F-16 SIM Facility Pre-Bid Site Visit.pdf

PDF 2 MB Posted

Attached to
Construct F16 Mission Training Center Federal contract opportunity
Solicitation number
W50S95-23-B-0001
Issued by
Department of the Army National Guard

About this file

This document includes a pre-bid site visit presentation and federal contract opportunity notice for construction of an F-16 mission training center. The pre-bid presentation provides an overview of the project scope, which involves demolishing an existing building and constructing a new 12,988 square foot facility at McEntire Joint National Guard Base in Eastover, South Carolina. The facility will include four simulator bays and supporting spaces, with structural, mechanical, electrical, and security systems designed to ICD/ICS 705 standards. The related federal contract opportunity is seeking bids for the construction project, with a base bid for the facility construction and demolition work, and nine optional bid line items. The solicitation number is W50S95-23-B-0001 and is set aside 100% for small businesses. The deadline for proposals is the date listed in any amendments to the solicitation. The contract duration is 549 days after notice to proceed.

View the file

Other files for this federal contract opportunity

Other files attached to Construct F16 Mission Training Center, newest first.
File Type Posted
Abstract.pdf PDF
Questions and Answers 3.3.2023.pdf PDF
W50S9523B0001 Amendment 0003 Conformed Copy.pdf PDF
W50S9523B0001 Amendment 0003.pdf PDF
ATTMT Item 23 - 31 31 16.13 - CHEMICAL TERMITE CONTROL.pdf PDF
ATTMT Item 27 - 11 94 11 - ROOFTOP CABLE FALL PROTECTION SYSTEM.pdf PDF
ATTMT Item 30 - Cast Iron Boot Detail.pdf PDF
ATTMT Item 43 - Recycling Receptacles.pdf PDF
ATTMT Item 46b - Bldg 958 Mech.pdf PDF
ATTMT Item 46a - Bldg 958 Bldg and Site.pdf PDF
ATTMT Item 130 - SECTION 07 27 10.00 10 BUILDING AIR BARRIER SYSTEM.pdf PDF
W50S9523B0001 Amendment 0002.pdf PDF
Asbestos and Lead Report - Basis of Design SCANG PSTE 189001.pdf PDF
W50S9523B0001 Amendment 0002 Conformed Copy.pdf PDF
Questions and Answers 2.21.2023.pdf PDF
W50S9523B0001 Amendment 0001.pdf PDF
W50S9523B0001 Amendment 0001 Conformed Copy.pdf PDF
Attendee Sign In Sheet.pdf PDF
Contracting Pre-Bid Conference.pdf PDF
FY23 PTSE 189001 J-A 23-006 Cores and Locksets FINAL_Redacted.pdf PDF
FY23 PTSE 189001 J-A 23-009 Soap Dispenser FINAL_Redacted.pdf PDF
FY23 PTSE 189001 J-A 23-004 HVAC Controls Final_Redacted.pdf PDF
FY23 PTSE 189001 J-A 23-007 Fire Alarm Control Panel FINAL_Redacted.pdf PDF
Wage Determination.pdf PDF
FY23 PTSE 189001 J-A 23-002 Paper Towel Dispenser Final_Redacted.pdf PDF
FY23 PTSE 189001 J-A 23-008 ATI FINAL_Redacted.pdf PDF
FY23 PTSE 189001 J-A 23-003 Toilet Paper Dispenser Final_Redacted.pdf PDF
W50S9523B0001.pdf PDF
SOW_ PSTE 189001 - Construct F-16 Mission Training Center.pdf PDF
FY23 PTSE 189001 J-A 23-001 Ceiling Tile FINAL_Redacted.pdf PDF
FY23 PTSE 189001 J-A 23-005 PA Speakers FINAL_Redacted.pdf PDF
Show all 31

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

McEntire Joint National Guard Base

PSTE189001 F-16 SIM Facility Eastover, South Carolina

27 January 2023

I n t e g r i t y - S e r v i c e - E x c e l l e n c e

Project Location

F-16 Mission Training Center

Demolition Site Plan

N

Partially Developed Site The site consists of existing Building 958 as well as turf and paved areas including an access drive and parking lot.

Building 958 and associated hardscape will be removed.

Site was selected based on proximity to surrounding facilities and because the existing paved areas were not disturbed for the F-16 project and will require only minor pavement removal for (future) F-35 expansion.

Curb Cuts and transitional pavements will be required for additional off-street parking being added on N/E/S of proposed building site.

Utility Plan

COMM

OVERHEAD ELEC

UNDERGROUND GAS

WATER N

SAN SEWER

STORM SEWER

Building footprint layout minimizes relocations of existing utilities with gas main requiring relocation due to conflict with facility.

New sanitary sewer lateral tie-in with existing sanitary sewer gravity main.

