Mechanical Bldg. 200 Energy Repairs.pdf
PDF 6 MB Posted
- Attached to
- Bldg. 200 Energy Repairs/Upgrades
- Solicitation number
- W50S8D26QA012
- Issued by
-
Department of the Army National Guard
About this file
This file is a 95% submittal design document for mechanical systems related to an energy repair project at Building 200 of the 105th Airlift Wing, Air National Guard Base, Stewart International Airport in Newburgh, New York. The project is identified by solicitation number WHAY142004 and was submitted on May 29, 2026.
The design encompasses the installation and configuration of seven gas-fired infrared radiant heaters (IRH-1 through IRH-7) distributed across maintenance bays, support shops, and covered storage areas. Each heater has a 60 MBH input capacity with 48,000 BTUH output and a 20-foot length, requiring 120V single-phase 60Hz electrical service. The heaters include 4-inch diameter combustion air inlets and vent terminations routed to the roof with manufacturer-provided caps. The project requires coordination with existing mechanical, electrical, and structural systems, including natural gas piping at various sizes (from 3/4-inch to 10-inch diameter), pressure regulators set for medium pressure (2 PSI) and low pressure (0.5 PSI) supply, and control integration with the building automation system. The design specifies compliance with UFC 4-214-02:2018, International Mechanical Code 2018, NFPA 54:2018, and IPC 2018. Control requirements include programmable thermostats, two-stage heating capability, occupancy-based scheduling, and alarming for system faults and low zone temperature conditions. All work must follow SMACNA HVAC duct construction standards, with proper flashing, support systems, and comprehensive operations and maintenance documentation required at project completion.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
U
M
CO
DP
SD
A
T
S
M
H
CO
EQUIPMENT TAG
MECHANICAL LEGEND MECHANICAL ABBREVIATIONS
NOTES:
1. THIS LEGEND IS FOR REFERENCE ONLY.
2. ALL SYMBOLS WITHIN THIS LEGEND MAY NOT APPLY TO THIS PROJECT.
DUCT SECTION, POSITIVE PRESSURE
DUCT SECTION, NEGATIVE PRESSURE
NEW DUCTWORK
FIRE DAMPER, PROVIDE ACCESS DOOR
VOLUME DAMPER
SUPPLY/INTAKE AIRFLOW DIRECTION
GRILLE OR REGISTER, SIDEWALL
LOUVER AND SCREEN
ANCHOR, INTERMEDIATE
BUTTERFLY VALVE
PRESSURE GAUGE
MANUAL AIR VENT
AUTOMATIC AIR VENT
MOTORIZED DAMPER
EMERGENCY SHUTDOWN SWITCH
HVAC - #
DUCT SIZE & SYSTEM ABBREVIATION
FIRST FIGURE IS DIMENSION SHOWN ON PLAN
FLEXIBLE DUCTWORK
DUCT TRANSITION
TURNING VANES
CEILING DIFFUSER - SUPPLY
CEILING DIFFUSER - RETURN
CEILING DIFFUSER - EXHAUST
PIPE CAP
PIPE CONNECTION, BOTTOM
PIPE CONNECTION, TOP
PIPE ELBOW, TURNED UP
PIPE ELBOW, TURNED DOWN
PIPE TEE
STRAINER VALVE
THREE-WAY CONTROL VALVE
TWO-WAY CONTROL VALVE
PUMP (SCHEMATIC)
THERMOSTAT
CARBON DIOXIDE SENSOR
20x12
SA
POINT OF DISCONNECTION
POINT OF CONNECTION
KEYED NOTE
AIR TERMINAL AND AIRFLOW TAG
DIFFERENTIAL PRESSURE SENSOR
DUCT SMOKE DETECTOR
GATE VALVE
CHECK VALVE
CD-A W X H ###
AIR QUANTITY DELIVERED
BY DEVICE IN CFM
AIR TERMINAL MARK AS
INDICATED IN SCHEDULE
MASTER EMERGENCY SHUTDOWN SWITCH
GATE VALVE
CEILING DIFFUSER - ROUND
BALL VALVE
BUTTERFLY VALVE
BRANCH DUCTWORK
RECT. TO ROUND TRANSITION
PNEUMATIC DAMPER
EXHAUST AIRFLOW DIRECTION
LINEAR SLOT DIFFUSER (DOUBLE SLOT)
BOTTOM OF DUCT ELEVATION TAGBOD: 4' - 7"
BACKDRAFT DAMPER
BD
HUMIDISTAT
CARBON MONOXIDE SENSOR
DOOR UNDERCUT
AREA OUT OF SCOPE
AREA OF DEMOLITION
Ø DIAMETER
AIR TERMINAL NECK SIZE (IN.)
