIDE P-TRAP. ENSURE TO PROVIDE CONCEALED ARM CARRIER.
ICE MAKER (EXIST) 3/4" 1/2" 2" EXISTING ICE MAKER FLOOR MODEL 115V, 60HZ. PROVIDE WATER FILTER KIT, SHUT-OFF VALVE AND DOUBLE CHECK BACKFLOW
PREVENTER IN THE WATER LINE. INDIRECT WASTE DISCHARGE THROUGH AN AIR GAP FITTING.
ICE MAKER DISPENSER TOUCH FREE ICE MACHINE/ DISPENSER 3/4" 1/2" 2" MDT3F12 - TOUCH FREE ICE MACHINE/ DISPENSER 115V, 60HZ. PROVIDE WATER FILTER KIT, SHUT-OFF VALVE AND DOUBLE CHECK BACKFLOW
PREVENTER IN THE WATER LINE. INDIRECT WASTE DISCHARGE THROUGH AN AIR GAP FITTING.
LAV-1A LAVATORY (PUBLIC TLT) 1 1/2" 1/2" 1/2" 1 1/2" 0.5 GPM KOHLER K-2205-G UNDER MOUNTED, OVAL CHINA W/GLAZED UNDERSIDE. CHICAGO FAUCETS: 116.102.21.1 ADA, ELECTRONIC FAUCET, HARD-WIRED, COORDINATE WITH ELEC.
LAV-2A LAVATORY 1 1/2" 1/2" 1/2" 1 1/2" AMERICAN STANDARD: 0356.015, CHICAGO FAUCETS: 786-GN1A-CP ADA, GOOSENECK, WRIST BLADES, PROVIDE CONCEALED ARM LAVATORY SUPPORT MSB-1 MOP SERVICE BASIN 3" 1/2" 1/2" 2" SERVICE SINK: FIAT TSB3010; SPEAKMAN FAUCETS: SC-5811-RCP WITH STAINLESS STEEL CAPS ON THRESHOLD ONLY SDB-1 SUPPLY DRAIN BOX (FOR CLOTH WASHER) 2" 1/2" 1/2" 1 1/2" GUY GRAY T200 MOUNT MINIMUM 4' AFF.
SH-1A SHOWER TRIM, VALVE & SHOWER PAN
(HANDICAP)
3" 1/2" 1/2" 1 1/2" 1.5 GPM POWERS E420S12-1-W (24" GRAB BAR), PROVIDE OMNI FLOW CONTROL A-710 (1.5 GPM). SHOWER PAN: SWANSTONE STS-3738, ADA
PROVIDE COLLAPSIBLE DAM WITH END CAPS. COLOR: CLOUD BONE
HAND SHOWER ONLY, SEE ARCH FOR SHOWER AND SHOWER DRAIN.
SK-1A SINK 1 1/2" 1/2" 1/2" 1 1/2" AMERICAN STANDARD: 0356.015, CHICAGO FAUCETS: 786-CP ADA, GOOSENECK, WRIST BLADES, PROVIDE CONCEALED ARM SINK SUPPORT
SK-2A 1 1/2" 1/2" 1/2" 1 1/2"
SK-2A W/ DISPOSAL SINK W/ DISPOSAL 1 1/2" 1/2" 1/2" 1 1/2" ELKAY: DLR191910-PD, K-15175-P (8-1/2" SPOUT), AERATOR: 1054432, BADGER #1 DISPOSER: 120V, 1/3HP PF Connector UR-1 URINAL 2" 3/4" 1 1/2" 0.125 GPF SLOAN SU-1000-0.125, WITH OVERRIDE BUTTON WALL HUNG, ELECTRONIC FLUSH VALVE, HARD-WIRED, COORDINATE WITH ELEC.
UR-1A URINAL (HANDICAP) 2" 3/4" 1 1/2" 0.125 GPF SLOAN SU-1000-0.125, WITH OVERRIDE BUTTON ADA, WALL HUNG, ELECTRONIC FLUSH VALVE, HARD-WIRED, COORDINATE WITH ELEC.
