2020-09-15 DPEZ182200 ADDENDUM 1 REPAIR SIM FAC FOR DELIVERY BRIDGING DOCS.pdf

PDF 4 MB Posted

Attached to
Modifications to C130 Simulator Building
Solicitation number
W50S8W20R0011
Issued by

About this file

This document package includes construction drawings and specifications for modifications to a C-130 simulator building. The drawings detail proposed architectural, structural, mechanical, electrical, and security system upgrades. Key work includes installing a retractable drawbridge stair, modifying classroom and briefing room layouts, upgrading HVAC, electrical, and fire protection systems, and adding security access controls and cameras. Bidders should price the design and construction in accordance with the specifications, with quotes due by September 21, 2020. The pre-bid site visit will be held on September 1 and questions are due by September 10. The solicitation is for a design-build contract between $250,000-$500,000 through the Department of the Army National Guard.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SUPV

MECHANICAL/FIRE

PROTECTION

WST SIM MAINT

PARTS STOR

WST HIGH BAY

INSTRUCTORS

SUITE

WST COMPUTER ROOM

DATA STORAGE/SAFE

COMM

VESTIBULE

MAINT

RECEPTION

LOBBY

SITE MGR

(CONTRACT)

PO/QAR

(GOV'T)

MEN

WOMEN

OFFICE

SECURITY

ELEV

CORR.

STAIR

STAIR

WORK NOTES:

1 (E) 24"x12" COMM TRENCH

2 (E) RAISED FLOOR SYSTEM

3 REMOVE EXISTING TRANSLUCENT PANELS (AND RETURN TO THE GOVERNMENT) ONLY ONCE ROLL-UP DOORS ARE DELIVERED AND READY FOR

INSTALLATION

4 FIRESTOP BELOW FLOOR OPENING AFTER SIM INSTALLATION IS COMPLETE

5 FROST WINDOW TO SAME OPACITY AS WINDOW IN RM 114

6 PAINT FLOOR WITH OIL RESISTANT NON-SLIP PAINT, PREP SURFACE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS

7 NEW WELDED METAL STAIR, PROVIDE SHOP DRAWING STAMPED BY STRUCTURAL ENGINEER

8 REMOVE EXISTING KABA LOCK AND RETURN TO GOVERNMENT, NO EXTERIOR HARDWARE, PROVIDE BLANK COVER PAINTED TO MATCH DOOR WITH

TAMPER RESISTANT FASTENERS

9 COORDINATE NEW WALL AND DOOR WITH STRUCTURAL STEEL ABOVE TO SECURE STUDS TO STEEL AND PROVIDE DIAGONAL BRACING. PROVIDE

EXPANDED METAL MESH ABOVE CEILING AT VERTICAL FACE OF STUDS AROUND PIPING AND DUCTWORK. OVERLAP MINIMUM 4" AND SPOT WELD

MAXIMUM 96 SQUARE INCH OPENINGS WITH MAXIMUM 6" DIMENSION IN ANY DIRECTION

10 COAT ENTIRE FLOOR WITH OIL RESISTANT NON SLIP COATING. PROVIDE EXPANSION JOINT MATERIAL AT MOTION SLAB. PAINT TRENCH COVERS

INDIVIDUALLY, PREPARE SURFACES TO BE COATED IN ACCORDANCE WITH RESINOUS FLOORING MANUFACTURER'S RECOMMENDATIONS

11 NOT USED

12 GRIND CONCRETE AT PAD LOCATIONS ON REACTION PAD WITHIN TOLERANCES IN TFR

DEMO NOTES:

1 REMOVE FLOOR TILES IN RM 116 AND GRIND ADHESIVE WITH DIAMOND IMPREGNATED

BLADE DESIGNED FOR ADHESIVE REMOVAL, REPAIR ANY DAMAGE TO EXISTING

EXPANSION JOINT SEALANT AROUND MOTION BASE

A

A

U P

(E)REACTION PAD

P7

1ST FLOOR PLAN

SCALE

"=1'

TYPICAL PARTITION TYPE

SCALE 1"=1'

P7

2ND FLOOR PLAN

SCALE

"=1'

MIOS

CLASSROOM

MEN

WOMEN

UNIT

JAN.

STORAGE

GALLEY &

VENDING

BREAK

AREA

LOBBY

STAIR

STAIR

ELEV

CORR.

