W9127821R0048 Solicitation Vol 2.pdf

PDF 2 MB Posted

Attached to
Construct Munitions Maintenance Facility and Igloos - Eglin Air Force Base, Florida Federal contract opportunity
Solicitation number
W9127821R0048
Issued by
Department of the Army Corps of Engineers Engineering District Mobile

About this file

This federal contract solicitation is for the construction of a Munitions Maintenance Facility and Igloos at Eglin Air Force Base in Florida. The project includes building a multi-bay explosive operating facility with reinforced concrete foundation and floor slab, concrete walls, and a reinforced concrete roof deck. Functional areas will include munitions inspection and maintenance labs/bays, receiving room, parts storage, administrative offices, latrines, a support/tool room, and a mechanical equipment room. The solicitation is a total small business set-aside, with the NAICS code being 236220. The procurement is using best value source selection. The pre-construction site visit information and questions will be included in the RFP available on SAM.gov. Bidders must register in SAM.gov in order to access the solicitation documents.

View the file

Other files for this federal contract opportunity

Other files attached to Construct Munitions Maintenance Facility and Igloos - Eglin Air Force Base, Florida, newest first.
File Type Posted
W9127821R0048 JA for Trane HVAC_Redacted.pdf PDF
W9127821R0048 Site Visit Sign In Sheet.pdf PDF
W9127821R0048 AM03.pdf PDF
W9127821R0048 AM03 DRAWINGS.pdf PDF
W9127821R0048 AM02.pdf PDF
W9127821R0048 AM01.pdf PDF
W9127821R0048 Solicitation Vol 3.pdf PDF
W9127821R0048 RTA DRAWINGS.pdf PDF
W9127821R0048 RTA DRAWINGS- BID OPTION.pdf PDF
W9127821R0048 Solicitation Vol 4.pdf PDF
W9127821R0048 Solicitation Vol 1.pdf PDF
W9127821R0048 EM_385-1-1 Safety Manual Link.pdf PDF
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

THIS IS A TOTAL SMALL BUSINESS (SB) SET-ASIDE

VOLUME 2 OF 4

SOLICITATION NO: W9127821R0048

CADD NO: MHF20006

SPECIFICATIONS

FOR

CONSTRUCT

MUNITIONS MAINTENANCE FACILITY

AND

IGLOOS

EGLIN AIR FORCE BASE, FLORIDA

(OKALOOSA COUNTY)

“GOOD ENGINEERING RESULTS IN A BETTER ENVIRONMENT”

U.S. ARMY ENGINEER DISTRICT, MOBILE

109 St. Joseph St

Mobile, Alabama 36602

CONSTRUCT MUNITIONS MAINTENANCE FACILITY AND IGLOOS W9127821R0048

EGLIN AIR FORCE BASE, FLORIDA MHF20006

Table of Contents Page 1

TABLE OF CONTENTS

VOLUME 1 OF 4

CHECKLIST FOR PREPARATION OF OFFERS

BIDDING REQUIREMENTS

CONTRACT CLAUSES

STANDARD FORM 1442 - SOLICITATION, OFFER, AND AWARD

BIDDING SCHEDULE

EXPLANATION OF BID ITEMS

STANDARD FORM 24 - BID BOND

STANDARD FORM 28 - AFFIDAVIT OF INDIVIDUAL SURETY

STANDARD FORM LLL - DISCLOSURE OF LOBBYING ACTIVITIES

00 11 00 PROPOSAL SUBMISSION AND INSTRUCTIONS

00 12 00 SELECTION PROCEDURES AND BASIS OF AWARD

00 21 16 INSTRUCTIONS TO PROPOSERS

00 45 00 REPRESENTATIONS AND CERTIFICATIONS

00 70 00 CONDITIONS OF THE CONTRACT

SPECIFICATIONS

DIVISION 01 - GENERAL REQUIREMENTS

01 00 00 ADDITIONAL SPECIAL CONTRACT REQUIREMENTS

BASE ACCESS FORM

EP310-1-6a PROJECT SIGNS

DD FORM 1354

DD FORM 1354 CHECKLIST

WAGE RATES

01 00 01 GENERAL CONTRACT REQUIREMENTS

CESAM FORM 1151

01 32 01.00 10 PROJECT SCHEDULE

01 33 00 SUBMITTAL PROCEDURES

SUBMITTAL REGISTER

FORM 4025

01 33 29 SUSTAINABILITY REPORTING

01 35 26 GOVERNMENTAL SAFETY REQUIREMENTS

01 42 00 SOURCES FOR REFERENCE PUBLICATIONS

01 45 00.00 10 QUALITY CONTROL

01 45 00.15 10 RESIDENT MANAGEMENT SYSTEM CONTRACTOR MODE (RMS CM)