SAD-#
### CFM
OR
AIR TERMINAL MARK AS INDICATED
IN SCHEDULE
AIR QUANTITY DELIVERED BY
DEVICE
SHEET ID
N A
T
IO
N A
L G
U A
R D
B U
R E
A U
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
F Y
T Y
P E
A -2
S
U B
M
IT
T A
L
A P
R
P E
B -2
P
R E
-F
IN
A L
D E
S
IG
N
J U
L
M-001
A B
B R
E V
IA
T
IO
N
S
L E
G E
N D
S
A N
D N
O T
E S
T H
A
IR
L
IF
T W
IN
G
A
IR
N
A T
IO
N
A L G
U A
R D
B A
S E
S
T E
W A
R T
IN
T
E R
N A
T
IO
N A
L A
IR
P
O R
T
M A
G U
IR
E
W A
Y
N E
W B
U R
G H
N
Y
R .E
A R
L
IE
R .E
A R
L
IE
S .R
O L
L
IN
S
M
AY
S
U B
M
IT
T A
L
E N
E R
G Y
R
E P
A
IR
B U
IL
D
IN
G
W H
A Y
DESIGN CONDITIONS FOR LOAD CALCULATIONS
SEASON OUTDOOR DESIGN CONDITIONS ELEV. (FT)
INDOOR CONDITIONS / ROOM TYPE
SHOPS
WINTER (99% DB) 4.6°F 581 55°F
(D) DEMOLITION
(E) EXISTING
(R) RELOCATED
AAV AUTOMATIC AIR VENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AP ACCESS PANEL
APD AIR PRESSURE DROP
BFF BELOW FINISHED FLOOR
BHP BRAKE HORSEPOWER
CAP CAPACITY
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CONC CONCRETE
COND CONDENSATE
CONN CONNECTION
CONT CONTINUATION
CP-1 CONTROL PANEL WITH DESIGNATION
CU CONDENSING UNIT
DB DRY BULB
DEG DEGREES
DEMO DEMOLITION
DIA DIAMETER
DN DOWN
DWG DRAWING
EA EXHAUST AIR
EAG EXHAUST AIR GRILLE
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
ENT ENTERING
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
EUH ELECTRIC UNIT HEATER
EXH EXHAUST
F FAHRENHEIT
FCU FAN COIL UNIT
FD FIRE DAMPER
FLEX FLEXIBLE
FM FLOW METER
FPM FEET PER MINUTE
GAL GALLONS
GM GAS METER
GPM GALLONS PER MINUTE
GUH GAS UNIT HEATER
HP HORSEPOWER
ID INSIDE DIAMETER/DIMENSION
IE INVERT ELEVATION
IN INCH
LAT LEAVING AIR TEMPERATURE
LVL LEVEL
LWT LEAVING WATER TEMPERATURE
M METER
MAX MAXIMUM
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
N/A NOT APPLICABLE
NG NATURAL GAS
NTS NOT TO SCALE
OA OUTDOOR AIR
OD OUTSIDE DIAMETER
OED OPEN ENDED DUCT
PD PRESSURE DROP
PSI POUNDS PER SQUARE INCH
R RADIUS
RA RETURN AIR
RAG RETURN AIR GRILLE
REFRIG REFRIGERANT
RH RADIANT HEATER
RL REFRIGERANT LIQUID LINE
RPM REVOLUTIONS PER MINUTE
SA SUPPLY AIR
SAG SUPPLY AIR GRILLE
SB SECURITY BARS
SF SUPPLY FAN
SPEC SPECIFICATION
STD STANDARD
T THERMOMETER
TA TRANSFER AIR
TBD TO BE DETERMINED
TEMP TEMPERATURE
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TYP TYPICAL
UH UNIT HEATER
VAV VARIABLE AIR VOLUME
VIF VERIFY IN FIELD
VRF VARIABLE REFRIGERANT FLOW
W WATT
WB WET BULB
WMS WIRE MESH SCREEN
APPLICABLE CODES AND STANDARDS
UNITED FACILITIES CRITERIA (UFC 4-214-02: 2018)
MECHANICAL CODE (IMC 2018)
NATIONAL FIRE PROTECTION AGENCY (NFPA) (NFPA 54: 2018)
PLUMBING CODE (IPC 2018)
NOTE: ALL APPLICABLE BUILDING CODES AND STANDARDS ARE NOT SPECIFIED HEREIN.
