SECTION J-5 SAMPLE MAINTENANCE TASK AND
INSPECTION FORMS
DDESS Maintenance PWS Page 1 of 26 Section J-5 – Sample Maint. /Insp. Forms
3-16-12 Final Quantico, VA
SECTION J-5
SAMPLE MAINTENANCE TASK AND INSPECTION FORMS
1. PREVENTIVE MAINTENANCE
Contractor shall provide Preventive Maintenance work orders and inspection schedules for all equipment and systems included in the facilities listed in Section J-1. Following are samples of the types of documents that could be used.
HEAT PUMP MAINTENANCE SCHEDULE
COMPONENT
TASK
FREQUENCY IN
DAYS
OUTSIDE COIL
INSPECT AND CLEAN
STRAIGHTEN FINS
CHECK FOR DAMAGE OR LEAKS
POWER CLEAN COIL OR CLEAN AS PER MANF. INSTRUCTIONS
OUTSIDE FAN MOTOR
INSPECT AND CLEAN
LUBRICATE
CHECK MOTOR MOUNT RESILIENCY
CHECK OUTSIDE FAN MOTOR INSULATION RESISTANCE
OUTSIDE FAN
INSPECT AND CLEAN
CHECK FOR SECURITY AT MOTOR SHAFT
CHECK ALIGNMENT AND BALANCE
DDESS Maintenance PWS Page 2 of 26 Section J-5 – Sample Maint. /Insp. Forms
3-16-12 Final Quantico, VA
HEAT PUMP MAINTENANCE SCHEDULE
COMPONENT
TASK
FREQUENCY IN
DAYS
COMPRESSOR
CHECK REFIGERANT CHARGE
CHECK FOR REFRIGERANT AND OIL LEAKS
CHECK CRANKCASE HEATER OPERATION
MEASURE OPERATING VOLTAGE AND CURRENT; RECORD,
COMPARE TO NAMEPLATE INFORMATION
CHECK FOR PROPER OPERATION OF ALL OPERATING AND
SAFETY CONTROLS
FILTER
REPLACE
INSIDE COIL
INSPECT AND CLEAN
STRAIGHTEN FINS
INSPECT AND CLEAN DRAIN PAN AND LINE
POWER CLEAN COIL OR CLEAN AS PER MANF. INSTRUCTIONS
SUPPLY FAN
INSPECT AND CLEAN
CHECK FOR PROPER ROTATION AND CLEARANCE
CHECK SECURITY TO MOTOR SHAFT
SUPPLY FAN MOTOR
INSPECT AND CLEAN
LUBRICATE
CHECK MOTOR MOUNT RESILIENCY
CHECK INSIDE FAN MOTOR INSULATION RESISTANCE
CHECK FAN START CAPACITOR
DDESS Maintenance PWS Page 3 of 26 Section J-5 – Sample Maint. /Insp. Forms
3-16-12 Final Quantico, VA
HEAT PUMP MAINTENANCE SCHEDULE
COMPONENT
TASK
FREQUENCY IN
DAYS
ELECTRIC HEAT ELEMENTS
CHECK AMP DRAW
CHECK CONDITION OF ELEMENTS
CONTROL PANEL
TEST FOR PROPER OPERATION
TIGHTEN ALL ELECTRICAL CONNECTIONS
SEQUENCE TEST ALL CONTROLS
INSPECT AND CLEAN CONTACTS
DDESS Maintenance PWS Page 4 of 26 Section J-5 – Sample Maint. /Insp. Forms
3-16-12 Final Quantico, VA
FAN COIL UNIT MAINTENANCE SCHEDULE 'L'
COMPONENT
TASK
FREQUENCY IN
DAYS
FAN
INSPECT AND CLEAN
CHECK FOR PROPER ROTATION
TEST FOR VIBRATION
CHECK SHAFT AND END PLAY
CHECK BEARINGS AND LUBRICATE
MOTOR
INSPECT STARTER COILS AND CONTACTS