SAM FORM 696

01 45 35 SPECIAL INSPECTIONS

STATEMENT OF SPECIAL INSPECTIONS

SCHEDULE OF SPECIAL INSPECTIONS

01 57 19 TEMPORARY ENVIRONMENTAL CONTROLS – EGLIN STANDARD

01 74 19 CONSTRUCTION AND DEMOLITION WASTE MANAGEMENT

01 78 23 OPERATION AND MAINTENANCE DATA

01 91 00.15 10 TOTAL BUILDING COMMISSIONING

DIVISION 02 – EXISTING CONDITIONS

02 41 00 DEMOLITION

Table of Contents Page 2

DIVISION 03 – CONCRETE

03 30 00 CAST-IN-PLACE CONCRETE

03 45 00 PRECAST ARCHITECTURAL CONCRETE

DIVISION 04 – MASONRY

04 20 00 UNIT MASONRY

DIVISION 05 – METALS

05 05 23 WELDING, STRUCTURAL

05 12 00 STRUCTURAL STEEL

05 21 00 STEEL JOIST FRAMING

05 30 00 STEEL DECKS

05 40 00 COLD-FORMED METAL FRAMING

05 50 13 MISCELLANEOUS METAL FABRICATIONS

DIVISION 06 – WOOD, PLASTICS, AND COMPOSITES

06 10 00 ROUGH CARPENTRY

06 41 16 LAMINATE CLAD ARCHITECTURAL CASEWORK

06 61 16 SOLID POLYMER (SOLID SURFACING) FABRICATIONS

VOLUME 2 OF 4

DIVISION 07 – THERMAL AND MOISTURE PROTECTION

07 15 00 WALL AIR AND VAPOR BARRIERS

07 21 16 MINERAL FIBER BLANKET INSULATION

07 22 00 ROOF AND DECK INSULATION

07 27 00 BUILDING AIR BARRIER SYSTEM

07 41 13 METAL ROOF PANELS

07 60 00 FLASHING AND SHEET METAL

07 84 00 FIRESTOPPING

07 92 00 JOINT SEALANTS

DIVISION 08 – OPENINGS

08 11 13 STEEL DOORS AND FRAMES

08 33 23 OVERHEAD COILING DOORS

08 34 59 VAULT DOORS

08 34 73 SOUND CONTROL DOOR ASSEMBLIES

08 71 00 DOOR HARDWARE

08 91 00.00 36 METAL WALL LOUVERS

DIVISION 09 – FINISHES

09 06 00 SCHEDULES FOR FINISHES

09 22 00.00 36 SUPPORTS FOR PLASTER AND GYPSUM BOARD

09 29 00.00 36 GYPSUM BOARD

09 30 10 PORCELAIN AND GLASS TILING

09 51 00.00 36 ACOUSTICAL CEILINGS

09 65 00.00 36 RESILIENT FLOORING

09 90 00.00 36 PAINTS AND COATINGS

09 97 13.00 40 STEEL COATINGS

Table of Contents Page 3

DIVISION 10 – SPECIALTIES

10 14 00.10 EXTERIOR SIGNAGE

10 14 00.20 36 INTERIOR SIGNAGE

10 21 13.00 36 TOILET COMPARTMENTS

10 28 13 TOILET ACCESSORIES

DIVISION 21 – FIRE SUPPRESSION

21 13 13.00 10 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION

21 30 00 FIRE PUMPS

DIVISION 22 – PLUMBING

22 00 00 PLUMBING, GENERAL PURPOSE

DIVISION 23 – HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)

23 00 00 AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST SYSTEMS

23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC

23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS

23 09 00 INSTRUMENTATION AND CONTROL FOR HVAC

23 09 13 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC

23 09 23.02 BACNET DIRECT DIGITAL CONTROL FOR HVAC AND OTHER BUILDING

CONTROL SYSTEMS

23 23 00 REFRIGERANT PIPING

23 64 10 WATER CHILLERS, VAPOR COMPRESSION TYPE

23 64 26 CHILLED, WATER PIPING SYSTEMS

23 81 00 DECENTRALIZED UNITARY HVAC EQUIPMENT

23 82 46.00 40 ELECTRIC UNIT HEATERS

DIVISION 25 – INTEGRATED AUTOMATION

25 05 11.01 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS – FIRE

ALARM AND MASS NOTIFICATION SYSTEM

25 05 11.02 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS – UTILITY

MONITORING CONTROL SYSTEM

VOLUME 3 OF 4

DIVISION 26 – ELECTRICAL

26 12 19.10 THREE-PHASE, LIQUID-FILLED PAD-MOUNTED TRANSFORMERS

26 20 00 INTERIOR DISTRIBUTION SYSTEM

26 29 23 ADJUSTABLE SPEED DRIVE (ASD) SYSTEMS UNDER 600 VOLTS

26 32 15.00 ENGINE-GENERATOR SET STATIONARY 15-2500 KW, WITH AUXILIARIES

26 35 43 400-HERTZ (HZ) SOLID STATE FREQUENCY CONVERTER

26 36 23 AUTOMATIC TRANSFER SWITCHES AND BY-PASS/ISOLATION SWITCH

26 41 00 LIGHTNING PROTECTION SYSTEM

26 42 14.00 10 CATHODIC PROTECTION SYSTEM (SACRIFICIAL ANODE)

26 51 00 INTERIOR LIGHTING

26 56 00 EXTERIOR LIGHTING

Table of Contents Page 4

DIVISION 27 – COMMUNICATIONS

27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM

DIVISION 28 – ELECTRONIC SAFETY AND SECURITY

28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM, ADDRESSABLE

DIVISION 31 - EARTHWORK

31 00 00 EARTHWORK

31 11 00 CLEARING AND GRUBBING

31 31 16.13 CHEMICAL TERMITE CONTROL

DIVISION 32 – EXTERIOR IMPROVEMENTS

32 01 16.71 COLD MILLING ASPHALT PAVING

32 01 19.61 SEALING OF JOINTS IN RIGID PAVEMENTS

32 05 33 LANDSCAPE ESTABLISHMENT

32 11 20 SUBBASES FOR FLEXIBLE PAVING

32 11 23 GRADED CRUSHED AGGREGATE BASE COURSES

32 12 13 BITUMINOUS TACK AND PRIME COATS

32 12 16 HOT-MIX ASPHALT (HMA) FOR ROADS AND PARKING

32 13 13.06 PORTLAND CEMENT CONCRETE PAVEMENT FOR ROADS AND SITE

FACILITIES

32 15 00 AGGREGATE SURFACING FOR CONSTRUCTION ACCESS ROAD

32 16 19 CONCRETE CURBS, GUTTERS AND SIDEWALKS

32 17 23 PAVEMENT MARKINGS

32 31 13.53 HIGH-SECURITY TEMPORARY AND PERMANENT CHAIN LINK FENCES AND

GATES

32 92 19 SEEDING

32 92 23 SODDING

DIVISION 33 – UTILITIES

33 11 00 WATER UTILITY DISTRIBUTION PIPING

33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION

33 82 00 TELECOMMUNICATIONS OUTSIDE PLANT (OSP)

DIVISION 41 – MATERIAL PROCESSING AND HANDLING EQUIPMENT

41 22 13.15 BRIDGE CRANES, OVERHEAD ELECTRIC, UNDER RUNNING

VOLUME 4 OF 4

APPENDICES

APPENDIX A AIR FORCE FORM 813 REQUEST FOR ENVIRONMENTAL IMPACT

ANALYSIS – SIGNED 30 MAY 2017

APPENDIX B BORING LOCATION PLAN AND BORING LOGS

APPENDIX C AF_SUST_SCORESHEET_GP_vFEB2017

APPENDIX D 33 10 00 WATER PIPING STRUCTURES AND APPURTENANCES

(REV. 07242019)

APPENDIX E 33 30 00 SANITARY SEWER PIPING, STRUCTURES AND APPURTENANCES

(REV. 07202016)

Table of Contents Page 5

APPENDICES (CONTINUED)

APPENDIX F 33 32 17 SUBMERSIBLE UTILITY WASTEWATER PUMPING STATION

(REV. 11292015)

APPENDIX G EGLIN ARCHITECTURAL COMPATIBILITY PLAN

APPENDIX H FF&E, CID AND SID

--End of Project Table of Contents--

This page was intentionally left blank for duplex printing.

