QNC_ADMIN-CEM_IMPROVE_FINAL.pdf

PDF 44 MB Posted

Attached to
Quantico National Cemetery Gravesite Expansion and Cemetery Improvements Project-Administraton Building
Solicitation number
W91236-18-B-0005
Issued by

About this file

QNC_ADMIN-CEM IMPROVE_FINAL

View the file

Other files

File Type Posted
ABSTRACT_OF_OFFERORS_pg2.pdf PDF
ABSTRACT_OF_OFFERORS.pdf PDF
W91236-18-B-0005-0004.pdf PDF
G-002-Amendment_4.pdf PDF
W91236-18-B-0005-0003.pdf PDF
NRO-15-280-1_2017-12-20_Quantico_Nat_Cemetery_Approval_Lttr.pdf PDF
W91236-18-B-0005-0002.pdf PDF
01_45_00.15_10.pdf PDF
W91236-18-B-0005-0001.pdf PDF
01_45_00.00_10.pdf PDF
01_32_01.00_10.pdf PDF
20180207_-_15125F_-_Detail_Sheets_C-502_Revised.pdf PDF
20180128_-_15125F_-_REVISIONS.pdf PDF
Site_Visit_Roster_18JAN2018.pdf PDF
W91236-18-B-0005_FINAL.pdf PDF
Combined_Spec_-_VOL_1.pdf PDF
QNC_Basis_of_Design.pdf PDF
Combined_Spec_-_VOL_2.pdf PDF
Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A

OF

1909 CYPRESS AVENUE

VIRGINIA BEACH, VA 23451

(757) 417 - 0140

US Army Corps of Engineers Norfolk District

SHEET

N O

R F

O

LK

D

IS

T R

IC

T

C O

R P

S O

F E

N G

IN

E

E R

S N

O R

F O

LK

V

IR

G

IN

IA

F

IN

A L

S U

B M

IT

T

A L

N

O V

E M

B E

R

D A

T E

C

H E

C K

E D

S U

B M

IT

T

E D

S

C A

LE

N O

R F

O

LK

D

IS

T R

IC

T

F

IL

E N

O

P R

O

JE

C T

N O

D R

A W

IN

G

N O

S

P E

C

IF

IC

A

T

IO

N N

O

D R

A W

N

D E

S

IG

N E

D

La st w or ke d on

F le n am e:

P lo t s ca le

1:

A S

N O

T E

D

R E

V

D A

T E

D E

S C

R

IP

T

IO

N B

Y A

P P

B

C

D

A

B

C

D

2 3 4 5 1 2 3 4 5

C :\U se rs

\a ge nu ng

\D oc um en ts \1

3-

II

Q

N C

B ld g R en ov

G ra ve Im pr ov e

A rc h_ ag en un g.

rv t

/1

3/

:1 7:

A

M

G-001

Q U

A N

T

IC

O N

A T

IO

N

A L C

E M

E T

E R

Y

B L D

G R

E N

O V

G

R A

V E

S

IT

E I M

P R

O V

E

C O

V E

R S

H E

E T

D S

R

D S

R

D P

I

-I I

/0

3/

11/03/2017 1261

D S

R

QUANTICO NATIONAL CEMETERY

BUILDING RENOVATION & GRAVESITE IMPROVEMENTS

18424 JOPLIN ROAD TRIANGLE, VIRGINIA

WALLER, TODD AND SADLER ARCHITECTS, INC.

MSA, P.C.

NRW ENGINEERING

J.P. HARVEY ENGINEERING SOLUTIONS

JENSEN HUGHES

MCCLESKEY PROFESSIONAL SERVICES

IRRIGATION RESEARCH & DESIGN

CIVIL ENGINEERING

STRUCTURAL ENGINEERS

MECHANICAL, ELECTRICAL, PLUMBING ENGINEERS

FIRE PROTECTION, LIFE SAFETY ENGINEERS

LANDSCAPE, CEMETERY DESIGNERS

IRRIGATION SPECIALISTS

LOCATION MAPVICINITY MAP

PROJECT LOCATIONSPROJECT LOCATION

JOPLIN RD.

EXIT 150

TRIANGLE EXIT 150

TRIANGLE

IN

TE

R

ST

AT

E

IN

TE

R S

TA

TE

YORKTOWN BLVD

SITE NAME BURIAL TYPE EXPANSION QUANTITY AREA OF DISTURBANCE

1. STANDARD BURIAL AREA (BID OPTION 1) 5'X10' PLOTS 533 1.84 ACRES

2. OSSUARY SITE (BID OPTION 2) CREMAINS 500 0.046 ACRES

3. IN-GROUND CREMAINS-OSSUARY SITE (BID OPTION 2) CREMAINS 791 0.624 ACRES

4. COLUMBARIUM SITE (BID OPTION 3) CREMAINS 2,640 0.67 ACRES

TOTAL BURIAL SITES 4,464 BURIALS

QNC BURIAL EXPANSION SCHEDULE

OF

1909 CYPRESS AVENUE

VIRGINIA BEACH, VA 23451

(757) 417 - 0140

US Army Corps of Engineers Norfolk District

SHEET

N O

R F

O

LK

D

IS

T R

IC

T

C O

R P

S O

F E

N G

IN

E

E R

S N

O R

F O

LK

V

IR

G

IN

IA

F

IN

A L

S U

B M

IT

T

A L

N

O V

E M

B E

R

D A

T E

C

H E

C K

E D

S U

B M

IT

T

E D

S

C A

LE

N O

R F

O

LK

D

IS

T R

IC

T

F

IL

E N

O

P R

O

JE

C T

N O

D R

A W

IN

G

N O

S

P E

C

IF

IC

A

T

IO

N N

O

D R

A W

N

D E

S

IG

N E

D

La st w or ke d on

F le n am e:

P lo t s ca le

1:

A S

N O

T E

D

R E

V

D A

T E

D E

S C

R

IP

T

IO

N B

Y A

P P

B

C

D

A

B

C

D

2 3 4 5 1 2 3 4 5

C :\U se rs

\a ge nu ng

\D oc um en ts \1

3-

II

Q

N C

B ld g R en ov

G ra ve Im pr ov e

A rc h_ ag en un g.

rv t

/1

3/

:3 2:

