am_4.pdf
PDF 5 MB Posted
- Attached to
- DLA General Purpose Warehouse Federal contract opportunity
- Solicitation number
- W9126G-18-R-0135
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Clarifications.docx | DOCX document | |
| BI_Responses.pdf | ||
| Site_Visit_Attendees.pdf | ||
| am_3.pdf | ||
| g18r0135_RFP_Final_v3.pdf | ||
| DLA_RRAD_GPW_RTA_Drawings_2017-10-05_Part3.pdf | ||
| DLA_RRAD_GPW_RTA_Drawings_2017-10-05_Part4.pdf | ||
| g18r0135_RFP_Final_v2.pdf | ||
| DLA_RRAD_GPW_RTA_Drawings_2017-10-05_Part1.pdf | ||
| DLA_RRAD_GPW_RTA_Drawings_2017-10-05_Part2.pdf | ||
| g18r0135_RFP_Final.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04 EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
The Solicitation for DLA General Purpose Warehouse; Red Rive Army depot, Texas is amended as follows.
See SF30 Continuation Sheet(s)
NOTE: Proposal Receipt date is 25 January 2017; at 11:00 a.m.,CST, as previously announced.
1. CONTRACT ID CODE PAGE OF PAGES
J 1 2
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY
16B. UNITED STATES OF AMERICA 15C. DATE SIGNED 15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer) (Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X 9A. AMENDMENT OF SOLICITATION NO.
W912618R0135
X 9B. DATED (SEE ITEM 11)
08-Dec-2017
10B. DATED (SEE ITEM 13)
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
24 -Jan-2018
CODE
US ARMY ENGINEER DISTRICT, FORT WORTH
ATTN: CESWF-CT
819 TAYLOR ST, ROOM 2A19
P.O. BOX 17300
FORT WORTH TX 76102-0300
W9126G 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODE CODE
EMAIL: TEL:
W9126G18R0135
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
CHANGES TO SOLICITATION W9126G18R0135
CHANGES TO THE SPECIFICATIONS
1. New Sections - Add the following accompanying new sections, each bearing the notation W9126G17R0135.
07 81 23 INTUMESCENT FIREPROOFING
2. Deletion of Sections – The following section has been removed from the solicitation.
07 81 00 SPRAY-APPLIED FIREPROOFING
CHANGES TO THE DRAWINGS
3. Replacement Drawings.- Replace the drawings listed below with the attached new drawings(s) of the same number, W9126G18R0135.
C-502 CIVIL DETAILS II
C-503 CIVIL DETAILS III
End of Summary of Changes
DLA General Purpose Warehouse (GPW)
Red River Army Depot, TX
SECTION 078123 - INTUMESCENT FIREPROOFING
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASSOCIATION OF THE WALL AND CEILING INDUSTRY (AWCI)
AWCI TM 12-A (1997; 3rd Ed) Standard Practice for the
Testing and Inspection of Field Applied
Sprayed Fire-Resistive Materials; An
Annotated Guide
1.2 SUMMARY
A. Section includes mastic and intumescent fire-resistive coatings.
B. Related Requirements:
1. Section 078100 "Applied Fireproofing" for sprayed fire-resistive materials (SFRM).
1.3 PREINSTALLATION MEETINGS
A. Preinstallation Conference: Conduct conference at Project site.
1. Review products, design ratings, restrained and unrestrained conditions, thicknesses, and other performance requirements.
1.4 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Sustainable Design Submittals:
1. Product Data for Credit EQ c4.2: Low emitting materials – Adhesives and sealants, documentation including printed statement of VOC content
2. VOC content: 0 g/L according to EPA method 24
C. Shop Drawings: Framing plans or schedules, or both, indicating the following:
SECTION 07 81 23 Page 1
W9126G18R0135, AMENDMENT 0004
1. Extent of fireproofing for each construction and fire-resistance rating.
2. Applicable fire-resistance design designations of a qualified testing and inspecting agency acceptable to authorities having jurisdiction.
3. Minimum fireproofing thicknesses needed to achieve required fire-resistance rating of each structural component and assembly.
4. Treatment of fireproofing after application.
D. Samples: For each exposed product and for each color and texture specified, 4 inches square in size.
1.5 INFORMATIONAL SUBMITTALS
A. Qualification Data: For Installer and testing agency.
B. Product Certificates: For each type of fireproofing.
C. Evaluation Reports: For fireproofing, from ICC-ES.
D. Field quality-control reports.
1.6 QUALITY ASSURANCE
A. Installer Qualifications: A firm or individual certified, licensed, or otherwise qualified by fireproofing manufacturer as experienced and with sufficient trained staff to install manufacturer's products according to specified requirements.
