This document is a Unified Facilities Guide Specification (UFGS) for Basic Electrical Materials and Methods, specifically section 26 00 00.00 20, issued by USACE/NAVFAC/AFCEC/NASA in July 2006. The specification provides comprehensive guidelines for electrical equipment and installation requirements, covering critical aspects such as regulatory compliance, standard products, warranty, nameplate requirements, and warning sign specifications. Key technical requirements include factory-applied painting systems meeting NEMA 250 corrosion-resistance standards, field-fabricated nameplates using ASTM D709 laminated plastic, and mandatory adherence to IEEE C2 and NFPA 70 electrical installation standards.
The document outlines detailed provisions for electrical equipment, including quality assurance criteria, submission requirements for shop drawings and product data, and instructions for government personnel. It specifies that electrical equipment must have been in satisfactory commercial use for at least 2 years, with manufacturing dates no more than 3 years prior to delivery. The specification also mandates posting operating instructions, providing manufacturer's nameplates, and mounting warning signs for high-voltage electrical equipment enclosures. Additionally, it requires competent instructors to train government personnel on equipment adjustment, operation, and maintenance, with the depth of training specified in individual technical sections.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USACE / NAVFAC / AFCEC / NASA UFGS- 26 00 00. 00 20 ( Jul y 2006) Pr epar i ng Act i v i t y: NAVFAC Super sedi ng UFGS- 26 00 00. 00 20 ( Apr i l 2006)
UNI FI ED FACI LI TI ES GUI DE SPECI FI CATI ONS
Ref er ences ar e i n agr eement wi t h UMRL dat ed Apr i l 2018
SECTI ON TABLE OF CONTENTS
DI VI SI ON 26 - ELECTRI CAL
SECTI ON 26 00 00. 00 20
BASI C ELECTRI CAL MATERI ALS AND METHODS
07/06
PART 1 GENERAL
1. 1 REFERENCES
1. 2 RELATED REQUI REMENTS
1. 3 DEFI NI TI ONS
1. 4 ELECTRI CAL CHARACTERI STI CS
1. 5 ADDI TI ONAL SUBMI TTALS I NFORMATI ON
1. 5. 1 Shop Dr awi ngs ( SD- 02)
1. 5. 2 Pr oduct Dat a ( SD- 03)
1. 6 QUALI TY ASSURANCE
1. 6. 1 Regul at or y Requi r ement s
1. 6. 2 St andar d Pr oduct s
1. 6. 2. 1 Al t er nat i ve Qual i f i cat i ons
1. 6. 2. 2 Mat er i al and Equi pment Manuf act ur i ng Dat e
1. 7 WARRANTY
1. 8 POSTED OPERATI NG I NSTRUCTI ONS
1. 9 MANUFACTURER' S NAMEPLATE
1. 10 FI ELD FABRI CATED NAMEPLATES
1. 11 WARNI NG SI GNS
1. 12 ELECTRI CAL REQUI REMENTS
1. 13 I NSTRUCTI ON TO GOVERNMENT PERSONNEL
PART 2 PRODUCTS
2. 1 FACTORY APPLI ED FI NI SH
PART 3 EXECUTI ON
3. 1 FI ELD APPLI ED PAI NTI NG
3. 2 FI ELD FABRI CATED NAMEPLATE MOUNTI NG
3. 3 WARNI NG SI GN MOUNTI NG
- - End of Sect i on Tabl e of Cont ent s - -
SECTI ON 26 00 00. 00 20 Page 1
USACE / NAVFAC / AFCEC / NASA UFGS- 26 00 00. 00 20 ( Jul y 2006) Pr epar i ng Act i v i t y: NAVFAC Super sedi ng UFGS- 26 00 00. 00 20 ( Apr i l 2006)
UNI FI ED FACI LI TI ES GUI DE SPECI FI CATI ONS
Ref er ences ar e i n agr eement wi t h UMRL dat ed Apr i l 2018
SECTI ON 26 00 00. 00 20
BASI C ELECTRI CAL MATERI ALS AND METHODS
07/06
NOTE: Thi s gui de speci f i cat i on cover s el ect r i cal gener al r equi r ement s, compl et e.
Adher e t o UFC 1- 300- 02 Uni f i ed Faci l i t i es Gui de Speci f i cat i ons ( UFGS) For mat St andar d when edi t i ng t hi s gui de speci f i cat i on or pr epar i ng new pr oj ect speci f i cat i on sect i ons. Edi t t hi s gui de speci f i cat i on f or pr oj ect speci f i c r equi r ement s by addi ng, del et i ng, or r evi s i ng t ext . For br acket ed i t ems, choose appl i cabl e i t em( s) or i nser t appr opr i at e i nf or mat i on.