A

M

G-002

Q U

A N

T

IC

O N

A T

IO

N

A L C

E M

E T

E R

Y

B L D

G R

E N

O V

G

R A

V E

S

IT

E I M

P R

O V

E

IN

D

E X

D R

A W

IN

G

S

D S

R

D S

R

D P

I

-I I

/0

3/

11/03/2017 1262

D S

R

INDEX OF DRAWINGS

SHEET # SHEET TITLE # OF

AH-101 FIRST FLOOR PLAN - HAZMAT REMOVAL 72

LS001 BUILDING CODE AND LIFE SAFETY ANALYSIS 73

LS101 LIFE SAFETY FLOOR PLAN 74

S-001 GENERAL NOTES 75

S-101 FOUNDATION PLAN 76

S-102 ROOF FRAMING PLAN 77

S-301 SECTIONS AND DETAILS 78

AD101 FIRST FLOOR PLAN - DEMOLITION 79

A-001 ABBREVIATIONS, SYMBOLS AND LEGENDS 80

A-101 FIRST FLOOR PLAN - NEW WORK 81

A-102 REFLECTED CEILING PLAN - NEW WORK 82

A-103 ROOF PLAN 83

A-201 BUILDING ELEVATIONS 84

A-301 WALL SECTION AND DETAILS 85

A-401 ENLARGED PLAN AND DETAILS 86

A-501 ROOF AND CEILING DETAILS 87

A-601 DOOR SCHEDULE AND DETAILS 88

A-701 FINISH SCHEDULE, NOTES & DETAILS 89

A-702 INTERIOR FINISH ELEVATIONS 90

FA001 FIRE ALARM GENERAL NOTES AND LEGEND 91

FA101 FIRE ALARM FLOOR PLAN 92

FA501 FIRE ALARM DETAILS 93

FX001 FIRE PROTECTION GENERAL NOTES AND LEGEND 94

FX101 FIRE PROTECTION FLOOR PLAN 95

FX501 FIRE PROTECTION DETAILS 96

P-001 PLUMBING LEGEND, ABBREVIATIONS AND GENERAL NOTES 97

PD101 FIRST FLOOR PLAN - PLUMBING DEMOLITION 98

P-101 FIRST FLOOR PLAN - WASTE PIPING 99

P-102 FIRST FLOOR PLAN - WATER PIPING 100

P-501 PLUMBING DETAILS 101

P-601 PLUMBING SCHEDULES 102

P-701 ISOMETRICS 103

M-001 GENERAL NOTES, LEGEND, ABBREVIATIONS, AND CONTROLS 104

MD101 FIRST FLOOR PLAN - MECHANICAL DEMOLITION 105

MD102 ROOF PLAN - MECHANICAL DEMOLITION 106

M-101 FIRST FLOOR PLAN - MECHANICAL HVAC 107

M-102 ROOF PLAN - MECHANICAL HVAC 108

M-501 MECHANICAL DETAILS 109

M-502 MECHANICAL DETAILS 110

M-601 MECHANICAL SCHEDULES 111

E-001 LEGEND AND ABBREVIATIONS 112

ED101 FIRST FLOOR PLAN - ELECTRICAL DEMOLITION 113

ED102 ROOF PLAN - ELECTRICAL DEMOLITION 114

E-101 FIRST FLOOR PLAN - LIGHTING 115

E-102 FIRST FLOOR PLAN - POWER 116

E-103 FIRST FLOOR PLAN - HVAC POWER 117

E-104 ROOF PLAN - HVAC POWER 118

E-501 LIGHT FIXTURE DETAILS 119

E-502 LIGHT FIXTURE DETAILS AND SCHEDULE 120

E-503 ELECTRICAL DETAILS 121

E-601 PANELBOARD SCHEDULES 122

E-701 POWER RISER DIAGRAM - DEMOLITION AND CONSTRUCTION 123

T-101 FIRST FLOOR PLAN - COMMUNICATIONS AND SECURITY 124

TS101 TELECOMMUNICATIONS SITE PLAN - AREA A 125

TS102 TELECOMMUNICATIONS SITE PLAN - AREA B 126

INDEX OF DRAWINGS

SHEET # SHEET TITLE # OF

G-002 INDEX DRAWINGS 2

G-001 COVER SHEET 1

GC001 LOCATION MAP 3

GC002 EROSION & SEDIMENT CONTROL NARRATIVE AND NOTES 4

GC003 EROSION & SEDIMENT CONTROL NARRATIVE AND NOTES 5

GC004 EROSION & SEDIMENT CONTROL NARRATIVE AND NOTES 6

GC005 EROSION & SEDIMENT CONTROL NARRATIVE AND NOTES 7

GC006 KEY PLAN, LEGEND AND ABBREVIATIONS 8

V-100 SURVEY CONTROL DATA 9

V-101 EXISTING TOPOGRAPHIC SURVEY - ADMIN BUILDING 10

V-102 EXISTING TOPOGRAPHIC SURVEY - STANDARD BURIAL (BID OPTION 1) 11

V-103 EXISTING TOPOGRAPHIC SURVEY - OSSUARY (BID OPTION 2) 12

V-104 EXISTING TOPOGRAPHIC SURVEY - COLUMBARIUM (BID OPTION 3) 13

CD101 DEMOLITION PLAN - ADMIN BUILDING 14

CD102 DEMOLITION PLAN - STANDARD BURIAL (BID OPTION 1) 15

CD103 DEMOLITION PLAN - OSSUARY (BID OPTION 2) 16

CD104 DEMOLITION PLAN - COLUMBARIUM (BID OPTION 3) 17

CS101 SITE PLAN - ADMIN BUILDING 18

CS102 SITE PLAN - STANDARD BURIAL AREA (BID OPTION 1) 19

CS103 SITE PLAN - OSSUARY (BID OPTION 2) 20

CS104 SITE PLAN - COLUMBARIUM (BID OPTION 3) 21

CS602 NUMBERING PLAN - STANDARD BURIAL SECTION 33 (BID OPTION 1) 22

CS603 NUMBERING PLAN - OSSUARY SECTION 34 (BID OPTION 2) 23

CS604 NUMBERING PLAN - COLUMBARIUM (BID OPTION 3) 24

CG101 GRADING AND DRAINAGE PLAN - ADMIN BUILDING 25

CG102 GRADING AND DRAINAGE PLAN - STANDARD BURIAL (BID OPTION 1) 26

CG103 GRADING AND DRAINAGE PLAN - OSSUARY (BID OPTION 2) 27

CG104 GRADING AND DRAINAGE PLAN - COLUMBARIUM (BID OPTION 3) 28

CG201 PROFILE - STORM DRAIN (BID OPTIONS 2 & 3) 29

CG301 CROSS-SECTIONS - STANDARD BURIAL (BID OPTION 1) 30

CG302 CROSS-SECTIONS - STANDARD BURIAL (BID OPTION 1) 31

CG303 CROSS-SECTIONS - OSSUARY (BID OPTION 2) 32

CG401 ENLARGED PLAN - OSSUARY UNDERDRAIN (BID OPTION 2) 33

CG402 ENLARGED PLAN - COLUMBARIUM UNDERDRAIN (BID OPTION 3) 34

C-501 EROSION AND SEDIMENT CONTOL DETAILS 35

C-502 DETAIL SHEET 36

C-503 DETAIL SHEET 37

C-504 DETAIL SHEET 38

C-505 DETAIL SHEET 39

C-506 DETAIL SHEET 40

C-507 DETAIL SHEET 41

LP101 LANDSCAPE PLAN - ADMIN BUILDING 42

LP102 LANDSCAPE PLAN - STANDARD BURIAL (BID OPTION 1) 43

LP103 LANDSCAPE PLAN - OSSUARY (BID OPTION 2) 44

LP104 LANDSCAPE PLAN - COLUMBARIUM (BID OPTION 3) 45

LP501 LANDSCAPE NOTES & DETAILS 46

LI101 IRRIGATION PLAN - ADMIN BUILDING 47

LI102 NOT USED 48

LI103 NOT USED 49

LI104 NOT USED 50

LI105 NOT USED 51

LI106 NOT USED 52

LI107 NOT USED 53

LI108 IRRIGATION PLAN - STANDARD BURIAL (BID OPTION 1) 54

LI109 IRRIGATION PLAN - OSSUARY (BID OPTION 2) 55

LI110 IRRIGATION PLAN - COLUMBARIUM (BID OPTION 3) 56

LI501 IRRIGATION PLAN DETAILS 57

LI502 IRRIGATION PLAN DETAILS 58

L-101 OSSUARY MEMORIAL WALL PLAN 59

L-102 OSSUARY WALL ELEVATIONS 60

L-103 OSSUARY DETAILS 61

L-104 OSSUARY DETAILS 62

L-105 OSSUARY DETAILS 63

L-106 COLUMBARIUM PLAN 64

L-107 DOUBLE-SIDED COLUMBARIUM ELEVATIONS 65

L-108 DOUBLE-SIDED COLUMBARIUM ELEVATIONS 66

L-109 DOUBLE-SIDED COLUMBARIUM ELEVATIONS 67

L-110 SINGLE-SIDED COLUMBARIUM ELEVATIONS 68

L-111 COLUMBARIUM DETAILS 69

L-112 PRECAST COLUMBARIUM DETAILS 70

L-113 COLUMBARIUM DETAILS 71

GRAPHIC SCALE

GC001

US Army Corps of Engineers ® Norfolk District

1909 CYPRESS AVENUE

VIRGINIA BEACH, VA 23451

(757) 417 - 0140

OFSHEET

N O

R

FO

LK

D

IS

TR

IC

T

C O

R P

S O

F E

N G

IN

E

E R

S N

O R

FO

LK

V

IR

G

IN

IA

FI

NA

L

SU

BM

IT

TA

L

N

O V

D A

TE

C H

E C

K E

D

S U

B M

IT

TE

D

S C

A

LE

N O

R

FO

LK

D

IS

TR

IC

T

FI

LE

N O

P

R O

JE

C

T N

O

D R

A W

IN

G

N O

S

P E

C

IF

IC

A

TI

O

N N

O

D R

A W

N

D E

S

IG

N E

D

La st w or ke d on

Fl e na m e:

P lo t s ca le

1:

A S

N O

TE

D

R E

V

D A

TE

D

E S

C R

IP

TI

O N

B Y

A P

P

-T

/0

3/

MSA, P.C.

5033 Rouse Drive, Virginia Beach, VA 23462 757-490-9264 (Ofc) 757-490-0634 (Fax) www.msaonline.com

Environmental Sciences Planning Surveying Civil & Environmental Engineering

Landscape Architecture

AS

M

M W

K

R R

C

D W

M W

K

Q U

A N

TI

C

O N

A

TI

O N

A L

C E

M E

TE

R

Y

BL

D G

. R

EN

O V.

G

RA

VE

. I M

PR

O

VE

M

EN

TS

I-9

LO

C

A

TI

O N

M A

P

ADMIN

BUILDING

STANDARD

BURIAL

OSSUARY

COLUMBARIUM

MAIN

ENTRANCE

I-

JOPLIN ROAD

EXIT 150

JOPLIN ROAD

STAGING/

CONTRACTOR

LAYDOWN

APPROXIMATELY

390 LF X 565 LF

CONTRACTOR

WORKFORCE

PARKING AREA

CONSTRUCTION VEHICLES

SHALL NOT PROCEED

PAST THIS POINT

CONSTRUCTION VEHICLES

SHALL NOT PROCEED

PAST THIS POINT

MAIN ENTRANCE

FOR CONSTRUCTION

INGRESS/EGRESS

CONSTRUCTION PROJECT

SIGN / PROJECT SAFETY SIGN

SEE SHEET SPECIFICATION 01

50 02.00 50 TEMPORARY

CONSTRUCTION FACILITIES

FOR DETAIL.

CONSTRUCTION PROJECT SIGN /

PROJECT SAFETY SIGN

SEE SHEET SPECIFICATION 01 50 02.00 50

TEMPORARY CONSTRUCTION FACILITIES

FOR DETAIL.

I R

R

I R

R

ADD NEW VALVES

TO EXISTING IRRIGATION

MAINLINE

ADD NEW VALVE

TO EXISTING

IRRIGATION

MAINLINE - RUN

NEW CONTROL

WIRE TO

CONTROLLER

ADD NEW IRRIGATION WIRES

FROM EXISTING CONTROLLER TO

NEW VALVE LOCATIONS

.0

.5

.2

.3

.8

.7

.6

.7

.9

.1

.9

A

D

M

N

B

L D

G

O

W

W

W

W

W

W

W

T Y

P

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

Q

Q

EXISTING

CONTROLLER

#2

REMOVE ALL EXISTING IRRIGATION

IN THESE AREAS INCLUDING ELECTRIC

VALVES - USE EXISTING MAINLINE

CONNECTIONS FOR NEW VALVES

36G

52G

12G

17G

EXTENDED MAINLINE

TO BE 1.5" CL200

PVC

US Army Corps of

Engineers ®

Norfolk District

1909 CYPRESS AVENUE

VIRGINIA BEACH, VA

23451

(757) 417 - 0140

OFSHEET

N O

R F

O

K

D

S

T R

I C

T

C O

R P

S

F

E

G

I N

E E

R S

N O

R F

O L

V

R

G I N

I A

D A

T E

C

H E

C K

E D

S U

B M

I T

T E

D

S C

A L E

N O

R F

O

S

T R

I C

T

F

I

P R

O J E

C T

D R

A W

I N

G

N

O

S P

E C

I F

I C

A T

I O

N

N

O

D R

A W

N

D E

S I G

N E

D

L a s t w o r k e d o n

F l e n a m e

P l o t s c a l e

T

E D

R E

V

D A

T E

D E

S C

R I P

T I O

N B

Y A

P P

Q U

A N

TI

C

O N

A

TI

O N

A L

C E

M

TE

R Y

E X

P A

N S

IO

N

IM

P R

O V

E M

E N

TS

W

A R

K R

R

W A

R

T

MSA, P.C.

5033 Rouse Drive, Virginia Beach, VA 23462 757-490-9264 (Ofc) 757-490-0634 (Fax) www.msaonline.com

Environmental Sciences Planning Surveying Civil & Environmental Engineering

Landscape Architecture

AS

M

F I N

U B

M I T

T A

L

V

E M

B E

R

GRAPHIC SCALE

LI101

I R

R I G

A T

I O

N

P

L A

N

A D

M

I L D

I N

G

LINE-SIZED LEEMCO LV-200 ISOLATION VALVE

RAINBIRD ESP-40-SAT-LS

RAINBIRD EXISTING SATELLITE

RAINBIRD PGA ELECTRIC VALVE (1" UP TO 25 GPM, 1.5" UP TO 50 GPM,

2" UP TO 80 GPM) - WITH PRESSURE REGULATOR

C18

EQUIPMENT LEGEND

C17

2 7

RAINBIRD 1806 FIXED SPRAY SPRINKLER W/ 12' & 15' W U - NOZZLES

RAINBIRD 1812 FIXED SPRAY SPRINKLER W/ 12' & 15' U - NOZZLES

RAINBIRD 1812 FIXED SPRAY SPRINKLER WITH END AND SIDE STRIPS

RAINBIRD GOLF SERIES 900E/FULL CIRCLE #48 NOZZLE 70 PSI

REGULATOR AND 950E WITH #18 AND 950E WITH #18 NOZZLE AND 70 PSI

REGULATOR

RAINBIRD GOLF SERIES 900E/FULL CIRCLE #44 NOZZLE 60 PSI

REGULATOR AND 950E WITH # AND 950E WITH #18 NOZZLE AND 60 PSI

REGULATOR

RAINBIRD 8005SS-08 - USE FULL CIRCLE MODEL ON 360 DEGREE AREA

AND PART CIRCLE MODEL ON 50 TO 330 DEGREE AREAS

RAINBIRD 5004-PC-SAM-PRS-SS W/ 2.0 - 4.0 RAIN CURTAIN NOZZLES

1" RAINBIRD QUICK COUPLER VALVE, SWIVEL AND KEY

HEAD LEGEND

3" PVC SCHEDULE 40 GASKET PIPE OR AS LABELED

1" PVC SCHEDULE 80 LATERALS

1.5" PVC SCHEDULE 80 LATERALS

2" PVC SCHEDULE 80 LATERALS

2.5" PVC SCHEDULE 80 LATERALS

ONE 4" PVC SCHEDULE 40 SLEEVE

ONE 4" AND ONE 3" PVC SCHEDULE 40 SLEEVE

PIPING LEGEND

IRRIGATION NOTES:

1) REMOVE ALL EXISTING IRRIGATION HEADS AND VALVES IN DISTURBED AREA

AND RETURN TO OWNER FOR FUTURE REPAIRS

2) ALL CONNECTIONS TO MAINLINE NOT RE-USED ARE TO BE CAPPED AND SECURED

BY MECHANICAL JOINT

3) ALL MAINLINE CONNECTIONS TO BE PERFORMED WITH MECHANICAL JOINTS - NO THRUST

BLOCKS ARE TO BE USED. USE LEEMCO DI SERVICE TEE FOR IRRIGATION GOLF HEADS AND

LV200 ANGLE VALVE AND JOINT RESTRAINTS FOR ALL CONNECTIONS.

4) ALL PROGRAMMING OF NEW IRRIGATION ZONES TO BE PERFORMED BY AN IRRIGATION

ASSOCIATION (WWW.IRRIGATION.ORG) CERTIFIED IRRIGATION DESIGNER (CID) OR CERTIFIED

LANDSCAPE IRRIGATION AUDITOR (CLIA)

5) ADD A 1" QUICK COUPLER TO EACH POINT OF CONNECTION FOR NEW IRRIGATION ALONG

THE MAINLINE FOR WINTERIZATION POINTS.