1. UNLESS OTHERWISE SHOWN, LOCATE ALL ROOM SENSORS AND THERMOSTATS SUCH THAT
OPERABLE PARTS ARE NO HIGHER THAN 48" ABOVE FINISHED FLOOR.
2. ALL CONTROL CONDUIT AND WIRING SHALL COMPLY WITH THE ELECTRICAL CODE AND THE
SPECIFICATIONS.
CONTROL NOTES
MECHANICAL GENERAL NOTES
1. THESE GENERAL NOTES APPLY TO ALL SHEETS. REFER TO INDIVIDUAL SHEETS FOR SHEET SPECIFIC NOTES.
2. CONTRACT DOCUMENT DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL ARRANGEMENT ONLY. DO NOT SCALE FOR MATERIAL QUANTITIES. ALL SCALING SHOULD BE REFERENCED TO
ARCHITECTURAL PLANS ONLY.
3. ALL MECHANICAL WORK SHALL BE IN STRICT COMPLIANCE WITH THE LATEST APPLICABLE EDITION OF THE INTERNATIONAL MECHANICAL AND PLUMBING CODES, APPLICABLE PROVISIONS OF THE NATIONAL FUEL GAS
CODE (NFPA 54), AND APPLICABLE UFCS (MILITARY WORK).
4. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH ALL OTHER DISCIPLINES AND AS SHOWN ON
OTHER CONTRACT DRAWINGS.
5. CONTRACTOR SHALL VISIT SITE AND VERIFY ALL EXISTING CONDITIONS AND CONNECTIONS TO EXISTING
WORK PRIOR TO BIDDING AND CONSTRUCTION.
6. COORDINATE ALL CUTTING AND PATCHING WITH GENERAL CONTRACTOR AND OTHER DISCIPLINES.
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING RELATED TO THEIR WORK.
7. ALL ATTACHMENTS TO THE BUILDING STRUCTURE SHALL BE COORDINATED WITH THE STRUCTURAL DESIGN.
ALL BRACING AND MOUNTING OF PIPES AND DUCTS SHALL MEET THE MINIMUM REQUIREMENTS OF THE MOST RECENT SMACNA HVAC DUCT CONSTRUCTION STANDARDS-METAL AND FLEXIBLE. CONTRACTOR SHALL
MAINTAIN ONE COPY OF THIS MANUAL ON SITE AT ALL TIMES.
8. PROVIDE FLASHING AND COUNTERFLASHING FOR ALL PENETRATIONS THROUGH WALLS OR ROOF TO MAKE
WATERPROOF INSTALLATION.
9. ALL MISCELLANEOUS STEEL REQUIRED TO ENSURE PROPER INSTALLATION AND AS SHOWN IN THE DETAILS FOR PIPING, DUCTWORK, AND EQUIPMENT (UNLESS OTHERWISE NOTED) SHALL BE FURNISHED AND INSTALLED
BY THE MECHANICAL CONTRACTOR.
10. AT COMPLETION OF CONSTRUCTION, CONTRACTOR SHALL PROVIDE COPIES OF BOUND OPERATIONS AND
MAINTENANCE MANUALS.
11. AT THE TIME OF ROUGH INSTALLATION AND DURING STORAGE ON THE CONSTRUCTION SITE UNTIL FINAL STARTUP OF THE HEATING, COOLING AND VENTILATING EQUIPMENT, ALL DUCT AND OTHER RELATED AIR DISTRIBUTION COMPONENT OPENINGS SHALL BE COVERED WITH TAPE, PLASTIC, SHEETMETAL OR OTHER METHODS ACCEPTABLE TO THE ENFORCING AGENCY TO REDUCE THE AMOUNT OF DUST, WATER AND DEBRIS
WHICH MAY ENTER THE SYSTEM.
