Updated_Drawings_Basewide_HVAC_Amend_0001.pdf
PDF 2 MB Posted
- Attached to
- Basewide HVAC Construction Federal contract opportunity
- Solicitation number
- W9124318B0001
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| W9124319C0001_HVAC_AWARD.pdf | ||
| Amendment_0002.released.pdf | ||
| Amendment_W91243-18-B-0001-0001.pdf | ||
| Updated_Specifications_Basewide_HVAC_Amend_0001.pdf | ||
| Basewide_HVAC_Site_Visit_Pictures_FBO_Post.docx | DOCX document | |
| Basewide_HVAC_Pre-Bid_Site_Visit_Sign_in_Roster_12Sep18.pdf | ||
| PreBidConferenceB0001.pdf | ||
| W9124318B0001.released.pdf | ||
| z_Repair_HVAC_Basewide_Drawings_B3.pdf | ||
| SPEC_Section_010000_-_NGCB_15-2603.pdf | ||
| NGCB_15-2603_-_AF_Form_66.pdf | ||
| z_Specifications_NEANG__Repair_HVAC_Basewide.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in
Acrobat X or Adobe Reader X, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader
5421 3 6 7 8 9 10 11 12 13
A
B
C
D
E
F
G
H
T
10x10 SA
10x10 SA 12x12 SA
14x12 SA
10x10 RA
8 Ø SA
12x8 EA 8x8 EA
10x8 EA
8x6 EA
12x12 SA 10x10 SA 6 Ø SA
18x14 SA
20x12 RA
12x6 SA
8x6 SA
10x6 SA
18x12 RA
10 Ø SA
16x12 SA
18x12 SA 16x14 SA
14 Ø SA
6x8 EA
20x14 SA
18x10 SA
12 Ø SA
18x12 SA16x12 SA
10x12 SA
(TYP.)
(E) FPB
(E) CU
RL/SRL/S
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
J
K
L
M
N
P
IS
R
W
IN
V
IL
Y
S
O
U
JE
IT
'S
IO
IC
IB
IA
X
IG
PROJECT NO.:
o
IP
s e r s
\m b c k m a n
\D u ts \0
-M c
.r v t
/1
/2
:0
:4
M0-09
IR
th
, N
06565.006
LB
TM
/3
0/
1 8
ID
/4 d d e n
REF. DEMO NOTES ( ):X
1 DEMOLISH EXISTING SPACE TEMPERATURE SENSOR AND ASSOCIATED
CONTROL WIRING.
2 DEMOLISH EXISTING CONDENSING UNIT, ASSOCIATED REFRIGERANT
PIPING, AND EXISTING CONDENSING UNIT CONTROLS AND CONTROL
WIRING. REMOVE EXISTING HOUSEKEEPING PAD AND PREPARE AREA
FOR INSTALLATION OF NEW PAD.
3 PROVIDE NEW CONTROLS FOR EXISTING FAN POWERED BOX. CONTROLS
TO BE COMPATIBLE WITH EXISTING JCI METASYS BMS PRESENT ON THE
BASE.
SCALE: 1/8" = 1'-0"
2500 - FIRST FLOOR PLAN - DEMOLITION HVAC
TRUE
NORTH
I
IF
IE
Z
-1
Sheets
M0-09 - BUILDING 2500 FIRST FLOOR DEMOLITION PLAN - MECHANICAL
M0-10 - BUILDING 2500 SECOND FLOOR DEMOLITION PLAN - MECHANICAL
M1-02 - BUILDING 608 FLOOR PLANS - HVAC
M1-04 - BUILDING 636 FLOOR PLANS - HVAC
M1-05 - BUILDING 636 MEZZANINE PLAN - HVAC
M1-09 - BUILDING 2500 FIRST FLOOR PLAN - HVAC
M1-10 - BUILDING 2500 SECOND FLOOR PLAN - HVAC
M5-01 - MECHANICAL SCHEDULES
6 Ø SA 10x6 SA
6 Ø SA 8x6 EA
6 Ø SA
12x8 RA
8x8 SA
8 Ø SA8 Ø SA
10x16 SA
16x8 RA
18x16 SA 22x22 SA
18x14 RA
16x24 RA 24x24 RA 36x20 RA
16 Ø OA
20 Ø OA22 Ø OA
26 Ø OA
40x24 OA
12x10 SA
10x10 SA 8 Ø SA
16x14 RA
24x24 RA
(E) EF
(E) AHU
(E) MAU
24x30 RA
(E) H
HWS/RHWS/R
c
:5
M0-10 d e n
2500 - SECOND FLOOR PLAN - DEMOLITION HVAC
REF. DEMO NOTES ( ):X
1 DEMOLISH EXISTING FAN POWERED BOX CONTROLS AND CONTROL
WIRING. EXISTING FAN POWERED BOX TO REMAIN AND BE REUSED.
2 DEMOLISH EXISTING SPACE TEMPERATURE SENSOR AND ASSOCIATED
CONTROL WIRING.
