Upgrade Nurse Call Drawings Part6.pdf

PDF 2 MB Posted

Attached to
Z2DZ-- Project 626A4-20-104 - Upgrade Nurse Call System
Solicitation number
36C24921R0141
Issued by

About this file

This federal contract opportunity notice seeks proposals for an upgrade of the nurse call system at the Alvin C. York VA Medical Center campuses in Murfreesboro and Nashville, Tennessee. The contractor will be responsible for all general construction, electrical work, and low voltage work required to upgrade the nurse call system, including labor, materials, equipment and supervision. The project specifications and drawings are provided in the opportunity description. The contracting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9.

View the file

Other files

File Type Posted
36C24921R0141 0008.docx DOCX document
JA Brand Name Nurse Call System.pdf PDF
36C24921R0141 0007.docx DOCX document
36C24921R0141 0006.docx DOCX document
36C24921R0141 0005.docx DOCX document
WD TN20220083 01-07-2022 Davidson County TN.pdf PDF
36C24921R0141 0004.docx DOCX document
WD TN20220100 01-07-2022 Rutherford County TN.pdf PDF
36C24921R0141 0003.docx DOCX document
36C24921R0141 0002.docx DOCX document
Government Answers to Industry Questions Upgrade Nurse Call System.pdf PDF
Nashville Nurse Call Site Visit 12.20.21.pdf PDF
36C24921R0141 0001.docx DOCX document
Murfreesboro Nurse Call Site Visit 12.21.21.pdf PDF
VHA Supplemental Contract Requirements for Combatting COVID-19 Updated 12-14-2021.pdf PDF
WD TN20210083 07_09_2021_Davidson.pdf PDF
Upgrade Nurse Call Drawings Part4.pdf PDF
Price Proposal Template.xlsx XLSX spreadsheet
36C24921R0141_1.docx DOCX document
Contractor EMR Certification Form.pdf PDF
PPQ-Template.pdf PDF
Upgrade Nurse Call Drawings Part3.pdf PDF
Upgrade Nurse Call Drawings Part2.pdf PDF
Upgrade Nurse Call Drawings Part5.pdf PDF
General Conditions Breakout.xlsx XLSX spreadsheet
Specs Combined Upgrade Nurse Call.pdf PDF
Upgrade Nurse Call Drawings Part1.pdf PDF
WD TN20210100 07_09_2021_Rutherford.pdf PDF
RFI Form 36C24921R0141.pdf PDF
Show all 29

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BLDG 1

LINEN

112I

STAFF

TOILET

112C

TELE

105D

STAIR

- 2

152A

NURSES

STATION

105G

CORRIDOR

CORRIDOR

TLT

114A

CORRIDOR

LOBBY

WAITING

RECOVERY

CORR

STAFF

LOUNGE

LOCKERS

146A

PATH LAB

OFFICE

SECRETARY

CHUTE

LABORATORY CHIEF

142PATHOLOGY

LOGISTICS

PACU

TOILET

WAITING

STORAGE

TOILET

TELE

ELECTRICAL

CORRIDOR

CONTROL

112L

ON CALL

HAC

ISOLATION

112G

CORRIDOR

CLEAN CORE

SUPPORT AREA

SCRUB

135E

CORRIDOR

CORRIDOR

STAIR - 1

102A

STORAGE

CLEAN

SUPPLY

SOILED

UTILITY

112M

ELECTRICAL

110TELE

112B

MED

112K

TOILET

ON CALL

PATIENT

NUTRITION

112D

STORAGE

112A

OFFICE

112E

ANTE

112F

LINEN

105C

STORAGE

105B

SOIL

UTILITY

105A

CHEMISTRY

CLINICAL

LABORATORY

IMMEDIATE

RESPONSE

139Q

SPECIMEN

ACCESSIONING

HEMATOLOGY LAB

URINE AND FECES

139P

BLOOD

COLLECTION

139O

TOILET

SHAFT

101A

BLOOD

BANK

139B

HAC

139N

145A

HISTOLOGY

CYTOLOGY

145B

STORAGE SUPPLIES AND

EQUIPMENT

139M

MICROBIOLOGY

IMMUNOLOGY

139I

MICROBIOLOGY

139R A&MMS

139L

FLOUROSCOPY

MICRO

139K

TRANSFER

139J

GLASS

WASH

139H

LABORATORY

COMPUTER

INFO

139G

MYCOLOGY

139F

ANCILLARY

TESTING

139E

TOXICOLOGY

139D

CLINICAL

LAB

SCIENTIST

139C

ANCILLARY

TESTING

CO-ORDR

139A

OPERATING ROOM 2

OPERATING ROOM 1

STERILIZATION

136A

HAC

NURSE

MGR

HAC

135A

SCRUB

INSTRUMENT

PREP

117A CYSTOSCOPE

SUITE

X-RAY

CONTROL

STORAGE

116A

LOUNGE

135B

LOCKERS

LOCKERS

ENTRY

121A

ENTRY

123A

SHAFT

135F

ELECTRICAL

STERILE

SUPPLIES

135C

ANESTHESIA

WORKROOM

STERILE

EQUIPMENT

135D

HAC

MED GAS

STORAGE

133ANESTHETIST

NURSE

ANESTHETIST

PHYSICIAN

PHYSICIAN

PHYSICIAN

127NURSE

ANESTHETIST

SURGICAL

SUPPLY

PHYSICIAN

NURSING

CORRIDOR

TLT.

TLT

112N

EQUIP

STORAGE

STATION

STATION

STATION

STATION

STATION

STATION

N

N

N

N

N

C

E

N

N

N

N

N

N

N

C

M

M

M

N

N C

C

C

C

E

N

N

N

C

C

C

C

C

C

C

C

S

D D D

D

EXISTING PANEL-

PANEL '2C7E2'

D

D

N N

B B

N N

D

TK405

P

P

P

P

P

P P

P

P

P

TO

BUILDING

TO BUILDING 3

TO BUILDING 1

N N

E

Z

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

"G" FLOOR

EXISTING

HEADWALL UNIT

C B

"G" FLOOR

EXISTING

HEADWALL UNIT

P

C

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

JULY 19, 2021 ADRJVE

626A4-20-10420-171

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.

NURSE CALL PATIENT BED INTERFACE RECEPTACLE (37 PIN)

WALL RATINGS

1 HR FIRE WALL

1 HR FIRE SMOKE WALL

2 HOUR FIRE WALL

2 HOUR FIRE SMOKE WALL

NON-RATED SMOKE PARTITION

SMOKE RESISTIVE HAZARDOUS

ROOM ENCLOSURE

107Engineers Architects U.S. Department of Veterans Affairs

TVHS- NASHVILLE CAMPUS

1310 24TH AVE S,NASHVILLE, TENNESSEE 37212

TVHS- ALVIN C. YORK CAMPUS

3400 LEBANON PIKE, MURFREESBORO, TENNESSEE 37129

UPGRADE NURSE CALL SYSTEM

NASHVILLE/MURFREESBORO

CAMPUS

NURSE CALL EQUIPMENT CABINETNCE

NURSE CALL SYMBOL LEGEND

SYMBOL DESCRIPTION

A NURSE CALL AUXILIARIES

B ENHANCED NURSE CALL, STAND ALONE, CODE

BLUE STATION WITH CLEAR BUTTON COVER

D NURSE CALL DUTY STATION

NURSE CALL EMERGENCY STATION

(SEE T-001 FOR MORE SPECIFICS, PB - PUSH BUTTON NO

PULL CORD, HS - HIGH SECURITY STEEL COVER PLATE)

M NURSE CALL MASTER STATION/CONSOLE

NURSE CALL PATIENT STATION

(PB - PUSH BUTTON, M - MICROPHONE, K -KEYED, HS - HIGH

SECURITY STEEL COVER PLATE)

N NURSE CALL DOME LIGHT

(Z - ZONE LIGHT, V - VANDAL RESISTANT)

N NURSE CALL DOME LIGHT - WALL MOUNTED

BUTTON STATION WITH CLEAR BUTTON COVER

NUMBER OF BUTTONS (1 - SINGLE BUTTON, 2 - DOUBLE

BUTTON)

BUTTON PROGRAMING (B- CODE BLUE, P - PUSH FOR HELP,

S - STAFF ASSIST)

C

NURSE CALL PATIENT STATION WITH CALL CORD INCLUDES:

- CODE BLUE

- STAFF ASSIST

- AUDIO

- CLEAR BUTTON COVER

(2 - DUAL PATIENT STATION, HS - VANDAL RESISTANT HIGH

SECURITY STEEL COVER PLATE)

E

N

S S S S S S

P

Z

M

PB

S

T NURSE CALL STAFF TERMINAL

MATV OR CATV WALL MOUNTED

MATV OR CATV CEILING MOUNTED

NURSE CALL PATIENT STATION WITH PILLOW SPEAKER (GET

WELL) INCLUDES:

- CODE BLUE

- STAFF ASSIST

- AUDIO

- CLEAR BUTTON COVER

(2 - DUAL PATIENT STATION, HS - VANDAL RESISTANT HIGH

SECURITY STEEL COVER PLATE)

HS

R

BS

P

117TN121

MURFREESBORO BUILDING 117 - "A"

FLOOR NURSE CALL PLAN

1 MURFREESBORO BUILDING 117 - "A" FLOOR NURSE CALL PLAN

SCALE: 1/8" = 1' 0"

N O

R

TH

TRUE

0 4 8 16

1. EXISTING NURSE CALL DEVICES IN EXISTING

PATIENT HEADWALL TO BE REPLACED WITH

NEW NURSE CALL DEVICES.