TIGHTEN ELECTRICAL CONNECTIONS
TEST FOR VIBRATION
LUBRICATE
EXAMINE MOTOR MOUNT RESILIENCY
INSPECT AND ADJUST DRIVE COUPLINGS, PULLEYS AND BELTS
INSPECT FOR CORROSION AND WEAR
CHECK HOUSING CLEARANCE
CHECK ALIGNMENT, BALANCE AND SECURITY TO SHAFT
COOLING COIL
INSPECT AND CLEAN
STRAIGHTEN FINS
CHECK FOR DAMAGE OR LEAKS
INSPECT AND CLEAN CONDENSATE PANS AND DRAINS
COIL PRESSURE CLEANING OR PER MFR INSTRUCTIONS
HEATING COIL
INSPECT AND CLEAN
DDESS Maintenance PWS Page 5 of 26 Section J-5 – Sample Maint. /Insp. Forms
3-16-12 Final Quantico, VA
CHECK FOR DAMAGE OR LEAKS
COIL PRESSURE CLEANING OR PER MFR INSTRUCTIONS
FILTERS
REPLACE
RETURN AIR DAMPERS
LUBRICATE BEARINGS
CHECK FOR PROPER CLOSE-OFF AND OPERATION
TIGHTEN ANY LOOSE BLADE CONNECTORS
INSPECT BEARINGS FOR EXCESSIVE WEAR
DDESS Maintenance PWS Page 6 of 26 Section J-5 – Sample Maint. /Insp. Forms
3-16-12 Final Quantico, VA
WATER HEATER (GAS-FIRED) MAINTENANCE SCHEDULE 'M'
COMPONENT
TASK
FREQUENCY IN
DAYS
CONTROLS & SAFETY LIMITS
PERFORM OPERATION TESTS AND ASSURE PROPER SETTINGS
OF: OPERATING CONTROL, HIGH TEMPERATURE SAFETY LIMIT,
FLAME-FAILURE SAFETY AND HIGH/LOW GAS PRESSURE
CUTOFF
TIGHTEN CONNECTIONS
INSPECT AND CLEAN CONTACTS
CHECK AND ADJUST FEEDWATER SYSTEM
CHECK AND ADJUST LOW-WATER CUTOFF DEVICE
TEST T&P RELIEF VALVE FOR PROPER OPERATION
BURNER SECTION
CHECK FLAME COMPOSITION AND SHAPE
PERFORM COMBUSTION AND DRAFT TEST
INSPECT AND CLEAN ORIFICES, PASSAGES AND NOZZLES
ADJUST FUEL/AIR RATIO
CHECK AND CLEAN PILOT AND IGNITERS
GAS TRAIN
CHECK FOR PROPER OPERATION OF MAIN AND SAFETY VALVES
CHECK FOR LEAKS AND OVERALL SECURITY
ASSURE GAS VALVE SHUTOFF
CHECK GAS PRESSURE REGULATOR SETTING
TANK
DRAIN AND BLOWDOWN TO REMOVE SCALING
GAUGE
CHECK FOR ACCURACY AND PROPER OPERATION
DDESS Maintenance PWS Page 7 of 26 Section J-5 – Sample Maint. /Insp. Forms
3-16-12 Final Quantico, VA
DDESS Maintenance PWS Page 8 of 26 Section J-5 – Sample Maint. /Insp. Forms
3-16-12 Final Quantico, VA
MAKE-UP AIR UNIT MAINTENANCE SCHEDULE 'N'
COMPONENT
TASK
FREQUENCY IN
DAYS
HOUSING
CHECK MOUNTS FOR SECURITY
CLEAN AND REMOVE EXTERNAL/INTERNAL DIRT ACCUMULATION
FILTERS
REPLACE
BURNER SECTION (FOR GAS-FIRED HEAT)
CHECK FLAME COMPOSITION AND SHAPE
PERFORM COMBUSTION AND DRAFT TEST
INSPECT AND CLEAN ORIFICES, PASSAGES AND NOZZLES
ADJUST FUEL/AIR RATIO
CHECK AND CLEAN PILOT AND IGNITERS
