DDPM262101_Alter CP and NDI_Plans (20260512).pdf
PDF 1 MB Posted
- Solicitation number
- W50S7626QA001
- Issued by
-
Department of the Army National Guard
About this file
Summary of Construction Specifications for Convert Command Post & NDI
This document contains detailed construction specifications and technical requirements for renovation work at the Texas Air National Guard Naval Air Station Joint Reserve Base Fort Worth, Texas. The project involves converting command post and non-developmental item (NDI) spaces (CLIN 001 - B1672 and CLIN 002 - B1675) through structural, electrical, HVAC, and security modifications.
The construction scope includes framing new walls using metal studs with gypsum board finishing, installation of VCT flooring (AZrock, Shale Gray #V-866) and carpet (Shaw Contract, Clear Tile Style #59564, Moonstone), and security-enhanced doors with reinforced steel covers and electronic locking mechanisms with manual override capability. Interior finishes require paint matching existing conditions (Sherwin-Williams SW1016 Silver Screen standard) and rubber cove base installation. The project features a mantrap/entrapment area with credential processing windows, double-layer gypsum board enclosure above drop ceilings, and cabinet/counter replacements. Electrical work includes installation of 20 AMP 120V receptacles at specified heights (16", 72", and 12" above counter), GFCI receptacles, occupancy sensor-operated lighting with manual override switches, emergency action processing rotating lights, fire alarm strobes, emergency lighting and exit signs, and ¾" EMT conduit runs with communication boxes for future card entry systems and security cameras. HVAC modifications require additional ductwork, supply diffusers, return grates, and an override button in the console room. All work must match existing finishes and meet specified security and operational requirements.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A
I B
C
D
E
F o n s tr u c t
Using m etal studs, fram e the new walls the full height from the floor to the second floor deck. Install 5/8 gypsum board to include all m ud, tape, and texture to m atch existing finishes. Paint new partitions to m atch existing finishes. Install rubber cove base to m atch existing finishes. If paint does not m atch well on blended portions of wall, the entirety of the wall shall be painted until the seam can be hidden.
Install VCT m atch existing finishes in the wing. (AZrock, Shale G ray #V-866)
Install new carpet (Shaw Contract, Clear Tile Style# 59564, color M oonstone 62500).
Properly fram e a penetration using m etal studs. Install Credential window to allow for proper identification processing and handling within the m antrap. Above credential sl ot, install an im pact rated, m esh reinfo rced 1 way window. Install trim around credential window if the credential window installed requires ii.
Rem ove sound deadening from walls, clean, texture and paint walls (Paint standard color is Sherw in-W illiam s SW 1016 Silver Screen)
Install doors to m atch existing. All doors m ust be solid wood constructed and reinforced externally with a steel sheet cover to prevent rem oval of t he door. They m ust protect to prevent rem oval each external pin, bolt, screw, or other fastening device. Each doorfram e m ust be com patible with both the strength of the door and the adjoining wall construction.
Install doors to m atch existing in wing. Identified security m easure not applicable to this door.
Install door alarm on door designated as em ergency exit. The em ergency exit door shall not have a handle or access from the hallway side and m ust only be able to be opened from the inside. Ensure door m eets all sound proof requirem ents, and ensure replacem ent seal & door m eet requirem ents.
Enclose space above drop ceiling. Using m etal studs, properly fram e the space above the false ceiling open the adjacent hallway to prevent access between the two spaces. Install double layer 5/8 gypsum board to include all m ud and tape. Texture and paint are not required above drop ceiling.
Equip the outer and inner door to the standoff/entrapm ent area w ith a key lock on the exterior side of the door for em ergency entry.
Install rem ote unlocking capability from the console for each m antrap door individually. Configure of the electronic locking doors m ust ensure only one door can open at any lim e (to include rem ote unlocking from the consoles). In the event of failure, the locks m ust fail in the locked position and have a m anual override for em ergency egress. M anual override shall be m ounted near the interior door of the m antrap to activate during egress. Install em pty EM
T conduit and em pty com m box near location of rem ote unlocking function and electronically activated locks to enable future installation of a card entry system
Rem ove and replace all c abinets, overhead cabinets, counters, and the sink in the new dim ensions and configuration. O verhead cabinets will be installed above all identified lower cabinets, Cabinets m ust be approved by governm ent.
D isassem ble and dispose of the existing rack system and the attached studio lighting in the current studio (Rm 143). R epair any penetrations to drop ceiling. R em ove Photo backdrop rolls and bracket and re-install into BLD
G 1669 R m 112 south-east w all. re-install m ay require fabrication of a back brace for the brackets. Top of bracket should be 11 feet high.