B. Mockups: Build mockups to verify selections made under Sample submittals and to demonstrate aesthetic effects and to set quality standards for materials and execution.
1. Build mockup of fireproofing and substrate and finish as shown on Drawings.
2. Approval of mockups does not constitute approval of deviations from the Contract
Documents contained in mockups unless Architect specifically approves such deviations in writing.
3. Subject to compliance with requirements, approved mockups may become part of the completed Work if undisturbed at time of Substantial Completion.
1.7 FIELD CONDITIONS
A. Environmental Limitations: Do not apply fireproofing when ambient or substrate temperature is
50 deg F or lower unless temporary protection and heat are provided to maintain temperature at or above this level for 24 hours before, during, and for 24 hours after product application.
B. Ventilation: Ventilate building spaces during and after application of fireproofing, providing complete air exchanges according to manufacturer's written instructions. Use natural means or, if they are inadequate, forced-air circulation until fireproofing dries thoroughly.
SECTION 07 81 23 Page 2
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Assemblies: Provide fireproofing, including auxiliary materials, according to requirements of each fire-resistance design and manufacturer's written instructions.
B. Source Limitations: Obtain fireproofing from single source.
C. Fire-Resistance Design: Indicated on Drawings, tested according to ASTM E 119 or UL 263;
testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.
1. Steel members are to be considered unrestrained unless specifically noted otherwise.
D. Asbestos: Provide products containing no detectable asbestos.
2.2 MASTIC AND INTUMESCENT FIRE-RESISTIVE COATINGS
A. Mastic and Intumescent Fire-Resistive Coating (for square steel columns to provide 2 hours fire resistive protection; for steel columns dimensions refer to structural drawings) UL-design number ANSI/UL 263 BXUV. Manufacturer's standard, factory-mixed formulation or factory-mixed, multicomponent system consisting of intumescent base coat and topcoat, and complying with indicated fire-resistance design.
1. Application: Designated for "interior general purpose" use by a qualified testing agency acceptable to authorities having jurisdiction.
2. Thickness: As required for fire-resistance design indicated, measured according to requirements of fire-resistance design.
3. Surface-Burning Characteristics: Comply with ASTM E 84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.
a. Flame-Spread Index: 0.
b. Smoke-Developed Index: 50 or less.
4. Hardness: Not less than 80, Type D durometer, according to ASTM D 2240.
5. Finish: As selected by Contracting Officer from manufacturer's standard finishes
a. Color and Gloss: As selected by Contracting Officer from manufacturer's full range.
2.3 AUXILIARY MATERIALS
A. General: Provide auxiliary materials that are compatible with fireproofing and substrates and are approved by UL or another testing and inspecting agency acceptable to authorities having jurisdiction for use in fire-resistance designs indicated.
SECTION 07 81 23 Page 3
B. Substrate Primers: Primers approved by fireproofing manufacturer and complying with required fire-resistance design by UL or another testing and inspecting agency acceptable to authorities having jurisdiction.
C. Reinforcing Fabric: Glass- or carbon-fiber fabric of type, weight, and form required to comply with fire-resistance designs indicated; approved and provided by fireproofing manufacturer.
D. Reinforcing Mesh: Metallic mesh reinforcement of type, weight, and form required to comply with fire-resistance design indicated; approved and provided by fireproofing manufacturer.
Include pins and attachment.
E. Topcoat: Suitable for application over applied fireproofing; of type recommended in writing by fireproofing manufacturer for each fire-resistance design.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates, areas, and conditions, with Installer present, for compliance with requirements for substrates and other conditions affecting performance of the Work and according to each fire-resistance design.
1. Verify that substrates are free of dirt, oil, grease, release agents, rolling compounds, mill scale, loose scale, incompatible primers, paints, and encapsulants, or other foreign substances capable of impairing bond of fireproofing with substrates under conditions of normal use or fire exposure.
2. Verify that objects penetrating fireproofing, including clips, hangers, support sleeves, and similar items, are securely attached to substrates.
3. Verify that substrates receiving fireproofing are not obstructed by ducts, piping, equipment, or other suspended construction that will interfere with fireproofing application.
B. Conduct tests according to fireproofing manufacturer's written instructions to verify that substrates are free of substances capable of interfering with bond.
C. Prepare written report, endorsed by Installer, listing conditions detrimental to performance of the Work.
D. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Cover other work subject to damage from fallout or overspray of fireproofing materials during application.
