VAV CON -00MH602.pdf

PDF 396 KB Posted

Attached to
Z2DA--CFM - Rebalance HVAC System Federal contract opportunity
Solicitation number
Not on record
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16

About this file

This document is a terminal unit and fan coil unit schedule for an HVAC system rebalance project at a Department of Veterans Affairs medical center. It provides specifications for 91 supply terminal units, return terminal units, and fan coil units across four floors and interstitial spaces of various buildings. Unit locations, controlled areas, maximum and minimum airflow capacities, flow control types, and control sequences are delineated. It also lists a related federal contract opportunity from the VA for rebalancing the HVAC system, identified as solicitation number REBALANCE. The schedule contains detailed technical specifications for terminal units and fan coils to be used in fulfilling the requirements of the rebalancing contract.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--CFM - Rebalance HVAC System, newest first.
File Type Posted
VAV DNT 02303-2MH628.pdf PDF
P12-AMS CEP 115-7MH608.pdf PDF
S02-XHIBIT B PAST AND PRESENT PERFORMANCE QUESTIONNAIRE v2.pdf PDF
VAV DNT 02305-2MH630.pdf PDF
DNT L05 G.pdf PDF
RESEARCH 4th mech plan.pdf PDF
CEP L03.pdf PDF
P12-000110 Table of Contents 4-7-20.pdf PDF
AMS TLR 03470-6MH604.pdf PDF
ICRA ILSM for CFM - Rebalance HVAC System.xlsx XLSX spreadsheet
013526 Safety Requirements.pdf PDF
VAV DNT 02302-2MH627.pdf PDF
PANAM 103.pdf PDF
230593 Testing Adjusting and Balancing for HVAC.pdf PDF
VAV DNT 02301-2MH626.pdf PDF
M-3 DNT Building Existing DOAS sequence.pdf PDF
OUT L07.pdf PDF
P13-INP L04.pdf PDF
DNT L01i D-E.pdf PDF
230511 Common Work Results for HVAC.pdf PDF
RESEARCH 2nd mech plan.pdf PDF
OUT L05.pdf PDF
390-8EP105-P.pdf PDF
S02-EXHIBIT D CONTRACTOR EVALUATION FORM CONSTRUCTION SAFETY v2.pdf PDF
PANAM 105.pdf PDF
P07-General Decision.pdf PDF
CEP L04.pdf PDF
230800 Commissioning of HVAC Systems.pdf PDF
RESEARCH 1st mech plan.pdf PDF
P15-M-1 Typical Existing Service Bay layout.pdf PDF
AMS PANAM 0243-9MH601.pdf PDF
AMS OP 03027-3MH604.pdf PDF
010000 General Requirements.pdf PDF
013323 Shop Drawings Product Data and Samples.pdf PDF
P12-230923 DDC Control System for HVAC 4-7-20.pdf PDF
VAV DNT 02306-2MH631.pdf PDF
VAV DNT 02304-2MH629.pdf PDF
P12-ROOMS NUMBERS LIST WITH OLD AND NEW ROOM NUMBERS.xlsx XLSX spreadsheet
03491-6EL103-M3.pdf PDF
OUT L08.pdf PDF
S02-EXHIBIT A PERFORMANCE RELEVANCY SURVEY v2.pdf PDF
PANAM 104.pdf PDF
03503-6EP103-M3.pdf PDF
OUT L06.pdf PDF
OUT L04.pdf PDF
OUT L03.pdf PDF
S02-EXHIBIT E SURETY FORM.pdf PDF
P15-M-2 DNT Building Existing AHU sequence.pdf PDF
AMS Research 348-8MH609.pdf PDF
P14-M-4 OP Building Existing AHU sequence.pdf PDF
Show all 50

Z2DA--CFM - Rebalance HVAC System has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL NOTES:

1. FOR SYMBOL LISTS, ABBREVIATIONS, AND GENERAL

NOTES THAT APPLY TO ALL DRAWINGS SEE THE

MH�0 SERIES OF DRAWINGS.