3 DEMOLISH EXISTING AIR HANDLING UNIT AND MIXING BOX. DISCONNECT
EXISTING SUPPLY AND RETURN DUCTWORK, AND EXISTING HEATING HOT
WATER PIPING, AND PREPARE FOR REUSE AS REQUIRED. DEMOLISH
EXISTING AIR HANDLING UNIT CONTROLS AND CONTROL WIRING.
Sheets
M0-09 - BUILDING 2500 FIRST FLOOR DEMOLITION PLAN - MECHANICAL
M0-10 - BUILDING 2500 SECOND FLOOR DEMOLITION PLAN - MECHANICAL
M1-02 - BUILDING 608 FLOOR PLANS - HVAC
M1-04 - BUILDING 636 FLOOR PLANS - HVAC
M1-05 - BUILDING 636 MEZZANINE PLAN - HVAC
M1-09 - BUILDING 2500 FIRST FLOOR PLAN - HVAC
M1-10 - BUILDING 2500 SECOND FLOOR PLAN - HVAC
M5-01 - MECHANICAL SCHEDULES
-21 EQUIPMENT101
PARTS &
ROOM
UTILITY
STORAGE
EQUIPMENT
-21 OFFICE
BATTERY ROOM
MAIN WORK BAY
TOOL ROOM
MECHANICAL
MEN
A.G.E. OFFICE
POWERED &
CLASSROOM
NON-POWERED
H G F E D C B A
AHU-1-608
CU-1-608
CU-2-608
1 1/2"
HWS/R
1 1/2"
HWS/R
3/4"3/4" HWS/R3/4"3/4" HWS/R
BCU-1-608
IH-1-6086
EH-1-608 7
(ON ROOF)
c
M1-02 d e n
REF. NOTES ( ):X
1 INSTALL NEW AIR HANDLER IN EXISTING MECHANICAL ROOM. SUPPORT
AIR HANDLER WITH ALL THREAD ROD AND SPRING HANGERS FROM
STRUCTURE ABOVE. CONNECT REFRIGERANT PIPING FROM CONDENSING
UNIT AND HEATING HOT WATER PIPING. SEE DETAILS FOR HYDRONIC COIL
CONNECTION. PROVIDE 3/4" CONDENSATE DRAIN TO EXISTING FLOOR
DRAIN IN MECHANICAL ROOM. WHEN AIR HANDLER IS INSTALLED,
REPLACE BOILER COMBUSTION AIR PIPING AND HEATING HOT WATER
PIPING AT BACK OF BOILERS, AND ANY OTHER PIPING OR SPECIALTIES
THAT WERE REMOVED TO FACILITATE DEMOLITION AND INSTALLATION.
2 INSTALL NEW CONDENSING UNIT ON NEW 4" CONCRETE HOUSEKEEPING
PAD. ANCHOR CONDENSING UNIT TO HOUSEKEEPING PAD.
3 PROVIDE NEW SPACE TEMPERATURE SENSOR FOR SYSTEM.
TEMPERATURE SENSOR TO BE COMPATIBLE WITH EXISTING JCI METASYS
BMS PRESENT ON THE BASE. TEMPERATURE SENSOR TO BE LARGE
ENOUGH TO COVER EXISTING HOLE IN WALL AT EACH LOCATION.
4 PROVIDE DUCT CLEANING AND PRESSURE TESTING OF EXISTING
DUCTWORK PRIOR TO CONNECTION TO NEW EQUIPMENT AND BEFORE
DUCTWORK IS BROUGHT BACK INTO SERVICE. REPAIR EXISTING
INSULATION AS REQUIRED AFTER CLEANING AND PRESSURE TESTING.
5 INSTALL NEW BLOWER COIL UNIT ABOVE EXISTING CEILING. CONNECT
NEW BLOWER COIL TO EXISTING SUPPLY, RETURN, AND OUTDOOR AIR
DUCTWORK AS REQUIRED. SUSPEND BLOWER COIL UNIT WITH ALL
THREAD ROD AND SPRING HANGERS FROM STRUCTURE ABOVE.
CONNECT REFRIGERANT PIPING FROM CONDENSING UNIT AND HEATING
HOT WATER PIPING. SEE DETAILS FOR HYDRONIC COIL CONNECTION.
PROVIDE CONDENSATE DRAIN TO NEAREST FLOOR DRAIN OR MOP/FLOOR
SINK.
6 FULL SIZE OA DOWN FROM INTAKE HOOD ON ROOF. PROVIDE PARALLEL
BLADE MOTORIZED DAMPER IN DUCT RISER, COORDINATE WITH
ELECTRICAL.
7 FULL SIZE EA UP TO EXHAUST HOOD ON ROOF. INSURE 10'-0" RADIAL
SEPARATION FROM ALL OTHER ROOF EQUIPMENT OR VENTS. PROVIDE
PARALLEL BLADE MOTORIZED DAMPER (SHOWN IN RUN FOR SCHEMATIC
CLARITY) IN DUCT RISER, COORDINATE WITH ELECTRICAL.
8 PROVIDE PIPE RACK OVER EXISTING SIDEWALK FOR REFRIGERANT
PIPING.