B. Clean substrates of substances that could impair bond of fireproofing.
SECTION 07 81 23 Page 4
C. Prime substrates where included in fire-resistance design and where recommended in writing by fireproofing manufacturer unless compatible shop primer has been applied and is in satisfactory condition to receive fireproofing.
D. For applications visible on completion of Project, repair substrates to remove surface imperfections that could affect uniformity of texture and thickness in finished surface of fireproofing. Remove minor projections and fill voids that would telegraph through fire-resistive products after application.
3.3 APPLICATION
A. Construct fireproofing assemblies that are identical to fire-resistance design indicated and products as specified, tested, and substantiated by test reports; for thickness, primers, topcoats, finishing, and other materials and procedures affecting fireproofing work.
B. Comply with fireproofing manufacturer's written instructions for mixing materials, application procedures, and types of equipment used to mix, convey, and apply fireproofing; as applicable to particular conditions of installation and as required to achieve fire-resistance ratings indicated.
C. Coordinate application of fireproofing with other construction to minimize need to cut or remove fireproofing.
1. Do not begin applying fireproofing until clips, hangers, supports, sleeves, and other items penetrating fireproofing are in place.
2. Defer installing ducts, piping, and other items that would interfere with applying fireproofing until application of fireproofing is completed.
D. Install auxiliary materials as required, as detailed, and according to fire-resistance design and fireproofing manufacturer's written instructions for conditions of exposure and intended use. For auxiliary materials, use attachment and anchorage devices of type recommended in writing by fireproofing manufacturer.
E. Spray apply fireproofing to maximum extent possible. After the spraying operation in each area, complete the coverage by trowel application or other placement method recommended in writing by fireproofing manufacturer.
F. Extend fireproofing in full thickness over entire area of each substrate to be protected.
G. Install body of fireproofing in a single course unless otherwise recommended in writing by fireproofing manufacturer.
H. Provide a uniform finish complying with description indicated for each type of fireproofing material and matching finish approved for required mockups.
I. Cure fireproofing according to fireproofing manufacturer's written instructions.
J. Do not install enclosing or concealing construction until after fireproofing has been applied, inspected, and tested and corrections have been made to deficient applications.
SECTION 07 81 23 Page 5
K. Finishes: Where indicated, apply fireproofing to produce the following finishes:
1. Manufacturer's Standard Finishes: Finish according to manufacturer's written instructions for each finish selected.
2. Spray-Textured Finish: Finish left as spray applied with no further treatment.
3. Rolled, Spray-Textured Finish: Even finish produced by rolling spray-applied finish with a damp paint roller to remove drippings and excessive roughness.
3.4 FIELD QUALITY CONTROL
A. Special Inspections: Contractor shall engage a qualified special inspector to perform the following special inspections:
1. Test and inspect as required by the IBC, Subsection 1705.14, "Mastic and Intumescent
Fire-Resistant Coatings".
B. Perform the tests and inspections of completed Work in successive stages. Do not proceed with application of fireproofing for the next area until test results for previously completed applications of fireproofing show compliance with requirements. Tested values must equal or exceed values as specified and as indicated and required for approved fire-resistance design.
C. Fireproofing will be considered defective if it does not pass tests and inspections.
1. Remove and replace fireproofing that does not pass tests and inspections, and retest.
2. Apply additional fireproofing, per manufacturer's written instructions, where test results indicate insufficient thickness, and retest.
D. Prepare test and inspection reports.
3.5 CLEANING, PROTECTING, AND REPAIRING
A. Cleaning: Immediately after completing spraying operations in each containable area of Project, remove material overspray and fallout from surfaces of other construction and clean exposed surfaces to remove evidence of soiling.
B. Protect fireproofing, according to advice of manufacturer and Installer, from damage resulting from construction operations or other causes, so fireproofing is without damage or deterioration at time of Substantial Completion.
C. As installation of other construction proceeds, inspect fireproofing and repair damaged areas and fireproofing removed due to work of other trades.
D. Repair fireproofing damaged by other work before concealing it with other construction.
E. Repair fireproofing by reapplying it using same method as original installation or using manufacturer's recommended trowel-applied product.
END OF SECTION 07 81 23
SECTION 07 81 23 Page 6
| AMENDMENT 0004 |
| SUMMARY OF CHANGES |
| 07 81 23 INTUMESCENT FIREPROOFING |
| C-502 CIVIL DETAILS II |
| C-503 CIVIL DETAILS III |
File details come from the government source that posted it.