This document provides information on an upcoming federal construction contract opportunity for the Utah Test and Training Range Consolidated Mission Control Center at Hill Air Force Base, Utah. The Army Corps of Engineers intends to issue a request for proposal for a firm-fixed-price construction contract between $25-100 million to build a new consolidated mission control center facility to replace outdated infrastructure and enable greater flexibility for air traffic control and post-mission evaluation. Interested vendors should monitor the beta.SAM.gov website for the solicitation anticipated for release on or around September 10, 2020, with proposals due tentatively on October 12, 2020. The period of performance is estimated at 852 days. NAICS code 236220 for commercial and institutional building construction applies, with a size standard of $36.5 million.

View the file

Other files for this federal contract opportunity

Show all 16

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LEAD BASED PAINT

ASBESTOS

LIMITED INSPECTION REPORT

Utah Certified State Inspector: Raudel Arteaga (ASB#-5863: Expires-25 October 2020, PB#-2244: Expires-6 November 2022)

INSPECTION DATE: 01 November 2019

Reference UDAQ R307-807-6

DEPARTMENT OF THE AIR FORCE

75TH CIVIL ENGINEERING (CEOHA)

HILL AIR FORCE BASE, UTAH

75 CEG

FACILITY CONSTRUCTION DATE:

WORK TASK #:

FACILITY:

REQUESTER:

09 September 2019

(This inspection is valid for three years from the inspection date regardless of Exp. Date of inspector cert. If past this date, a visual or additional assessment will then be required)

SIGNATURE:

PREPARED BY: Taylor Brimberry (ASB#-6727, PB#-2546)

DEMOLISH BUILDING

THIS REPORT IS NOT TO BE USED FOR BIDDING PURPOSES

ORGANIZATION:

REQUESTED:

6471282

RICHARD NEHRING

ASBESTOS

6% Chrysotile (Via Point

Count) 2%

Chrysotile (Via Point

Count) 3%

Chrysotile (Via Point

Count) 2%

Chrysotile (Via Point

Count)

Assumed

Assumed

Assumed

Assumed

Category INon-Friable

Civil Engineering personnel also reviewed previous asbestos inspection reports of suspect asbestos containing materials (ACM) that could potentially be encountered in the proposed area/areas. The information gathered from all current and previous inspections is shown below by homogenous area (R307-801-9-4).

Window Putty, Tan Non-Friable Category II 200 Square

Feet

Rooms 117 And 118 Exterior Windows and Northwest Door

Windows

Block Filler Paint, Brown/Concrete

Cloth Vibration Collar, White

Friable RACM 200 Linear

Feet AHU's Throughout The Attic

Non-Friable Category II 1,500 Square

Feet Exterior Of The Building

Block Filler Paint, Tan/Concrete

Demolish Building.Statement of Work:

DEPARTMENT OF THE AIR FORCE

75 CIVIL ENGINEERING (CEOHA)

HILL AIR FORCE BASE, UTAH

The quantities within this report are estimates and are not to be used for bidding purposes.

Table 1

SUMMARY OF ASBESTOS CONTAINING MATERIALS FOUND

MATERIAL TYPE

Rooms 117, 118, North Hallway and North Restrooms

*RACM

*Category I *Category II

FRIABILITY QUANTITY

1,200 Square Feet

LIMITED ASBESTOS INSPECTION REPORT INFORMATION

This inspection was performed in accordance with the Utah Division of Air Quality (DAQ) requirements as found in the Utah Air Quality Rule R307-801-10. This inspection report is required to be on site during all abatement, renovation, and demolition activities. Samples referenced in this report were analyzed by polarized light microscopy (PLM) utilizing method 600R-93-116 by The Science and Engineering Laboratory (AIHA Acc.#-

101572) at Hill Air Force Base, Utah (R307-801-10.8.a-b).

Carpet Adhesive, Yellow/ 9" Floor Tile, Tan/ Adhesive, Black

*LOCATIONS FOUND

Non-Friable Category II 12,500

Square Feet Exterior Of The Building

Thermal System Hard Pipe Fittings, White Friable RACM

150 Linear feet

Possibly Throughout The Attic, Pipe Chases And In The Walls

Asbestos Cement Pipe (Transite)

Non-Friable Category II 500 Linear

Feet Possible Buried Lines

Conduit And/Or Pipe Coatings

Non-Friable Category II 500 Linear

Feet Possible Buried Lines

12" Acoustical Ceiling Tile, Wormygrooves/Pinholes Pattern, White/ Puck, Brown 12" Acoustical Ceiling Tile, Heavy Textured Pattern, Off-White/Puck, Brown

*Per UDAQ definition.

