This document provides specifications for aluminum windows to be installed at the Utah Test and Training Range Consolidated Mission Control Center project. Key requirements include fixed aluminum windows rated for wind load design pressure and blast resistance. Windows must meet thermal performance standards for U-factor and SHGC, and provide sound attenuation of STC 41. The specification outlines submittal requirements, quality assurance testing and certification to AAMA standards, warranty terms, and installation instructions. Product standards include aluminum alloy and finish composition, thermal barrier construction, operation and performance levels for air infiltration, water penetration and structural performance.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UTAH TEST AND TRAINING RANGE (UTTR) 100% FINAL/RTA SUBMITTAL
CONSOLIDATED MISSION CONTROL CENTER (CMCC) 11 OCTOBER 2019
SECTION TABLE OF CONTENTS
DIVISION 08 - OPENINGS
SECTION 08 51 13
ALUMINUM WINDOWS
05/11
PART 1 GENERAL
1.1 REFERENCES
1.2 CERTIFICATION
1.3 SUBMITTALS
1.4 QUALITY ASSURANCE
1.4.1 Shop Drawing Requirements
1.4.2 Sample Requirements
1.4.2.1 Finish Sample Requirements
1.4.3 Design Data Requirements
1.4.4 Test Report Requirements
1.5 DELIVERY AND STORAGE
1.6 PROTECTION
1.7 PLASTIC IDENTIFICATION
1.8 FIELD MEASUREMENTS
1.9 PERFORMANCE REQUIREMENTS
1.9.1 Wind Loading Design Pressure
1.9.2 Tests
1.10 WINDOW PERFORMANCE
1.10.1 Structural Performance
1.10.2 Minimum Antiterrorism Performance
1.10.3 Air Infiltration
1.10.4 Water Penetration
1.10.5 Thermal Performance
1.10.6 Sound Attenuation
1.11 QUALIFICATION
1.12 WARRANTY
PART 2 PRODUCTS
2.1 WINDOWS
2.1.1 Fixed Windows (F)
2.1.2 Forced Entry Resistant Windows
2.1.3 Glass and Glazing
2.1.4 Caulking and Sealing
2.1.5 Weatherstripping
2.2 FABRICATION
2.2.1 Provisions for Glazing
2.2.2 Weatherstripping
2.2.3 Fasteners
2.2.4 Sealants
2.2.5 Drips and Weep Holes
2.2.6 Accessories
2.2.6.1 Fasteners
2.2.6.2 Window Anchors
2.2.7 Finishes
SECTION 08 51 13 Page 1
2.2.7.1 Anodic Coating
2.3 THERMAL-BARRIER WINDOWS
PART 3 EXECUTION
3.1 SCHEDULE
3.2 INSTALLATION
3.2.1 Method of Installation
3.2.2 Dissimilar Materials
3.2.3 Anchors and Fastenings
3.3 CLEANING
-- End of Section Table of Contents --
SECTION 08 51 13 Page 2
SECTION 08 51 13
ALUMINUM WINDOWS
05/11
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ALUMINUM ASSOCIATION (AA)
AA DAF45 (2003; Reaffirmed 2009) Designation System for Aluminum Finishes
AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA)
AAMA 1302.4 (1973) Specifications for Forced-Entry Resistant Aluminum Prime Windows
AAMA 1503 (2009) Voluntary Test Method for Thermal Transmittance and Condensation Resistance of Windows, Doors and Glazed Wall Sections
AAMA 611 (2014) Voluntary Specification for Anodized Architectural Aluminum
AAMA/WDMA/CSA 101/I.S.2/A440 (2011; Update 1 2014) North American Fenestration Standard/Specification for Windows, Doors, and Skylights
ASTM INTERNATIONAL (ASTM)
ASTM F2248 (2012) Standard Practice for Specifying an Equivalent 3-Second Duration Design Loading for Blast Resistant Glazing Fabricated with Laminated Glass
NATIONAL FENESTRATION RATING COUNCIL (NFRC)
NFRC 100 (2014) Procedure for Determining Fenestration Product U-Factors
NFRC 200 (2014) Procedure for Determining Fenestration Product Solar Heat Gain Coefficient and Visible Transmittance at Normal Incidence
1.2 CERTIFICATION
Each prime window unit must bear the AAMA Label warranting that the product complies with AAMA/WDMA/CSA 101/I.S.2/A440 . Certified test reports attesting that the prime window units meet the requirements of AAMA/WDMA/CSA 101/I.S.2/A440 , including test size, will be acceptable in
SECTION 08 51 13 Page 3 lieu of product labeling.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance with Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Windows ; G, AE
Fabrication Drawings
SD-03 Product Data
Windows ; G, AE
Recycled Content of Aluminum Windows ; S
Hardware ; G, RO
Fasteners ; G, RO
Window Performance ; G, RO
Thermal-Barrier Windows ; G, RO
Accessories ; G, RO
Submit manufacturer's product data, indicating VOC content.
