Mechanical Bldg. 200 Energy Repairs.pdf

PDF 6 MB Posted

Attached to
Bldg. 200 Energy Repairs/Upgrades
Solicitation number
W50S8D26QA012
Issued by

About this file

This file is a 95% submittal design document for mechanical systems related to an energy repair project at Building 200 of the 105th Airlift Wing, Air National Guard Base, Stewart International Airport in Newburgh, New York. The project is identified by solicitation number WHAY142004 and was submitted on May 29, 2026.

The design encompasses the installation and configuration of seven gas-fired infrared radiant heaters (IRH-1 through IRH-7) distributed across maintenance bays, support shops, and covered storage areas. Each heater has a 60 MBH input capacity with 48,000 BTUH output and a 20-foot length, requiring 120V single-phase 60Hz electrical service. The heaters include 4-inch diameter combustion air inlets and vent terminations routed to the roof with manufacturer-provided caps. The project requires coordination with existing mechanical, electrical, and structural systems, including natural gas piping at various sizes (from 3/4-inch to 10-inch diameter), pressure regulators set for medium pressure (2 PSI) and low pressure (0.5 PSI) supply, and control integration with the building automation system. The design specifies compliance with UFC 4-214-02:2018, International Mechanical Code 2018, NFPA 54:2018, and IPC 2018. Control requirements include programmable thermostats, two-stage heating capability, occupancy-based scheduling, and alarming for system faults and low zone temperature conditions. All work must follow SMACNA HVAC duct construction standards, with proper flashing, support systems, and comprehensive operations and maintenance documentation required at project completion.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

U

M

CO

DP

SD

A

T

S

M

H

CO

EQUIPMENT TAG

MECHANICAL LEGEND MECHANICAL ABBREVIATIONS

NOTES:

1. THIS LEGEND IS FOR REFERENCE ONLY.

2. ALL SYMBOLS WITHIN THIS LEGEND MAY NOT APPLY TO THIS PROJECT.

DUCT SECTION, POSITIVE PRESSURE

DUCT SECTION, NEGATIVE PRESSURE

NEW DUCTWORK

FIRE DAMPER, PROVIDE ACCESS DOOR

VOLUME DAMPER

SUPPLY/INTAKE AIRFLOW DIRECTION

GRILLE OR REGISTER, SIDEWALL

LOUVER AND SCREEN

ANCHOR, INTERMEDIATE

BUTTERFLY VALVE

PRESSURE GAUGE

MANUAL AIR VENT

AUTOMATIC AIR VENT

MOTORIZED DAMPER

EMERGENCY SHUTDOWN SWITCH

HVAC - #

DUCT SIZE & SYSTEM ABBREVIATION

FIRST FIGURE IS DIMENSION SHOWN ON PLAN

FLEXIBLE DUCTWORK

DUCT TRANSITION

TURNING VANES

CEILING DIFFUSER - SUPPLY

CEILING DIFFUSER - RETURN

CEILING DIFFUSER - EXHAUST

PIPE CAP

PIPE CONNECTION, BOTTOM

PIPE CONNECTION, TOP

PIPE ELBOW, TURNED UP

PIPE ELBOW, TURNED DOWN

PIPE TEE

STRAINER VALVE

THREE-WAY CONTROL VALVE

TWO-WAY CONTROL VALVE

PUMP (SCHEMATIC)

THERMOSTAT

CARBON DIOXIDE SENSOR

20x12

SA

POINT OF DISCONNECTION

POINT OF CONNECTION

KEYED NOTE

AIR TERMINAL AND AIRFLOW TAG

DIFFERENTIAL PRESSURE SENSOR

DUCT SMOKE DETECTOR

GATE VALVE

CHECK VALVE

CD-A W X H ###

AIR QUANTITY DELIVERED

BY DEVICE IN CFM

AIR TERMINAL MARK AS

INDICATED IN SCHEDULE

MASTER EMERGENCY SHUTDOWN SWITCH

GATE VALVE

CEILING DIFFUSER - ROUND

BALL VALVE

BUTTERFLY VALVE

BRANCH DUCTWORK

RECT. TO ROUND TRANSITION

PNEUMATIC DAMPER

EXHAUST AIRFLOW DIRECTION

LINEAR SLOT DIFFUSER (DOUBLE SLOT)

BOTTOM OF DUCT ELEVATION TAGBOD: 4' - 7"

BACKDRAFT DAMPER

BD

HUMIDISTAT

CARBON MONOXIDE SENSOR

DOOR UNDERCUT

AREA OUT OF SCOPE

AREA OF DEMOLITION

Ø DIAMETER

AIR TERMINAL NECK SIZE (IN.)