NORTHSCALE: 1/8" = 1'-0"
608 - FIRST FLOOR PLAN - HVAC
Sheets
M0-09 - BUILDING 2500 FIRST FLOOR DEMOLITION PLAN - MECHANICAL
M0-10 - BUILDING 2500 SECOND FLOOR DEMOLITION PLAN - MECHANICAL
M1-02 - BUILDING 608 FLOOR PLANS - HVAC
M1-04 - BUILDING 636 FLOOR PLANS - HVAC
M1-05 - BUILDING 636 MEZZANINE PLAN - HVAC
M1-09 - BUILDING 2500 FIRST FLOOR PLAN - HVAC
M1-10 - BUILDING 2500 SECOND FLOOR PLAN - HVAC
M5-01 - MECHANICAL SCHEDULES
CORRIDOR
LSP
BREAK
REFUELER
BAYS
FIRE TRUCK
BAYS
VEHICLE
REPAIR/LUB
BATTERY
SHOP
INDUSTRIAL
SHOP
LUBE BAY
VEST.
SUPER
CONTROL
MAT'L
CONTROL
TOOLS &
BENCH STORAGE
WOMENS
WOMENS
LOCKERS
VM
LOCKER
COMM.
ELEC.
MECH.
SHOWER
MENS
SP MENS
LOCKER
VEST
CLASSROOM
CHIEF
1ST
SGT
CSC
ATOEXEC.
C.O.
FLIGHT
CHIEF
CORR.
ADMIN/ WAITING
ELEC.
TRAINING MGR.
TESTING
QUALITY CONTROL
EXPANDED
WEAPONS
CLEAN
NCOIC
PM
SEC
STOR.
CATM CLASSROOM/
BREAK
1 2 3 4 5 6 7 8 9 11 12
108.74
SF
24x36 25x15 x
36x24
12 Ø
6 Ø
10 Ø
8 Ø
7 Ø
20 Ø 14 Ø 14 Ø
48x12
16 Ø
22x22
22x10
14x14
20x12
10x6
10x8
36x15
12x8 10 Ø
12x8
14 Ø 26x18 12x6
26x18
30x20
12x12
14 Ø
60x48
14x12
12x4
22x10
20 Ø
10 Ø10 Ø
6x6
6x6
30x26
30x36 30x28 30x28
24x24 20x20
18 Ø
16x1612x10
80x20
16x12
14x10
12x10
10x12
15x15 14x14
28x20
16x16
22x8
14x8
10x14
18x16
22 Ø 9x9
9x9
28 Ø
32 Ø
44x22
28 Ø
60x36
48x34
12 Ø 12 Ø
28 Ø 20 Ø
18x16
36x24
16x16
36x20
16x14
12x10 8x8
12x10
12x10 12x8
8x812x6
8x12
8 Ø12x8
6x5
6x5
12x18
(E) AC
(E) ERU
(E) VAV
(E) FCU
(E) CUH
(E) UH
(E) CU
(E) FT
CU-1-636
M1-05
CU-2-636
BCU-1-636
c
M1-04 d e n
1 PROVIDE NEW SPACE TEMPERATURE SENSOR FOR SYSTEM.
2 INSTALL NEW CONDENSING UNIT ON NEW 4" CONCRETE HOUSEKEEPING
3 PROVIDE NEW CONTROLS FOR EXISTING VAV BOX. CONTROLS TO BE
COMPATIBLE WITH EXISTING JCI METASYS BMS PRESENT ON THE BASE.
5 SIZE AND INSTALL REFRIGERANT PIPING PER MANUFACTURER'S
REQUIREMENTS AND THE SPECIFICATIONS. ALL PIPE PENETRATIONS
SHALL BE DONE VIA A CORE DRILL TO BE NEAT AND CLEAN.
NORTHSCALE: 1/8" = 1'-0"
636 - FIRST FLOOR PLAN - HVAC
Sheets
M0-09 - BUILDING 2500 FIRST FLOOR DEMOLITION PLAN - MECHANICAL
M0-10 - BUILDING 2500 SECOND FLOOR DEMOLITION PLAN - MECHANICAL
M1-02 - BUILDING 608 FLOOR PLANS - HVAC
M1-04 - BUILDING 636 FLOOR PLANS - HVAC
M1-05 - BUILDING 636 MEZZANINE PLAN - HVAC
M1-09 - BUILDING 2500 FIRST FLOOR PLAN - HVAC
M1-10 - BUILDING 2500 SECOND FLOOR PLAN - HVAC
M5-01 - MECHANICAL SCHEDULES
M100
MECH.