Thermal Performance ; G, RO
SD-04 Samples
Finish Sample ; G, AE
SD-05 Design Data
Structural Calculations for Deflection ; G, RO
Design Analysis ; G, RO
Submit design analysis with calculations showing that the design of each different size and type of aluminum window unit and its anchorage to the structure meets the minimum antiterrorism standards required by paragraph MINIMUM ANTITERRORISM PERFORMANCE , unless conformance is demonstrated by Standard Airblast Test results . Calculations verifying the structural performance of each window proposed for use, under the given loads, must be prepared and signed by a registered Professional Engineer. The window components and anchorage devices to the structure, as determined by the design analysis, must be reflected in the shop drawings.
SECTION 08 51 13 Page 4
SD-06 Test Reports
Minimum Condensation Resistance Factor
Resistance to Forced Entry
Standard Airblast Test ; G, RO
For Minimum Antiterrorism windows, in lieu of a Design Analysis, results of airblast testing, whether by arena test or shocktube, must be included in a test report, providing information in accordance with ASTM F1642/F1642M , as prepared by the independent testing agency performing the test. The test results must demonstrate the ability of each window proposed for use to withstand the airblast loading parameters and achieve the hazard level rating specified in paragraph STANDARD AIRBLAST TEST METHOD.
SD-10 Operation and Maintenance Data
Windows , Data Package 1; G, RO
Submit in accordance with Section 01 78 23 OPERATION AND
MAINTENANCE DATA.
Plastic Identification
When not labeled, identify types in Operation and Maintenance Manual.
1.4 QUALITY ASSURANCE
1.4.1 Shop Drawing Requirements
Provide fabrication drawings that indicate elevations of windows, full-size sections, thickness and gages of metal, fastenings, proposed method of anchoring, size and spacing of anchors, details of construction, method of glazing, mullion details, method and materials for weatherstripping, stools, casings, sills, trim, installation details, and other related items.
1.4.2 Sample Requirements
1.4.2.1 Finish Sample Requirements
Submit range samples of finished metal used in product.
1.4.3 Design Data Requirements
Submit calculations to substantiate compliance with deflection requirements and Minimum Antiterrorism Performance criteria. A registered Professional Engineer must provide calculations.
Submit design analysis with calculations showing that the design of each different size and type of aluminum window unit and its anchorage to the structure meets the requirements of paragraph MINIMUM ANTITERRORISM PERFORMANCE CRITERIA. Calculations verifying the structural performance of each window proposed for use, under the given loads, must be prepared and signed by a registered professional engineer. Reflect the window
SECTION 08 51 13 Page 5 components and anchorage devices to the structure, as determined by the design analysis, in the shop drawings.
1.4.4 Test Report Requirements
Submit test reports for each type of window attesting that identical windows have been tested and meet the requirements specified herein for conformance to AAMA/WDMA/CSA 101/I.S.2/A440 including test size, and minimum condensation resistance factor (CRF), and resistance to forced entry , and, for Minimum Antiterrorism windows, in lieu of a Design Analysis, results of a Standard Airblast Test .
1.5 DELIVERY AND STORAGE
Deliver windows to project site in an undamaged condition. Use care in handling and hoisting windows during transportation and at the jobsite.
Store windows and components out of contact with the ground, under a weathertight covering, so as to prevent bending, warping, or otherwise damaging the windows. Repair damaged windows to an "as new" condition as approved. If windows can not be repaired, provide a new unit.
1.6 PROTECTION
Protect finished surfaces during shipping and handling using the manufacturer's standard method. Do not apply coatings or lacquers to surfaces to which caulking and glazing compounds must adhere.
1.7 PLASTIC IDENTIFICATION
Label plastic products provided to indicate their polymeric composition according to the following list. Where products are not labeled, provide product data indicating polymeric information in Operation and Maintenance Manual.
a. Type 1: Polyethylene Terephthalate (PET, PETE).
b. Type 2: High Density Polyethylene (HDPE).
c. Type 3: Vinyl (Polyvinyl Chloride or PVC).
d. Type 4: Low Density Polyethylene (LDPE).
e. Type 5: Polypropylene (PP).
f. Type 6: Polystyrene (PS).
g. Type 7: Other. Use of this code indicates that the package in question is made with a resin other than the six listed above, or is made of more than one resin listed above, and used in a multi-layer combination.