SECTION 07 15 00

WALL AIR AND VAPOR BARRIERS

05/11

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

ASTM INTERNATIONAL (ASTM)

ASTM C 1060 (90; R 2003) Standard Practice for Thermographic Inspection of Insulation Installations in Envelope Cavities of Frame Buildings

ASTM C 836 (2003) High Solids Content, Cold Liquid-Applied Elastomeric Waterproofing Membrane for Use With Separate Wearing Course

ASTM D 1876 (2008) Standard Test Method for Peel Resistance of Adhesives (T-Peel Test)

ASTM D 1970 (2001) Self-Adhering Polymer Modified Bituminous Sheet Materials Used as Steep Roofing Underlayment for Ice Dam Protection

ASTM D 2000 (2005) Rubber Products in Automotive Applications

ASTM D 3767 (1992) Standard Practice for Rubber - Measurements of Dimensions

ASTM D 412 (2006ae2) Standard Test Methods for Vulcanized Rubber and Thermoplastic Elastomers - Tension

ASTM D 4541 (2002) Standard Test Method for Pull-Off Strength of Coatings Using Portable Adhesion Testers

ASTM E 96 (2005) Water Vapor Transmission of Materials

ASTM E 154 (2008a) Water Vapor Retarders Used in Contact with Earth Under Concrete Slabs, on Walls, or as Ground Cover

ASTM E 162 (2002a) Surface Flammability of Materials Using a Radiant Heat Energy Source

SECTION 07 15 00 Page 1

ENTIRE SECTION ADDED BY AMENDMENT NO. 0002

ASTM E 283 (2004) Determining the Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen

ASTM E 779 (2003) Standard Test Method for Determining Air Leakage Rate by Fan Presurization

ASTM E 1186 (2003) Standard Practices for Air Leakage Site Detection in Building Envelopes and Air Barrier Systems

ASTM E 1677 (2005) Standard Specification for an Air Retarder (AR) Material or System for Low-Rise Framed Building Walls

ASTM E 1680 (95; R 2003) Standard Test Method for Rate of Air Leakage Through Exterior Metal Roof Panel Systems

ASTM E 2178 (2003) Standard Test Method for Air Permeance of Building Materials

ASTM E 2357 (2005) Standard Test Method for Determining Air Leakage of Air Barrier Assemblies

INTERNATIONAL ORGANIZATION FOR STANDARDIZATION (ISO)

ISO 6781 (1983) Thermal Insulation - Qualitative Detection of Thermal Irregularities in Building Envelopes - Infrared Method, First Edition

US ARMY CORPS OF ENGINEERS (USACE)

USACE-ALTP Air Leakage Test Protocol for Measuring Air Leakage in Buildings

1.2 SUBMITTALS

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are for Contractor Quality Control approval. The following shall be submitted in accordance with Section

01 33 00 SUBMITTAL PROCEDURES:

SD-02 Shop Drawings

Shop Drawings

Manufacturer's standard detail catalog and shop drawings depicting typical and specific detail conditions of the required installation.

Details shall include, but are not limited to, interface with other envelope assemblies and materials, corners, terminations, transitions, joints and gaps to be bridged, and sealing of attachments and penetrations through the barrier membrane materials.

SECTION 07 15 00 Page 2

SD-03 Product Data

Closed-cell sprayed polyurethane foam barrier; G, DO

Accessory materials

Submit product data to identify the materials to be used and compliance with specified requirements.

SD-04 Samples

Composite, self-adhering membrane barrier sheeting

SD-05 Design Data

Design Data G, DO

Information related to the postive and negative pressure resistance and adhesion properties (e.g., pull-off and peel strength) of the barrier material to the substrate.

SD-06 Test Reports

Test Reports; G, DO

Whole Building Air Leakage Test Report; G, DO

Thermography Test Report; G, DO

SD-07 Certificates

Manufacturer's certification of materials compatibility; G, RO

Inspector Qualifications; G, RO

Whole Building Air Leakage Test Technician Qualifications; G, RO

Thermography Technician Qualifications; G, RO

Certify that the inspectors and technicians meet the specified requirements.

Whole Building Air Leakage Test Procedures; G, RO

Thermography Test Procedures; G, RO

SD-08 Manufacturer's Instructions

Manufacturer's instructions; G, RO

Detailed surface preparation and application instructions and precautions for all materials used, including but not limited to, membrane, fluid-applied products, cleaners, primers, adhesives, mastics, and other accessory materials.

Material safety data sheets (MSDS).

SECTION 07 15 00 Page 3

1.3 PREINSTALLATION CONFERENCE

Prior to starting application of the air and vapor barrier system, arrange and attend a preinstallation conference to ensure a clear understanding of the requirements. Give the Contracting Officer 7 days advance written notice of the time and place of meeting. Ensure that the air and vapor barrier inspector, mechanical and electrical subcontractor, flashing and sheetmetal subcontractor, and other trades that may perform other types of work penetrating through, on, or over the barrier membrane attend this conference. The conference shall address where each sub-contractor begins and ends, the sequence of installation, and each sub-contractor's responsibility to ensure airtight joints, junctures, penetrations and transitions between materials, products, and assemblies of products specified in the different sections to be installed by the different sub-contractors.

1.4 DELIVERY, STORAGE, AND HANDLING

Deliver materials in manufacturer's original, unopened containers, with labels intact and legible. Containers of materials covered by a referenced specification number shall bear the specification number, type, and class of the contents. Deliver materials in sufficient quantity to continue work without interruption. Store and protect materials in accordance with manufacturer's instructions, and use within their indicated shelf life. When hazardous materials are involved, adhere to special precautions of the manufacturer, unless precautions conflict with local, state, and federal regulations. Promptly remove from the site materials or incomplete work adversely affected by exposure to moisture, freezing, or contaminents. Store materials on pallets and cover from top to bottom with canvas tarpaulins.

1.5 ENVIRONMENTAL CONDITIONS

Apply materials when ambient temperature is 40 degrees F or above for a period of 24 hours prior to the application and when there is no ice, frost, surface moisture, or visible dampness on the substrate surface, except as allowed by the product manufacturer's published instructions.