EQUIPMENT

PLATFORM

BRIEF/DEBRIEF

#2

BRIEF/DEBRIEF

#1

WORK NOTES:

1 FROST WINDOWS TO SAME OPACITY AS WINDOWS IN RM 114

2 PROVIDE DIAGONAL BRACING ABOVE CEILING. PROVIDE EXPANDED METAL MESH ABOVE

CEILING AT VERTICAL FACE OF STUDS AROUND PIPING AND DUCTWORK. OVERLAP

MINIMUM 6" AND SPOT WELD TO CREATE MAXIMUM 96 SQUARE INCH OPENINGS WITH

MAXIMUM 6" DIMENSION IN EITHER DIRECTION.

3 AFTER SNS INSTALLATION INFILL OPENING WITH WALL TYPE P7. TRIM PATCH AND PAINT

OPENING AND ENTIRE WEST WALL OF ROOM 210 TO MATCH REST OF ROOM. PAINT PATCH

TO MATCH (N) WEST HIGH BAY SIDE OF WALL.

4 INSTALL ACOUSTIC PANEL ON CLASSROOM SIDE OF WEST WALL OF RM 215

DEMO NOTES:

1 REMOVE PORTION OF (E) CASEWORK TO ALLOW INSTALLATION OF NEW WALL

TWO UPPER CABINETS AND ONE LOWER TRIM AND FINISH EDGE OF COUNTER

2 CREATE MINIMUM 84" WIDE BY 84" TALL OPENING INTO M103 210. STRUCTURAL ENGINEER

TO DETERMINE LINTEL/REINFORCEMTN/BOND BEAM. COORDINATE WITH ELECTRICAL FOR

TEMPORARY RELOCATION OF OUTLETS AND NETWORK DROPS.

P7

P1

VERTICAL PLANE, DOWNWARD

DRAWBRIDGE WEIGHTS AT STAIR LANDING:

267 LBS (EACH OF 4 POINTS)

HORIZONTAL PLANE, OUTWARD 800 LBS (EACH OF UPPER 2 POINTS)

HORIZONTAL PLANE, INWARD 800 LBS (EACH OF LOWER 2 POINTS)

VERTICAL PLANE, DOWNWARD

CABLE SUPPORT INTERFACE WEIGHTS

1675 LBS

HORIZONTAL PLANE, OUTWARD 400 LBS

TORQUE MOMENT AT FORCE POINT 620 FT/LBS

DELEGATED DESIGN:

REFERENCE SPECIFICATION SECTION 055000 METAL

FABRICATIONS

A20

A STAIR SECTION

SCALE: 1/2"=1'-0"

A20

B STAIR SECTION

SCALE: 1/2"=1'-0"

DOOR DETAILS 1

DOOR SCHEDULE

FRAME TYPES

DOOR TYPES

WORK NOTES:

1 PROVIDE 12 X 12 FACTORY FABRICATED SECURITY BARS (MAX 96 SQ. IN. OPENINGS AND MAX 6"

OPEN DIMENSION, 3/4" BARS) IN (E) DUCT, COORDINATE WITH ARCHITECTURAL TO BE IN SAME PLANE AS

EXPANDED METAL MESH AT NEW WALL, PROVIDE SQUARE TO ROUND DUCT TRANSITIONS AS

NECESSARY

2 EXISTING CWS/R TAPS INTO HIGH BAY 116 WILL NOT BE USED

3 PROVIDE REMOTE TEMPERATURE SENSOR APPROXIMATELY 15'-0" A.F.F. ROUTE WIRING IN

SURFACE MOUNTED CONDUIT, OFFSET OVER EXISTING CONDUIT

1ST FLOOR HVAC PLAN

SCALE

"=1'

SUPV

MECHANICAL/FIRE

PROTECTION

WST SIM MAINT

PARTS STOR

WST HIGH BAY

INSTRUCTORS

SUITE

WST COMPUTER ROOM

DATA STORAGE/SAFE

COMM

VESTIBULE

MAINT

RECEPTION

LOBBY

SITE MGR

(CONTRACT)

(GOV'T)

PO/QAR

WOMEN

MEN

STOR

PO/QAR

ELEV

CORR.

STAIR

STAIR

SUPV

MECHANICAL/FIRE

PROTECTION

WST HIGH BAY

PARTS STOR

SUITE

INSTRUCTORS

DATA STORAGE/SAFE

WST COMPUTER ROOM

COMM

VESTIBULE

RECEPTION

MAINT

LOBBY

SITE MGR

MEN

(CONTRACT)

WOMEN

ELEV

CORR.

STAIR

STAIR

SUPV

MECHANICAL/FIRE

PROTECTION

WST SIM MAINT

PARTS STOR

WST HIGH BAY

INSTRUCTORS

SUITE

WST COMPUTER ROOM

DATA STORAGE/SAFE

COMM

VESTIBULE

MAINT

RECEPTION

LOBBY

SITE MGR

(CONTRACT)

PO/QAR

(GOV'T)

MEN

WOMEN

OFFICE

SECURITY

ELEV

CORR.

