This document provides information on an upcoming federal construction contract opportunity for the Utah Test and Training Range Consolidated Mission Control Center at Hill Air Force Base, Utah. The Army Corps of Engineers intends to issue a request for proposal for a firm-fixed-price construction contract between $25-100 million to build a new consolidated mission control center facility to replace outdated infrastructure and enable greater flexibility for air traffic control and post-mission evaluation. Interested vendors should monitor the beta.SAM.gov website for the solicitation anticipated for release on or around September 10, 2020, with proposals due tentatively on October 12, 2020. The period of performance is estimated at 852 days. NAICS code 236220 for commercial and institutional building construction applies, with a size standard of $36.5 million.
View the file
Other files for this federal contract opportunity
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LEAD BASED PAINT
ASBESTOS
LIMITED INSPECTION REPORT
Utah Certified State Inspector: Raudel Arteaga (ASB#-5863: Expires-25 October 2020, PB#-2244: Expires-6 November 2022)
INSPECTION DATE: 01 November 2019
Reference UDAQ R307-807-6
DEPARTMENT OF THE AIR FORCE
75TH CIVIL ENGINEERING (CEOHA)
HILL AIR FORCE BASE, UTAH
75 CEG
FACILITY CONSTRUCTION DATE:
WORK TASK #:
FACILITY:
REQUESTER:
09 September 2019
(This inspection is valid for three years from the inspection date regardless of Exp. Date of inspector cert. If past this date, a visual or additional assessment will then be required)
SIGNATURE:
PREPARED BY: Taylor Brimberry (ASB#-6727, PB#-2546)
DEMOLISH BUILDING
THIS REPORT IS NOT TO BE USED FOR BIDDING PURPOSES
ORGANIZATION:
REQUESTED:
6471282
RICHARD NEHRING
ASBESTOS
6% Chrysotile (Via Point
Count) 2%
Chrysotile (Via Point
Count) 3%
Chrysotile (Via Point
Count) 2%
Chrysotile (Via Point
Count)
Assumed
Assumed
Assumed
Assumed
Category INon-Friable
Civil Engineering personnel also reviewed previous asbestos inspection reports of suspect asbestos containing materials (ACM) that could potentially be encountered in the proposed area/areas. The information gathered from all current and previous inspections is shown below by homogenous area (R307-801-9-4).
Window Putty, Tan Non-Friable Category II 200 Square
Feet
Rooms 117 And 118 Exterior Windows and Northwest Door
Windows
Block Filler Paint, Brown/Concrete
Cloth Vibration Collar, White
Friable RACM 200 Linear
Feet AHU's Throughout The Attic
Non-Friable Category II 1,500 Square
Feet Exterior Of The Building
Block Filler Paint, Tan/Concrete
Demolish Building.Statement of Work:
DEPARTMENT OF THE AIR FORCE
75 CIVIL ENGINEERING (CEOHA)
HILL AIR FORCE BASE, UTAH
The quantities within this report are estimates and are not to be used for bidding purposes.
Table 1
SUMMARY OF ASBESTOS CONTAINING MATERIALS FOUND
MATERIAL TYPE
Rooms 117, 118, North Hallway and North Restrooms
*RACM
*Category I *Category II
FRIABILITY QUANTITY
1,200 Square Feet
LIMITED ASBESTOS INSPECTION REPORT INFORMATION
This inspection was performed in accordance with the Utah Division of Air Quality (DAQ) requirements as found in the Utah Air Quality Rule R307-801-10. This inspection report is required to be on site during all abatement, renovation, and demolition activities. Samples referenced in this report were analyzed by polarized light microscopy (PLM) utilizing method 600R-93-116 by The Science and Engineering Laboratory (AIHA Acc.#-
101572) at Hill Air Force Base, Utah (R307-801-10.8.a-b).
Carpet Adhesive, Yellow/ 9" Floor Tile, Tan/ Adhesive, Black
*LOCATIONS FOUND
Non-Friable Category II 12,500
Square Feet Exterior Of The Building
Thermal System Hard Pipe Fittings, White Friable RACM
150 Linear feet
Possibly Throughout The Attic, Pipe Chases And In The Walls
Asbestos Cement Pipe (Transite)
Non-Friable Category II 500 Linear
Feet Possible Buried Lines
Conduit And/Or Pipe Coatings
Non-Friable Category II 500 Linear
Feet Possible Buried Lines
12" Acoustical Ceiling Tile, Wormygrooves/Pinholes Pattern, White/ Puck, Brown 12" Acoustical Ceiling Tile, Heavy Textured Pattern, Off-White/Puck, Brown
*Per UDAQ definition.