2. FOR GENERAL DETAILS SEE THE MH�5 SERIES OF DRAWINGS.

3. FOR CONTROL DIAGRAMS SEE THE MH�8 SERIES OF DRAWINGS.

DATE

LOCATION

CHECKED DRAWN

PROJECT TITLE PROJECT NUMBER

DOCUMENT SET PACKAGE

DRAWING NUMBERAPPROVED: PROJECT DIRECTOR

DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:

REVISIONS: DATE

B

A

D

C

E

VA FORM 08-6231

O N

E

EI

G H

T

IN

C H

O

N E

FO

O

T O

N E

Q U

AR

TE

R

IN

C H

O

N E

FO

O

T O

N E

H A L

F

IN

C H

O

N E

FO

O

T

TH

R

EE

Q U

AR

TE

R S

IN

C

H

O N

E

FO

O T

TH

R

EE

IN

C H

ES

O N

E

FO

O T

O N

E

IN

C H

F

O R

TY

F

E E T

(1

0'

6"

6"

0'

0'

123456

F

B

A

D

C

E

F

O N

E

SI

X T

EE

N

TH

IN

C

H

O N

E

FO

O T

O N

E

AN

D O

N E

H

AL

F

IN

C H

ES

O N

E

FO

O T

6"

BUILDING NUMBER

NEW ORLEANS, LOUISIANA

00MH602

CONCOURSE HVAC TERMINAL UNIT AND FAN

COIL UNIT SCHEDULE

KJS BEFebruary 29, 2012

00629-HS2-401SLVHCS REPLACEMENT MEDICAL

CENTER PROJECT

SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL

KORDA/NEMETH ENGINEERING / STRUCTURAL

BR+A CONSULTING ENGINEERS / MECH, ELECT, PLUMBING, LOW VOLTAGE

ARCHITECTURAL ENGINEERING/ PLUMBING

SCALES ASSOCIATES / FIRE PROTECTION

DESMAN ASSOCIATES / PARKING

CODE CONSULTANTS, INC. / CODE CONSULTANT

THE SEXTANT GROUP / AV & ACOUSTICAL

HAMMER DESIGN ASSOCIATES / FOOD SERVICE

PYBURN & ODOM / ABATEMENT

TATA & HOWARD / TANK CONSULTANT

I.S.C. GROUP, INC./ IRRIGATION

DAN EUSER WATER ARCHITECTURE, INC./ WATER FEATURE

Department of

Veterans Affairs

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

WP_08

CONSTRUCTION DOCUMENTS 1

FULLY SPRINKLERED

SUPPLY TERMINAL UNIT SCHEDULE � FIRST FLOOR A1 � A7

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S�1 00�1A1 E1 1155 CFM 1155 2.0 CV 2/ MH821 NOTE (1)

S�2 00�1A1 G1 2155 CFM 1155 3.5 CV 2/ MH821 NOTE (1)

S�3 00�1A1 H1 2400 CFM 2400 4.0 CV 2/ MH817 NOTE (1)

S�4 00�1A2 H1 2400 CFM 2400 4.0 CV 2/ MH817 NOTE (1)

S�5 00�1A2 G1 1680 CFM 1680 2.75 CV 2/ MH821 NOTE (1)

S�6 00�1A2 G1 1800 CFM 1800 3.0 CV 2/ MH821 NOTE (1)

S�7 00�1A3 H1 2940 CFM 1500 2.5 VCV 4/ MH821 NOTE (1)

S�8 00�1A3 E1 1365 CFM 700 1.25 VCV 4/ MH821 NOTE (1)

S�9 00�1A4 G1 2205 CFM 1205 2.0 VCV 4/ MH817 NOTE (1)

S�10 00�1A4 G1 2205 CFM 1205 2.0 VCV 4/ MH817 NOTE (1)

S�11 00�1A4 F1 1625 CFM 825 1.5 VCV 4/ MH821 NOTE (1)

S�12 00�1A4 F1 1625 CFM 825 1.5 VCV 4/ MH821 NOTE (1)

S�13 00�1A4 H1 3000 CFM 2750 4.3 VCV 4/ MH817 NOTE (1)

S�14 00�1A4 H1 2400 CFM 2150 3.5 VCV 4/ MH817 NOTE (1)

S�15 00�1A5 G1 2015 CFM 1000 1.75 VCV 4/ MH821 NOTE (1)

S�16 00�1A5 E1 1200 CFM 1200 2.0 CV 2/ MH821 NOTE (1)

S�17 00�1A6 G1 1900 CFM 1900 3.25 CV 2/ MH821 NOTE (1)