GAS TRAIN (FOR GAS-FIRED HEAT)
CHECK FOR PROPER OPERATION OF MAIN AND SAFETY VALVES
CHECK FOR LEAKS AND OVERALL SECURITY
ASSURE GAS VALVE SHUTOFF
CHECK GAS PRESSURE REGULATOR SETTING
FAN
INSPECT AND CLEAN
CHECK FOR PROPER ROTATION
TEST FOR VIBRATION
CHECK SHAFT AND END PLAY
CHECK BEARINGS AND LUBRICATE
MOTOR
INSPECT STARTER COILS AND CONTACTS
TIGHTEN ELECTRICAL CONNECTIONS
DDESS Maintenance PWS Page 9 of 26 Section J-5 – Sample Maint. /Insp. Forms
3-16-12 Final Quantico, VA
MAKE-UP AIR UNIT MAINTENANCE SCHEDULE 'N'
COMPONENT
TASK
FREQUENCY IN
DAYS
TEST FOR VIBRATION
LUBRICATE
EXAMINE MOTOR MOUNT RESILIENCY
INSPECT AND ADJUST DRIVE COUPLINGS, PULLEYS AND BELTS
INSPECT FOR CORROSION AND WEAR
CHECK HOUSING CLEARANCE
CHECK ALIGNMENT, BALANCE AND SECURITY TO SHAFT
CHECK MOTOR WINDING INSULATION RESISTANCE
MEASURE AND RECORD OPERATING VOLTAGE AND CURRENT - COMPARE TO NAME PLATE DATA
ELECTRIC HEAT ELEMENTS (FOR ELECTRIC HEAT)
CHECK AMP DRAW
INSPECT AND CLEAN ELEMENTS
COOLING COIL
INSPECT FOR DEBRIS AND REMOVE
CLEAN COILW/FLUID AND ALIGN FINS
UV LIGHTS
VERIFY OPERATION
REPLACE LAMPS
CHECK SAFTIES
TIGHTEN ALL CONNECTIONS
DDESS Maintenance PWS Page 10 of 26 Section J-5 – Sample Maint. /Insp. Forms
3-16-12 Final Quantico, VA
AIR COOLED CONDENSER MAINTENANCE SCHEDULE 'A'
COMPONENT
TASK
FREQUENCY IN
DAYS
FAN
CHECK FOR ALIGNMENT, BALANCE AND SECURITY TO SHAFT
CHECK FOR CORROSION AND WEAR
LUBRICATE BEARINGS AND CHECK FOR END PLAY, EXCESSIVE
BEARING TEMPERATURE AND UNUSUAL BEARING WEAR
CHECK CONDITION OF DRIVE COUPLINGS AND BELTS
CHECK FAN WHEEL AND CLEAN DIRT ACCUMULATION
CHECK AND TIGHTEN MOUNTING BOLTS
CHECK FOR PROPER BELT TENSION
CHECK RAIN SHIELDS
VERIFY UNIT OPERATION
MOTOR
INSPECT STARTER COILS AND CONTACTS
TIGHTEN ALL ELECTRICAL CONNECTIONS
LUBRICATE MOTOR BEARINGS
EXAMINE MOTOR MOUNT RESILIENCY
MEASURE AND RECORD OPERATING VOLTAGE AND CURRENT
RECORD, COMPARE TO NAME PLATE DATA
TEST MOTOR WINDING INSULATION RESISTANCE
CONDENSER COIL
CLEAN FINNED SURFACES WITH WIRE BRUSH OR HIGH
PRESSURE WATER
CHECK FOR DAMAGE OR LEAKS
STRAIGHTEN BENT FINS
DDESS Maintenance PWS Page 11 of 26 Section J-5 – Sample Maint. /Insp. Forms
3-16-12 Final Quantico, VA
CHECK PIPE CLAMPS FOR SECURITY AND VIBRATION
CHECK FINS FOR DEBRIS AND REMOVE
FRAME
CHECK FOR DAMAGE, RUST AND CORROSION
TREAT FOR CORROSION AS REQUIRED
DDESS Maintenance PWS Page 12 of 26 Section J-5 – Sample Maint. /Insp. Forms
