VAMC Bedford MA UPS Preventative Maintenance Report 6-24-2025.pdf
PDF 534 KB Posted
- Solicitation number
- 36C24126Q0223
About this file
This is a preventative maintenance (PM) report prepared by EOLA Power for Antoncecchi Power LLC (AP) detailing the condition and service recommendations for three uninterruptible power supply (UPS) systems and associated batteries at the Department of Veterans Affairs Bedford VAMC facility in Bedford, Massachusetts. The report is dated June 24, 2025, with job number MPM13819.
The assessment covers three UPS units: UPS-2 Single Phase (APC Symmetra SYMSTRF, 16 KVA, manufactured 6/10/2003), UPS-1 Single Phase (APC Symmetra SYMSTRF, 16 KVA, manufactured 5/1/2016), and RK-H09 (R13) Three Phase (APC Symmetra PX, 40 KVA, manufactured 3/16/2005). Critical findings include that UPS-2 has a faulty L5 power module and is past end-of-life requiring replacement; its batteries (CSB UPS12460F2FR) have reached end-of-life. UPS-1 currently requires no action, with all systems operating normally and voltage readings within acceptable ranges (135.9-137.1 Vdc). The three-phase RK-H09 unit has a PDU internal communication alarm requiring replacement of the power monitoring circuit module with complete UPS shutdown; its batteries (CSB GP 1272 F2, 48 units) have reached end-of-life with voltage readings of 106.4-107.8 Vdc. Additionally, multiple VRLA battery packs across the three units require replacement due to age and condition, with jars trending toward failure. UPS-1's battery pack (Interstate SLA1079) remains in acceptable condition with no immediate recommendations. All units underwent visual inspection, mechanical verification, thermal checks, and electrical measurements, with detailed voltage readings and load analysis provided for each system.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24126Q0223_2.docx | DOCX document | |
| 36C24126Q0223_1.docx | DOCX document | |
| Answers to Combined Questions from Offerors_Due Date 1-14-26.docx | DOCX document | |
| P07 Wage Determinations.pdf | ||
| 36C24126Q0223.docx | DOCX document | |
| RFI 1 Answers Combined Questions from Offerors.docx | DOCX document | |
| 20250718_142323443_iOS.jpg | JPG image | |
| 20250718_142331204_iOS.jpg | JPG image | |
| 20250718_142326351_iOS.jpg | JPG image | |
| RFI 2 Answers UPS Bedford_Questions from Vendors_Due Date 1-14-26.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Executive Summary
UPS is online with fault alarm -- Bad Power Module L5. Thermal Checks OK. Batteries OK. Battery module voltage readings range 137.4 - 137.9. No other discrepancies. Current battery cabinet temperature is 68 Deg F.
Replace faulty L5 Power Module.
Unit is past End of Life and is recommended to be replaced.
UPS Single Phase - UPS-2 Bldg. 61 Room 137
Comments:
Recommendations:
Batteries have reached End of Life and are recommended to be replaced.
Batteries have reached End of Life and are recommended to be replaced.
VRLA Battery - UPS-2 S1 Bldg. 61
Comments:
Recommendations:
UPS is online with no alarms. Thermal Checks OK. Batteries OK. Batteries have reached EOL.
Completed self-test. Battery module voltage readings range 106.4 - 107.8 Vdc. No other discrepancies.
Current battery cabinet temperature is 85 Deg F. Room had problem with ac this time and is being addressed.
Additional Notes:
PDU has an internal communication alarm. The power monitoring circuit module needs to be replaced. This will require a complete UPS shutdown and disconnecting the main AC input power.
PDU has an internal communication alarm. The power monitoring circuit module needs to be replaced. This will require a complete UPS shutdown and disconnecting the main AC input power.