Apply materials when air temperature is expected to remain above 40 degrees F during the cure period recommended by the manufacturer. Work may be performed within heated enclosures, provided the surface temperature of the substrate is maintained at a minimum of 40 degrees F for 24 hours prior to the application of the materials, and remains above that temperature during the cure period recommended by the manufacturer.

1.6 PERFORMANCE REQUIREMENTS

1.6.1 General Materials Performance Requirements

All materials of the barrier membrane system shall comply with the following:

a. Air Permeance of Materials - Materials shall have an air permeance less than or equal to 0.004 cfm/sf under a pressure differential of

1.57 psf when testing in accordance with ASTM E 2178 .

b. Moisture Vapor Permeance - Materials shall have water vapor permeance of 1.0 perm or less, unless otherwise indicated,when tested in accordance with ASTM E 96 . Closed-cell sprayed polyurethane foam shall provide the specified water vapor permeance at the cured foam

SECTION 07 15 00 Page 4 thickness over the substrate material.

1.6.2 Assembly Performance Requirements

The assembly shall accommodate movements of building materials by providing expansion and control joints and flexible connections as required with accessory air and vapor seal materials at such locations, changes in substrate and perimeter conditions. Assembly shall be capable of withstanding combined positive and negative design wind, fan and stack pressures on the envelope without damage or displacement, and shall transfer the load to the structure. Assembly shall not displace adjacent materials under full load. Assembly shall be joined in an air and water-tight flexible manner to the barrier material of adjacent assemblies, allowing for the relative movement of assemblies due to thermal and moisture variations and creep, and anticipated seismic movement. For drainage or cavity wall constructions, the air and vapor barrier assembly shall perform as a liquid drainage plane flashed to discharge condensation or water penetration to the exterior.

1.6.2.1 Connections

Connections shall prevent air leakage and vapor migration at the following locations:

a. Foundation and walls, including penetrations, ties and anchors.

b. Walls, windows, curtain walls, storefronts, louvers or doors.

c. Different wall assemblies, and fixed openings within those assemblies.

d. Wall and roof connections and penetrations.

e. Floors over unconditioned space.

f. Walls, floor and roof across construction, control and expansion joints.

g. Walls, floors and roof to utility, pipe and duct penetrations.

h. Seismic and expansion joints.

i. All other leakage pathways in the building envelope.

1.6.3 Air Permeance of Assemblies

Assemblies of materials and components including, but not limited to, sealants and tapes, shall have an average air leakage of 0.04 cfm/sf or less under a pressure differential of 1.57 psf when tested in accordance with ASTM E 2357 , ASTM E 1680 , ASTM E 1677 , or ASTM E 283 , as applicable to the assembly.

1.6.4 Whole Building Air Leakage

Whole building air leakage testing shall indicate air leakage not to exceed 0.25 cfm/sf of building envelope area at a pressure differential of

1.57 psf when tested in accordance with USACE-ALTP Air Leakage Test Protocol for Measuring Air Leakage in Buildings.

SECTION 07 15 00 Page 5

1.7 QUALITY CONTROL

The Contractor shall provide quality control personnel, procedures, testing and verification as specified. The Contractor shall facilitate inspections, tests, and other quality control services specified elsewhere in the Contract Documents and required by the Contracting Officer.

1.7.1 Coordination of Sub-Contractor(s)

The Contractor shall provide coordination between the sub-contractors involved in the construction of the air and vapor barrier system, coordinate the sequence of construction to ensure continuity of the barrier system joints, junctures, penetrations, and transitions between materials and assemblies of materials and products from substructure to walls to roof.

1.7.2 Inspection

The Contractor shall provide an experienced inspector knowledgeble of air and vapor barrier construction to oversee: the sequencing and installation of the air and vapor barrier component materials and assemblies; the proper joining and sealing of the materials and assemblies; the sealing of penetrations of the barrier materials and assemblies; and to instruct the subcontractors on the above. The inspector shall also verify the items under "Field Quality Control" paragraph of this specification section.

1.7.2.1 Inspector Qualifications

The inspector shall have a minium of 3 years experience in the installation of air and vapor barrier materials and assemblies in similar construction including the experience in joining and sealing various components, and sealing of penetrations of the barrier. The inspector shall have experience coordinating and instructing installers involved in the installation, joining, and sealing of the barrier system materials and components.

1.7.2.2 Documentation and Reporting

Document the installation process on daily reports to the Contracting Officer. Include information on the installer, substrates, substrate preparation, products used, ambient and substrate temperature, the location of the barrier installation, problems encountered and their resolution, the results of the quality control procedures, and any testing results.

1.7.3 Testing

The Contractor shall perform the testing specified. Qualified personnel meeting the specified requirements shall conduct the test and report the test results.

1.7.3.1 Whole Building Air Leakage Test Technician Qualifications

The testing technician shall have a minimum of 3 years experience in whole building leakage testing using the specified testing procedure.

Technician shall also have experience in identifying deficiencies in the building construction upon failure of the test to meet the specified requirements.

SECTION 07 15 00 Page 6

1.7.3.2 Thermography Technician Qualifications

The testing technician shall have received formal training in the application of infrared thermography to building envelope inspection, moisture intrusion, and energy loss in buildings. Training shall be documented by certificate from a recognized thermographer training organization such as the Infrared Training Center, Building Science Institute, Infraspection Institute, or other entity as approved by and at the sole discretion of the Contracting Officer. The thermographer shall have a minimum of 5 years experience in infrared thermography applied to building science.

1.7.3.3 Test Procedures

The Contractor shall submit detailed test procedures indicating the test apparatus, the test methods and procedures, and the analysis methods to be employed for the Whole Building Air Leakage Test and the Thermography Test.

The procedure shall be submitted not later than 90 days after the Notice to Proceed. Refer to the drawings for the indicated test areas and excluded areas.

1.7.3.4 Test Reports

The inspection and testing agency shall submit a certifed written report, in duplicate, of each inspection, test, or similar service to the Contracting Officer not later than 10 days after each inspection or test.