WC-1 WATER CLOSET 4" 1 1/4" 2" 1.28 GPF SLOAN 2050. 1001-1.28
WC-1A WATER CLOSET (HANDICAP) 4" 1 1/4" 2" 1.28 GPF SLOAN 2050. 1001-1.28
WH-1 WALL HYDRANT 3/4" ZURN Z1320
NICoE DOMESTIC WATER HEATER SCHEDULE
TAG LOCATION
STORAGE
GALLON
RECOVERY GPH 40°
F-140° F
TEMPERATURE
INPUT BTU
MINIMUM
PRESSURE
MAXIMUM
PRESSURE
ELECTRICAL
OPERATING
WEIGHT (LBS) Model Type CommentsTYPE INLET WATER (° F) OUTLET WATER (° F) VOLTAGE MFLA
INPUT
POWER
DWH-1 MECHANICAL 220 NATURAL GAS 130 471 45 140 399,000 3.5 W.C 14" W.C 120 V 1800 PVI 40 L 130A-GCML PROVIDE WITH TMV LAWLER MODEL 802 MS AND EXPANSION TANK
BY WESSELS MODEL TTA-12 2" HOT/COLD, RETURN AND 3/4" GAS
CONNECTION
NICoE DRAIN SCHEDULE
TAG DRAIN TYPE
System Served BASIS OF DESIGN Comments
FD-1 FLOOR DRAIN FINISHED AREAS SANITARY ZURN MODEL Z415S-6X6-P-VP SEE DRAWINGS FOR SIZES, PROVIDE TRAP PRIMER CONNECTION FD-2 FLOOR DRAIN UNFINISHED AREAS SANITARY ZURN MODEL Z554-P SEE DRAWINGS FOR SIZES, PROVIDE TRAP PRIMER CONNECTION
OSD-1 FLOOR DRAIN PT GYM 200 SANITARY ZURN MODEL Z554-P
RD-1 ROOF DRAIN PRIMARY STORM ZURN MODEL Z100-ZC-E-EA SEE DRAWINGS FOR SIZES
RD-2 ROOF DRAIN SECONDARY(OVERFLOW) STORM ZURN MODEL Z100-ZC-E-EA WITH W2 OPTION (2" INTERNAL WATER DAM)
NICoE HOT WATER EXPANSION TANK SCHEDULE
TAG LOCATION
TANK
VOLUME
(GAL)
MAX
ACCEPTANCE
(GAL) DIAMETER HEIGHT
BASIS OF
DESIGN Comments
ET-1 MECHANICAL
5 3.1 1' - 0" 1' - 2" WESSELS
TTA-12
NICoE PUMP SCHEDULE
TAG SYSTEM TYPE LOCATION
CAPACITY
(GPM)
DISCHARGE
HEAD (FT) SUCTION DISCHARGE HP RPM VOLTAGE PHASE Manufacturer Model
Type Comments
RP-1 DOMESTIC HOT WATER MECHANICAL 220 0-31 20 1" 1" 1/8 3250 115 V 1 TACO 0011-SF4
NICoE TRAP PRIMER SCHEDULE TAG LOCATION BASIS OF DESIGN Type Comments
ETP-1 MECHANICAL 220 PPP TS-8 ELECTRONIC TRAP PRIMER (FOR FD-2), SURFACE MOUNTED
| P2 - Sheet - P0-1 - PLUMBING ABBREVIATIONS -SYMBOLS-GENERAL NOTES |
| Sheets |
| P0.1 - PLUMBING ABBREVIATIONS /SYMBOLS/GENERAL NOTES |
| P2.00 - UNDERGROUND PLUMBING PLAN |
| P2.01 - GROUND FLOOR PLUMBING PLAN |
| P2.02 - ROOF PLUMBING PLAN |
| P5.01 - DOMESTIC WATER, SANITARY WASTE & VENT RISER DIAGRAMS |
| P5.02 - STORM WATER AND GAS RISER DIAGRAM |
| P7.01 - PLUMBING SCHEDULES |
| P2 - Sheet - P2-00 - UNDERGROUND PLUMBING PLAN |
| Sheets |