STAIR

STAIR

1ST FLOOR DOMESTIC PLUMBING PLAN

SCALE

"=1'

SUPV

MECHANICAL/FIRE

PROTECTION

WST SIM MAINT

PARTS STOR

WST HIGH BAY

INSTRUCTORS

SUITE

WST COMPUTER ROOM

DATA STORAGE/SAFE

COMM

VESTIBULE

MAINT

RECEPTION

LOBBY

SITE MGR

(CONTRACT)

PO/QAR

(GOV'T)

MEN

WOMEN

OFFICE

SECURITY

ELEV

CORR.

STAIR

STAIR

WORK NOTES:

1 ROUTE CONDENSATE DRAIN FROM COCKPIT A/C UNIT TO CONDENSATE PUMP (CP-1),

ROUTE PUMPED CONDENSATE AGAINST WALL BELOW ELECTRICAL PANELS AND INTO

COMPUTER ROOM BELOW RAISED FLOOR TO AIR GAP AT EXISTING FLOOR SINK

2 ROUTE 2" DRAIN THROUGH WALL DOWN THROUGH ACCESS FLOOR AND BELOW FLOOR

TO AIR GAP AT EXISTING FLOOR SINK

3 ENLARGE TO 3" SS TRANSITION FROM 4" AT FIRST FLOOR AND TO 2" BELOW SECOND

FLOOR (BID OPTION #1)

4 ROUTE

" HW/CW TO NEW MOP SINK ABOVE (BID OPTION #1)

1ST FLOOR SANITARY PLUMBING PLAN

SCALE

"=1'

SHEET

E 100

E 101

E 201

SHEET NAME

LEGEND, TOC, SCHEDULE

FIRST FLOOR LIGHTING PLAN, LIGHT FIXTURE AND LIGHTING DEVICE SCHEDULE

FIRST FLOOR POWER PLAN AND SWITCHBOARD SB1 SCHEDULE

E 202

E 300

E 301

SECOND FLOOR POWER PLAN, SWITCHBOARD SCHEDULE SB2, ELEVATOR EWUIPMENT ROOM AND GROUND BUSS DETAIL

ELECTRICAL EQUIPMENT SCHEDULE

ELECTRICAL ONE LINE AND ELECTRICAL FEEDER SCHEDULE

E 302

E 401

E 500S

GROUNDING ONE LINE & GROUNDING ONELINE FOR SEPARATELY DERIVED SYSTEMS, HP11 PANEL SCHEDULE, BRANCH CIRCUITS LARGER THAN #12

FIRST FLOOR HVAC POWER PLAN AND MECHANICAL EQUIPMENT SCHEDULE

FIRST & SECOND FLOOR SECURITY PLAN, SECURITY DEVICE SCHEDULE & SECURTY LEGEND

EXISTING LIGHTING FIXTURE SCHEDULE

Type Mark Count Manufacturer Model Description

A 15 H.E. Williams DIG-S24-254T5HO-WPR-STEP

DIMMING-277

DIRECT/INDIRECT 2 LAMP RECESSED FIXTURE, DUAL

LEVEL SWITCHING

B 11 H.E. Williams DIG-S24-154T5HO-WPR-EB1-277 DIRECT/INDIRECT 1 LAMP RECESSED FIXTURE

CD 8 PRESCOLITE LFD6LED277HDM-CLFLED7-35K-WHWT

B24

6" RECESSED LED CAN WITH LUTRON SERIES A LED

DRIVER AND 2000 LUMEN LED MODULE

CL 1 PRESCOLITE LFD6LED277-CLFLED5-35K-WHWTB24 6" RECESSED LED CAN WITH 1000 LUMEN OUTPUT

CW 3 PRESCOLITE LFD6LED277WW-6LFLED7-35K-WHWTB2

6" RECESSED LED CAN CONFIGURED TO WALL WASH

WITH LUTRON SERIES A DRIVER

D 16 Finelite Inc. S16WM-SSL-4-T5HO-SC-91W-277-FE-1.0 WALL MOUNTED LINEAR

E 10 DUAL LITE EVCUGWD4I CEILING MOUNTED EXIT SIGN, 277 VOLT

EE 14 DUAL LITE LZ20NI03L EMERGENCY LED WALLPACK, NICKEL CADMIUM

BATTERY, 6 VOLT,

EO 3 DUAL LITE EVO TWO LED OUTDOOR REMOTE EMERGENCY LIGHTING

HEADS

EW 1 DUAL LITE EVCUGWD4I WALL MOUNTED EXIT SIGN, 277 VOLT

F 10 HE WILLIAMS 73-4-154T5H-WG-73141-EB2-277 SINGLE LAMP STRIP FIXTURE WITH WIRE GUARD FE 1 HE WILLIAMS 73-4-1-54T5H-WG-73141-EB2-277-EM SINGLE LAMP STRIP FIXTURE WITH WIRE GUARD AND