UPS 3 Phase - RK-H09 (R13) Bldg 3 Room 107
Comments:
Recommendations:
Client: Antoncecchi Power LLC (AP)
Client Address: Department of Veterans Affairs Bedford VAMC NCO1 200 Springs Road
Job#: MPM13819
Report Date: 6/24/2025
Bedford, MA 01730
Minor PM - Antoncecchi Power LLC (AP)
EOLA Power 8782 NW 18th Terrace, Miami, FL 33172 TEL: (800)399-7414 http://eolapower.com
Batteries OK, but need to be replaced due to age soon. Jars trending towards failure.
Batteries need to be replaced due to age and condition.
VRLA Battery - Bldg 3 Room 107
Comments:
Recommendations:
UPS is online with no alarms. Thermal Checks OK. Batteries OK. Battery module voltage readings range 135.9
- 137.1 Vdc. No other discrepancies. Current battery cabinet temperature is 73 Deg F.
No discrepancies or recommendations at this time.
UPS Single Phase - UPS-1 Bldg. 61 Room 137
Comments:
Recommendations:
Batteries OK. Battery module voltage readings range 135.9 - 137.1 Vdc. No other discrepancies. Current battery cabinet temperature is 73 Deg F.
No discrepancies or recommendations at this time.
VRLA Battery - UPS-2 Batt Packs Bldg. 61
Comments:
Recommendations:
Client: Antoncecchi Power LLC (AP)
Client Address: Department of Veterans Affairs Bedford VAMC NCO1 200 Springs Road
Job#: MPM13819
Report Date: 6/24/2025
Bedford, MA 01730
Minor PM - Antoncecchi Power LLC (AP)
EOLA Power
Client: VAMC Bedford, MA
Client Address: Department of Veterans Affairs Bedford VAMC
NCO1
200 Springs Road
Client Contact: Gaurav Dhakal
Job#: 13819
Report Date: 6/24/2025
Bedford, MA 01730 Report ID: 28724
Customer Asset ID: UPS-2 APC Symmetra SYMSTRF S/N CA0324110569
Regarding Minor PM on (3) UPS Units & Batteries
Service Comments UPS is online with fault alarm -- Bad Power Module L5. Thermal Checks OK. Batteries OK. Battery module voltage readings range 137.4 - 137.9. No other discrepancies. Current battery cabinet temperature is 68 Deg F.
UPS Single Phase - UPS-2 Customer Equip ID:
Bldg. 61 Room 137Serial#:
Manufacturer:
Model: 6/10/2003
APC
Symmetra SYMSTRF
CA0324110569
UPS-2
Manufactured:
Location:
UPS Single Phase Details
Part# Input Breaker Amp Rating 100
Power Factor .90 DC Breaker Amp Rating N/A
Area Served N/A Filter Size N/A
Load Multiplier 1 Internal Maintenance Bypass
Maintenance Bypass None External Maintenance Bypass No
Volts In 208 Battery Module Model # SYBATT
Volts Out 120/208/240 Battery Make CSB
KVA 16 Battery Model UPS12460F2-FR
Total Batteries 230 Total Number of Battery Modules 23
I.P. ADDRESS N/A Total Number of Batteries Per Module 10
Air Filter Size N/A DC Cap Date Code (Year)
Air Filter Quantity N/A AC Input Cap Date Code (Year)
Service Recommendations Replace faulty L5 Power Module.
Unit is past End of Life and is recommended to be replaced.