1.8 FIELD MEASUREMENTS
Take field measurements prior to preparation of the drawings and fabrication.
SECTION 08 51 13 Page 6
1.9 PERFORMANCE REQUIREMENTS
1.9.1 Wind Loading Design Pressure
Design window components, including mullions, hardware , and anchors, to withstand a wind-loading design pressure as indicated on the drawings.
1.9.2 Tests
Test windows proposed for use in accordance with AAMA/WDMA/CSA 101/I.S.2/A440 for the particular type and quality window specified.
Perform tests by a nationally recognized independent testing laboratory equipped and capable of performing the required tests. Submit the results of the tests as certified laboratory reports required herein.
Minimum design load for a uniform-load structural test must be 50 psf .
1.10 WINDOW PERFORMANCE
Aluminum windows must meet the following performance requirements.
Perform testing requirements by an independent testing laboratory or agency.
1.10.1 Structural Performance
Structural test pressures on window units must be for positive load (inward) and negative load (outward). After testing, there will be no glass breakage, permanent damage to fasteners, hardware parts, support arms or actuating mechanisms or any other damage which could cause window to be inoperable. There must be no permanent deformation of any main frame, sash or ventilator member in excess of the requirements established by AAMA/WDMA/CSA 101/I.S.2/A440 for the window types and classification specified in this section.
1.10.2 Minimum Antiterrorism Performance
Windows must meet the minimum antiterrorism performance as specified in the paragraphs below UFC 4-010-01 dated December 2018 section 3-11 .
Conformance to the performance requirements must be validated by one of the following methods.
The glazing frame bite for the window frames must be in accordance with
ASTM F2248.
1.10.2.1 Computational Design Analysis Method
Window frames, mullions, and sashes must be designed to the criteria listed herein. Computational design analysis must include calculations verifying the structural performance of each window proposed for use, under the given static equivalent loads.
Aluminum window framing members must restrict deflections of the edges of glazing they support to L/60 under two times (2X) the glazing resistance per the requirements of ASTM F2248 and ASTM E1300. Glazing resistance must be greater than equivalent 3-second duration loading.
The glazing frame bite for the window frames must be in accordance with
SECTION 08 51 13 Page 7
ASTM F2248.
Window frames must be anchored to the supporting structure with anchors designed to resist two times (2X) the glazing resistance in accordance with ASTM F2248 and ASTM E1300.
1.10.2.2 Alternate Dynamic Design Analysis Method
As an alternative to the static equivalent load design approach described above, window framing members, anchors, and glazing may be designed using a dynamic analysis to prove the window system will provide performance equivalent to or better than a very low hazard rating in accordance with ASTM F1642/F1642M associated with the applicable low level of protection for the project.
1.10.3 Air Infiltration
Air infiltration must not exceed the amount established by AAMA/WDMA/CSA 101/I.S.2/A440 for each window type.
1.10.4 Water Penetration
Water penetration must not exceed the amount established by AAMA/WDMA/CSA 101/I.S.2/A440 for each window type.
1.10.5 Thermal Performance
Non-residential aluminum windows (including frames and glass) must be certified by the National Fenestration Rating Council with a whole-window Solar Heat Gain Coefficient (SHGC) maximum of .45 determined according to
NFRC 200 procedures and a U-factor maximum of .36 Btu/hr-ft 2-F in accordance with NFRC 100.
1.10.6 Sound Attenuation
The window unit must have a minimum STC of 41 with the window glazed with two pieces of 1/4 inch thick laminated glass 1/2 inch air space when tested in accordance with AAMA/WDMA/CSA 101/I.S.2/A440 acoustical performance (optional).
1.11 QUALIFICATION
Window manufacturer must specialize in designing and manufacturing the type of aluminum windows specified in this section, and have a minimum of 5 years of documented successful experience. Manufacturer must have the facilities capable of meeting contract requirements, single-source responsibility and warranty.
1.12 WARRANTY
Provide Manufacturer's standard performance guarantees or warranties that extend beyond a 1 year period.
PART 2 PRODUCTS
2.1 WINDOWS
Provide prime windows that comply with AAMA/WDMA/CSA 101/I.S.2/A440 and the requirements specified herein. In addition to compliance with
SECTION 08 51 13 Page 8
AAMA/WDMA/CSA 101/I.S.2/A440 , window framing members for each individual light of glass must not deflect to the extent that deflection perpendicular to the glass light exceeds L/175 of the glass edge length when subjected to uniform loads at specified design pressures. Provide Structural calculations for deflection to substantiate compliance with deflection requirements. Provide windows of types, performance classes, performance grades, combinations, and sizes indicated or specified.