Per EPA requirements, all materials analyzed as containing ≤10% asbestos are point counted utilizing EPA method 600/R-93/116 this information is summarized in Table 2.
Table 2.
ASBESTOS
RACM: Regulated Asbestos-Containing Material (RACM)" means friable ACM, Category I non-friable ACM that has become friable, Category I non-friable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading, or Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material in the course of demolition or renovation project operations.
Locations found: Locations of building materials as described in this report indicate where they were found, but do not necessarily mean that these are the only locations where these materials may be encountered during the project.
Category II Non-Friable ACM: Any material, excluding Category I non- friable ACM, containing more than 1% asbestos as determined by using the methods specified in 40 CFR Part 763, Subpart E, Appendix E, Section 1, Polarized Light Microscopy (PLM) that, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure.
*LOCATIONS FOUND
N/A N/A
Cove Base, Brown/Adhesive, Black 12" Floor Tile, Off-White/Adhesive, Yellow
MATERIAL TYPE
Per Hill AFB requirements, all materials containing any detectable amount of asbestos shall be handled as Asbestos Containing Material (ACM). Table 2 shows the summary of materials containing ≤1% that were identified via "Point Counting". Per EPA/UDAQ
≤1% is not considered to be an asbestos containing material, but special handling/packaging requirements are necessary per OSHA 29CFR 1926.1101 and
29CFR 1910.1001
QUANTITY
N/A
Category I Non-Friable ACM: Asbestos-containing packings, gaskets, resilient floor coverings, or asphalt roofing products containing more than 1% asbestos as determined by using the method specified in 40 CFR Part 763, Subpart E, Appendix E, Section 1, Polarized Light Microscopy (PLM).
The following is a list of the "Suspect Materials" that were sampled as part of this inspection:
N/A
Carpet Adhesive, Yellow/9" Floor Tile, Tan/Adhesive, Black12" Floor Tile, Tan/Adhesive, Yellow/Brown Linoleum, Tan/Adhesive, Black Floor Level, Grey
Drywall/Joint Compound Ceiling System Textured Drywall/Joint Compound Wall System
Wall Noise Insulation, Black Duct Insulation, Foil/Yellow Duct Insulation, Foil/White Flex Duct Insulation, Black/Pink
Flex Duct Insulation, Grey/Yellow Vibration Collar, White
Drywall/Joint Compound Wall System Roofing Debris, Black Window Putty, Tan Block Filler Paint/Concrete, Brown
Roof Batt Insulation, Foil/Pink Roof Batt Insulation, Foil/Yellow Wall Batt Insulation, Brown/Pink Wall Batt Insulation, White/Pink
Wall Batt Insulation, Foil/Off-White Wall Batt Insulation, White/Yellow
Insulation Debris, Black Gasket, Black Thermal System Pipe Insulation Lagging, White/Yellow Thermal System Pipe Insulation, White/Yellow Thermal System Pipe Insulation Lagging, White/White Thermal System Pipe Fitting Insulation, White/White
Thermal System Tank Insulation, White/Yellow Sound Board, Brown Wire Insulation, Off-White/Black Wire Insulation, Black
A total of 149 46 suspect materials assessed as part of the inspection.
Sample # samples reference the Table 3.
The following table summarizes the sampling data.
Homogenous Building Material, Description, ResultsSample Location GM200100 Southeast None Detected GM200101 Southwest None Detected GM200102 Southwest None Detected GM200103 Southwest None Detected GM200104 Southwest None Detected
GM200105 Southwest, South Hall None Detected
GM200106 Southeast, South Janitor's None Detected
GM200107 Southwest, Room 14 None Detected
GM200108 North Center, Room 118 6% Chrysotile
(Via Point Count)
GM200109 East Center, Room 117 5% Chrysotile
(Via Point Count) GM200110 West Center, Room 117 5% Chrysotile GM200111 Southwest None Detected GM200112 Southeast None Detected
GM200113 North Center None Detected
Floor Level, Grey, Room 120, 1,200 Square Feet
GM200114 West Center None Detected
Northeast, Room 110 None Detected
GM200115 Southeast, Women's None Detected GM200116 Northeast, Men's None Detected GM200117 North Center, Men's None Detected
12" Acoustical Ceiling Tile, Textured Pattern, Black Over Puck, Brown, Room 9 Vault 2, 450
Square Feet
GM200121 Southwest, Room 112 None Detected
GM200122 East Center, Room 120 None Detected