The report shall include the following information as a minimum:

a. Date of issue

b. Project title and number

c. Name, address, and phone number of the testing agency

d. Names of individuals making the inspection or test

e. Dates and locations of tests, inspections, or samples

f. Designation of the Work and test method

g. Identification of product(s) and applicable specification section

h. Complete, detailed inspection or test data

i. Test results and a professional, conclusive interpretation of the test results

j. Comments and profession opinion on whether the inspected or tested Work complies with the contract requirements and recommendations for remedy as applicable

k. Recommendations on re-inspection or retesting.

l. Name and signature of inspector The Whole Building Air Leakage Test Reports, Bond Adhesion Strength Test Reports and Thermography Test Reports shall be submitted in duplicate to the Contracting Officer not later than 10 days after each inspection or test. The report shall adhere to and include the requirements specified for Test Reports and additionally as otherwise stated or referenced in the

SECTION 07 15 00 Page 7 test standards or procedures.

1.8 WARRANTY

1.8.1 Material Warranty

Provide barrier membrane manufacturer's material warranty for a minimum of 3 years from date of substantial completion. Warranty shall provide for the replacement of any materials that fail to cure or that deteriorate to the point of no longer meeting the specified requirements.

1.8.2 Contractor Warranty

Provide a minimum 2 year contractor materials and workmanship warranty from the date of substantial completion. Warranty shall include all components of the air and vapor barrier system assembly. Failure of airtight seal, failure of watertight seal, loss of adhesion, loss of cohesion, failure to cure, or other failures of materials or installation workmanship such that the barrier system no longer meets the specified requirements shall be corrected by the contractor at no additional cost to the Government, including all costs of removals and repair work necesary to return the construction to the original construction requirements.

PART 2 PRODUCTS

2.1 MATERIALS

Provide the type of air and vapor barrier material and related primers, adhesives, mastics, tapes, sealants, and other accessories as specified and necessary for a complete air and vapor barrier system assembly.

Ensure compatibility of the materials within a specific barrier membrane type, with each other, and with the materials to which they will be applied. Materials shall conform to the specified Performance Requirements and materials properties specified when tested in accordance with the referenced standards.

Submit to the Contracting Officer the following items as detailed in the Submittals Article:

a. Shop drawings G, DO

b. Design data G, DO

c. Manufacturer's certification of materials compatibility

d. Manufacturer's instructions G, DO

e. Material safety data sheets (MSDS)

2.2 FLUID-APPLIED MEMBRANE BARRIER

Fluid-applied, self-curing, synthetic rubber based, vapor-retarding membrane air and vapor barrier material, free of solvents, isocyanates and bitumen. Membrane shall have the following properties:

a. Cured Film Thickness, ASTM D 3767 , 40 mils minimum;

b. Solids Content: 60 percent minimum;

SECTION 07 15 00 Page 8

c. Extensibility After Heat Aging, ASTM C 836 : Pass. 2.3 COMPOSITE, SELF-ADHERING MEMBRANE BARRIER SHEETING

Self-adhering membrane composed of flexible facing material coated completely and uniformly on one side with adhesive material, formed into uniform flexible sheets, and with disposable release liner that is removed prior to application or membrane that adheres upon application of heat to the membrane surface. Provide sample of composite, self-adhering membrane barrier sheeting to Contracting Officer for approval. Materials shall meet the requirements indicated:

a. Thickness, ASTM D 3767 , 40 mils minimum;

b. Tensile Strength, ASTM D 412 , Die C: 250 psi minimum;

c. Ultimate Elongation, ASTM D 412 , Die C: 200 percent minimum;

d. Puncture Resistance, ASTM E 154 : 40 lb. minimum;

e. Lap Adhesion at Minimum Application Temperature, ASTM D 1876 Modified:

4.0 lbs/in. width.

2.4 ACCESSORY MATERIALS

2.4.1 Primers, Adhesives and Mastics

As required and recommended by the air and vapor barrier membrane manufacturer.

2.4.2 Sealants and Tapes

As required and recommended by the air and vapor barrier membrane manufacturer and capable of accommodating inherent movement while maintaining required performance, attachment, and seal to the connected components.

2.4.3 Counterflashing Stripping

Modified bituminous, minimum 30 mil thick, self-adhering sheet, ASTM D 1970 , of rubberized asphalt laminate to a 10 mil thick, crosslaminated polyethylene film with release liner backing. Provide for counterflashing seal of metal flashings.

2.4.4 Elastomeric Flashing Sheet

Neoprene or EPDM membrane, ASTM D 2000 , 2BC415 to 3BC620, minimum 40 mil, cured sheet neoprene with manufacturer's recommended contact adhesives and lap sealant with stainless-steel termination bars and fasteners.

2.4.5 Foam Sealant

One or two-component, foamed-in-place, polyurethane foam sealant; flame spread index of 25 or less in accordance with ASTM E 162 , with primer and noncorrosive substrate cleaner recommended by foam sealant manufacturer.

SECTION 07 15 00 Page 9

2.5 THERMAL BARRIER

Spray applied thin film aqueous base resin intumescent paint for use as a thermal and ignition barrier over spray polyurethane foam insulation. ICC approved 15 minute fire barrier paint.

PART 3 EXECUTION

3.1 VERIFICATION OF CONDITIONS

Before starting the work, verify that substrate surfaces are in satisfactory condition. Notify the Contracting Officer of defects or conditions that will prevent a satisfactory application. Do not start application until defects and conditions have been corrected.

3.2 EXAMINATION

Ensure that the following conditions are met:

a. Surfaces are sound, dry, even, and free of oil, grease, dirt, excess mortar or other contaminants that may affect application of air and vapor barrier materials.

b. Concrete surfaces are cured and dry, smooth without large voids, spalled areas or sharp protrusions.

c. Masonry joints are flush, and all excess mortar sitting on masonry ties has been removed.

d. Verify substrate is visibly dry and free of moisture.

e. Verify sealants used in sheathing are compatible with membrane proposed for use. Perform field peel-adhesion test on materials to which sealants are adhered.

f. Notify the Contracting Officer in writing of anticipated problems or issues with the substrates prior to proceeding.

3.3 PREPARATION

Coordinate work with that of other trades to ensure that components to be incorporated into the barrier system are available when needed. Inspect and approve surfaces immediately before application of barrier system materials. Clean, prepare, and treat substrate according to manufacturer's written instructions. Provide clean, dust-free, and dry substrate, unless otherwise recommended by the barrier manufacturer's appliction instructions. Remove laitance, loose aggregate, sharp projections, grease, oil, dirt, curing compounds, and other contaminants which could adversely affect the complete bonding of the barrier membrane materials to substrate surface.