BATTERY BACKUP

G 12 HE WILLIAMS 73-4-2-54T5H-WG-73141-EB2-277 DUAL LAMP STRIP FIXTURE WITH WIRE GUARD

H 18 HE WILLIAMS CL-4-354T5H-F-KSH-34RF-AMW-EB3-277

V

3 LAMP WALL MOUNTED CORNER LIGHT WITH CLEAR

ACRYLIC LENS

J 8 FINELITE S10-SSL-8-2T5HO-DC-91W-OPEN-277-A

C-EE-C4-1.0

SUSPENDED LINEAR PENDANT 8' NOMINAL LENGTH

K 3 FINELITE S16-SSL-12-2T5HO-DC-91W-OPEN-277-A

C-EE-C4-1.0

SUSPENDED LINEAR PENDANT 12' NOMINAL LENGTH

L 9 CROSSOVER XCHWM3-LED-WT LED 48

450-NW-UE-BLK

LED EXTERIOR WALL SCONCE

M 1 HUBBELL NVX15GHGA-NVBA WALL MOUNTED VAPOR-TIGHT FIXTURE, TOSHIBA

8A19/27F-UP LED LAMP, 120 VOLT

N 2 CROUSE HINDS 43961-116-GR ROOF MOUNTED, TWO HEAD, AIRCRAFT WARNING

LIGHT

O 2 Kim Lighting CFL1-27L3KUV-BL LED FLOODLIGHT WITH ADJUSTABLE BARN DOOR

LOUVERS (BD-CFL/BL), ON STANCHION MOUNT

(SM18BL), 8" ABOVE GROUND

P 6 KIM Lighting GEM1C-36L3K277-LG-NG-C PERFORMANCE BOLLARD MOUNTED ON CONCRETE

SHAFT. TO BE BURIED 3' 6"

EXISTING LIGHTING DEVICE SCHEDULE

Model Description

4 CONTACT CONTACTOR FOR LIGHTING CIRCUITS WITH ON/OFF/AUTO SWITCH AND REMOTE PHOTOCELL 4 CONTACT CONTACTOR FOR LIGHTING CIRCUITS WITH ON/OFF/AUTO SWITCH AND REMOTE PHOTOCELL

RMJ-16R-DV-B PULL BOX FOR LIGHTING SYSTEM WITH POWPAK RELAY MODULE

LRF2-OCR2B-P-WH CEILING-MOUNT WIRELESS OCCUPACY SENSOR WITH SURFACE OR RECESSED MOUNTING HARDWARE AS REQUIRED FOR LOCATIONS INSTALLED

PULL BOX FOR LIGHTING SYSTEM, TYPICAL, FOR REFERENCE ONLY, MORE BOXES MAY BE REQUIRED

PHOTOCELL FOR USE WITH SITE LIGHTING CIRCUITS

PHOTO CELL FOR AIRCRAFT WARNING LIGHTS

HEAVY DUTY 120/277 VOLT SINGLE POLE SNAP SWITCH WITH FACE PLATE

MRF2-6ANS-277-** WIRELESS SWITCH. WHEN DUAL LEVEL SWITCHING IS USED, ENSURE THAT BOTH SWITCHES ARE CONFIGURED TO RESPOND TO WIRELESS OCCUPANCY SENSOR (OS) IN AREA.

