CenTraVac Centrifugal Chiller Product Report (Existing)

Job Information

HAFB ~ 891

Salt Lake City (U41)Daniel Goulding

Tag CH-1 Model Number CVHF0570 1 Quantity

Rated in accordance with ARI Standard 550/590.

Sound pressure measured in accordance with ARI Standard 575-94.

ASHRAE 90.1 - 1999 Complies

Unit Information

CVHF Model Evap tube type IMCU 570 Compressor size 0.025" Evap tube thickness

Motor size 323 2 Evap passes 60 Hz Motor frequency Cond shell size 050S

Motor voltage 460 Cond bundle size 500 Impeller size 265 Cond tube type TECU

Cond tube thickness 0.028" Orifice size 680 Cond passes 2 050S Evap shell size

700 Evap bundle size

Design Information

500.0 tons Cooling capacity HCFC-123 refrigerant charge 1250 lb Primary power 248.7 kW 16332 lb Shipping weight

0.497 kW/ton Primary efficiency 19003 lb Operating weight

0.437 kW/ton NPLV Sound level

Wye-delta starter type No Green Seal certification Unit Mounted WyeD Application type Standard cooling Yes Free cooling option

4.25 MBh Heat rejected into equip room

Evaporator Information

45.00 F Evap leaving temp Evap pressure drop 16.36 ft H2O

1194.7 gpm Evap flow rate water Evap fluid type

55.00 F Evap entering temp Evap fluid concentration N/A

2.39 gpm/ton Evap flow/capacity non-marine Evap water box type

Evap water box pressure 0.00010 hr-sq ft-deg F/Btu Evap fouling factor 150 psig

Condenser Information

80.00 F Cond entering temp 31.83 ft H2O Cond pressure drop

Cond flow rate 1415.4 gpm propylene glycol Cond fluid type

90.00 F Cond leaving temp Cond fluid concentration 20.00 %

Cond flow/capacity 2.83 gpm/ton non-marine Cond water box type

Cond water box pressure 0.00025 hr-sq ft-deg F/Btu Cond fouling factor 150 psig

Electrical Information

Min circuit ampacity Motor LRA 2169 A 471 A Primary RLA 369.4 A Max overcurrent protection 800 A Un-corrected power factor

Selection code revision level 8/19/2010

M0C1E111C111S10 29.12

55115.0 Product Version

W91238-10-R-0053 Amendment 0005

CenTraVac Centrifugal Chiller Product Report (Existing)

Job Information

HAFB ~ 891

Salt Lake City (U41)Daniel Goulding

Tag CH-1 Model Number CVHF0570 1 Quantity

Information for LEED Projects

Primary power 248.70 kW HCFC-123 refrigerant charge 1250.0 lb NPLV 0.437 kW/ton Cooling capacity 500.00 tons

Note: Although Trane recognizes and respects the decision by the U.S. Green Building Council to mandate a default assumption of a 2% Refrigerant

Leakage Rate (Lr) for all manufacturers of centrifugal chillers, the value used in the calculations for achieving Energy and Atmosphere Credit 4 of

LEED-NC (version 2.2), Trane has exhaustively documented and guarantees a low 0.5% leak rate for HCFC-123 CenTraVac centrifugal chillers

(models CVHE, CVHF, and CVHG). This documented 0.5% refrigerant leakage rate, as well as our average 1.7 Lb/Ton refrigerant charge, are just some examples of Trane's commitment to safeguarding the environment.