Addendum 1 MANG-Building 321_E300.pdf

PDF 207 KB Posted

Attached to
B321 Fire Pumps Federal contract opportunity
Solicitation number
W50S7L-21-B-0001
Issued by
Department of the Army National Guard

About this file

This document provides details for a firm fixed-price construction contract solicitation for fire pump repairs at Building 321 of the 120th Airlift Wing in Great Falls, Montana. The solicitation seeks to replace the roof, HVAC system, fire pumps, piping control system, lighting and conduct interior and exterior painting, maintain the building generator, and provide site work and pavements. The project is set aside 100% for small businesses under NAICS code 237110 with a size standard of $39.5 million. The estimated value is between $500,000 and $1 million. Funds are not presently available but are expected to be allocated by September 30, 2021. The award will be made to the responsible bidder providing the most advantageous price. The soliciting agency is the Department of the Army National Guard.

View the file

Other files for this federal contract opportunity

Other files attached to B321 Fire Pumps, newest first.
File Type Posted
C4-Abstract - JKSE 182404 Repair Fire Pumps B321.pdf PDF
Amendment 0002.pdf PDF
Addendum 1 MANG-Building 321_E400.pdf PDF
Amendment 0001.pdf PDF
B7-Site Visit Attendance.pdf PDF
B8-Questions and Answers 12-2-2020.pdf PDF
A3- B321 full set - drawings.pdf PDF
W50S7L21B0001 Repair Fire Pumps.pdf PDF
A3-REVISED - B321 FULL SPECIFICATIONS.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

T

T

F

FACP

A A

B B

Pump and

Controls Room

Generator Room

T

L

H

EDB

NDB

GENERATOR

BATTERIES

230kW GENERATOR

DAY TANK

208208

BIM FILE PATH:

SHEET NO.:

TITLE:

copyright 2018 SMA, P.C.

REVISIONS:

KEYMAP:

HELENA

920 Front Street | Suite 101 Helena | MT | 59601 P| 406/442.4933 www.architects-sma.com

ARCHITECT SEAL:

PROJECT:

PROJECT LOCATION:

PREPARED FOR:

LOGO:

CONSULTANT:

PROJECT NUMBER:

DRAWN BY:

CHECKED BY:

TEAM:

PHASE:

DATE:

PROJECT NUMBER:

Pl ot

D at e:

BOZEMAN

109 East Oak Street | Suite 2E Bozeman | MT | 59715 P| 406/219.2216 www.architects-sma.com

920 Front Street, Suite 104 Helena, MT 59601 tel: 406.438.1467

6/10/2019

C:\Revit Local Files\MANG-Building 321_Elec-R19_julie.heitman.rvt

/1

7/

:3 1:

P

M

E3.00

1823 - PN JKSE 182404

2019-06-10

FIRST FLOOR POWER PLAN

JH

CEL

UPGRADE FIRE PUMPS B321

1823 - PN JKSE

182404

MONTANA AIR NATIONAL GUARD

GREAT FALLS AIR NATIONAL GUARD BASE

GREAT FALLS, MT

TYPE B-3 100% SUBMITTAL

1/4" = 1'-0"E3.00

1 FIRST FLOOR POWER PLAN

KEYNOTES - FLOOR PLAN

200 PROVIDE THE FOLLOWING SERVICES FOR THE GENERATOR. ALL WORK TO BE PERFORMED

BY A COMPANY CERTIFIED TO WORK ON CUMMINS GENERATORS, EXAMPLE: CUMMINS

SALES AND SERVICES MISSOULA, MT. 406-728-1300 :

1. CHECK AND REPLACE AS NECESSARY THE FRONT AND REAR CRANK SEAL.

2. REPLACE BELTS AND HOSES.

3. REPLACE IF THE ENGINE LUBE OIL AND ANTIFREEZE MIXTURE

4. REPLACE THE ENGINE START BATTERIES.

5.PROVIDE NEW GENERATOR CONTROLS, CUMMINS POWER COMMAND 1302. PROVIDE

ALL CONNECTIONS REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM.

6. CHECK THE ENTIRE GENERATOR PACKAGE FOR RECOMMENDED MAINTENANCE OR

REPAIR ITEMS.