GENERAL NOTES
1. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH MANUFACTURERS
RECOMMENDATIONS, CONTRACT DOCUMENTS, AND APPLICABLE CODES AND REGULATIONS.
2. WHERE TWO OR MORE ITEMS OF THE SAME TYPE OF EQUIPMENT ARE REQUIRED, THE PRODUCT OF ONE
MANUFACTURER SHALL BE USED.
3. IDENTIFY ALL NEW MECHANICAL EQUIPMENT WITH NAMEPLATES PERMANENTLY ENGRAVED PER
SPECIFICATIONS.
4. EQUIPMENT AND APPLIANCES SHALL BE ACCESSIBLE FOR SERVICE, INSPECTION, REPAIR AND REPLACEMENT WITHOUT REMOVING PERMANENT CONSTRUCTION. SUFFICIENT CLEARANCE SHALL BE MAINTAINED TO PERMIT CLEANING, REPLACEMENT OF FILTERS, BLOWERS, MOTORS, CONTROLS AND
LUBRICATION OF MOVING PARTS.
EQUIPMENT NOTES
1. ALL GAS PIPING SHALL BE LABELED AT BEGINNING, ALL ENDS, AND AT 6' INTERVALS DESIGNATING GAS
& PRESSURE. LABELS SHALL BE PER SPECIFICATIONS.
2. PROVIDE/INSTALL THROUGH WALL PIPE PENETRATIONS AS REQUIRED WHERE PIPE ENTERS BUILDING.
SLEEVE AND SEAL.
3. SUPPORT ALL PIPING SO THAT IT IS FIRMLY HELD IN PLACE BY APPROVED HANGERS AND SUPPORTS.
PIPING NOTES
TY
PE
B
-3 (1
) F
IN
AL
D
ES
IG
N
F
EB
S.
FO
R D
M
AY
IS
SU
E
FO
R
C O
N
ST
R U
C
TI
O
(E)MAU-1A(E)MUU-1
(E)F-1
(E)F-2
(E)F-3 (E)F-4 (E)F-5
(E)F-6
6"ø NG
10"ø NG8"ø NG
(E)PRV-2 (E)PRV-3(E)PRV-1
(E)VUH-4
(E)VUH-3
(E)VUH-5 (E)VUH-6 (E)VUH-7
(E)RH
(E)RH
IRH-1IRH-2IRH-3
IRH-4
IRH-5
IRH-6
IRH-7
(E)WH-1
3"ø NG3"ø NG
"ø
N G
"ø
N G
HEATED
COVERED
STORAGE
UNHEATED
COVERED
STORAGE
MAINTENANCE
BAYS
105A
SUPPORT
SHOP
MAINTENANCE
BAYS
105B
(E
(E)
2"ø NG(E)
(E)
(E)
2"ø NG(E) (E)
(E)
(E
/4
"ø N
G
3/4"ø NG
3/4"ø NG
3/4"ø NG
/4
"ø N
G
/4
"ø N
G
/4
"ø N
G
(E
/4 "ø
N G
(E) 3/4"ø NG
UP
1 2 2.5 2.6 3 4 5 6 7 8 9 10 10.1 10.5 11 12
A
B
D.1
D
E
G
J
T
T T
T T
T
T
4" OSA
4" VENT
4" OSA
4" VENT 4" OSA
4" VENT
4" OSA
4" VENT
K
4" OSA
4" VENT
L
4" OSA
4" VENT
M
4" OSA
4" VENT
4 4
SHEET ID
N A
T
IO
N A
L G
U A
R D
B U
R E
A U
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
0.5' 1' 2'
1"=1'-0"SCALE:
PLAN NORTH
F Y
P E
A -2
S
U B
M
IT
T
A P
R
P E
B -2
P
R E
-F
IN
A L
D E
S
J U
L
M-101
M E
C H
A N
IC
A
L F
L O
O R
P L
A N
T H
A
IR
L
IF
T W
IN
G
A
IR
N
A T
IO
N
A L G
U A
R D
B A
S E
S
T E
W A
R T
IN
T
E R
N A
T
IO
N A
L A
IR
P
O R
T
M A
G U
IR
E
W A
Y
N E
W B
U R
G H
N
Y
R .E
A R
L
IE
R .E
A R
L
IE
S .R
O L
L
IN
S
M
AY
S
U B
M
IT
T A
L
E N
E R
G Y
R
E P
A
IR
B U
IL
D
IN
G
W H
A Y
SCALE: 1" = 10'-0"A1
MECHANICAL FLOOR PLAN
GENERAL SHEET NOTES
1. ALL EXISTING MECHANICAL SYSTEMS SHALL
REMAIN.