SAD-#

### CFM

OR

AIR TERMINAL MARK AS INDICATED

IN SCHEDULE

AIR QUANTITY DELIVERED BY

DEVICE

SHEET ID

N A

T

IO

N A

L G

U A

R D

B U

R E

A U

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

F Y

T Y

P E

A -2

S

U B

M

IT

T A

L

A P

R

P E

B -2

P

R E

-F

IN

A L

D E

S

IG

N

J U

L

M-001

A B

B R

E V

IA

T

IO

N

S

L E

G E

N D

S

A N

D N

O T

E S

T H

A

IR

L

IF

T W

IN

G

A

IR

N

A T

IO

N

A L G

U A

R D

B A

S E

S

T E

W A

R T

IN

T

E R

N A

T

IO

N A

L A

IR

P

O R

T

M A

G U

IR

E

W A

Y

N E

W B

U R

G H

N

Y

R .E

A R

L

IE

R .E

A R

L

IE

S .R

O L

L

IN

S

M

AY

S

U B

M

IT

T A

L

E N

E R

G Y

R

E P

A

IR

B U

IL

D

IN

G

W H

A Y

DESIGN CONDITIONS FOR LOAD CALCULATIONS

SEASON OUTDOOR DESIGN CONDITIONS ELEV. (FT)

INDOOR CONDITIONS / ROOM TYPE

SHOPS

WINTER (99% DB) 4.6°F 581 55°F

(D) DEMOLITION

(E) EXISTING

(R) RELOCATED

AAV AUTOMATIC AIR VENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

AP ACCESS PANEL

APD AIR PRESSURE DROP

BFF BELOW FINISHED FLOOR

BHP BRAKE HORSEPOWER

CAP CAPACITY

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

CONC CONCRETE

COND CONDENSATE

CONN CONNECTION

CONT CONTINUATION

CP-1 CONTROL PANEL WITH DESIGNATION

CU CONDENSING UNIT

DB DRY BULB

DEG DEGREES

DEMO DEMOLITION

DIA DIAMETER

DN DOWN

DWG DRAWING

EA EXHAUST AIR

EAG EXHAUST AIR GRILLE

EAT ENTERING AIR TEMPERATURE

EF EXHAUST FAN

ENT ENTERING

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

EUH ELECTRIC UNIT HEATER

EXH EXHAUST

F FAHRENHEIT

FCU FAN COIL UNIT

FD FIRE DAMPER

FLEX FLEXIBLE

FM FLOW METER

FPM FEET PER MINUTE

GAL GALLONS

GM GAS METER

GPM GALLONS PER MINUTE

GUH GAS UNIT HEATER

HP HORSEPOWER

ID INSIDE DIAMETER/DIMENSION

IE INVERT ELEVATION

IN INCH

LAT LEAVING AIR TEMPERATURE

LVL LEVEL

LWT LEAVING WATER TEMPERATURE

M METER

MAX MAXIMUM

MFR MANUFACTURER

MIN MINIMUM

MISC MISCELLANEOUS

N/A NOT APPLICABLE

NG NATURAL GAS

NTS NOT TO SCALE

OA OUTDOOR AIR

OD OUTSIDE DIAMETER

OED OPEN ENDED DUCT

PD PRESSURE DROP

PSI POUNDS PER SQUARE INCH

R RADIUS

RA RETURN AIR

RAG RETURN AIR GRILLE

REFRIG REFRIGERANT

RH RADIANT HEATER

RL REFRIGERANT LIQUID LINE

RPM REVOLUTIONS PER MINUTE

SA SUPPLY AIR

SAG SUPPLY AIR GRILLE

SB SECURITY BARS

SF SUPPLY FAN

SPEC SPECIFICATION

STD STANDARD

T THERMOMETER

TA TRANSFER AIR

TBD TO BE DETERMINED

TEMP TEMPERATURE

TSP TOTAL STATIC PRESSURE

TSTAT THERMOSTAT

TYP TYPICAL

UH UNIT HEATER

VAV VARIABLE AIR VOLUME

VIF VERIFY IN FIELD

VRF VARIABLE REFRIGERANT FLOW

W WATT

WB WET BULB

WMS WIRE MESH SCREEN

APPLICABLE CODES AND STANDARDS

UNITED FACILITIES CRITERIA (UFC 4-214-02: 2018)