GM200123
North Center, North Break
Room None Detected
GM200545 Southwest None Detected
GM200546 Southeast None Detected GM200073 North Center, Room 4 None Detected
2'x4' Ceiling Tile, Pockmarks/Pinholes Pattern, White, Multiple Locations 6,500 Square Feet
GM200074 Southwest, Room 5 None Detected GM200075 Northeast, Room 6B None Detected GM200076 Northwest, Room 122 None Detected GM200077 Northwest, Room 120 None Detected GM200078 Northeast, Room 121 None Detected
Cove Base, Brown/Adhesive, Black, Room 110, 5,000 Linear Feet
12" Floor Tile, Off-White Over Adhesive, Yellow, Room 120, 2,500 Square Feet
12" Floor Tile, Tan Over Adhesive, Yellow, Multiple Locations, 2,500 Square Feet
Carpet Adhesive, Yellow/9" Floor Tile, Tan Over Adhesive, Black, Multiple Locations, 1,200 Square Feet
Linoleum, Tan Over Adhesive, Black, North Janitor's Closet, 40 Square Feet
12" Acoustical Ceiling Tile, Heavy Textured Pattern, Off-White Over Puck, Brown, North
Restroom Entries, 120 Square Feet
12" Acoustical Ceiling Tile, Wormygrooves/Pinholes Pattern, White Over Puck, Brown, Multiple Locations, 6,500 Square
Feet
2'x4' Ceiling Tile, Pockmarks/Pinholes Pattern, White 2'x4' Ceiling Tile, Wormygrooves/Pinholes, White 2'x4' Simulated Ceiling Tile, Textured Pattern, White 2'x2' Ceiling Tile, Textured Pattern, White
Portable Wall Panel, Brown Stanchion Adhesive, Black Block Filler Paint/Concrete, Tan Roof Decking, Black
Roof Flashing, Black 12" Textured Acoustical Ceiling Tile, Black/Puck, Brown
GM200118 Southwest, Room 13B None Detected GM200119 Northwest, Room 108 None Detected
GM200120
GM200079 West Center, Room 5 None Detected
2'x4' Ceiling Tile, Wormygrooves/Pinholes Pattern, White, Multiple Locations 7,000
Square Feet GM200083 Northeast, Room 6B None Detected GM200084 Northwest, Room 108 None Detected GM200085 Center, Room 106 None Detected
GM200080 South Center, Room 8 None Detected GM200081 North Center, Room 2 None Detected GM200082 West Center, Room 4 None Detected
GM200086 West Center, Room 121 None Detected GM200087 Southwest, Room 121 None Detected GM200088 Center, Room 12 None Detected
2'x4' Simulated Ceiling Tile, Textured Pattern, White, Multiple Locations, 4,000 Square Feet
GM200089 West Center, Room 12 None Detected GM200090 South Center, South Hall None Detected GM200091 Northeast, Room 12 None Detected GM200092 East Center, Room 8 None Detected
GM200124
Southwest, South Janitor's
Closet None Detected
GM200125
Southeast, Hall Outside
Room 112 None Detected
2'x2' Ceiling Tile, Textured pattern, White, North Half Main Hallway, 2,500 Square Feet
Drywall/Joint Compound Ceiling System, Multiple Locations, 1,300 Square Feet
GM200126
Northwest, North Men's
Restroom None Detected
GM200127 North Center, North None Detected
GM200093 Center None Detected GM200094 South Center None Detected
GM200095 North Center None Detected
GM200128 Northeast None Detected Textured Drywall/Joint Compound Wall
System, Room 8, 935 Square Feet GM200129 Northwest None Detected GM200130 Southwest None Detected GM200131 Northwest, Room 4 None Detected
Drywall/Joint Compound Wall System, Multiple Locations, 53,000 Square Feet
GM200132 West Center, Room 6 None Detected GM200133 Northeast, Room 112 None Detected GM200134 North Center, Room 12 None Detected GM200135 Southwest, Room 13B None Detected GM200136 Southwest, Room 108 None Detected GM200137 Southeast, Room 109 None Detected GM200138 Southwest, Room 110 None Detected GM200139 Southeast, Room 139 None Detected GM200140 Southwest, Room 120 None Detected GM200141 Northwest, Room 120 None Detected
GM200142 West Center, Room 121 None Detected
GM200143
Northwest, Janitor's
Closet None Detected
GM200144 Southeast, North None Detected
GM200542 Southwest, Room 6A None Detected
GM200543 Southeast, Room 9 Vault 2 None Detected
GM200544 Southeast, None Detected
West Center, Room 5 None Detected
Roof Batt Insulation, Foil Over Yellow, Multiple Locations, 16, 250 Square Feet
Wall Batt Insulation, Brown Over Pink, Multiple Locations, 20,000 Square Feet
GM200027 East Center, Room 8 None Detected
GM200028 West Center, Room 12 None Detected
GM200029
Southwest, Southwest
Entry None Detected
GM200022 West Center, Room 121 None Detected GM200023 Northwest, Room 122 None Detected GM200024 Northwest, Room 122 None Detected GM200025 South Center, South Hall None Detected