MEZZANINE
2 1/2"
1"
1"1"
1 1/4"
3"
1 1/4" 3"
4"
4"4"
2"2"
2"
1 1/4"1 1/4"
80x20
46x30
40x30
40x30
32x36
32x36
40x15
40x15
20x36
18x18
46x36
64x36
64x36
44x36
14x36
(E) FCU
(E) ST
(E) B
(E) B
(E) HWCP
AHU-1-636
c
M1-05 d e n
SCALE: 1/4" = 1'-0"
636 - MEZZANINE PLAN - HVAC
1 INSTALL NEW AIR HANDLING UNIT IN MECHANICAL PENTHOUSE. SUPPORT
UNIT ON MINIMUM 6" BASE RAILS ANCHORED TO MECHANICAL
PENTHOUSE FLOOR. PROVIDE SPRING ISOLATORS BETWEEN BASE RAILS
AND AIR HANDLING UNIT. CONNECT NEW AIR HANDLER TO EXISTING
SUPPLY, RETURN, AND OUTDOOR AIR DUCTWORK AS REQUIRED.
CONNECT REFRIGERANT PIPING FROM CONDENSING UNIT, AND HEATING
HOT WATER PIPING. SEE DETAILS FOR HYDRONIC COIL CONNECTION.
PROVIDE CONDENSATE DRAIN TO EXISTING FLOOR DRAIN IN MECHANICAL
MEZZANINE.
2 SIZE AND INSTALL REFRIGERANT PIPING PER MANUFACTURER'S
Sheets
M0-09 - BUILDING 2500 FIRST FLOOR DEMOLITION PLAN - MECHANICAL
M0-10 - BUILDING 2500 SECOND FLOOR DEMOLITION PLAN - MECHANICAL
M1-02 - BUILDING 608 FLOOR PLANS - HVAC
M1-04 - BUILDING 636 FLOOR PLANS - HVAC
M1-05 - BUILDING 636 MEZZANINE PLAN - HVAC
M1-09 - BUILDING 2500 FIRST FLOOR PLAN - HVAC
M1-10 - BUILDING 2500 SECOND FLOOR PLAN - HVAC
M5-01 - MECHANICAL SCHEDULES
10x10 SA 12x12 SA
10x8 EA
18x14 SA
10x10 SA8 Ø SA
12x6 SA
8x6 SA
18x12 RA
16x14 SA
14 Ø SA
6x8 EA
20x14 SA
18x10 SA
18x12 SA16x12 SA
(TYP.)
CU-1-2500
c
:2
M1-09 d e n
1 INSTALL NEW CONDENSING UNIT ON NEW 4" CONCRETE HOUSEKEEPING
2 PROVIDE NEW SPACE TEMPERATURE SENSOR FOR SYSTEM.
3 PROVIDE NEW CONTROLS FOR EXISTING FAN POWERED BOX. CONTROLS
5 SIZE AND INSTALL REFRIGERANT PIPING PER MANUFACTURER'S
6 ROUTE REFRIGERANT PIPING EXPOSED ON OUTSIDE OF THE BUILDING.
2500 - FIRST FLOOR PLAN - HVAC
Sheets
M1-09 - BUILDING 2500 FIRST FLOOR PLAN - HVAC
6 Ø SA 10x6 SA
6 Ø SA 8x6 EA
8 Ø SA8 Ø SA
18x16 SA
16x24 RA 24x24 RA 36x20 RA
26 Ø OA
40x24 OA
10x10 SA 8 Ø SA
16x14 RA
24x24 RA
24x30 RA
AHU-1-2500
72x24 RA
32x26 SA
RL/S
2" HWS/R2" HWS/R
RL/S
c
M1-10 d e n
1 PROVIDE NEW CONTROLS FOR EXISTING FAN POWERED BOX. CONTROLS
2 PROVIDE NEW SPACE TEMPERATURE SENSOR FOR SYSTEM.
3 INSTALL NEW AIR HANDLING UNIT ON EXISTING MECHANICAL MEZZANINE.
SUPPORT AIR HANDLER AS REQUIRED ON MEZZANINE. CONNECT
REFRIGERANT PIPING FROM CONDENSING UNIT, AND HEATING HOT
WATER PIPING. SEE DETAILS FOR HYDRONIC COIL CONNECTION. PROVIDE
CONDENSATE DRAIN TO EXISTING FLOOR DRAIN.
4 SIZE AND INSTALL REFRIGERANT PIPING PER MANUFACTURER'S
5 ROUTE REFRIGERANT PIPING UP THROUGH THE ROOF. PENETRATIONS
SHALL BE
MADE WATER TIGHT.
6 ROUTE REFRIGERANT PIPING ACROSS THE ROOF OF THE BUILDING.
PROVIDE ROOF
SUPPORTS AS REQUIRED BY THE SPECIFICATIONS. MAINTAIN ANY
WARRANTIES FOR
ROOFING MATERIALS.
2500 - SECOND FLOOR PLAN - HVAC
Sheets
M1-10 - BUILDING 2500 SECOND FLOOR PLAN - HVAC
A. DEMOLITION SHOWN IS AS REQUIRED FOR THE COMPLETE PROJECT.
THE CONTRACTOR SHALL COORDINATE THE DEMOLITION EFFORT.
COORDINATE DEMOLITION WITH THE WORK OF OTHER TRADES.
PROVIDE TEMPORARY POWER AND LIGHTS AS REQUIRED TO ALLOW
THE WORK OF OTHER TRADES TO PROCEED OR AS REQUIRED TO
ALLOW THE OWNER TO OCCUPY THE SPACE.