Per EPA requirements, all materials analyzed as containing ≤10% asbestos are point counted utilizing EPA method 600/R-93/116 this information is summarized in Table 2.

Table 2.

ASBESTOS

RACM: Regulated Asbestos-Containing Material (RACM)" means friable ACM, Category I non-friable ACM that has become friable, Category I non-friable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading, or Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material in the course of demolition or renovation project operations.

Locations found: Locations of building materials as described in this report indicate where they were found, but do not necessarily mean that these are the only locations where these materials may be encountered during the project.

Category II Non-Friable ACM: Any material, excluding Category I non- friable ACM, containing more than 1% asbestos as determined by using the methods specified in 40 CFR Part 763, Subpart E, Appendix E, Section 1, Polarized Light Microscopy (PLM) that, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure.

*LOCATIONS FOUND

N/A N/A

Cove Base, Brown/Adhesive, Black 12" Floor Tile, Off-White/Adhesive, Yellow

MATERIAL TYPE

Per Hill AFB requirements, all materials containing any detectable amount of asbestos shall be handled as Asbestos Containing Material (ACM). Table 2 shows the summary of materials containing ≤1% that were identified via "Point Counting". Per EPA/UDAQ

≤1% is not considered to be an asbestos containing material, but special handling/packaging requirements are necessary per OSHA 29CFR 1926.1101 and

29CFR 1910.1001

QUANTITY

N/A

Category I Non-Friable ACM: Asbestos-containing packings, gaskets, resilient floor coverings, or asphalt roofing products containing more than 1% asbestos as determined by using the method specified in 40 CFR Part 763, Subpart E, Appendix E, Section 1, Polarized Light Microscopy (PLM).

The following is a list of the "Suspect Materials" that were sampled as part of this inspection:

N/A

Carpet Adhesive, Yellow/9" Floor Tile, Tan/Adhesive, Black12" Floor Tile, Tan/Adhesive, Yellow/Brown Linoleum, Tan/Adhesive, Black Floor Level, Grey

Drywall/Joint Compound Ceiling System Textured Drywall/Joint Compound Wall System

Wall Noise Insulation, Black Duct Insulation, Foil/Yellow Duct Insulation, Foil/White Flex Duct Insulation, Black/Pink

Flex Duct Insulation, Grey/Yellow Vibration Collar, White

Drywall/Joint Compound Wall System Roofing Debris, Black Window Putty, Tan Block Filler Paint/Concrete, Brown

Roof Batt Insulation, Foil/Pink Roof Batt Insulation, Foil/Yellow Wall Batt Insulation, Brown/Pink Wall Batt Insulation, White/Pink

Wall Batt Insulation, Foil/Off-White Wall Batt Insulation, White/Yellow

Insulation Debris, Black Gasket, Black Thermal System Pipe Insulation Lagging, White/Yellow Thermal System Pipe Insulation, White/Yellow Thermal System Pipe Insulation Lagging, White/White Thermal System Pipe Fitting Insulation, White/White

Thermal System Tank Insulation, White/Yellow Sound Board, Brown Wire Insulation, Off-White/Black Wire Insulation, Black

A total of 149 46 suspect materials assessed as part of the inspection.

Sample # samples reference the Table 3.

The following table summarizes the sampling data.

Homogenous Building Material, Description, ResultsSample Location GM200100 Southeast None Detected GM200101 Southwest None Detected GM200102 Southwest None Detected GM200103 Southwest None Detected GM200104 Southwest None Detected

GM200105 Southwest, South Hall None Detected

GM200106 Southeast, South Janitor's None Detected

GM200107 Southwest, Room 14 None Detected

GM200108 North Center, Room 118 6% Chrysotile

(Via Point Count)

GM200109 East Center, Room 117 5% Chrysotile

(Via Point Count) GM200110 West Center, Room 117 5% Chrysotile GM200111 Southwest None Detected GM200112 Southeast None Detected

GM200113 North Center None Detected

Floor Level, Grey, Room 120, 1,200 Square Feet

GM200114 West Center None Detected

Northeast, Room 110 None Detected

GM200115 Southeast, Women's None Detected GM200116 Northeast, Men's None Detected GM200117 North Center, Men's None Detected

12" Acoustical Ceiling Tile, Textured Pattern, Black Over Puck, Brown, Room 9 Vault 2, 450

Square Feet

GM200121 Southwest, Room 112 None Detected

GM200122 East Center, Room 120 None Detected

GM200123

North Center, North Break

Room None Detected

GM200545 Southwest None Detected

GM200546 Southeast None Detected GM200073 North Center, Room 4 None Detected

2'x4' Ceiling Tile, Pockmarks/Pinholes Pattern, White, Multiple Locations 6,500 Square Feet