Provide aluminum window frames with a minimum recycled content of 20 percent. Provide data identifying percentage of recycled content of aluminum windows . Design windows to accommodate hardware, glass, weatherstripping, screens, and accessories to be furnished. Each window must be a complete factory assembled unit with or without glass installed. Dimensions shown are minimum. Provide windows with insulating glass and thermal break necessary to achieve a minimum Condensation Resistance Factor (CRF) of 75 when tested in accordance with AAMA 1503.
2.1.1 Fixed Windows (F)
Type F-CW30 Performance Grade.
2.1.2 Forced Entry Resistant Windows
In addition to meeting the requirements of AAMA/WDMA/CSA 101/I.S.2/A440 , windows designated for resistance to forced entry must conform to the requirements of AAMA 1302.4 .
2.1.3 Glass and Glazing
Materials are specified in Section 08 81 00 GLAZING.
2.1.4 Caulking and Sealing
Are specified in Section 07 92 00 JOINT SEALANTS.
2.1.5 Weatherstripping
AAMA/WDMA/CSA 101/I.S.2/A440 .
2.2 FABRICATION
Fabrication of window units must comply with AAMA/WDMA/CSA 101/I.S.2/A440 .
2.2.1 Provisions for Glazing
Design windows and rabbets suitable for glass thickness shown or specified. For minimum antiterrorism windows, attach glazing to its supporting frame using structural silicone sealant or adhesive glazing tape in accordance with ASTM F2248.
2.2.2 Weatherstripping
Provide easily replaceable factory-applied weatherstripping. Use molded vinyl, molded or molded-expanded neoprene or molded or expanded Ethylene Propylene Diene Terpolymer (EPDM) compression-type weatherstripping for compression contact surfaces. Use treated woven pile or wool, or polypropylene or nylon pile bonded to nylon fabric and metal or plastic backing strip weatherstripping for sliding surfaces. Do not use neoprene or polyvinylchloride weatherstripping where exposed to direct sunlight.
SECTION 08 51 13 Page 9
2.2.3 Fasteners
Use window manufacturer's standard for windows, trim, and accessories.
Self-tapping sheet-metal screws are not acceptable for material more than 1/16 inch thick.
2.2.4 Sealants
Provide joint sealants as specified in Section 07 92 00 JOINT SEALANTS.
For interior application of joint sealants, comply with applicable regulations regarding reduced VOC's, and as specified in Section 07 92 00
JOINT SEALANTS.
2.2.5 Drips and Weep Holes
Provide drips and weep holes as required to return water to the outside.
2.2.6 Accessories
Provide windows complete with necessary hardware, fastenings, clips, fins, anchors, glazing beads, and other appurtenances necessary for complete installation and proper operation. Furnish extruded aluminum subframe receptors and subsill with each window unit.
2.2.6.1 Fasteners
Provide concealed anchors of the type recommended by the window manufacturer for the specific type of construction. Anchors and fasteners must be compatible with the window and the adjoining construction. Provide a minimum of three anchors for each jamb located approximately 6 inches from each end and at midpoint.
2.2.6.2 Window Anchors
Anchoring devices for installing windows must be made of aluminum, cadmium-plated steel, stainless steel, or zinc-plated steel conforming to
AAMA/WDMA/CSA 101/I.S.2/A440 .
2.2.7 Finishes
Exposed aluminum surfaces must be factory finished with an anodic coating. Color must match storefront and glazed curtainwall framing specified in other sections. All windows must have the same finish.
2.2.7.1 Anodic Coating
Clean exposed aluminum surfaces and provide an anodized finish conforming to AA DAF45 and AAMA 611. Finish must be:
b. Architectural Class I ( 0.7 mil or thicker), designation AA-M10-C22-A44, color anodized as indicated.
2.3 THERMAL-BARRIER WINDOWS
Provide thermal-barrier windows, complete with accessories and fittings, where indicated.
Specify material and construction except as follows:
SECTION 08 51 13 Page 10
a. Aluminum alloy must be 6063-T6.
b. Frame construction, including operable sash, must be factory-assembled and factory-sealed inner and outer aluminum completely separated from metal-to-metal contact. Join assembly by a continuous, concealed, low conductance divider housed in an interlocking extrusion of the inner frame. Metal fasteners, straps, or anchors must not bridge the connection between the inner and outer frame.
c. Operating hardware for each sash must consist of spring-loaded nylon cushion blocks and pin locks designed to lock in predetermined locations.
d. Sash must be completely separated from metal-to-metal contact by means of woven-pile weatherstripping, plastic, or elastomeric separation members.
e. Operating and storm sash must be factory-glazed with the type of glass indicated and of the quality specified in Section 08 81 00 GLAZING.