S�18 00�1A6 F1 1500 CFM 1500 2.5 CV 1/MH821 NOTE (1)

S�19 00�1A6 F1 1500 CFM 1500 2.5 CV 1/MH821 NOTE (1)

RETURN TERMINAL UNIT SCHEDULE � FIRST FLOOR A1 � A7

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

R�1 00�1A1 D1 805 CFM 805 N/A CV 2/ MH821 TRACKS S�1, NOTE (1)

R�2 00�1A1 G1 1790 CFM 1790 N/A CV 2/ MH821 TRACKS S�2, NOTE (1)

R�3 00�1A3 E1 1350 CFM 1350 N/A CV 2/ MH821 TRACKS S�6, NOTE (1)

R�4 00�1A3 E1 1230 CFM 1230 N/A CV 2/ MH821 TRACKS S�5, NOTE (1)

R�5 00�1A4 H1 2600 CFM 1160 N/A VCV 4/ MH821 TRACKS S�7, NOTE (1)

R�6 00�1A4 F1 1620 CFM 820 N/A VCV 4/ MH821 TRACKS S�11, NOTE (1)

R�7 00�1A4 F1 1620 CFM 820 N/A VCV 4/ MH821 TRACKS S�12, NOTE (1)

R�8 00�1A5 H1 3200 CFM 2200 N/A VCV 4/ MH821 TRACKS S�15, NOTE (1)

R�9 00�1A5 D1 700 CFM 700 N/A CV 2/ MH821 TRACKS S�16, NOTE (1)

R�10 00�1A6 H1 2700 CFM 2700 N/A CV 2/ MH821 TRACKS S�17, NOTE (1)

SUPPLY TERMINAL UNIT SCHEDULE �SECOND FLOOR A1 � A7

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S�1 00�2A1 H1 2400 CFM 2400 4.0 CV 2/ MH821 NOTE (1)

S�2 00�2A1 B2 400 CFM 200 0.5 VCV 4/ MH821 NOTE (1)

S�3 00�2A1 F2 1525 CFM 750 1.25 VCV 4/ MH821 NOTE (1)

S�4 00�2A1 G1 2150 CFM 2150 3.5 CV 2/ MH821 NOTE (1)

S�5 00�2A2 D1 900 CFM 450 0.75 VCV 4/ MH821 NOTE (1)

S�6 00�2A3 G1 1800 CFM 900 1.5 VCV 4/ MH821 NOTE (1)

S�7 00�2A3 H1 2400 CFM 1200 2.0 VCV 4/ MH821 NOTE (1)

S�8 00�2A3 H1 2700 CFM 1350 2.25 VCV 4/ MH821 NOTE (1)

S�9 00�2A4 H1 3000 CFM 1500 2.5 VCV 4/ MH821 NOTE (1)

S�10 00�2A4 H1 3000 CFM 1800 3.0 VCV 4/ MH821 NOTE (1)

S�11 00�2A5 G1 1800 CFM 1800 3.0 CV 1/MH821 NOTE (1)

S�12 00�2A5 G1 1800 CFM 900 1.5 VCV 4/ MH821 NOTE (1)

S�13 00�2A5 H1 2400 CFM 1200 2.0 VCV 4/ MH821 NOTE (1)

RETURN TERMINAL UNIT SCHEDULE � SECOND FLOOR A1 � A7

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

R�1 00�2A1 H1 2700 CFM 2700 N/A CV 2/ MH821 TRACKS S�1, NOTE (1)

R�2 00�2A1 B2 400 CFM 200 N/A VCV 4/ MH821 TRACKS S�2, NOTE (1)

R�3 00�2A1 F2 1525 CFM 750 N/A VCV 4/ MH821 TRACKS S�3, NOTE (1)

R�4 00�2A1 G1 1800 CFM 1800 N/A CV 2/ MH821 TRACKS S�4, NOTE (1)

R�5 00�2A2 D1 900 CFM 450 N/A VCV 4/ MH821 TRACKS S�5, NOTE (1)

R�6 00�2A2 G1 1800 CFM 900 N/A VCV 4/ MH821 TRACKS S�6, NOTE (1)

R�7 00�2A3 H1 2400 CFM 1200 N/A VCV 4/ MH821 TRACKS S�7, NOTE (1)