3-16-12 Final Quantico, VA
PUMP MAINTENANCE SCHEDULE 'B'
COMPONENT
TASK
FREQUENCY IN
DAYS
MOTOR
INSPECT AND CLEAN STARTER COILS
INSPECT AND TIGHTEN CONTACTS
TEST FOR VIBRATION
LUBRICATE MOTOR BEARINGS
TEST MOTOR WINDING INSULATION RESISTANCE
MEASURE AND RECORD OPERATING VOLTAGE AND CURRENT
DRAW; COMPARE TO NAME PLATE DATA
COUPLING
CHECK FOR PROPER ALIGNMENT AND CONDITION
INSPECT FOR WEAR AND SHAFT SECURITY
REPLACE IF WORN
LUBRICATE
BEARING ASSEMBLY
LUBRICATE AS REQUIRED
CHECK FOR LEAKS OR WEAR
IMPELLER
REPLACE AS REQUIRED
HOUSING
CHECK PACKAGING AND MECHANICAL SEALS FOR LEAKAGE
INSPECT GASKETS FOR LEAKAGE AND DETERIORATION
LUBRICATE DRIVEN SHAFT BEARINGS
BASE
SECURE MOUNTS
REPLACE IF WORN
DDESS Maintenance PWS Page 13 of 26 Section J-5 – Sample Maint. /Insp. Forms
3-16-12 Final Quantico, VA
CHECK FOR CORROSION
CLEAN AND PAINT
STRAINER
BLOWDOWN STRAINER
REMOVE STRAINER MEDIA AND CLEAN
DDESS Maintenance PWS Page 14 of 26 Section J-5 – Sample Maint. /Insp. Forms
3-16-12 Final Quantico, VA
AIR HANDLING UNIT MAINTENANCE SCHEDULE 'D
COMPONENT
TASK
FREQUENCY IN
DAYS
FAN
INSPECT AND CLEAN
CHECK FOR PROPER ROTATION
TEST FOR VIBRATION
CHECK SHAFT AND END PLAY
CHECK BEARINGS AND LUBRICATE
MOTOR
INSPECT STARTER COILS AND CONTACTS
TIGHTEN ELECTRICAL CONNECTIONS
TEST FOR VIBRATION
LUBRICATE
EXAMINE MOTOR MOUNT RESILIENCY
INSPECT AND ADJUST DRIVE COUPLINGS, PULLEYS AND BELTS
INSPECT FOR CORROSION AND WEAR
CHECK HOUSING CLEARANCE
CHECK ALIGNMENT, BALANCE AND SECURITY TO SHAFT
COOLING COIL
INSPECT AND CLEAN DEBRIS
STRAIGHTEN FINS
CHECK FOR DAMAGE OR LEAKS
INSPECT AND CLEAN CONDENSATE PANS AND DRAINS
COIL POWER CLEAN OR PER MFR INSTRUCTIONS
HEATING COIL
INSPECT AND CLEAN DEBRIS
DDESS Maintenance PWS Page 15 of 26 Section J-5 – Sample Maint. /Insp. Forms
3-16-12 Final Quantico, VA
CHECK FOR DAMAGE OR LEAKS
COIL POWER CLEAN OR PER MFR INSTRUCTIONS
FACE & BYPASS DAMPERS
LUBRICATE BEARINGS
CHECK FOR PROPER CLOSE-OFF AND OPERATION
TIGHTEN ANY LOOSE BLADE CONNECTORS
FILTERS
REPLACE
RETURN AIR DAMPERS
LUBRICATE BEARINGS
CHECK FOR PROPER CLOSE-OFF AND OPERATION
TIGHTEN ANY LOOSE BLADE CONNECTORS
INSPECT BEARINGS FOR EXCESSIVE WEAR
OUTSIDE AIR DAMPERS
LUBRICATE BEARINGS
CHECK FOR PROPER CLOSE-OFF AND OPERATION
TIGHTEN ANY LOOSE BLADE CONNECTORS
COIL BYPASS
CHECK FOR PROPER OPERATION OF BYPASS
WATER HEATERS (ELECTRIC)
COMPONENT
FREQ.