GM200026
Wall Batt Insulation, White Over Pink, Room 003, 400 Square Feet
GM200030 North Center None Detected
GM200031 South Center, South Hall None Detected GM200032 South Center, Room 8 None Detected
Wall Batt Insulation, Foil Over Off-White, Multiple Locations, 15,000 Square Feet
GM200033 South Center, Room 8 None Detected
GM200536 South Center None Detected GM200537 South Center None Detected
Roof Decking, Black, Fire Riser Shed, 50 Square Feet
GM200538 South Center None Detected GM200539 South Center None Detected GM200540 South Center None Detected
Roof Flashing, Black, Fire Riser Shed, 25 Linear Feet
GM200541 South Center None Detected GM200145 Center, MCC Attic None Detected
GM200146 South Center, MCC Attic None DetectedRoofing Debris, Black, Multiple Locations, 1,500 Feet
GM200147
Northwest, Room 117
Attic None Detected
GM200148 West, Room 117 Exterior 2% Chrysotile
(Via Point Count)
GM200149 North, Room 117 Exterior 1% Chrysotile
(Via Point Count) Window Putty, Tan, Multiple Locations, 200
Square Feet
GM200150 North, Room 118 Exterior 1% Chrysotile
(Via Point Count)
GM200151 Southwest 3% Chrysotile
(Via Point Count)
GM200152 Northwest 2% Chrysotile
(Via Point Count) Block Filler Paint, Brown Over Concrete, Exterior Of The Building, 1,500 Square Feet
GM200153 Southeast 3% Chrysotile
(Via Point Count)
GM200154 Southwest 2% Chrysotile
(Via Point Count)
GM200155 South Center 2% Chrysotile
(Via Point Count)
Block Filler Paint Tan Over Concrete, Exterior Of The Building, 12, 500 Square Feet
GM200156 Northwest 2% Chrysotile
GM200019 East Center, Room 8 None Detected
GM200020 Southeast, Attic Room 13B None Detected Roof Batt Insulation, Foil Over Pink, Multiple
Locations, 16, 250 Square Feet GM200021 Northwest, Room 108 None Detected
GM200034 Northeast, Bldg.1274 None Detected GM200035 East Center, Bldg.1274 None DetectedWall Batt Insulation, White Over Yellow, Multiple Locations, 3,500 Square Feet GM200036 Southeast, Room 12 None Detected
Wall Noise Insulation, Black, Room 110, 300 Square Feet
GM200037 North Center None Detected
GM200038 Center None Detected Duct Insulation, Foil Over Yellow, Attic, 5,000
Linear Feet GM200039 North Center None Detected GM200040 North Center None Detected GM200041 West Center, Room 12 None Detected
Duct Insulation, Foil Over White, Multiple Locations, 2,000 Linear Feet
GM200042 North Center, Room 12 None Detected
GM200043
Southeast, Southwest
Mechanical Room None Detected
Duct Insulation, White Over Yellow, North Mechanical Room, 1,000 Linear Feet
GM200044 Northwest None Detected
GM200045 Southwest, South Hall None Detected GM200046 Southwest, South Entry None Detected GM200047 Southeast, Room 5 None Detected
Flex Duct Insulation, Black Over Pink, Multiple Locations, 1,500 Linear Feet
GM200048 South Center, Room 6 None Detected GM200049 North Center, Room 6 None Detected
GM200050 South Center, Room 12 None Detected
Flex Duct Insulation, Grey Over Yellow, Multiple Locations, 1,000 Linear Feet
Vibration Collar, White, North Restroom Attic, 20 Linear Feet
GM200051 Northeast None Detected
Insulation Debris, Black, Room 112, 50 Square Feet
GM200052 North Center None Detected
GM200056
Northeast, North Mechanical Room
None Detected
GM200057 West Center, Break Room None Detected
Thermal System Pipe Insulation Lagging, White Over Yellow, Multiple Locations, 500 Linear
Feet
Gasket, Black, North Mechanical Room, 10 Linear Feet
GM200053 North Unit None Detected
GM200054
Northeast, North Mechanical Room
None Detected
GM200055 Center, Room 108 Attic None Detected
GM200063
Center, North Mechanical
Room None Detected
GM200061
Northeast, South Mechanical Room
None Detected
Thermal System Pipe Insulation Lagging, White Over White, Multiple Locations, 100 Linear
Feet
GM200062
Northwest, South Mechanical Room
None Detected
Thermal System Pipe Insulation, White Over Yellow, Multiple Locations, 2,000 Linear Feet
GM200058
Northwest, North Mechanical Room
None Detected
GM200059
Northwest, Break Room
Closet None Detected
GM200060
Northwest, Break Room
Closet None Detected
GM200065 Northwest None Detected
GM200066 Northeast None Detected
Thermal System Pipe Fitting Insulation, White Over White, South Mechanical Room, 50
Linear Feet
GM200064 Northwest None Detected
Table 4.