2. NEW TV OUTLET REPLACING EXISTING.

INTERCONNECT TELEVISIONS WITH NEW

NURSE CALL SYSTEM.

PACU

SURGERY

A. THE EXISTING CONDITIONS, DEVICES,

EQUIPMENT, CABLING, AND CONDUITS ARE

BASED ON THE BEST AVAILABLE INFORMATION

AT THE TIME OF SURVEY AND VISUAL

INSPECTION. VERIFY EXISTING CONDITIONS.

B. ALL EXISTING NURSE CALL AND CODE BLUE

DEVICES TO BE REPLACED WITH NEW NURSE

CALL AND CODE BLUE DEVICES UNO.

C. PROVIDE STAINLESS STEEL COVER PLATE FOR

ALL UNUSED NURSE CALL DEVICE LOCATIONS.

D. REUSE THE EXISTING NURSE CALL RACEWAY

SYSTEM FOR NEW NURSE CALL CABLING.

E. THE REMOVAL OF ANY EXISTING NURSE CALL

DEVICES SHALL NOT INTERRUPT THE NURSE

CALL DEVICES IN OTHER ROOMS. BOTH EXISTING

NURSE CALL SYSTEM AND NEW NURSE CALL

SYSTEMS SHALL BE IN OPERATION UNTIL NEW

NURSE CALL SYSTEM IS COMPLETELY

OPERATIONAL ON EACH FLOOR.

F. ALL NURSE CALL AND CODE BLUE WORK SHALL

BE COORDINATED WITH THE COR AND NURSE

MANAGER.

G. THE NURSE CALL SYSTEM IS A ONE FOR ONE

REPLACEMENT WITH NEW DEVICES AND/OR AS

SHOWN ON DRAWINGS - SEE NOTE "J" BELOW.

H. INTERFACE EXISTING TVS-GETWELL WITH THE

NEW NURSE CALL SYSTEM.

I. INTERFACE EXISTING PATIENT BEDS WITH NEW

NEW 37 PIN BED RECEPTACLES. PROVIDE

BREAKOUT PATCH CABLES COORDINATE WORK

WITH COR.

J. PROVIDE NEW NURSE CALL DEVICES, CONDUITS,

CABLES, BOXES AND CONNECT TO THE NEW

NURSE CALL SYSTEM CABINET. CONTRACTOR

SHALL COORDINATE NEW DEVICES WITH THE

EXISTING DEMOLITION PLANS. NEW AND

REPLACEMENT DEVICES SHALL BE TESTED.

K. PROVIDE NEW BUILD UP FOR THE NEW NURSE

CALL EQUIPMENT RACK/CABINET WITH ALL

NEEDED EQUIPMENT FOR A COMPLETE

OPERATIONAL SYSTEM FOR EACH WING, UNIT

AND AREA AS SHOWN. SYSTEM SHALL BE TESTED

WITH EVERY DEVICE.

L. PROVIDE GROUNDING FOR ALL THE NURSE CALL

EQUIPMENT CABINETS AND BOND TO THE

EXISTING GROUNDING SYSTEM WITH A MINIMUM

OF 6 AWG GROUND WIRE, LABEL GROUND CABLE.

2 EXISTING HEADWALL DETAIL

SCALE: N.T.S.

3 REVISED HEADWALL DETAIL

SCALE: N.T.S.

SHEET KEY NOTES:#

SHEET NOTES:

DocuSign Envelope ID: BA659FA3-E303-449B-A1FA-811899152E7D

7/19/2021

AREA OF WORK

A G

CHASE

MECH

MECH

DATA

CHASE

VESTIBULE

TLT

RF

TLT

RF

CONTROL

WAITING

ELEC

VIEWING & READING

LINEN

SUPPLY

MEDIA

G08A

G08

G11

G10A

G07

G06

GO2

G06A G03

G04

G13 G12

G01G05

G16

G15

CHEST ROOM

G14 HOLDING

RECEPTION

CONTROL

ULTRASOUND

G17

RAD ROOM

G18

TLT

G18A G20

WAITINGG19

SOILED

MRI

RADIOLOGY

RADIOLOGY

G21

G10

G22

G23

ULTRASOUND

G25

RADIOLOGY

RADIOLOGIST

G10B

RADIOLOGIST

G10C

RADIOLOGIST

G10D

RADIOLOGY

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

STORAGE

DRESSING

TLT.

PREP

CONTROL

SCAN EQUIPMENT

STORAGE

ROOM

ROOM ROOM

G09

G09A

G09B

G09C

G09D

G09D

G09F

G09G G09H

G54b G54a ELECTRICAL G49A

N

N

N

B

E

E E

N N

E

B

NN

N

N N

B

B

B

D

NN

B BD

B

M

D

N

N z z

TK405

TO

BUILDING

1CORRIDOR

CORRIDOR

CONTROL CENTER

LOUNGE

SOILED

UTILITY

TLT

103D

CUBICLE-9

105K

CUBICLE-10

105L

NURSE MGR

ELEC

HAC

IV PUMP

STOR

STOR

EQUIP STOR

TLT

103A

TLT

LINEN

CLEAN UTILITY

TLT

103B

MECH

103E

CUBICLE-1

105A

ON CALL

103C

CUBICLE-2

105B

CUBICLE-3

105CISOLATION-4

105D

ANTE

105E

CUBICLE-5

105F

CUBICLE-6

105G

CUBICLE-7

105H

ANTE

105I

ISOLATION-8

105J

N N N N

N

N

N

N N N

M

SSS

S

S

S

S S S S

R S

EEE

E

E

E

E E E E

D

D D

1 1 1

PPP

P

P

P

P P P P

TK405

TO BUILDING 1

TO BUILDING 1

2 2

"A" FLOOR

EXISTING

HEADWALL UNIT

P S

"A" FLOOR

EXISTING

HEADWALL UNIT

P

S

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

JULY 19, 2021 ADRJVE

626A4-20-10420-171

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.

NURSE CALL PATIENT BED INTERFACE RECEPTACLE (37 PIN)

WALL RATINGS

1 HR FIRE WALL

1 HR FIRE SMOKE WALL

2 HOUR FIRE WALL

2 HOUR FIRE SMOKE WALL

NON-RATED SMOKE PARTITION

SMOKE RESISTIVE HAZARDOUS

ROOM ENCLOSURE

107Engineers Architects U.S. Department of Veterans Affairs

TVHS- NASHVILLE CAMPUS

1310 24TH AVE S,NASHVILLE, TENNESSEE 37212

TVHS- ALVIN C. YORK CAMPUS

3400 LEBANON PIKE, MURFREESBORO, TENNESSEE 37129

UPGRADE NURSE CALL SYSTEM

NASHVILLE/MURFREESBORO

CAMPUS

NURSE CALL EQUIPMENT CABINETNCE

NURSE CALL SYMBOL LEGEND

SYMBOL DESCRIPTION

A NURSE CALL AUXILIARIES

B ENHANCED NURSE CALL, STAND ALONE, CODE

BLUE STATION WITH CLEAR BUTTON COVER

D NURSE CALL DUTY STATION

NURSE CALL EMERGENCY STATION

(SEE T-001 FOR MORE SPECIFICS, PB - PUSH BUTTON NO

PULL CORD, HS - HIGH SECURITY STEEL COVER PLATE)

M NURSE CALL MASTER STATION/CONSOLE

NURSE CALL PATIENT STATION

(PB - PUSH BUTTON, M - MICROPHONE, K -KEYED, HS - HIGH

SECURITY STEEL COVER PLATE)

N NURSE CALL DOME LIGHT

(Z - ZONE LIGHT, V - VANDAL RESISTANT)

N NURSE CALL DOME LIGHT - WALL MOUNTED

BUTTON STATION WITH CLEAR BUTTON COVER

NUMBER OF BUTTONS (1 - SINGLE BUTTON, 2 - DOUBLE

BUTTON)

BUTTON PROGRAMING (B- CODE BLUE, P - PUSH FOR HELP,

S - STAFF ASSIST)

C

NURSE CALL PATIENT STATION WITH CALL CORD INCLUDES:

- CODE BLUE

- STAFF ASSIST

- AUDIO

- CLEAR BUTTON COVER

(2 - DUAL PATIENT STATION, HS - VANDAL RESISTANT HIGH

SECURITY STEEL COVER PLATE)

E

N

S S S S S S

P

Z

M

PB

S

T NURSE CALL STAFF TERMINAL

MATV OR CATV WALL MOUNTED

MATV OR CATV CEILING MOUNTED

NURSE CALL PATIENT STATION WITH PILLOW SPEAKER (GET

WELL) INCLUDES:

- CODE BLUE

- STAFF ASSIST

- AUDIO

- CLEAR BUTTON COVER

(2 - DUAL PATIENT STATION, HS - VANDAL RESISTANT HIGH

SECURITY STEEL COVER PLATE)

HS

R

BS

P

120TN111

MURFREESBORO BUILDING 120 - "G"

AND "A" FLOOR NURSE CALL PLAN

1 MURFREESBORO BUILDING 120 - "G" FLOOR NURSE CALL PLAN

SCALE: 1/8" = 1' 0"

N O

R

TH

TRUE

0 4 8 16

2 MURFREESBORO BUILDING 120 - "A" FLOOR NURSE CALL PLAN

SCALE: 1/8" = 1' 0"

N O

R

TH

TRUE

0 4 8 16

ICU

1. NEW TV OUTLET REPLACING EXISTING.

INTERCONNECT TELEVISIONS WITH NEW

NURSE CALL SYSTEM.