Minor PM - Antoncecchi Power LLC (AP) UPS Single Phase - UPS-2
EOLA Power
MONITORING DEVICE INSTALLED N/A AC Output Date Code (Year)
KW 11.2 Commutation Cap Date Code (Year)
Phases 1 Power Supply Cap Date Code (Year)
Output Breaker Amp Rating N/A Fans Date Code (Year)
Visual and Mechanical Inspection
UPS is online with no alarms Pass Work Space Clear Pass
Cover on EPO Switch Pass Proper Ventilation Pass
Damaged Components or Cables Pass First Visit to Site £
Hardware and connections Pass MBP Labeled Correctly £
Unit cleanliness, vacuumed, clean exterior Pass Transfer to Static Bypass £
Fans normal operation Pass Transfer from Static Bypass to Normal £
SNMP Card Pass Transfer to MBP (When Applicable) £
Room Temperature OK? Pass Verify all Alarms R
Safety Gear available Pass Input and Output Voltage Waveforms £
Clean work area Pass Input and Output Current Waveforms £
Minor PM - Antoncecchi Power LLC (AP) UPS Single Phase - UPS-2
EOLA Power
UPS Input
Voltage L1 204.4 Current - L1 7
Voltage L2 N/A Current - L2 N/A
UPS Bypass Input
Bypass Input Voltage L1 Bypass Input Current L1
Bypass Input Voltage L2 Bypass Input Current L2
UPS Output
Voltage L1 211.9 Current - L1 5.3
Voltage L2 N/A Current - L2 N/A
Output Load
Load kW 1.01 KVA (from Details) 16
Load kVA 1.12 KW (from Details) 11.2
Percentage of Load kW 9.02 POWER FACTOR .90
Percentage of Load kVA 7.02
Rectifier and Battery Measurements
Total DC Voltage (VDC) 137 AC Ripple Voltage (VAC) 0
+Positive to Ground (VDC) 0.1 DC Current (IDC) 0
-Negative to Ground (VDC) 0.1 AC Current (IAC) 0
Minor PM - Antoncecchi Power LLC (AP) UPS Single Phase - UPS-2
EOLA Power
UPS Single Phase Images
UPS Nameplate Pic
UPS Profile Pic
Battery Profile Pic
Minor PM - Antoncecchi Power LLC (AP) UPS Single Phase - UPS-2
EOLA Power
Battery Date Code
Equipment Location Nameplate
Minor PM - Antoncecchi Power LLC (AP) UPS Single Phase - UPS-2
EOLA Power
Bedford VAMC
NCO1
200 Springs Road
Client Contact: Gaurav Dhakal
Job#: 13819
Report Date: 6/24/2025
Bedford, MA 01730 Report ID: 28727
Customer Asset ID: UPS-2 S1 CSB UPS12460F2FR S/N
Regarding Minor PM on (3) UPS Units & Batteries
Service Comments Batteries have reached End of Life and are recommended to be replaced.
VRLA Battery - UPS-2 S1 Customer Equip ID:
Bldg. 61Serial#:
Manufacturer:
Model: 8/13/2020
CSB
UPS12460F2FR
UPS-2 S1
Manufactured:
Location:
APC
Symmetra SYMSTRF CA0324110569Serial#:
Manufacturer:
Model:
Customer Equip ID:
Bldg. 61 Room 137 6/10/2003
UPS-2
Manufactured:
Location:
Parent UPS Single Phase Infomation
VRLA Battery Details
Sealed (Dry) or Flooded (Wet Cell) Dry Number of Strings 23
Battery Housing Battery Pack Amp Hours 7
Battery Type (Voltage) 12 Jars per strings 10
Service Recommendations Batteries have reached End of Life and are recommended to be replaced.