POTENTIAL FOR ADDITIONAL MATERIALS:
This inspection report only encompasses the areas/materials designated within the scope of work that was provided at the date of inspection (see title page for inspection date). Should the scope of the project be altered in any way or any materials found that are not identified in this report shall require additional assessment. This report cannot be used for any other projects within the building.
Any questions or concerns regarding this inspection report or if any new suspect asbestos containing material (ACM) is encountered, stop work and contact the personnel listed below for further assistance/assessment.
GM200098 West Center None Detected
GM200099
Cell: (801)430-3976 Supervisor: Traver Andreasen: DSN: (801)586-7094
Asbestos/LBP Shop 75 CES(CEOHA)
Asbestos/LBP Shop Personnel
DSN:(801)777-8006
CONTACT INFORMATION
Southeast None Detected
Stanchion Adhesive, Black, Room 120, 300 Square Feet
Wire Insulation, Black, Room 8, 10 Linear Feet GM200072 South Center None Detected
Portable Wall Panel, Brown, Room 003, 400 Square Feet
GM200096 West None Detected
GM200097 Northeast None Detected
Sound Board, Brown, Multiple Location, 1,000 Square Feet
Thermal System Tank Insulation, White Over Yellow, North Mechanical Room, 250 Square
Feet GM200067 Southeast None Detected
GM200068 Southeast, Room 13B Attic None Detected
GM200069 Southeast, Room 13B Attic None Detected
GM200070
Southeast, MCC Room
Attic None Detected
Wire Insulation, Off-White Over Black, Room 8, 10 Linear Feet
GM200071 South Center None Detected
SCOPE OF WORK:
XL Number Substrate Component Color Lead Reading Paint
Condition 1672 Wood Window Frame Off-White 1.46 Fair 1673 Wood Muntin Off-White 1.95 Fair 1674 Wood Window Sill Green 1.33 Fair 1681 Wood Window Sill White 1.49 Fair 1697 Ceramic 4" Wall Tile Tan 3.01 Fair 1698 Ceramic Cove Tile Tan 5.18 Fair 1702 Porcelain Urinal White 2.58 Fair 1703 Porcelain Sink White 5.08 Fair 1704 Porcelain Toilet White 3.18 Fair 1708 Wood Window Casing White 2.25 Fair 1709 Wood Window Frame White 0.89 Fair 1710 Wood Window Sill White 1.63 Fair 1711 Ceramic 4" Wall Tile Green 4.81 Fair 1714 Ceramic Cove Tile Green 3.99 Fair 1715 Porcelain Toilet White 2.96 Fair 1726 Concrete Wall Tan 5.65 Fair
XRF Analyzer Used: XRF Analyzer XL3t 300 (Serial #96588)
LIMITED LEAD-BASED PAINT IDENTIFICATION REPORT INFORMATION
Table 1.
2-The condition column is the condition only of the painted/coated component (See final page for all readings/samples).
3-The U.S. Department of Housing and Urban Development defines Lead-based paint as any paint, varnish, stain, or other applied coating that has 1 mg/cm² as measured by an X-ray Fluorescence (XRF) Analyzer or laboratory analysis or 0.5 percent by weight (5,000 µg/g by dry weight) by laboratory analysis, or more of lead.
All other components tested were less than 0.80 mg/cm².
4-Any effort to disturb lead paint can create lead dust. Ensure that appropriate abatement, cleanup, and disposal will be accomplished and that appropriate safety measures are taken IAW 29 CFR 1926.62. If you have any questions concerning this report, contact the Asbestos/LBP Shop: Traver Andreasen at 586-7094.
DEPARTMENT OF THE AIR FORCE
75TH CIVIL ENGINEERING (CEOHA)
HILL AIR FORCE BASE, UTAH
1-Table 1 below, summarizes the painted/coated building components that tested positive for Lead Based Paint/Coating. These components should be segregated or abated prior to renovation or demolition, and a composite TCLP taken of the waste before disposal.
Demolish Building.
5-This inspection report only encompasses the areas/materials designated within the scope of work that was provided at the date of the inspection (see title page for date). This report must be modified should the scope of the project be altered in any way or additional materials not previously identified within this report are encountered. This report may not be used for any other projects within the building.