2. THE CONTRACTOR SHALL MAINTAIN ALL
CLEARANCE REQUIREMENTS FOR IRHS DURING
INSTALLATION
1. RELOCATED VUH-4 AS REQUIRED TO ALLOW
CLEARANCE FOR VENT AND INTAKE DUCTWORK
FOR IRH-4.
2. MOUNT IRH AS A HIGH AS POSSIBLE WHILE
MAINTAINING A MINIMUM OF 6" CLEARANCE
ABOVE HEATER.
3. 4" COMBUSTION AIR INLET ROUTED UP TO ROOF.
TERMINATE WITH MANUFACTURER'S PROVIDED
ROOF INTAKE CAP.
4. 4" VENT ROUTED UP TO ROOF. TERMINATE WITH
MANUFACTURER'S PROVIDED ROOF VENT CAP.
KEYNOTES#
TY
PE
B
-3 (1
) F
IN
AL
D
ES
IG
N
F
EB
S.
FO
R D
IS
SU
E
FO
R C
O N
ST
R
U C
TI
O
N
M
AY
VERIFY MOUNTING
HEIGHT WITH
OWNER
TYPE B
GAS VENT
SEE DETAIL C1 FOR SUSPENSION
INSTRUCTIONS.
NOTES:
1. REFER TO PLANS FOR SIZES AND CONTINUATION.
MANUFACTURER'S
STANDARD VENT CAP
ROOF FLASHING
ROOF
INFRARED GAS HEATER
MANUFACTURER'S
STANDARD
INTAKE CAP
ROOF FLASHING
6" MIN.
DIRT LEG
GAS PIPE
THREADED CAP FITTING
UNION
GAS COCK.
PROVIDE "LOCKOUT"
ON VALVE.
NOTE:
REFER TO DRAWINGS FOR INLET AND OUTLET LINE SIZES.
ALL GAS FUELED EQUIPMENT SHALL BE PROVIDED WITH A PRESSURE
REGULATOR UNLESS IT IS PROVIDED INTEGRAL TO THE EQUIPMENT.
MEDIUM PRESSURE GAS
SUPPLIED AT 2 PSI
MAXITROL GAS
PRESSURE
REGULATOR
LOW PRESSURE GAS
SUPPLIED AT 0.5 PSI
TO EQUIPMENT
VENT LIMITER
SHEET ID
N A
T
IO
N A
L G
U A
R D
B U
R E
A U
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
F Y
P E
A -2
S
U B
M
IT
T
A P
R
P E
B -2
P
R E
-F
IN
A L
D E
S
J U
L
M-501
M E
C H
A N
IC
A
L D
E T
A
IL
S A
N D
S C
H E
D U
L E
S
T H
A
IR
L
IF
T W
IN
G
A
IR
N
A T
IO
N
A L G
U A
R D
B A
S E
S
T E
W A
R T
IN
T
E R
N A
T
IO
N A
L A
IR
P
O R
T
M A
G U
IR
E
W A
Y
N E
W B
U R
G H
N
Y
R .E
A R
L
IE
R .E
A R
L
IE
S .R
O L
L
IN
S
M
AY
S
U B
M
IT
T A
L
E N
E R
G Y
R
E P
A
IR
B U
IL
D
IN
G
W H
A Y
GAS FIRED RADIANT HEATER SCHEDULE
TAG LOCATION TYPE INPUT (MBH)
OUTPUT
(BTUH) LENGTH (FT)
ELECTRICAL VENT DIA.