S

E

C

T I

N

O

T

B

U

R

I E

D

QUANTICO DRIVE

A

C

R

E

R

E

F

E

R

E

N

E

F

E

R

E

N

E

C

T

I

E

C

T

I O

N

M

A

R

K

E

R

M

A

R

K

E

R

H

Y

D

R

A

N

T

QUANTI CO

DRI VE

9T

Y

P

W

W

W

W

W

W

W

W

W

W

W

W W

WWWW

W

W W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

Q

Q

Q

REMOVE ALL EXISTING IRRIGATION

HEADS, PIPING, AND IRRIGATION

COMPONENTS ALONG ROADWAY ON

BOTH SIDES OF THE ROADWAY WITH

IN PROJECT LIMITS CAPPING MAINLINE

POINTS OF CONNECTION WITH

MECHANICAL JOINT - DO NOT REMOVE

4" OR 12" MAINLINE IN ANY AREA

CONNECT TO EXISTING

4" POINT OF CONNECTION

WITH MECHANICAL JOINT

RESTRAINT

23G

C14

23G

2C14

23G

C14

23G

C14

32G

C14

23G

C14

23G

7C14

23G

C14

23G

C14

23G

C14

23G

C14

G

C

23G

C14

42G

C14

52G

C14

44G

19C14

"3

.5

3"

2.5"

2.5"

2.5"

REMOVE ALL EXISTING

IRRIGATION COMPONENTS FROM

WITHIN PROJECT LIMITS - SAVE

ALL IRRIGATION HEADS FOR

OWNERS REUSE

US Army Corps of

Engineers ®

Norfolk District

1909 CYPRESS AVENUE

VIRGINIA BEACH, VA

23451

(757) 417 - 0140

OFSHEET

N O

R F

O

S

T R

I C

T

C O

R

G

I N

E E

R S

N O

R F

O L

R

G I N

I A

D A

T E

C

H E

C K

E D

S U

B M

I T

T E

D

S C

A L E

N O

R F

O

S

T R

I C

T

F

I

P R

O J E

D R

A W

I N

G

N

O

S P

E C

I F

I C

A T

I O

N

N

O

D R

A W

N

D E

S I G

N E

D

L a s t w o r k e d o n

F l e n a m e

P l o t s c a l e

T

E D

R E

V

D A

T E

D E

S C

R I P

T I O

N B

Y A

P P

Q U

A N

TI

C

O N

A

TI

O N

A L

C E

M

TE

R Y

E X

P A

N S

IO

N

IM

P R

O V

E M

E N

TS

W

A R

K R

R

W A

R

T

MSA, P.C.

5033 Rouse Drive, Virginia Beach, VA 23462 757-490-9264 (Ofc) 757-490-0634 (Fax) www.msaonline.com

Environmental Sciences Planning Surveying Civil & Environmental Engineering

Landscape Architecture

AS

M

F I N

B

M I T

T A

L

V

E M

B E

R

LI108

GRAPHIC SCALE

I R

R I G

A T

I O

N

P

L A

N

S T

A N

D A

R

I A

L

A

R E

A

LINE-SIZED LEEMCO LV-200 ISOLATION VALVE

RAINBIRD ESP-40-SAT-LS

RAINBIRD EXISTING SATELLITE

RAINBIRD PGA ELECTRIC VALVE (1" UP TO 25 GPM, 1.5" UP TO 50 GPM,

2" UP TO 80 GPM) - WITH PRESSURE REGULATOR

C18

EQUIPMENT LEGEND

C17

2 7

RAINBIRD 1806 FIXED SPRAY SPRINKLER W/ 12' & 15' W U - NOZZLES

RAINBIRD 1812 FIXED SPRAY SPRINKLER W/ 12' & 15' U - NOZZLES

RAINBIRD 1812 FIXED SPRAY SPRINKLER WITH END AND SIDE STRIPS

RAINBIRD GOLF SERIES 900E/FULL CIRCLE #48 NOZZLE 70 PSI

REGULATOR AND 950E WITH #18 AND 950E WITH #18 NOZZLE AND 70 PSI

REGULATOR

RAINBIRD GOLF SERIES 900E/FULL CIRCLE #44 NOZZLE 60 PSI

REGULATOR AND 950E WITH # AND 950E WITH #18 NOZZLE AND 60 PSI

REGULATOR

RAINBIRD 8005SS-08 - USE FULL CIRCLE MODEL ON 360 DEGREE AREA

AND PART CIRCLE MODEL ON 50 TO 330 DEGREE AREAS

RAINBIRD 5004-PC-SAM-PRS-SS W/ 2.0 - 4.0 RAIN CURTAIN NOZZLES

1" RAINBIRD QUICK COUPLER VALVE, SWIVEL AND KEY

HEAD LEGEND

3" PVC SCHEDULE 40 GASKET PIPE OR AS LABELED

1" PVC SCHEDULE 80 LATERALS

1.5" PVC SCHEDULE 80 LATERALS

2" PVC SCHEDULE 80 LATERALS

2.5" PVC SCHEDULE 80 LATERALS

ONE 4" PVC SCHEDULE 40 SLEEVE

ONE 4" AND ONE 3" PVC SCHEDULE 40 SLEEVE

PIPING LEGEND

IRRIGATION NOTES:

1) REMOVE ALL EXISTING IRRIGATION HEADS AND VALVES IN DISTURBED AREA

AND RETURN TO OWNER FOR FUTURE REPAIRS

2) ALL CONNECTIONS TO MAINLINE NOT RE-USED ARE TO BE CAPPED AND SECURED

BY MECHANICAL JOINT

3) ALL MAINLINE CONNECTIONS TO BE PERFORMED WITH MECHANICAL JOINTS - NO THRUST

BLOCKS ARE TO BE USED. USE LEEMCO DI SERVICE TEE FOR IRRIGATION GOLF HEADS AND

LV200 ANGLE VALVE AND JOINT RESTRAINTS FOR ALL CONNECTIONS.

4) ALL PROGRAMMING OF NEW IRRIGATION ZONES TO BE PERFORMED BY AN IRRIGATION

ASSOCIATION (WWW.IRRIGATION.ORG) CERTIFIED IRRIGATION DESIGNER (CID) OR CERTIFIED

LANDSCAPE IRRIGATION AUDITOR (CLIA)

.7

.3

.1

.1

.9

.3

.1

.9

W

W

W

W

W

W

T Y

P

Q

MOVE EXISTING CONTROLLER

#5 FROM THIS LOCATION

TO NEW LOCATION - ALL WIRES

TO BE SPLICED IN A VALVE BOX

USING 3M DBR'S OR DBY'S

NEW LOCATION FOR CONTROLLER

#5 - RUN NEW WIRES FROM EXISTING

(AND UN-TOUCHED) ELECTRIC VALVES

TO THIS LOCATION - RE-ROUTE POWER

WIRE FROM A POINT AT THE EDGE OF

THE DISTURBED AREA FOR THIS PROJECT

TO POWER THIS CONTROLLER. RUN OLD

WIRES/VALVES FROM OLD CONTROLLER

LOCATION TO NEW CONTROLLER LOCATION.

REMOVE ALL EXISTING IRRIGATION HEADS, PIPING

AND IRRIGATION COMPONENTS ALONG ROADWAY

WITHIN PROJECT LIMITS - DO NOT REMOVE 4" OR 12'

MAINLINE IN ANY AREA

REMOVE ALL EXISTING IRRIGATION HEADS, PIPING

AND IRRIGATION COMPONENTS

ALONG ROADWAY WITHIN PROJECT

LIMITS - DO NOT REMOVE 4" OR 12" MAINLINE IN

ANY AREA

REMOVE ALL EXISTING IRRIGATION HEADS

AND PIPING WITHIN PROJECT

LIMITS

CONNECTION TO

EXISTING 4"

MAINLINE -

STUBOUT

WITH A

MECHANICAL

JOINT RESTRAINT

G

G

G g

G

RUN NEW WIRES FROM NEW VALVES TO

CONTROLLER #5 AT NEW LOCATION

US Army Corps of

Engineers ®

Norfolk District

1909 CYPRESS AVENUE

VIRGINIA BEACH, VA

23451

(757) 417 - 0140

OFSHEET

N O

R F

O

S

T R

I C

T

C O

R

G

I N

E E

R S

N O

R F

O L

R

G I N

I A

D A

T E

C

H E

C K

E D

S U

B M

I T

T E

D

S C

A L E

N O

R F

O

S

T R

I C

T

F

I

P R

O J E

D R

A W

I N

G

N

O

S P

E C

I F

I C

A T

I O

N

N

O

D R

A W

N

D E

S I G

N E

D

L a s t w o r k e d o n

F l e n a m e

P l o t s c a l e

T

E D

R E

V

D A

T E

D E

S C

R I P

T I O

N B

Y A

P P

Q U

A N

TI

C

O N

A

TI

O N

A L

C E

M

TE

R Y

E X

P A

N S

IO

N

IM

P R

O V

E M

E N

TS

W

A R

K R

R

W A

R

T

MSA, P.C.

5033 Rouse Drive, Virginia Beach, VA 23462 757-490-9264 (Ofc) 757-490-0634 (Fax) www.msaonline.com

Environmental Sciences Planning Surveying Civil & Environmental Engineering

Landscape Architecture

AS

M

F I N

B

M I T

T A

L

V

E M

B E

R

GRAPHIC SCALE

LI109

I R

R I G

A T

I O

N

P

L A

N

O S

S U

A R

Y

A

R E

A

LINE-SIZED LEEMCO LV-200 ISOLATION VALVE

RAINBIRD ESP-40-SAT-LS

RAINBIRD EXISTING SATELLITE

RAINBIRD PGA ELECTRIC VALVE (1" UP TO 25 GPM, 1.5" UP TO 50 GPM,

2" UP TO 80 GPM) - WITH PRESSURE REGULATOR

C18

EQUIPMENT LEGEND

C17

2 7

RAINBIRD 1806 FIXED SPRAY SPRINKLER W/ 12' & 15' W U - NOZZLES

RAINBIRD 1812 FIXED SPRAY SPRINKLER W/ 12' & 15' U - NOZZLES

RAINBIRD 1812 FIXED SPRAY SPRINKLER WITH END AND SIDE STRIPS

RAINBIRD GOLF SERIES 900E/FULL CIRCLE #48 NOZZLE 70 PSI

REGULATOR AND 950E WITH #18 AND 950E WITH #18 NOZZLE AND 70 PSI

REGULATOR

RAINBIRD GOLF SERIES 900E/FULL CIRCLE #44 NOZZLE 60 PSI

REGULATOR AND 950E WITH # AND 950E WITH #18 NOZZLE AND 60 PSI

REGULATOR

RAINBIRD 8005SS-08 - USE FULL CIRCLE MODEL ON 360 DEGREE AREA

AND PART CIRCLE MODEL ON 50 TO 330 DEGREE AREAS

RAINBIRD 5004-PC-SAM-PRS-SS W/ 2.0 - 4.0 RAIN CURTAIN NOZZLES

1" RAINBIRD QUICK COUPLER VALVE, SWIVEL AND KEY

HEAD LEGEND

3" PVC SCHEDULE 40 GASKET PIPE OR AS LABELED

1" PVC SCHEDULE 80 LATERALS

1.5" PVC SCHEDULE 80 LATERALS

2" PVC SCHEDULE 80 LATERALS

2.5" PVC SCHEDULE 80 LATERALS

ONE 4" PVC SCHEDULE 40 SLEEVE

ONE 4" AND ONE 3" PVC SCHEDULE 40 SLEEVE

PIPING LEGEND

IRRIGATION NOTES:

1) REMOVE ALL EXISTING IRRIGATION HEADS AND VALVES IN DISTURBED AREA

AND RETURN TO OWNER FOR FUTURE REPAIRS

2) ALL CONNECTIONS TO MAINLINE NOT RE-USED ARE TO BE CAPPED AND SECURED

BY MECHANICAL JOINT

3) ALL MAINLINE CONNECTIONS TO BE PERFORMED WITH MECHANICAL JOINTS - NO THRUST

BLOCKS ARE TO BE USED. USE LEEMCO DI SERVICE TEE FOR IRRIGATION GOLF HEADS AND

LV200 ANGLE VALVE AND JOINT RESTRAINTS FOR ALL CONNECTIONS.