Remove i nf or mat i on and r equi r ement s not r equi r ed i n r espect i ve pr oj ect , whet her or not br acket s ar e present.
Comment s, suggest i ons and r ecommended changes f or t hi s gui de speci f i cat i on ar e wel come and shoul d be submi t t ed as a Cr i t er i a Change Request ( CCR) .
NOTE: The f ol l owi ng i nf or mat i on shal l be shown on t he pr oj ect dr awi ngs:
1. Ext ent and l ocat i on of wor k t o be accompl i shed.
2. Wi r i ng, equi pment , and accessor i es necessar y f or a compl et e i nst al l at i on.
PART 1 GENERAL
1. 1 REFERENCES
NOTE: Thi s par agr aph i s used t o l i s t t he publ i cat i ons c i t ed i n t he t ext of t he gui de speci f i cat i on. The publ i cat i ons ar e r ef er r ed t o i n t he t ext by basi c desi gnat i on onl y and l i s t ed i n t hi s par agr aph by or gani zat i on, desi gnat i on, dat e, SECTI ON 26 00 00. 00 20 Page 2 and t i t l e.
Use t he Ref er ence Wi zar d' s Check Ref er ence f eat ur e when you add a Ref er ence I dent i f i er ( RI D) out s i de of t he Sect i on' s Ref er ence Ar t i c l e t o aut omat i cal l y pl ace t he r ef er ence i n t he Ref er ence Ar t i c l e. Al so use t he Ref er ence Wi zar d' s Check Ref er ence f eat ur e t o updat e t he i ssue dat es.
Ref er ences not used i n t he t ext wi l l aut omat i cal l y be del et ed f r om t hi s sect i on of t he pr oj ect speci f i cat i on when you choose t o r econci l e r ef er ences i n t he publ i sh pr i nt pr ocess.
The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o i n t he t ext by t he basi c desi gnat i on onl y.
ASTM I NTERNATI ONAL ( ASTM)
ASTM D709 ( 2017) St andar d Speci f i cat i on f or Lami nat ed Ther moset t i ng Mat er i al s
I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)
I EEE 100 ( 2000; Ar chi ved) The Aut hor i t at i ve Di ct i onar y of I EEE St andar ds Ter ms
I EEE C2 ( 2017; Er r at a 1- 2 2017; I NT 1 2017) Nat i onal El ect r i cal Saf et y Code
I EEE C57. 12. 28 ( 2014) St andar d f or Pad- Mount ed Equi pment
- Encl osur e I nt egr i t y
I EEE C57. 12. 29 ( 2014) St andar d f or Pad- Mount ed Equi pment
- Encl osur e I nt egr i t y f or Coast al Environments
NATI ONAL ELECTRI CAL MANUFACTURERS ASSOCI ATI ON ( NEMA)
NEMA 250 ( 2014) Encl osur es f or El ect r i cal Equi pment ( 1000 Vol t s Maxi mum)
NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)
NFPA 70 ( 2017; ERTA 1- 2 2017; TI A 17- 1; TI A 17- 2;
TI A 17- 3; TI A 17- 4; TI A 17- 5; TI A 17- 6;
TI A 17- 7; TI A 17- 8; TI A 17- 9; TI A 17- 10;
TI A 17- 11; TI A 17- 12; TI A 17- 13; TI A
17- 14) Nat i onal El ect r i cal Code
1. 2 RELATED REQUI REMENTS
NOTE: To appl y t hi s gui de speci f i cat i on t o ot her di v i s i ons of t he pr oj ect speci f i cat i on, i nser t t he appr opr i at e di v i s i on number and t i t l e. Ensur e t hat t he appr opr i at e sect i ons havi ng el ect r i cal equi pment
SECTI ON 26 00 00. 00 20 Page 3 i nc l ude t he f ol l owi ng par agr aph:
" 1. X RELATED REQUI REMENTS: Sect i on 26 00 00. 00 20 BASI C ELECTRI CAL MATERI ALS AND METHODS, appl i es t o t hi s sect i on, wi t h t he addi t i ons and modi f i cat i ons speci f i ed her ei n. "
Del et e sect i ons i n t he par agr aph t hat ar e not i n t he j ob. The r equi r ement s of t hi s speci f i cat i on sect i on ar e bei ng i ncor por at ed i nt o t he ot her speci f i cat i on sect i ons t hat r ef er ence i t wi t h t he i nt ent of phasi ng out t hi s sect i on. As t he r equi r ement s of t hi s sect i on ar e i ncor por at ed i nt o each speci f i cat i on sect i on, t hat sect i on shoul d be added t o t he l i s t i n t he par agr aph bel ow. Do not use t hi s sect i on, and del et e r ef er ence t o i t , i f t he onl y sect i ons used i n t he j ob ar e l i s t ed bel ow.