DAYS
MINUTES PER TASK
MON
THLY
QUAR
TERLY
SEMI
-ANL
ANN
UAL
CONTROLS &
SAFETY LIMITS
TIGHTEN CONNECTIONS
INSPECT AND CLEAN CONTACTS
DDESS Maintenance PWS Page 16 of 26 Section J-5 – Sample Maint. /Insp. Forms
CHECK AND ADJUST FEED WATER
SYSTEM
CHECK AND ADJUST LOW-WATER
CUTOFF DEVICE
TEST T&P RELIEF VALVE FOR
PROPER OPERATION
PERFORM OPERATION TESTS AND
ASSURE PROPER SETTINGS
OF: OPERATING CONTROL, HIGH
TEMPERATURE SAFETY LIMIT,
FLAME-FAILURE SAFETY AND
HIGH/LOW GAS PRESSURE
CUTOFF
ELECTRIC
HEATER
SECTION
CHECK CURRENT ON EACH HEATER
(RECORD/COMPARE)
TANK
DRAIN AND BLOW DOWN TO
REMOVE SCALING
GAUGE
CHECK FOR ACCURACY AND
PROPER OPERATION
DDESS Maintenance PWS Page 17 of 26 Section J-5 – Sample Maint. /Insp. Forms
3-16-12 Final Quantico, VA
FOOD SERVICE WALK-IN COOLER/FREEZER 'I'
COMPONENT
TASK
FREQUENCY IN
DAYS
MOTOR
CHECK CURRENT
LUBRICATE MOTOR BEARINGS
FAN
INSPECT AND CLEAN
CHECK FOR PROPER ROTATION, ALIGNMENT AND BALANCE
TEST FOR VIBRATION
COMPRESSOR
CHECK REFRIGERANT CHARGE
CHECK FOR REFRIGERANT AND OIL LEAKS
VALVES
INSPECT AND REPLACE AS REQUIRED
CONDENSER COIL
CHECK FOR DEBRIS AND REMOVE
CLEAN COIL W/FLUID AND ALIGN FINS
EVAPORATOR COIL
CHECK FOR DEBRIS AND REMOVE
CLEAN COIL W/FLUID AND ALIGN FINS
DDESS Maintenance PWS Page 18 of 26 Section J-5 – Sample Maint. /Insp. Forms
3-16-12 Final Quantico, VA
AIR COOLED CHILLER SCHEDULE 'J1'
COMPONENT
TASK
FREQUENCY IN
DAYS
CONTROL CENTER
CALIBRATE AND CLEAN CONTROLS AND SAFETY DEVICES
INSPECT, CLEAN AND TIGHTEN ELECTRICAL CONTACTS
CHECK SET POINT OF CONTROLS AND LIMITS
SEQUENCE TEST ALL CONTROLS
TEST TEMPERATURE AND PRESSURE CONTROLS
VANES
CHECK FOR PROPER OPERATION
LUBRICATE VANE LINKAGES
CHECK VANE CONTROL FOR PROPER OPERATION
COMPRESSOR
CHECK REFRIGERANT CHARGE AND FOR RFRGT. AND OIL LEAKS
TEST FOR PROPER OPERATION AND EFFICIENCY
OBSERVE BEARING AND OPERATING SURFACE TEMPS AND RECORD
TEMPERATURES AND REPORT THOSE OUTSIDE NORMAL OPERATION
PERFORM AND MEASURE ACID TEST
MEASURE VIBRATION ON MAIN BEARINGS
CHECK OIL LEVEL AND CONDITION
CHECK OIL HEATER OPERATION
IMPELLER
MEASURE VIBRATION (WHERE APPLICABLE)
MOTOR
MEASURE OPERATING CURRENT AND VOLTAGE; RECORD,
COMPARE TO NAMEPLATE DATA
DDESS Maintenance PWS Page 19 of 26 Section J-5 – Sample Maint. /Insp. Forms
3-16-12 Final Quantico, VA
AIR COOLED CHILLER SCHEDULE 'J1'
COMPONENT
TASK
FREQUENCY IN
DAYS
LUBRICATE MOTOR BEARINGS
EXAMINE MOTOR MOUNT RESILIENCY
CHECK MOTOR INSULATION RESISTANCE
CHECK CONDITION AND ALIGNMENT OF DRIVE SECTION
TRANSMISSION (WHERE APPLICABLE)
CHECK FOR PROPER LUBRICATION
LUBRICATION PUMP
INSPECT AND CHECK FOR PROPER OPERATION
CHECK OIL HEATER FOR PROPER OPERATION
CHANGE OIL AND FILTER
TEST OPERATION OF OIL PUMP
VIBRATION ISOLATORS
CHECK FOR CORROSION AND FATIGUE
PURGE UNIT
