Electrical Bldg. 200 Energy Repairs.pdf
PDF 284 KB Posted
- Attached to
- Bldg. 200 Energy Repairs/Upgrades
- Solicitation number
- W50S8D26QA012
- Issued by
-
Department of the Army National Guard
About this file
This is a set of electrical construction drawings and specifications for a federal facility renovation project under Air Force contract FA8903-21-D-0013. The solicitation was issued on 29 May 2026, with design milestones including a Type A-2 (35%) Submittal due 10 April 2024, Type B-2 (100%) Pre-Final Design due 18 July 2025, and Type B-3 (100%) Final Design due 26 February 2026.
The electrical work encompasses comprehensive building systems including power distribution, lighting, GFCI-protected receptacles, fire-rated wall penetrations, emergency lighting with battery backup, arc flash hazard labeling, conduit systems, and mechanical equipment connections. All work must be performed by certified electricians in compliance with local, state, and federal codes. Key specifications require coordination with other disciplines, field adjustment of fixtures to avoid structural elements, recessed electrical boxes offset minimum 2 feet in fire-rated walls, flexible metallic conduit for final mechanical equipment connections, and mounting of fixtures over 31 pounds using rigid or flexible support systems. The drawings include an electrical power plan, existing one-line diagram, equipment connection schedules for multiple branch panels (WDP, PP1, RP), cable schedules with conductor specifications, and disconnect information. The project includes a 50 kW portable generator with 480/277 three-phase capability and associated weatherproof receptacles rated 200 amperes at 600 VAC.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ES ES
E E
G G
ES ES
E E
LP LP
ELECTRICAL SYMBOLS LEGEND
RECEPTACLE, WALL MOUNTED, DUPLEX, 20A, 125V, 18" AFF TO CENTER OF DEVICE UON
RECEPTACLE, GFCI PROTECTION, WEATHERPROOF WHILE IN USE COVER
RECEPTACLE, GFCI PROTECTION
RECEPTACLE, WALL MOUNTED AT 48" HEIGHT TO CENTER OF DEVICE 48"
RECEPTACLE, CORD REEL MOUNTED, DUPLEX, REEL TO BE 30' IN LENGTH
RECEPTACLE, WALL MOUNTED, QUADRULEX, 20A, 125V, 18" AFF TO CENTER OF DEVICE
UON
RECEPTACLE, SPECIAL PURPOSE, TYPE NOTED ON PLANS
MOTOR STARTER & DISCONNECT SWITCH, FUSIBLE 30/25/3R/1 INDICATES 30A 25A
FUSED, NEMA 3R NEMA MOTOR STARTER TYPE 1
DISCONNECT SWITCH, FUSIBLE 3/30/25 INDICATES 3P 30A 25A FUSE, NEMA 3R
DISCONNECT SWITCH, NON-FUSIBLE 3/30 INDICATES 3P 30A, NEMA 3R
MOTOR RATED SWITCH
JUNCTION BOX
PANELBOARD. DASHED LINES REPRESENT REQUIRED CLEARANCE.
BRANCH CIRCUIT, CONCEALED ABOVE CEILING OR IN WALL WHERE POSSIBLE,
WHERE EXPOSED ROUTE PARALLEL OR PERPENDICULAR TO STRUCTURE.
BRANCH CIRCUIT, UNDERGROUND OR CONCEALED BELOW SLAB.
BRANCH CIRCUIT, HOMERUN, A20 MIN UON
3/30/25/3R
3/30/NF/3R
30/25/3R/1
M
CONTROL SWITCH FOR MOTORS
GROUND BUS BAR
PROVIDE ELECTRICAL CONNECTION TO EQUIPMENT FURNISHED BY OTHERS, SEE
MECHANICAL EQUIPMENT CONNECTION SCHEDULE
GROUND ROD
GROUND ROD TEST WELL
BONDING CLAMP
UNDERGROUND GROUND CONDUCTOR
UNDERGROUND ELECTRICAL SECONDARY CONDUCTOR
PAD MOUNT TRANSFORMER
RECEPTACLE, MOUNTED IN CEILING OR AT STRUCTURE (WHICHEVER IS LOWER),
DUPLEX, 20A, 125V
HIGH VOLTAGE SWITCH
STATIC GROUNDING POINT GROUND MOUNTED
METER
POWER/DATA/AV FLOOR BOX, FLUSH FLOOR MOUNTED, 4 REPRESENTS QUANTITY OF
COMPARTMENTS
UNDERGROUND ELECTRICAL PRIMARY CONDUCTOR
OVERHEAD ELECTRICAL PRIMARY CONDUCTOR
AIR TERMINAL
TRANSFORMER
RECEPTACLE, TAMPER-RESISTANT
OVERHEAD ELECTRICAL SECONDARY CONDUCTOR
POWER/DATA/TV/AV WALL BOX, FLUSH WALL MOUNTED, 3 REPRESENTS QUANTITY OF
COMPARTMENTS
S
E
G
J
TV
FB
RECEPTACLE, 50% SWITCHED
RECEPTACLE, 100% SWITCHED
RECEPTACLE, AFCI PROTECTION
RECEPTACLE, FLUSH FLOOR MOUNTED, QUADRUPLEX, 20A, 125V
JUNCTION BOX, WALL MOUNTED, RECESSED, 18" AFF TO CENTER OF DEVICE UONJ
JUNCTION BOX, WALL MOUNTED WITH MODULAR FURNITURE WHIP, 18" AFF TO
CENTER OF DEVICE UON
J
RECEPTACLE, FLUSH FLOOR MOUNTED, DUPLEX, 20A, 125V
UFER GROUND
LIGHTNING PROTECTION CONDUCTOR
ENCLOSED CIRCUIT BREAKER, 3/30/3R INDICATES 3P 30A TRIP, NEMA 3R3/30/3R C
RECEPTACLE, WALL MOUNTED, SIMPLEX, 20A, 125V, 18" AFF TO CENTER OF DEVICE UON
A
RECEPTACLE, CORD REEL WALL MOUNTED, DUPLEX, REEL TO BE 30' IN LENGTH
SHEET ID
N
AT
IO
N
AL
G
U
AR
D B
U R
EA
U
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FY
TY
PE
A
-2 (3
5% ) S
U
BM
IT
TA
L
A
PR
TY
PE
B -2
(1
) P
R E-
FI
N
AL
D
ES
IG
N
J U
L
E-001
LE
G
EN
D
,A
BB
R
EV
IA
TI
O N
S, A
N D
N O
TE
S
5T
H A
IR
LI
FT
W
IN
G
, A
IR
N
AT
IO
N
AL
G
U
AR
D B
AS
E, S
TE
W
AR
T
IN
TE
R
N
AT
IO
N
AL
A
IR
PO
R T, M
AG
U
IR
E W
AY
, N
EW
G
U R
G H
, N Y
M
AG
U
IR
E W
AY
N
EW
BU
R G
H , N
Y
J.
H
AR
LA
N
R .B
AR
N
AR
D
S.
FO
R D
J.
H
O O
VE
R
M
AY
FA
-2
1- D
-0
0%
S U
BM
IT
TA
L
EN
ER
G Y:
R
EP
AI
R
B U
IL
D
IN
G
W H
AY
SHEET NOTES
1. ALL WORK SHALL BE PERFORMED BY CERTIFIED ELECTRICIANS OR UNDER THE
SUPERVISION OF A CERTIFIED ELECTRICIAN. ELECTRICIAN SHALL BE LICENSED
IN ACCORDANCE WITH LOCAL, STATE, AND FEDERAL GOVERNING AUTHORITIES.
2. REFER TO THE APPROPRIATE DRAWING FOR THE EXACT LOCATION OF
EQUIPMENT INSTALLED UNDER DIVISIONS OF THE DOCUMENTS WHICH
REQUIRE ELECTRICAL SERVICE.
3. FIELD ADJUST LIGHT FIXTURES UP TO 3' MAX TO CLEAR ANY BEAMS, COLUMNS,
MECHANICAL EQUIPMENT, PIPING, ETC.
4. VERIFY DOOR SWINGS WITH ARCHITECTURAL PLANS AND MANUFACTURER
SHOP DRAWINGSLOCATE LIGHT SWITCHES ON JAMB SIDE OF DOOR, WHERE
POSSIBLE.
5. FIXTURE FINISHES SHALL BE COORDINATED WITH CONTRACTING OFFICER.
6. RECESSED ELECTRICAL BOXES SHALL BE OFFSET 2'-0" MINIMUM IN FIRE RATED
WALLS. COORDINATE WITH CONTRACTING OFFICER FOR LOCATION AND TYPES
OF FIRE RATED WALLS.
7. PENETRATIONS THROUGH FIRE RATED WALLS SHALL BE FIRE STOPPED BY A UL
APPROVED FIRE STOP SYSTEM.
8. ELECTRICAL WORK SHALL CONFORM WITH ALL LOCALLY, STATE, AND
FEDERALLY ADOPTED CODES, REGULATIONS, AND STANDARDS.
9. MECHANICAL EQUIPMENT IS INDICATED ON POWER PLANS FOR LOCATION
REFERENCE ONLY. REFER TO MECHANICAL EQUIPMENT SCHEDULE FOR
SPECIFIC WIRING, DISCONNECT, AND CONTROLS REQUIREMENTS.
10. PROVIDE FINAL ELECTRICAL CONNECTION TO MECHANICAL EQUIPMENT USING
FLEXIBLE METALLIC CONDUIT.
11. THE CONTRACTOR SHALL BECOME FAMILIAR WITH ALL OTHER DISCIPLINE
DRAWINGS AND SPECIFICATIONS DRAWINGS PRIOR TO THE INSTALLATION OF
THE ELECTRICAL SYSTEMS.
12. PROVIDE GFCI PROTECTED RECEPTACLES AT THE FOLLOWING LOCATIONS:
A. BUILDING EXTERIOR.
B. WITHIN 6' OF A SINK AND WATER FOUNTAINS.
C. SERVING VENDING MACHINES
D. LATRINES, SHOWER ROOMS, LOCKER ROOMS, KITCHENS, MECHANICAL
ROOMS, FIRE PUMP ROOMS, ELECTRICAL ROOMS, AND GARAGES.
13. RECEPTACLE AND SWITCH BOXES SHALL BE ROUGHED IN FLUSH WITH WALL
SURFACE, UON.
14. PROVIDE SUPPORTS AS REQUIRED FOR ALL ELECTRICAL SYSTEMS. MOUNT ALL
OVERHEAD UTILITIES AND OTHER FIXTURES WEIGHING 31LBS OR MORE USING
EITHER RIGID OR FLEXIBLE SYSTEMS.
15. COORDINATE EXACT MOUNTING LOCATION OF SERVICE RECEPTACLES,
DISCONNECTS, AND STARTERS FOR MECHANICAL AND OWNER FURNISHED
EQUIPMENT IN FIELD WITH EQUIPMENT INSTALLER BEFORE ROUGH-IN. INSTALL
AS INDICATED ON THE EQUIPMENT CONNECTION SCHEDULE, WHETHER OR NOT
EXPLICITLY SHOWN ON FLOOR PLANS. DO NOT INSTALL DEVICES WHERE
LOCATION IMPEDES REQUIRED EQUIPMENT CLEARANCES AND SERVICE
ACCESS POINTS.
16. EXIT SIGNS SHALL BE CIRCUITED AHEAD OF ANY LIGHTING CONTROLS.
17. EMERGENCY LIGHTING FIXTURES WITH BATTERY BACK-UP UNITS SHALL BE
PROVIDED WITH AN UNSWITCHED CONDUCTOR.
18. PROVIDE JUNCTION BOXES AS INDICATED ON PLANS AND WHERE REQUIRED..
19. DISCONNECT SWITCHES FOR MECHANICAL EQUIPMENT SHALL BE MOUNTED TO
THE STRUCTURE, NOT TO THE EQUIPMENT.
20. LABEL RECEPTACLES AND LINES VOLTAGE SWITCHES WITH PANEL NAME AND
CIRCUIT NUMBER(S).
21. CONDUITS LEAVING OR ENTERING BUILDING SHALL BE SEALED TO PREVENT
ENTRANCE OF MOISTURE.
22. PROVIDE ARC FLASH HAZARD WARNING LABELS ON ELECTRICAL EQUIPMENT.
LABELS SHALL BE LOCATED SO AS TO BE CLEARLY VISIBLE TO QUALIFIED
PERSONS BEFORE EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE
OF EQUIPMENT. LABEL TEMPLATES MAY BE OBTAINED FROM WBDG UFC
3-560-01.
23. BRANCH CONDUITS SHALL BE RUN HIGH AND TIGHT TOGETHER WHEN
FEASIBLE, UON.
24. ELECTRICAL LEGEND IS GENERIC AND NOT ALL ITEMS MAY BE USED.
25. SPECIAL CARE SHALL BE TAKEN TO AVOID DAMAGING EXISTING UTILITIES
(WATER, SEWER, POWER, GAS, COMMUNICATIONS, ETC.) DURING DEMOLITION
AND CONSTRUCTION. CONTRACTOR SHALL BE RESPONSIBLE FOR IDENTIFYING
AND LOCATING ALL EXISTING SITE UTILITIES (OVERHEAD & UNDERGROUND) IN
THE AREA OF EXCAVATION AND/OR DRILLING. CONTRACTOR MUST CONTACT
MISS DIG SYSTEM, INC. BY PHONE AT 811 OR VIA THE WEB A MINIMUM OF 3
BUSINESS DAY PRIOR TO EXCAVATING AND/OR DRILLING, EXCLUDING
WEEKENDS AND HOLIDAYS. NO ADDITIONAL COMPENSATION SHALL BE GIVEN
FOR REPAIRS REQUIRED FOR ANY INCURRED DAMAGES, WHICH MIGHT BE
CAUSED BY THE CONTRACTOR'S FAILURE TO EXACTLY LOCATE AND PRESERVE
ANY AND ALL UNDERGROUND UTILITIES. SUCH DAMAGES (IF HAPPENED) SHALL
BE REPAIRED IMMEDIATELY TO RESUME SERVICES WITH MINIMAL OUTAGES
AND AT NO ADDITIONAL COST TO THE GOVERNMENT.
26. WHERE POWER CABLES ARE NOT ROUTED IN CABLE TRAY, REFER TO CABLE
SCHEDULE FOR CONDUIT SIZE. CABLES IN CABLE TRAY DO NOT NEED TO BE
ROUTED IN CONDUIT.
27. PROVIDE FIRE ALARM INTERFACE FOR EMERGENCY LIGHTING AS INDICATED.
28. PROVIDE ALL FIRE ALARM AND FIRE PROTECTION SYSTEMS WITH CIRCUIT
BREAKERS LOCKABLE IN THE "ON" POSITION AND RED IN COLOR.
29. EXTERIOR DEVICES AND EQUIPMENT SHALL BE NEMA 3R RATED, UON.
30. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING WIRING, CABLING,
CONDUIT, AND ANY ANCILLARY EQUIPMENT INCLUDING PROGRAMMING OF
LIGHTING CONTROL SYSTEM. THE INSTALLATION SHALL BE TESTED BY AN
REPRESENTATIVE OF THE LIGHTING CONTROL SYSTEM MANUFACTURER AFTER
INSTALLATION. THE REPRESENTATIVE SHALL CERTIFY THAT THE LIGHTING
CONTROL SYSTEM IS INSTALLED AND TESTED TO THEIR FULL SATISFACTION.
31. LEADS BETWEEN SPD AND ASSOCIATED BREAKER SHALL NOT EXCEED 36". SPD
MUST BE LOCATED IN A SEPERATE ENCLOSURE FROM THEIR ASSOCIATED
PANELS.
ABBREVIATIONS
# NUMBER
' FEET
'' INCHES
° DEGREES
Ø DIAMETER
Φ PHASE
A AMPERE
ACP ACCESS CONTROL PANEL
ACS ACCESS CONTROL SYSTEM
ADJ ADJUSTABLE
AFCI ARC FAULT CIRCUIT INTERUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AL ALUMINUM
ALT ALTERNATIVE
AMRS ADVANCED METER READING SYSTEM
ANN ANNUNCIATOR
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILLARY
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BC BELOW COUNTER
BCG BARE COPPER GROUNDING/BONDING CONDUCTOR
BCT BONDING CONDUCTOR FOR TELECOMMUNICATIONS
BLDG BUILDING
BOCT BOTTOM OF CABLE TRAY
C CONDUIT
CAT CATEGORY
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCT CORRELATED COLOR TEMPERATURE
cd CANDELA RATING
CFCI CONTRACTOR FURNISHED, CONTRACTOR INSTALLED
CFGI CONTRACTOR FURNISHED, GOVERNMENT INSTALLED
CH COUNTER HEIGHT
CKT CIRCUIT
CLG CEILING
CMU CONCRETE MASONRY UNIT
COMM COMMUNICATION
CONN CONNECTED
COR CONTRACTING OFFICER
CP CONTROL PANEL
CRI COLOR RENDERING INDEX
CTB COMPUTER TERMINAL BACKBOARD
CTRL CONTROL/CONTROLLER
CU COPPER
(D) DEMOLISH
DACT DIGITAL ALARM COMMUNICATOR TRANSMITTER
dBA DECIBEL LEVEL
DDC DIRECT DIGITAL CONTROL
DMU DIGITAL METERING UNIT
DP DISTRIBUTION PANELBOARD
DS DISCONNECT
DWG DRAWING
(E) EXISTING DEVICE
EC ELECTRICAL CONTRACTOR
ECU ENERGY CONTROL UNIT
EF ENTRANCE FACILITY
EGB ELECTRIC GROUND BAR
EIA ELECTRONIC INDUSTRIES ALLIANCE
ELCU EMERGENCY LIGHTING CONTROL UNIT
ELEC ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
ENT ELECTRICAL NONMETALLIC TUBING
EPA ENVIRONMENTAL PROTECTION AGENCY
ESS ELECTRONIC SECURITY SYSTEM
EST ESTIMATED
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EX EXISTING DEVICE
EXT EXTERIOR
F FAHRENHEIT
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATION PANEL
FACP FIRE ALARM CONTROL PANEL
FDU FIBER DISTRIBUTION UNIT
FL FLOOR
FLA FULL LOAD AMPERES
FLR FLOOR
FMC FLEXIBLE METALLIC CONDUIT
FMCP FIRE ALARM & MASS NOTIFICATION CONTROL PANEL
FO FIBER OPTIC
FOPP FIBER OPTIC PATCH PANEL
FOV FIELD OF VIEW
FP FIRE PUMP
FPC FIRE PUMP CONTROLLER
FT FEET
FTU FAN TERMINAL UNIT
GC GENERAL CONTRACTOR
GE GROUNDING EQUALIZER
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER /
GOVERNMENT FURNISHED, CONTRACTOR INSTALLED
GFGI GOVERNMENT FURNISHED, GOVERNMENT INSTALLED
GFP GROUND FAULT PROTECTION
GND GROUND
HC HEATING, VENTILATION, AND AIR CONDITIONING
CONTRACTOR
HH HANDHOLE
HP HORSEPOWER
ABBREVIATIONS
HT HEIGHT
HVAC HEATING, VENTILATION, AND AIR CONDITIONING
HZ HERTZ
I/O INPUT/OUTPUT
IAW IN ACCORDANCE WITH
ID IDENTIFICATION, INSIDE DIAMETER
IDP INTRUSION DETECTION PANEL
IDS INTRUSION DETECTION SYSTEM
IEEE INSTITUTE OF ELECTRICAL AND ELECTRONIC
ENGINEERS
IG ISOLATED GROUND
IMC INTERMEDIATE METALLIC CONDUIT
IR IMPACT RESISTANT
ISP INSIDE PLANT
IT INFORMATION TECHNOLOGY
ITN INFORMATION TRANSFER NODE
JACE JAVA APPLICATION CONTROL ENGINE
JB/JBOX JUNCTION BOX
JP JOCKEY PUMP
JPC JOCKEY PUMP CONTROLLER
K KELVIN
KAIC KILOAMP INTERRUPTING CAPACITY
KCMIL THOUSAND CIRCULAR MILS
KV KILOVOLT
KVA KILOVOLT-AMPERE
KW KILOWATT
KWH KILOWATT-HOUR
LB POUND
LC LUCENT CONNECTOR
LCU LIGHTING CONTROL UNIT
LFMC LIQUIDTIGHT FLEXIBLE METAL CONDUIT
LFNC LIQUIDTIGHT FLEXIBLE NON-METALLIC CONDUIT
LI LONG TIME AND INSTANTANEOUS
LIU LIGHT INTERFACE UNIT
LLF LIGHT LOSS FACTOR
LM LUMEN
LMC LIQUIDTIGHT METAL CONDUIT
LPS LIGHTNING PROTECTION SYSTEM
LPW LUMEN PER WATT
LSI LONG TIME, SHORT TIME, AND INSTANTANEOUS
LSIG LONG TIME, SHORT TIME, INSTANTANEOUS, AND
GROUND FAULT
LTG LIGHTING
m METERS
MAX MAXIMUM
MC MECHANICAL CONTRACTOR/METAL-CLAD
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCP MAIN CONTROL PANEL
MECH MECHANICAL
MEZZ MEZZANINE
MGB MAIN GROUND BAR
MIN MINIMUM
MLO MAIN LUGS ONLY
MM MULTI-MODE
mm MILLIMETERS
MNS MASS NOTIFICATION SYSTEM
MOD MOTOR OPERATED DAMPER
MOV METAL-OXIDE-VARISTOR
MPZ MINI POWER ZONE
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
N NEUTRAL
N/A, NA NOT APPLICABLE
NAC NOTIFICATION APPLIANCE CIRCUIT
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NF NON-FUSED
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OE OVERHEAD ELECTRICAL
OFCI OWNER FURNISHED, CONTRACTOR INSTALLED
OFOI OWNER FURNISHED, OWNER INSTALLED
OH OVERHEAD
OHD OVERHEAD DOOR
OSHA OCCUPATIONAL SAFETY AND HEALTH
ADMINISTRATION
OSP OUTSIDE PLANT
OT OVERHEAD TELECOMMUNICATIONS
P POLE(S)
PA PUBLIC ADDRESS
PAS PUBLIC ADDRESS SYSTEM
PB PULL BOX
PBB PRIMARY BONDING BUSBAR
PC PLUMBING CONTRACTOR/PERSONAL COMPUTER
PCB POLYCHLORINATED BIPHENYLS
PCU PREMISES CONTROL UNIT
PDS PROTECTED DISTRIBUTION SYSTEM
PDU POWER DISTRIBUTION UNIT
PF POWER FACTOR
PH PHASE
PLC PROGRAMMABLE LOGIC CONTROLLER
PNL PANEL
POE POWER OVER ETHERNET
POTS PLAIN OLD TELEPHONE SYSTEM
PP PATCH PANEL
PRI PRIMARY
PS POWER SUPPLY
PV PHOTOVOLTAIC
ABBREVIATIONS
PVC POLYVINYL-CHLORIDE
(R) RELOCATE
RBB RACK BONDING BUSBAR
RCP REFLECTED CEILING PLAN
RE RELOCATED/REQUEST TO EXIT
REC RECEPTACLE
REQ REQUIRED
REV REVISION
RF RADIO-FREQUENCY
RGS RIGID STEEL CONDUIT
RM ROOM
RMC RIGID METALLIC CONDUIT
RNC RIGID NON-METALLIC CONDUIT
RO REVERSE OSMOSIS
RPS REMOTE POWER SUPPLY
RSC RIGID GALVANIZED STEEL CONDUIT
RSFACU RELEASING SERVICE FIRE ALARM CONTROL UNIT
RT REMOTE TRANSMITTER
RU RACK UNIT
RX REQUEST TO EXIT
SBB SECONDARY BONDING BUSBAR
SC SHORT-CIRCUIT/SQUARE CONNECTOR
SCCR SHORT-CIRCUIT CURRENT RATING
SE SERVICE ENTRANCE
SEC SECONDARY
SECT SECTION
SER SERVICE ENTRANCE RATED
SF SQUARE FEET
SM SINGLE MODE
SN SOLID NEUTRAL
SPD SURGE PROTECTION DEVICE
SPEC SPECIFICATION(S)
ST STRAIGHT TIP
STP SHIELDED TWISTED PAIR
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TBB TELECOMMUNICATIONS BONDING BACKBONE
TE TELECOMMUNICATIONS ENCLOSURE
TEBC TELECOMMUNICATIONS EQUIPMENT BONDING
CONDUCTOR
TELE TELEPHONE
TER TELECOMMUNICATIONS EQUIPMENT ROOM
TIA TELECOMMUNICATIONS INDUSTRY ASSOCIATION
TOCT TOP OF CABLE TRAY
TR TELECOMMUNICATIONS ROOM
TTB TELEPHONE TERMINAL BACKBOARD
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION
TX TRANSMIT
TYP TYPICAL
UFCI UTILITY FUNDED CONTRACTOR INSTALLED
UFUI UTILITY FUNDED UTILITY INSTALLED
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITERS LABORATORIES
UMCS UTILITY MANAGEMENT CONTROL SYSTEM
UON UNLESS OTHERWISE NOTED
UPC ULTRA-PHYSICAL CONTACT
UPS UNINTERRUPTIBLE POWER SUPPLY
UTP UNSHIELDED TWISTED PAIR
V VOLTAGE
VA VOLT AMPERE
VFD VARIABLE FREQUENCY DRIVE
VSD VARIABLE SPEED DRIVE
W WATT
W/ WITH
WAP WIRELESS ACCESS POINT
WID WIRELESS INTRUSION DEVICE
WKST WORKSTATION
WP WEATHERPROOF
XFMR TRANSFORMER
DEMOLITION SHEET NOTES
1. DEMOLITION DRAWINGS INDICATE GENERAL DEMOLITION SCOPE AND INTENT OF
DEMOLITION WORK REQUIRED. DEMOLITION DRAWINGS DO NOT PROVIDE EXACT
QUANTITIES AND SPECIFIC TYPES OF MATERIALS AND EQUIPMENT TO BE REMOVED.
2. EXISTING CONDUITS REMAINING IN PLACE MAY BE REUSED, PROVIDED CONDUIT IS IN
SATISFACTORY CONDITION, AS DETERMINED BY OWNER, AND IS RUN IN DIRECT
MANNER BETWEEN INTENDED SOURCE AND LOAD. THOROUGHLY CLEAN EXISTING
CONDUITS BEFORE INSTALLATION OF WIRE.
3. DO NOT REUSE REMOVED CONDUIT, CABLE, AND WIRE.
4. IN AREAS OF WORK (INCLUDING AREAS WHERE CEILING WILL BE REMOVED), REMOVE
EXISTING EXPOSED UNUSED SYSTEMS CABLES IN THEIR ENTIRETY IAW THE NEC.
VERIFY WITH OWNER THAT CABLES ARE UNUSED AND OBTAIN OWNER'S WRITTEN
APPROVAL PRIOR TO REMOVAL.
5. DEVICES AND EQUIPMENT NOT EXPLICITLY NOTED AS DEMOLISHED ARE TO REMAIN
POWERED, UON. ELECTRICAL DEVICES AND CIRCUITRY INTERFERING WITH
DEMOLITION WORK SHALL BE DISCONNECTION AND REMOVED, UON. EXISTING
CIRCUIT WIRING SHALL BE REMOVED BACK TO SOURCE AND PANEL DIRECTORIES
MODIFIED ACCORDINGLY.
6. ELECTRICAL DEMOLITION WORK SHALL BE PROPERLY COORDINATED WITH OTHER
TRADES.
7. CONTRACTOR IS SOLELY RESPONSIBLE FOR THE SAFE HANDLING AND DISPOSAL OF
ALL REMOVED LIGHT FIXTURES AND BALLASTS THAT MAY CONTAIN PCBs OR
MERCURY, IAW ALL APPLICABLE EPA, OSHA, FEDERAL, STATE, AND LOCAL CODES
AND LAW.
8. REVIEW EQUIPMENT SCHEDULED TO BE REMOVED WITH OWNER, DELIVER TO
OWNER'S STORAGE FACILITY ALL EQUIPMENT REQUESTED, BY OWNER, ALL OTHER
EQUIPMENT TO BE DISPOSED OF PROPERLY.
DEMOLITION SHEET NOTES
9. DISCONNECT AND REMOVE EXISTING RECEPTACLE, RECEPTACLE CONTROL
DEVICES, RACEWAYS, CABLES, WIRES, AND ASSOCIATED COMPONENTS CIRCUITRY
TO SOURCE UON. MODIFY/EXTEND CIRCUITRY TO MAINTAIN OPERATION OF
REMAINING DEVICES ON THE SAME CIRCUIT. UPDATE MARKS/LABELS/TAGS ON
CIRCUITRY TO INDICATE TYPE OF CIRCUIT (NORMAL/EMERGENCY/ETC.) AND THE
AREA OR ITEMS SERVED.
10. DISCONNECT AND REMOVE EXISTING LIGHTING, LIGHTING CONTROL DEVICES,
RACEWAYS, CABLES, WIRES, AND ASSOCIATED COMPONENTS INDICATED TO
SOURCE, UON. MODIFY/EXTEND CIRCUITRY TO MAINTAIN OPERATION OF REMAINING
DEVICES ON THE SAME CIRCUIT. UPDATE MARKS/LABELS/TAGS ON CIRCUITRY TO
INDICATE TYPE OF CIRCUIT (NORMAL/EMERGENCY/ETC.) AND THE AREA OR ITEMS
SERVED.
11. UPON COMPLETION OF SCHEDULED WORK, TRACE AND IDENTIFY NEW AND EXISTING
LOADS SERVED BY EACH CIRCUIT FROM PANELS AND BALANCE LOADS AMONG
PHASE (RE-CIRCUITING) WHEN NEEDED. PROVIDE NEW ACCURATE TYPE-WRITTEN
PANEL DIRECTORIES IDENTIFYING LOADS. SWITCH OFF UNUSED BREAKERS AND
LABEL AS "SPARE".
12. WHERE EXISTING CEILINGS ARE TO BE DEMOLISHED, THE CONTRACTOR IS TO
PROVIDE SUPPORT FOR EXISTING TO REMAIN RACEWAYS AND CIRCUITRY
SUPPORTED BY CEILING GRID OR CEILING SUPPORT CABLES. MODIFY/EXTEND
RACEWAYS AND CIRCUITRY AS NECESSARY TO MAINTAIN REQUIRED SUPPORT.
13. WHERE WALL DEVICES ARE SHOWN AS DEMOLISHED IN WALLS THAT ARE EXISTING
TO REMAIN, PATCH TO MATCH ADJACET FINISHES. WHERE WIRING FOR OTHER
DEVICES PASS THROUGH THE WALL BOX OR THE BOX IS OTHERWISE STILL UTILIZED,
PROVIDE COVER PLATE.
TY
PE
B
-3 (1
) F
IN
AL
D
ES
IG
N
F
EB
IS
SU
E
FO
R C
O N
ST
R
U C
TI
O
N
M
AY
E
IRH-3
E
IRH-2
E
IRH-1
E
IRH-4
E
IRH-5
E
IRH-6 E
IRH-7
(E)F-4 (E)F-5
(E)F-6
(E)F-3
(E)VUH-7
(E)RH
(E)F-1
(E)F-2 (E)RH
(E)VUH-5 (E)VUH-6
(E)PRV-2
(E)MUU-1
(E)MAU-1A
(E)PRV-3(E)PRV-1
(E)VUH-4 (E)VUH-3
PRODUCTION
CONTROL
102 SUPPLY OFFICE
TOOL
ISSUE/BENCH
STOCK
HEATED
COVERED
STORAGE
UNHEATED
COVERED
STORAGE
MAINTENANCE
BAYS
105A
SUPPORT SHOP
VEST A
ENTRY A
100A
MAINTENANCE
BAYS
105B
MECH RM
SCREENED
MECH/ELEC
ASSEMBLY/DISASSEMBLY
ELEC/REFRIG
BREAK RM
(E) PANEL EM
(E) PANEL MDP(E) PANEL EMA
(E) PANEL LPB
(E) PANEL LPA
(E) PANEL PB
(E) T1
(E) PANEL PRB
(E) PANEL PA
(E) PANEL PC
(E) PANEL LPC
(E) PANEL PRC
(E)WH-1
2 2.5 2.6 3 4 5 6 7 8 9 10 10.1 10.5 11 12
J
G
E
D
D.1
B
A
(E) T-PA
(E) PANEL RP
(E) T-RP
(E) PANEL PP1
(E) PANEL PP2
1 1 1 11 1 1 1 1 1
1 1
1 1 1 1 1 1(E) T-RPC
(E) T-PC
(E) T-EMA
106C. 106D. 106E. 106F. 107A. 107B. 107C. 107D. 107E. 107F.
127B 127A
105A.105B.105C.105F. 105E. 105D.
127C 127D 106A.106B.
108A. 108B.
1 1
SCALE: 3/32"=1'-0"
0 10 21 32
SHEET ID
N
AT
IO
N
AL
G
U
AR
D B
U R
EA
U
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
PLAN NORTH
FY
TY
PE
A
-2 (3
5% ) S
U
BM
IT
TA
L
A
PR
TY
PE
B -2
(1
) P
R E-
FI
N
AL
D
ES
U
L
E-101
EL
EC
TR
IC
AL
P
O W
ER
P
LA
N
5T
H A
IR
LI
FT
W
IN
G
, A
IR
N
AT
IO
N
AL
G
U
AR
D B
AS
E, S
TE
W
AR
T
IN
TE
R
N
AT
IO
N
AL
A
IR
PO
R T, M
AG
U
IR
E W
AY
, N
EW
G
U R
G H
, N Y
M
AG
U
IR
E W
AY
N
EW
BU
R G
H , N
Y
J.
H
AR
LA
N
R .B
AR
N
AR
D
S.
FO
R D
J.
H
O O
VE
R
M
AY
FA
-2
1- D
-0
0%
S U
BM
IT
TA
L
EN
ER
G Y:
R
EP
AI
R
B U
IL
D
IN
G
W H
AY
SCALE: 3/32" = 1'-0"A1 ELECTRICAL POWER PLAN
SHEET NOTES
1. REFER TO SHEET E-001 FOR GENERAL NOTES, ABBREVIATIONS, AND SYMBOL
LEGENDS.
2. SEE EQUIPMENT CONNECTION SCHEDULE FOR CIRCUITS TO EQUIPMENT SPECIFIED
BY OTHER DISCIPLINES.
3. REFER TO MECHANICAL SHEETS FOR ALL CONTROL AND NETWORK CABLING
ASSOCIATED WITH HVAC AND BUILDING AUTOMATION SYSTEM. ELECTRICAL
CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLATION OF CABLING.
4. EXTERIOR DEVICES SHALL BE NEMA 3R RATED, MINIMUM.
KEYNOTES
1. REMOVE AND REINSTALL EXISTING CONDUCTORS
TO NEW COILING DOOR MOTOR.
NOTE: DOORS 127A, 127B, 127C AND 127D ARE
NIC.
B
-3 (1
) F
IN
AL
D
ES
IG
N
F
EB
IS
SU
E
FO
R
C O
N
ST
R U
C
TI
O N
M
AY
13200 500kVA 480/277
M
(E) MDP
800A, MCB
480/277V 3-Φ, 4W
42CKT
(E) EM
100A, MCB
208/120V 3-Φ, 4W
42CKT
(E) EMA
50A, MCB
208/120V 3-Φ, 4W
42CKT
(E) LPC
400A, MCB
480/277V 3-Φ, 4W
42CKT
(E) LPA
400A, MCB
480/277V 3-Φ, 4W
42CKT
(E) PA
100A, MCB
208/120V 3-Φ, 4W
42CKT
(E) PRB
125A, MCB
240V 3-Φ, 4W
42CKT
(E) PRC
125A, MCB
240V 3-Φ, 3W
42CKT
(E) LPB
400A, MCB
480/277V 3-Φ, 4W
42CKT
45 kVA
15 kVA 208/120
MTS
100A
30kVA 208/120
(E) PC
100A, MCB
208/120V 3-Φ, 4W
42CKT
30kVA 208/120
(E) PB
100A, MCB
208/120V 3-Φ, 4W
42CKT
45 kVA
30kVA 208/120
WEATHERPROOF 200A, 4 POLE, 480/277V
DISCONNECT WITH S/N. FUSED AT 100A
WEATHERPROOF 200A, 4 WIRE, 600 VAC
CIRCUIT BREAKING RECEPTACLE
CROUSE HINDS AREA 204126
G
50KW PORTABLE GENERATOR
480/277 3PH
GENERATOR BREAKER, UNIT MOUNTED
(E) PP1
200A, MCB
480/277V 3-Φ, 4W
42CKT
(E) RP
80A, MCB
208/120V 3-Φ, 4W
18CKT
(E) PP2
200A, MCB
480/277V 3-Φ, 4W
18CKT
30kVA 208/120
SHEET ID
N
AT
IO
N
AL
G
U
AR
D B
U R
EA
U
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FY
TY
PE
A
-2 (3
5% ) S
U
BM
IT
TA
L
A
PR
TY
PE
B -2
(1
) P
R E-
FI
N
AL
D
ES
U
L
E-601
EL
EC
TR
IC
AL
O
N E-
LI
N
E D
IA
G
R
AM
5T
H A
IR
LI
FT
W
IN
G
, A
IR
N
AT
IO
N
AL
G
U
AR
D B
AS
E, S
TE
W
AR
T
IN
TE
R
N
AT
IO
N
AL
A
IR
PO
R T, M
AG
U
IR
E W
AY
, N
EW
G
U R
G H
, N Y
M
AG
U
IR
E W
AY
N
EW
BU
R G
H , N
Y
J.
H
AR
LA
N
R .B
AR
N
AR
D
S.
FO
R D
J.
H
O O
VE
R
M
AY
FA
-2
1- D
-0
0%
S U
BM
IT
TA
L
EN
ER
G Y:
R
EP
AI
R
B U
IL
D
IN
G
W H
AY
SCALE: 12" = 1'-0"B4 EXISTING ONE-LINE DIAGRAM
SHEET NOTES
1. SEE SHEET E-001 FOR GENERAL ELECTRICAL NOTES, ABBREVIATIONS, AND SYMBOL
LEGEND.
2. NOT ALL CIRCUITS ARE SHOWN ON THIS SHEET. REFER TO INDIVIDUAL PANEL
SCHEDULES FOR ADDITIONAL INFORMATION.
B
-3 (1
) F
IN
AL
D
ES
IG
N
F
EB
IS
SU
E
FO
R
C O
N
ST
R U
C
TI
O N
M
AY
SHEET ID
AT
IO
N
AL
G
U
AR
D B
U R
EA
U
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FY
TY
PE
A
-2 (3
5% ) S
U
BM
IT
TA
L
A
PR
TY
PE
B -2
(1
) P
R E-
FI
N
AL
D
ES
U
L
E-602
EL
EC
TR
IC
AL
S
C H
ED
U
LE
S
5T
H A
IR
LI
FT
W
IN
G
, A
IR
N
AT
IO
N
AL
G
U
AR
D B
AS
E, S
TE
W
AR
T
IN
TE
R
N
AT
IO
N
AL
A
IR
PO
R T, M
AG
U
IR
E W
AY
, N
EW
G
U R
G H
, N Y
M
AG
U
IR
E W
AY
N
EW
BU
R G
H , N
Y
J.
H
AR
LA
N
R .B
AR
N
AR
D
S.
FO
R D
J.
H
O O
VE
R
M
AY
FA
-2
1- D
-0
0%
S U
BM
IT
TA
L
EN
ER
G Y:
R
EP
AI
R
B U
IL
D
IN
G
W H
AY
EQUIPMENT CONNECTIONS SCHEDULE
NAME PANEL CKT # LOAD DESCRIPTION
EQUIPMENT CIRCUIT INFORMATION
FEEDER
DISCONNECT INFORMATION
NAME NOTESV POLES Φ HP W MCA MOCP FURNISHED
BY
INSTALLED
BY TYPE SWITCH
RATING
NEMA
TYPE
MECHANICAL
IRH-1 (E) PANEL RP 3 120 1 1 - 120 1 20 A30 EC EC SWITCH 20 A 1 IRH-1
IRH-2 (E) PANEL RP 3 120 1 1 - 120 1 20 A30 EC EC SWITCH 20 A 1 IRH-2
IRH-3 (E) PANEL RP 3 120 1 1 - 120 1 20 A30 EC EC SWITCH 20 A 1 IRH-3
IRH-4 (E) PANEL RP 7 120 1 1 - 120 1 20 A30 EC EC SWITCH 20 A 1 IRH-4
IRH-5 (E) PANEL RP 7 120 1 1 - 120 1 20 A30 EC EC SWITCH 20 A 1 IRH-5
IRH-6 (E) PANEL RP 5 120 1 1 - 120 1 20 A30 EC EC SWITCH 20 A 1 IRH-6
IRH-7 (E) PANEL RP 5 120 1 1 - 120 1 20 A30 EC EC SWITCH 20 A 1 IRH-7
MECHANICAL: 7
CABLE SCHEDULE (CU)
LABEL CB
RATING
# OF
SETS
CURRENT
CARRYING
CONDUCTORS
NEUTRAL
CONDUCTORS
GROUNDING
CONDUCTORS CONDUIT
# SIZE # SIZE # SIZE
A
A20 20 A 1 2 #12 0 N/A 1 #12 3/4" A30 30 A 1 2 #10 0 N/A 1 #10 3/4" A40 40 A 1 2 #8 0 N/A 1 #10 3/4" A50 50 A 1 2 #6 0 N/A 1 #10 1" A60 60 A 1 2 #4 0 N/A 1 #10 1" A70 70 A 1 2 #4 0 N/A 1 #8 1" A80 80 A 1 2 #3 0 N/A 1 #8 1-1/2" A90 90 A 1 2 #2 0 N/A 1 #8 1-1/2" A100 100 A 1 2 #1 0 N/A 1 #8 1-1/2" A110 110 A 1 2 #1 0 N/A 1 #6 1-1/2" A125 125 A 1 2 #1 0 N/A 1 #6 1-1/2" A150 150 A 1 2 #1/0 0 N/A 1 #6 1-1/2" A175 175 A 1 2 #2/0 0 N/A 1 #6 1-1/2" A200 200 A 1 2 #3/0 0 N/A 1 #6 2" A225 225 A 1 2 #4/0 0 N/A 1 #4 2"
A250 250 A 1 2 250KCMIL 0 N/A 1 #4 2"
A300 300 A 1 2 350KCMIL 0 N/A 1 #4 2-1/2"
A350 350 A 1 2 500KCMIL 0 N/A 1 #4 3"
A400 400 A 2 2 #3/0 0 N/A 1 #3 2" A450 450 A 2 2 #4/0 0 N/A 1 #2 2"
TOTAL EST. DEMAND CURRENT 326 A
TOTAL CONNECTED CURRENT: 326 A
TOTAL ESTIMATED DEMAND: 270990 VA
Spare 270150 VA 100.00% 270150 VA TOTAL CONNECTED LOAD: 270990 VA Mechanical Equipment 840 VA 100.00% 840 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
NOTES: PROVIDE PROVISIONS FOR LOCKING IN THE OPEN POSITION FOR BREAKERS FEEDING TO REMOTELY LOCATED TRANSFORMERS.