3.3.1 Penetrations and Projections

Seal penetrations in accordance with barrier system manufacturer's requirements before application of air and vapor barrier system.

SECTION 07 15 00 Page 10

3.3.2 Cracks and Joints

Prepare visible cracks and joints in substrate to receive barrier membrane in accordance with the membrane manufacturer's requirements. Joints shall be prepared and sealed with flexible materials to accommodate joint movement.

3.3.3 Priming

Prime surfaces to receive barrier membrane materials as required by the material manufacturer's printed instructions.

3.3.4 Protection from Spray Applied Materials

Mask and cover adjacent areas to protect from over spray. Ensure any required foam stop or back up material are in place to prevent over spray and achieve complete seal. Seal off existing ventilation equipment.

Install temporary ducting and fans as necessary to remove required operational exhaust fumes. Provide for make-up air. Erect barriers, isolate area and post warning signs to advise non-protected personnel to avoid the spray area. 3.3.5 Materials Integrity

Protect materials during transport and application. Do not dilute primers and other materials, unless specifically recommended by materials manufacturer. Keep containers closed except when removing contents. Do not mix remains of unlike materials. Thoroughly remove residual materials before using application equipment for mixing and transporting materials.

Do not permit equipment on the project site that has residue of materials used on previous projects. Use cleaners only for cleaning, not for thinning primers or membrane materials.

3.4 APPLICATION

Follow manufacturer's printed installation instructions and additional requirements specified.

3.4.1 Transition Materials

Install transition materials to provide continuity throughout the building envelope. Install materials in accordance with manufacturer's recommendations and the following:

a. Apply primer for transition strips at rate recommended by manufacturer. Allow primer to dry completely before transition strip application. Apply as many coats as necessary for proper adhesion.

b. Position subsequent sheets of transition strips applied above so that membrane overlaps the membrane sheet below by a minimum of 2 inches, unless greater overlap is recommended by manufacturer. Roll into place with roller.

c. Overlap horizontally adjacent pieces of transition strips a minimum of 2 inches, unless greater overlap is recommended by manufacturer. Roll seams with roller.

d. Seal around all penetrations with a transition material or other procedure in accordance with manufacturer's recommendations.

e. Seal the barrier membrane in exterior wall assembly continuously to

SECTION 07 15 00 Page 11 the barrier conditions of the roof, to concrete below-grade structures, to windows, curtain wall, storefront, louvers, exterior doors, penetrations, and other intersection conditions using transition membranes and sealants and in accordance with the manufacturer's recommendations.

f. At changes in substrate plane, provide transition material recommended by manufacturer to make a smooth transition from one plane to another.

g. Provide mechanically fastened non-corrosive metal sheet to span gaps in substrate plane and to make a smooth transition from one plane to the other. Barrier membrane shall be continuously supported by substrate.

h. At through-wall flashings, provide an additional 6 inch wide strip of manufacturer's recommended membrane counterflashing to seal top of through-wall flashing to membrane. Seal exposed top edge of strip with bead of mastic as recommended by manufacturer.

i. At deflection and control joints, provide backup for the barrier membrane to accommodate anticipated movement.

j. At expansion and seismic joints provide transition to the joint assemblies.

k. Do not allow materials to come in contact with chemically incompatible materials.

l. Do not expose transition membrane to sunlight longer than as recommended by the manufacturer.

m. Inspect installation prior to enclosing transition areas and repair damaged areas with like materials as recommended by manufacturer.

3.4.2 Fluid-Applied Membrane Barrier

Over primed surfaces, provide a uniform, wet, monolithic coating of fluid-applied membrane in accordance with the manufacturer's printed instructions to provide for the at the required dry film thickness (DFT).

Apply material by trowel, squeegee, roller, brush, spray apparatus, or other method recommended by membrane material manufacturer. Check wet film thickness as specified in paragraph entitled "Film Thickness" and adjust application rate as necessary to provide a uniform coating of the thickness specified. Where possible, mark off surface to be coated in equal units to facilitate proper coverage. At expansion joints, control joints, prepared cracks, flashing, and terminations, carry membrane material over the prepared condition in the required uniform thickness to provide a monolithic coating and tie-in to the accessory seal material.

If membrane cures before next application, clean previously applied membrane in a manner recommended by the membrane material manufacturer to remove dirt, dust, and other contaminents that could inhibit adhesion of overlapping membrane coat.

3.4.2.1 Film Thickness

Measure wet film thickness every 500 square feet during application by placing flat metal plates on the substrate or using a mil-thickness gage

SECTION 07 15 00 Page 12 especially manufactured for the purpose. 3.4.3 Composite, Self-Adhering Membrane Barrier Sheeting

Apply composite, self-adhering membrane on surfaces primed at a uniform coverage rate in accordance with membrane manufacturer's printed instructions. Remove release sheet and apply with tacky surface in contact with dried primer. Avoid wrinkles and buckles in applying membrane and joint reinforcement. Lap sheets at edges and ends a minimum of 2-1/2 inches over the preceding sheet. All side laps shall be minimum 2-1/2 inches and end laps shall be 5 inches. Laps shall be made shingle fashion to shed water in the direction fo flow. Laps shall be self adhesive or mastic in accordance with the manufacturer's recommendation.

Roll or firmly press to adhere membrane to substrate and firmly seal laps. Cover corners and joints with two layers of reinforcement by first applying a 12 inch width of membrane centered along the axis. Flash projections with a second ply of membrane extending for a distance of not less than 6 inches from the projection. Finish exposed, terminated edges of membrane on horizontal surfaces with a trowelled bead of mastic.

Finish vertical joints similary when required by the membrane manufacturer's printed instructions or recommendations.

3.5 PROTECTION

Protection and repair is the Contactor's responsibility regardless of the assignment of responsibility for inspection, testing or sample taking and similar services. Protect air and vapor barrier assemblies from damage during application and remainder of construction period. Coordinate with installation of materials which cover the barrier, to ensure exposure period does not exceed that recommended by the barrier manufacturer.

Clean spillage and soiling from adjacent construction using cleaning agents and procedures recommended by manufacturer of affected construction and acceptable to the primary barrier material manufacturer. Repair damaged construction, or construction impacted by destructive or other testing and sampling, in a manner to meet specified requirements.