LUBRICATE MOTOR
CLEAN PURGE DRUM
CHANGE PURGE UNIT OIL
CHECK DRIVE BELT AND ADJUST TENSION (WHERE APPLICABLE)
FLOW CONTROL
CHECK FLOAT CONTROL OPERATION
COOLER
INSPECT RUPTURE DISC FOR LEAKS
INSPECT AND CLEAN TUBES
ELIMINATOR
CHECK FOR PROPER REFRIGERANT LEVEL IN COOLER
DDESS Maintenance PWS Page 20 of 26 Section J-5 – Sample Maint. /Insp. Forms
3-16-12 Final Quantico, VA
AIR COOLED CHILLER SCHEDULE 'J1'
COMPONENT
TASK
FREQUENCY IN
DAYS
CHILLED WATER CONNECTION
CLEAN ALL WATER STRAINERS IN WATER PIPING SYSTEM
CHECK FOR LEAKS AT CONNECTION, REPAIR OR TIGHTEN AS REQ'D.
FAN
CHECK FOR ALIGNMENT, BALANCE AND SECURITY TO SHAFT
CHECK FOR CORROSION AND WEAR
LUBRICATE BEARINGS AND CHECK FOR END PLAY, EXCESSIVE
BEARING TEMPERATURE AND UNUSUAL BEARING WEAR
CHECK FAN WHEEL AND CLEAN DIRT ACCUMULATION
CHECK AND TIGHTEN MOUNTING BOLTS
CHECK RAIN SHIELDS
VERIFY UNIT OPERATION
CONDENSER COILS
INSPECT AND CLEAN FINS
INSPECT FOR CORROSION
INSPECT AND TREAT FOR CORROSION AND PAINT AS REQUIRED
STARTER
CHECK OVERLOAD SETTING TRIP POINT AMPS
TIGHTEN ALL TERMINALS
CHECK CONDITION OF STARTER CONTACTS
DDESS Maintenance PWS Page 21 of 26 Section J-5 – Sample Maint. /Insp. Forms
3-16-12 Final Quantico, VA
WATER COOLED CHILLER SCHEDULE 'J'
COMPONENT
TASK
FREQUENCY IN
DAYS
CONTROL CENTER
CALIBRATE AND CLEAN CONTROLS AND SAFETY DEVICES
INSPECT, CLEAN AND TIGHTEN ELECTRICAL CONTACTS
CHECK SET POINT OF CONTROLS AND LIMITS
SEQUENCE TEST ALL CONTROLS
TEST TEMPERATURE AND PRESSURE CONTROLS
VANES
CHECK FOR PROPER OPERATION
LUBRICATE VANE LINKAGES
CHECK VANE CONTROL FOR PROPER OPERATION
COMPRESSOR
CHECK REFRIGERANT CHARGE AND FOR RFRGT. AND OIL LEAKS
TEST FOR PROPER OPERATION AND EFFICIENCY
OBSERVE BEARING AND OPERATING SURFACE TEMPS AND
REPORT TEMPERATURES OUTSIDE NORMAL OPERATION TO KO
PERFORM AND MEASURE ACID TEST
MEASURE VIBRATION ON MAIN BEARINGS
CHECK OIL LEVEL AND CONDITION
CHECK OIL HEATER OPERATION
IMPELLER
MEASURE VIBRATION
MOTOR
MEASURE OPERATING CURRENT AND VOLTAGE; RECORD,
COMPARE TO NAMEPLATE DATA
DDESS Maintenance PWS Page 22 of 26 Section J-5 – Sample Maint. /Insp. Forms
3-16-12 Final Quantico, VA
WATER COOLED CHILLER SCHEDULE 'J'
COMPONENT
TASK
FREQUENCY IN
DAYS
LUBRICATE MOTOR BEARINGS
EXAMINE MOTOR MOUNT RESILIENCY
CHECK MOTOR INSULATION RESISTANCE
CHECK CONDITION AND ALIGNMENT OF DRIVE SECTION
TRANSMISSION
CHECK FOR PROPER LUBRICATION
LUBRICATION PUMP
INSPECT AND CHECK FOR PROPER OPERATION
CHECK OIL HEATER FOR PROPER OPERATION
CHANGE OIL AND FILTER
TEST OPERATION OF OIL PUMP
VIBRATION ISOLATORS
CHECK FOR CORROSION AND FATIGUE
PURGE UNIT
LUBRICATE MOTOR
CLEAN PURGE DRUM
CHANGE PURGE UNIT OIL
FLOW CONTROL
CHECK FLOAT CONTROL OPERATION
COOLER
INSPECT RUPTURE DISC FOR LEAKS
INSPECT AND CLEAN TUBES
ELIMINATOR