MECHANICAL CODE (IMC 2018)

NATIONAL FIRE PROTECTION AGENCY (NFPA) (NFPA 54: 2018)

PLUMBING CODE (IPC 2018)

NOTE: ALL APPLICABLE BUILDING CODES AND STANDARDS ARE NOT SPECIFIED HEREIN.

1. UNLESS OTHERWISE SHOWN, LOCATE ALL ROOM SENSORS AND THERMOSTATS SUCH THAT

OPERABLE PARTS ARE NO HIGHER THAN 48" ABOVE FINISHED FLOOR.

2. ALL CONTROL CONDUIT AND WIRING SHALL COMPLY WITH THE ELECTRICAL CODE AND THE

SPECIFICATIONS.

CONTROL NOTES

MECHANICAL GENERAL NOTES

1. THESE GENERAL NOTES APPLY TO ALL SHEETS. REFER TO INDIVIDUAL SHEETS FOR SHEET SPECIFIC NOTES.

2. CONTRACT DOCUMENT DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL ARRANGEMENT ONLY. DO NOT SCALE FOR MATERIAL QUANTITIES. ALL SCALING SHOULD BE REFERENCED TO

ARCHITECTURAL PLANS ONLY.

3. ALL MECHANICAL WORK SHALL BE IN STRICT COMPLIANCE WITH THE LATEST APPLICABLE EDITION OF THE INTERNATIONAL MECHANICAL AND PLUMBING CODES, APPLICABLE PROVISIONS OF THE NATIONAL FUEL GAS

CODE (NFPA 54), AND APPLICABLE UFCS (MILITARY WORK).

4. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH ALL OTHER DISCIPLINES AND AS SHOWN ON

OTHER CONTRACT DRAWINGS.

5. CONTRACTOR SHALL VISIT SITE AND VERIFY ALL EXISTING CONDITIONS AND CONNECTIONS TO EXISTING

WORK PRIOR TO BIDDING AND CONSTRUCTION.

6. COORDINATE ALL CUTTING AND PATCHING WITH GENERAL CONTRACTOR AND OTHER DISCIPLINES.

CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING RELATED TO THEIR WORK.

7. ALL ATTACHMENTS TO THE BUILDING STRUCTURE SHALL BE COORDINATED WITH THE STRUCTURAL DESIGN.

ALL BRACING AND MOUNTING OF PIPES AND DUCTS SHALL MEET THE MINIMUM REQUIREMENTS OF THE MOST RECENT SMACNA HVAC DUCT CONSTRUCTION STANDARDS-METAL AND FLEXIBLE. CONTRACTOR SHALL

MAINTAIN ONE COPY OF THIS MANUAL ON SITE AT ALL TIMES.

8. PROVIDE FLASHING AND COUNTERFLASHING FOR ALL PENETRATIONS THROUGH WALLS OR ROOF TO MAKE

WATERPROOF INSTALLATION.

9. ALL MISCELLANEOUS STEEL REQUIRED TO ENSURE PROPER INSTALLATION AND AS SHOWN IN THE DETAILS FOR PIPING, DUCTWORK, AND EQUIPMENT (UNLESS OTHERWISE NOTED) SHALL BE FURNISHED AND INSTALLED

BY THE MECHANICAL CONTRACTOR.

10. AT COMPLETION OF CONSTRUCTION, CONTRACTOR SHALL PROVIDE COPIES OF BOUND OPERATIONS AND

MAINTENANCE MANUALS.

11. AT THE TIME OF ROUGH INSTALLATION AND DURING STORAGE ON THE CONSTRUCTION SITE UNTIL FINAL STARTUP OF THE HEATING, COOLING AND VENTILATING EQUIPMENT, ALL DUCT AND OTHER RELATED AIR DISTRIBUTION COMPONENT OPENINGS SHALL BE COVERED WITH TAPE, PLASTIC, SHEETMETAL OR OTHER METHODS ACCEPTABLE TO THE ENFORCING AGENCY TO REDUCE THE AMOUNT OF DUST, WATER AND DEBRIS

WHICH MAY ENTER THE SYSTEM.

GENERAL NOTES

1. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH MANUFACTURERS

RECOMMENDATIONS, CONTRACT DOCUMENTS, AND APPLICABLE CODES AND REGULATIONS.

2. WHERE TWO OR MORE ITEMS OF THE SAME TYPE OF EQUIPMENT ARE REQUIRED, THE PRODUCT OF ONE

MANUFACTURER SHALL BE USED.

3. IDENTIFY ALL NEW MECHANICAL EQUIPMENT WITH NAMEPLATES PERMANENTLY ENGRAVED PER

SPECIFICATIONS.

4. EQUIPMENT AND APPLIANCES SHALL BE ACCESSIBLE FOR SERVICE, INSPECTION, REPAIR AND REPLACEMENT WITHOUT REMOVING PERMANENT CONSTRUCTION. SUFFICIENT CLEARANCE SHALL BE MAINTAINED TO PERMIT CLEANING, REPLACEMENT OF FILTERS, BLOWERS, MOTORS, CONTROLS AND

LUBRICATION OF MOVING PARTS.

EQUIPMENT NOTES

1. ALL GAS PIPING SHALL BE LABELED AT BEGINNING, ALL ENDS, AND AT 6' INTERVALS DESIGNATING GAS

& PRESSURE. LABELS SHALL BE PER SPECIFICATIONS.

2. PROVIDE/INSTALL THROUGH WALL PIPE PENETRATIONS AS REQUIRED WHERE PIPE ENTERS BUILDING.

SLEEVE AND SEAL.

3. SUPPORT ALL PIPING SO THAT IT IS FIRMLY HELD IN PLACE BY APPROVED HANGERS AND SUPPORTS.

PIPING NOTES

TY

PE

B

-3 (1

) F

IN

AL

D

ES

IG

N

F

EB

S.

FO

R D

M

AY

IS

SU

E

FO

R

C O

N

ST

R U

C

TI

O

(E)MAU-1A(E)MUU-1

(E)F-1

(E)F-2

(E)F-3 (E)F-4 (E)F-5

(E)F-6

6"ø NG

10"ø NG8"ø NG

(E)PRV-2 (E)PRV-3(E)PRV-1

(E)VUH-4

(E)VUH-3

(E)VUH-5 (E)VUH-6 (E)VUH-7

(E)RH

(E)RH

IRH-1IRH-2IRH-3

IRH-4

IRH-5

IRH-6

IRH-7

(E)WH-1

3"ø NG3"ø NG

"ø

N G

"ø

N G

HEATED

COVERED

STORAGE

UNHEATED

COVERED

STORAGE

MAINTENANCE

BAYS

105A

SUPPORT

SHOP

MAINTENANCE

BAYS

105B

(E

(E)

2"ø NG(E)

(E)

(E)

2"ø NG(E) (E)

(E)

(E

/4

"ø N

G

3/4"ø NG

3/4"ø NG

3/4"ø NG

/4

"ø N

G

/4

"ø N

G

/4

"ø N

G

(E

/4 "ø

N G

(E) 3/4"ø NG

UP

1 2 2.5 2.6 3 4 5 6 7 8 9 10 10.1 10.5 11 12

A

B

D.1

D

E

G

J

T

T T

T T

T

T

4" OSA

4" VENT

4" OSA

4" VENT 4" OSA

4" VENT

4" OSA

4" VENT

K

4" OSA

4" VENT

L

4" OSA

4" VENT

M

4" OSA

4" VENT

4 4

SHEET ID

N A

T

IO

N A

L G

U A

R D

B U

R E

A U

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

0.5' 1' 2'

1"=1'-0"SCALE:

PLAN NORTH

F Y

P E

A -2

S

U B

M

IT

T

A P

R

P E

B -2

P

R E

-F

IN

A L

D E

S

J U

L

M-101

M E

C H

A N

IC

A

L F

L O

O R

P L

A N

T H

A

IR

L

IF

T W

IN

G

A

IR

N

A T

IO

N

A L G

U A

R D

B A

S E

S

T E

W A

R T

IN

T

E R

N A

T

IO

N A

L A

IR

P

O R

T

M A

G U

IR

E

W A

Y

N E

W B

U R

G H

N

Y

R .E

A R

L

IE

R .E

A R

L

IE

S .R

O L

L

IN

S

M

AY

S

U B

M

IT

T A

L

E N

E R

G Y

R

E P

A

IR

B U

IL

D

IN

G

W H

A Y

SCALE: 1" = 10'-0"A1

MECHANICAL FLOOR PLAN

GENERAL SHEET NOTES

1. ALL EXISTING MECHANICAL SYSTEMS SHALL

REMAIN.

2. THE CONTRACTOR SHALL MAINTAIN ALL

CLEARANCE REQUIREMENTS FOR IRHS DURING

INSTALLATION

1. RELOCATED VUH-4 AS REQUIRED TO ALLOW

CLEARANCE FOR VENT AND INTAKE DUCTWORK

FOR IRH-4.

2. MOUNT IRH AS A HIGH AS POSSIBLE WHILE

MAINTAINING A MINIMUM OF 6" CLEARANCE

ABOVE HEATER.

3. 4" COMBUSTION AIR INLET ROUTED UP TO ROOF.

TERMINATE WITH MANUFACTURER'S PROVIDED

ROOF INTAKE CAP.

4. 4" VENT ROUTED UP TO ROOF. TERMINATE WITH

MANUFACTURER'S PROVIDED ROOF VENT CAP.

KEYNOTES#

TY

PE

B

-3 (1

) F

IN

AL

D

ES

IG

N

F

EB

S.

FO

R D

IS

SU

E

FO

R C

O N

ST

R

U C

TI

O

N

M

AY

VERIFY MOUNTING

HEIGHT WITH

OWNER

TYPE B

GAS VENT

SEE DETAIL C1 FOR SUSPENSION

INSTRUCTIONS.

NOTES:

1. REFER TO PLANS FOR SIZES AND CONTINUATION.

MANUFACTURER'S

STANDARD VENT CAP

ROOF FLASHING

ROOF

INFRARED GAS HEATER

MANUFACTURER'S

STANDARD

INTAKE CAP

ROOF FLASHING

6" MIN.

DIRT LEG

GAS PIPE

THREADED CAP FITTING

UNION

GAS COCK.

PROVIDE "LOCKOUT"

ON VALVE.

NOTE:

REFER TO DRAWINGS FOR INLET AND OUTLET LINE SIZES.

ALL GAS FUELED EQUIPMENT SHALL BE PROVIDED WITH A PRESSURE

REGULATOR UNLESS IT IS PROVIDED INTEGRAL TO THE EQUIPMENT.

MEDIUM PRESSURE GAS

SUPPLIED AT 2 PSI

MAXITROL GAS

PRESSURE

REGULATOR

LOW PRESSURE GAS

SUPPLIED AT 0.5 PSI

TO EQUIPMENT

VENT LIMITER

SHEET ID

N A

T

IO

N A

L G

U A

R D

B U

R E

A U

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

F Y

P E

A -2

S

U B

M

IT

T

A P

R

P E

B -2

P

R E

-F

IN

A L

D E

S

J U

L

M-501

M E

C H

A N

IC

A

L D

E T

A

IL

S A

N D

S C

H E

D U

L E

S

T H

A

IR

L

IF

T W

IN

G

A

IR

N

A T

IO

N

A L G

U A

R D

B A

S E

S

T E

W A

R T

IN

T

E R

N A

T

IO

N A

L A

IR

P

O R

T

M A

G U

IR

E

W A

Y

N E

W B

U R

G H

N

Y

R .E

A R

L

IE

R .E

A R

L

IE

S .R

O L

L

IN

S

M

AY

S

U B

M

IT

T A

L

E N

E R

G Y

R

E P

A

IR

B U

IL

D

IN

G

W H

A Y

GAS FIRED RADIANT HEATER SCHEDULE

TAG LOCATION TYPE INPUT (MBH)

OUTPUT

(BTUH) LENGTH (FT)

ELECTRICAL VENT DIA.