GM200074 Southwest, Room 5 None Detected GM200075 Northeast, Room 6B None Detected GM200076 Northwest, Room 122 None Detected GM200077 Northwest, Room 120 None Detected GM200078 Northeast, Room 121 None Detected

Cove Base, Brown/Adhesive, Black, Room 110, 5,000 Linear Feet

12" Floor Tile, Off-White Over Adhesive, Yellow, Room 120, 2,500 Square Feet

12" Floor Tile, Tan Over Adhesive, Yellow, Multiple Locations, 2,500 Square Feet

Carpet Adhesive, Yellow/9" Floor Tile, Tan Over Adhesive, Black, Multiple Locations, 1,200 Square Feet

Linoleum, Tan Over Adhesive, Black, North Janitor's Closet, 40 Square Feet

12" Acoustical Ceiling Tile, Heavy Textured Pattern, Off-White Over Puck, Brown, North

Restroom Entries, 120 Square Feet

12" Acoustical Ceiling Tile, Wormygrooves/Pinholes Pattern, White Over Puck, Brown, Multiple Locations, 6,500 Square

Feet

2'x4' Ceiling Tile, Pockmarks/Pinholes Pattern, White 2'x4' Ceiling Tile, Wormygrooves/Pinholes, White 2'x4' Simulated Ceiling Tile, Textured Pattern, White 2'x2' Ceiling Tile, Textured Pattern, White

Portable Wall Panel, Brown Stanchion Adhesive, Black Block Filler Paint/Concrete, Tan Roof Decking, Black

Roof Flashing, Black 12" Textured Acoustical Ceiling Tile, Black/Puck, Brown

GM200118 Southwest, Room 13B None Detected GM200119 Northwest, Room 108 None Detected

GM200120

GM200079 West Center, Room 5 None Detected

2'x4' Ceiling Tile, Wormygrooves/Pinholes Pattern, White, Multiple Locations 7,000

Square Feet GM200083 Northeast, Room 6B None Detected GM200084 Northwest, Room 108 None Detected GM200085 Center, Room 106 None Detected

GM200080 South Center, Room 8 None Detected GM200081 North Center, Room 2 None Detected GM200082 West Center, Room 4 None Detected

GM200086 West Center, Room 121 None Detected GM200087 Southwest, Room 121 None Detected GM200088 Center, Room 12 None Detected

2'x4' Simulated Ceiling Tile, Textured Pattern, White, Multiple Locations, 4,000 Square Feet

GM200089 West Center, Room 12 None Detected GM200090 South Center, South Hall None Detected GM200091 Northeast, Room 12 None Detected GM200092 East Center, Room 8 None Detected

GM200124

Southwest, South Janitor's

Closet None Detected

GM200125

Southeast, Hall Outside

Room 112 None Detected

2'x2' Ceiling Tile, Textured pattern, White, North Half Main Hallway, 2,500 Square Feet

Drywall/Joint Compound Ceiling System, Multiple Locations, 1,300 Square Feet

GM200126

Northwest, North Men's

Restroom None Detected

GM200127 North Center, North None Detected

GM200093 Center None Detected GM200094 South Center None Detected

GM200095 North Center None Detected

GM200128 Northeast None Detected Textured Drywall/Joint Compound Wall

System, Room 8, 935 Square Feet GM200129 Northwest None Detected GM200130 Southwest None Detected GM200131 Northwest, Room 4 None Detected

Drywall/Joint Compound Wall System, Multiple Locations, 53,000 Square Feet

GM200132 West Center, Room 6 None Detected GM200133 Northeast, Room 112 None Detected GM200134 North Center, Room 12 None Detected GM200135 Southwest, Room 13B None Detected GM200136 Southwest, Room 108 None Detected GM200137 Southeast, Room 109 None Detected GM200138 Southwest, Room 110 None Detected GM200139 Southeast, Room 139 None Detected GM200140 Southwest, Room 120 None Detected GM200141 Northwest, Room 120 None Detected

GM200142 West Center, Room 121 None Detected

GM200143

Northwest, Janitor's

Closet None Detected

GM200144 Southeast, North None Detected

GM200542 Southwest, Room 6A None Detected

GM200543 Southeast, Room 9 Vault 2 None Detected

GM200544 Southeast, None Detected

West Center, Room 5 None Detected

Roof Batt Insulation, Foil Over Yellow, Multiple Locations, 16, 250 Square Feet

Wall Batt Insulation, Brown Over Pink, Multiple Locations, 20,000 Square Feet

GM200027 East Center, Room 8 None Detected

GM200028 West Center, Room 12 None Detected

GM200029

Southwest, Southwest

Entry None Detected

GM200022 West Center, Room 121 None Detected GM200023 Northwest, Room 122 None Detected GM200024 Northwest, Room 122 None Detected GM200025 South Center, South Hall None Detected