7. RUN THE ENGINE/GENERATOR AND CHECK FOR LEAKS

8. NFPA110 LOAD BANK TEST THE UNIT.

201 CHECK ENTIRE EXISTING DAY TANK FUEL SYSTEM AND REPLACE SHAFT SEALS AND

RECOMMEND MAINTENANCE AND REPAIR ITEMS.

202 PROVIDE NEW 480V/3PH, 70A 3P AUTOMATIC TRANSFER SWITCH FOR PANELBOARDS.

NEW ATS SHALL BE COMPATIBLE WITH NEW GENERATOR CONTROLS.

203 PROVIDE THERMAL OVERLOAD SWITCH AT NEW GAS UNIT AND CONNECT TO EXISTING

CIRCUIT SAVED DURING DEMOLITION.

204 PROVIDE NEW DUPLEX RECEPTACLE IN EXISTING BACK BOX AND CONNECT TO EXISTING

CIRCUIT SAVED DURING DEMOLITION.

205 CONNECT NEW FIRE PUMP CONTROLLER WITH INTEGRAL AUTOMATIC TRANSFER SWITCH

(ATS) TO EXISTING FEEDER SAVED DURING DEMOLITION. ELECTRICAL CONTRACTOR TO

PROVIDE ALL REQUIRED LINE VOLTAGE CONNECTIONS INCLUDING BUT NOT LIMITED TO

THE CONNECTION BETWEEN THE CONTROLLER AND THE FIRE PUMP. FIRE PUMP

CONTROLLER BEING PROVIDED WITH A WYE-DELTA STARTER, COORDINATE NUMBER OF

CONDUCTORS NECESSARY FOR THE CONNECTION BETWEEN THE FIRE PUMP CONTROLLER

AND THE FIRE PUMP WITH THE FIRE PUMP SYSTEM PROVIDER.

206 PROVIDE NEW 480V/3PH, 30A3P DISCONNECT SWITCH IN NEMA 3R ENCLOSURE WITH 5A

LPN-RK FUSES AND CONNECT NEW JOCKEY PUMP TO EXISTING FEEDER SAVED DURING

DEMOLITION. LOAD ADDED IS EQUAL TO LOAD REMOVED.

207 CONNECT NEW FIRE ALARM CONTROL PANEL TO EXISTING CIRCUIT SAVED DURING

DEMOLITION. PROVIDE SURGE PROTECTION DEVICE FOR CIRCUIT SERVING FIRE ALARM

CONTROL PANEL.

208 PROVIDE NEW LOAD BANK PLUGS PER MTANG STANDARD; MELTRIC DR250

39-28027-K14, 600V 3P+N+G. CONNECT NEW PLUGS TO EXISTING CIRCUIT BREAKERS

AND PROVIDE NEW FEEDER FROM BREAKER OUT TO LOAD BANK PLUG LOCATED AT THE

EXTERIOR OF THE BUILDING. COORDINATE EXACT LOCATION FOR PLUGS WITH OWNER

PRIOR TO ROUGH IN. MOUNT AT +3'-0" AFG TO BOTTOM OF LOAD BANK PLUG. SEE ONE

LINE DIAGRAM ON E4.00 FOR ADDITIONAL ELECTRICAL REQUIREMENTS AND

INFORMATION.

209 PROVIDE DUPLEX RECEPTACLE ON A DEDICATED CIRCUIT FOR ERV UNIT. LOCATE

RECEPTACLE WITHIN 36" OF UNIT. COORDINATE EXACT LOCATION WITH MECHANICAL

CONTRACTOR PRIOR TO ROUGH IN. CONNECT TO EXISTING SPARE 20A BREAKER AT

PANELBOARD L WITH (2#12+#12G)1/2"C.

SHEET NOTES - FLOOR PLAN

A. THE ELECTICAL CONTRACTOR SHALL COORDINATE ALL LINE VOLTAGE WIRING REQUIRED

FOR ALL THE FIRE PROTECTION RELATED WORK PRIOR TO THE START OF WORK.

B. ALL GENERATOR RELATED WORK TO BE COORDINATED WITH THE OWNER AND

SCHEDULED ACCORDINGLY PRIOR TO THE START OF ANY WORK.

C. COORDINATE ALL MECHANICAL WORK WITH MECHANICAL CONTRACTOR PRIOR TO THE

START OF WORK.

N

NO. DATE REVISION DESCRIPTION

1 12/17/2020 Addendum #1

Sheets
E3.00 - FIRST FLOOR POWER PLAN

File details come from the government source that posted it. Updated .