4) ALL PROGRAMMING OF NEW IRRIGATION ZONES TO BE PERFORMED BY AN IRRIGATION

ASSOCIATION (WWW.IRRIGATION.ORG) CERTIFIED IRRIGATION DESIGNER (CID) OR CERTIFIED

LANDSCAPE IRRIGATION AUDITOR (CLIA)

.4

.9

.3

.3

.3

.3

.2

.9

.9

D

A

O

R

N

O

S

R

P

P

A

R

D A

O R

N O

S R

E

F

F

E

J

S

A

M

O

H

T

S E

C T

IO

N

S E

C T

IO

N

(N O

T B

U R

IE

D

V E

R T

IC

A

L M

A R

K E

R S

(1 .1

A

C R

E

A

C R

E

W

W

W

W

W

W

W

W

W

W

R

E

F E

R

E

N

E

F E

R

E

N

E

C

T I

T

H

O

M

A

S

J

E

F

F

E

R

S

O N

R O

A D

R

T Y

P

T Y

P

T Y

P

Q

Q

Q

Q

US Army Corps of

Engineers ®

Norfolk District

1909 CYPRESS AVENUE

VIRGINIA BEACH, VA

23451

(757) 417 - 0140

OFSHEET

N O

R F

O

S

T R

I C

T

C O

R

G

I N

E E

R S

N O

R F

O L

R

G I N

I A

D A

T E

C

H E

C K

E D

S U

B M

I T

T E

D

S C

A L E

N O

R F

O

S

T R

I C

T

F

I

P R

O J E

D R

A W

I N

G

N

O

S P

E C

I F

I C

A T

I O

N

N

O

D R

A W

N

D E

S I G

N E

D

L a s t w o r k e d o n

F l e n a m e

P l o t s c a l e

T

E D

R E

V

D A

T E

D E

S C

R I P

T I O

N B

Y A

P P

Q U

A N

TI

C

O N

A

TI

O N

A L

C E

M

TE

R Y

E X

P A

N S

IO

N

IM

P R

O V

E M

E N

TS

W

A R

K R

R

W A

R

T

MSA, P.C.

5033 Rouse Drive, Virginia Beach, VA 23462 757-490-9264 (Ofc) 757-490-0634 (Fax) www.msaonline.com

Environmental Sciences Planning Surveying Civil & Environmental Engineering

Landscape Architecture

AS

M

F I N

B

M I T

T A

L

V

E M

B E

R

GRAPHIC SCALE

LI110

I R

R I G

A T

I O

N

P

L A

N

C O

L U

M B

A R

I U

M

A

R E

Engineers ®

Norfolk District

1909 CYPRESS AVENUE

VIRGINIA BEACH, VA

23451

(757) 417 - 0140

OFSHEET

N O

R F

O

S

T R

I C

T

C O

R

G

I N

E E

R S

N O

R F

O L

R

G I N

I A

D A

T E

C

H E

C K

E D

S U

B M

I T

T E

D

S C

A L E

N O

R F

O

S

T R

I C

T

F

I

P R

O J E

D R

A W

I N

G

N

O

S P

E C

I F

I C

A T

I O

N

N

O

D R

A W

N

D E

S I G

N E

D

L a s t w o r k e d o n

F l e n a m e

P l o t s c a l e

T

E D

R E

V

D A

T E

D E

S C

R I P

T I O

N B

Y A

P P

Q U

A N

TI

C

O N

A

TI

O N

A L

C E

M

TE

R Y

E X

P A

N S

IO

N

IM

P R

O V

E M

E N

TS

W

A R

K R

R

W A

R

T

MSA, P.C.

5033 Rouse Drive, Virginia Beach, VA 23462 757-490-9264 (Ofc) 757-490-0634 (Fax) www.msaonline.com

Environmental Sciences Planning Surveying Civil & Environmental Engineering

Landscape Architecture

AS

M

F I N

B

M I T

T A

L

V

E M

B E

R

LI501

I R

R I G

A T

I O

N

P

L A

N

D E

T A

I L S

6" FIXED SPRAY SPRINKLER

SCALE: NTS

MATCHED PRECIPITATION

RATE NOZZLE

INSTALL SPRINKLER AT

FINISHED GRADE

APPROVED BACKFILL

FIXED SPRAY SPRINKLER

MALE ELL

FUNNY PIPE

LATERAL PIPE

LATERAL TEE

GEAR DRIVE ROTOR W/SWING ASSEMBLY

SCALE: NTS

APPROVED BACKFILL

SPRINKLER HEAD

AT GRADE)

3/4" OR 1" MANUFACTURED SWING ASSEMBLY

LATERAL PIPE

LATERAL TEE

IRR

IRR

RAINBIRD ESP-SAT FIELD CONTROLLER

IRR

SCALE: NTS

WITH LEEMCO LV-200 LATERAL CONNECTION

IRR

SCALE: NTS

ELECTRIC REMOTE CONTROL VALVE

SAT

INSTALL A #4 BARE COPPER GROUND WIRE FROM

GROUND ROD GRID A MINIMUM OF 150' WITHIN

AN ADJACENT FAIRWAY OR IRRIGATED AREA.

WIRING SHALL BE INSTALLED IN OPEN TRENCH ONLY

ADD ADDITIONAL PLATES AND RODS TO ACHIEVE

10 OHMS OR LESS IN GROUNDING WHERE NECESSARY.

24" MIN.

#4 BARE COPPER WIRE TO

8' COPPER GROUND ROD

16' SPACING

BETWEEN RODS

WIRING TO VALVES

GROUND WIRE INSTALLATION W/ CONTROLLER

IRR

SCALE: NTS

CONCRETE SUPPORT SLAB

RAINBIRD 751 GOLF ROTOR

IRR

SCALE: NTS

QUICK COUPLING VALVE ASSEMBLY

IRR

SCALE: NTS

LASCO UNITIZED #G17B-212

SWING JOINT W/ BRASS INSERT

ADD EXTRA SUPPORT BY

PLACING REBAR IN SPECIAL LUGS

6" ECONO VALVE BOX &

LID INSTALLED AT GRADE

QUICK COUPLING VALVE

INSTALLED 2-3" BELOW GRADE

QUICK COUPLER VALVE

BODY SUPPORTED W/

TWO U-BOLTS & REBAR.

MINIMUM 24" LONG WITH

A 1x1x12 PIECE OF REDWOOD

REBAR & VALVE BODY.

BRASS NIPPLE

1" BRASS INSERT

90 DEGREE ELL OUTLET

DUCTILE IRON SERVICE TEE

WITH RESTRAINING JOINTS

Engineers ®

Norfolk District

1909 CYPRESS AVENUE

VIRGINIA BEACH, VA

23451

(757) 417 - 0140

OFSHEET

N O

R F

O

S

T R

I C

T

C O

R

G

I N

E E

R S

N O

R F

O L

R

G I N

I A

D A

T E

C

H E

C K

E D

S U

B M

I T

T E

D

S C

A L E

N O

R F

O

S

T R

I C

T

F

I

P R

O J E

D R

A W

I N

G

N

O

S P

E C

I F

I C

A T

I O

N

N

O

D R

A W

N

D E

S I G

N E

D

L a s t w o r k e d o n

F l e n a m e

P l o t s c a l e

T

E D

R E

V

D A

T E

D E

S C

R I P

T I O

N B

Y A

P P

Q U

A N

TI

C

O N

A

TI

O N

A L

C E

M

TE

R Y

E X

P A

N S

IO

N

IM

P R

O V

E M

E N

TS

W

A R

K R

R

W A

R

T

MSA, P.C.

5033 Rouse Drive, Virginia Beach, VA 23462 757-490-9264 (Ofc) 757-490-0634 (Fax) www.msaonline.com

Environmental Sciences Planning Surveying Civil & Environmental Engineering

Landscape Architecture

AS

M

F I N

B

M I T

T A

L

V

E M

B E

R

LI502

I R

R I G

A T

I O

N

P

L A

N

D E

T A

I L S

LARGE TURF GEARED ROTOR AND TRENCHING DETAIL

SCALE: NTS

IRR

N O

R T

H

3'

APPLICABLE BUILDING CODES

USE GROUP/OCCUPANCY

FIRE PROTECTION SYSTEMS

CONSTRUCTION TYPE

ALLOWABLE AREA & HEIGHT

ACTUAL AREA & HEIGHT

FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS

EXTERIOR WALLS

INTERIOR FIRE RESISTANCE REQUIREMENTS

INTERIOR FINISH CLASSIFICATION

TRAVEL DISTANCES

CAPACITY OF EXITS

ADDITIONAL LIFE SAFETY CRITERIA

MEANS OF EGRESS

LEGEND

1. IBC INTERNATIONAL BUILDING CODE, 2012

2. FPDM DEPARTMENT OF VETERANS AFFAIRS - FIRE PROTECTION DESIGN MANUAL, SIXTH EDITION

3. UFC 1-200-01 GENERAL BUILDING REQUIREMENTS, 1 NOVEMBER 2014

4. UFC 3-600-01 FIRE PROTECTION ENGINEERING FOR FACILITIES, 1 MARCH 2013

5. NFPA 10 STANDARD FOR PORTABLE FIRE EXTINGUISHERS, 2013

6. NFPA 13 INSTALLATION OF SPRINKLER SYSTEMS, 2013

7. NFPA 70 NATIONAL ELECTRIC CODE, 2014

8. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE, 2013

9. NFPA 90A INSTALLATION OF AIR-CONDITIONING AND VENTILATING SYSTEMS, 2015

10. NFPA 101 LIFE SAFETY CODE, 2015 (LSC)

11. UFAS UNIFORM FEDERAL ACCESSIBILITY STANDARDS

12. ABA ARCHITECTURAL BARRIERS ACT

LIMITS BASED ON BUSINESS OCCUPANCY WITH PERMITTED REDUCTION FOR SPRINKLERS (TABLE A.10.2.2):

EXITS MINIMUM CLASS C

EXIT ACCESS CORRIDORS MINIMUM CLASS C

OTHER SPACES MINIMUM CLASS C

FLOOR FINISH IN EXITS, EXIT ACCESS CORRIDORS, & OTHER SPACES NO REQUIREMENT

FLOOR LEVEL

REQUIRED EXIT

CAPACITY

AVAILABLE EXIT

CAPACITY

NUMBER OF EXITS

REQUIRED

NUMBER OF EXITS

PROVIDED

FIRST FLOOR 3290054

FIRE SEPARATION DISTANCE (FSD)

FSD < 10 FT

GROUP B

1 HR.

FSD > 10 FT 0 HR.

AREA OCCUPANCY USE

APPROX. AREA

(SF)

OCCUPANT LOAD

FACTOR

(SF/PERSON)

OCCUPANT LOAD

(PERSONS)

GROUND FLOOR

BUSINESS 5,325 100 53OFFICE AND SUPPORT

5,535 54TOTAL

EQUIPMENT ROOMS 210 1300MEP

B BUSINESS (IBC 304.1, LSC 6.1.11.1) - ORDINARY HAZARD (LSC 38.1.5)

WET PIPE SPRINKLER SYSTEM

ADDRESSABLE FIRE ALARM SYSTEM

ADMIN BUILDING TYPE V-B

BASED ON GROUP B USE GROUP

BASIC AREA (IBC TABLE 503): 9,000 SF

INCREASE FOR AUTOMATIC SPRINKLERS (200%) (IBC 506.3): 27,000 SF

TOTAL ALLOWABLE AREA PER STORY: 36,000 SF

BASIC ALLOWABLE STORIES/HEIGHT (IBC TABLE 503): 2/40 FT

INCREASE FOR AUTOMATIC SPRINKLERS (IBC 504.2): 1/20 FT

TOTAL ALLOWABLE STORIES/HEIGHT: 3/60 FT

TOTAL FOOTPRINT FLOOR AREA 7,572 SF

TOTAL BUILDING HEIGHT 1 STORY/20 FT

(IBC TABLE 601, TYPE V-B CONSTRUCTION)

STRUCTURAL FRAME, INCL. COLUMNS, GIRDERS & TRUSSES 0 HR

BEARING WALLS, INTERIOR & EXTERIOR 0 HR

NON-BEARING WALLS, INTERIOR & EXTERIOR 0 HR

FLOOR CONSTRUCTION 0 HR

ROOF CONSTRUCTION 0 HR

EXTERIOR FIRE-RESISTANCE RATING BASED ON FIRE SEPARATION DISTANCE (TYPE V-B)

THE BUILDING IS LOCATED MORE THAN 40-FEET FROM ANY SURROUNDING STRUCTURES; THEREFORE, NO EXTERIOR WALL RATINGS

BASED ON FIRE SEPARATION DISTANCE ARE REQUIRED.

OCCUPANT LOADS (LSC TABLE 7.3.1.2)

BUSINESS 100 SF/PERSON

ASSEMBLY (LESS CONCENTRATED USE WITHOUT FIXED SEATING) 15 SF/PERSON

MEP SPACE 300 SF/PERSON

STORAGE (IN OTHER THAN STORAGE OCCUPANCIES) 500 SF/PERSON

COMMON PATH OF TRAVEL (LSC TABLE A.7.6): (BUSINESS): 100 FT.