(IN)
COMB AIR
DIA. (IN)
INLET PRESSURE
(IN WC)
MOUNTING HEIGHT
AFF (FT) WEIGHT (LBS) NOTESVOLTS PH. HZ.
IRH-1 105 - MAINTENANCE BAY LOW INTENSITY 60 48,000 20 120 1 60 4 4 4.6 16 86 ALL
IRH-2 104 - SUPPORT SHOP LOW INTENSITY 60 48,000 20 120 1 60 4 4 4.6 16 86 ALL
IRH-3 105 - MAINTENANCE BAY LOW INTENSITY 60 48,000 20 120 1 60 4 4 4.6 16 86 ALL
IRH-4 106 - COVERED STORAGE LOW INTENSITY 60 48,000 20 120 1 60 4 4 4.6 16 86 ALL
IRH-5 106 - COVERED STORAGE LOW INTENSITY 60 48,000 20 120 1 60 4 4 4.6 16 86 ALL
IRH-6 107 - COVERED STORAGE LOW INTENSITY 60 48,000 20 120 1 60 4 4 4.6 16 86 ALL
IRH-7 107 - COVERED STORAGE LOW INTENSITY 60 48,000 20 120 1 60 4 4 4.6 16 86 ALL
SCALE: NONEK1
INFRARED HEATER
SCALE: 1 1/2" = 1'-0"K7
BURNER TUBE INSTALLATION
DETAIL
SCALE: 1 1/2" = 1'-0"C1
TYPICAL SUSPENSION DETAILS
SCALE: 1 1/2" = 1'-0"K14
TUBE CLAMP PACKAGE
INSTALLATION DETAIL
NOTE:
1. PROVIDE PROGRAMMABLE THERMOSTATS. CONNECT THERMOSTATS TO EXISTING BAS.
2. PROVIDE DIRECT SPARK IGNITION.
3. PROVIDE STANDARD REFLECTOR.
4. PROVIDE A MINIMUM OF 6" CLEARANCE ABOVE HEATER, 63" BELOW HEATER AND 35" TO THE LEFT AND RIGHT OF HEATER.
NTS
NTS NTS NTS
SCALE: NTSC9
GAS CONNECTION TO
EQUIPMENT
B
-3 (1
) F
IN
AL
D
ES
IG
N
F
EB
S.
FO
R D
IS
SU
E
FO
R C
O N
ST
R
U C
TI
O
N
M
AY
IRH-1
IRH-3
IRH-2
IRH-1
SHEET ID
N A
T
IO
N A
L G
U A
R D
B U
R E
A U
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
F Y
P E
A -2
S
U B
M
IT
T
A P
R
P E
B -2
P
R E
-F
IN
A L
D E
S
J U
L
M-502
M E
C H
A N
IC
A
L P
H O
T O
S
T H
A
IR
L
IF
T W
IN
G
A
IR
N
A T
IO
N
A L G
U A
R D
B A
S E
S
T E
W A
R T
IN
T
E R
N A
T
IO
N A
L A
IR
P
O R
T
M A
G U
IR
E
W A
Y
N E
W B
U R
G H
N
Y
R .E
A R
L
IE
R .E
A R
L
IE
S .R
O L
L
IN
S
M
AY
S
U B
M
IT
T A
L
E N
E R
G Y
R
E P
A
IR
B U
IL
D
IN
G
W H
A Y
SCALE: 1 1/2" = 1'-0"C1
105 MAINTENANCE BAY
LOOKING WEST 1
SCALE: 1 1/2" = 1'-0"C7
105 MAINTENANCE BAY
LOOKING WEST 2
SCALE: 1 1/2" = 1'-0"C14
105 MAINTENANCE BAY
LOOKING SOUTHWEST
GENERAL SHEET NOTES
1. PHOTOS ARE PROVIDED TO SHOW AS-BUILT
CONDITIONS. ALL EXISTING MECHANICAL AND
ELECTRICAL COMPONENTS SHALL BE
PRESERVED AND PROTECTED UNLESS
OTHERWISE NOTED.
NTS NTS NTS
B
-3 (1
) F
IN
AL
D
ES
IG
N
F
EB
S.