HEAVY DUTY 120/277 VOLT SINGLE POLE SNAP SWITCH WITH FACE PLATE FOR GARBAGE DISPOSER CONTROL, WIRE TO RECEPTACLE

MRF2-6ND-120-WH WIRELESS DIMMER

HEAVY DUTY 120/277 VOLT SINGLE POLE SNAP SWITCH WITH FACE PLATE FOR CONTROL OF EXHAUST FAN

Type Mark Count Manufacturer Model

CON1 1

CON2 1

JRM 2 LUTRON RMJ-16R-DV-B

OS 28 LUTRON LRF2-OCR2B-P-WH

PB 18

PC 1

PCAW 1

S1 17 HUBBELL 1221

S2 34 Lutron Electronics MRF2-6ANS-277-**

S3 1 HUBBELL 1221

S4 2 Lutron Electronics MRF2-6ND-120-WH

S5 1 HUBBELL 1221

Grand total: 107

(N) BL 1 HE WILLIAMS DIG-522-L32/840-WPR-DRV-277 DIRECT/INDIRECT RECESSED LED FIXTURE, 3200

LUMEN, ROUND PERFORATED BAFFLE, 4000K

E 700FA

E 701FA

E 800

FIRST FLOOR FIRE ALARM AND MASS NOTIFICATION PLAN, SCHEDULE, AND LEGEND

SECOND FLOOR FIRE ALARM AND MASS NOTIFICATION PLAN

PANELBOARDS LP11, LP12, AND EL11 SCHEDULES

PANELBOARDS LP13, LP21, AND LP22 SCHEDULESE 801

(N)BL 1 HE WILLIAMS 76-4-L53/840-W6-7614-DRV-277 SINGLE LED LAMP, 5300 LUMEN, 4000K, WIRE GUARD

1ST FLOOR LIGHTING PLAN

SCALE

"=1' lv lv lv

J l v lv lv l v

D D

J J

J

JJ

J

J

J

JJ

J l v l v lvlv lv

J l v l v l v l v lv

S1 (b) S1 (a)

EW

LP13

CW (c)

CW (c)

CW (c)

A (d)

E

J (b)

G

CD

S1

S1 (e)

S1

E

S1

S2

S2

EO

EO

EO

OS

OS OS

OS

OS

OS

OS

OSOS

OS

OS

OS

GG

G G

M

S2 (a)

E-602

F (b)

F (a)

F (a)

F (b)

F (b) F (a)

F (a)

B

D

D

B

B B

B

A

A

A A

A

A

A A

F

D (a)

D (a)

A (d)

CL (e)

S2 S2

S2

H (b)H (a)H (b)

H (a)

H (a)

H (b)

H (a) H (b) H (a) H (b)

H (b)

H (a)

CD (b)

S4 (c) S4 (b)

S2

S2 (a)

A

T2LP11

HP11

SB2 SB1

EH11

T3

EL11

D1H2

METER

LP12

D

EE

EE

EE

EE

EE

EE

EE

CON2

S2 S2

S2 (d)

OS

CD (b)

CD (b)

CD (b)

TO UPPER LEVEL FIXTURES (SEE SECOND

FLOOR LIGHTING PLAN)

JRM

PCAW

PC

D (a)

E

E

EH11 -

J (a)

J (b)

J (a)

J (a)

J (a)

G

D

S2 (b)

S2

H (b)

CON1

S1

UP TO LIGHTS

ABOVE

SWITCH FOR

UPPER LIGHTS

S3

HP11 -

EH11 -

L

S2 (d)

HP11 -

13,15,17,4

S1 (a) S1 (b)

S1 (a) S1 (b)

TO UPPER LEVEL SWITCHES

S1

EL11 -

S2 (a) S2 (b)

EE

OS

OS

OS

CD

CD

S2

RD

(R) l v l v lv lv lv lv lv lv

J

J

J

J

JJ

J lv lv lvlv

J l v l v l v l v l v

JJ

K

KK

A

A

S1

S1

E E

E

E

(R)OS

OS

OS

OS

OS

OS

OS

OS OS

OS

OS

D

B

B

(N)BL

B B

B

F

F

D

D D

D

DD

A

D

A

CD

S2

S2

S2 S2

S2 S2

S2

S2

H (c)

FE

EE

EE

EE

EES2

S2S2

S2

FROM LOWER LEVEL

LIGHTING FIXTURES (SEE

FIRST FLOOR LIGHTING

PLAN)

JRM

L

S1 HP11 -

LP22

S1

E DS2 (c)

H (c)

G G

G

G G

G

EH11 -

LIGHTS SWITCHED FROM

SNAP SWITCH ON 1ST

FLOOR

EE

S5

S2S2

S2 (a) S2 (b)

EH11 -

DOWN TO

SUMP PUMP

2ND FLOOR LIGHTING PLAN

SCALE

"=1'

D1H2

(N)BL

J

WORK NOTES:

1 RELOCATE TYPE H FIXTURE NORTH TO AVOID NEW STAIR. MOVE FAR

ENOUGH TO MAINTAIN MINIMUM 7'-0" FROM RISER BELOW.

COORDINATE WITH FINAL STAIR SHOP DRAWINGS.

