This document is a set of Request for Information (RFI) questions and responses regarding a federal contract opportunity for the repair of Fuel Cell B1171 at Eielson Air Force Base, Alaska.

The key details are:

  • The project involves replacement of the existing Aqueous Film Forming Foam (AFFF) fire protection system with a water-only system, architectural modifications to expand office and storage space, and heating, ventilation, and lighting upgrades.
  • The solicitation will include option line items for 1) Constructing a Fire Protection Water Loop and Fire Hydrants, and 2) Telecommunications Cabling.
  • The RFI responses clarify the extent of the Class 1 Division 2 hazardous classification area, which is up to 5 feet around the aircraft and 18 inches above the finished floor in the Fuel Cell Repair Area 100.
  • The RFI responses also provide guidance on the installation requirements for lighting fixtures, receptacles, and other electrical equipment in relation to the classified area.

View the file

Other files for this federal contract opportunity

Other files attached to Repair Fuel Cell, B1171, newest first.
File Type Posted
W50S6K24B0002 Amendment 6.pdf PDF
W50S6K24B0002 Amendment 5.pdf PDF
EIELSON E-4.1 ESK-1.pdf PDF
ESK-3.pdf PDF
W50S6k24B0002 Amendment 4.pdf PDF
ESK-2.pdf PDF
W50S6K24B0002U0003 Amendment 3.pdf PDF
5. Frequency Converter Photos.pdf PDF
18. B1171 Original Construction Design Drawings.pdf PDF
65. 01 35 26.pdf PDF
71. 2019 Roof Report - B1171 Breakout.pdf PDF
76. AKANG Eielson B1171_Civil Drawings 65- - clouds.pdf PDF
W50S6K24B0002 Amendment 2.pdf PDF
1. 23 30 00.pdf PDF
3. Pages from Env Atlas - B1171.pdf PDF
49. revised C-1.1.pdf PDF
19. Air Regulator Photos.pdf PDF
W50S6K24B0002 Amendment 1.pdf PDF
Sign In Sheet.pdf PDF
Site Visit Slides.pdf PDF
Eielson B1171 Type B-3 Submittal Drawings FP revised Addendum 1.pdf PDF
W50S6K24B0002 - Solicitation.pdf PDF
Type B-3 Final Design Submittal_SPECS_20240412.pdf PDF
FTQW072002 AF 813 RCS 20-111 Repair Fuel Cell Revised.pdf PDF
Show all 24

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Title: Date Updated: 6/25/2024

RFI #

Date

Received

(DM)

Contractor RFI Description (entered by DM)

Responder (Entered by DM)

Date Sent to

Responder

(DM)

RFI Answer (entered by DM)

Date Answered

(DM)

Remarks

Amendment Number

(CS)

Date Amendment

Sent

(CS)

6 05/09/2024

Please clarify the hazardous classification plan shown on drawing E-

4.1 detail 3. The side view details a 5 foot bubble around the aircrafts as class 1 div 2 but the aerial view shows a bubble that scales to around 12 feet making the class 1 div 2 significantly larger. If the bubble on the aerial view is correct, please provide accurate dimensions of the bubble area for bidding purposes as the cost difference is significant. If the side view is correct, please provide the two elevations not called out on detail 3.

Jacobs 05/09/2024

The hazardous classification of Class 1 Div 2 in Fuel Cell Repair Area 100 is up to 5 feet around aircraft and 18" above finished floor.

05/16/2024

7 05/09/2024

Type F2 and EXXP fixtures on drawing E1.2 are detailed to be mounted well above the 18 inch class 1 div 2 area from drawing E-4.1 detail 3, but are listed in the luminaire schedule as class 1 div 2 type fixtures. Please clarify the extent of the classified area as the costs are significantly different between non-classified and classified areas.

Jacobs 05/09/2024

The lighting fixtures F2 and EXXP are not required to Class 1 Div 2 if it is not within the classified area. The hazardous classification of Class 1 Div 2 in Fuel Cell Repair Area 100 is up to 5 feet around aircraft and 18" above finished floor.