FO
R D
M
AY
IS
SU
E
FO
R
C O
N
ST
R U
C
TI
O
IRH-7
IRH-6
IRH-7
SHEET ID
N A
T
IO
N A
L G
U A
R D
B U
R E
A U
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
F Y
P E
A -2
S
U B
M
IT
T
A P
R
P E
B -2
P
R E
-F
IN
A L
D E
S
J U
L
M-503
M E
C H
A N
IC
A
L P
H O
T O
S
T H
A
IR
L
IF
T W
IN
G
A
IR
N
A T
IO
N
A L G
U A
R D
B A
S E
S
T E
W A
R T
IN
T
E R
N A
T
IO
N A
L A
IR
P
O R
T
M A
G U
IR
E
W A
Y
N E
W B
U R
G H
N
Y
R .E
A R
L
IE
R .E
A R
L
IE
S .R
O L
L
IN
S
M
AY
S
U B
M
IT
T A
L
E N
E R
G Y
R
E P
A
IR
B U
IL
D
IN
G
W H
A Y
SCALE: 1 1/2" = 1'-0"C3
107 COVERED STORAGE
LOOKING NORTH
SCALE: 1 1/2" = 1'-0"C11
107 COVERED STORAGE
LOOKING SOUTH
GENERAL SHEET NOTES
1. PHOTOS ARE PROVIDED TO SHOW AS-BUILT
CONDITIONS. ALL EXISTING MECHANICAL AND
ELECTRICAL COMPONENTS SHALL BE
PRESERVED AND PROTECTED UNLESS
OTHERWISE NOTED.
NTS NTS
B
-3 (1
) F
IN
AL
D
ES
IG
N
F
EB
S.
FO
R D
IS
SU
E
FO
R
C O
N
ST
R U
C
TI
O N
M
AY
IRH-4
IRH-5
IRH-4
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
F Y
M-504
M E
C H
A N
IC
A
L P
H O
T O
S
T H
A
IR
L
IF
T W
IN
G
A
IR
N
A T
IO
N
A L G
U A
R D
B A
S E
S
T E
W A
R T
IN
T
E R
N A
T
IO
N A
L A
IR
P
O R
T
M A
G U
IR
E
W A
Y
N E
W B
U R
G H
N
Y
R .E
A R
L
IE
R .E
A R
L
IE
S .R
O L
L
IN
S
M
AY
S
U B
M
IT
T A
L
E N
E R
G Y
R
E P
A
IR
B U
IL
D
IN
G
W H
A Y
SCALE: 1 1/2" = 1'-0"C3
108 COVERED STORAGE
LOOKING NORTH
SCALE: 1 1/2" = 1'-0"C11
108 COVERED STORAGE
LOOKING SOUTH
GENERAL SHEET NOTES
1. PHOTOS ARE PROVIDED TO SHOW AS-BUILT
CONDITIONS. ALL EXISTING MECHANICAL AND
ELECTRICAL COMPONENTS SHALL BE
PRESERVED AND PROTECTED UNLESS
OTHERWISE NOTED.
NTS NTS
B
-3 (1
) F
IN
AL
D
ES
IG
N
F
EB
B -2
(1
) P
R E-
FI
N
AL
D
ES
IG
N
J U
LY
YP
E A-
(3
5% ) S
U
BM
IS
SI
O N
S
A
PR
S.
FO
R
D
IS
SU
E
FO
R
C O
N
ST
R U
C
TI
O N
M
AY
2) UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR SHALL SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW.
3) DDC HW ID FOR DEVICE CONTAINING EVENT ENROLLMENT OBJECT FOR REMOTE ALARMING FOR THIS SYSTEM: <_____>
Notes:
1) THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS INDICATED IN THE SPECIFICATION AND IN ACCORDANCE WITH THE POINTS SCHEDULE INSTRUCTIONS DRAWING.