2 RELOCATE SWITCH S5 FOR EXHAUST FAN TO (N) JANITOR'S CLOSET.

2ND FLOOR POWER PLAN

SCALE

"=1'

J

J

J

J

J

J

J

LP21

R2

R2

R2

R2

R2R2

R4

R4

R1

R1

R1

R1

SGBB

LOCATE AT WIRING "WATERFALL"

ON TOWER

R7LP22 - 5

R11

R2 R2

R2

R2 R2 R2

R2 R2

R2

R2 R2

R2

R2

R2

R2 R2 R2

R2R2R2R2

R1

R1

R1

R1

R1

R12 R12 R12

R9 R9 R9 R9

LP22 -

6,8

LP22 - 2

R2

LP21 - 2

LP21 - 3

LP21 - 7

LP21 - 6

LP21 - 4

E-602

LP21 - 5

LP22 - 8

LP22 - 7

LP22 -

1,3

LP22 - 9

NOTE: ALL CIRCUITS RUN TO PANEL LP21

SHALL HAVE AN ISOLATED GROUND AS

WELL AS AN EQUIPMENT GROUND

R1

LP21 - 1

R2 D9H3

CC

HP11 -

20,22,24

R15 R15

R15

R15

R15

LP22 -

GPB

GPB

GPB

GPB

GPB

LP22

R5 R5 R5

R5

LP22 -

2,4 LP22 -

LP22 -

LP22 -

Notes:

Spare 64830 VA 100.00% 64830 VA

Receptacle 51010 VA 59.80% 30505 VA

Power 5800 VA 100.00% 5800 VA

Other 25554 VA 100.00% 25554 VA

Motor 76469 VA 111.26% 85078 VA Total Est. Demand: 445 A

Lighting 11232 VA 125.00% 14040 VA Total Conn.: 455 A

Heating 11200 VA 100.00% 11200 VA Total Est. Demand: 369653 VA

HVAC 80679 VA 100.00% 80679 VA Total Conn. Load: 378527 VA

Cooling 63172 VA 100.00% 63172 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 539 A 530 A 525 A

Total Conn. Load: 149151 VA 146636 VA 145553 VA

8 H-1, H-2, H-3 3 60 A 60 A 11400 VA 11400 VA 11400 VA

7 ACC-1 3 200 A 125 A 20633 VA 20633 VA 20633 VA

6 MTS 3 200 A 200 A 30668 VA 31459 VA 30853 VA

5 T2 3 200 A 175 A 48792 VA 43151 VA 43027 VA

4 TVSS 3 60 A 60 A 0 VA 0 VA 0 VA

3 MSEMM 3 100 A 100 A 19214 VA 19214 VA 19214 VA

2 HCB1 3 60 A 40 A 7834 VA 7834 VA 7834 VA

1 HP11 3 200 A 200 A 14054 VA 16344 VA 16016 VA

CKT Circuit Description # of Poles Frame Size Trip Rating

A B C

Remarks

Notes:

Enclosure: NEMA 1 MCB Rating: 1 A

Mounting: PAD Wires: 4 Mains Rating: 800 A

Supply From: SB1 Phases: 3 Mains Type:

Location: Volts: 480/277 Wye A.I.C. Rating: 30000

Switchboard:SB2

WORK NOTES:

1 TEMPORARILY RELOCATE RECEPTACLES IN WEST WALL OF CLASSROOM 210 TO AVOID TEMPORARY OPENING, REINSTALL

WITH WALL PATCH

2 MOUNT GPS ANTENNA (REFERENCE A-302 FOR APPROXIMATE LOCATION) ROUTE CABLE TO INTERIOR, SEAL WALL

PENETRATION

3 INSTALL SURGE PROTECTOR AS CLOSE AS POSSIBLE TO WALL PENETRATION, PROVIDE GROUND IN CONDUIT TO NEW SGBB

BELOW

4 COORDINATE ROUTING OF GPS CABLE WITH EXISTING MECH/ELEC/PLUMB ON WALLS OFFSET AS REQUIRED (REFERENCE

E-301 FOR CONTINUATION)

5 PROVIDE 2" AND 6" CONDUIT STUB THROUGH FLOOR FOR SNS POWER AND COMM

CONTRACTOR INSTALLED GOVERNMENT PROPERTY - GPS ANTENNA:

1. GPS ANTENNA, MOUNTING BRACKET, SURGE PROTECTOR, AND RG58 CABLE ARE GOVERNMENT FURNISHED, CONTRACTOR

INSTALLED

2. CONTRACTOR SHALL PROVIDE AND INSTALL CONDUIT AND ACCESSORIES FROM EXTERIOR WALL PENETRATION TO

VERTICAL DROP 5' A.F.F. IN CENTER OF COMPUTER ROOM, COORDINATE WITH FUTURE CABINET LOCATION

3. CONTRACTOR SHALL PROVIDE TYPE N CABLE CONNECTIONS AT ANTENNA AND SURGE PROTECTOR

4. CONTRACTOR SHALL PROVIDE GROUND AND CONDUIT FORM SURGE PROTECTOR TO NEW SGBB BELOW

5. GOVERNMENT WILL PROVIDE CABLE FINAL CONNECTION AT FUTURE GPS RECEIVER IN COMPUTER ROOM

(E)

UTILITY TRANSFORMER

277/480V, 3PH, 4W

ELECTRIC METER

A

MTS

E

S/P F

C

HCB1

I

T-1 K

T-2

HP11

LP11

M

LP21 LP22

LP12

LP1

P

Q

T

O

(N)MSUPS

R

MSEMM

(N)EMM

N.I.C.