Thi s sect i on appl i es t o cer t ai n sect i ons of [ Di v i s i on 02, EXI STI NG CONDI TI ONS] [ Di v i s i on 11, EQUI PMENT, ] [ Di v i s i on 13, SPECI AL CONSTRUCTI ON, ] [ and] [ Di v i s i on 14, CONVEYI NG EQUI PMENT] [ and] [ Di v i s i ons 22 and 23, PLUMBI NG and HEATI NG VENTI LATI NG AND AI R CONDI TI ONI NG] . Thi s sect i on appl i es t o al l sect i ons of Di v i s i on 26 and 33, ELECTRI CAL and UTI LI TI ES, of t hi s pr oj ect speci f i cat i on unl ess speci f i ed ot her wi se i n t he i ndi v i dual sect i ons. Thi s sect i on has been i ncor por at ed i nt o, and t hus, does not appl y t o, and i s not r ef er enced i n t he f ol l owi ng sect i ons.
Sect i on 26 12 19. 10 THREE- PHASE PAD MOUNTED TRANSFORMERS Sect i on 26 12 21 SI NGLE- PHASE PAD- MOUNTED TRANSFORMERS Sect i on 26 11 16 SECONDARY UNI T SUBSTATI ONS Sect i on 26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM Sect i on 26 23 00 LOW VOLTAGE SWI TCHGEAR Sect i on 26 24 13 SWI TCHBOARDS Sect i on 26 51 00 I NTERI OR LI GHTI NG Sect i on 26 56 00 EXTERI OR LI GHTI NG Sect i on 27 10 00 BUI LDI NG TELECOMMUNI CATI ONS CABLI NG SYSTEM Sect i on 33 71 02 UNDERGROUND ELECTRI CAL DI STRI BUTI ON Sect i on 33 82 00 TELECOMMUNI CATI ONS OUTSI DE PLANT ( OSP)
1. 3 DEFINITIONS
a. Unl ess ot her wi se speci f i ed or i ndi cat ed, el ect r i cal and el ect r oni cs t er ms used i n t hese speci f i cat i ons, and on t he dr awi ngs, shal l be as def i ned i n I EEE 100.
b. The t echni cal sect i ons r ef er r ed t o her ei n ar e t hose speci f i cat i on sect i ons t hat descr i be pr oduct s, i nst al l at i on pr ocedur es, and equi pment oper at i ons and t hat r ef er t o t hi s sect i on f or det ai l ed descr i pt i on of submi t t al t ypes.
c. The t echni cal par agr aphs r ef er r ed t o her ei n ar e t hose par agr aphs i n PART 2 - PRODUCTS and PART 3 - EXECUTI ON of t he t echni cal sect i ons t hat descr i be pr oduct s, syst ems, i nst al l at i on pr ocedur es, equi pment , and t est met hods.
1. 4 ELECTRI CAL CHARACTERI STI CS
SECTI ON 26 00 00. 00 20 Page 4
NOTE: Del et e t hi s par agr aph f or NAVFAC SE pr oj ect s. Use I EEE C57. 12. 00 desi gnat i ons, such as 4160 V and 480Y/ 277 V, when r ef er r i ng t o t he pr i mar y and secondar y vol t ages, r espect i vel y, i n t he f ol l owi ng par agr aph.
El ect r i cal char act er i st i cs f or t hi s pr oj ect shal l be [ _____] kV pr i mar y, [ s i ngl e] [ t hr ee] phase, [ t wo] [ t hr ee] [ f our ] wi r e, [ 60] [ 50] [ _____] Hz, and [ _____] vol t s secondar y, [ s i ngl e] [ t hr ee] phase, [ t hr ee] [ f our ] wi r e.
Fi nal connect i ons t o t he power di st r i but i on syst em at t he exi st i ng [ subst at i on] [ manhol e] [ _____] shal l be made by t he [ Cont r act or as di r ect ed by t he Cont r act i ng Of f i cer ] [ Gover nment ] .