2. EXISTING NURSE CALL DEVICES IN EXISTING

PATIENT HEADWALL TO BE REPLACED WITH

NEW NURSE CALL DEVICES.

2 EXISTING HEADWALL DETAIL

SCALE: N.T.S. 3 REVISED HEADWALL DETAIL

SCALE: N.T.S.

SHEET NOTES:

SHEET KEY NOTES:#

NCE

'ECLA' - 17

N C

E N

C E

3NCENCE

NCE

'BEM33(1)' - 35

Ra mp

U p

'BEQM1' - 2

NCENCE

NCE

NCE

NCE

14 15

'1EMA1' - 18

M

N C

E

'CLL1A' - 2

'CLL1A' - 1

N C

EN

C

E

NCE

NCE

FINISHED FLOOR

GROUNDING BAR

NEW NURSE CALL

EQUIPMENT CABINET

NEW NURSE CALL

EQUIPMENT CABINET

FINISHED FLOOR

GROUNDING BAR

NEW NURSE CALL

EQUIPMENT CABINET

NEW NURSE CALL

EQUIPMENT CABINET

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

JULY 19, 2021 ADRJVE

626A4-20-10420-171

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A. 107Engineers Architects

U.S. Department of Veterans Affairs

TVHS- NASHVILLE CAMPUS

1310 24TH AVE S,NASHVILLE, TENNESSEE 37212

TVHS- ALVIN C. YORK CAMPUS

3400 LEBANON PIKE, MURFREESBORO, TENNESSEE 37129

UPGRADE NURSE CALL SYSTEM

NASHVILLE/MURFREESBORO

CAMPUS

TK401

NASHVILLE BUILDING 1 - BASEMENT FLOOR NURSE

CALL ALCOVE B-B101R ENLARGEMENTS (1TN102)

SCALE: 1/4" = 1' 0"

NASHVILLE BUILDING 1 - BASEMENT FLOOR NURSE CALL

CT-11 ROOM D-27A ENLARGEMENT (1TN103)

SCALE: 1/4" = 1' 0"

NASHVILLE BUILDING 1 - BASEMENT FLOOR NURSE CALL

SIGNAL CLOSET ROOM C-01 ENLARGEMENT (1TN104)

SCALE: 1/4" = 1' 0"

4 NASHVILLE BUILDING 1 - BASEMENT FLOOR NURSE CALL ADP COMPUTER ROOM D-03 ENLARGEMENT (1TN103)

SCALE: 1/4" = 1' 0"

NASHVILLE BUILDING 1 - BASEMENT FLOOR NURSE CALL

SIGNAL ROOM G-49A ENLARGEMENT (1TN105)

SCALE: 1/4" = 1' 0"

NASHVILLE BUILDING 1 - SECOND FLOOR

NURSE CALL ENLARGEMENT AREA G

NORTH (1TN121)

SCALE: 1/4" = 1' 0"

NASHVILLE BUILDING 1 - SECOND

FLOOR NURSE CALL CLOSET A-239

ENLARGEMENT (1TN122)

SCALE: 1/4" = 1' 0"

NASHVILLE BUILDING 1 - FIRST FLOOR NURSE CALL

ROOM "DATA" ENLARGEMENT (1TN112)

SCALE: 1/4" = 1' 0"

A. DEMOLISH ALL EXISTING NURSE CALL CABLING

BACK TO THE NURSE CALL EQUIPMENT CABINET.

B. CONTRACTOR MAY USE THE EXISTING NURSE

CALL CABLE AS A PULL WIRE FOR THE NEW NURSE

CALL CABLING.

C. FOLLOW ICRA REQUIREMENTS.

D. REMOVE ALL TRASH DAILY FROM THE WORK AREA.

E. REUSE THE EXISTING NURSE CALL RACEWAY

SYSTEM FOR NEW NURSE CALL CABLING.

F. THE REMOVAL OF ANY EXISTING NURSE CALL

DEVICES SHALL NOT INTERRUPT THE NURSE CALL

DEVICES IN OTHER ROOMS. BOTH EXISTING NURSE

CALL SYSTEM AND NEW NURSE CALL SYSTEMS

SHALL BE IN OPERATION UNTIL NEW NURSE CALL

SYSTEM IS COMPLETELY OPERATIONAL ON EACH

FLOOR.

G. PATCH EXISTING NURSE CALL OPENINGS IF NOT

USED AND PAINT TO MATCH.

H. PATCH AND PAINT AT THE LOCATION OF THE

EXISTING NURSE CALL EQUIPMENT CABINET.

I. PROVIDE STAINLESS STEEL COVER PLATES AS

REQUIRED.

J. ALL NURSE CALL WORK SHALL BE COORDINATED

WITH THE COR AND NURSE MANAGER.

K. PATCH ALL PENETRATIONS AND OPENINGS IN

SMOKE AND FIRE WALLS WITH APPROVED UL

LISTED MATERIALS. SUBMIT APPLICATION PER VA.

SEE SPECIFICATIONS FOR FORM.

L. ALL DEVICES SHOWN TO BE REPLACED UNLESS

NOTED OTHERWISE.

M. THESE DRAWINGS ARE BASED ON FIELD SURVEY

AND EXISTING PLANS. VERIFY ALL FIELD

CONDITIONS.

N. COORDINATE ALL NURSE CALL SYSTEM WITH COR.

O. PATCH ALL NURSE CALL RACEWAY PENETRATIONS

OR OPENINGS IN SMOKE OR FIRE WALLS WITH AN

APPROVED UL LISTED MATERIAL.

P. MOUNT NEW NCE CABINET ON FIRE RATED

PLYWOOD. PROVIDE TEMPORARY STAND ON

HEAVY DUTY CASTERS FOR THE NCE

CABINET/PLYWOOD. AFTER THE WORK IS

COMPLETE REMOVE THE EXISTING NCE CABINET.

THEN REMOVE THE TEMPORARY STAND AND

MOUNT THE NEW NCE CABINET/PLYWOOD AT THE

LOCATION OF THE EXISTING NCE LOCATION.

COORDINATE ALL WORK WITH COR.

Q. PROVIDE STAINLESS STEEL COVER PLATE FOR ALL

UNUSED NURSE CALL DEVICE LOCATIONS.

R. REFER TO PHASING NOTES, SHEET T-001, FOR

ADDITIONAL INFORMATION.

S. COORDINATE ALL DOWNTIME WITH COR PRIOR TO

ANY WORK.

1 2 3

1. EXISTING NURSE CALL EQUIPMENT CABINET TO BE

REPLACED WITH NEW NURSE CALL CABINET.

2. LOCATION OF NEW NURSE CALL EQUIPMENT

CABINET. CONTRACTOR SHALL COORDINATE

WORK AND PHASING PER PLANS AND SPECS.

CONNECT TO EXISTING EMERGENCY ELECTRICAL

CIRCUIT.

3. PROVIDE NEW GROUND BUS BAR AND BOND TO

EXISTING BONDING/GROUNDING SYSTEM.PROVIDE

NEW GROUND BUS BAR AND BOND TO EXISTING

BONDING/GROUNDING SYSTEM.

4. PROVIDE 2-CAT 6A CABLES TO CLOSEST DATA

RACK WITH SPARE NETWORK PORTS.

5. PROVIDE 2-10 AWG AND 1-10 AWG GND IN 3/4" C TO

SPARE 1P-20A CIRCUIT BREAKER.

6. PROVIDE 3" UL LISTED FIRE/SMOKE SLEEVE

ASSEMBLY.

7. REMOVE EXISTING NURSE CALL EQUIPMENT IN

EXISTING DATA RACK. REMOVE ALL NURSE CALL

CABLING.

8. LOCATION OF NEW NURSE CALL EQUIPMENT

CABINET. CONTRACTOR SHALL COORDINATE

WORK AND PHASING PER PLANS AND SPECS.

9. FROM NEW ENTERPRISE EQUIPMENT RUN

CABLING TO VA DATA SWITCH FOR VLAN / WAN

INTEGRATION. PROVIDE 4 PR UTP CABLE FOR

DISTANCE UP TO 295 FEET OR 2 STRAND FIBER

WITH FIBER CONVERTER FOR DISTANCE OVER 295

FEET. COORDINATE WITH COR.