B. ALL OF THE EQUIPMENT AND DEVICES SHOWN ON THIS DRAWING ARE
EXISTING. THE LOCATIONS OF THE EQUIPMENT AND DEVICES WERE
OBTAINED FROM EXISTING DRAWING AND FIELD INVESTIGATION. THE
LOCATIONS OF THE EXISTING EQUIPMENT AND DEVICES ARE SHOWN
FOR THE CONVENIENCE OF THE CONTRACTOR. ACCURACY OF THE
INFORMATION SHOWN IS NOT GUARANTEED. THE CONTRACTOR IS
RESPONSIBLE FOR THE VERIFICATIONS OF ALL EXISTING CONDITIONS
PRIOR TO SUBMITTING BIDS. SITE VISITS PRIOR TO SUBMISSION OF
BIDS NEED TO BE FULLY COORDINATED WITH THE OWNER.
C. CIRCUIT INFORMATION FOR ALL AFFECTED CIRCUITS SHALL BE
VERIFIED PRIOR TO COMMENCING WORK. ACCURACY OF THE
INFORMATION SHOWN AND INCLUDED ON THE PANEL SCHEDULES IS
NOT GUARANTEED.
D. DEVICES INDICATED TO BE REMOVED, WHICH ARE LOCATED ON
CEILINGS OR WALLS, SHALL HAVE DEVICE AND ALL ASSOCIATED
CIRCUIT WIRING AND CONDUIT REMOVED BACK TO NEAREST
JUNCTION BOX, OR DEVICE NOT INDICATED TO BE REMOVED. ACTUAL
CIRCUITING MUST BE DETERMINED IN THE FIELD. THE CONTRACTOR
SHALL PROVIDE ALL NECESSARY WIRE, CONDUIT, DEVICES AND
CONNECTIONS NECESSARY TO ENSURE CIRCUIT CONTINUITY OF THE
REMAINING DEVICES.
E. THE OWNER HAS THE RIGHT TO RETAIN ALL SALVAGEABLE MATERIAL.
ANY MATERIAL THE OWNER CHOOSES NOT TO ACCEPT SHALL BE
REMOVED FROM THE SITE AND PROPERLY DISPOSED OF BY THE
CONTRACTOR. CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL OF
ANY PCB BALLAST OR HAZARDOUS LAMPS.
F. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE
LABELING OF SPARE OR ABANDONED CIRCUITS AND/OR CIRCUIT
BREAKERS IN ALL PANELS AFFECTED BY THE DEMOLITION. SPARE
CIRCUITS AND/OR CIRCUIT BREAKERS MAY BE REUSED FOR THE
CIRCUITING OF THE NEW OR REMODELED AREA AS SPACE AND PANEL
LOADING WILL ALLOW.
G. THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE
PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRING
PATCHING, PLASTERING, PAINTING AND/OR OTHER REPAIR DUE TO
THE DEMOLITION WORK DONE BY THE ELECTRICAL CONTRACTOR,
UNDER THE TERMS OF THIS SPECIFICATION. CLOSE AND SEAL ALL
OPENINGS, REPAIR ALL SURFACES, ETC., AS REQUIRED.
H. PROTECT EXISTING FURNITURE, CARPET AND OTHER
APPURTENANCES FROM DAMAGE DURING THE COURSE OF
CONSTRUCTION. REPLACE DAMAGED ITEMS FREE OF COST TO THE
OWNER.
I. ITEMS WHICH ARE INTENDED TO BE REMOVED, RELOCATED, OR
SALVAGED ARE SHOWN AS FULL-TONE LINES ON DEMO PLANS. ALL
OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE AND ARE SHOWN
AS HALF-TONE.
A. DRAWINGS DO NOT SHOW TOTAL NUMBER OF CONDUCTORS FOR
CIRCUITS REQUIRED. PROVIDE THE NUMBER OF CONDUCTORS
NEEDED TO COMPLETE INSTALLATION OF SPECIFIC EQUIPMENT
FURNISHED. A GREEN GROUND CONDUCTOR, SIZED PER NEC, SHALL
ALSO BE INCLUDED IN EACH CIRCUIT. ADJUST CONDUCTOR SIZES AS
NEEDED TO LIMIT VOLTAGE DROP TO LEVELS RECOMMENDED BY
NEC.
B. ALL CIRCUITS SHALL HAVE SEPARATE NEUTRAL WIRES BUT CAN
SHARE AN INSULATED GREEN GROUND WIRE IN MINIMUM 3/4" EMT
CONDUIT.
C. NO BOXES SHALL BE MOUNTED BACK TO BACK.
D. CONTRACTOR TO SEAL ALL PENETRATIONS THROUGH FIRE OR
FIRE/SMOKE RATED WALLS AND FLOORS.
E. ALL RACEWAYS SHALL BE SEALED AS REQUIRED BY NEC AND NFPA.
F. CABLE AND CONDUIT SHALL NOT INTERFERE WITH EQUIPMENT
ACCESS.
G. CONTRACTOR SHALL COORDINATE FINAL PANEL DIRECTORIES WITH
OWNER.