TOTAL TRAVEL DISTANCE (LSC TABLE A.7.6): (BUSINESS): 300 FT.

DEAD END CORRIDOR (LSC TABLE A.7.6): (BUSINESS): 50 FT.

CAPACITY OF EXITS (LSC TABLE 7.3.3.1):

LEVEL COMPONENTS (WIDTH/PERSON) 0.2 IN/PERSON

NUMBER OF EXITS (LSC 7.4)

2 FOR OCCUPANT LOAD < 500

3 FOR OCCUPANT LOAD > 500 AND < 1,000

EMERGENCY LIGHTING SYSTEMS SHALL PROVIDE IN ACCORDANCE WITH LSC 7.9 (LSC 38.2.9.1).

MEANS OF EGRESS SHALL BE PROVIDED WITH SIGNS IN ACCORDANCE WITH LSC 7.10 AND UFC 3-600-01 2-5.2 (LSC 38.2.10). SIGNS MUST

HAVE LETTERING ON AN OPAQUE BACKGROUND. INTERNALLY ILLUMINATED SIGNS MUST BE LIGHT EMITTING DIODE (LED) TYPE, ELECTROLUMINESCENCE (LEC), OR COLD CATHODE TYPE. INCANDESCENT FIXTURES ARE NOT PERMITTED. RADIOLUMINOUS EXIT SIGNS

ARE NOT PERMITTED (UFC 3-600-01 2-5.2).

FIRE EXTINGUISHERS SHALL BE PROVIDED IN ACCORDANCE WITH LSC AND NFPA 10 REQUIREMENTS (LSC 38.3.5).

ROOM AREA (SQ. FT)

OCCUPANT LOAD (SQ. FT/PERSON)

NUMBER OF OCCUPANTS (PERSONS)

REQUIRED EGRESS CAPACITY

PROVIDED EGRESS CAPACITY

TRAVEL DISTANCE

DEAD END CORRIDOR DISTANCE

COMMON PATH OF TRAVEL DISTANCE

SEMI-RECESSED FIRE EXTINGUISHER

CABINET

NONE

1,000

TD = ## FT

DE = ## FT

CPT = ## FTA

OF

1909 CYPRESS AVENUE

VIRGINIA BEACH, VA 23451

(757) 417 - 0140

US Army Corps of Engineers Norfolk District

SHEET

N O

R F

O

LK

D

IS

T R

IC

T

C O

R P

S O

F E

N G

IN

E

E R

S N

O R

F O

LK

V

IR

G

IN

IA

D A

T E

C

H E

C K

E D

S U

B M

IT

T

E D

S

C A

LE

N O

R F

O

LK

D

IS

T R

IC

T

F

IL

E N

O

P R

O

JE

C T

N O

D R

A W

IN

G

N O

S

P E

C

IF

IC

A

T

IO

N N

O

D R

A W

N

D E

S

IG

N E

D

La st w or ke d on

F le n am e:

P lo t s ca le

1:

A S

N O

T E

D

R E

V

D A

T E

D E

S C

R

IP

T

IO

N B

Y A

P P

B

C

D

A

B

C

D

2 3 4 5 1 2 3 4 5

F

IN

A L

S U

B M

IT

T

A L

N

O V

E M

B E

R

03 NOV 2017

Lic. No. 044409

AARON P FREIDC

O M M O

N W

EA

LTHOF

V

IR

G

IN

IA

P R O F

E

SSIONAL EN

G

IN

E E R

V :\1

A

JW

\0

-0

\1 A

JW

8.

Q ua nt ic o N

C A dm in

R en o\ C

A D

R ev it

\1

3- T

Q ua nt ic o N at io na l

C em et er y E xp an si on

F ire .r vt

/1

2/

:5 9:

P

M

LS001

Q U

A N

T

IC

O N

A T

IO

N

A L C

E M

E T

E R

Y

B L D

G R

E N

O V

G

R A

V E

S

IT

E I M

P R

O V

E

B U

IL

D

IN

G

C O

D E

A N

D L

IF

E

S A

F E

T Y

A N

A L Y

S

IS

A E

C

D E

G

A

JW

-I I

/0

3/

12673

A

F

UP

A

B

C

D

E

F

G

2 3 4 5 6

5,325

DE = 21 FT

VESTIBULE

FIN. OPEN

OFFICE 01

FIN.OFF.

CORRIDOR

CON. OPEN

OFFICE 01

CORRIDOR

CON. OFF.

CON. OPEN

OFFICE 02

OPERATIONS

OPEN OFFICE

CON. OPEN

OFFICE 03

BREAK

JAN.

FIRE

STOR.

FIN. OPEN

OFFICE 02

MECH / ELEC

COMM / IT

MEN'S

WOMEN'S

CL.

C P

T

F T

T D

F

T

A

OF

1909 CYPRESS AVENUE

VIRGINIA BEACH, VA 23451

(757) 417 - 0140

US Army Corps of Engineers Norfolk District

SHEET

N O

R F

O

LK

D

IS

T R

IC

T

C O

R P

S O

F E

N G

IN

E

E R

S N

O R

F O

LK

V

IR

G

IN

IA

D A

T E

C

H E

C K

E D

S U

B M

IT

T

E D

S

C A

LE

N O

R F

O

LK

D

IS

T R

IC

T

F

IL

E N

O

P R

O

JE

C T

N O

D R

A W

IN

G

N O

S

P E

C

IF

IC

A

T

IO

N N

O

D R

A W

N

D E

S

IG

N E

D

La st w or ke d on

F le n am e:

P lo t s ca le

1:

A S

N O

T E

D

R E

V

D A

T E

D E

S C

R

IP

T

IO

N B

Y A

P P

B

C

D

A

B

C

D

2 3 4 5 1 2 3 4 5

F

IN

A L

S U

B M

IT

T

A L

N

O V

E M

B E

R

03 NOV 2017

Lic. No. 044409

AARON P FREIDC

O M M O

N W

EA

LTHOF

V

IR

G

IN

IA

P R O F

E

SSIONAL EN

G

IN

E E R

V :\1

A

JW

\0

-0

\1 A

JW

8.

Q ua nt ic o N

C A dm in

R en o\ C

A D

R ev it

\1

3- T

Q ua nt ic o N at io na l

C em et er y E xp an si on

F ire .r vt

/1

2/

:5 9:

P

M

LS101

Q U

A N

T

IC

O N

A T

IO

N

A L C

E M

E T

E R

Y

B L D

G R

E N

O V

G

R A

V E

S

IT

E I M

P R

O V

E

L

IF

E S

A F

E T

Y F

L O

O R

P L A

N

A E

C

D E

G

A

JW

-I I

/0

3/

12674

A P

F

1/8" = 1'-0"

LIFE SAFETY FLOOR PLAN

4' 8' 16' 32'0'

1/8" =1'-0"SCALE:

GRAPHIC SCALE

NOTE: IF THIS DRAWING IS A REDUCTION, GRAPHIC SCALE

MUST BE USED.

ARCH. ARCHITECT, ARCHITECTURAL

BLDG. BUILDING

BOTT. BOTTOM

C.M.U. CONCRETE MASONRY UNIT

C.J. CONTROL JOINT

COL. COLUMN

CONC. CONCRETE

CONN. CONNECTION

CONT. CONTINUOUS

DIA. DIAMETER

DIAG. DIAGONAL

DWG. DRAWING

E.F. EACH FACE

ELEV. ELEVATION

EXIST. EXISTING

EXP. EXPANSION

FOUND. FOUNDATION

FNDN. FOUNDATION

F.O. FACE OF

F.O. FACE OF BRICK

FTG. FOOTING

GALV. GALVANIZED

HORIZ. HORIZONTAL

INSUL. INSULATION

JT. JOINT

L ANGLE

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

MECH. MECHANICAL

OPP. OPPOSITE

STRUCTURAL ABBREVIATIONS LIST

P.S.I. POUNDS PER SQUARE INCH

P.S.F. POUNDS PER SQUARE FOOT

REF. REFERENCE

REINF. REINFORCE,REINFORCING

REQ'D. REQUIRED

SCHED. SCHEDULE

SECT. SECTION

SHT. SHEET

SPECS. SPECIFICATIONS

STL. STEEL

T.O. TOP OF

TYP. TYPICAL

U.O.N. UNLESS OTHERWISE NOTED

VERT. VERTICAL

W.W.F. WELDED WIRE FABRIC

W/ WITH

W/O WITHOUT

C.L. CENTERLINE

PL. PLATE

O.C. ON CENTER

Ø DIAMETER

° DEGREES

± PLUS OR MINUS

A

OF

1909 CYPRESS AVENUE

VIRGINIA BEACH, VA 23451

(757) 417 - 0140

US Army Corps of Engineers Norfolk District

SHEET

N O

R F

O

LK

D

IS

T R

IC

T

C O

R P

S O

F E

N G

IN

E

E R

S N

O R

F O

LK

V

IR

G

IN

IA

F

IN

A L

S U

B M

IT

T

A L

N

O V

E M

B E

R

D A

T E

C

H E

C K

E D

S U

B M

IT

T

E D

S

C A

LE

N O

R F

O

LK

D

IS

T R

IC

T

F

IL

E N

O

P R

O

JE

C T

N O

D R

A W

IN

G

N O

S

P E

C

IF

IC

A

T

IO

N N

O

D R

A W

N

D E

S

IG

N E

D

La st w or ke d on

F le n am e:

P lo t s ca le

1:

A S

N O

T E

D

R E

V

D A

T E

D E

S C

R

IP

T

IO

N B

Y A

P P

B

C

D

A

B

C

D

2 3 4 5 1 2 3 4 5

C :\A

_R ev it Lo ca l F ile s\

-T Q ua nt ic o

N at io na l C em et er y E xp an si on

S tr uc t_ C

O M

P U

T E

R

.r vt

/1

2/

:5 2:

P

M

S-001

Q U

A N

T

IC

O N

A T

IO

N

A L C

E M

E T

E R

Y

B L D

G R

E N

O V

G

R A

V E

S

IT

E I M

P R

O V

E

G E

N E

R A

L N

O T

E S

LM

M

JS

S

M

LM

-Y

/0

3/

11/03/2017 12675

JS

S

GENERAL NOTES:

GENERAL NOTES:

1.THIS STRUCTURE HAS BEEN DESIGNED IN ACCORDANCE WITH THE PROVISIONS OF THE INTERNATIONAL BUILDING CODE, 2012 EDITION, AS ADOPTED BY THE VIRGINIA UNIFORM STATEWIDE BUILDING CODE, 2012 EDITION, EFFECTIVE JULY, 2014 AND AS MODIFIED BY UFC 1-200-01, AND IN ACCORDANCE WITH UFC 3-301,01 "STRUCTURAL ENGINEERING", DATED JUNE 2013.

2.ALL WORK SHALL COMPLY WITH THE CODES LISTED BELOW AND IN THE SPECIFICATIONS.

3.VERIFY ALL DRAWINGS FOR COORDINATION BETWEEN TRADES, LOCATE SLOTS, SLEEVES AND TRENCHES AS REQUIRED FOR MECHANICAL TRADES. PROVIDE AND INSTALL ANCHORS, INSERTS, HANGERS, ETC. AS REQUIRED FOR

VARIOUS TRADES.

4.THE CONTRACTOR IS RESPONSIBLE FOR DIMENSIONS, ELEVATIONS, ETC., NECESSARY FOR THE PROPER CONSTRUCTION AND ALIGNMENT OF THE NEW PORTIONS OF THE STRUCTURE TO THE EXISTING STRUCTURE. MAKE ALL MEASUREMENTS NECESSARY PRIOR TO THE FABRICATION AND ERECTION OF STRUCTURAL MEMBERS.

5.BEFORE PROCEEDING WITH ANY WORK WITHIN THE EXISTING STRUCTURE, BECOME FAMILIAR WITH STRUCTURAL CONDITIONS OF THE EXISTING STRUCTURE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE ALL NECESSARY SAFEGUARDS, TO MAINTAIN ALL PARTS OF THE STRUCTURE IN A SAFE CONDITION AT ALL TIMES DURING THE PROCESS OF CONSTRUCTION AND TO PROTECT FROM DAMAGE THOSE PORTIONS OF THE EXISTING BUILDING WHICH

ARE TO REMAIN.