1. 5 ADDI TI ONAL SUBMI TTALS I NFORMATI ON
Submi t t al s r equi r ed i n ot her sect i ons t hat r ef er t o t hi s sect i on must conf or m t o t he f ol l owi ng addi t i onal r equi r ement s as appl i cabl e.
1. 5. 1 Shop Dr awi ngs ( SD- 02)
I ncl ude wi r i ng di agr ams and i nst al l at i on det ai l s of equi pment i ndi cat i ng pr oposed l ocat i on, l ayout and ar r angement , cont r ol panel s, accessor i es, pi pi ng, duct wor k, and ot her i t ems t hat must be shown t o ensur e a coor di nat ed i nst al l at i on. Wi r i ng di agr ams shal l i dent i f y c i r cui t t er mi nal s and i ndi cat e t he i nt er nal wi r i ng f or each i t em of equi pment and t he i nt er connect i on bet ween each i t em of equi pment . Dr awi ngs shal l i ndi cat e adequat e c l ear ance f or oper at i on, mai nt enance, and r epl acement of oper at i ng equi pment devi ces.
1. 5. 2 Pr oduct Dat a ( SD- 03)
Submi t t al shal l i ncl ude per f or mance and char act er i st i c cur ves.
1. 6 QUALI TY ASSURANCE
1. 6. 1 Regul at or y Requi r ement s
I n each of t he publ i cat i ons r ef er r ed t o her ei n, consi der t he advi sor y pr ovi s i ons t o be mandat or y, as t hough t he wor d, " shal l " had been subst i t ut ed f or " shoul d" wher ever i t appear s. I nt er pr et r ef er ences i n t hese publ i cat i ons t o t he " aut hor i t y havi ng j ur i sdi ct i on, " or wor ds of s i mi l ar meani ng, t o mean t he Cont r act i ng Of f i cer . Equi pment , mat er i al s, i nst al l at i on, and wor kmanshi p shal l be i n accor dance wi t h t he mandat or y and advi sor y pr ovi s i ons of NFPA 70 unl ess mor e st r i ngent r equi r ement s ar e speci f i ed or i ndi cat ed.
1. 6. 2 St andar d Pr oduct s
Pr ovi de mat er i al s and equi pment t hat ar e pr oduct s of manuf act ur er s r egul ar l y engaged i n t he pr oduct i on of such pr oduct s whi ch ar e of equal mat er i al , desi gn and wor kmanshi p. Pr oduct s shal l have been i n sat i sf act or y commer ci al or i ndust r i al use f or 2 year s pr i or t o bi d openi ng. The 2- year per i od shal l i nc l ude appl i cat i ons of equi pment and mat er i al s under s i mi l ar c i r cumst ances and of s i mi l ar s i ze. The pr oduct shal l have been on sal e on t he commer ci al mar ket t hr ough adver t i sement s, manuf act ur er s ' cat al ogs, or br ochur es dur i ng t he 2- year per i od. Wher e t wo or mor e i t ems of t he same cl ass of equi pment ar e r equi r ed, t hese i t ems shal l be pr oduct s of a s i ngl e manuf act ur er ; however , t he component par t s of t he i t em need not be t he
SECTI ON 26 00 00. 00 20 Page 5 pr oduct s of t he same manuf act ur er unl ess st at ed i n t he t echni cal sect i on.
1. 6. 2. 1 Al t er nat i ve Qual i f i cat i ons
Pr oduct s havi ng l ess t han a 2- year f i el d ser vi ce r ecor d wi l l be accept abl e i f a cer t i f i ed r ecor d of sat i sf act or y f i el d oper at i on f or not l ess t han 6000 hour s, excl usi ve of t he manuf act ur er s ' f act or y or l abor at or y t est s, i s furnished.
1. 6. 2. 2 Mat er i al and Equi pment Manuf act ur i ng Dat e
Pr oduct s manuf act ur ed mor e t han 3 year s pr i or t o dat e of del i ver y t o s i t e shal l not be used, unl ess speci f i ed ot her wi se.
1. 7 WARRANTY
The equi pment i t ems shal l be suppor t ed by ser vi ce or gani zat i ons whi ch ar e r easonabl y conveni ent t o t he equi pment i nst al l at i on i n or der t o r ender sat i sf act or y ser vi ce t o t he equi pment on a r egul ar and emer gency basi s dur i ng t he war r ant y per i od of t he cont r act .