R�8 00�2A3 G1 1800 CFM 600 N/A VCV 4/ MH821 TRACKS S�8, NOTE (1)

R�9 00�2A4 H1 2200 CFM 700 N/A VCV 4/ MH821 TRACKS S�9, NOTE (1)

R�10 00�2A4 G1 1800 CFM 600 N/A VCV 4/ MH821 TRACKS S�10, NOTE (1)

R�11 00�2A5 G1 1800 CFM 600 N/A VCV 4/ MH821 TRACKS S�12, NOTE (1)

R�12 00�2A5 G1 2000 CFM 800 N/A VCV 4/ MH821 TRACKS S�13, NOTE (1)

SUPPLY TERMINAL UNIT SCHEDULE � THIRD FLOOR A1 � A7

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S�1 00�3A1 H1 2600 CFM 2600 4.25 CV 2/ MH821 NOTE (1)

S�2 00�3A1 A2 100 CFM 100 0.5 CV 1/MH821 NOTE (1)

S�3 00�3A1 A2 100 CFM 100 0.5 CV 1/MH821 NOTE (1)

S�4 00�3A1 D2 900 CFM 450 0.75 VCV 4/ MH821 NOTE (1)

S�5 00�3A1 G1 2150 CFM 2150 3.5 CV 2/ MH821 NOTE (1)

S�6 00�3A2 D1 900 CFM 450 0.75 VCV 4/ MH821 NOTE (1)

S�7 00�3A3 H1 2610 CFM 1300 2.25 VCV 4/ MH821 NOTE (1)

S�8 00�3A3 H1 2400 CFM 1200 2.0 VCV 4/ MH821 NOTE (1)

S�9 00�3A3 H1 2700 CFM 1350 2.25 VCV 4/ MH821 NOTE (1)

S�10 00�3A4 H1 3300 CFM 1650 2.25 VCV 4/ MH821 NOTE (1)

S�11 00�3A4 H1 2400 CFM 1200 2.0 VCV 4/ MH821 NOTE (1)

S�12 00�3A5 H1 2400 CFM 1200 2.0 VCV 4/ MH821 NOTE (1)

S�13 00�3A5 E1 1200 CFM 600 1.0 VCV 4/ MH821 NOTE (1)

S�14 00�3A6 F1 1500 CFM 1500 2.5 CV 2/ MH821 NOTE (1)

RETURN TERMINAL UNIT SCHEDULE � THIRD FLOOR A1 � A7

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

R�1 00�3A1 H1 2600 CFM 2600 N/A CV 2/ MH821 TRACKS S�1, NOTE (1)

R�2 00�3A1 D2 900 CFM 450 N/A VCV 4/ MH821 TRACKS S�4, NOTE (1)

R�3 00�3A1 H1 2500 CFM 2500/0 N/A VCV 4/ MH817 TRACKS S�3 LEVEL 1,

NOTE (1)

R�4 00�3A1 G1 1800 CFM 1800 N/A CV 2/ MH821 TRACKS S�5, NOTE (1)

R�5 00�3A2 D1 900 CFM 450 N/A VCV 4/ MH821 TRACKS S�6, NOTE (1)

R�6 00�3A2 H1 2500 CFM 2500/0 N/A VCV 4/ MH817 TRACKS S�4 LEVEL 1,

NOTE (1)

R�7 00�3A3 H1 2400 CFM 1200 N/A VCV 4/ MH821 TRACKS S�7, NOTE (1)

R�8 00�3A3 H1 2430 CFM 1120 N/A VCV 4/ MH821 TRACKS S�8, NOTE (1)

R�9 00�3A3 H1 2700 CFM 1350 N/A VCV 4/ MH821 TRACKS S�9, NOTE (1)

R�10 00�3A3 H1 2500 CFM 1500/0 N/A VCV 4/ MH817 TRACKS S�9 LEVEL 1,

NOTE (1)

R�11 00�3A3 H1 2500 CFM 1500/0 N/A VCV 4/ MH817 TRACKSS�10 LEVEL 1,

NOTE (1)

R�12 00�3A4 H1 3300 CFM 1650 N/A VCV 4/ MH821 TRACKS S�10, NOTE (1)

R�13 00�3A4 F1 1520 CFM 600 N/A VCV 4/ MH821 TRACKS S�11, NOTE (1)