Minor PM - Antoncecchi Power LLC (AP) VRLA Battery - UPS-2 S1
EOLA Power
Battery Readings
Room Temperature 68 Sulfurous Odor? Pass
Battery Temperature 69 Total DC Voltage (VDC) 137
Is Container and Cover OK? Pass +Positive to Ground (VDC) 0.1
Bulging/Swollen? Pass -Negative to Ground (VDC) 0.1
Missing Connector or Hardware? Pass AC Ripple Voltage (VAC) 0.1
Leaking? Pass DC Current (IDC) 0.1
Corrosion? Pass AC Current (IAC) 0.1
Minor PM - Antoncecchi Power LLC (AP) VRLA Battery - UPS-2 S1
EOLA Power
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Replace Watch Baseline
VRLA Battery DC Volts Chart
Battery#
Minor PM - Antoncecchi Power LLC (AP) VRLA Battery - UPS-2 S1
EOLA Power
Battery# ConditionConductanceDC Volts VRLA Battery Tests
1 137.100 Pass
2 137.200 Pass
3 137.300 Pass
4 137.200 Pass
5 137.300 Pass
6 137.300 Pass
7 137.100 Pass
8 137.200 Pass
9 137.200 Pass
10 137.300 Pass
11 137.100 Pass
12 137.100 Pass
Battery# ConditionConductanceDC Volts VRLA Battery Tests
13 137.000 Pass
14 137.000 Pass
15 137.200 Pass
16 137.300 Pass
17 137.300 Pass
18 137.100 Pass
19 137.300 Pass
20 137.000 Pass
21 137.100 Pass
22 137.200 Pass
23 137.200 Pass
Minor PM - Antoncecchi Power LLC (AP) VRLA Battery - UPS-2 S1
EOLA Power
Bedford VAMC
NCO1
200 Springs Road
Client Contact: Gaurav Dhakal
Job#: 13819
Report Date: 6/24/2025
Bedford, MA 01730 Report ID: 28725
Customer Asset ID: RK-H09 (R13) APC Symmetra PX S/N PD0535338629
Regarding Minor PM on (3) UPS Units & Batteries
Service Comments UPS is online with no alarms. Thermal Checks OK. Batteries OK. Batteries have reached EOL.
Completed self-test. Battery module voltage readings range 106.4 - 107.8 Vdc. No other discrepancies.
Current battery cabinet temperature is 85 Deg F. Room had problem with ac this time and is being addressed.
Additional Notes:
PDU has an internal communication alarm. The power monitoring circuit module needs to be replaced. This will require a complete UPS shutdown and disconnecting the main AC input power.
UPS 3 Phase - RK-H09 (R13) Customer Equip ID:
Bldg 3 Room 107Serial#:
Manufacturer:
Model: 3/16/2005
APC
Symmetra PX
PD0535338629
RK-H09 (R13)
Manufactured:
Location:
UPS 3 Phase Details
Part# SYCF40KF Air Filter Size N/A
Power Factor Air Filter Quantity N/A
Maintenance Bypass Internal Bypass Only Phases 3
Volts In 120/208 Internal Maintenance Bypass
Volts Out 208 DC Cap Date Code (Year) 0
KVA 40 AC Input Cap Date Code (Year)
KW 40 AC Output Date Code (Year)
Battery Make CSB Commutation Cap Date Code (Year)
Service Recommendations PDU has an internal communication alarm. The power monitoring circuit module needs to be replaced. This will require a complete UPS shutdown and disconnecting the main AC input power.
Minor PM - Antoncecchi Power LLC (AP) UPS 3 Phase - RK-H09 (R13)
EOLA Power
Battery Model GP 1272 F2 Power Supply Cap Date Code (Year)
Total Batteries 384 Fans Date Code (Year) 2005
Visual and Mechanical Verificaiton
UPS is online with no alarms Pass SNMP Card Pass
Cover on EPO Switch Pass Room Temperature OK? Pass
Damaged Components or Cables Pass Safety Gear available Pass