1. 8 POSTED OPERATI NG I NSTRUCTI ONS
Pr ovi de f or each syst em and pr i nc i pal i t em of equi pment as speci f i ed i n t he t echni cal sect i ons f or use by oper at i on and mai nt enance per sonnel . The oper at i ng i nst r uct i ons shal l i ncl ude t he f ol l owi ng:
a. Wi r i ng di agr ams, cont r ol di agr ams, and cont r ol sequence f or each pr i nci pal syst em and i t em of equi pment .
b. St ar t up, pr oper adj ust ment , oper at i ng, l ubr i cat i on, and shut down procedures.
c. Saf et y pr ecaut i ons.
d. The pr ocedur e i n t he event of equi pment f ai l ur e.
e. Ot her i t ems of i nst r uct i on as r ecommended by t he manuf act ur er of each syst em or i t em of equi pment .
Pr i nt or engr ave oper at i ng i nst r uct i ons and f r ame under gl ass or i n appr oved l ami nat ed pl ast i c. Post i nst r uct i ons wher e di r ect ed. For oper at i ng i nst r uct i ons exposed t o t he weat her , pr ovi de weat her - r esi st ant mat er i al s or weat her pr oof encl osur es. Oper at i ng i nst r uct i ons shal l not f ade when exposed t o sunl i ght and shal l be secur ed t o pr event easy r emoval or peel i ng.
1. 9 MANUFACTURER' S NAMEPLATE
Each i t em of equi pment shal l have a namepl at e bear i ng t he manuf act ur er ' s name, addr ess, model number , and ser i al number secur el y af f i xed i n a conspi cuous pl ace; t he namepl at e of t he di st r i but i ng agent wi l l not be acceptable.
1. 10 FI ELD FABRI CATED NAMEPLATES
NOTE: Use t he f ol l owi ng par agr aph wher e namepl at es ar e f abr i cat ed t o i dent i f y speci f i c equi pment
SECTI ON 26 00 00. 00 20 Page 6 desi gnat ed on t he dr awi ngs.
ASTM D709. Pr ovi de l ami nat ed pl ast i c namepl at es f or each equi pment encl osur e, r el ay, swi t ch, and devi ce; as speci f i ed i n t he t echni cal sect i ons or as i ndi cat ed on t he dr awi ngs. Each namepl at e i nscr i pt i on shal l i dent i f y t he f unct i on and, when appl i cabl e, t he posi t i on. Namepl at es shal l be mel ami ne pl ast i c, 3 mm 0. 125 i nch t hi ck, whi t e wi t h [ bl ack] [ _____] cent er cor e. Sur f ace shal l be mat t e f i ni sh. Cor ner s shal l be squar e.
Accur at el y al i gn l et t er i ng and engr ave i nt o t he cor e. Mi ni mum si ze of namepl at es shal l be 25 by 65 mm one by 2. 5 i nches. Let t er i ng shal l be a mi ni mum of 6. 35 mm 0. 25 i nch hi gh nor mal bl ock st y l e.
1. 11 WARNI NG SI GNS
Pr ovi de war ni ng s i gns f or t he encl osur es of el ect r i cal equi pment i ncl udi ng subst at i ons, pad- mount ed t r ansf or mer s, pad- mount ed swi t ches, gener at or s, and swi t chgear havi ng a nomi nal r at i ng exceedi ng 600 vol t s.
a. When t he encl osur e i nt egr i t y of such equi pment i s speci f i ed t o be i n accor dance wi t h I EEE C57. 12. 28 or I EEE C57. 12. 29, such as f or pad- mount ed t r ansf or mer s[ and pad- mount ed SF6 swi t ches] , pr ovi de sel f - adhesi ve war ni ng s i gns on t he out s i de of t he hi gh vol t age compar t ment door ( s) . Si gn shal l be a decal and shal l have nomi nal di mensi ons of 178 by 255 mm 7 by 10 i nches wi t h t he l egend " DANGER HI GH VOLTAGE" pr i nt ed i n t wo l i nes of nomi nal 50 mm 2 i nch hi gh l et t er s.
The wor d " DANGER" shal l be i n whi t e l et t er s on a r ed backgr ound and t he wor ds " HI GH VOLTAGE" shal l be i n bl ack l et t er s on a whi t e backgr ound.
Decal shal l be Pandui t No. PPSO710D72 or appr oved equal .
[ b. When such equi pment i s guar ded by a f ence, mount s i gns on t he f ence.
Pr ovi de met al s i gns havi ng nomi nal di mensi ons of 355 by 255 mm 14 by 10 i nches wi t h t he l egend " DANGER HI GH VOLTAGE KEEP OUT" pr i nt ed i n t hr ee l i nes of nomi nal 75 mm 3 i nch hi gh whi t e l et t er s on a r ed and bl ack field.