GM200026

Wall Batt Insulation, White Over Pink, Room 003, 400 Square Feet

GM200030 North Center None Detected

GM200031 South Center, South Hall None Detected GM200032 South Center, Room 8 None Detected

Wall Batt Insulation, Foil Over Off-White, Multiple Locations, 15,000 Square Feet

GM200033 South Center, Room 8 None Detected

GM200536 South Center None Detected GM200537 South Center None Detected

Roof Decking, Black, Fire Riser Shed, 50 Square Feet

GM200538 South Center None Detected GM200539 South Center None Detected GM200540 South Center None Detected

Roof Flashing, Black, Fire Riser Shed, 25 Linear Feet

GM200541 South Center None Detected GM200145 Center, MCC Attic None Detected

GM200146 South Center, MCC Attic None DetectedRoofing Debris, Black, Multiple Locations, 1,500 Feet

GM200147

Northwest, Room 117

Attic None Detected

GM200148 West, Room 117 Exterior 2% Chrysotile

(Via Point Count)

GM200149 North, Room 117 Exterior 1% Chrysotile

(Via Point Count) Window Putty, Tan, Multiple Locations, 200

Square Feet

GM200150 North, Room 118 Exterior 1% Chrysotile

(Via Point Count)

GM200151 Southwest 3% Chrysotile

(Via Point Count)

GM200152 Northwest 2% Chrysotile

(Via Point Count) Block Filler Paint, Brown Over Concrete, Exterior Of The Building, 1,500 Square Feet

GM200153 Southeast 3% Chrysotile

(Via Point Count)

GM200154 Southwest 2% Chrysotile

(Via Point Count)

GM200155 South Center 2% Chrysotile

(Via Point Count)

Block Filler Paint Tan Over Concrete, Exterior Of The Building, 12, 500 Square Feet

GM200156 Northwest 2% Chrysotile

GM200019 East Center, Room 8 None Detected

GM200020 Southeast, Attic Room 13B None Detected Roof Batt Insulation, Foil Over Pink, Multiple

Locations, 16, 250 Square Feet GM200021 Northwest, Room 108 None Detected

GM200034 Northeast, Bldg.1274 None Detected GM200035 East Center, Bldg.1274 None DetectedWall Batt Insulation, White Over Yellow, Multiple Locations, 3,500 Square Feet GM200036 Southeast, Room 12 None Detected

Wall Noise Insulation, Black, Room 110, 300 Square Feet

GM200037 North Center None Detected

GM200038 Center None Detected Duct Insulation, Foil Over Yellow, Attic, 5,000

Linear Feet GM200039 North Center None Detected GM200040 North Center None Detected GM200041 West Center, Room 12 None Detected

Duct Insulation, Foil Over White, Multiple Locations, 2,000 Linear Feet

GM200042 North Center, Room 12 None Detected

GM200043

Southeast, Southwest

Mechanical Room None Detected

Duct Insulation, White Over Yellow, North Mechanical Room, 1,000 Linear Feet

GM200044 Northwest None Detected

GM200045 Southwest, South Hall None Detected GM200046 Southwest, South Entry None Detected GM200047 Southeast, Room 5 None Detected

Flex Duct Insulation, Black Over Pink, Multiple Locations, 1,500 Linear Feet

GM200048 South Center, Room 6 None Detected GM200049 North Center, Room 6 None Detected

GM200050 South Center, Room 12 None Detected

Flex Duct Insulation, Grey Over Yellow, Multiple Locations, 1,000 Linear Feet

Vibration Collar, White, North Restroom Attic, 20 Linear Feet

GM200051 Northeast None Detected

Insulation Debris, Black, Room 112, 50 Square Feet

GM200052 North Center None Detected

GM200056

Northeast, North Mechanical Room

None Detected

GM200057 West Center, Break Room None Detected

Thermal System Pipe Insulation Lagging, White Over Yellow, Multiple Locations, 500 Linear

Feet

Gasket, Black, North Mechanical Room, 10 Linear Feet

GM200053 North Unit None Detected

GM200054

Northeast, North Mechanical Room

None Detected

GM200055 Center, Room 108 Attic None Detected

GM200063

Center, North Mechanical

Room None Detected

GM200061

Northeast, South Mechanical Room

None Detected

Thermal System Pipe Insulation Lagging, White Over White, Multiple Locations, 100 Linear

Feet

GM200062

Northwest, South Mechanical Room

None Detected

Thermal System Pipe Insulation, White Over Yellow, Multiple Locations, 2,000 Linear Feet

GM200058

Northwest, North Mechanical Room

None Detected

GM200059

Northwest, Break Room

Closet None Detected

GM200060

Northwest, Break Room

Closet None Detected

GM200065 Northwest None Detected

GM200066 Northeast None Detected

Thermal System Pipe Fitting Insulation, White Over White, South Mechanical Room, 50

Linear Feet

GM200064 Northwest None Detected

Table 4.