10. FROM NEW ENTERPRISE EQUIPMENT WITH NEW

SERVERS IN A NEW 4 POST EQUIPMENT RACK,

PROVIDE CABLING TO CLOSEST NURSE CALL

EQUIPMENT CABINET (D-27A). PROVIDE 4 PR UTP

CABLE FOR DISTANCE UP TO 295 FEET OR 2

STRAND FIBER WITH FIBER CONVERTER FOR

DISTANCE OVER 295 FEET.

11. PROVIDE NEW 4 POST DATA RACK - COORDINATE

WITH COR. PLUG SERVER POWER CONNECTION

CORDS INTO RACK MOUNTED UPS.

12. ADD NEW MONITOR FOR NURSE CALL USE.

13. EXISTING RAULAND DURESS, PUSH BUTTONS TO

BE REPLACED WITH NEW.

14. OWNER TO RELOCATE EXISTING LOCKERS.

15. DESKTOP CLIENT COMPUTER WITH 21" MONITOR

FOR ENTERPRISE SOFTWARE TO DISPLAY

MONITORING STATION.

16. RELOCATE PHONE FOR CODE BLUE FROM DESK

TO WALL WITH MASTER STATION.

17. STACK NURSE CALL CABINETS AND GROUNDING

BAR AS SHOWN.

18. EXISTING NURSE CALL CABINET TO BE

DEMOLISHED. PATCH AND REPAIR TO MATCH

SURROUNDING.

19. PROVIDE 2-10AWG AND 1-10AWG GND IN 1" C TO

NEW 30A, 2P CIRCUIT BREAKER WITH MATCHING

AIC RATING.

20. PROVIDE 30 AMP 208V, TWIST LOCK, NEMA L6-30R

RECEPTACLE TO SERVE UPS. MOUNT

RECEPTACLE TO RACK. PROVIDE MATCHING

CORD.

0 2 4 8

N O

R

TH

TRUE

0 2 4 8

N O

R

TH

TRUE

0 2 4 8

N O

R

TH

TRUE

0 2 4 8

N O

R

TH

TRUE

0 2 4 8

N O

R

TH

TRUE

0 2 4 8

N O

R

TH

TRUE

0 2 4 8

N O

R

TH

TRUE

0 2 4 8

N O

R

TH

TRUE

0 2 4 8

N O

R

TH

TRUE

NASHVILLE BUILDING 1 - FIRST FLOOR NURSE

CALL SECURITY MONITOR A-140

ENLARGEMENT(1TN114)

SCALE: 1/4" = 1' 0"

CRASH CART

ALCOVE

B-B101R

CT-11

D-27A

SIGNAL

CLOSET

C-01

ADP COMPUTER RM

D-03

ALCOVE

G-49 SIGNAL

G-49A

ELECTRICAL

CLOSET

SIGNAL

G-49B

TELE

G-49C

NASHVILLE BUILDING 1 - FIRST FLOOR NURSE CALL

DATA ROOM F-138A ENLARGEMENT (1TN113)

SCALE: 1/4" = 1' 0"

0 2 4 8

N O

R

TH

TRUE

DATA

F-138A

'1EMA1' - 39

SECURITY MONITOR

A-140

TOILET

A-140A

DATA

G-213

ELECTRICAL

G-212

CLOSET

A-239

NURSE CALL ENLARGEMENTS

EXISTING PANEL -

PANEL '2ECA-A'

NORMAL - '2A3' - 66

EMERGENCY - '2CRN-2' - 50

SHEET NOTES:

SHEET KEY NOTES:#

'EAL' - 6

'EAL' - 8

17 38

'1EMA1' - 40

DATA CLOSET

A-116

N C

E N

C E

N C

E N

C E

EXISTING

PANEL -

PANEL

'2C1'

N C

E

NCE

NCE

NCE

NCE

N C

E 8

N C

E 7

NCENCE

NCE

NCE

NCE

N C

E N

C E

N

C E

N C

E

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

JULY 19, 2021 ADRJVE

626A4-20-10420-171

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A. 107Engineers Architects

U.S. Department of Veterans Affairs

TVHS- NASHVILLE CAMPUS

1310 24TH AVE S,NASHVILLE, TENNESSEE 37212

TVHS- ALVIN C. YORK CAMPUS

3400 LEBANON PIKE, MURFREESBORO, TENNESSEE 37129

UPGRADE NURSE CALL SYSTEM

NASHVILLE/MURFREESBORO

CAMPUS

TK402

NASHVILLE BUILDING 1 - SECOND FLOOR NURSE CALL

LINEN CLOSET C-226 ENLARGEMENT (1TN124)

SCALE: 1/4" = 1' 0"

NASHVILLE BUILDING 1 - SECOND FLOOR NURSE CALL

ENLARGEMENT AREA G SOUTH (1TN125)

SCALE: 1/4" = 1' 0"

NASHVILLE BUILDING 1 - THIRD FLOOR NURSE CALL

"DATA" ROOM ENLARGEMENT (1TN131)

SCALE: 1/4" = 1' 0"

NASHVILLE BUILDING 1 - FOURTH FLOOR NURSE CALL

ELECTRICAL ROOM A440 ENLARGEMENT (1TN141)

SCALE: 1/4" = 1' 0"

NASHVILLE BUILDING 1 - FOURTH FLOOR NURSE CALL AREA B

EQUIPMENT CABINET CLOSET ENLARGEMENT (1TN142)

SCALE: 1/4" = 1' 0"

NASHVILLE BUILDING 1 - THIRD FLOOR NURSE CALL

SIGNAL CLOSET ROOM A -351 ENLARGEMENT (1TN132)

SCALE: 1/4" = 1' 0"

A. DEMOLISH ALL EXISTING NURSE CALL CABLING

BACK TO THE NURSE CALL EQUIPMENT CABINET.

B. CONTRACTOR MAY USE THE EXISTING NURSE

CALL CABLE AS A PULL WIRE FOR THE NEW NURSE

CALL CABLING.

C. FOLLOW ICRA REQUIREMENTS.

D. REMOVE ALL TRASH DAILY FROM THE WORK AREA.

E. REUSE THE EXISTING NURSE CALL RACEWAY

SYSTEM FOR NEW NURSE CALL CABLING.

F. THE REMOVAL OF ANY EXISTING NURSE CALL

DEVICES SHALL NOT INTERRUPT THE NURSE CALL

DEVICES IN OTHER ROOMS. BOTH EXISTING NURSE

CALL SYSTEM AND NEW NURSE CALL SYSTEMS

SHALL BE IN OPERATION UNTIL NEW NURSE CALL

SYSTEM IS COMPLETELY OPERATIONAL ON EACH

FLOOR.

G. PATCH EXISTING NURSE CALL OPENINGS IF NOT

USED AND PAINT TO MATCH.

H. PATCH AND PAINT AT THE LOCATION OF THE

EXISTING NURSE CALL EQUIPMENT CABINET.

I. PROVIDE STAINLESS STEEL COVER PLATES AS

REQUIRED.

J. ALL NURSE CALL WORK SHALL BE COORDINATED

WITH THE COR AND NURSE MANAGER.

K. PATCH ALL PENETRATIONS AND OPENINGS IN

SMOKE AND FIRE WALLS WITH APPROVED UL

LISTED MATERIALS. SUBMIT APPLICATION PER VA.

SEE SPECIFICATIONS FOR FORM.

L. ALL DEVICES SHOWN TO BE REPLACED UNLESS

NOTED OTHERWISE.

M. THESE DRAWINGS ARE BASED ON FIELD SURVEY

AND EXISTING PLANS. VERIFY ALL FIELD

CONDITIONS.

N. COORDINATE ALL NURSE CALL SYSTEM WITH COR.

O. PATCH ALL NURSE CALL RACEWAY PENETRATIONS

OR OPENINGS IN SMOKE OR FIRE WALLS WITH AN

APPROVED UL LISTED MATERIAL.

P. MOUNT NEW NCE CABINET ON FIRE RATED

PLYWOOD. PROVIDE TEMPORARY STAND ON

HEAVY DUTY CASTERS FOR THE NCE

CABINET/PLYWOOD. AFTER THE WORK IS

COMPLETE REMOVE THE EXISTING NCE CABINET.

THEN REMOVE THE TEMPORARY STAND AND

MOUNT THE NEW NCE CABINET/PLYWOOD AT THE

LOCATION OF THE EXISTING NCE LOCATION.

COORDINATE ALL WORK WITH COR.

Q. PROVIDE STAINLESS STEEL COVER PLATE FOR ALL

UNUSED NURSE CALL DEVICE LOCATIONS.

R. REFER TO PHASING NOTES, SHEET T-001, FOR

ADDITIONAL INFORMATION.

S. COORDINATE ALL DOWNTIME WITH COR PRIOR TO

ANY WORK.

1. EXISTING NURSE CALL EQUIPMENT CABINET TO

BE REPLACED WITH NEW NURSE CALL CABINET.

2. LOCATION OF NEW NURSE CALL EQUIPMENT

CABINET. CONTRACTOR SHALL COORDINATE

WORK AND PHASING PER PLANS AND SPECS.

CONNECT TO EXISTING EMERGENCY ELECTRICAL

CIRCUIT.

3. PROVIDE NEW GROUND BUS BAR AND BOND TO

EXISTING BONDING/GROUNDING

SYSTEM.PROVIDE NEW GROUND BUS BAR AND

BOND TO EXISTING BONDING/GROUNDING

SYSTEM.