3.6 CORRECTION OF DEFICIENCIES

Where any form of deficiency is found, additional measures shall be taken as deemed necessary by the Contracting Officer to determine the extent of the deficiency. Corrective action shall be performed as recommended by the barrier membrane material manufacturer in a manner that complies with the full performance requirements specified and as approved by the Contracting Officer.

3.7 FIELD QUALITY CONTROL

3.7.1 Inspection and Construction Monitoring

Inspect the work to ensure compliance with specified requirements adn provide daily inspection report during the air and vapor barrier installation activity. Verfy the following:

a. Materials comply with the specified requirements.

b. Materials are not installed in adverse weather conditions nor temperatures beyond the application range specified or recommended by the barrier membrane manfuacturer.

SECTION 07 15 00 Page 13

c. All materials are properly stored, handled and protected from damage.

d. Application equipment is in working order. Metering devices are accurate.

e. Substrates are in acceptable condition, primed as appropriate, and in compliance with specification prior to application of subsequent materials.

f. Installer adheres to specified and detailed application parameters.

g. Ensure proper transitions for change in direction and structural support at gaps.

h. Ensure continuity of the air and vapor barrier system throughout the building enclosure and that all gaps are covered, the covering is structurally sound, and all penetrations are sealed.

i. Ensure structural support of the barrier system to withstand design air pressures.

j. Ensure masonry and concrete substrate surfaces are smooth, clean, and free of voids, protrusions and mortar droppings, with mortar joints struck flush.

k. Ensure laps in sheet materials are at least a 2-inch minimum, shingled in the correct direction to shed water.

l. Ensure that a roller has been used to enhance adhesion of adhered sheet membrane materials.

m. Ensure proper connection between assemblies (membrane and sealants) for cleaning, preparation and priming of surfaces, structural support, integrity and continuity of seal.

n. Measure application thickness of liquid applied materials to manufacturer's requirements for the specific substrate.

o. Temporary protection measures are in place at the end of each work shift.

3.8 PERFORMANCE VERIFICATION TESTING

3.8.1 Whole Building Air Leakage Test

A whole building air leakage test shall follow the guidance in the USACE-ALTP Air Leakage Test Protocol for Measuring Air Leakage in Buildings. This protocol is available on the Whole Building Design Guide website- http://www.wbdg.org/pdfs/usace_airleakagetestprotocol.pdf The fan pressurization test to determine final compliance with the airtightness requirement shall be conducted when all components of the air barrier system have been installed and inspected, and have passed any intermediate testing procedures as detailed in the construction drawings and specifications. The test may be conducted before finishes that are not part of the air barrier system have been installed. For example, if suspended ceiling tile, interior gypsum board, or cladding systems are not part of the air barrier system, the test may be conducted before they are installed.

SECTION 07 15 00 Page 14

3.8.1.1 Test Requirements

The whole building air leakage test must be performed in accordance with ASTM E 779 with the following additions and exceptions:

The test consists of measuring the flow rates required to establish a minimum of 12 positive and 12 negative building pressures. The lowest test pressure shall be 0.50 psf (25 Pa); the highest test pressure shall be 1.57 psf (75 Pa); and there must be at least 0.50 psf (25 Pa) difference between the lowest and highest test pressures.

The test pressure must be measured in a representative location such that pressures in the extremities of the enclosure can be shown to not exceed 10% of the measured test pressure. At least 12 bias pressure readings must be taken across the envelope and averaged over at least 20 seconds each before and after the flow rate measurements. None of the bias pressure readings must exceed 30 percent of the minimum test pressure when testing in both directions.

Where it can be shown that it is impossible to test in both directions, then the building may be tested in the positive direction only, provided the bias pressure does not exceed 10 percent of the minimum test pressure.

The mean value of the air leakage flow rate calculated from measured data at 1.57 psf or 0.3 in wg (75 Pa) must not exceed 0.25 cfm/ft2 of envelope area with an upper confidence limit as defined by ASTM E 779 not exceeding 0.27 cfm/ft2 based upon a confidence interval of +0.02 cfm/ft2; should the confidence interval exceed +0.02 cfm/ft2 the upper confidence limit may not exceed 0.25 cfm/ft2 (75 Pa). Measurements must be referenced at standard conditions of 14.70 psi (101.33 KPa) and 68F (20C). The envelope area is to be supplied and/or confirmed by the Designer of Record (DOR).

The test shall be conducted with ventilation fans and exhaust fans turned off and the outdoor air inlets and exhaust outlets sealed (by dampers or masking). The contractor must provide a responsible HVAC technician with the authority to place the HVAC system in the correct mode for the pressure test. The test technician must have unhindered access to mechanical rooms, air handlers, exhaust fans, and outdoor air and exhaust dampers.

The contractor must ensure that all windows in the enclosure are kept closed. Entry and exit through doors in the test enclosure must be prohibited during the test. Data collected while the pressures and flows are affected by a door opening and closing shall be discarded.

The testing agency is required to perform a diagnostic evaluation in accordance with ASTM E 1186 , whether the building achieves the air tightness requirement or not. The diagnostic evaluation will assist the contractor and responsible parties in identifying and eliminating air leakage so the building meets the requirement upon retesting. The testing results will also be expressed in terms of the Equivalent Leakage Area (EqLA) at 1.57 psf (75 Pa). The EqLA is a the equivalent area of a flat plate that leaks the same amount as the building envelope at 1.57 psf (75 Pa).

SECTION 07 15 00 Page 15

3.8.2 Thermography Test

The building envelope shall be tested using Infrared Thermography technology. The thermography testing shall be completed in accordance with the requirements of ASTM C 1060 , ASTM E 1186 , and ISO 6781 . The Contracting Officer shall witness the testing. Testing shall occur just before the building airtightness test. Testing shall also occur during the airtightness test so that areas of building air leaks are detected.

If the building air tightess test is failed, Thermographic testing shall be repeated just before and during subsequent airtightness tests until the airtightness test is successful. The contractor shall provide a report.

The report shall include thermographs in color and a color temperature scale to define the temperature indicated by the various colors. The report shall identify the high temperature reading, the outdoor air temperature, the building indoor air temperature, and the wind speed and direction. The report shall note any areas of compromise in the building envelope, and shall note all actions required and taken to correct those areas. Final thermography test report shall demonstrate the problem areas have been corrected. The complete test and analysis will be submitted to the Government for review and approval.