H. VERIFY CODE REQUIRED CLEARANCE AT EQUIPMENT TO BE REUSED.
RELOCATE AS REQUIRED TO PROVIDE CLEARANCE.1
\k w ll in g
-E
E0-00
TB
/J
JC
D1 EXISTING DISCONNECT TO REMAIN AND IS TO BE RE-USED FOR
NEW EQUIPMENT.
D2 EXISTING EQUIPMENT TO BE REMOVED. ALL ASSOCIATED
CONDUIT, WIRING, ETC. TO REMAIN TO BE RE-USED FOR NEW
EQUIPMENT.
D3 EXISTING EQUIPMENT AND DISCONNECT TO BE REMOVED. ALL
ASSOCIATED CONDUIT, WIRING, ETC. TO REMAIN TO BE RE-USED
FOR NEW EQUIPMENT.
D4 EXISTING EQUIPMENT AND MOTOR/STARTER TO BE REMOVED.
ALL ASSOCIATED CONDUIT, WIRING, ETC. TO REMAIN TO BE
RE-USED FOR NEW EQUIPMENT.
D5 EXISTING EQUIPMENT, DISCONNECT, AND WIRING TO BE
REMOVED.
1 VERIFY MOCP OF NEW EQUIPMENT. PROVIDE NEW FUSE IN
DISCONNECT, AS REQUIRED, TO MEET NEW MOCP.
2 PROVIDE NEW 200A DISCONNECT WITH 125A FUSE.
3 VFD WITH INTEGRAL DISCONNECT SUPPLIED WITH EQUIPMENT.
4 CONNECT NEW EQUIPMENT TO EXISTING CIRCUIT AND
DISCONNECT (IF APPLICABLE) AS SHOWN. VERIFY EXISTING
CIRCUIT.
5 CONNECT TO EXISTING FIRE ALARM CUT OFF RELAY.
6 CONNECT TO EXISTING SPARE 225/3 CIRCUIT BREAKER IN
DISTRIBUTION PANEL 'MDA'. PROVIDE 3#4/0, 1#4G - 2"C AND 400A
NON-FUSED DISCONNECT.
E0-00 ELECTRICAL INFO SHEET
E0-01 BUILDING 605 - DEMOLITION
E0-02 BUILDING 608 - DEMOLITION
E0-03 BUILDING 635 - DEMOLITION
E0-04 BUILDING 636 - DEMOLITION
E0-05 BUILDING 649 - DEMOLITION
E0-06 BUILDING 651 - DEMOLITION
E0-07 BUILDING 652 - EMOLITION
E0-08 BUILDING 2500 FIRST FLOOR - DEMOLITION
E0-09 BUILDING 2500 SECOND FLOOR - DEMOLITION
E0-10 BUILDING 2901 - DEMOLITION
E1-01 BUILDING 605 - ELECTRICAL
E1-02 BUILDING 608 - ELECTRICAL
E1-03 BUILDING 635 - ELECTRICAL
E1-04 BUILDING 636 - ELECTRICAL
E1-05 BUILDING 649 - ELECTRICAL
E1-06 BUILDING 651 - ELECTRICAL
E1-07 BUILDING 652 - ELECTRICAL
E1-08 BUILDING 2500 FIRST FLOOR - ELECTRICAL
E1-09 BUILDING 2500 SECOND FLOOR - ELECTRICAL
E1-10 BUILDING 2901 - ELECTRICAL
PLAN
ARROW
SYMBOL LEGEND
MATCHLINE
AREA A
AREA B
EXISTING
COLUMN
NEW
COLUMN
XX-XX
SIM
XX-XX
XXXX
DX
SECTION/
DETAIL
PLAN
DETAIL
REFERENCE
NOTE
DEMOLITION
NOTE
NUMBER
ROOM NAME
150 SF
LETTER INDICATES
NEW COLUMN LINE
LETTER INDICATES
EXISTING COLUMN LINE
SECTION/DETAIL NUMBER
SHEET NUMBER
INDICATES DIRECTION OF VIEW
DETAIL NUMBER
SHEET NUMBER
DESIGNATION
DEMOLITION
ROOM NAME DESIGNATION
ROOM NUMBER DESIGNATION
ROOM AREA DESIGNATION
REFERENCE LEGEND
NAME
ELEVATION
LEVEL
TITLE
MARKER
VIEW NAME
DETAIL NUMBER
LEVEL CALLOUT
ELEVATION
GRAPHIC AREA FOR DRAWING
TITLE
SCALE OF THE DRAWING
PC
OS
MS
TV
VC
N E
N S
N D
N 2
K1
FS
PS
TS
DH
WALL MOUNTED STRIP LUMINAIRE
SYMBOL NOTES:
STROBE
HORN
MANUAL PULL STATION
HORN STROBE
PHOTOCELL
VOICE AND DATA
JUNCTION BOX - CEILING MOUNT
JUNCTION BOX - WALL MOUNT
VOICE OUTLET
DATA OUTLET
OCCUPANCY SENSOR
MOTION SENSOR
CEILING FAN
HEAT DETECTOR
SMOKE DETECTOR
REMOTE INDICATOR LIGHT
SPRINKLER TAMPER SWITCH
DUCT SMOKE DETECTOR
FLOW SWITCH
POST INDICATING VALVE SWITCH
POLE MOUNTED SITE LUMINAIRE