4. PROVIDE 2-CAT 6A CABLES TO CLOSEST DATA

RACK WITH SPARE NETWORK PORTS.

5. PROVIDE 2-10 AWG AND 1-10 AWG GND IN 3/4" C

TO SPARE 1P-20A CIRCUIT BREAKER.

6. PROVIDE 3" UL LISTED FIRE/SMOKE SLEEVE

ASSEMBLY.

7. REMOVE EXISTING NURSE CALL EQUIPMENT IN

EXISTING DATA RACK. REMOVE ALL NURSE CALL

CABLING.

8. LOCATION OF NEW NURSE CALL EQUIPMENT

CABINET. CONTRACTOR SHALL COORDINATE

WORK AND PHASING PER PLANS AND SPECS.

9. REMOVE EXISTING NURSE CALL CABINET.

10. RECESSED NURSE CALL EQUIPMENT CABINET TO

BE REPLACED WITH SURFACE MOUNTED NURSE

CALL EQUIPMENT CABINET. PATCH AND REPAIR

WALL TO MATCH SURROUNDINGS. REUSE

EXISTING CIRCUIT.

0 2 4 8

N O

R

TH

TRUE

0 2 4 8

N O

R

TH

TRUE

0 2 4 8

N O

R

TH

TRUE

0 2 4 8

N O

R

TH

TRUE

0 2 4 8

N O

R

TH

TRUE

0 2 4 8

N O

R

TH

TRUE

NASHVILLE BUILDING 1 - SECOND FLOOR NURSE

CALL BIOMED STORAGE A-257 ENLARGEMENT (1TN124)

SCALE: 1/4" = 1' 0"

0 2 4 8

N O

R

TH

TRUE

NASHVILLE BUILDING 1 - FOURTH FLOOR NURSE CALL

DATA CLOSET ROOM C-449 ENLARGEMENT (1TN143)

SCALE: 1/4" = 1' 0"

0 2 4 8

N O

R

TH

TRUE

BIOMED

STORAGE

A-257

TELE

CLOSET

C-227

ELECTRICAL

C-225

LC

C-226

TELE

SIG

G-230

ELECTRICAL

G-229

DATA

SIGNAL CLOSET

ELECTRICAL

A440

MULTI PURPOSE

B-415A

DATA CLOSET

C-449

NURSE CALL ENLARGEMENTS

'2CRS2' - 10

'2C1' - 15

EXISTING PANEL -

PANEL '4EALN'

'4CR1' - 1

EXISTING PANEL -

PANEL 'ECLC'

'3EC-S2' - 6

NORMAL '3A2' - 3

CRITICAL '3EA' - 1

'3EC-S2' - 2

'4ECLC' - 10

'4ECLC' - 12

SHEET NOTES:

SHEET KEY NOTES:#

'ECLC' - 35

C

E

M

NCE

N C

E

'2LC1W-A' - 10

N C

E

'2LC1Y' - 3

NCE

NCE

NCE

N C

E N

C E

NCE

NCE

N

C E

NCE

N C

E

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

JULY 19, 2021 ADRJVE

626A4-20-10420-171

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A. 107Engineers Architects

U.S. Department of Veterans Affairs

TVHS- NASHVILLE CAMPUS

1310 24TH AVE S,NASHVILLE, TENNESSEE 37212

TVHS- ALVIN C. YORK CAMPUS

3400 LEBANON PIKE, MURFREESBORO, TENNESSEE 37129

UPGRADE NURSE CALL SYSTEM

NASHVILLE/MURFREESBORO

CAMPUS

TK403

MURFREESBORO 1 - "G" FLOOR NURSE CALL

RECEPTION ROOM G19 ENLARGEMENT (01TN111)

SCALE: 1/4" = 1' 0"

MURFREESBORO 1 - "1" FLOOR NURSE CALL

ELECTRICAL ROOM 125 ENLARGEMENT (01TN121)

SCALE: 1/4" = 1' 0"

MURFREESBORO 1 - "1B" FLOOR NURSE CALL TELE. ROOMS

350 AND 351A ENLARGEMENT (01TN141)

SCALE: 1/4" = 1' 0"

MURFREESBORO 1 - "1B" FLOOR NURSE

CALL TELE ROOM 343 ENLARGEMENT (01TN142)

SCALE: 1/4" = 1' 0"

MURFREESBORO 1 - "4" FLOOR NURSE CALL ELECTRICAL

CLOSET 406A ENLARGEMENT (01TN151)

SCALE: 1/4" = 1' 0"

MURFREESBORO 2 - "G" FLOOR NURSE CALL ELECTRICAL

ROOM G11A ENLARGEMENT (02TN111)

SCALE: 1/4" = 1' 0"

A. DEMOLISH ALL EXISTING NURSE CALL CABLING

BACK TO THE NURSE CALL EQUIPMENT CABINET.

B. FOLLOW ICRA REQUIREMENTS.

C. REMOVE ALL TRASH DAILY FROM THE WORK AREA.

D. REUSE THE EXISTING NURSE CALL RACEWAY

SYSTEM FOR NEW NURSE CALL CABLING.

E. THE REMOVAL OF ANY EXISTING NURSE CALL

DEVICES SHALL NOT INTERRUPT THE NURSE CALL

DEVICES IN OTHER ROOMS. BOTH EXISTING NURSE

CALL SYSTEM AND NEW NURSE CALL SYSTEMS

SHALL BE IN OPERATION UNTIL NEW NURSE CALL

SYSTEM IS COMPLETELY OPERATIONAL ON EACH

FLOOR.

F. PATCH EXISTING NURSE CALL OPENINGS IF NOT

USED AND PAINT TO MATCH.

G. PATCH AND PAINT AT THE LOCATION OF THE

EXISTING NURSE CALL EQUIPMENT CABINET.

H. PROVIDE STAINLESS STEEL COVER PLATES AS

REQUIRED.

I. ALL NURSE CALL WORK SHALL BE COORDINATED

WITH THE COR AND NURSE MANAGER.

J. PATCH ALL PENETRATIONS AND OPENINGS IN

SMOKE AND FIRE WALLS WITH APPROVED UL

LISTED MATERIALS. SUBMIT APPLICATION PER VA.

SEE SPECIFICATIONS FOR FORM.

K. ALL DEVICES SHOWN TO BE REPLACED UNLESS

NOTED OTHERWISE.

L. THESE DRAWINGS ARE BASED ON FIELD SURVEY

AND EXISTING PLANS. VERIFY ALL FIELD

CONDITIONS.

M. COORDINATE ALL NURSE CALL SYSTEM WITH COR.

N. PATCH ALL NURSE CALL RACEWAY PENETRATIONS

OR OPENINGS IN SMOKE OR FIRE WALLS WITH AN

APPROVED UL LISTED MATERIAL.

O. MOUNT NEW NCE CABINET ON FIRE RATED

PLYWOOD. PROVIDE TEMPORARY STAND ON

HEAVY DUTY CASTERS FOR THE NCE

CABINET/PLYWOOD. AFTER THE WORK IS

COMPLETE REMOVE THE EXISTING NCE CABINET.

THEN REMOVE THE TEMPORARY STAND AND

MOUNT THE NEW NCE CABINET/PLYWOOD AT THE

LOCATION OF THE EXISTING NCE LOCATION.

COORDINATE ALL WORK WITH COR.

P. PROVIDE STAINLESS STEEL COVER PLATE FOR ALL

UNUSED NURSE CALL DEVICE LOCATIONS.

Q. REFER TO PHASING NOTES, SHEET T-001, FOR

ADDITIONAL INFORMATION.

R. COORDINATE ALL DOWNTIME WITH COR PRIOR TO

ANY WORK.

'CEG' - 39

0 2 4 8

N O

R

TH

TRUE

0 2 4 8

N O

R

TH

TRUE

0 2 4 8

N O

R

TH

TRUE

0 2 4 8

N O

R

TH

TRUE

0 2 4 8

N O

R

TH

TRUE

0 2 4 8

N O

R

TH

TRUE

EXISTING PANEL-

PANEL '2L11N'

NURSE CALL ENLARGEMENTS

RECEPTION

G19

ELEC

TELE

351A

STOR

TELE

TELE

EEC

406A

ELEC

G11A

EXISTING PANEL-

PANEL '2N1FF'

SHEET NOTES:

SHEET KEY NOTES:#

1. EXISTING NURSE CALL EQUIPMENT CABINET TO

BE REPLACED WITH NEW NURSE CALL CABINET.

EXTEND AND REUSE EXISTING CIRCUIT FOR NEW

CABINET.

2. LOCATION OF NEW NURSE CALL EQUIPMENT

CABINET. CONTRACTOR SHALL COORDINATE

WORK AND PHASING PER PLANS AND SPECS.

CONNECT TO EXISTING EMERGENCY ELECTRICAL

CIRCUIT.

3. PROVIDE NEW GROUND BUS BAR AND BOND TO

EXISTING BONDING/GROUNDING SYSTEM.

4. PROVIDE 2-CAT 6A CABLES TO CLOSEST DATA

RACK WITH SPARE NETWORK PORTS.