3.8.3 Bond Adhesion Strength Test

Test for bond adhesion pull-off strength of fluid-applied or sheet-applied barrier membrane in accordance with ASTM D 4541 . Minimum acceptable bond adhesion pull-off strength shall be as stated in the barrier membrane manufacturer's product data for the substrate to which applied. In the absence of manufacturer's data the minimum bond strength shall be the minimum specified. Test bond strength after the adhesive bond set time recommended by the barrier membrane manufacturer. Bond strength shall be tested on each day's application and as follows: a minimum of one bond adhesion test shall be performed on each wall section length of less than 100 feet; two bond adhesion tests for wall section lengths of 100 to 200 feet in length; For walls sections longer than 200 feet, conduct a minimum of one bond adhesion test at 50 feet to 75 feet intervals.

Location of testing shall be as selected by the Contracting Officer. Bond failure strength shall be compared to the manufacturer's indicated adhesion strength for the substrate. Failed test shall result in a second test of the application in another selected area of the same wall section. Any failures shall be investigated by the Contractor to determine the reason for failure and corrective action to remedy failures and prevent further failures shall be taken. All test areas shall be repaired by the Contractor.

3.9 INVESTIGATION OF CAUSE OF FAILED TESTS

The Contractor shall investigate the cause of failed air leakage tests.

The air and vapor barrier inspector shall assist with the investigation.

Procedures outlined in ASTM E 1186 (infrared scanning, smoke tracer, tracer gas, etc.) shall be implemented to assist in determining the air leakage locations. Cause shall be determined and included in the report to the Contracting Officer. Repairs shall be made and testing repeated until the required airtightness is achieved.

-- End of Section --

SECTION 07 15 00 Page 16

SECTION 07 21 16

MINERAL FIBER BLANKET INSULATION

11/11

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

ASTM INTERNATIONAL (ASTM)

ASTM C665 (2012) Mineral-Fiber Blanket Thermal Insulation for Light Frame Construction and Manufactured Housing

ASTM C930 (2012) Potential Health and Safety Concerns Associated with Thermal Insulation Materials and Accessories

ASTM D3575 (2008) Flexible Cellular Materials Made From Olefin Polymers

ASTM D3833/D3833M (1996; R 2011) Water Vapor Transmission of Pressure-Sensitive Tapes

ASTM D4397 (2010) Standard Specification for Polyethylene Sheeting for Construction, Industrial, and Agricultural Applications

ASTM E136 (2012) Behavior of Materials in a Vertical Tube Furnace at 750 Degrees C

ASTM E84 (2013a) Standard Test Method for Surface Burning Characteristics of Building Materials

ASTM E96/E96M (2012) Standard Test Methods for Water Vapor Transmission of Materials

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 211 (2013) Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances

NFPA 31 (2011) Standard for the Installation of Oil-Burning Equipment

NFPA 54 (2012) National Fuel Gas Code

NFPA 70 (2014) National Electrical Code

SCIENTIFIC CERTIFICATION SYSTEMS (SCS)

SCS Scientific Certification Systems

SECTION 07 21 16 Page 1

(SCS)Indoor Advantage

TECHNICAL ASSOCIATION OF THE PULP AND PAPER INDUSTRY (TAPPI)

TAPPI T803 OM (2010) Puncture Test of Container Board

U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

29 CFR 1910.134 Respiratory Protection

UL ENVIRONMENT (ULE)

ULE Greenguard UL Greenguard Certification Program

1.2 SUBMITTALS

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. The following shall be submitted in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-03 Product Data

Blanket insulation

Sill sealer insulation

Vapor retarder

Pressure sensitive tape

Accessories

Certification

SD-08 Manufacturer's Instructions

Insulation

1.3 SUSTAINABLE DESIGN CERTIFICATION

Product shall be third party certified in accordance with ULE Greenguard , SCS Scientific Certification Systems Indoor Advantageor equal.

Certification shall be performed annually and shall be current.

1.4 DELIVERY, STORAGE, AND HANDLING

1.4.1 Delivery

Deliver materials to site in original sealed wrapping bearing manufacturer's name and brand designation, specification number, type, grade, R-value, and class. Store and handle to protect from damage. Do not allow insulation materials to become wet, soiled, crushed, or covered with ice or snow. Comply with manufacturer's recommendations for handling, storing, and protecting of materials before and during installation.

SECTION 07 21 16 Page 2

1.4.2 Storage

Inspect materials delivered to the site for damage; unload and store out of weather in manufacturer's original packaging. Store only in dry locations, not subject to open flames or sparks, and easily accessible for inspection and handling.

1.5 SAFETY PRECAUTIONS

1.5.1 Respirators

Provide installers with dust/mist respirators, training in their use, and protective clothing, all approved by National Institute for Occupational Safety and Health (NIOSH)/Mine Safety and Health Administration (MSHA) in accordance with 29 CFR 1910.134 .

1.5.2 Smoking

Do not smoke during installation of blanket thermal insulation.

1.5.3 Other Safety Concerns

Consider other safety concerns and measures as outlined in ASTM C930.

PART 2 PRODUCTS

2.1 BLANKET INSULATION

ASTM C665, Type I, blankets without membrane coverings and II, blankets with non-reflecting coverings ; Class B, membrane-faced surface with a flame propagation resistance; critical radiant flux of 0.11 Btu/ft2 or greater, except a flame spread rating of 25 or less and a smoke developed rating of 150 or less when tested in accordance with ASTM E84.

2.1.1 Thermal Resistance Value (R-VALUE)

As indicated

2.1.2 Recycled Materials

Provide Thermal Insulation containing recycled materials to the extent practicable, provided the material meets all other requirements of this section. The minimum required recycled materials content by weight are:

Rock Wool: 75 percent slag Fiberglass: 20 to 25 percent glass cullet

2.1.3 Prohibited Materials

Do not provide asbestos-containing materials.

2.2 SILL SEALER INSULATION

Provide polyethylene foam sill sealer to fit the width of the sill with the following characteristics:.

SECTION 07 21 16 Page 3

Physical Properties Test Method Measurement

Nominal Thickness ASTM D3575 3/16 inch

Compressive Strength ASTM D3575 1.2 psi

- Vertical Direction Suffix D

Tensile Strength ASTM D3575 32 psi

Suffix T

2.3 BLOCKING

Wood, metal, unfaced mineral fiber blankets in accordance with ASTM C665, Type I, or other approved materials.

This is the start of the file's text. The full file is on GovTribe.