(N)UPS

N.I.C.

CRAC-1

DISC-H1

N

WST COMPUTER ROOM FLOOR

FIRST FLOOR

TVSS

J

TVSS2

Y

MSA

D1

S

V

P1

U W

MSS-1

Z

Z1

X

UPON COMPLETION OF PROJECT THE FOLLOWING MEASUREMENTS SHALL BE MADE OVER A PERIOD OF SEVERAL DAYS (THE RESULTS TO BE SENT TO CAE FOR ANALYSIS) PREFERABLY WHEN THE AREA OF INTEREST AND ANY NEAR-BY AREAS HAVE THEIR FULL COMPLEMENT OF ELECTRICAL EQUIPMENT INSTALLED AND OPERATED:

MAIN INPUT VOLTAGE VARIATIONS, SAGS AND SURGES (ALL PHASES AND NEUTRAL)

FREQUENCY VARIATIONS

TRANSIENTS MAGNITUDE EXCEEDING 1.5 TIMES THE NOMINAL VOLTAGE

TRANSIENTS DURATION EXCEEDING 1/2 POWER CYCLE

NUMBER AND DURATION OF POWER OUTAGES

1" CONDUIT FOR METER WIRING

WST COMPUTER ROOM LOWERED FLOOR

EH11

EL11

SB1 SB2

D1H2

D

T3 HG

L

PDU

Z2

MSPDU

Z3

Z4

ELECTRICAL FEEDER SCHEDULE

FEEDER

DESIGNATION

FOR ONE LINE Panel Circuit Number Load Name Wire Size

Conduit Size When

Larger Than 1/2" Voltage

ASCI At Load Comments

A T-1 1 SB1 3 runs of 3-#300, 1-#300, 1-#1/0 3 - 3" 480 V 28739

C SB2 6 MTS 3-#3/0, 1-#3/0, 1-#6 2" 480 V 24268

D MTS 2 D1H2 3-#3/0, 1-#3/0, 1-#6 2" 480 V LESS THAN 10000

E D1H2 1,3,5 S/P 3-#3/0, 1-#3/0, 1-#6 2" 480 V LESS THAN 10000

F MTS 1 EH11 3-#3/0, 1-#3/0, 1-#6 2" 480 V 22769

G EH11 1,3,5 T3 3-#3, 1-#3, 1-#6 1 1/4" 480 V 20728

H T3 1 EL11 3-#3/0, 1-#3/0, 1-#6 2" 208 V LESS THAN 10000

I SB2 2 HCB1 3-#8, 1-#8, 1-#10 1 1/4" 480 V 4561

J SB2 4 TVSS 3-#6, 1-#6, 1-#10 1" 480 V 19482

K SB2 1 HP11 3-#3/0, 1-#3/0, 1-#6 2" 480 V 27172

L SB2 5 T2 3-#2/0, 1-#2/0, 1-#6 2" 480 V 25064

M T2 1 LP11 2 runs of 3-#3/0, 1-#3/0, 1-#3 2 - 2" 208 V LESS THAN 10000

N (R) SB2 3 MSEMM 3-#3, 1-#3, 1-#8 (N) 240 A 1 1/4" 480 V 7373

O LP11 1,3,5 LP12 3-#1/0, 1-#1/0, 1-#6 2" 208 V LESS THAN 10000

P LP11 2,4,6 LP21 3-#1/0, 1-#1/0, 1-#6 2" 208 V LESS THAN 10000

Q LP11 8,10,12 LP22 3-#1/0, 1-#1/0, 1-#6 2" 208 V LESS THAN 10000

R (N) LP11 20,22,24 MSUPS 3-#3/0, 1-#3/0, 1-#6 2" 208 V LESS THAN 10000

S LP11 13,15,17 MSA 3-#6, 1-#6, 1-#10 1" 208 V LESS THAN 10000

T LP11 7,9,11 LP13 3-#1/0, 1-#1/0, 1-#6 2" 208 V LESS THAN 10000

U HCB1 1,3,5 CRAC-1 3-#8, 1-#8, 1-#10 1 1/4" 480 V LESS THAN 10000

V (N) MSA 1 D1 HVAC WST HIGH BAY 124 3-#6, 1-#6, 1-#10 1" 208 V LESS THAN 10000 VERIFY WIRE AND CONDUIT WITH PROVIDED A/C

