Technical Exhibit 7.5.9.6 Bureau of Mine Standards for Water Treatment name
HEATING AND COOLING PLANTS
BUREAU OF MINE STANDARDS FOR WATER TREATMENT
Item # TESTS BOILER WATER RANGES
1 Tannin Color Light to Medium
2 Hydroxide (OH) (Causticity) 20 TO 200 parts per million
3 Sulfite (S04) 30 to 40 parts per million
4 Phosphate (P04) 30 to 60 parts per million
5 Phosphate, minimum required For scaling control 30 parts per million
6 Dissolved Solids by Conductivity 1,000 to 4,000 parts per million
&14Attachment J- C5.9 06 Bureau of Mine Standards for Water Treatment
&11&F FOUO - Source Selection Sensitive - See FAR 2.101 and FAS 3.104 &11PAGE &P of &N