FLOOD LIGHT
NURSE CALL
SPEAKER
BEDSIDE STATION
INTERCOM SPEAKER STATION
VOLUME CONTROL STATION
MICROPHONE JACK
TELEVISION OUTLET
CCTV CAMERA
SOUND, TELEVISION, AND SECURITY
FUSE
EMERGENCY PULL STATION
DISCONNECT SWITCH
STAFF STATION
DUTY STATION
DOME LIGHT
MASTER STATION
EMERGENCY GENERATOR
POWER DISTRIBUTION ONE LINE
CONDUIT UP
CONDUIT DOWN
INDICATES BUSHED CONDUIT
VOICE/DATA OUTLET
DOUBLE BED BEDSIDE STATION
DRAW OUT VACUUM CIRCUIT BREAKER
LIGHTNING SURGE ARRESTOR
THERMAL OVERLOAD RELAY
PLUG-IN OR DRAWOUT CONNECTOR
CIRCUIT BREAKER
FUSED DISCONNECT SWITCH
VOLTMETER
AMMETER
X:Y CURRENT TRANSFORMER - (RATIO)
KIRK KEY INTERLOCK
MAGNETIC DOOR HOLDER
"C" INDICATES CEILING MOUNTED
"F" INDICATES FLOOR MOUNTED
"S" INDICATES SURFACE MOUNTED
"G" INDICATES GROUND FAULT INTERRUPTING
"IG" INDICATES ISOLATED GROUND
"AC" INDICATES MOUNTING 6" ABOVE COUNTERTOP OR
BACKSPLASH
"WP" INDICATES WEATHERPROOF
"XP" INDICATES EXPLOSION PROOF
"R" INDICATES EXISTING DEVICE REMOVED AND
RELOCATED
LOWER CASE LETTER BY SWITCHES AND FIXTURES
INDICATE ASSOCIATED UNIT FOR SWITCHING
LIGHTING
LUMINAIRE
WALL MOUNTED LUMINAIRE
RECESSED LUMINAIRE
WALL MOUNTED LUMINAIRE
SURFACE MOUNTED LUMINAIRE
TRACK LIGHTING
DIMMER SWITCH
TIMER SWITCH
WIRING DEVICES - SWITCHES
SINGLE POLE SWITCH
KEY OPERATED SWITCH
SINGLE POLE SWITCH WITH PILOT
THERMAL ELEMENT SWITCH
FOUR-WAY SWITCH
TWO POLE SWITCH
THREE-WAY SWITCH
STRIP / INDUSTRIAL LUMINAIRE
LUMINAIRE - NIGHT LIGHTING
LUMINAIRE - EMERGENCY SYSTEM
EMERGENCY BATTERY PACK LUMINAIRE
REMOTE EMERGENCY HEAD
WALL WASH LUMINAIRE
PENDANT MOUNTED LUMINAIRE
POWER POLE
METER SOCKET
POWER EQUIPMENT
WIRING DEVICES - RECEPTACLES
COMBINATION STARTER SAFETY SWITCH
RELAY - CONTROL AS NOTED
PUSHBUTTON STATION
MOTOR CONNECTION
SIMPLEX RECEPTACLE
DUPLEX RECEPTACLE
QUADRUPLEX RECEPTACLE
EMERGENCY RECEPTACLE
SPECIAL PURPOSE RECEPTACLE, NEMA
CONFIGURATION NOTED
PLUG-IN STRIP - LENGTH AND QUANTITY
OF OUTLETS AS SHOWN
SAFETY SWITCH
DROP CORD RECEPTACLE ASSEMBLY
FUSIBLE SWITCH (FUSETRON)
PANELS AND CABINETS
DISTRIBUTION PANEL
SWITCHBOARD, SWITCHGEAR, MCC
EQUIPMENT OR TERMINAL CABINET
DRY TYPE TRANSFORMER
BRANCH CIRCUIT PANEL
CONDUIT AND BOXES
FIRE ALARM SYSTEM
HORN (PA, PUBLIC ADDRESS)
TRANSFORMER
EXIT LIGHT - WALL MOUNT WITH
DIRECTIONAL ARROWS AS INDICATED,
FILLED-IN QUARTERS INDICATE
ILLUMINATION SIDES
EXIT LIGHT - CEILING OR PENDANT
MOUNT WITH DIRECTIONAL ARROWS AS
INDICATED, FILLED-IN QUARTERS
INDICATE ILLUMINATION SIDES
EMERGENCY EXIT LIGHT COMBO
LOW VOLTAGE MOMENTARY
CONTACT SWITCH
REF. DEMO NOTES ( )
ELECTRICAL SHEET LIST
PROJECT ELECTRICAL REFERENCED DEMOLITION NOTES
GENERAL NOTES XDXGENERAL DEMO NOTESABBREVIATIONS
N P PILLOW SPEAKER
REF. NOTES ( )
PROJECT ELECTRICAL REFERENCED NOTES
FB FLOOR BOX
FP FLOOR POKE-THROUGH DEVICE
N M
QTY QUANTITY
REC RECEPTACLE
REFR REFRIGERATOR
REINF REINFORCEMENT
REQD REQUIRED
SOUTH
SCHED SCHEDULE
SF SQUARE FOOT (FEET)
SPEC SPECIFICATIONS