Building: 1274 WT/CP#: 6471282 Date: 20 September 2019
1664 1.12 1745 0.91 1665 0.92 1746 1.01
1666 1.18 POS 1747 1.03
Range: .8 to 1.2 Paint Range: .8 to 1.2 Side Condition Color PbL(mg/cm2) NEG/POS West Fair Brown 0.01 NEG West Fair Varnish 0.01 NEG North Fair White 0.01 NEG East Fair White 0.01 NEG
South Fair Green 0.01 NEG West Fair Off-White 1.46 POS West Fair Off-White 1.95 POS West Fair Green 1.33 POS West Fair Green 0.58 NEG West Fair Green 0.01 NEG South Fair Varnish 0.01 NEG East Fair White 0.06 NEG East Fair White 0.01 NEG
South Fair Grey 0.01 NEG North Fair White 1.49 POS North Fair White 0.50 NEG East Fair Grey 0.01 NEG East Fair Grey 0.01 NEG East Fair Grey 0.55 NEG North Fair Grey 0.01 NEG North Fair Tan 0.01 NEG North Fair White 0.01 NEG Center Fair Tan 0.01 NEG East Fair Tan 0.01 NEG North Fair Tan 0.44 NEG West Fair White 0.01 NEG West Fair White 0.01 NEG East Fair White 0.01 NEG East Fair White 0.01 NEG East Fair White 0.01 NEG
1694 Hall Ledge Wood 1693 Hall Panel Wood
1690 Janitor's Closet Wall Drywall 1689 Janitor's Closet Ceiling Drywall
1692 Hall Opening Casing (Window) Wood 1691 Janitor's Closet Wall Concrete
1686 Room 118 Heater Metal 1685 Room 118 Opening Ledge Wood
1688 Hall Ceiling Drywall 1687 Room 118 Heater Metal
1682 Room 118 Window Casing Wood 1681 Room 118 Window Sill Wood
1684 Room 118 Opening Panel (Window) Wood 1683 Room 118 Casing Wood
1678 Room 117 Door Casing Wood 1677 Room 117 Door Wood
1680 Room 118 Wall Drywall 1679 Room 117 Door Jamb Wood
1674 Room 117 Window Sill Wood 1673 Room 117 Muntin Wood
1676 Room 117 Heater Cover Metal 1675 Room 117 Window Casing Wood
1669 Room 13B Wall Drywall
1672 Room 117 Window Frame Wood 1671 Room 117 Wall Drywall
1696 Half Wall Door Jamb
Post Calibration
PbL (mg/cm²)XRF Analyzer XL3t 300 (Serial #96588)
Per 20 Second Reading
1668 Room 13B Door Wood 1667 Room 13B Door Jamb Metal
Pre Calibration PbL (mg/cm²) Calibration
Range Model# Serial #
XL Number Room/Area Structure
Per 20 Second Reading
Calibration Range
Substrate
Hall Wood Wood
Half Wall TopHall
Room 13B Duct Metal
1664 1.12 1745 0.91 1665 0.92 1746 1.01
1666 1.18 POS 1747 1.03
Range: .8 to 1.2 Paint Range: .8 to 1.2 Side Condition Color PbL(mg/cm2) NEG/POS
North Fair Tan 3.01 POS North Fair Tan 5.18 POS Center Fair Tan 0.01 NEG North Fair White 0.01 NEG North Fair Yellow 0.50 NEG North Fair White 2.58 POS North Fair White 5.08 POS North Fair White 3.18 POS North Fair White 0.02 NEG Center Fair White 0.02 NEG North Fair White 0.01 NEG North Fair White 2.25 POS North Fair White 0.89 POS North Fair White 1.63 POS South Fair Green 4.81 POS South Fair Green 0.41 NEG Center Fair Green 0.08 NEG South Fair Green 3.99 POS North Fair White 2.96 POS South Fair White 0.23 NEG North Fair Tan 0.46 NEG West Fair White 0.01 NEG South Fair White 0.01 NEG West Fair Off-White 0.01 NEG West Fair White 0.01 NEG West Fair Varnish 0.01 NEG North Fair Brown 0.01 NEG East Fair Varnish 0.01 NEG North Fair Varnish 0.01 NEG East Fair Tan 5.65 POS
Pre Calibration PbL (mg/cm²) Calibration
Range Model# Serial # Post
Calibration PbL
(mg/cm²) Calibration
RangeXRF Analyzer XL3t 300 (Serial #96588)
Per 20 Second Reading
Per 20 Second Reading