POTENTIAL FOR ADDITIONAL MATERIALS:

This inspection report only encompasses the areas/materials designated within the scope of work that was provided at the date of inspection (see title page for inspection date). Should the scope of the project be altered in any way or any materials found that are not identified in this report shall require additional assessment. This report cannot be used for any other projects within the building.

Any questions or concerns regarding this inspection report or if any new suspect asbestos containing material (ACM) is encountered, stop work and contact the personnel listed below for further assistance/assessment.

GM200098 West Center None Detected

GM200099

Cell: (801)430-3976 Supervisor: Traver Andreasen: DSN: (801)586-7094

Asbestos/LBP Shop 75 CES(CEOHA)

Asbestos/LBP Shop Personnel

DSN:(801)777-8006

CONTACT INFORMATION

Southeast None Detected

Stanchion Adhesive, Black, Room 120, 300 Square Feet

Wire Insulation, Black, Room 8, 10 Linear Feet GM200072 South Center None Detected

Portable Wall Panel, Brown, Room 003, 400 Square Feet

GM200096 West None Detected

GM200097 Northeast None Detected

Sound Board, Brown, Multiple Location, 1,000 Square Feet

Thermal System Tank Insulation, White Over Yellow, North Mechanical Room, 250 Square

Feet GM200067 Southeast None Detected

GM200068 Southeast, Room 13B Attic None Detected

GM200069 Southeast, Room 13B Attic None Detected

GM200070

Southeast, MCC Room

Attic None Detected

Wire Insulation, Off-White Over Black, Room 8, 10 Linear Feet

GM200071 South Center None Detected

SCOPE OF WORK:

XL Number Substrate Component Color Lead Reading Paint

Condition 1672 Wood Window Frame Off-White 1.46 Fair 1673 Wood Muntin Off-White 1.95 Fair 1674 Wood Window Sill Green 1.33 Fair 1681 Wood Window Sill White 1.49 Fair 1697 Ceramic 4" Wall Tile Tan 3.01 Fair 1698 Ceramic Cove Tile Tan 5.18 Fair 1702 Porcelain Urinal White 2.58 Fair 1703 Porcelain Sink White 5.08 Fair 1704 Porcelain Toilet White 3.18 Fair 1708 Wood Window Casing White 2.25 Fair 1709 Wood Window Frame White 0.89 Fair 1710 Wood Window Sill White 1.63 Fair 1711 Ceramic 4" Wall Tile Green 4.81 Fair 1714 Ceramic Cove Tile Green 3.99 Fair 1715 Porcelain Toilet White 2.96 Fair 1726 Concrete Wall Tan 5.65 Fair

XRF Analyzer Used: XRF Analyzer XL3t 300 (Serial #96588)

LIMITED LEAD-BASED PAINT IDENTIFICATION REPORT INFORMATION

Table 1.

2-The condition column is the condition only of the painted/coated component (See final page for all readings/samples).

3-The U.S. Department of Housing and Urban Development defines Lead-based paint as any paint, varnish, stain, or other applied coating that has 1 mg/cm² as measured by an X-ray Fluorescence (XRF) Analyzer or laboratory analysis or 0.5 percent by weight (5,000 µg/g by dry weight) by laboratory analysis, or more of lead.

All other components tested were less than 0.80 mg/cm².

4-Any effort to disturb lead paint can create lead dust. Ensure that appropriate abatement, cleanup, and disposal will be accomplished and that appropriate safety measures are taken IAW 29 CFR 1926.62. If you have any questions concerning this report, contact the Asbestos/LBP Shop: Traver Andreasen at 586-7094.

DEPARTMENT OF THE AIR FORCE

75TH CIVIL ENGINEERING (CEOHA)

HILL AIR FORCE BASE, UTAH

1-Table 1 below, summarizes the painted/coated building components that tested positive for Lead Based Paint/Coating. These components should be segregated or abated prior to renovation or demolition, and a composite TCLP taken of the waste before disposal.

Demolish Building.

5-This inspection report only encompasses the areas/materials designated within the scope of work that was provided at the date of the inspection (see title page for date). This report must be modified should the scope of the project be altered in any way or additional materials not previously identified within this report are encountered. This report may not be used for any other projects within the building.