SPKR SPEAKER
SQ SQUARE
STD STANDARD
STL STEEL
SW SWITCH
SWBD SWITCH BOARD
SYM SYMMETRICAL
TEL TELEPHONE
TEMP TEMPERATURE
TVSS TRANSIENT VOLTAGE
SURGE SUPPRESSOR
TYP TYPICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITERS
LABORATORIES
UPS UNINTERRUPTIBLE
POWER SYSTEM
VFD VARIABLE FREQUENCY
DRIVE
W WEST
W/ WITH
W/O WITHOUT
WHM WATTHOUR METER
WT WEIGHT
XFMR TRANSFORMER
ACSR ALUMINUM CONDUCTOR
STEEL REINFORCED
AFF ABOVE FINISH FLOOR
AIC AMPS INTERRUPTING
CAPACITY (SYM RMS)
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
ANSI AMERICAN NATIONAL
STANDARDS INSTITUTE
APPROX APPROXIMATE
AUTO AUTOMATIC
AVG AVERAGE
L ANGLE
BKR BREAKER
C OR CL CENTER LINE
C OR CND CONDUIT (ELECTRICAL
SHEETS)
CKT CIRCUIT
CLG CEILING
COL COLUMN
CONC CONCRETE
CONF CONFERENCE
CUH CABINET UNIT HEATER
DC DIRECT CURRENT
DEG DEGREE
DEMO DEMOLITION
DIA DIAMETER
DIM DIMENSION
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DWG DRAWING
E EAST
EA EACH
EL OR
ELEV
ELEVATION - GRADE OR
BUILDING
ELEC ELECTRIC OR
ELECTRICAL
ELEV ELEVATOR
EMD ESTIMATED MAXIMUM
DEMAND
ENCL ENCLOSURE
EQUIP EQUIPMENT
EST ESTIMATE
EWC ELECTRIC WATER
COOLER
EXIST EXISTING
EXP EXPOSED
EXT EXTERIOR
FA FIRE ALARM
FLA FULL LOAD AMPS
FLEX FLEXIBLE
FLUOR FLUORESCENT
AWG GAUGE
HP HORSE POWER
HR HOUR
HTG HEATING
HTR HEATER
HZ HERTZ
ID INSIDE DIAMETER
IES ILLUMINATING
ENGINEERING SOCIETY
IN INCH
INSUL INSULATION
INT INTERIOR
KCMIL KCM KILO CIRCULAR MIL
KV KILOVOLTS
KVA KILOVOLT AMPERES
KVAR KILOVOLT AMPERES
REACTIVE
KW KILOWATT
LBS POUNDS
LRA LOCKED ROTOR AMPS
LTG LIGHTING
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
N NORTH
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL
CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS
ASSOCIATION
NFPA NATIONAL FIRE
PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NO NUMBER
NTS NOT TO SCALE
OD OUTSIDE DIAMETER
OH OVERHEAD
OPNG OPENING
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
PSI POUNDS PER SQUARE IN.
WIRELESS ACCESS POINT
S2
S3
S4
SD
SK
SP
STE
ST
SFT
CONTROLLED RECEPTACLE
WB WALL AV BOX
F SPEAKER STROBES
FAAP FIRE ALARM
ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL
PANEL
FAEP FIRE ALARM EXTENDER
PANEL
Sheets
E0-00 - ELECTRICAL INFO SHEET
E1-06 - BUILDING 651 - ELECTRICAL
RTU-1-651
PANEL 'MDA'
\k
-E
E1-06
TB
/J
JC
6 CONNECT TO EXISTING SPARE 225/3 CIRCUIT BREAKER IN DISTRIBUTION
PANEL 'MDA'. PROVIDE 3#4/0, 1#4G - 2"C AND 400A NON-FUSED
DISCONNECT.
d e n
651 - FIRST FLOOR PLAN - ELECTRICAL
NOTE: HVAC EMERGENCY SHUTDOWN PUSHBUTTON TO BE LOCATED PER
GOVT RECOMMENDATION. ACTIVATION SHALL CAUSE ALL HVAC EQUIPMENT TO
SHUTDOWN AND DE-ENERGIZE. PROVIDE MUSHROOM RED PUSHBUTTON WITH
HEAVY DUTY PLASTIC TAMPER-PROOF COVER. LABEL FOR USE. PROVIDED HVAC
SHUTDOWN CONTACTOR TO BE LOCATED PER GOVT RECOMMENDATION.
Sheets
E0-00 - ELECTRICAL INFO SHEET
E1-06 - BUILDING 651 - ELECTRICAL
File details come from the government source that posted it.