XL Number Room/Area Structure Substrate 1697 Men's Restroom 4" Wall Tile Ceramic 1698 Men's Restroom Cove Tile Ceramic 1699 Men's Restroom 1" Floor Tile Ceramic 1700 Men's Restroom Wall Drywall 1701 Men's Restroom Partition Metal 1702 Men's Restroom Urinal Porcelain 1703 Men's Restroom Sink Porcelain 1704 Men's Restroom Toilet Porcelain 1705 Men's Restroom Ceiling Drywall 1706 Women's Restroom Ceiling Drywall 1707 Women's Restroom Wall Drywall 1708 Women's Restroom Window Casing Wood 1709 Women's Restroom Window Frame Wood 1710 Women's Restroom Window Sill Wood 1711 Women's Restroom 4" Wall Tile Ceramic 1712 Women's Restroom Partition Metal 1713 Women's Restroom 1" Floor Tile Ceramic 1714 Women's Restroom Cove Tile Ceramic 1715 Women's Restroom Toilet Porcelain 1716 Women's Restroom Sink Porcelain 1717 Room 121 Wall Concrete 1718 Room 121 Wall Drywall 1719 Room 121 Wall Drywall 1720 Room 122 Door Metal 1721 Room 122 Wall Drywall 1722 Room 122 Chair Rail Wood 1723 Room 112 Baseboard Wood 1724 Room 112 Cabinet Wood 1725 Room 107 Chair Rail Wood 1726 Room 115 Wall Concrete
1664 1.12 1745 0.91 1665 0.92 1746 1.01
1666 1.18 POS 1747 1.03
Range: .8 to 1.2 Paint Range: .8 to 1.2 Side Condition Color PbL(mg/cm2) NEG/POS
Center Fair Yellow 0.01 NEG Center Fair White 0.01 NEG South Fair Red 0.40 NEG West Fair Blue 0.01 NEG North Fair Off-White 0.01 NEG South Fair Off-White 0.01 NEG East Fair Off-White 0.02 NEG West Fair Tan 0.01 NEG South Fair Red 0.02 NEG South Fair Grey 0.01 NEG North Fair White 0.01 NEG North Fair White 0.01 NEG Center Fair Grey 0.01 NEG East Fair Grey 0.01 NEG East Fair Grey 0.01 NEG
Pre Calibration PbL (mg/cm²) Calibration
Range Model# Serial # Post
Calibration PbL
(mg/cm²) Calibration
RangeXRF Analyzer XL3t 300 (Serial #96588)
Per 20 Second Reading
Per 20 Second Reading
XL Number Room/Area Structure Substrate 1727 Mechanical 3" Floor Tile Concrete 1728 Mechanical 3" Floor Tile Concrete 1729 Mechanical 3" Floor Tile Concrete 1730 Mechanical Wall Board Wood 1731 Room 106 Wall Concrete 1732 Room 106 Structural Post Metal 1733 Room 106 Floor Angle Metal 1734 Building 1273 Wall Block 1735 Building 1273 Structural Steel Metal 1736 Building 1273 Structural Steel Metal 1737 Building 1273 Door Metal 1738 Building 1273 Door Jamb Metal 1739 Building 1273 Floor Concrete 1740 Building 1273 Rollup Door Metal 1741 Building 1273 Rollup Door Channel Metal
1798 0.80 1861 0.88 1799 0.94 1862 0.83
1800 1.01 POS 1863 0.98
Range: .8 to 1.2 Paint Range: .8 to 1.2 Side Condition Color PbL(mg/cm2) NEG/POS East Good White 0.01 NEG East Good Brown 0.01 NEG East Good Brown 0.01 NEG North Good Blue 0.01 NEG North Good Blue 0.01 NEG North Good Varnish 0.01 NEG North Good White 0.01 NEG North Good Blue 0.01 NEG East Good Varnish 0.01 NEG East Good Blue 0.01 NEG East Good Tan 0.01 NEG East Good Blue 0.01 NEG West Good Varnish 0.01 NEG South Good Yellow 6.29 POS Center Good Light Yellow 0.09 NEG Center Good Light Yellow 0.01 NEG Center Good Brown 0.04 NEG Center Good Brown 0.01 NEG Center Good Yellow 0.39 NEG Center Good Yellow 12.14 POS
East Good Off-White 0.01 NEG Center Good Brown 0.34 NEG Center Good Yellow 0.26 NEG Center Good Yellow 0.01 NEG Center Good Yellow 0.01 NEG Center Good Brown 0.01 NEG East Good Off-White 0.01 NEG West Poor Brown 0.4 NEG West Poor Tan 0.01 NEG West Fair Tan 0.12 NEG
Pre Calibration PbL (mg/cm²) Calibration
Range Model# Serial # Post
Calibration PbL
(mg/cm²) Calibration
RangeXRF Analyzer XL3t 300 (Serial #96588)