05/16/2024

8 05/09/2024

The Class 1 div 2 receptacles shown on drawing E1.1 and E-4.1 detail 1 are noted to be relocated. On drawing E-0.1 these are called out to be at 48” AFF, well outside of the classified area shown on E-4.1 detail 3. Please clarify the classified areas and installations.

Jacobs 05/09/2024

The Class 1 Div 2 receptacles are required to be Class 1 Div 2 even though it may be outside the classified area. The hazardous classification of Class 1 Div 2 in Fuel Cell Repair Area 100 is up to 5 feet around aircraft and 18" above finished floor.

05/16/2024

9 05/09/2024

Drawing E-4.1, detail 2, key note 6 states to relocate the explosion proof phone to an area not located in the class 1 div 2 classification. Please clarify the classified areas and installations.

Jacobs 05/09/2024

The hazardous classification of Class 1 Div 2 in Fuel Cell Repair Area 100 is up to 5 feet around aircraft and 18" above finished floor.

05/16/2024

Project #: D32121000 AKANG Eielson AFB Repair Fuel Cell B1171

RFI #

Date

Received

(DM)

Contractor RFI Description (entered by DM)

Responder (Entered by DM)

Date Sent to

Responder

(DM)

RFI Answer (entered by DM)

Date Answered

(DM)

Remarks

Amendment Number

(CS)

Date Amendment

Sent

(CS)

10 05/09/2024

Spec section 26 35 43, 2.4.f. states that the remote monitoring and control panel is to be in a NEMA 7 explosion proof enclosure even though the location is outside of the classified zone as shown on detail 3 drawing E4.1. Please clarify the classified areas and installations.

Jacobs 05/09/2024

The remote monitoring and control panel are not required to be explosion proof if it is not within the classified area. The hazardous classification of Class 1 Div 2 in Fuel Cell Repair Area 100 is up to 5 feet around aircraft and 18" above finished floor.

05/16/2024

11 05/09/2024

Drawing E-4.1 demolition key notes 1 & 2 for detail 1, and key notes 1 & 2 for detail 2. Are these electrical items currently class 1 div 2, and if so, they don’t appear to be relocated into a classified area. Please clarify the classified areas and installations.

Jacobs 05/09/2024

Junction boxes are not required for Class 1 Div 2 if it is not within the classified area. The hazardous classification of Class 1 Div 2 in Fuel Cell Repair Area 100 is up to 5 feet around aircraft and 18" above finished floor.

05/16/2024

12 05/09/2024

Drawing E-4.1 detail 2 key note 3 calls for three class 1 div 2 receptacles installed at 48 inches AFF which is outside of the classified area. Please clarify the classified areas and installations.

Jacobs 05/09/2024

The Class 1 Div 2 receptacles are required to be Class 1 Div 2 even though it may be outside the classified area. The hazardous classification of Class 1 Div 2 in Fuel Cell Repair Area 100 is up to 5 feet around aircraft and 18" above finished floor.

05/16/2024

13 05/09/2024

Drawing E-4.0, detail 1, demolition key note 7 and detail 2, key note 4. Is the existing installation and device class 1 div 2? Will the new installation location be class 1 div 2?

Jacobs 05/09/2024

The hazardous classification of Class 1 Div 2 in Fuel Cell Repair Area 100 is up to 5 feet around aircraft and 18" above finished floor.

05/16/2024

14 05/09/2024

If classified fixtures, devices, equipment, and or like items are to be installed outside of classified areas, provide a detail of each item and circuit installation method as NEC code does not require any classified circuit installation outside of a classified area. If the intent is to have a larger classified area than that detailed on E-4.1, provide a new classified area drawing and detail so that all systems can be priced accordingly.

Jacobs 05/09/2024

Wall mounted outlets are required to be Class 1 Div 2 even though it may be outside the classified area. The hazardous classification of Class 1 Div 2 in Fuel Cell Repair Area 100 is up to 5 feet around aircraft and 18" above finished floor.

05/16/2024