| P0.1 - PLUMBING ABBREVIATIONS /SYMBOLS/GENERAL NOTES |
| P2.00 - UNDERGROUND PLUMBING PLAN |
| P2.01 - GROUND FLOOR PLUMBING PLAN |
| P2.02 - ROOF PLUMBING PLAN |
| P5.01 - DOMESTIC WATER, SANITARY WASTE & VENT RISER DIAGRAMS |
| P5.02 - STORM WATER AND GAS RISER DIAGRAM |
| P7.01 - PLUMBING SCHEDULES |
| P2 - Sheet - P2-01 - GROUND FLOOR PLUMBING PLAN |
| Sheets |
| P0.1 - PLUMBING ABBREVIATIONS /SYMBOLS/GENERAL NOTES |
| P2.00 - UNDERGROUND PLUMBING PLAN |
| P2.01 - GROUND FLOOR PLUMBING PLAN |
| P2.02 - ROOF PLUMBING PLAN |
| P5.01 - DOMESTIC WATER, SANITARY WASTE & VENT RISER DIAGRAMS |
| P5.02 - STORM WATER AND GAS RISER DIAGRAM |
| P7.01 - PLUMBING SCHEDULES |
| P2 - Sheet - P2-02 - ROOF PLUMBING PLAN |
| Sheets |
| P0.1 - PLUMBING ABBREVIATIONS /SYMBOLS/GENERAL NOTES |
| P2.00 - UNDERGROUND PLUMBING PLAN |
| P2.01 - GROUND FLOOR PLUMBING PLAN |
| P2.02 - ROOF PLUMBING PLAN |
| P5.01 - DOMESTIC WATER, SANITARY WASTE & VENT RISER DIAGRAMS |
| P5.02 - STORM WATER AND GAS RISER DIAGRAM |
| P7.01 - PLUMBING SCHEDULES |
| P2 - Sheet - P5-01 - DOMESTIC WATER, SANITARY WASTE & VENT RISER DIAGRAMS |
| Sheets |
| P0.1 - PLUMBING ABBREVIATIONS /SYMBOLS/GENERAL NOTES |
| P2.00 - UNDERGROUND PLUMBING PLAN |
| P2.01 - GROUND FLOOR PLUMBING PLAN |
| P2.02 - ROOF PLUMBING PLAN |
| P5.01 - DOMESTIC WATER, SANITARY WASTE & VENT RISER DIAGRAMS |
| P5.02 - STORM WATER AND GAS RISER DIAGRAM |
| P7.01 - PLUMBING SCHEDULES |
| P2 - Sheet - P5-02 - STORM WATER AND GAS RISER DIAGRAM |
| Sheets |
| P0.1 - PLUMBING ABBREVIATIONS /SYMBOLS/GENERAL NOTES |
| P2.00 - UNDERGROUND PLUMBING PLAN |
| P2.01 - GROUND FLOOR PLUMBING PLAN |
| P2.02 - ROOF PLUMBING PLAN |
| P5.01 - DOMESTIC WATER, SANITARY WASTE & VENT RISER DIAGRAMS |
| P5.02 - STORM WATER AND GAS RISER DIAGRAM |
| P7.01 - PLUMBING SCHEDULES |
| P2 - Sheet - P7-01 - PLUMBING SCHEDULES |
| Sheets |
| P0.1 - PLUMBING ABBREVIATIONS /SYMBOLS/GENERAL NOTES |
| P2.00 - UNDERGROUND PLUMBING PLAN |
| P2.01 - GROUND FLOOR PLUMBING PLAN |
| P2.02 - ROOF PLUMBING PLAN |
| P5.01 - DOMESTIC WATER, SANITARY WASTE & VENT RISER DIAGRAMS |
| P5.02 - STORM WATER AND GAS RISER DIAGRAM |
| P7.01 - PLUMBING SCHEDULES |
| P2-00 - UNDERGROUND PLUMBING PLAN.pdf |
| Sheets |
| P2.00 - UNDERGROUND PLUMBING PLAN |