Building: 1274 WT/CP#: 6471282 Date: 20 September 2019

1664 1.12 1745 0.91 1665 0.92 1746 1.01

1666 1.18 POS 1747 1.03

Range: .8 to 1.2 Paint Range: .8 to 1.2 Side Condition Color PbL(mg/cm2) NEG/POS West Fair Brown 0.01 NEG West Fair Varnish 0.01 NEG North Fair White 0.01 NEG East Fair White 0.01 NEG

South Fair Green 0.01 NEG West Fair Off-White 1.46 POS West Fair Off-White 1.95 POS West Fair Green 1.33 POS West Fair Green 0.58 NEG West Fair Green 0.01 NEG South Fair Varnish 0.01 NEG East Fair White 0.06 NEG East Fair White 0.01 NEG

South Fair Grey 0.01 NEG North Fair White 1.49 POS North Fair White 0.50 NEG East Fair Grey 0.01 NEG East Fair Grey 0.01 NEG East Fair Grey 0.55 NEG North Fair Grey 0.01 NEG North Fair Tan 0.01 NEG North Fair White 0.01 NEG Center Fair Tan 0.01 NEG East Fair Tan 0.01 NEG North Fair Tan 0.44 NEG West Fair White 0.01 NEG West Fair White 0.01 NEG East Fair White 0.01 NEG East Fair White 0.01 NEG East Fair White 0.01 NEG

1694 Hall Ledge Wood 1693 Hall Panel Wood

1690 Janitor's Closet Wall Drywall 1689 Janitor's Closet Ceiling Drywall

1692 Hall Opening Casing (Window) Wood 1691 Janitor's Closet Wall Concrete

1686 Room 118 Heater Metal 1685 Room 118 Opening Ledge Wood

1688 Hall Ceiling Drywall 1687 Room 118 Heater Metal

1682 Room 118 Window Casing Wood 1681 Room 118 Window Sill Wood

1684 Room 118 Opening Panel (Window) Wood 1683 Room 118 Casing Wood

1678 Room 117 Door Casing Wood 1677 Room 117 Door Wood

1680 Room 118 Wall Drywall 1679 Room 117 Door Jamb Wood

1674 Room 117 Window Sill Wood 1673 Room 117 Muntin Wood

1676 Room 117 Heater Cover Metal 1675 Room 117 Window Casing Wood

1669 Room 13B Wall Drywall

1672 Room 117 Window Frame Wood 1671 Room 117 Wall Drywall

1696 Half Wall Door Jamb

Post Calibration

PbL (mg/cm²)XRF Analyzer XL3t 300 (Serial #96588)

Per 20 Second Reading

1668 Room 13B Door Wood 1667 Room 13B Door Jamb Metal

Pre Calibration PbL (mg/cm²) Calibration

Range Model# Serial #

XL Number Room/Area Structure

Per 20 Second Reading

Calibration Range

Substrate

Hall Wood Wood

Half Wall TopHall

Room 13B Duct Metal

1664 1.12 1745 0.91 1665 0.92 1746 1.01

1666 1.18 POS 1747 1.03

Range: .8 to 1.2 Paint Range: .8 to 1.2 Side Condition Color PbL(mg/cm2) NEG/POS

North Fair Tan 3.01 POS North Fair Tan 5.18 POS Center Fair Tan 0.01 NEG North Fair White 0.01 NEG North Fair Yellow 0.50 NEG North Fair White 2.58 POS North Fair White 5.08 POS North Fair White 3.18 POS North Fair White 0.02 NEG Center Fair White 0.02 NEG North Fair White 0.01 NEG North Fair White 2.25 POS North Fair White 0.89 POS North Fair White 1.63 POS South Fair Green 4.81 POS South Fair Green 0.41 NEG Center Fair Green 0.08 NEG South Fair Green 3.99 POS North Fair White 2.96 POS South Fair White 0.23 NEG North Fair Tan 0.46 NEG West Fair White 0.01 NEG South Fair White 0.01 NEG West Fair Off-White 0.01 NEG West Fair White 0.01 NEG West Fair Varnish 0.01 NEG North Fair Brown 0.01 NEG East Fair Varnish 0.01 NEG North Fair Varnish 0.01 NEG East Fair Tan 5.65 POS

Pre Calibration PbL (mg/cm²) Calibration

Range Model# Serial # Post

Calibration PbL

(mg/cm²) Calibration

RangeXRF Analyzer XL3t 300 (Serial #96588)