R�14 00�3A4 E1 1200 CFM 600 N/A VCV 4/ MH821 TRACKS S�11, NOTE (1)

R�15 00�3A5 H1 2400 CFM 1200 N/A VCV 4/ MH821 TRACKS S�12, NOTE (1)

R�16 00�3A5 H1 3000 CFM 2500/0 N/A VCV 4/ MH810 TRACKS S�13, S�14

LEVEL 1, NOTE (1)

R�17 00�3A5 E1 1200 CFM 600 N/A VCV 4/ MH821 TRACKS S�13, NOTE (1)

SUPPLY TERMINAL UNIT SCHEDULE � FOURTH FLOOR A1 � A7

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S�1 00�4A1 G1 2250 CFM 2250 3.75 CV 2/ MH821 NOTE (1)

S�2 00�4A4 F1 1500 CFM 1500 2.5 CV 2/ MH821 NOTE (1)

S�3 00�4A5 G1 2250 CFM 2250 3.75 CV 2/ MH821 NOTE (1)

RETURN TERMINAL UNIT SCHEDULE � FOURTH FLOOR A1 � A7

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

R�1 00�4A1 G1 2250 CFM 2250 N/A CV 2/ MH821 TRACKS S�1, NOTE (1)

R�2 00�4A4 F1 1500 CFM 1500 N/A CV 2/ MH821 TRACKS S�2, NOTE (1)

R�3 00�4A6 G1 2250 CFM 2250 N/A CV 2/ MH821 TRACKS S�3, NOTE (1)

FAN COIL UNIT SCHEDULE � FOURTH FLOOR A1 � A7

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

FCU�1 00�4A1 4J4 � 2/ MH820 NOTE (2)

FCU�2 00�4A1 4J4 � 2/ MH820 NOTE (2)

FCU�3 00�4A1 4J2 � 2/ MH820 NOTE (2)

FCU�4 00�4A1 4J2 � 2/ MH820 NOTE (2)

FCU�5 00�4A1 4J2 � 2/ MH820 NOTE (2)

FCU�5 00�4A2 4J2 � 2/ MH820 NOTE (2)

FCU�5 05�4A6 4J2 � 2/ MH820 NOTE (2)

FCU�6 00�4A2 4J2 � 2/ MH820 NOTE (2)

FCU�6 04�4A5 4J2 � 2/ MH820 NOTE (2)

FCU�6 05�4A6 4J2 � 2/ MH820 NOTE (2)

FCU�7 00�4A2 4J2 � 2/ MH820 NOTE (2)

FCU�7 04�4A5 4J2 � 2/ MH820 NOTE (2)

FCU�8 00�4A3 4J2 � 2/ MH821 NOTE (2)

FCU�9 00�4A3 4J2 � 2/ MH820 NOTE (2)

FCU�10 00�4A3 4J2 � 2/ MH820 NOTE (2)

FCU�11 00�4A3 4J2 � 2/ MH820 NOTE (2)

FCU�12 00�4A4 4J2 � 2/ MH820 NOTE (2)

FCU�13 00�4A4 4J2 � 2/ MH820 NOTE (2)

FCU�14 00�4A5 4J2 � 2/ MH820 NOTE (2)

FCU�15 00�4A5 4J2 � 2/ MH820 NOTE (2)

FCU�16 00�4A5 4J2 � 2/ MH820 NOTE (2)

FCU�17 00�4A6 4J2 � 2/ MH820 NOTE (2)

FCU�18 00�4A6 4J2 � 2/ MH820 NOTE (2)

FCU�19 00�4A6 4J2 � 2/ MH820 NOTE (2)

FCU�20 00�4A6 4J2 � 2/ MH820 NOTE (2)

FCU�21 00�4A6 4J2 � 2/ MH820 NOTE (2)

FCU�22 00�4A7 4J2 � 2/ MH820 NOTE (2)

FCU�23 00�4A7 4J2 � 2/ MH820 NOTE (2)

FCU�24 00�4A7 4J2 � 2/ MH820 NOTE (2)

FCU�25 00�4A7 4J2 � 2/ MH820 NOTE (2)

FAN COIL UNIT SCHEDULE � THIRD FLOOR A1 � A7

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

FCU�1 00�3A6 2D5 � 1/MH820 NOTE (2), (3)