5. PROVIDE 2-10 AWG AND 1-10 AWG GND IN 3/4" C

TO SPARE 1P-20A CIRCUIT BREAKER.

6. PROVIDE 3" UL LISTED FIRE/SMOKE SLEEVE

ASSEMBLY.

7. REMOVE EXISTING NURSE CALL EQUIPMENT IN

EXISTING EQUIPMENT RACK. REMOVE ALL NURSE

CALL CABLING.

8. LOCATION OF NEW NURSE CALL EQUIPMENT

CABINET. CONTRACTOR SHALL COORDINATE

WORK AND PHASING PER PLANS AND SPECS.

9. PROVIDE 2-10 AWG AND 1-10 AWG GND IN 3/4" C

TO SPARE 1P-20A CIRCUIT BREAKER IN CLOSEST

CRITICAL BRANCH PANEL.

MURFREESBORO 3 - "G" FLOOR NURSE CALL

STORAGE ROOM G15B ENLARGEMENT (03TN111)

SCALE: 1/4" = 1' 0"

0 2 4 8

N O

R

TH

TRUE

MURFREESBORO 3 - "A" FLOOR NURSE CALL

TELE. ROOM 131 ENLARGEMENT (03TN121)

SCALE: 1/4" = 1' 0"

0 2 4 8

N O

R

TH

TRUE

MURFREESBORO 3 - "A" FLOOR NURSE CALL

STORAGE ROOM 107 ENLARGEMENT (03TN121)

SCALE: 1/4" = 1' 0"

0 2 4 8

N O

R

TH

TRUE

MURFREESBORO 3 - "B" FLOOR NURSE CALL

MECH. ROOM 234 ENLARGEMENT (03TN131)

SCALE: 1/4" = 1' 0"

0 2 4 8

N O

R

TH

TRUE

MURFREESBORO 3 - "B" FLOOR NURSE CALL

TELE. ROOM 205 ENLARGEMENT (03TN131)

SCALE: 1/4" = 1' 0"

0 2 4 8

N O

R

TH

TRUE

MURFREESBORO 4 - "G" FLOOR NURSE CALL

STOR. ROOM G108D ENLARGEMENT (04TN111)

SCALE: 1/4" = 1' 0"

0 2 4 8

N O

R

TH

TRUE

TELE

STOR

G15B

'2L3A' - 4

STORAGE

'2C3B'- 17

MECH

'2L3E' - 9

TELE

'2C3D' - 25

STOR

G108D '2C4GC' - 1

C

E

N C

E

N C

E

NCE

NCE

NCE

N C

E N

C E

N C

E N

C E

N C

E N

C E

N C

E N

C E

WH

N C

E

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

JULY 19, 2021 ADRJVE

626A4-20-10420-171

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A. 107Engineers Architects

U.S. Department of Veterans Affairs

TVHS- NASHVILLE CAMPUS

1310 24TH AVE S,NASHVILLE, TENNESSEE 37212

TVHS- ALVIN C. YORK CAMPUS

3400 LEBANON PIKE, MURFREESBORO, TENNESSEE 37129

UPGRADE NURSE CALL SYSTEM

NASHVILLE/MURFREESBORO

CAMPUS

TK404

NURSE CALL ENLARGEMENTS

MURFREESBORO 5 - "G" FLOOR TELE. ROOM G04

ENLARGEMENT (05TN111)

SCALE: 1/4" = 1' 0"

MURFREESBORO 7 - "G" FLOOR DATA ROOM G05

ENLARGEMENT (07TN111)

SCALE: 1/4" = 1' 0"

MURFREESBORO 7 - "A" FLOOR COMM. ROOM 102

ENLARGEMENT (07TN121)

SCALE: 1/4" = 1' 0"

MURFREESBORO 7 -"B" FLOOR COMM. ROOM 203

ENLARGEMENT (07TN131)

SCALE: 1/4" = 1' 0"

A. DEMOLISH ALL EXISTING NURSE CALL CABLING

BACK TO THE NURSE CALL EQUIPMENT CABINET.

B. FOLLOW ICRA REQUIREMENTS.

C. REMOVE ALL TRASH DAILY FROM THE WORK AREA.

D. REUSE THE EXISTING NURSE CALL RACEWAY

SYSTEM FOR NEW NURSE CALL CABLING.

E. THE REMOVAL OF ANY EXISTING NURSE CALL

DEVICES SHALL NOT INTERRUPT THE NURSE CALL

DEVICES IN OTHER ROOMS. BOTH EXISTING NURSE

CALL SYSTEM AND NEW NURSE CALL SYSTEMS

SHALL BE IN OPERATION UNTIL NEW NURSE CALL

SYSTEM IS COMPLETELY OPERATIONAL ON EACH

FLOOR.

F. PATCH EXISTING NURSE CALL OPENINGS IF NOT

USED AND PAINT TO MATCH.

G. PATCH AND PAINT AT THE LOCATION OF THE

EXISTING NURSE CALL EQUIPMENT CABINET.

H. PROVIDE STAINLESS STEEL COVER PLATES AS

REQUIRED.

I. ALL NURSE CALL WORK SHALL BE COORDINATED

WITH THE COR AND NURSE MANAGER.

J. PATCH ALL PENETRATIONS AND OPENINGS IN

SMOKE AND FIRE WALLS WITH APPROVED UL

LISTED MATERIALS. SUBMIT APPLICATION PER VA.

SEE SPECIFICATIONS FOR FORM.

K. ALL DEVICES SHOWN TO BE REPLACED UNLESS

NOTED OTHERWISE.

L. THESE DRAWINGS ARE BASED ON FIELD SURVEY

AND EXISTING PLANS. VERIFY ALL FIELD

CONDITIONS.

M. COORDINATE ALL NURSE CALL SYSTEM WITH COR.

N. PATCH ALL NURSE CALL RACEWAY PENETRATIONS

OR OPENINGS IN SMOKE OR FIRE WALLS WITH AN

APPROVED UL LISTED MATERIAL.

O. MOUNT NEW NCE CABINET ON FIRE RATED

PLYWOOD. PROVIDE TEMPORARY STAND ON

HEAVY DUTY CASTERS FOR THE NCE

CABINET/PLYWOOD. AFTER THE WORK IS

COMPLETE REMOVE THE EXISTING NCE CABINET.

THEN REMOVE THE TEMPORARY STAND AND

MOUNT THE NEW NCE CABINET/PLYWOOD AT THE

LOCATION OF THE EXISTING NCE LOCATION.

COORDINATE ALL WORK WITH COR.

P. PROVIDE STAINLESS STEEL COVER PLATE FOR ALL

UNUSED NURSE CALL DEVICE LOCATIONS.

Q. REFER TO PHASING NOTES, SHEET T-001, FOR

ADDITIONAL INFORMATION.

R. COORDINATE ALL DOWNTIME WITH COR PRIOR TO

ANY WORK.

MURFREESBORO 8 - "A" FLOOR TELE. ROOM 143

ENLARGEMENT (08TN121)

SCALE: 1/4" = 1' 0"

0 2 4 8

N O

R

TH

TRUE

0 2 4 8

N O

R

TH

TRUE

0 2 4 8

N O

R

TH

TRUE

0 2 4 8

N O

R

TH

TRUE

0 2 4 8 NORTH

TRUE

MURFREESBORO 8 - "B" FLOOR DATA ROOM 246

ENLARGEMENT (08TN131)

SCALE: 1/4" = 1' 0"

0 2 4 8 NORTH

TRUE

MURFREESBORO 9 - "G" FLOOR TELE. ROOM G09A

ENLARGEMENT (09TN111)

SCALE: 1/4" = 1' 0"

0 2 4 8

N O

R

TH

TRUE

MURFREESBORO 9 - "B" FLOOR DATA ROOM 203

ENLARGEMENT (09TN131)

SCALE: 1/4" = 1' 0"

N O

R

TH

TRUE

0 4 8 16

MURFREESBORO 106 - IT CLOSET 120

ENLARGEMENT (106TN111)

SCALE: 1/4" = 1' 0"

0 2 4 8

N O

R

TH

TRUE

MURFREESBORO 11 - "A" FLOOR

STORAGE 101A ENLARGEMENT 11TN111

SCALE: 1/4" = 1' 0"

0 2 4 8

N O

R

TH

TRUE

TELE

DATA

G05

TELE

G04

STORAGE

101A

DATA

CLOSET

SCI

CHECK-IN

G09

TELE

G09A

DATA

'2L7G' - 26

SHEET NOTES:

SHEET KEY NOTES:#

'2N5G1(2)' - 54

'2C8D' - 6

'2C8F' - 15

'2L9GM' - 8

'2C9BS' - 3

'EP11'

COMM

ELEC

EXISTING PANEL-

PANEL '2C7E'

'2C7E' - 16

'2C7E' - 15

COMM

'2C7C' - 12

'2C7C' - 17

ELECTRICAL

EXISTING PANEL -

PANEL '2C7C'

MURFREESBORO 17 - NURSE CALL DATA

ROOM 155 ENLARGEMENT (17TN111)

SCALE: 1/4" = 1' 0"

0 2 4 8

N O

R

TH

TRUE1

DATA

'EM' - 11

EXISTING PANEL -

PANEL 'L2'

ELEC

I.T.