Per 20 Second Reading

Per 20 Second Reading

XL Number Room/Area Structure Substrate 1697 Men's Restroom 4" Wall Tile Ceramic 1698 Men's Restroom Cove Tile Ceramic 1699 Men's Restroom 1" Floor Tile Ceramic 1700 Men's Restroom Wall Drywall 1701 Men's Restroom Partition Metal 1702 Men's Restroom Urinal Porcelain 1703 Men's Restroom Sink Porcelain 1704 Men's Restroom Toilet Porcelain 1705 Men's Restroom Ceiling Drywall 1706 Women's Restroom Ceiling Drywall 1707 Women's Restroom Wall Drywall 1708 Women's Restroom Window Casing Wood 1709 Women's Restroom Window Frame Wood 1710 Women's Restroom Window Sill Wood 1711 Women's Restroom 4" Wall Tile Ceramic 1712 Women's Restroom Partition Metal 1713 Women's Restroom 1" Floor Tile Ceramic 1714 Women's Restroom Cove Tile Ceramic 1715 Women's Restroom Toilet Porcelain 1716 Women's Restroom Sink Porcelain 1717 Room 121 Wall Concrete 1718 Room 121 Wall Drywall 1719 Room 121 Wall Drywall 1720 Room 122 Door Metal 1721 Room 122 Wall Drywall 1722 Room 122 Chair Rail Wood 1723 Room 112 Baseboard Wood 1724 Room 112 Cabinet Wood 1725 Room 107 Chair Rail Wood 1726 Room 115 Wall Concrete

1664 1.12 1745 0.91 1665 0.92 1746 1.01

1666 1.18 POS 1747 1.03

Range: .8 to 1.2 Paint Range: .8 to 1.2 Side Condition Color PbL(mg/cm2) NEG/POS

Center Fair Yellow 0.01 NEG Center Fair White 0.01 NEG South Fair Red 0.40 NEG West Fair Blue 0.01 NEG North Fair Off-White 0.01 NEG South Fair Off-White 0.01 NEG East Fair Off-White 0.02 NEG West Fair Tan 0.01 NEG South Fair Red 0.02 NEG South Fair Grey 0.01 NEG North Fair White 0.01 NEG North Fair White 0.01 NEG Center Fair Grey 0.01 NEG East Fair Grey 0.01 NEG East Fair Grey 0.01 NEG

Pre Calibration PbL (mg/cm²) Calibration

Range Model# Serial # Post

Calibration PbL

(mg/cm²) Calibration

RangeXRF Analyzer XL3t 300 (Serial #96588)

Per 20 Second Reading

Per 20 Second Reading

XL Number Room/Area Structure Substrate 1727 Mechanical 3" Floor Tile Concrete 1728 Mechanical 3" Floor Tile Concrete 1729 Mechanical 3" Floor Tile Concrete 1730 Mechanical Wall Board Wood 1731 Room 106 Wall Concrete 1732 Room 106 Structural Post Metal 1733 Room 106 Floor Angle Metal 1734 Building 1273 Wall Block 1735 Building 1273 Structural Steel Metal 1736 Building 1273 Structural Steel Metal 1737 Building 1273 Door Metal 1738 Building 1273 Door Jamb Metal 1739 Building 1273 Floor Concrete 1740 Building 1273 Rollup Door Metal 1741 Building 1273 Rollup Door Channel Metal

1798 0.80 1861 0.88 1799 0.94 1862 0.83

1800 1.01 POS 1863 0.98

Range: .8 to 1.2 Paint Range: .8 to 1.2 Side Condition Color PbL(mg/cm2) NEG/POS East Good White 0.01 NEG East Good Brown 0.01 NEG East Good Brown 0.01 NEG North Good Blue 0.01 NEG North Good Blue 0.01 NEG North Good Varnish 0.01 NEG North Good White 0.01 NEG North Good Blue 0.01 NEG East Good Varnish 0.01 NEG East Good Blue 0.01 NEG East Good Tan 0.01 NEG East Good Blue 0.01 NEG West Good Varnish 0.01 NEG South Good Yellow 6.29 POS Center Good Light Yellow 0.09 NEG Center Good Light Yellow 0.01 NEG Center Good Brown 0.04 NEG Center Good Brown 0.01 NEG Center Good Yellow 0.39 NEG Center Good Yellow 12.14 POS

East Good Off-White 0.01 NEG Center Good Brown 0.34 NEG Center Good Yellow 0.26 NEG Center Good Yellow 0.01 NEG Center Good Yellow 0.01 NEG Center Good Brown 0.01 NEG East Good Off-White 0.01 NEG West Poor Brown 0.4 NEG West Poor Tan 0.01 NEG West Fair Tan 0.12 NEG

