Lightning Inspection Building 306.pdf
PDF 9 MB Posted
- Attached to
- Lightning Protection Systems Repair Federal contract opportunity
- Solicitation number
- W50S8V-24-B-0003
- Issued by
- Department of the Army National Guard
About this file
This document is a Lightning Protection Systems (LPS) Inspection Checklist for Building 306 Hangar. The checklist details the visual inspection of the roof top components, ground system, and ground resistance and continuity testing performed on the LPS. It includes descriptions of the items inspected, notes on any corrections needed, and the resistance readings taken at various locations on the system.
The related federal contract opportunity is for the Repair of Lightning Protection Systems, with a Solicitation Number of W50S8V-24-B-0003. This is a Total Small Business Set-Aside project with a NAICS code of 238210 and a size standard of $19.0M. The expected contract value is between $25,000.00 and $100,000.00. Davis Bacon Wage Rates apply, and payment bonds are required for bids over $35,000.00. Award will be made to the responsible bidder with the most advantageous bid, considering only price.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| W50S8V-24-B-0003-0002.pdf | ||
| Lightning Protection Systems Repair Site Visit Attendance Sheet.pdf | ||
| QA - Lightning Protection System W50S8V-24-B-0003.pdf | ||
| WD WV20240034 12 July 2024.pdf | ||
| Site Visit PP - Lightning Protection System Repairs.pptx | PPTX presentation | |
| W50S8V-24-B-0003-0001.pdf | ||
| Visitor and Contractor Background Check Form Repair LPS.docx | DOCX document | |
| SOW - Repair LPS Base Wide.pdf | ||
| Lightning Inspection Building 302.pdf | ||
| Lightning Inspection Building Hangar 308.pdf | ||
| W50S8V-24-B-0003 Repair LPS.pdf | ||
| Lightning Inspection Building 305.pdf | ||
| Lightning Inspection Building 307.pdf | ||
| Lightning Inspection Building 119.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MULTIVARIABLE SYSTEMS TECH, LLC
DUNS: 080122060 || FEIN: 81-0768594 || 3923 S. TAVISTOCK PL. || MERIDIAN, ID 83642 || Tel. (208)
867-713ON & TESTING CHECKLIST
Date: _______11/8/23________ Inspected and Tested By: __MVS (Jesse, Dustin, Lumuli)________
Structure/Building Identification: ________306 Hangar_________________________
Date Last Known Rainy Day: ____11 days__________ Humidity: ___1%______________________
A. Visual Inspection of Roof Top Components
B. Visual Inspection Ground System:
Item Descriptions Notes/Correction
1 Visual inspections of the overall system condition. Appearance (neat, dislodged, broken cables etc.). See Notes
2 Visually inspect all air terminals. Verify that size and quantity is sufficient per NFPA 780/UL96A requirements.
3 Verify that all air terminals (lightning rods) have been placed at 20’-0” maximum spacing around roof perimeter and/or roof ridges.
4 Verify that perimeter air terminals are within 2’-0” of the outside edge including corners of the structure.
5 Verify that mid-roof air terminals are spaced at maximum spacing of 50’-0” in accordance with NFPA 780.
6 Verify interconnecting mid-roof cables connecting mid-roof air terminals are properly spaced. Further verify 150’-0” maximum length of cross run conductor to the main perimeter or down conductor in accordance with
NFPA 780.
7 Verify that copper materials are not mounted or in contact with aluminum materials and vice-versa.
8 Verify that all conductors are fastened horizontally and vertically not more than 3’-0” maximum spacing.
9 Verify inductive metallic bodies located within 6’ 0” of lightning conductor or another bonded metal body shall be interconnected to the lightning conductor system, unless inherently connected.
10 Verify air terminals and bonding connectors are installed on rooftop, fans, ventilators. A/C units etc. in accordance with NFPA 780 UL96A.
11 Remove and clean all cable connections including but not limited to;
Bonding plates, lugs, cable to cable connectors etc.
Item Descriptions Notes/Correction
3923 S. TAVISTOCK PL. || MERIDIAN, ID 83642
C. Ground Resistance & Continuity Testing:
D. Additional Notes (If Necessary):
1 Locate all through roof connection to down runs or to structural steel. Visually inspect for damage and tightness.
2 Verify the quantity of down runs/connection to ground is adequate per NFPA 780 and UL96A based on the size of the structure.
3 If the connection is to steel, verify that connection is made in accordance with NFPA 780 and that the area under connection is clean of all paint, oil, grease etc.
4 Verify that spacing of down conductors at roof level are installed in accordance with NFPA 780 and UL96A (100’ on average).
5 Visually inspect connections to rebar/structural steel etc. for corrosion remove connections clean and reinstall. Replace if necessary.
6 Visually inspect ground rods and cable connections to ground rods. Remove and clean if necessary.
Item Descriptions Notes/Correction
1 Record the device readings for all tested points: See Additional Notes
2 Inspect and document status of surge protection - transient voltage surge suppression (TVSS) systems. Verify TVSS systems are installed in accordance to NEC 70 or other applicable codes or standards.
N/A
Perform ground resistance on lightning protection grounding system.
Performed, see notes.
3 Take additional photographic or video documentation of particular areas of the lightning protection system that needs further long term repair that may go beyond the scope of this inspection but needs attention.
See below.
READING LOCATIONS RESISTANCE READINGS
EAST SLOPE
SW 0.082Ω
W 0.029Ω
NW 0.52Ω Missing nut on wall connector
NE 0.015Ω
E 0.035Ω
E2 0.25Ω
SE 0.013Ω
CENTER DOME Reattached 3 full lines of cables that were dislodged from connectors. 2 air terminals re-glued.
SE 0.096Ω
SE2 0.062Ω
SE Antenna 0.015Ω
Red Lights 0.033Ω
S Red Lights 0.013Ω
SW Antenna 0.013Ω
SW Antenna 0.014Ω
HVAC 0.07Ω
West 0.13Ω
West 2 0.16Ω
West 3 0.14Ω
NW Red Lights 0.14Ω
NW Antenna 0.017Ω
N Red Lights 0.015Ω
NE Corner 2.2Ω
East 0.052Ω
E2 0.015Ω
E3 0.016Ω
E4 0.019Ω
WEST SLOPE
SE Corner 0.013Ω
East 0.019Ω
NE Corner 0.20Ω
N 42.0Ω
W 0.22Ω
W 0.017Ω
SW 0.059Ω
S 0.080Ω