'L2' - 3

1. EXISTING NURSE CALL EQUIPMENT CABINET TO

BE REPLACED WITH NEW NURSE CALL CABINET.

EXTEND AND REUSE EXISTING CIRCUIT FOR NEW

CABINET.

2. LOCATION OF NEW NURSE CALL EQUIPMENT

CABINET. CONTRACTOR SHALL COORDINATE

WORK AND PHASING PER PLANS AND SPECS.

CONNECT TO EXISTING EMERGENCY ELECTRICAL

CIRCUIT.

3. PROVIDE NEW GROUND BUS BAR AND BOND TO

EXISTING BONDING/GROUNDING SYSTEM.

4. PROVIDE 2-CAT 6A CABLES TO CLOSEST DATA

RACK WITH SPARE NETWORK PORTS.

5. PROVIDE 2-10 AWG AND 1-10 AWG GND IN 3/4" C

TO SPARE 1P-20A CIRCUIT BREAKER.

6. PROVIDE 3" UL LISTED FIRE/SMOKE SLEEVE

ASSEMBLY.

7. LOCATION OF NEW NURSE CALL EQUIPMENT

CABINET. CONTRACTOR SHALL COORDINATE

WORK AND PHASING PER PLANS AND SPECS.

8. PROVIDE 3" UL LISTED, FIRE RATED SLEEVE FOR

FLOOR PENETRATION.

C

E

EXISTING PANEL -

PANEL '2C7A'

NCE

N C

E N

C E

N C

E N

C E

N C

E N

C E

1NCENCE

112B

N C

E N

C E

N C

E N

C E

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

JULY 19, 2021 ADRJVE

626A4-20-10420-171

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A. 107Engineers Architects

U.S. Department of Veterans Affairs

TVHS- NASHVILLE CAMPUS

1310 24TH AVE S,NASHVILLE, TENNESSEE 37212

TVHS- ALVIN C. YORK CAMPUS

3400 LEBANON PIKE, MURFREESBORO, TENNESSEE 37129

UPGRADE NURSE CALL SYSTEM

NASHVILLE/MURFREESBORO

CAMPUS

TK405

NURSE CALL ENLARGEMENTS

MURFREESBORO 117 - "G" FLOOR TELE. ROOM G17A

ENLARGEMENT (117TN111)

SCALE: 1/4" = 1' 0"7

MURFREESBORO 120 - "A" FLOOR ELEC. ROOM 107

ENLARGEMENT (120TN111)

SCALE: 1/4" = 1' 0"

A. DEMOLISH ALL EXISTING NURSE CALL CABLING

BACK TO THE NURSE CALL EQUIPMENT CABINET.

B. FOLLOW ICRA REQUIREMENTS.

C. REMOVE ALL TRASH DAILY FROM THE WORK AREA.

D. REUSE THE EXISTING NURSE CALL RACEWAY

SYSTEM FOR NEW NURSE CALL CABLING.

E. THE REMOVAL OF ANY EXISTING NURSE CALL

DEVICES SHALL NOT INTERRUPT THE NURSE CALL

DEVICES IN OTHER ROOMS. BOTH EXISTING NURSE

CALL SYSTEM AND NEW NURSE CALL SYSTEMS

SHALL BE IN OPERATION UNTIL NEW NURSE CALL

SYSTEM IS COMPLETELY OPERATIONAL ON EACH

FLOOR.

F. PATCH EXISTING NURSE CALL OPENINGS IF NOT

USED AND PAINT TO MATCH.

G. PATCH AND PAINT AT THE LOCATION OF THE

EXISTING NURSE CALL EQUIPMENT CABINET.

H. PROVIDE STAINLESS STEEL COVER PLATES AS

REQUIRED.

I. ALL NURSE CALL WORK SHALL BE COORDINATED

WITH THE COR AND NURSE MANAGER.

J. PATCH ALL PENETRATIONS AND OPENINGS IN

SMOKE AND FIRE WALLS WITH APPROVED UL

LISTED MATERIALS. SUBMIT APPLICATION PER VA.

SEE SPECIFICATIONS FOR FORM.

K. ALL DEVICES SHOWN TO BE REPLACED UNLESS

NOTED OTHERWISE.

L. THESE DRAWINGS ARE BASED ON FIELD SURVEY

AND EXISTING PLANS. VERIFY ALL FIELD

CONDITIONS.

M. COORDINATE ALL NURSE CALL SYSTEM WITH COR.

N. MOUNT NEW NCE CABINET ON FIRE RATED

PLYWOOD. PROVIDE TEMPORARY STAND ON

HEAVY DUTY CASTERS FOR THE NCE

CABINET/PLYWOOD. AFTER THE WORK IS

COMPLETE REMOVE THE EXISTING NCE CABINET.

THEN REMOVE THE TEMPORARY STAND AND

MOUNT THE NEW NCE CABINET/PLYWOOD AT THE

LOCATION OF THE EXISTING NCE LOCATION.

COORDINATE ALL WORK WITH COR.

O. REFER TO PHASING NOTES, SHEET T-001, FOR

ADDITIONAL INFORMATION.

P. COORDINATE ALL DOWNTIME WITH COR PRIOR TO

ANY WORK.

0 2 4 8

N O

R

TH

TRUE

0 2 4 8

N O

R

TH

TRUE

0 2 4 8 NORTH

TRUE

EXISTING PANEL -

PANEL '2C20G'

TELE

G17A

ELEC

G17

ELEC

G01

CORR

G21

DATA

G02

MURFREESBORO 120 - "G" FLOOR ELEC. ROOM G01

ENLARGEMENT (120TN111)

SCALE: 1/4" = 1' 0"

0 2 4 8

N O

R

TH

TRUE

SHEET NOTES:

SHEET KEY NOTES:#

'2C7A' - 3

'2C20G' - 18

MURFREESBORO 116 - TELECOM ROOM B152

ENLARGEMENT (116TN113)

SCALE: 1/4" = 1' 0"

0 2 4 8 NORTH

TRUE

SIGNAL

TELE

C100

'EC' - 23

MURFREESBORO 116 - SIGNAL/TELE. ROOM C100

ENLARGEMENT (116TN111)

SCALE: 1/4" = 1' 0"

MURFREESBORO 117 - "G" FLOOR TELE. ROOM G39

ENLARGEMENT (117TN111)

SCALE: 1/4" = 1' 0"

0 2 4 8

N O

R

TH

TRUE

MURFREESBORO 117 - "A" FLOOR TELE. ROOM 112B

ENLARGEMENT (117TN121)

SCALE: 1/4" = 1' 0"

0 2 4 8

N O

R

TH

TRUE

TELECOM

B152

'EB' - 2

'EB' - 2

TELE

G39

ELEC

G38

'2L7C' - 2

EXISTING PANEL -

PANEL '2L7C'

TELE

112B

ELEC

EXISTING PANEL-

PANEL '2C20A'

'2C20A' - 23

1. EXISTING NURSE CALL EQUIPMENT CABINET TO

BE REPLACED WITH NEW NURSE CALL CABINET.

EXTEND AND REUSE EXISTING CIRCUIT FOR NEW

CABINET.

2. LOCATION OF NEW NURSE CALL EQUIPMENT

CABINET. CONTRACTOR SHALL COORDINATE

WORK AND PHASING PER PLANS AND SPECS.

CONNECT TO EXISTING EMERGENCY ELECTRICAL

CIRCUIT.

3. PROVIDE NEW GROUND BUS BAR AND BOND TO

EXISTING BONDING/GROUNDING SYSTEM.

4. PROVIDE 2-CAT 6A CABLES TO CLOSEST DATA

RACK WITH SPARE NETWORK PORTS.

5. PROVIDE 2-10 AWG AND 1-10 AWG GND IN 3/4" C

TO SPARE 1P-20A CIRCUIT BREAKER.

6. PROVIDE 3" UL LISTED FIRE/SMOKE SLEEVE

ASSEMBLY.

7. LOCATION OF NEW NURSE CALL EQUIPMENT

CABINET. CONTRACTOR SHALL COORDINATE

WORK AND PHASING PER PLANS AND SPECS.

White/Blue Blue White/Orange

Orange

White/Green

Green

White/Brown Brown

W hi te /G re en

G re en

W hi te /B ro w n

Br ow n C ha nn el

D at a (R

IN

G

Au di o

(T

IP

C om m on

(S

LE

EV

E)

PILLOW

SPEAKER

(GEN4)

Pa tie nt S ta tio n

TV

C on ne ct or

Responder 5 Enhanced

Patient Station

Pillow Speaker Specific for

Responder 5

CAT 6

S

TYPICAL NURSE CALL SYSTEM RISER NOTES:

1. NURSE CALL EQUIPMENT CABINET

2. NURSE CALL CABLE, 4 PR CAT 6A (BLUE) OR FIBER OR PER MANUFACTURER'S

RECOMMENDATIONS.

3. NURSE CALL POWER CABLE, 2-12 AWG, 1-12 AWG EG IN 3/4" CONDUIT OR

PER MANUFACTURER'S RECOMMENDATIONS. REQUIRED ON FIRST DOME

LIGHT OR DOMELESS CONTROLLER OF EVERY SIX CONSECUTIVE

DOME LIGHTS OR DOMELESS CONTROLLERS ON CHAIN.