W (N) MSUPS 1,3,5 UPS 3-#3/0, 1-#3/0, 1-#6 2" 208 V LESS THAN 10000

X (R) MSEMM 1 EMM 3-#3, 1-#3, 1-#8 1 1/4" 480 V LESS THAN 10000 VERIFY WIRE AND CONDUIT SIZE

Y MSUPS 2,4,6 TVSS2 3-#10, 1-#10, 1-#10 1/2" 208 V LESS THAN 10000

Z (N) UPS 1 MSS-1 3-#3/0, 1-#3/0, 1-#6 2" 208 V LESS THAN 10000

Z1 MSS-1 1,3,5 P1 3-#3/0, 1-#3/0, 1-#6 2" 208 V LESS THAN 10000 WIRING FROM BREAKER TO EQUPMENT NOT REQUIRED IN THIS CONTRACT Z2 SB1 1 SB2 3 runs of 3-#300, 1-#300, 1-#1/0 480 V 28739

Z3 LP11 14,16,18 MSPDU 3-#3, 1-#3, 1-#8 1 1/4" 208 V LESS THAN 10000

Z4 MSPDU 1,3,5 PDU 3-#3, 1-#3, 1-#8 1 1/4" 208 V WIRING FROM BREAKER TO EQUPMENT NOT REQUIRED IN THIS CONTRACT

WORK NOTES:

1 (N) UPS TO BE GOVERNMENT PROVIDED AND CONTRACTOR TO

PROVIDE WIRING AND FINAL CONNECTION

2 (N) D1 TO BE GOVERNMENT PROVIDED AND CONTRACTOR TO

PROVIDE WIRING AND FINAL CONNECTION

3 (N) EMM TO BE GOVERNMENT PROVIDED AND CONTRACTOR

VERIFY WIRE AND CONDUIT, SIZE FOR INCREASED LENGTH OF RUN

VERIFY WIRE AND CONDUIT, SIZE FOR 240 A

VERIFY WIRE AND CONDUIT, SIZE FOR 222 A

ELECTRICAL ONE LINE

N.T.S.

(R)

(N)GARAGE

DOOR

(N)GARAGE

DOOR

Z6

Z5

VERIFY WIRE AND CONDUIT, SIZE FOR 240 A

Z5 LP12 FIELD VERIFY GARAGE DOOR 208 V

Z6 208 V VERIFY WIRE AND CONDUIT, SIZE FOR PROVIDED DOORLP12 FIELD VERIFY GARAGE DOOR

VERIFY WIRE AND CONDUIT, SIZE FOR PROVIDED DOOR

Z7 LP12 OR 21

N.I.C.

SNS 200 V VERIFY WIRE AND CONDUIT

STRIKEPLATE

(4) INCARD READER (TYP)

DOOR

SIDE OF

UN-SECURE

FINISHED FLOOR DOOR

SECURE SIDE OF

REQUEST-TO-EXIT SENSOR

3/4" CONDUIT (TYP)

EXIT BUTTON

JUNCTION BOX

JUNCTION BOX

(3) M62 MAGLOCK (TYP)

3/4" CONDUIT (TYP)

(1) 3/4" CONDUIT (TYP)

3/4" CONDUIT (TYP)

FINISHED CEILING

CONDUIT SYSTEM

3/4" EMT CONDUIT TO SECURITY

3/4" CONDUIT

3/4" HOLE

DOORSTOP

MAG LOCK

M62DOOR

HEADER

JUNCTION BOX

SINGLE ENTRY SECURITY DOOR DETAIL

N.T.S

WORK NOTES:

1 COORDINATE EXACT LOCATIONS WITH SECURITY CONTRACTOR, WIRING NOT IN THIS

SCOPE.

DPEZ182200 8-15-20 COVER
DPEZ182200 9-15-20 A-101-A 101
DPEZ182200 9-15-20 A-102-A 102
DPEZ182200 9-15-20 A-401-A 401
DPEZ182200 8-15-20 A-402-A 402
DPEZ182200 9-15-20 M-101-M 101
DPEZ182200 9-15-20 P-101-P-101
DPEZ182200 8-15-20 E-100-E 100
DPEZ182200 8-15-20 E-101-E-101
DPEZ182200 9-15-20 E-202-E-202
DPEZ182200 8-15-20 E-301-E-301
DPEZ182200 8-15-20 E-501S-E-501

File details come from the government source that posted it. Updated .