Per 20 Second Reading
Per 20 Second Reading
XL Number Room/Area Structure Substrate 1801 Room 12 Wall Drywall 1802 Room 12 Door Frame Metal 1803 Room 12 Door Metal 1804 Room 12 Door Frame Wood 1805 Room 12 Door Casing Wood 1806 Room 12 Door Wood 1807 Room 12B Wall Textured Drywall 1808 Room 5 Door Frame Metal 1809 Room 5 Door Wood 1810 Room 4 Door Jamb Metal 1811 Room 4 Door Jamb Metal 1812 Room 4 Chair Rail Wood 1813 Room 6B Chair Rail Wood 1814 Men's Restroom 4" Wall Tile Ceramic 1815 Men's Restroom 2" Floor Tile Ceramic 1816 Men's Restroom 2" Floor Tile Ceramic 1817 Men's Restroom 2" Floor Tile Ceramic 1818 Men's Restroom Partition Metal 1819 Men's Restroom Partition Metal 1820 Women's Restroom 4" Wall Tile Ceramic 1821 Women's Restroom Wall Drywall 1822 Women's Restroom Partition Metal 1823 Women's Restroom Partition Metal 1824 Women's Restroom 2" Floor Tile Drywall 1825 Women's Restroom 2" Floor Tile Drywall 1826 Women's Restroom 2" Floor Tile Drywall 1827 Conference Room 8 Wall Drywall 1828 Exterior Wall Concrete 1829 Exterior Wall Concrete 1830 Exterior Wall Block
1798 0.80 1861 0.88 1799 0.94 1862 0.83
1800 1.01 POS 1963 0.98
Range: .8 to 1.2 Paint Range: .8 to 1.2 Side Condition Color PbL(mg/cm2) NEG/POS West Fair Brown 0.01 NEG West Fair Brown 0.01 NEG West Fair Yellow 0.56 NEG West Good Black 0.01 NEG South Poor Brown 6.59 POS East Poor Brown 0.34 NEG East Poor Yellow 0.42 NEG East Poor Yellow 0.01 NEG West Fair Brown 0.01 NEG West Fair Brown 0.03 NEG West Poor Brown 0.12 NEG East Poor Brown 0.08 NEG East Good White 0.01 NEG East Good Blue 0.01 NEG East Good Blue 0.01 NEG East Good Varnish 0.01 NEG North Good Off-White 0.01 NEG North Good Green 0.35 NEG North Good Green 0.02 NEG South Good Tan 0.01 NEG
Pre Calibration PbL (mg/cm²) Calibration
Range Model# Serial # Post
Calibration PbL
(mg/cm²) Calibration
RangeXRF Analyzer XL3t 300 (Serial #96588)
Per 20 Second Reading
Per 20 Second Reading
XL Number Room/Area Structure Substrate 1831 Exterior Awning Post Metal 1832 Exterior Gutter Metal 1833 Exterior Gutter Metal 1834 Exterior Handrail Metal 1835 Southeast Exterior Handrail Metal 1836 Southeast Exterior Guardrail Metal 1837 Southeast Exterior Window Apron Metal 1838 Exterior Gutter Spout Metal 1839 West Center Exterior Ladder Metal 1840 West Center Exterior Awning Post Metal 1841 West Center Exterior Handrail Metal 1842 East Center Exterior Handrail Metal 1843 Room 6A Wall Drywall 1844 Room 6A Door Frame Wood 1845 Room 6A Door Trim Wood
1849 Room 9 Vault Door Metal 1850 Room 9 Back Room Wall Drywall
1846 Room 6A Door Wood 1847 Comm Room Wall Drywall 1848 Room 9 Vault Door Jamb Metal
| Title Page |
| Asbestos |
| LBP |
| Readings |
| 2020-01-02T13:20:51-0700 | |
| BRIMBERRY.TAYLOR.MIKE.1543589558 |
| GM200108: |
| North Center Room 118: |
| GM200109: |
| East Center Room 117: |
| GM200148: |
| West Room 117 Exterior: |
| GM200149: |
| North Room 117 Exterior: |
| GM200150: |
| North Room 118 Exterior: |
| GM200151: |
| Southwest: |
| GM200152: |
| Northwest: |
| GM200153: |
| Southeast: |
| GM200154: |
| Southwest_2: |
| GM200155: |
| South Center: |
| Wire Insulation Black Room 8 10 Linear Feet: |
| GM200072: |
| South Center_2: |
| None Detected: |
| Range 8 to 12: |
| Range 8 to 12_2: |
| Range 8 to 12_3: |
| Range 8 to 12_4: |
| Range 8 to 12_5: |