OTHER POINTS IR-ALM INFRARED HEATER ALARM <___> - <___> <___> ~ ~ V V X
SYSTEM INTERNAL
FAULTS
CRIT [X] <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___>
ZN-T-SP ZONE HEATING SETPOINT <___>
65 °F (OCC) /
55 °F (UNOCC)
50 °F - 75 °F < AV > ~ OC V V X ~ ~ ~ <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___>
ZN-T-SP-ADJUST ZONE SETPOINT - ADJUSTABLE <___> - <___> < AI > ~ ~ V V X ~ ~ ~ <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___>
HTG-IR-2P
STAGED HEATING - TWO-
POSITION
<___> ~ STAGE 1 / STAGE 2 < BO > ~ ~ VO V X ~ ~ ~ <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___>
ZONE
TEMPERATURE
CONTROL
ZN-T ZONE TEMPERATURE <___> - <___> < AI > ~ ~ V V X
LOW ZONE TEMP: IF ZN-
T < (ZN-T-SP - 10 °F)
INFO [X] <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___>
GAS FIRED INFRARED RADIANT HEATERS POINTS LIST ALARMING PRIMARY POINT INFORMATION
NETWORK DATA
EXCHANGE
OVERRIDES ALARM INFORMATION
CONFIGURATION
INFORMATION
FUNCTION POINT NAME DESCRIPTION
DDC
HARDWAR
E
ID
SETTING
(WITH UNITS)
RANGE
(WITH UNITS)
IO
TYPE
HOA
REQ'D
CONFIG.
TYPE
M&C
VIEW
AND
OVRD
LDP
VIEW
AND
OVRD
TREND
REQ'D
ALARM CONDITION
(SEE NOTES)
ALARM
PRIORITY
M&C
ROUTING
OBJECT TYPE AND
INSTANCE NUMBER
(AND PROPERTY ID)
SNVT
NAME
SNVT
TYPE
NIAGARA
ID
DATA
FROM
DATA
TO
OBJECT TYPE &
INSTANCE NUMBER
OR
COMMANDABLE
SNVT
NAME
SNVT
TYPE
ALARM TYPE
(PROVIDE DDC ID FOR
REMOTE IN NOTES)
NOTIFICATION CLASS
OBJECT INSTANCE
NUMBER
START/STOP
SYS-OCC-C
SYSTEM OCCUPANCY (FROM
SYSTEM SCHEDULER)
<___> ~ OCC / UNOCC <NET-IN> ~ ~ VO ~ ~ ~ ~ ~ <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___>
SYS-OCC SYSTEM OCCUPANCY (ACTUAL) <___> ~ OCC / UNOCC <NET-OUT> ~ ~ V V X ~ ~ ~
ZN-OCC ZONE OCCUPANCY OVERRIDE <___> ~ OCCUPIED < BI > ~ OC V V X ~ ~ ~ <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___> <___>
SHEET ID
N A
T
IO
N A
L G
U A
R D
B U
R E
A U
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
F Y
P E
A -2
S
U B
M
IT
T
A P
R
P E
B -2
P
R E
-F
IN
A L
D E
S
J U
L
M-901
M E
C H
N
IC
A L
C O
N T
R O
L S
T H
A
IR
L
IF
T W
IN
G
A
IR
N
A T
IO
N
A L G
U A
R D
B A
S E
S
T E
W A
R T
IN
T
E R
N A
T
IO
N A
L A
IR
P
O R
T
M A
G U
IR
E
W A
Y
N E
W B
U R
G H
N
Y
R .E
A R
L
IE
R .E
A R
L
IE
S .R
O L
L
IN
S
M
AY
S
U B
M
IT
T A
L
E N
E R
G Y
R
E P
A
IR
B U
IL
D
IN
G
W H
A Y
SCALE: 12" = 1'-0"A1
RADIANT HEATER CONTROLS
NTS
B
-3 (1
) F
IN
AL
D
ES
IG
N
F
EB
S.
FO
R D
IS
SU
E
FO
R
C O
N
ST
R U
C
TI
O N
M
AY
| Sheets |
| M-001 - ABBREVIATIONS, LEGENDS, AND NOTES |
| M-101 - MECHANICAL FLOOR PLAN |
| M-501 - MECHANICAL DETAILS AND SCHEDULES |
| M-502 - MECHANICAL PHOTOS |
| M-503 - MECHANICAL PHOTOS |
| M-504 - MECHANICAL PHOTOS |
| M-901 - MECHNICAL CONTROLS |
File details come from the government source that posted it. Updated .