W50S6U24QA011_Solicitation_Questions_and_Answers_RFI.pdf
PDF 61 KB Posted
- Attached to
- Replace Air Conditioning Unit 3 at Building 23
- Solicitation number
- W50S6U24QA011
- Issued by
-
Department of the Army National Guard
About this file
This document contains questions and answers related to a Request for Information (RFI) for the replacement of an air conditioning unit at Building 23, Sepulveda Air National Guard Station, CA.
The key details are:
- The new HVAC unit must include a duct smoke detector, per UFC 410-01 and UFC 3-600-01 requirements.
- The new unit must be compatible and integrated with the existing Automated Logic building management system under this contract. The contractor is responsible for the BMS integration, it is not covered under the BMS maintenance contract.
The related federal contract opportunity is for the replacement of Air Conditioning Unit 3 at Building 23. The 195th Wing/Mission Support Contracting (195 WG/MSC) intends to issue a Request for Quote (RFQ) for this firm-fixed-price purchase order. The work includes providing all personnel, equipment, tools, materials, supervision, and quality control to perform the unit replacement, as defined in the Performance Work Statement (PWS).
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Solicitation questions and request for information as of 25 Jul 2024
Question 1) Did not see a duct smoke detector on the duct. Is it required or is it global shut down from the Fire Alarm and who will be connecting and testing the fire shut down system?
Response: Yes, a smoke detector shall be included on the new packaged HVAC unit. UFC 410-01 states that air distribution systems must be equipped with smoke detectors listed and labeled for installation in air distribution systems as required by Section 606 and UFC 3-600-01. If any conflict occurs between Section 606 and UFC 3-600- 01, the requirements of UFC 3-600-01 take precedence. Duct smoke detectors must comply with UL 268A. Other smoke detectors must comply with UL 268. Locate smoke detectors in accordance with manufacturer’s recommendations and downstream from the fan discharge, downstream of the air filters, ahead of any branch connections, and at the center of the duct.
Question 2) Do we need to add cost for BMS integration by American Building Automation, or is it under their BMS maintenance contract?
Response: The new unit must be compatible and integrated with the existing Automated Logic system under this contract.
File details come from the government source that posted it. Updated .