PART 3 EXECUTION
3.1 SCHEDULE
Some metric measurements in this section are based on mathematical conversion of inch-pound measurements, and not on metric measurement commonly agreed to by the manufacturers or other parties. The inch-pound and metric measurements are as follows:
PRODUCTS INCH-POUND METRIC
Metal Casing 0.0625 inch 1.59 mm
Aluminum Tube (Diameter) 0.0625 inch 1.59 mm
1 inch 25 mm
3.2 INSTALLATION
3.2.1 Method of Installation
Install in accordance with the window manufacturer's printed instructions and details. Build in windows as the work progresses or install without forcing into prepared window openings. Set windows at proper elevation, location, and reveal; plumb, square, level, and in alignment; and brace, strut, and stay properly to prevent distortion and misalignment. Bed screws or bolts in sill members, joints at mullions, contacts of windows with sills, built-in fins, and subframes in mastic sealant of a type recommended by the window manufacturer. Install and caulk windows in a manner that will prevent entrance of water and wind.
Any materials that show visual evidence of biological growth due to the presence of moisture must not be installed on the building project.
3.2.2 Dissimilar Materials
Where aluminum surfaces are in contact with, or fastened to masonry, concrete, wood, or dissimilar metals, except stainless steel or zinc, SECTION 08 51 13 Page 11 protect the aluminum surface from dissimilar materials as recommended in the Appendix to AAMA/WDMA/CSA 101/I.S.2/A440 . Do not coat surfaces in contact with sealants after installation with any type of protective material.
3.2.3 Anchors and Fastenings
Make provision for securing units to each other, to masonry, and to other adjoining construction. Windows installed in masonry walls must have head and jamb members designed to recess into masonry wall not less than 7/16 inch .
3.3 CLEANING
Clean interior and exterior surfaces of window units of mortar, plaster, paint spattering spots, and other foreign matter to present a neat appearance, to prevent fouling of weathering surfaces and weather-stripping, and to prevent interference with the operation of hardware. Replace all stained, discolored, or abraded windows that cannot be restored to their original condition with new windows.
-- End of Section --
SECTION 08 51 13 Page 12
| 08 51 13 - ALUMINUM WINDOWS |
| 08 51 13 - ALUMINUM WINDOWS |
| PART 1 GENERAL |
| 1.1 REFERENCES |
| 1.2 CERTIFICATION |
| 1.3 SUBMITTALS |
| 1.4 QUALITY ASSURANCE |
| 1.4.1 Shop Drawing Requirements |
| 1.4.2 Sample Requirements |
| 1.4.2.1 Finish Sample Requirements |
| 1.4.3 Design Data Requirements |
| 1.4.4 Test Report Requirements |
| 1.5 DELIVERY AND STORAGE |
| 1.6 PROTECTION |
| 1.7 PLASTIC IDENTIFICATION |
| 1.8 FIELD MEASUREMENTS |
| 1.9 PERFORMANCE REQUIREMENTS |
| 1.9.1 Wind Loading Design Pressure |
| 1.9.2 Tests |
| 1.10 WINDOW PERFORMANCE |
| 1.10.1 Structural Performance |
| 1.10.2 Minimum Antiterrorism Performance |
| 1.10.3 Air Infiltration |
| 1.10.4 Water Penetration |
| 1.10.5 Thermal Performance |
| 1.10.6 Sound Attenuation |
| 1.11 QUALIFICATION |
| 1.12 WARRANTY |
| PART 2 PRODUCTS |
| 2.1 WINDOWS |
| 2.1.1 Fixed Windows F |
| 2.1.2 Forced Entry Resistant Windows |
| 2.1.3 Glass and Glazing |
| 2.1.4 Caulking and Sealing |
| 2.1.5 Weatherstripping |
| 2.2 FABRICATION |
| 2.2.1 Provisions for Glazing |
| 2.2.2 Weatherstripping |
| 2.2.3 Fasteners |
| 2.2.4 Sealants |
| 2.2.5 Drips and Weep Holes |
| 2.2.6 Accessories |
| 2.2.6.1 Fasteners |
| 2.2.6.2 Window Anchors |
| 2.2.7 Finishes |
| 2.2.7.1 Anodic Coating |
2.3 THERMAL-BARRIER WINDOWS
| PART 3 EXECUTION |
| 3.1 SCHEDULE |
| 3.2 INSTALLATION |
| 3.2.1 Method of Installation |
| 3.2.2 Dissimilar Materials |
| 3.2.3 Anchors and Fastenings |
3.3 CLEANING