CHECK FOR PROPER REFRIGERANT LEVEL IN COOLER
DDESS Maintenance PWS Page 23 of 26 Section J-5 – Sample Maint. /Insp. Forms
3-16-12 Final Quantico, VA
WATER COOLED CHILLER SCHEDULE 'J'
COMPONENT
TASK
FREQUENCY IN
DAYS
CHILLED WATER CONNECTION
CLEAN ALL WATER STRAINERS IN WATER PIPING SYSTEM
CHECK FOR LEAKS AT CONNECTION, REPAIR OR TIGHTEN AS REQ'D.
CONDENSER WATER CONNECTIONS
CHECK FOR LEAKS AT CONNECTION, REPAIR OR TIGHTEN AS REQ'D.
CONDENSER
INSPECT AND CLEAN TUBES
INSPECT FOR CORROSION
INSPECT AND TREAT FOR CORROSION AND PAINT AS REQUIRED
STARTER
CHECK OVERLOAD SETTING TRIP POINT AMPS
TIGHTEN ALL TERMINALS
CHECK CONDITION OF STARTER CONTACTS
DDESS Maintenance PWS Page 24 of 26 Section J-5 – Sample Maint. /Insp. Forms
2. INSPECTIONS
Contractor shall provide Inspection for where the service is required in this PWS. Inspection forms shall be included for required components in the facilities listed in Section J-1. Following is a sample of the type of document that could be used.
DDESS Maintenance PWS Page 25 of 26 Section J-5 – Sample Maint. /Insp. Forms
3-16-12 Final Quantico, VA
General Roof Conditions Debris on Roof Drainage Physical Damage Attic Conditions Structural Deformation Other Flat / Membrane Roof Condition of Coating Granular Loss Punctures Cracks / Alligatoring Blisters / Fishmouths Ponding Other Sloped Roof Roof Material Condition of Surface Deformed Edges Shingle: Buckled Curled Missing Tabs Granular Loss Other Metal: Corrosion Fasteners Other Roof Features Fascia Soffit Flashing Gutters / Drains, etc.
Skylights Chimneys / Vents Fall Arrest Anchors Control Zone Access Other
Cracks Water Staining Water Leaks Seasonal Change Other
Deformed Finish Surface Deterioration Staining Other
Cracks Water Staining Water Leaks Deformed Finish Seasonal Change Window Leaks Door/Window Alignment Other
ROOF INSPECTION CHECKLIST
Ceiling Conditions
Exterior Wall Surfaces
Interior Wall Surfaces
DDESS Maintenance PWS Page 26 of 26 Section J-5 – Sample Maint. /Insp. Forms
3-16-12 Final Quantico, VA
Facility Name:______________________________ Bldg. #:_______________________________
Type of Roof Flat / Membrane / Metal / Composition Tile: __________________ Sloped: __________Slope:________in 12
Construction / Re-roofing / Repair Dates: __________________________________________
Inspected by: __________________ Date: ____________________
ROOF INSPECTION CHECKLIST
Summary/Comments
(Highlight areas of concern and any rapid degradation in roof system)
Comment on changes from previous inspections and overall roof condition. Indicate recommended action of roof repair and/or further assessment and estimated remaining life expectancy of room system. Include any photographs and thermolgraphy records in their rreport.