6.SUBMIT SHOP DRAWINGS OF REINFORCEMENT DETAILS, STRUCTURAL STEEL, ETC. FOR APPROVAL BEFORE PROCEEDING WITH THE WORK. THE CONTRACTOR SHALL CHECK ALL DIMENSIONS AND ACCEPT FULL RESPONSIBILITY

FOR DIMENSIONAL CORRECTNESS.

7.UNDER NO CIRCUMSTANCES SHALL REPRODUCTION OF CONTRACT DRAWINGS BE USED AS SHOP DRAWINGS.

8. PROVIDE ALL TEMPORARY GUYING AND BRACING REQUIRED TO ERECT AND HOLD THE STRUCTURE IN PROPER

ALIGNMENT UNTIL ALL STRUCTURAL WORK AND CONNECTIONS HAVE BEEN COMPLETED.

9.LOADING APPLIED TO THE STRUCTURE DURING THE PROCESS OF CONSTRUCTION SHALL NOT EXCEED THE SAFE LOAD-CARRYING CAPACITY OF THE STRUCTURAL MEMBERS. THE LIVE LOADINGS USED IN THE DESIGN OF THIS STRUCTURE ARE INDICATED IN THE “DESIGN CRITERIA NOTES”. DO NOT APPLY ANY CONSTRUCTION LOADS UNTIL ALL STRUCTURAL FRAMING IS PROPERLY CONNECTED TOGETHER AND UNTIL ALL TEMPORARY BRACING IS IN PLACE.

10. IN ACCORDANCE WITH GENERALLY ACCEPTED CONSTRUCTION PRACTICES, CONTRACTOR WILL BE SOLELY AND COMPLETELY RESPONSIBLE FOR CONDITION OF JOB SITE INCLUDING SAFETY OF ALL PERSONS AND PROPERTY

DURING PERFORMANCE OF THE WORK.

11. THE DUTY OF THE ARCHITECT IN CONDUCTING CONSTRUCTION REVIEW OF CONTRACTOR'S PERFORMANCE IS NOT INTENDED TO INCLUDE REVIEW OF ADEQUACY OF CONTRACTOR'S SAFETY MEASURES IN, ON, OR NEAR THE

CONSTRUCTION SITE.

12. TYPICAL DETAILS AND GENERAL NOTES APPLY TO ALL PARTS OF THE JOB EXCEPT WHERE SPECIFICALLY

DETAILED OR NOTED OTHERWISE.

13. STRUCTURAL DRAWINGS SHOW ONLY THE BASIC STRUCTURAL FRAMING. REFER TO ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS FOR NON-STRUCTURAL ITEMS WHICH REQUIRE SPECIAL PROVISIONS

DURING THE CONSTRUCTION OF THE STRUCTURAL FRAME.

14. INFORM THE PROFESSIONAL OF RECORD IN WRITING OF ANY DEVIATION FROM THE CONTRACT DOCUMENTS.

THE CONTRACTOR IS NOT RELIEVED OF THE RESPONSIBILITY OF SUCH DEVIATION BY THE PROFESSIONAL OF RECORD REVIEW OF SHOP DRAWINGS, PRODUCT DATA, ETC. UNLESS THE CONTRACTOR HAS SPECIFICALLY INFORMED THE PROFESSIONAL OF RECORD OF SUCH DEVIATION AT THE TIME OF SUBMISSION, AND THE

PROFESSIONAL OF RECORD HAS GIVEN WRITTEN APPROVAL TO THE SPECIFIC DEVIATION.

15. MECHANICAL UNITS AND EQUIPMENT LOCATIONS SHOWN ON THE PLANS ARE APPROXIMATE. CONTRACTOR SHALL VERIFY LOCATIONS AND WEIGHTS SHOWN AND REPORT DISCREPANCIES TO THE ARCHITECT PRIOR TO

INSTALLATION.

FOUNDATION NOTES:

1.FOUNDATIONS HAVE BEEN DESIGNED IN ACCORDANCE WITH THE RECOMMENDATIONS IN THE GEOTECHNICAL EXPLORATION REPORT, PREPARED BY THE US CORP OF ENGINEERS, AND DATED OCTOBER 2015.

2.ALL NEW FOUNDATIONS SHALL BE FOUNDED ON VERY WELL COMPACTED STRUCTURAL SOIL WITH A DESIGN

BEARING PRESSURE OF 2,000 PSF.

3.PRIOR TO PLACING FOUNDATION CONCRETE, ALL FOUNDATION EXCAVATIONS SHALL BE INSPECTED BY THE GEOTECHNICAL ENGINEER TO VERIFY THE DESIGN BEARING PRESSURE AND THAT THE SETTLEMENTS ARE WITHIN GENERALLY ACCEPTED TOLERABLE LIMITS. THE GEOTECHNICAL ENGINEER WILL PROVIDE DIRECTION

FOR CORRECTIVE ACTION WHERE REQUIRED.

4.DO NOT INSTALL FOUNDATION WORK UNTIL IT HAS BEEN COORDINATED WITH ADJACENT UNDERGROUND

UTILITIES, ETC. FOOTINGS SHALL BE LOWERED WHERE REQUIRED.

5.DO NOT PUT IN UNBALANCED BACKFILL AGAINST FOUNDATION WALLS UNLESS WALLS ARE SECURELY BRACED

AGAINST OVERTURNING.

6.FROST LINE DEPTH IS 24” BELOW GRADE. BOTTOM OF EXTERIOR FOUNDATIONS SHALL BEAR A MINIMUM OF 36”

BELOW FINAL GRADE. LOWER FOOTINGS AS REQUIRED TO MAINTAIN COVERAGE.

CAST IN PLACE CONCRETE NOTES:

1.CAST IN PLACE CONCRETE SHALL COMPLY WITH THE AMERICAN CONCRETE INSTITUTE (ACI- 318-11), COMMENTARY, (ACI-318R-11), AND THE SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS (ACI 301).

2.ALL CONCRETE SHALL BE NORMAL WEIGHT AGGREGATE CONCRETE HAVING A MINIMUM COMPRESSIVE

STRENGTH AT 28 DAYS AS FOLLOWS:

A) SLAB ON GRADE 3,500 PSI

B) CONCRETE OTHERWISE NOTED 3,000 PSI

C) CONCRETE EXPOSED TO WEATHER SHALL BE AIR ENTRAINED.

STRUCTURAL STEEL NOTES:

1.STRUCTURAL STEEL SHALL COMPLY WITH THE FOURTEENTH EDITION OF THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC 360-10) “STEEL CONSTRUCTION MANUAL” – ALLOWABLE STRESS DESIGN.

2.STRUCTURAL STEEL SHALL BE NEW, CLEAN, AND STRAIGHT, AND CONFORM TO THE FOLLOWING:

A) RECTANGULAR AND SQUARE HSS SHAPES - ASTM A500, GRADE B

B) ANCHOR RODS - ASTM F1554, GRADE 36

C) HIGH STRENGTH BOLTS – ASTM A325

D) ALL OTHER STEEL SHAPES - ASTM A36, UNLESS OTHERWISE NOTED

3.SHOW ALL HOLES REQUIRED IN STRUCTURAL STEEL MEMBERS FOR PIPING ON THE SHOP DRAWINGS AND MAKE THEM IN THE SHOP. DO NOT CUT HOLES IN THE FIELD WITHOUT THE APPROVAL OF THE REGISTERED DESIGN

PROFESSIONAL OF RECORD.

4.WELDING SHALL COMPLY WITH THE "STRUCTURAL WELDING CODE - STEEL" (AWS D1.1). WELD ELECTRODES SHALL BE E70XX.UNLESS OTHERWISE NOTED, MINIMUM WELD SIZE SHALL BE 3/16" CONTINUOUS FILLET WELDS

5.REFER TO THE ARCHITECTURAL, CIVIL, MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR ADDITIONAL

STEEL (IF ANY) NOT SHOWN ON THE STRUCTURAL DRAWINGS.

6.FOR PRIMING AND PAINTING OF EXTERIOR STEEL, REFER TO PAINTING SPECIFICATION.

DESIGN CRITERIA:

1.LOADS USED IN THE DESIGN OF THE NEW PORTION OF THE STRUCTURE ARE AS

FOLLOWS:

2.UNIFORM LIVE LOADS:

ROOF 20 PSF

3.ROOF SNOW LOADS:

GROUND SNOW LOAD Pg = 25 PSF SNOW EXPOSURE FACTOR Ce = 1.0

SNOW LOAD IMPORTANCE FACTOR I =1.0

THERMAL FACTOR Ct=1.0 UNIFORM ROOF DESIGN SNOW LOAD: Pf = 20 PSF

4.WIND LOADS:

RISK CATEGORY = II

ULTIMATE WIND SPEED = 115 MPH

NOMINAL WIND SPEED = 89 MPH

EXPOSURE CATEGORY (MAIN WINDFORCE-RESISTING SYSTEM): C

EXPOSURE CATEGORY (COMPONENTS AND CLADDING): C

INTERNAL PRESSURE COEFFICIENT: +/- 0.18 (ENCLOSED)

5.SEISMIC LOADS:

RISK CATEGORY II

IMPORTANCE FACTOR I = 1.0

Ss = .129 S1 = .053g

SOIL SITE CLASS D

Sds = 0.138 Sd1 = 0.085

SEISMIC DESIGN CATEGORY B

BASIC SEISMIC FORCE RESISTING SYSTEM: STRUCTURAL STEEL SYSTEMS NOT

SPECIFICALLY DETAILED FOR SEISMIC RESISTANCE

RESPONSE MODIFICATION FACTOR, R= 3.0

SEISMIC RESPONSE COEFFICIENT, Cs = 0.046

DESIGN BASE SHEAR: 0.046W

CAST IN PLACE CONCRETE NOTES CONT'D:

3.ALL REINFORCING SHALL BE AS FOLLOWS:

A) REINFORCING BARS - ASTM A-615, GRADE 60

4.UNLESS OTHERWISE NOTED, REINFORCING STEEL MARKED CONTINUOUS (CONT.) SHALL BE LAPPED 36x BAR

DIAMETER.

5.HOLD ALL REINFORCING STEEL SECURELY IN PLACE TO PREVENT DISLOCATION DURING THE POURING OPERATION. SUPPORT SLAB REINFORCING BARS ON HIGH CHAIRS AND BAR SPACERS OF SUITABLE DESIGN, OR CONCRETE BLOCKS HAVING THE SAME MINIMUM COMPRESSIVE STRENGTH OF THE CONCRETE SLAB.

6.DETAILING OF ALL CONCRETE STEEL REINFORCEMENT SHALL BE IN ACCORDANCE WITH THE MANUAL OF

STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES (ACI-315).

7.DO NOT PLACE CONCRETE UNTIL ALL EMBEDDED WORK HAS BEEN INSTALLED, TESTED AND INSPECTED.

8.EXCEPT AS OTHERWISE SHOWN MINIMUM PROTECTION (CONCRETE COVER) FOR REINFORCING STEEL SHALL BE

AS FOLLOWS:

CONCRETE SURFACES CAST AGAINST SOIL: 3"

CONCRETE SURFACES EXPOSED TO EARTH OR WEATHER:1-1/2"

LM

M

PHONE: (757) 474-0612 FAX: (757) 474-0919

VIRGINIA BEACH, VIRGINIA, 23464

748 LORD DUNMORE DRIVE, SUITE 101

NRW

CONSULTING STRUCTURAL ENGINEERS

1 2 3 4 5 6

B

C

D

E

F

G

F4.5 3 (-3'-8")

'-0

12'-0" ±

16'-0" ± 20'-0" ± 18'-4" ± 17'-8" ± 24'-4" ±

4' -0

'-4

5' -8

'-0

'-4

'-0

2 7

10"

EXISTING 6"Ø

STEEL COLUMN

(TYP)

5' -0

A

OF

1909 CYPRESS AVENUE

VIRGINIA BEACH, VA 23451

(757) 417 - 0140

US Army Corps of Engineers Norfolk District

SHEET

N O

R F

O

LK

D

IS

T R

IC

T

C O

R P

S O

F E

N G

IN

E

E R

S N

O R

F O

LK

V

IR

G

IN

IA

F

IN

A L

S U

B M

IT

T

A L

N

O V

E M

B E

R

D A

T E

C

H E

C K

E D

S U

B M

IT

T

E D

S

C A

LE

N O

R F

O

LK

D

IS

T R

IC

T

F

IL

E N

O

P R

O

JE

C T

N O

D R

A W

IN

G

N O

S

P E

C

IF

IC

A

T

IO

N N

O

D R

A W

N

D E

S

IG

N E

D

La st w or ke d on

F le n am e:

P lo t s ca le

1:

A S

N O

T E

D

R E

V

D A

T E

D E

S C

R

IP

T

IO

N B

Y A

P P

B

C

D

A

B

C

D

2 3 4 5 1 2 3 4 5

C :\A

_R ev it Lo ca l F ile s\

-T Q ua nt ic o

N at io na l C em et er y E xp an si on

S tr uc t_ C

O M

P U

T E

R

.r vt

/1

2/

:5 2:

P

M

S-101

Q U

A N

T

IC

O N

A T

IO

N

A L C

E M

E T

E R

Y

B L D

G R

E N

O V

G

R A

V E

S

IT

E I M

P R

O V

E

F O

U N

D A

T

IO

N P

L A

N

LM

M

JS

S

M

LM

-Y

/0

3/

11/03/2017 12676

JS

S

1/8" = 1'-0"

FOUNDATION PLAN

FOUNDATION PLAN NOTES:

1. DATUM FOR ELEVATIONS SHOWN ON PLAN IS EXISTING FINISHED

FLOOR = 0'-0"

2. BOTTOM OF ALL EXISTING FOOTINGS ARE AT (-3'-8"+/-) BELOW

DATUM.