(IN)

COMB AIR

DIA. (IN)

INLET PRESSURE

(IN WC)

MOUNTING HEIGHT

AFF (FT) WEIGHT (LBS) NOTESVOLTS PH. HZ.

IRH-1 105 - MAINTENANCE BAY LOW INTENSITY 60 48,000 20 120 1 60 4 4 4.6 16 86 ALL

IRH-2 104 - SUPPORT SHOP LOW INTENSITY 60 48,000 20 120 1 60 4 4 4.6 16 86 ALL

IRH-3 105 - MAINTENANCE BAY LOW INTENSITY 60 48,000 20 120 1 60 4 4 4.6 16 86 ALL

IRH-4 106 - COVERED STORAGE LOW INTENSITY 60 48,000 20 120 1 60 4 4 4.6 16 86 ALL

IRH-5 106 - COVERED STORAGE LOW INTENSITY 60 48,000 20 120 1 60 4 4 4.6 16 86 ALL

IRH-6 107 - COVERED STORAGE LOW INTENSITY 60 48,000 20 120 1 60 4 4 4.6 16 86 ALL

IRH-7 107 - COVERED STORAGE LOW INTENSITY 60 48,000 20 120 1 60 4 4 4.6 16 86 ALL

SCALE: NONEK1

INFRARED HEATER

SCALE: 1 1/2" = 1'-0"K7

BURNER TUBE INSTALLATION

DETAIL

SCALE: 1 1/2" = 1'-0"C1

TYPICAL SUSPENSION DETAILS

SCALE: 1 1/2" = 1'-0"K14

TUBE CLAMP PACKAGE

INSTALLATION DETAIL

NOTE:

1. PROVIDE PROGRAMMABLE THERMOSTATS. CONNECT THERMOSTATS TO EXISTING BAS.

2. PROVIDE DIRECT SPARK IGNITION.

3. PROVIDE STANDARD REFLECTOR.

4. PROVIDE A MINIMUM OF 6" CLEARANCE ABOVE HEATER, 63" BELOW HEATER AND 35" TO THE LEFT AND RIGHT OF HEATER.

NTS

NTS NTS NTS

SCALE: NTSC9

GAS CONNECTION TO

EQUIPMENT

B

-3 (1

) F

IN

AL

D

ES

IG

N

F

EB

S.

FO

R D

IS

SU

E

FO

R C

O N

ST

R

U C

TI

O

N

M

AY

IRH-1

IRH-3

IRH-2

IRH-1

SHEET ID

N A

T

IO

N A

L G

U A

R D

B U

R E

A U

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

F Y

P E

A -2

S

U B

M

IT

T

A P

R

P E

B -2

P

R E

-F

IN

A L

D E

S

J U

L

M-502

M E

C H

A N

IC

A

L P

H O

T O

S

T H

A

IR

L

IF

T W

IN

G

A

IR

N

A T

IO

N

A L G

U A

R D

B A

S E

S

T E

W A

R T

IN

T

E R

N A

T

IO

N A

L A

IR

P

O R

T

M A

G U

IR

E

W A

Y

N E

W B

U R

G H

N

Y

R .E

A R

L

IE

R .E

A R

L

IE

S .R

O L

L

IN

S

M

AY

S

U B

M

IT

T A

L

E N

E R

G Y

R

E P

A

IR

B U

IL

D

IN

G

W H

A Y

SCALE: 1 1/2" = 1'-0"C1

105 MAINTENANCE BAY

LOOKING WEST 1

SCALE: 1 1/2" = 1'-0"C7

105 MAINTENANCE BAY

LOOKING WEST 2

SCALE: 1 1/2" = 1'-0"C14

105 MAINTENANCE BAY

LOOKING SOUTHWEST

GENERAL SHEET NOTES

1. PHOTOS ARE PROVIDED TO SHOW AS-BUILT

CONDITIONS. ALL EXISTING MECHANICAL AND

ELECTRICAL COMPONENTS SHALL BE

PRESERVED AND PROTECTED UNLESS

OTHERWISE NOTED.

NTS NTS NTS

B

-3 (1

) F

IN

AL

D

ES

IG

N

F

EB

S.

FO

R D

M

AY

IS

SU

E

FO

R

C O

N

ST

R U

C

TI

O

IRH-7

IRH-6

IRH-7

SHEET ID

N A

T

IO

N A

L G

U A

R D

B U

R E

A U

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

F Y

P E

A -2

S

U B

M

IT

T

A P

R

P E

B -2

P

R E

-F

IN

A L

D E

S

J U

L

M-503

M E

C H

A N

IC

A

L P

H O

T O

S

T H

A

IR

L

IF

T W

IN

G

A

IR

N

A T

IO

N

A L G

U A

R D

B A

S E

S

T E

W A

R T

IN

T

E R

N A

T

IO

N A

L A

IR

P

O R

T

M A

G U

IR

E

W A

Y

N E

W B

U R

G H

N

Y

R .E

A R

L

IE

R .E

A R

L

IE

S .R

O L

L

IN

S

M

AY

S

U B

M

IT

T A

L

E N

E R

G Y

R

E P

A

IR

B U

IL

D

IN

G

W H

A Y

SCALE: 1 1/2" = 1'-0"C3

107 COVERED STORAGE

LOOKING NORTH

SCALE: 1 1/2" = 1'-0"C11

107 COVERED STORAGE

LOOKING SOUTH

GENERAL SHEET NOTES

1. PHOTOS ARE PROVIDED TO SHOW AS-BUILT

CONDITIONS. ALL EXISTING MECHANICAL AND

ELECTRICAL COMPONENTS SHALL BE

PRESERVED AND PROTECTED UNLESS

OTHERWISE NOTED.

NTS NTS

B

-3 (1

) F

IN

AL

D

ES

IG

N

F

EB

S.

FO

R D

IS

SU

E

FO

R

C O

N

ST

R U

C

TI

O N

M

AY

IRH-4

IRH-5

IRH-4

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

F Y

M-504

M E

C H

A N

IC

A

L P

H O

T O

S

T H

A

IR

L

IF

T W

IN

G

A

IR

N

A T

IO

N

A L G

U A

R D

B A

S E

S

T E

W A

R T

IN

T

E R

N A

T

IO

N A

L A

IR

P

O R

T

M A

G U

IR

E

W A

Y

N E

W B

U R

G H

N

Y

R .E

A R

L

IE

R .E

A R

L

IE

S .R

O L

L

IN

S

M

AY

S

U B

M

IT

T A

L

E N

E R

G Y

R

E P

A

IR

B U

IL

D

IN

G

W H

A Y

SCALE: 1 1/2" = 1'-0"C3

108 COVERED STORAGE

LOOKING NORTH

SCALE: 1 1/2" = 1'-0"C11

108 COVERED STORAGE

LOOKING SOUTH

GENERAL SHEET NOTES

1. PHOTOS ARE PROVIDED TO SHOW AS-BUILT

CONDITIONS. ALL EXISTING MECHANICAL AND

ELECTRICAL COMPONENTS SHALL BE

PRESERVED AND PROTECTED UNLESS

OTHERWISE NOTED.

NTS NTS

B

-3 (1

) F

IN

AL

D

ES

IG

N

F

EB

B -2

(1

) P

R E-

FI

N

AL

D

ES

IG

N

J U

LY

YP

E A-

(3

5% ) S

U

BM

IS

SI

O N

S

A

PR

S.

FO

R

D

IS

SU

E

FO

R

C O

N

ST

R U

C

TI

O N

M

AY

2) UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR SHALL SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW.

3) DDC HW ID FOR DEVICE CONTAINING EVENT ENROLLMENT OBJECT FOR REMOTE ALARMING FOR THIS SYSTEM: <_____>

Notes:

1) THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS INDICATED IN THE SPECIFICATION AND IN ACCORDANCE WITH THE POINTS SCHEDULE INSTRUCTIONS DRAWING.