Hardware and connections Pass Clean work area Pass
Unit cleanliness, vacuumed, clean exterior Pass Work Space Clear Pass
Fans normal operation Pass Proper Ventilation Pass
Transfer Verification(Major Only)
First Visit to Site £ Transfer to MBP (When Applicable) £
MBP Labeled Correctly £ Verify all Alarms R
Transfer to Static Bypass £ Input and Output Voltage Waveforms R
Transfer from Static Bypass to Normal £ Input and Output Current Waveforms R
Minor PM - Antoncecchi Power LLC (AP) UPS 3 Phase - RK-H09 (R13)
EOLA Power
Voltage A-B Current - A N/A
Voltage B-C Current - B N/A
Voltage C-A Current - C N/A
Voltage A-N N/A
Voltage B-N N/A
Voltage C-N N/A
UPS Bypass Input
Bypass Input Voltage A-B Bypass Input Current A 58
Bypass Input Voltage B-C Bypass Input Current B 55
Bypass Input Voltage C-A Bypass Input Current C 57
Bypass Input Voltage A-N 118.5
Bypass Input Voltage B-N 118.6
Bypass Input Voltage C-N 118
UPS Output Load
Voltage A-B 207 Current - A 47
Voltage B-C 206 Current - B 69
Voltage C-A 207 Current - C 43
Voltage A-N N/A
Voltage B-N N/A
Voltage C-N N/A
Output Load
Load kW 0 Percentage of Load kVA 47.37
Load kVA 18.95 KVA (from Details) 40
Percentage of Load kW 0 Power Factor
Minor PM - Antoncecchi Power LLC (AP) UPS 3 Phase - RK-H09 (R13)
EOLA Power
UPS 3 Phase Images
UPS Nameplate
UPS Profile Picture
Minor PM - Antoncecchi Power LLC (AP) UPS 3 Phase - RK-H09 (R13)
EOLA Power
Minor PM - Antoncecchi Power LLC (AP) UPS 3 Phase - RK-H09 (R13)
EOLA Power 8782 NW 18th Terrace, Miami, FL 33172
Bedford VAMC
NCO1
200 Springs Road
Client Contact: Gaurav Dhakal
Job#: 13819
Report Date: 6/24/2025
Bedford, MA 01730 Report ID: 28728
Customer Asset ID: CSB GP 1272 F2 S/N
Regarding Minor PM on (3) UPS Units & Batteries
Service Comments Batteries OK, but need to be replaced due to age soon. Jars trending towards failure.
VRLA Battery - Customer Equip ID:
Bldg 3 Room 107Serial#:
Manufacturer:
Model: 6/7/2020
CSB
GP 1272 F2 Manufactured:
Location:
APC
Symmetra PX PD0535338629Serial#:
Manufacturer:
Model:
Customer Equip ID:
Bldg 3 Room 107 3/16/2005
RK-H09 (R13)
Manufactured:
Location:
Parent UPS 3 Phase Infomation
VRLA Battery Details
Sealed (Dry) or Flooded (Wet Cell) Dry Number of Strings 24
Battery Housing Battery Pack Amp Hours 7
Battery Type (Voltage) 12 Jars per strings 16
Service Recommendations Batteries need to be replaced due to age and condition.
Minor PM - Antoncecchi Power LLC (AP) VRLA Battery -
EOLA Power
Room Temperature Sulfurous Odor? Pass
Battery Temperature Total DC Voltage (VDC) 212
Is Container and Cover OK? Pass +Positive to Ground (VDC) 106
Bulging/Swollen? Pass -Negative to Ground (VDC) 106
Missing Connector or Hardware? Pass AC Ripple Voltage (VAC) 0.1
Leaking? Pass DC Current (IDC) 0.1
Corrosion? Pass AC Current (IAC) 0.1
Minor PM - Antoncecchi Power LLC (AP) VRLA Battery -
EOLA Power
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
Replace Watch Baseline
VRLA Battery DC Volts Chart
Battery#
Minor PM - Antoncecchi Power LLC (AP) VRLA Battery -
EOLA Power
41 42 43 44 45 46 47 48