3. BOTTOM OF NEW FOOTING IS INDICATED THUS: (-X'-X") INDICATING

DISTANCE BELOW DATUM.

FOUNDATION PLAN KEY NOTES:

SAWCUT & REMOVE EXISTING 5"± SLAB AT NEW PLUMBING,

REFER TO PLUMBING DRAWINGS FOR EXTENT OF SLAB

REMOVAL.

AT SLAB REMOVAL, PROVIDE 5" CONCRETE SLAB ON 15 MIL

VAPOR BARRIER AND 4" POROUS FILL. REINFORCE SLAB WITH #

3 @ 12" O.C. , EACH WAY LOCATED 1 " FROM TOP OF SLAB. FOR

NEW SLAB TO EXISTING SLAB-ON-GRADE JOINT DETAIL, REFER

TO SHEET S-301.

NEW HSS6x6x5/16 COLUMN & FOOTING, REFER TO NEW

SUPPORT DETAILS, SHEET S-301.

AT EXISTING BRICK CRACK, PROVIDE NEW BRICK EXPANSION

JOINT FROM TOP OF CONCRETE WALK TO TOP OF BRICK.

REMOVE BRICK, EACH SIDE OF JOINT AND TOOTH IN NEW BRICK

AND PROVIDE A 3/8" JOINT FILLED WITH PREMOLDED

COMPRESSIBLE FILLER AND SEALANT, REFER TO ARCH

DRAWING A-301 FOR DETAIL.

REMOVE EXISTING STEEL COLUMN TO 4" MINIMUM BELOW

FINISHED FLOOR. FOR SHORING REQUIREMENTS PRIOR TO

COLUMN REMOVAL, REFER TO ROOF SHEET S-102.

FOR HOUSEKEEPING SLAB, REFER TO PLUMBING DRAWINGS.

SAWCUT & REMOVE EXISTING 5"± SLAB AT NEW FOOTING.

REFER TO DETAILS ON SHEET S-301.

4'0 8' 16'

SCALE: 1/8"=1'-0"

GRAPHIC SCALE

LM

M

PHONE: (757) 474-0612 FAX: (757) 474-0919

VIRGINIA BEACH, VIRGINIA, 23464

748 LORD DUNMORE DRIVE, SUITE 101

ROOF FRAMING PLAN NOTES:

1.ELEVATION OF TOP OF EXISTING BAR JOISTS IS (+12'-8")±.

2.EXISTING ROOF DECK CONSISTS OF 1 1/2" - 20 GAGE METAL DECK.

3.UNLESS OTHERWISE NOTED, SUPPORT NEW DECK OPENINGS MEASURED

GREATER THAN 12" WITH L4X4X1/4. COORDINATE OPENING SIZES, LOCATIONS,

AND DETAILS WITH ARCHITECTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL

DWGS.

4.REINFORCE CONCENTRATED LOADS EXCEEDING 100 POUNDS APPLIED TO

EXISTING JOIST NOT AT PANEL POINT. SEE TYPICAL DETAIL ON S-301.

5.REFER TO TYPICAL ROOF MECHANICAL SUPPORT DETAIL ON SHEET S-301 FOR

ANY UNITS DIRECTLY SUPPORTED ON ROOF.

ROOF FRAMING KEY NOTES:

REMOVE EXISTING COLUMN AND CAP PLATE. SHORE ROOF EXISTING FRAMING

PRIOR TO REMOVING COLUMN. SHORE WIDE FLANGE BEAMS, EACH SIDE OF

COLUMN AND JOISTS FRAMING INTO COLUMN AT FIRST BOTTOM CHORD PANEL

POINT.

NEW HSS6X6X5/16 AND FOOTING TO SUPPORT W18. REFER TO NEW SUPPORT

DETAILS ON S-301.

AT EXISTING BRICK CRACK, PROVIDE NEW BRICK EXPANSION JOINT FROM TOP OF

CONCRETE WALK TO TOP OF BRICK. REMOVE BRICK, EACH SIDE OF JOINT AND

TOOTH IN NEW BRICK AND PROVIDE A 3/8" JOINT FILLED WITH PREMOLDED

COMPRESSIBLE FILLER AND SEALANT, REFER TO ARCH DRAWING S-301 FOR

DETAIL.

TRANSFORMER 750#, HANG FROM NEW FRAMING ATTACHED TO EXISTING ROOF

FRAMING. REFER TO TRANSFORMER SUPPORT DETAIL ON S-301 AND

ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION.

ADD (2) W8X21 BEAMS TO EXISTING W-BEAM ROOF TOP MECHANICAL UNIT

SUPPORTS. VERIFY EXACT LOCATIONS WITH MECHANICAL UNIT REQUIREMENTS

AND EXISTING FIELD CONDITIONS. REFER TO MECHANICAL UNIT SUPPORT

CONNECTION DETAIL ON SHEET S-301.

NEW ROOFTOP UNIT. PROVIDE ANGLES AROUND UNIT EDGES AND NEW DECK

OPENINGS, REFER TO ROOF FRAMING NOTES 3 & 5.

CLEAN EXISTING STEEL AND REMOVE LOOSE RUST, SCALE AND PAINT. REPAINT

STEEL PER SPECIFICATIONS.

1 2 3 4 5 6

A

B

C

D

E

F

G

4'-3 1/2" ± 16'-0" ± 20'-0" ± 18'-4" ± 17'-8" ± 24'-4" ± 4'-3 1/2" ±

62'-11" ± 9'-1" ± 32'-11" ±

4' -3

/2

'-0

'-4

'-0

5' -8

'-4

4' -0

4' -3

/2

'-0

'-1

1"

EXIST.

W21X44

EXIST.

W21X44

EXIST.

W12X22

EXIST.

W12X22

E X

IS

T

W

X

E

X

IS

T

W

X

EXIST.

W21X44

EXIST.

W14X30

EXIST.

W12X22

EXIST.

W14X30

E X

IS

T

W

X

E

X

IS

T

W

X

EXIST.

W14X30

EXIST.

W14X30

E X

IS

T

W

X

E X

IS

T

W

X

EXIST.

W12X22

EXIST.

HSS12X3X1/4

EXIST.

HSS12X3X1/4

E X

IS

T

W

X

EXIST.

W14X30

EXIST.

W12X22

E X

IS

T

W

X

E X

IS

T

W

X

EXIST.

W14X30

E X

IS

T

W

X

E X

IS

T

W

X

E X

IS

T

W

X

E X

IS

T

W

X

E X

IS

T

W

X

E X

IS

T

. 1 8H

JO

IS

T

S

E X

IS

T

. 1 2H

JO

IS

T

S

EXIST.

W12X22

E X

IS

T

. 1 2H

JO

IS

T

S

EXIST.

W12X22

E X

IS

T

. 1 6H

JO

IS

T

S

E X

IS

T

W

X

EXIST. C12X20.7

EXIST. W12X22

EXIST. 12H4

EXIST. 12H4

EXIST. C12X20.7

EXIST. 12H4

EXIST. 12H4

EXIST.

EXIST. W14x22

W12X16

EXIST.

W14X22

EXIST.

W12X16

EXIST. W14x22

EXIST.

W12X16

EXIST. W8X10

EXIST.

W8X10

EXIST. W8X10

EXIST.

W8X10

EXIST.

W8x10

EXIST.

HSS12X3X1/4

EXIST. HSS12X3X1/4

EXIST.

W8X40

EXIST.

W8X40

EXIST.

W8X40

EXIST. W8X40

EXIST.

W21X44

EXIST.

W12X16

EXIST. W12x22

EXIST. C12X20.7

EXIST.

C12X20.7

RTU-1

1,000#

RTU-2

1,000#

RTU-3

1,000#

EXIS

T. 6

"Ø C

OLU

MN

EXIST.

W12X16

(T

YPIC

AL U

.O

.N

EXIST. W-BEAM @ ROOFTOP FRAME

(ABOVE EXIST. ROOF)

5' -0

EXIST. ROOF

HATCH

A

OF

1909 CYPRESS AVENUE

VIRGINIA BEACH, VA 23451

(757) 417 - 0140

US Army Corps of Engineers Norfolk District

SHEET

N O

R F

O

LK

D

IS

T R

IC

T

C O

R P

S O

F E

N G

IN

E

E R

S N

O R

F O

LK

V

IR

G

IN

IA

F

IN

A L

S U

B M

IT

T

A L

N

O V

E M

B E

R

D A

T E

C

H E

C K

E D

S U

B M

IT

T

E D

S

C A

LE

N O

R F

O

LK

D

IS

T R

IC

T

F

IL

E N

O

P R

O

JE

C T

N O

D R

A W

IN

G

N O

S

P E

C

IF

IC

A

T

IO

N N

O

D R

A W

N

D E

S

IG

N E

D

La st w or ke d on

F le n am e:

P lo t s ca le

1:

A S

N O

T E

D

R E

V

D A

T E

D E

S C

R

IP

T

IO

N B

Y A

P P

B

C

D

A

B

C

D

2 3 4 5 1 2 3 4 5

C :\A

_R ev it Lo ca l F ile s\

-T Q ua nt ic o

N at io na l C em et er y E xp an si on

S tr uc t_ C

O M

P U

T E

R

.r vt

/1

2/

:5 2:

P

M

S-102

Q U

A N

T

IC

O N

A T

IO

N

A L C

E M

E T

E R

Y

B L D

G R

E N

O V

G

R A

V E

S

IT

E I M

P R

O V

E

R O

O F

F R

A M

IN

G

P L A

N

LM

M

JS

S

M

LM

-Y

/0

3/

11/03/2017 12677

JS

S

1/8" = 1'-0"

ROOF FRAMING PLAN

4'0 8' 16'

SCALE: 1/8"=1'-0"

GRAPHIC SCALE

LM

M

PHONE: (757) 474-0612 FAX: (757) 474-0919

VIRGINIA BEACH, VIRGINIA, 23464

748 LORD DUNMORE DRIVE, SUITE 101

TYPICAL ADDED REINF. @ CONCENTRATED

LOADS BETWEEN PANEL POINTS

L-2x2x1/4

EXIST JOIST, REFER

TO PLAN

NOT TO SCALE

LOAD

LOAD

1/8

TYP. EACH

END

PLACE HANGER ROD ON JOIST CENTERLINE

BETWEEN BOTTOM CHORD ANGLES. "C"

CLAMP CONNECTIONS ARE NOT PERMITTED.

DETAIL APPLIES FOR LOADS GREATER

THAN 100# AND OCCURS MORE THAN 6"

FROM JOIST PANEL POINT

TYPICAL ROOF MECHANICAL UNIT

SUPPORT DETAIL

1/4" TAB PLATE (TYP.)

EXIST. JOIST,

REFER TO PLAN

L-4x4x1/4" FRAME AT CURB

AND MECH. OPENINGS

EXIST. DECK (TYP.)

MECH. UNIT AND CURB,

REFER TO MECH. DWGS.

