Questions 34-35.pdf

PDF 139 KB Posted

Attached to
Bldg 408 Dormitory Repair Federal contract opportunity
Solicitation number
W50S98-20-B-7001
Issued by
Department of the Army Tennessee Army National Guard

About this file

This document contains responses to questions regarding specifications for a dormitory repair project for the Tennessee Army National Guard. The project involves installation of wall protection rails in corridors and lounge areas, as well as clarification of finishes for millwork. Responses specify the use of combination core hardwood plywood and stainless steel drawer construction. Open shelving is to include protective angles. Solid polymer countertop thickness is increased to 1.125 inches with chase countertops and window sills at 0.75 inches. The vented attic design and thermal envelope are to remain as is.

View the file

Other files for this federal contract opportunity

Other files attached to Bldg 408 Dormitory Repair, newest first.
File Type Posted
Amendment 5.pdf PDF
Abstract of Offers 20B7001 Signed.pdf PDF
RFI Roof Insulation Revision.pdf PDF
Amendment 3.pdf PDF
Revised Detail B1 A-501.jpg JPG image
Amendment 2.pdf PDF
Questions 36-40.pdf PDF
Revised Finish Materials Legend 11-15-19.png PNG image
23 07 00.pdf PDF
Amendment 1.pdf PDF
Question 11-33 Answered.pdf PDF
Questions_1-10_Answered.pdf PDF
Prep-Bid_Minutes_W50S98-20-B-7001.pdf PDF
Sign_in_Sheet_Page_2_of_2.pdf PDF
Sign_in_Sheet_Page_1_of_2.pdf PDF
Pre-Bid_Slides.pdf PDF
W50S98-20-B-7001_Solicitation.pdf PDF
Repair_B408_-_Specifications.zip ZIP file
Show all 18

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Question 34. WP‐1 (Wall protection – Rail) is called out on sheet A‐610 in the Miscellaneous

Finish Material Legend. However, the WP‐1 does not show up on the Room Finish Schedule for any room. Sheet A‐301 / B‐1 Building Section shows a product that appears to be a chair rail or a wall protection rail but it is unclear where the product goes and what the product is. Specification section 066116 is specifying a solid polymer product but does not say it is for the Wall Protection Rail. Please clarify product material and where wall protection rails are to be installed.

Answer 34. Refer to General Sheet Notes #13 on all three floor plan sheets. The note refers to the use of Continuous Wall Guards as shown on Sheet A‐001. On Sheet A‐001, under

Control Joints, Fixtures and Devices, a note at the far‐right points to the Wall Rail and states "Install Bumper Guards at all Corridors and Lounge Areas". Revise this note to read "Install 4‐inch tall x 3/8 inch thick Wall Protection Rails at all Corridors and Lounge

Areas at the height indicated". Specification Section 06 61 16 describes the solid polymer product to be used as Wall Protection Rails (WP‐1). Disregard the Material

Legends Chart on Sheet A‐610. It will be revised and distributed NLT 11‐15‐19.

Question 35. Can you give us some direction on the factory finishing specification for the millwork in Section 06410 Custom Cabinets ? The finish system typically utilized for this type of project would be the AWI Systems 2,3,or 5 with the required defect sanding prior to stain and sealer and sealer sanding before top coats . These are the type finishes utilized on previous

TANG project Bldg 406. Please advise

Answer 35. Specifications Section 06 20 00, Finish Carpentry:

Part 2.1.6, Hardwood Plywood: Concerning the apparent scarce availability of lumber core hardwood plywood specified in this section, approval is given to use

Combination Core hardwood plywood. The plywood shall consist of a center veneer core and a crossband veneer on both sides of the center with a layer of Medium

Density Fiberboard (MDF) under the face and back veneer. Face and back veneers shall be rotary cut maple or birch of 3/32 inch thickness.

Part 2.2, Countertops; Subpart 2.2.1, Solid Surface: Delete reference to Section 06

61 16, Solid Polymer Fabrications and instead use Section 12 36 00, Vanity

Countertops, Window Sills and Chase Countertops.

Part 2.6.2.1, Cabinet Hardware: Delete Subpart (a.) regarding European style concealed hinges. Instead insert the following: Hinges shall be five (5) knuckle, 2.75”, grade 1, type 304 stainless steel for all hinged doors. Two hinges for doors 4 feet in height or less and three hinges for doors over 4 feet in height.

Part 2.6.2.1, Cabinet Hardware: Under Subpart (e.) Include the following: Lockable hasps as located on the drawings for the room dividers on sheet A‐410 shall be equal to Hafele America Co. part number 235.17.200 with matte nickel finish.

Part 2.6.2, Cabinets, Aprons and Room Divider Millwork: Include the following at the end of the paragraph: Drawer boxes shall be fabricated of ½ inch solid birch, 9/16” Baltic birch or maple plywood with dovetail joints at all four corners. Drawer bottoms shall be ¼” tempered hardboard, birch or maple hardwood plywood, set in to ¼ inch grooves on all four sides with hot‐melt glue. Drawer heads shall be replaceable in case of damage and attached to the drawer boxes with wood screws.

Part 3.3.1, Countertops: Delete reference to Section 06 61 16, Solid Surfacing

Fabrications and instead reference Section 12 36 00, Vanity Countertops, Window

Sills and Chase Countertops.

The balance of Specifications Section 06 20 00 still applies.

Drawing sheet A‐410, Millwork Elevations B1 & B3:

Apply the requirements for ¾ inch x ¾ inch stainless steel open shelf protective angles indicated in Elevation B3 to the open shelving in Elevation B1. ALL open shelves in the Room Divider Millwork shall have this protection applied to the bottom shelf front lip.

Specifications Section 12 36 00, Vanity Countertops, Window Sills and Chase

Countertops:

Part 2.2, Subpart 2.2.1, Vanity Countertop and Backsplash: Delete the requirement for 0.094 inch thick material and replace with 1.125 inch thick. Chase countertops and window sills shall remain at 0.75 inch thick.

Part 2.2.1.1, Solid Polymer Countertops: Delete the requirement for 0.094 inch thick material and replace with 1.125 inch thick. Chase countertops and window sills shall remain at 0.75 inch thick.

A verbal question was posed regarding the vented attic as it relates to heating and cooling loads. Our mechanical engineers verified that the FCU’s on the 3rd floor have been sized to account for the additional heating and cooling loads from the vented attic.

Therefore, the attic shall remain vented, and the thermal envelope formed by the rigid insulation placed on the new sloping metal trusses and decking shall remain as designed.