Pre Calibration PbL (mg/cm²) Calibration

Range Model# Serial # Post

Calibration PbL

(mg/cm²) Calibration

RangeXRF Analyzer XL3t 300 (Serial #96588)

Per 20 Second Reading

Per 20 Second Reading

XL Number Room/Area Structure Substrate 1801 Room 12 Wall Drywall 1802 Room 12 Door Frame Metal 1803 Room 12 Door Metal 1804 Room 12 Door Frame Wood 1805 Room 12 Door Casing Wood 1806 Room 12 Door Wood 1807 Room 12B Wall Textured Drywall 1808 Room 5 Door Frame Metal 1809 Room 5 Door Wood 1810 Room 4 Door Jamb Metal 1811 Room 4 Door Jamb Metal 1812 Room 4 Chair Rail Wood 1813 Room 6B Chair Rail Wood 1814 Men's Restroom 4" Wall Tile Ceramic 1815 Men's Restroom 2" Floor Tile Ceramic 1816 Men's Restroom 2" Floor Tile Ceramic 1817 Men's Restroom 2" Floor Tile Ceramic 1818 Men's Restroom Partition Metal 1819 Men's Restroom Partition Metal 1820 Women's Restroom 4" Wall Tile Ceramic 1821 Women's Restroom Wall Drywall 1822 Women's Restroom Partition Metal 1823 Women's Restroom Partition Metal 1824 Women's Restroom 2" Floor Tile Drywall 1825 Women's Restroom 2" Floor Tile Drywall 1826 Women's Restroom 2" Floor Tile Drywall 1827 Conference Room 8 Wall Drywall 1828 Exterior Wall Concrete 1829 Exterior Wall Concrete 1830 Exterior Wall Block

1798 0.80 1861 0.88 1799 0.94 1862 0.83

1800 1.01 POS 1963 0.98

Range: .8 to 1.2 Paint Range: .8 to 1.2 Side Condition Color PbL(mg/cm2) NEG/POS West Fair Brown 0.01 NEG West Fair Brown 0.01 NEG West Fair Yellow 0.56 NEG West Good Black 0.01 NEG South Poor Brown 6.59 POS East Poor Brown 0.34 NEG East Poor Yellow 0.42 NEG East Poor Yellow 0.01 NEG West Fair Brown 0.01 NEG West Fair Brown 0.03 NEG West Poor Brown 0.12 NEG East Poor Brown 0.08 NEG East Good White 0.01 NEG East Good Blue 0.01 NEG East Good Blue 0.01 NEG East Good Varnish 0.01 NEG North Good Off-White 0.01 NEG North Good Green 0.35 NEG North Good Green 0.02 NEG South Good Tan 0.01 NEG

Pre Calibration PbL (mg/cm²) Calibration

Range Model# Serial # Post

Calibration PbL

(mg/cm²) Calibration

RangeXRF Analyzer XL3t 300 (Serial #96588)

Per 20 Second Reading

Per 20 Second Reading

XL Number Room/Area Structure Substrate 1831 Exterior Awning Post Metal 1832 Exterior Gutter Metal 1833 Exterior Gutter Metal 1834 Exterior Handrail Metal 1835 Southeast Exterior Handrail Metal 1836 Southeast Exterior Guardrail Metal 1837 Southeast Exterior Window Apron Metal 1838 Exterior Gutter Spout Metal 1839 West Center Exterior Ladder Metal 1840 West Center Exterior Awning Post Metal 1841 West Center Exterior Handrail Metal 1842 East Center Exterior Handrail Metal 1843 Room 6A Wall Drywall 1844 Room 6A Door Frame Wood 1845 Room 6A Door Trim Wood

1849 Room 9 Vault Door Metal 1850 Room 9 Back Room Wall Drywall

1846 Room 6A Door Wood 1847 Comm Room Wall Drywall 1848 Room 9 Vault Door Jamb Metal

Title Page
Asbestos
LBP
Readings
2020-01-02T13:20:51-0700
BRIMBERRY.TAYLOR.MIKE.1543589558
GM200108:
North Center Room 118:
GM200109:
East Center Room 117:
GM200148:
West Room 117 Exterior:
GM200149:
North Room 117 Exterior:
GM200150:
North Room 118 Exterior:
GM200151:
Southwest:
GM200152:
Northwest:
GM200153:
Southeast:
GM200154:
Southwest_2:
GM200155:
South Center:
Wire Insulation Black Room 8 10 Linear Feet:
GM200072:
South Center_2:
None Detected:
Range 8 to 12:
Range 8 to 12_2:
Range 8 to 12_3:
Range 8 to 12_4:
Range 8 to 12_5: