This document contains questions and answers related to solicitation number W50S87-21-B-5002 for replacing HVAC equipment and systems. The solicitation involves replacing HVAC units, casings, collars and ductwork insulation at multiple buildings at a North Carolina Army National Guard facility. Bidders are encouraged to attend an on-site pre-bid conference on April 29, 2021. The questions and answers provide clarification that the government will handle security badging, requests for work schedule deviations can be submitted after award, the contractor must submit a salvage plan for removed equipment, and any issues found during testing would be evaluated on a case-by-case basis. Load calculations and equipment sizing were performed by the design engineer and are not required from contractors.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Questions and Answers #1 Solicitation Number W50S87-21-B-5002
1. Question: CO approve building entry? Security badging or access for duration of project?
Answer: Contractor and subcontractor employees will receive a badge for the duration of the project.
2. Question: Temporary service for demo. What if we scheduled project work around office hours to avoid down time. Saving costs and reducing inconvenience to occupants.
Answer: Contractor work hours are listed in section 01000, paragraph 3 of the solicitation.
Requests for deviations from this schedule can be submitted by the contractor after award.
3. Question: See nothing identified on plans as salvage please provide a list clarifying equipment to be kept and location to be stored.
Answer: Per submittal schedule – 1.6 – contractor is to submit a salvage plan after contract award. The Government would determine at that time if any removed equipment will be kept and determine location, but does not intend on keeping any equipment at this time.
4. Question: Buildings requiring TAB may discover issues outside scope of this project for corrective action. Do you want a cost provided to address these issues?
Answer: Any issues discovered by TAB would be considered unforeseen conditions and would be evaluated on a case by case basis and handled via contract modification. Contractor to notify contracting officer immediately of any issues identified.
5. Question: Clarify the intent behind 1" thick insulation. Is insulation missing, is it known to be inadequate allowing condensate to form?
Answer: The contractor did not call out which spec sections or drawing he was referencing the 1” thick insulation. For any of the new units and connection to existing ductwork - casings, collars, it is in the scope to replace with the new unit 1” insulation or 2” insulation as required –
Example –
Spec section 23 00 00 2.12.1.1.e - Casing insulation that conforms to NFPA 90A. Insulate single-wall casing sections handling conditioned air with not less than 1 inch thick, 1-1/2 pound density coated fibrous glass material having a thermal conductivity not greater than 0.23 Btu/hr-sf-F. Insulate double-wall casing sections handling conditioned air with not less than 2 inches of the same insulation specified for single-wall casings. Foil-faced insulation is not an acceptable substitute for use with double wall casing. Seal double wall insulation completely by inner and outer panels.
Also – 99M004 – Detail 1 - 1 INCH SEMI-RIGID OUTDOOR INSULATION WITH VAPOR BARRIER needs to be replaced with new unit.
If this is referring to the ductwork insulation, then if there are insulation issues identified during the TAB, contractor is to verify all supply ductwork is insulated and advise contracting officer of any discrepancies or locations requiring insulation immediately.
Questions and Answers #1 Solicitation Number W50S87-21-B-5002
6. Question: Performing load calcs on BLDG 54 per Code should be done by the mechanical engineer not a contractor. We can provide this service but it is outside typical industry practice to do so.
Answer: HVAC unit sizing was evaluated by design engineer. No additional calculations required.
7. Question: Bldg. 60 matching the existing minisplit linseed "gutter" would suffice?
Answer: Bldg. 60 minisplit is not in scope and should remain as-is.