FCU�2 00�3A6 2D5 � 1/MH820 NOTE (2), (3)

FCU�3 00�3A6 2D5 � 1/MH820 NOTE (2), (3)

FCU�4 00�3A6 2D5 � 1/MH820 NOTE (2), (3)

SUPPLY TERMINAL UNIT SCHEDULE � FOURTH FLOOR INTERSTITIAL A1 � A7

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S�1 00�4iA1 H1 3200 CFM 3200 2.5 CV 2/ MH821 NOTE (1)

S�2 00�4iA4 H1 3200 CFM 3200 2.5 CV 2/ MH821 NOTE (1)

S�3 00�4iA7 H1 3200 CFM 3200 2.5 CV 2/ MH821 NOTE (1)

RETURN TERMINAL UNIT SCHEDULE � FOURTH FLOOR INTERSTITIAL A1 � A7

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

R�1 00�4iA1 H1 3200 CFM 3200 N/A CV 2/ MH821 TRACKS S�1, NOTE (1)

R�2 00�4iA4 H1 3200 CFM 3200 N/A CV 2/ MH821 TRACKS S�2, NOTE (1)

R�3 00�4iA7 H1 3200 CFM 3200 N/A CV 2/ MH821 TRACKS S�3, NOTE (1)

FAN COIL UNIT SCHEDULE � BUILDING#4 LOBBY

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

FCU�1 04�2A5 4J2 � 2/ MH820 NOTE (2)

FCU�2 04�2A5 4J2 � 2/ MH820 NOTE (2)

FCU�3 04�2A5 4J2 � 2/ MH820 NOTE (2)

FCU�4 04�3A5 4J2 � 2/ MH820 NOTE (2)

FCU�5 04�3A5 4J2 � 2/ MH820 NOTE (2)

FCU�6 04�4A5 4J2 � 2/ MH820 NOTE (2)

FCU�7 04�4A5 4J2 � 2/ MH820 NOTE (2)

FCU�8 04�5A5 4J2 � 2/ MH820 NOTE (2)

FCU�9 04�5A5 4J2 � 2/ MH820 NOTE (2)

FCU�10 04�6A5 4J2 � 2/ MH820 NOTE (2)

FCU�11 04�6A5 4J2 � 2/ MH820 NOTE (2)

FCU�12 04�7A5 4J2 � 2/ MH820 NOTE (2)

FCU�13 04�7A5 4J2 � 2/ MH820 NOTE (2)

FCU�14 04�8A5 4H6 � 2/ MH820 NOTE (2)

FAN COIL UNIT SCHEDULE � BUILDING#5 LOBBY

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

FCU�1 05�2A6 4J2 � 2/ MH820 NOTE (2)

FCU�2 05�2A6 4J2 � 2/ MH820 NOTE (2)

FCU�3 05�3A6 4J2 � 2/ MH820 NOTE (2)

FCU�4 05�3A6 4J2 � 2/ MH820 NOTE (2)

FCU�5 05�4A6 4J2 � 2/ MH820 NOTE (2)

FCU�6 05�4A6 4J2 � 2/ MH820 NOTE (2)

FCU�7 05�5A6 4J2 � 2/ MH820 NOTE (2)

FCU�8 05�5A6 4J2 � 2/ MH820 NOTE (2)

FCU�9 05�6A6 4J2 � 2/ MH820 NOTE (2)

FCU�10 05�6A6 4J2 � 2/ MH820 NOTE (2)

FCU�11 05�7A6 4J2 � 2/ MH820 NOTE (2)

FCU�12 05�7A6 4J2 � 2/ MH820 NOTE (2)

FCU�13 05�8A6 4H7 � 2/ MH820 NOTE (2)

FCU�14 05�2A6 4A1 � 2/ MH820 NOTE (2)

RFI 01739: 04-1A5

RFI 01738: 05-4A6

RFI 01871: DULICATED

FROM 4TH FLOOR

SCHEDULE ABOVE

RFI 01871: DULICATED

FROM 4TH FLOOR

SCHEDULE ABOVE

jamie.dorland Text Box RFI 07289.1: VAV to be deleted and replaced with a section of duct.

jamie.dorland Arrow

File details come from the government source that posted it. Updated .