Replace Watch Baseline
VRLA Battery DC Volts Chart
Battery#
Minor PM - Antoncecchi Power LLC (AP) VRLA Battery -
EOLA Power
1 106.500 Pass
2 106.500 Pass
3 106.500 Pass
4 106.500 Pass
5 106.500 Pass
6 106.500 Pass
7 106.500 Pass
8 106.500 Pass
9 106.500 Pass
10 106.500 Pass
11 106.500 Pass
12 106.500 Pass
13 106.500 Pass
14 106.500 Pass
15 106.500 Pass
16 106.500 Pass
17 106.500 Pass
18 106.500 Pass
19 106.500 Pass
20 106.500 Pass
21 106.500 Pass
22 106.500 Pass
23 106.500 Pass
24 106.500 Pass
Battery# ConditionConductanceDC Volts VRLA Battery Tests
25 106.500 Pass
26 106.500 Pass
27 106.500 Pass
28 106.500 Pass
29 106.500 Pass
30 106.500 Pass
31 106.500 Pass
32 106.500 Pass
33 106.500 Pass
34 106.500 Pass
35 106.500 Pass
36 106.500 Pass
37 106.500 Pass
38 106.500 Pass
39 106.500 Pass
40 106.500 Pass
41 106.500 Pass
42 106.500 Pass
43 106.500 Pass
44 106.500 Pass
45 106.500 Pass
46 106.500 Pass
47 106.500 Pass
48 106.500 Pass
Minor PM - Antoncecchi Power LLC (AP) VRLA Battery -
EOLA Power
Bedford VAMC
NCO1
200 Springs Road
Client Contact: Gaurav Dhakal
Job#: 13819
Report Date: 6/24/2025
Bedford, MA 01730 Report ID: 28726
Customer Asset ID: UPS-1 APC Symmetra SYMSTRF S/N ED9823076441
Regarding Minor PM on (3) UPS Units & Batteries
Service Comments UPS is online with no alarms. Thermal Checks OK. Batteries OK. Battery module voltage readings range 135.9 - 137.1 Vdc. No other discrepancies. Current battery cabinet temperature is 73 Deg F.
UPS Single Phase - UPS-1 Customer Equip ID:
Bldg. 61 Room 137Serial#:
Manufacturer:
Model: 5/1/2016
APC
Symmetra SYMSTRF
ED9823076441
UPS-1
Manufactured:
Location:
UPS Single Phase Details
Part# Input Breaker Amp Rating N/A
Power Factor .90 DC Breaker Amp Rating N/A
Area Served N/A Filter Size N/A
Load Multiplier 1 Internal Maintenance Bypass
Maintenance Bypass None External Maintenance Bypass
Volts In 208 Battery Module Model # SYBATT
Volts Out 120/208/240 Battery Make Interstate
KVA 16 Battery Model SLA1079
Total Batteries 100 Total Number of Battery Modules 10
I.P. ADDRESS N/A Total Number of Batteries Per Module 10
Air Filter Size N/A DC Cap Date Code (Year) N/A
Air Filter Quantity N/A AC Input Cap Date Code (Year) N/A
Service Recommendations No discrepancies or recommendations at this time.
Minor PM - Antoncecchi Power LLC (AP) UPS Single Phase - UPS-1
EOLA Power
MONITORING DEVICE INSTALLED AC Output Date Code (Year) N/A
KW 11.2 Commutation Cap Date Code (Year) N/A
Phases 1 Power Supply Cap Date Code (Year) N/A
Output Breaker Amp Rating N/A Fans Date Code (Year) N/A
Visual and Mechanical Inspection
UPS is online with no alarms Pass Work Space Clear Pass
Cover on EPO Switch Pass Proper Ventilation Pass
Damaged Components or Cables Pass First Visit to Site £
Hardware and connections Pass MBP Labeled Correctly £
Unit cleanliness, vacuumed, clean exterior Pass Transfer to Static Bypass £
Fans normal operation Pass Transfer from Static Bypass to Normal £
SNMP Card Pass Transfer to MBP (When Applicable) £
Room Temperature OK? Pass Verify all Alarms R