] 1. 12 ELECTRI CAL REQUI REMENTS
El ect r i cal i nst al l at i ons shal l conf or m t o I EEE C2, NFPA 70, and r equi r ement s speci f i ed her ei n.
1. 13 I NSTRUCTI ON TO GOVERNMENT PERSONNEL
Wher e speci f i ed i n t he t echni cal sect i ons, f ur ni sh t he ser vi ces of compet ent i nst r uct or s t o gi ve f ul l i nst r uct i on t o desi gnat ed Gover nment per sonnel i n t he adj ust ment , oper at i on, and mai nt enance of t he speci f i ed syst ems and equi pment , i ncl udi ng per t i nent saf et y r equi r ement s as r equi r ed.
I nst r uct or s shal l be t hor oughl y f ami l i ar wi t h al l par t s of t he i nst al l at i on and shal l be t r ai ned i n oper at i ng t heor y as wel l as pr act i cal oper at i on and mai nt enance wor k. I nst r uct i on shal l be gi ven dur i ng t he f i r st r egul ar wor k week af t er t he equi pment or syst em has been accept ed and t ur ned over t o t he Gover nment f or r egul ar oper at i on. The number of man- days ( 8 hour s per day) of i nst r uct i on f ur ni shed shal l be as speci f i ed i n t he i ndi v i dual sect i on.
[ When mor e t han 4 man- days of i nst r uct i on ar e speci f i ed, use appr oxi mat el y hal f of t he t i me f or c l assr oom i nst r uct i on. Use ot her t i me f or i nst r uct i on wi t h equi pment or syst em. When s i gni f i cant changes or modi f i cat i ons i n t he equi pment or syst em ar e made under t he t er ms of t he cont r act , pr ovi de addi t i onal i nst r uct i ons t o acquai nt t he oper at i ng per sonnel wi t h t he changes or modi f i cat i ons. ]
SECTI ON 26 00 00. 00 20 Page 7
PART 2 PRODUCTS
2. 1 FACTORY APPLI ED FI NI SH
NOTE: Thi s par agr aph cover s onl y t he basi c pai nt i ng r equi r ement s f or most el ect r i cal equi pment . I ncl ude i n t he sect i on speci f y i ng t he equi pment any speci al f i ni shes f or hi gh or l ow t emper at ur es and cor r osi ve at mospher es. Ret ai n t he br acket ed st at ement when swi t chgear and ot her equi pment havi ng speci f i c pai nt r equi r ement s ar e speci f i ed.
El ect r i cal equi pment shal l have f act or y- appl i ed pai nt i ng syst ems whi ch shal l , as a mi ni mum, meet t he r equi r ement s of NEMA 250 cor r osi on- r esi st ance t est [ and t he addi t i onal r equi r ement s speci f i ed i n t he t echni cal sect i ons] .
PART 3 EXECUTI ON
3. 1 FI ELD APPLI ED PAI NTI NG
NOTE: Use and coor di nat e pai nt and coat i ng r equi r ement s wi t h Sect i on 09 90 00 PAI NTS AND COATI NGS when pr ovi ded i n t he j ob. Use t he second br acket ed opt i on when Sect i on 09 90 00 i s not pr ovi ded or when r equi r ement s ar e beyond what i s speci f i ed i n Sect i on 09 90 00.
Pai nt el ect r i cal equi pment as r equi r ed t o mat ch f i ni sh of adj acent sur f aces or t o meet t he i ndi cat ed or speci f i ed saf et y cr i t er i a. Pai nt i ng shal l be as speci f i ed i n [ Sect i on 09 90 00 PAI NTS AND COATI NGS] [ t he sect i on speci f y i ng t he associ at ed el ect r i cal equi pment ] .
3. 2 FI ELD FABRI CATED NAMEPLATE MOUNTI NG
Pr ovi de number , l ocat i on, and l et t er desi gnat i on of namepl at es as i ndi cat ed. Fast en namepl at es t o t he devi ce wi t h a mi ni mum of t wo sheet - met al scr ews or t wo r i vet s.
3. 3 WARNI NG SI GN MOUNTI NG
Pr ovi de t he number of s i gns r equi r ed t o be r eadabl e f r om each accessi bl e s i de, but space t he s i gns a maxi mum of 9 met er s 30 f eet apar t .
- - End of Sect i on - -
SECTI ON 26 00 00. 00 20 Page 8