UPS SON W50S6V24Q0004 Amendment 01.pdf
PDF 188 KB Posted
- Attached to
- NCC UPS Replacement
- Solicitation number
- W50S6V24Q0004
About this file
This document is a Statement of Work (SOW) for a solicitation to replace a 30kVA Uninterruptible Power Supply (UPS) at the Colorado Air National Guard 140th Communications Squadron Network Control Center. The key requirements include providing a new 30kVA/27kW UPS with lithium-ion batteries, 3-phase 208/120VAC input/output, at least 30-minute battery runtime, and the capability to monitor and manage the UPS remotely. The vendor will be required to provide all labor, equipment, and materials to install the new UPS, remove the existing UPS, and provide training to the end user. The solicitation number is W50S6V24Q0004, the NAICS code is 335999, and the requirement is for full and open competition. Partial quotes and awards may be considered.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Q and A NCC UPS Site Visit.pdf | ||
| Base Access Request Form.pdf | ||
| Combo W50S6V24Q0004 Amendment 01.pdf | ||
| Work Site Pictures Amend 01.pdf | ||
| Q and A NCC UPS.pdf | ||
| Work Site Pictures.pdf | ||
| UPS SON W50S6V24Q0004.pdf | ||
| 30-Load Study.pdf | ||
| Combo W50S6V24Q0004.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Militat Quasi Tigris Quisque “Each Fights Like a Tiger”
COLORADO AIR NATIONAL GUARD
140TH WING
BUCKLEY SPACE FORCE BASE COLORADO
13 June 2024
STATEMENT OF WORK
SUBJECT: UNINTERRUPTIBLE POWER SUPPLY
The Colorado Air National Guard (COANG) is currently soliciting bids for a replacement 30KVA Uninterruptible Power Supply (UPS). The UPS is to be installed in building 850 located on Buckley Space Force Base and will provide temporary emergency power to the 140th Communications Squadron (140th CS) Network Control Center (NCC) in times of commercial power failure. The primary load will consist of mainly network serves, routers, switches, desk top computers, monitors, and encryption devices. The UPS is to be in an interior room that is not accessible from the outside and is not environmentally controlled. (Currently, there is a UPS located in this location with install infrastructure and circuit breakers). The vendor who is awarded the contract is to provide all necessary equipment, labor, and materials as required to perform the general and electrical phases of this project.
Due to the operations tempo of the COANG, any electrical outages associated with this project that would require the shutdown of the network infrastructure should be minimized or whenever possible should be coordinated at least 48 hours in advance.
Below are key elements of this project that will be required of the awarded vendor to provide and install new UPS.
30kVA/27kW Lithium-Ion Batteries 3-phase 208/120VAC input/output Minimum 30-minute battery runtime (see 30-Load Study) Capability to monitor/manage UPS through a LAN connection (Cat5e w/ RJ45 connection) Engine Generator Compatible Provide all labor and administrative functions for job completion Provide and install any new circuit breakers and/or panels as required per code Provide and install all new wiring and receptacles per code Provide and install all associated conduits as required per code Testing and startup of new UPS Remove any wire abandoned by this project Remove existing UPS and battery cabinet upon successful installation, testing and startup of new UPS Remove all trash and rubbish 140 CS has no other UPS on-site. Vendor to provide on-site equipment training to end user including basic level operation, troubleshooting, and maintenance support Battery warranty/maintenance agreement IAW manufactures recommended maintenance schedule
Installation site specifics.
See Visio room diagram and images for work site layout Unit will be installed in a data center environment on a raised floor Masonite floor protection not required when servicing, deinstallation or installation.
Installation on first floor of building Flex conduit, power panels, and other hardware previously installed.
UPS is connected in-line to a backup generator to provide continuous power. We do not foresee a scenario where we require emergency service Current UPS: Chloride; Serial number: B273349; Equipment type: EP36305225F. Bar Code: CRWU
02320
Installation site does not have a loading dock. Unit has a BigJoe forklift with a 2500lb max capacity onsite, and a floor jack.
o If loading dock is required, there is one located ~1/2 mile away and the equipment can be relocated afterwards