No off-site utility upgrades or major extensions required for facility

Authority / Scope

F-16 Mission Training Center

12,988 GSF

FLOOR PLAN

Project will be constructed to ICD/ICS 705 v4 Standards to follow SCIF certification requirements but will not be registered.

Building Characteristics/

SCIF

Secure Area Construct IAW IC Tech Spec – for ICD/ICS-705, Version 1.4 (Open Storage with SID)

Construct perimeter walls, floors, ceilings, doors, windows and penetrations that outline the Vault according to Open Storage with SID requirements (Wall A - Suggested Standard

Acoustic Wall Construction).

Install Acoustic sealant and RF protection of perimeter walls where required.

Construct one primary entrance and vestibule with approved door, alarm, deadbolt, combination lock, access-control device, door closure, and secure hinge pins.

Minimize utility penetrations into secure area to a single point if possible.

Install acoustic treatment, RF shielding, and dielectric breaks or grounding for utility systems and penetrations as required.

Install permanently affixed bars or grills with an access port at any penetration of perimeter larger than 96 square inches.

Install Intrusion Detection System (IDS) with a 15 minute alarm response time.

ICD 705 Standards

Building Elevations

Building Elevations

Building Perspectives

Perspective View - Looking Northeast

Building Perspectives

Perspective View - Looking Northwest

Structural Foundations

Shallow Foundations

Geotechnical Investigation Report dated September 10th, 2019.

Building Superstructure Traditional post and beam steel framing system

Steel ordinary concentrically braced frames for lateral resistance

Building Envelope Structural metal studs supporting masonry wainscot and insulated metal panel façade

Standing seam metal roof on joist/roof deck (diaphragm) below

Designed in accordance with ASCE 7-10 Design Loads and Seismic Requirements

Building Systems

Mechanical Support Spaces

Indoor air handling unit with chilled water cooling and hot water heating.

VAV boxes with hot water reheat for zone temperature control.

Comm rooms conditioned by chilled water fan coil units.

Flight Simulator Spaces Floor mounted, up-flow chilled water computer room units with integral humidifiers and electric reheat for stringent temperature and humidity control.

The network room and UPS room will be provided with ceiling mounted computer room units with chilled water cooling, integral humidifier, and SCR electric heat.

Cooling and Heating Generation Two air cooled chillers will provide chilled water for the flight simulator and support space cooling.

Two high efficiency gas boilers (each 60% of total required capacity) will provide heating for the support spaces.

Each water system will be provided with two vertical inline pumps. (one pump is redundant)

Mechanical / LCCA Direct Digital Control (DDC) System will tie into base EMCS

(Automated Logic).

Energy Analysis – Proposed building will exceed ASHRAE 90.1- 2013 energy efficiency requirements by 43.4%.

A 40yr Life Cycle Cost Analysis (LCCA) was performed for building mechanical systems with the following cooling plant types: chilled water, direct expansion, geothermal. Full calculations available in A-

2 CD ROM.

Chilled water – $694k first cost, $10.7m total life-cycle cost

Geothermal – $3.2m first cost, $12.9m total life-cycle cost

Direct expansion – $868k first cost, $11.3m total life-cycle cost

Direct expansion first cost greater than chilled water due to increased cost of DX CRAC units.

Geothermal first cost greatest due to large ground-source heat exchanger. Not feasible for cooling dominated load.

Electrical New underground service to a pad mounted 12.47kV/8.32 kV –

480/277V transformer.

Transformer designed to allow an upgrade to 12.47 kV system with dual rated transformer and 15 kV rated cable.

Install 1.5MVA transformer and new 2000A service entrance panel.

Preliminary load calcs indicate total demand of 1093 kVA including 10% future growth.

Install generator connection cabinet.

Provide a new lightning protection system on facility roof.

Electrical Provide new 480/277V panels for HVAC and lighting loads and

208/120V panels for receptacle and branch circuit loads.

Provide new LED fixtures throughout the building. Exterior lighting fixtures will be matched to base standards.

F16 Flight Simulator system will include a L3 provided 400kVA UPS to serve the flight simulator system and a 60 kVA UPS to serve the network. UPS’s will be located in a dedicated UPS Room. Room is adequately sized to become an Electrical Room with power distribution to the F35 Flight Simulator System.

Communications/Security Construct New 2x2 4-inch Duct Bank from new facility to existing

Building 258.

Install (4) 4” conduits with (3) 3 cell, 4 inch textile innerducts containing pull tape in each innerduct and an integrated trace wire from new facility Comm Room to new duct bank established to Building 258.

Install new 50 pair copper PE89 and (2) 24 strand SMF from new facility to existing Building 258.

Non-secure and Secure Comm rooms will have dedicated 150 A and 100A, 208/120V panelboards, respectively.

30A twist-lock receptacles will be provided in each of the two comm rooms.

All equipment required shall be contractor furnished/contractor installed

Grounding and bonding will adhere to TIA 607-C standards.