Safety Gear available Pass Input and Output Voltage Waveforms £
Clean work area Pass Input and Output Current Waveforms £
Minor PM - Antoncecchi Power LLC (AP) UPS Single Phase - UPS-1
EOLA Power
Voltage L1 200.9 Current - L1
Voltage L2 N/A Current - L2 N/A
UPS Bypass Input
Bypass Input Voltage L1 Bypass Input Current L1
Bypass Input Voltage L2 Bypass Input Current L2
UPS Output
Voltage L1 204.3 Current - L1 6.7
Voltage L2 N/A Current - L2 N/A
Output Load
Load kW 1.23 KVA (from Details) 16
Load kVA 1.37 KW (from Details) 11.2
Percentage of Load kW 11 POWER FACTOR .90
Percentage of Load kVA 8.56
Rectifier and Battery Measurements
Total DC Voltage (VDC) 136.5 AC Ripple Voltage (VAC) 0.1
+Positive to Ground (VDC) 0.1 DC Current (IDC) 0
-Negative to Ground (VDC) 0.1 AC Current (IAC) 0
Minor PM - Antoncecchi Power LLC (AP) UPS Single Phase - UPS-1
EOLA Power
UPS Single Phase Images
UPS Nameplate Pic
UPS Profile Pic
Battery Profile Pic
Minor PM - Antoncecchi Power LLC (AP) UPS Single Phase - UPS-1
EOLA Power
Battery Date Code
Minor PM - Antoncecchi Power LLC (AP) UPS Single Phase - UPS-1
EOLA Power
Bedford VAMC
NCO1
200 Springs Road
Client Contact: Gaurav Dhakal
Job#: 13819
Report Date: 6/24/2025
Bedford, MA 01730 Report ID: 28729
Customer Asset ID: UPS-2 Batt Packs Interstate SLA1079 S/N
Regarding Minor PM on (3) UPS Units & Batteries
Service Comments Batteries OK. Battery module voltage readings range 135.9 - 137.1 Vdc. No other discrepancies. Current battery cabinet temperature is 73 Deg F.
VRLA Battery - UPS-2 Batt Packs Customer Equip ID:
Bldg. 61Serial#:
Manufacturer:
Model: 8/31/2022
Interstate
SLA1079
UPS-2 Batt Packs Manufactured:
Location:
APC
Symmetra SYMSTRF ED9823076441Serial#:
Manufacturer:
Model:
Customer Equip ID:
Bldg. 61 Room 137 5/1/2016
UPS-1
Manufactured:
Location:
Parent UPS Single Phase Infomation
VRLA Battery Details
Sealed (Dry) or Flooded (Wet Cell) Dry Number of Strings 10
Battery Housing Battery Pack Amp Hours 7
Battery Type (Voltage) 12 Jars per strings 10
Service Recommendations No discrepancies or recommendations at this time.
Minor PM - Antoncecchi Power LLC (AP) VRLA Battery - UPS-2 Batt Packs
EOLA Power
Room Temperature Sulfurous Odor? Pass
Battery Temperature Total DC Voltage (VDC) 137
Is Container and Cover OK? Pass +Positive to Ground (VDC) 0.1
Bulging/Swollen? Pass -Negative to Ground (VDC) 0.1
Missing Connector or Hardware? Pass AC Ripple Voltage (VAC) 0.1
Leaking? Pass DC Current (IDC) 0.1
Corrosion? Pass AC Current (IAC) 0.1
Minor PM - Antoncecchi Power LLC (AP) VRLA Battery - UPS-2 Batt Packs
EOLA Power
1 2 3 4 5 6 7 8 9 10
Replace Watch Baseline
VRLA Battery DC Volts Chart
Battery#
Minor PM - Antoncecchi Power LLC (AP) VRLA Battery - UPS-2 Batt Packs
EOLA Power
1 137.000 Pass
2 136.700 Pass
3 136.500 Pass
4 137.000 Pass
5 137.000 Pass
Battery# ConditionConductanceDC Volts VRLA Battery Tests
6 137.100 Pass
7 137.300 Pass
8 136.800 Pass
9 136.800 Pass
10 136.500 Pass
Minor PM - Antoncecchi Power LLC (AP) VRLA Battery - UPS-2 Batt Packs
EOLA Power
File details come from the government source that posted it. Updated .