LEGEND:
TOTAL AMPS: 359 A 312 A 308 A
TOTAL LOAD: 99440 VA 86210 VA 85340 VA
35 -- -- -- 18.54 18.8 -- -- -- 36 33 -- -- -- 18.66 19.55 -- -- -- 34
31 PANEL PP1 (E) 225 A 3 30.34 21.1 3 400 A PANEL LPC (E) 32
29 -- -- -- 0 27 -- -- -- 30 27 -- -- -- 0 27 -- -- -- 28
25 OFF - SPARE 400 A 3 0 27 3 400 A PANEL LPB (E) 26
23 -- -- -- 0 21 -- -- -- 24 21 -- -- -- 0 21 -- -- -- 22
19 OFF - SPARE 400 A 3 0 21 3 400 A PANEL LPA (E) 20
17 -- -- -- 0 0 -- -- -- 18 15 -- -- -- 0 0 -- -- -- 16 13 DEAD RELAY PANEL MAINT BAYS 105 (E) 200 A 3 0 0 3 70 A OFF - SPARE CAPPED OFF 14 11 -- -- -- 0 0 -- -- -- 12 9 -- -- -- 0 0 -- -- -- 10 7 TRANSFER SWITCH (E) 100 A 3 0 0 3 100 A DEAD RELAY PANEL MARINE AREA HIGH BA... 8 5 -- -- -- 0 0 -- -- -- 6 3 -- -- -- 0 0 -- -- -- 4 1 DEAD RELAY PANEL NORTH WALL (E) 100 A 3 0 0 3 100 A DEAD RELAY PANEL SOUTH MAINT BAYS "10... 2
CKT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CKT
MOUNTING: Surface WIRES: 4 BUS RATING: 800 A
SUPPLY FROM: PHASES: 3 MAINS TYPE: MCB
LOCATION: MECH RM 120 VOLTS: 480Y/277V A.I.C. RATING: 50000
Branch Panel: (E) PANEL MDP
TOTAL EST. DEMAND CURRENT 20 A
TOTAL CONNECTED CURRENT: 20 A
TOTAL ESTIMATED DEMAND: 7240 VA
Spare 6400 VA 100.00% 6400 VA TOTAL CONNECTED LOAD: 7240 VA Mechanical Equipment 840 VA 100.00% 840 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
NOTES: PROVIDE PROVISIONS FOR LOCKING IN THE OPEN POSITION FOR BREAKERS FEEDING TO REMOTELY LOCATED TRANSFORMERS.
LEGEND:
TOTAL AMPS: 35 A 13 A 12 A
TOTAL LOAD: 4240 VA 1560 VA 1440 VA
17 SPARE 20 A 1 0 0 1 20 A SPARE 18
15 SPARE 20 A 1 0 0 1 20 A SPARE 16
13 SPARE 20 A 1 0 0 1 20 A SPARE 14
11 SPARE 20 A 1 0 0 1 20 A SPARE 12
9 SPARE 20 A 1 0 0 1 20 A SPARE 10
7 IRH-4,5 20 A 1 0.24 1.2 -- -- -- 8
5 IRH-6,7 20 A 1 0.24 1.2 2 20 A HAND DRYER (E) 6
3 IRH-1,2,3 20 A 1 0.36 1.2 -- -- -- 4
1 FOOD DISPOSER, HEATER (E) 20 A 1 1.6 1.2 2 20 A HAND DRYER (E) 2
CKT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CKT
MOUNTING: Surface WIRES: 4 BUS RATING: 80 A
SUPPLY FROM: (E) T-RP PHASES: 3 MAINS TYPE: MCB
LOCATION: MAINTENANCE BAYS 105B VOLTS: 208Y/120V A.I.C. RATING: 14000
Branch Panel: (E) PANEL RP
TOTAL EST. DEMAND CURRENT 81 A
TOTAL CONNECTED CURRENT: 81 A
TOTAL ESTIMATED DEMAND: 67540 VA
Spare 66700 VA 100.00% 66700 VA TOTAL CONNECTED LOAD: 67540 VA Mechanical Equipment 840 VA 100.00% 840 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
NOTES: PROVIDE PROVISIONS FOR LOCKING IN THE OPEN POSITION FOR BREAKERS FEEDING TO REMOTELY LOCATED TRANSFORMERS.
LEGEND:
TOTAL AMPS: 110 A 67 A 67 A
TOTAL LOAD: 30340 VA 18660 VA 18540 VA
41 -- -- -- 1.44 0.8 -- -- -- 42 39 -- -- -- 1.56 0.8 -- -- -- 40
37 T-RP (E) 50 A 3 4.24 0.8 3 20 A CRANE (E) 38
35 SPARE 20 A 1 0 0.5 -- -- -- 36
33 SPARE 20 A 1 0 0.5 -- -- -- 34
31 EWH-1 (E) 40 A 1 9 0.5 3 20 A F-5 (E) 32
29 -- -- -- 0.5 0.5 -- -- -- 30 27 -- -- -- 0.5 0.5 -- -- -- 28 25 F-6 (E) 20 A 3 0.5 0.5 3 20 A F-4 (E) 26 23 -- -- -- 0.7 0.5 -- -- -- 24 21 -- -- -- 0.7 0.5 -- -- -- 22
19 EF-2 (E) 20 A 3 0.7 0.5 3 20 A F-3 (E) 20
17 -- -- -- 0.7 0.5 -- -- -- 18 15 -- -- -- 0.7 0.5 -- -- -- 16
13 EF-1 (E) 20 A 3 0.7 0.5 3 20 A F-2 (E) 14
11 -- -- -- 3 0.5 -- -- -- 12 9 -- -- -- 3 0.5 -- -- -- 10
7 MAU-1A (E) 20 A 3 3 0.5 3 20 A F-1 (E) 8
5 -- -- -- 3.9 3.6 -- -- -- 6 3 -- -- -- 3.9 3.6 -- -- -- 4
1 RTU-1 (E) 20 A 3 3.9 3.6 3 20 A RTU-2 (E) 2
CKT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CKT
MOUNTING: Surface WIRES: 4 BUS RATING: 200 A
SUPPLY FROM: (E) PANEL MDP PHASES: 3 MAINS TYPE: MCB
LOCATION: MAINTENANCE BAYS 105B VOLTS: 480Y/277V A.I.C. RATING: 25000
Branch Panel: (E) PANEL PP1
B
-3 (1
) F
IN
AL
D
ES
IG
N
F
EB
IS
SU
E
FO
R
C O
N
ST
R U
C
TI
O N
M
AY
| E-001 - LEGEND,ABBREVIATIONS, AND NOTES |
| E-101 - ELECTRICAL POWER PLAN |
| E-601 - ELECTRICAL ONE-LINE DIAGRAM |
| E-602 - ELECTRICAL SCHEDULES |