IN
FO
. ASSURAN
CE
I
( t
FCI
G)
(3
5 6
ZS
G
H
J
K
L le c tric a l
Install 20 AM P 120V receptacles and any peripherals 16" above finished floor as indicated on drawings
Install a 20 AM P 120V receptacle and any peripherals 72" above finished floor as indicated fo r a wall m ounted TV or a phone box.
Install a 20 AM P 120V G
FCI receptacle and any peripherals 12" above counter height.
Lighting fo r the m an trap shall be operated by a switch and occupancy sensor. This switch will be m ounted near the door of the m an trap in room
143 so that an occupant of the m an trap will not be able to turn the light off. The occupancy sensor inside of the m antrap will be configured so that if the switch is m oved to "O FF", the lights will still com e on.
Configure lighting to be operated by occupancy sensor that is to be positioned to capture m ovem ent through the entirety of the room s.
Configure lighting to be operated by a m anual switch. Install switches at indicated location.
Install Em ergency Action Processing rotating light. Switch activated. Switch will be installed in the console room . Install sign displaying
"Classified W ork in Progress" below rotating lights.
Install fire alanm strobes. All strobes m ust be tested and synchronized in tim ing.
Install light to m atch existing into the drop ceiling. The light is 24"x48". Properly configure the light to operate on the proper switch.
Install battery back up em ergency lights and exit signs to illum inate the surrounding areas.
Install ¾
" EM
T conduit to above the drop ceiling, an em pty com m box, a pull string, and any peripheral in new partition walls at indicated locations. The box will be installed 16" above finished floor.
Install ¾
" EM
T conduit to above the drop ceiling, a single em pty com m box, a pull siring, and any peripheral in new partition walls at indicated locations. The box will be installed 72" above finished floor as indicated on drawings for a wall m ounted TV in the te le c o n fe re n c e ro o m
Install ¾
" EM
T conduit to above the drop ceiling, a single em pty com m box, a pull string, and any peripheral in new partition walls at indicated locations. The box will be installed above door height for a security cam era.
install¾
" EM
T conduit to above the drop ceiling, a single em pty com m box, a pull string, and any peripheral in new partition walls at indicated locations. The box will be installed 48" from finished floor for wall m ounted phones .
H V
Split off additional ducting from the current ducting and add 1 additional supply diffuser.
Install return grates into drop ceilings and constructed walls at the identified locations
Install a H VAC override button inside of the console room
. This button will include any accessories or peripherals to allow ii to tum
VAC on fo r a designated am ount of tim e without being scheduled.
I I □I l i
ZS
ZS
f
15'
,L.._ 15'-10"
16'-6"
I□
Com m
1-
SZ
FO
YER
B
D
F
J
K
L
M
N e n e r a l N o te s odify and replace drop ceiling grid and tiles to accom m odate new wall partitions.
Adjust, rem ove, or replace carpet tiles as needed to accom m odate the new wall partitions to m atch existing carpet.
All flooring and ceilings will be a seam less transition with aligned tiles.
Any equipm ent (I.E. H
VAC grills, light switches, light fixtures) that interfere with new wall construction shall be relocated.
Hardware m ust be Stanley/Best Lock Core com patible.
Drop ceiling m ay be tem porarily taken down to allow for access. Any section that is rem oved m ust be reinstalled in its original condition.
All pre-existing lights will be configured to be operated by the control m echanism (Switch or occupancy sensor) for ii designated area.
All electrical shall be installed in¾
" EM
T conduit or greater in accordance with N
EC.
All room s shall have adequate fire suppression installed. M odify the current system to sufficiently encom pass all newly constructed areas.
Balance the applicable H VAC system to correctly provide adequate clim ate control.
Install bars or applicable m easures to any ducting or returns to allow no access into the secure space (the current Rm
143 & 144).
-Cl'.
t"--bQ
;g
U i::Q t-d o ><"� r-__ 5;
c-€ � w uj
O
:i:
ii;
f-
Cl z
Cl a.
>-a.
Cl'.
ii:
Q C/) a..
(l) Z c:::
a..
(.9 fr
_J
U
Z ffi u f-w
I- Ill c:::
c:::
Z z
C/) ti
...J
I-z 0 z �
Ill □
:es:
ii:
iii f-z
...J co f-
DRAW
IN
G
SIZE:11X17
SPEC. N
O
SCALE: 3/16" = 1'
PRO
JECT N
UM
BER
D
D
PM
262001
SHEET
O
F
A -1
1 PHOTO BACKDROP ADDED TO CONSTRUCT NOTE 12 NRM 20260512
| B1672 - CP.pdf |
| B1675 - NDI.pdf |