C6 OVER DECK RIBS

WELDED TO L4x4 THRU

DECK

NOT TO SCALE

WHERE CONCENTRATED LOAD IS NOT AT

PANEL POINT, REINFORCE EXIST. JOIST -

REFER TO TYPICAL ADDED REINF. @

CONCENTRATED LOADS BETWEEN PANEL

POINTS THIS SHEET

3/16

NEW TO EXISTING SLAB-ON-GRADE DETAIL

NOT TO SCALE

8" 8"

5"

5" SLAB-ON-GRADE REINFORCED #3 @ 12"

O.C., EACH WAY PLACED 1" CLEAR FROM

TOP OF SLAB, OVER 15 MIL VAPOR

RETARDER AND 4" OF POROUS FILL

DRILL AND EPOXY DOWELS

INTO SLAB WITH HILTI HIT

HY200 OR EQUAL

JOINT SEALANT

EXISTING SLAB

POUR NEW SLAB WHERE EXISTING COLUMN IS

BEING REMOVED, AT NEW COLUMN FOOTING

LOCATION & AT PLUMBING REVISIONS.

1/2"Ø X 1'-4" LONG SMOOTH

DOWELS @ 8" O.C., GREASE

EXPOSED END.

NEW SUPPORT DETAILS

NOT TO SCALE

3/16

FOOTING

4' - 6" SQ.

2" (TYP.)

PLATE 3/4"X14X14

(4) 3/4"Ø HEADED ANCHORS

WITH 9" EMBEDMENT

(4) #5 BOTTOM,

EACH WAY

3" CLR (TYP.)

BOTTOM OF FTG.

ELEV. = (-3'-8')

BELOW FINISHED

FLOOR

COLUMN SUPPORT DETAIL

2" (TYP.)2" (TYP.)

3/16

(4) 3/4"Ø BOLTS (GAGE = 3")

EXIST. BEAM - REFER

TO PLAN

NEW COLUMN - REFER TO PLAN

1/4" STIFFENER PLATE

EACH SIDE

3/16

CONNECTION OF W12 TO W18

1 1/2" ±

6" ±

3"

3"

1"

2"

1/4

TYP.

3/16"

EXIST. BEAM (TYP.) -

REFER TO PLAN

PLATE 3/8X8"X17"±

EACH SIDE. FIELD

VERIFY HEIGHT AND

WIDTH AND ADJUST

HEIGHT TO FIT HSS6

EXIST. ROOF DECK

EXIST. JOIST (TYP.)

(3) 3/4"Ø BOLTS

MATCH HOLES TO

EXISTING BOLT HOLES

AND ADD STEEL

SHIMS BETWEEN 3/8"

PLATE AND W12

1 5/16" OVERSIZED HOLES WITH

1/4"X2"Ø PLATE WASHER

1" NON-SHRINK GROUT

PAINT STEEL BELOW FINISHED

FLOOR WITH (2) COATS OF

BLACK ASPHALTUM

NEW SLAB OVER 15 MIL. VAPOR

RETARDER AND 4" POROUS FILL.

REFER TO NEW TO EXISTING

SLAB-ON-GRADE DETAIL ON

THIS SHEET

DRILL BOTTOM

FLANGE OF EXIST.

BEAM FOR NEW BOLTS

MECHANICAL UNIT SUPPORT

CONNECTION DETAIL

NOT TO SCALE

3"

1 1/2"

1/4

NEW BEAM -

REFER TO PLAN

EXIST. MECHANICAL

UNIT SUPPORT BEAM

PLATE 3/8"X3"X6" W/

(2) 3/4"Ø HIGH

STRENGTH BOLTS

IN AREA OF CONNECTION,

CLEAN EXISTING STEEL OF

LOOSE RUST, SCALE, AND

PAINT TO EXPOSE BEAR STEEL

1/2"Ø THRU BOLT EXIST.

JOIST TO NEW HSS AT

SAME LOCATION AS

CONNECTION TO

REMOVED CAP PLATE

HSS6X2X5/16 (LSH) -

LENGTH TO MATCH

EXISTING COLUMN CAP

PLATE (REMOVED)

TRANSFORMER SUPPORT DETAIL

EXIST. BEAM,

REFER TO PLAN

C4x4.5 COORDINATE

LOCATION WITH

TRANSFORMER

REQUIREMENTS AND

ELECTRICAL DWGS.

NOT TO SCALE

EXISTING ROOF DECK

1/4" TAB PLATE (TYP.)

3/16

A

OF

1909 CYPRESS AVENUE

VIRGINIA BEACH, VA 23451

(757) 417 - 0140

US Army Corps of Engineers Norfolk District

SHEET

N O

R F

O

LK

D

IS

T R

IC

T

C O

R P

S O

F E

N G

IN

E

E R

S N

O R

F O

LK

V

IR

G

IN

IA

F

IN

A L

S U

B M

IT

T

A L

N

O V

E M

B E

R

D A

T E

C

H E

C K

E D

S U

B M

IT

T

E D

S

C A

LE

N O

R F

O

LK

D

IS

T R

IC

T

F

IL

E N

O

P R

O

JE

C T

N O

D R

A W

IN

G

N O

S

P E

C

IF

IC

A

T

IO

N N

O

D R

A W

N

D E

S

IG

N E

D

La st w or ke d on

F le n am e:

P lo t s ca le

1:

A S

N O

T E

D

R E

V

D A

T E

D E

S C

R

IP

T

IO

N B

Y A

P P

B

C

D

A

B

C

D

2 3 4 5 1 2 3 4 5

C :\A

_R ev it Lo ca l F ile s\

-T Q ua nt ic o

N at io na l C em et er y E xp an si on

S tr uc t_ C

O M

P U

T E

R

.r vt

/1

2/

:5 2:

P

M

S-301

Q U

A N

T

IC

O N

A T

IO

N

A L C

E M

E T

E R

Y

B L D

G R

E N

O V

G

R A

V E

S

IT

E I M

P R

O V

E

S E

C T

IO

N

S A

N D

D E

T A

IL

S

LM

M

JS

S

M

LM

-Y

/0

3/

11/03/2017 12678

JS

S

LM

M

PHONE: (757) 474-0612 FAX: (757) 474-0919

VIRGINIA BEACH, VIRGINIA, 23464

748 LORD DUNMORE DRIVE, SUITE 101

UP

A C P

D A C T

P

P

P P

A

B

C

D

E

F

G

2 3 4 5 6

3'-4" ± 32'-0" ± 4'-0" ± 20'-0" ± 16'-0" ± 26'-0" ±

'-0

4' -0

'-0

'-1

0"

12'-1" ± 3'-0" ± 10'-0" ± 3'-0" ± 12'-0" ± 16'-0" ± 8'-0" ± 10'-1" ± 7'-11" ±

19'-3" ± 82'-1" ±

'-1

0"

98'-0" ±

5'-11" ± 3'-2" ± 7'-11" ± 3'-2" ± 5'-11" ±

1' -4

'-4

1' -4

'-0

8' -4

'-0

4' -0

'-0

4' -0

'-0

'-0

3' -1

0"

2'-6"

1' -6

2' -0

1' -6

2' -0

2'-6" ±

'-9

2'-6" ±

'-0

12'-0"

OPEN OFFICE

TOILET

OFFICEOFFICE

LOBBYRECORDSMULTI-PURPOSE

ROOM

BREAK ROOM

OPEN OFFICE

UTILITY ROOM

WOMEN MEN

OFFICE WAITING OFFICE

VESTIBULE

CL.

TYP.

151515

TYP.

TYP.

TYP.

TYP.

16 1 16

A. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS IN THE FIELD.

B. ALL EXISTING MATERIALS TO REMAIN WHICH ARE DAMAGED OR

OTHERWISE DISTURBED BY THE CONTRACTOR'S OPERATIONS SHALL BE

PATCHED AND REPAIRED TO MATCH EXISTING ADJACENT MATERIALS SO

THAT REPAIR IS IMPERCEPTIBLE.

C. ON ALL ARCHITECTURAL SHEETS, ALL MATERIALS NOTED ARE NEW

UNLESS SPECIFICALLY NOTED AS EXISTING. ALL MATERIALS NOTED AS

EXISTING SHALL REMAIN UNLESS SPECIFICALLY NOTED TO BE

REMOVED. SEE DEMOLITION AND NEW WORK NOTES FOR SPECIFIC

NOTES.

D. SEE SHEET A-601 FOR DOOR SCHEDULE

E. SEE SHEET A-701 FOR FINISH SCHEDULE

GENERAL NOTES

A

OF

1909 CYPRESS AVENUE

VIRGINIA BEACH, VA 23451

(757) 417 - 0140

US Army Corps of Engineers Norfolk District

SHEET

N O

R F

O

LK

D

IS

T R

IC

T

C O

R P

S O

F E

N G

IN

E

E R

S N

O R

F O

LK

V

IR

G

IN

IA

F

IN

A L

S U

B M

IT

T

A L

N

O V

E M

B E

R

D A

T E

C

H E

C K

E D

S U

B M

IT

T

E D

S

C A

LE

N O

R F

O

LK

D

IS

T R

IC

T

F

IL

E N

O

P R

O

JE

C T

N O

D R

A W

IN

G

N O

S

P E

C

IF

IC

A

T

IO

N N

O

D R

A W

N

D E

S

IG

N E

D

La st w or ke d on

F le n am e:

P lo t s ca le

1:

A S

N O

T E

D

R E

V

D A

T E

D E

S C

R

IP

T

IO

N B

Y A

P P

B

C

D

A

B

C

D

2 3 4 5 1 2 3 4 5

C :\U se rs

\a ge nu ng

\D oc um en ts \1

3-

II

Q

N C

B ld g R en ov

G ra ve Im pr ov e

A rc h_ ag en un g.

rv t

/1

3/

:1 7:

A

M

AD101

Q U

A N

T

IC

O N

A T

IO

N

A L C

E M

E T

E R

Y

B L D

G R

E N

O V

G

R A

V E

S

IT

E I M

P R

O V

E

F

IR

S T

F L O

O R

P L A

N

D E

M O

L

IT

IO

N

D S

R

JR

M

D P

I

-I I

/0

3/

11/03/2017 12679

JR

M

1/8" = 1'-0"

FIRST FLOOR PLAN - DEMOLITION

SHEET KEYNOTES

1 REMOVE EXISTING CARPET. CLEAN SUBSURFACE TO RECEIVE NEW

FINISH

2 REMOVE EXISTING TILE FLOORING. CLEAN SUBSURFACE TO

RECEIVE NEW FINISH

3 REMOVE EXISTING DOOR, DOOR FRAME, HARDWARE AND

ACCESSORIES

4 REMOVE EXISTING GYPSUM WALLBOARD PARTITION, FULL HEIGHT.

CLEAN EXISTING FLOOR SLAB TO RECEIVE NEW FINISH

5 REMOVE EXISTING DOOR, HARDWARE AND ACCESSORIES.

EXISTING FRAME SHALL REMAIN

6 REMOVE EXISTING CASEWORK, ASSOCIATED PLUMBING AND

ACCESSORIES

7 REMOVE EXISTING TOILET FIXTURES, ACCESSORIES AND

PARTITIONS. COORDINATE WITH PLUMBING DRAWINGS

8 REMOVE EXISTING STEEL COLUMN. COORDINATE WITH

STRUCTURAL DRAWINGS

9 REMOVE EXISTING WINDOW BLINDS

10 REMOVE EXISTING UTILITY SINK. CLEAN AREA OF REMOVAL TO

RECEIVE NEW FINISH

11 REMOVE EXISTING VINYL TILE FLOORING. CLEAN SURFACE TO

RECEIVE NEW FINISH

12 REMOVE ABANDONED EQUIPMENT/SYSTEMS. CLEAN AREA OF

REMOVAL TO RECEIVE NEW FINISH

13 REMOVE EXISTING SKYLIGHT ABOVE, CURBS SHALL REMAIN

14 REMOVE EXTERIOR MASONRY AS REQUIRED TO FACILITATE NEW

CONTROL JOINTS AND MASONRY INFILL, AS REQUIRED.

COORDINATE WITH STRUCTURAL DRAWINGS

15 REMOVE EXISTING MODULAR CASEWORK/SHELVING UNITS

16 REMOVE EXISTING SUSPENDED ACOUSTIC PANEL SYSTEM AND

GRID

17 REMOVE EXISTING GWB CEILING AND…