OTHER POINTS IR-ALM INFRARED HEATER ALARM <___> - <___> <___> ~ ~ V V X

SYSTEM INTERNAL

FAULTS

CRIT [X] <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___>

ZN-T-SP ZONE HEATING SETPOINT <___>

65 °F (OCC) /

55 °F (UNOCC)

50 °F - 75 °F < AV > ~ OC V V X ~ ~ ~ <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___>

ZN-T-SP-ADJUST ZONE SETPOINT - ADJUSTABLE <___> - <___> < AI > ~ ~ V V X ~ ~ ~ <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___>

HTG-IR-2P

STAGED HEATING - TWO-

POSITION

<___> ~ STAGE 1 / STAGE 2 < BO > ~ ~ VO V X ~ ~ ~ <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___>

ZONE

TEMPERATURE

CONTROL

ZN-T ZONE TEMPERATURE <___> - <___> < AI > ~ ~ V V X

LOW ZONE TEMP: IF ZN-

T < (ZN-T-SP - 10 °F)

INFO [X] <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___>

GAS FIRED INFRARED RADIANT HEATERS POINTS LIST ALARMING PRIMARY POINT INFORMATION

NETWORK DATA

EXCHANGE

OVERRIDES ALARM INFORMATION

CONFIGURATION

INFORMATION

FUNCTION POINT NAME DESCRIPTION

DDC

HARDWAR

E

ID

SETTING

(WITH UNITS)

RANGE

(WITH UNITS)

IO

TYPE

HOA

REQ'D

CONFIG.

TYPE

M&C

VIEW

AND

OVRD

LDP

VIEW

AND

OVRD

TREND

REQ'D

ALARM CONDITION

(SEE NOTES)

ALARM

PRIORITY

M&C

ROUTING

OBJECT TYPE AND

INSTANCE NUMBER

(AND PROPERTY ID)

SNVT

NAME

SNVT

TYPE

NIAGARA

ID

DATA

FROM

DATA

TO

OBJECT TYPE &

INSTANCE NUMBER

OR

COMMANDABLE

SNVT

NAME

SNVT

TYPE

ALARM TYPE

(PROVIDE DDC ID FOR

REMOTE IN NOTES)

NOTIFICATION CLASS

OBJECT INSTANCE

NUMBER

START/STOP

SYS-OCC-C

SYSTEM OCCUPANCY (FROM

SYSTEM SCHEDULER)

<___> ~ OCC / UNOCC <NET-IN> ~ ~ VO ~ ~ ~ ~ ~ <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___>

SYS-OCC SYSTEM OCCUPANCY (ACTUAL) <___> ~ OCC / UNOCC <NET-OUT> ~ ~ V V X ~ ~ ~

ZN-OCC ZONE OCCUPANCY OVERRIDE <___> ~ OCCUPIED < BI > ~ OC V V X ~ ~ ~ <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___>

SHEET ID

N A

T

IO

N A

L G

U A

R D

B U

R E

A U

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

F Y

P E

A -2

S

U B

M

IT

T

A P

R

P E

B -2

P

R E

-F

IN

A L

D E

S

J U

L

M-901

M E

C H

N

IC

A L

C O

N T

R O

L S

T H

A

IR

L

IF

T W

IN

G

A

IR

N

A T

IO

N

A L G

U A

R D

B A

S E

S

T E

W A

R T

IN

T

E R

N A

T

IO

N A

L A

IR

P

O R

T

M A

G U

IR

E

W A

Y

N E

W B

U R

G H

N

Y

R .E

A R

L

IE

R .E

A R

L

IE

S .R

O L

L

IN

S

M

AY

S

U B

M

IT

T A

L

E N

E R

G Y

R

E P

A

IR

B U

IL

D

IN

G

W H

A Y

SCALE: 12" = 1'-0"A1

RADIANT HEATER CONTROLS

NTS

B

-3 (1

) F

IN

AL

D

ES

IG

N

F

EB

S.

FO

R D

IS

SU

E

FO

R

C O

N

ST

R U

C

TI

O N

M

AY

Sheets
M-001 - ABBREVIATIONS, LEGENDS, AND NOTES
M-101 - MECHANICAL FLOOR PLAN
M-501 - MECHANICAL DETAILS AND SCHEDULES
M-502 - MECHANICAL PHOTOS
M-503 - MECHANICAL PHOTOS
M-504 - MECHANICAL PHOTOS
M-901 - MECHNICAL CONTROLS

File details come from the government source that posted it. Updated .