4. LIGHTING CONTROL CABLE, 3-20 AWG IN 1/2" CONDUIT OR PER

MANUFACTURER'S RECOMMENDATIONS.

5. NURSE CALL MULTI-COLOR DOME LIGHT WITH PILLOW SPEAKER

AND TV CONTROL.

6. NURSE CALL PATIENT BED STATION, SINGLE WITH CODE BLUE/CODE

WHITE ARE INTEGRATED INTO BED STATION, EXTERNAL DEVICES

FOR CODE BLUE/CODE WHITE ARE NOT REQUIRED AT THESE

LOCATIONS.

7.

8. NURSE CALL EMERGENCY STATION WITH PULL CORD. (+40")

9. NURSE CALL SHOWER EMERGENCY STATION WITH PULL CORD. (+72")

10. NURSE CALL MASTER CONSOLE STATION.

11. NURSE CALL DUTY/STAFF STATION (SEE DRAWINGS FOR MORE

INFORMATION).

12. NURSE CALL DOMELESS CONTROLLER (SEE DRAWINGS FOR MORE

INFORMATION).

13. TO OTHER NURSE CALL EQUIPMENT CABINET(S).

14. NURSE CALL CODE STATION (SEE DRAWINGS FOR MORE INFO).

15. NURSE CALL PILLOW SPEAKER AND CONTROLS (PATIENT ENTERTAINMENT

SYSTEM, GETWELL, LIGHTING, AND OTHER SYSTEMS PER VA).

16. PATIENT ROOM TV (INTEGRATE EXISTING TV WITH NEW NURSE CALL

SYSTEM).

17. PATIENT ROOM LIGHTING.

PROVIDE INTEGRATION WITH THE FOLLOWING:

A. HOSPITAL SIP PHONE SYSTEM.

B. VA'S PATIENT ENTERTAINMENT TV SYSTEM (GETWELL).

C. POCKET PAGERS.

D. HL7/ADT.

E. OTHER SYSTEMS AS IDENTIFIED IN SPECS.

NURSE CALL

EQUIPMENT

CABINET

TYPICAL PATIENT BATHROOMTYPICAL PATIENT BED

2 16

5 N12 N D

TO GROUNDING

BUS

GENERAL NURSE CALL SYSTEM RISER NOTES:

A. PROVIDE 1" CONDUIT FROM EACH DEVICE TO

THE CABLE TRAY (IF APPLICABLE).

B. CONTRACTOR SHALL VERIFY RACEWAY

REQUIREMENT WITH THE NURSE CALL

SYSTEM MANUFACTURER.

B

S

E E

M

D

TO NEXT

DOME LIGHT

5 N

B

PATIENT STATION/CODE BLUE PATIENT STATION

CODE BLUE

PATIENT STATION

CODE BLUE

REMODELED/NEW

EXISTING

P

BED RECEPTACLEBED RECEPTACLE

PROVIDE S.S.

COVER PLATE

S

P

(TYP.) PROVIDE A NEW STAINLESS

STEEL COVER PLATE FOR THE

EXISTING NURSE CALL DEVICES

BEING DEMOLISHED

TYPICAL NEW SINGLE PATIENT

STATION WITH CODE BLUE AND

BED RECEPTACLE (COLOR TO BE

COORDINATED WITH VA/COR)

EXISTING DATA

RACK

NEW

NURSE

CALL

EQUIPMENT

CABINET

BIO MED OR

ELECTRICAL OR

OIT ROOM

(SEE PLAN)

BIO MED OR

ELECTRICAL OR

OIT ROOM

(SEE PLAN)

PATIENT ROOM OR

BATHROOM OR

EXAM ROOM

(SEE PLAN)

DOME

LIGHT

10"

4"

1/4"

3/16" DIAMETER, TYP. FOR 6

1/4" DIAMETER, TYP. FOR 12

TMGB & TGB

1 TELECOM ROOM OPPER GOUND BAR, 1/4" x 4" x 10", HOLE CENTERS TO MATCH NEMA DOUBLE

LUG CONFIGURATION.

STANDOFF BRACKET ASSEMBLY WITH INSULATORS, TYP. FOR 2.

LOCK WASHER, TYPICAL FOR 2.

ANCHOR BOLTS, TYPICAL FOR 2.

A CONTINUOUS #1/0 GREEN INSULATED CONDUCTOR SHALL BE RUN

FROM SERVICE GROUND AT TMGB. BOND NCE CABINET WITH #4 GREEN INSULATED

CONDUCTOR.

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

JULY 19, 2021 ADRJVE

626A4-20-10420-171

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A. 107Engineers Architects

U.S. Department of Veterans Affairs

TVHS- NASHVILLE CAMPUS

1310 24TH AVE S,NASHVILLE, TENNESSEE 37212

TVHS- ALVIN C. YORK CAMPUS

3400 LEBANON PIKE, MURFREESBORO, TENNESSEE 37129

UPGRADE NURSE CALL SYSTEM

NASHVILLE/MURFREESBORO

CAMPUS

TK501

NURSE CALL DETAILS

2 VA'S PATIENT ENTERTAINMENT SYSTEM WIRING DETAIL

SCALE: N.T.S.

A. ALL NEW NURSE CALL CABLING INSTALLED

WITHOUT THE USE OF CONDUIT IS PERMITTED IF

POWER SUPPLIES ARE "POWER LIMITED" TYPE

AND CONDUCTORS ARE LISTED FOR SUCH USE

PER NEC 725, 760, AND 800.

1. FROM NEW NURSE CALL EQUIPMENT CABINET

RUN TWO CAT 6A CABLES TO TWO SPARE PORTS

IN PATCH PANEL, LABEL NURSE CALL.

2. PROVIDE PATCH CORD TO CYSCO SWITCH.

PROVIDE VLAN TO RUN ON CAMPUS FIBER OPTIC

CABLE BACKBONE. COORDINATE WITH OIT AND

COR.

3. PROVIDE "J-HOOKS" ABOVE CEILING FOR NURSE

CALL HORIZONTAL CABLING. "J-HOOKS" SHALL BE

SPACED 4-5 FEET O.C. OR LESS TO ENSURE THE

CABLES DO NOT SAG TOWARDS THE GROUND

MORE THAN 11.81" FROM THE TOP OF THE

CABLES TO THE LOWEST POINT AT THE BOTTOM

OF THE CABLES.

4. NURSE CALL CABLING FROM THE DOME LIGHT

OUTSIDE OF ROOMS OR IN CORRIDORS GOING

INTO THE ROOMS WITH NURSE CALL EQUIPMENT

TO BE INSTALLED IN CONDUIT.

NOTE: PULL CORDS IN BATHROOMS SHALL BE

ANTI-LIGATURE RIBBON PULL CORD AS SHOWN

IN PHOTO.

4 PULL CORD DETAIL

SCALE: N.T.S.

1 TYPICAL NURSE CALL SYSTEM RISER

SCALE: N.T.S.

3 PATIENT HEAD WALL

SCALE: N.T.S.

5 TYPICAL NETWORK CABLING RISER DIAGRAM

SCALE: N.T.S.

6 ROOM EQUIPMENT GROUND BAR

N.T.S.

SHEET NOTES:

SHEET KEY NOTES:#

(1) 4 PR UTP

DATA

CABLE/JACK

(1) 4 PR UTP

TELEPHONE

CABLE/JACK

1/2" HIGH BLACK LETTERS

ON CLEAR BACKGROUND,

PANDUIT OR EQUAL ON

PERMANENT LABEL,

TYPICAL.

XXX

XXX

B B

T B

BLANK

SINGLE GANG COVER

PLATE WITH 6 OUTLETS

(TYPICAL). LOCATIONS

AS SHOWN ON PLANS

TELE/DATA (TYP.) ( 2)

BLANK

C B

BLANK

BLANK

FINISHED FLOOR

MOUNTING HEIGHT AS

SHOWN IN DRAWINGS

4-11/16" SQ. BY 2-1/2"

DEEP BOX WITH SINGLE

GANG 5/8" TILE RING.

1-1/4" CONDUIT WITH

COMMUNICATIONS WIRING

WALL

CORRIDORROOM

6" MIN NYLON BUSHING

COORDINATE WITH DUCTWORK

EXTEND CONDUIT TO ABOVE

FINISHED ACCESSABLE

CEILING IN CORRIDOR TO

CABLE TRAY UNLESS NOTED

OTHERWISE.

SUSPENDED LAY-IN

CEILING

CABLE TRAY

1. FLOOR OR WALL ASSEMBLY - MIN 4-1/2 IN. (114 MM) THICK LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M3) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE

BLOCKS*. MAX DIAM OF CIRCULAR THROUGH OPENING IS 32-1/2 IN. (826 MM).

SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF

MANUFACTURERS.

1A. STEEL SLEEVE (OPTIONAL, NOT SHOWN) - NOM 12 IN. (305 MM) DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL PIPE SLEEVE CAST INTO CONCRETE FLOOR OR WALL. SLEEVE TO BE FLUSH WITH OR PROJECT MAX 2 IN. (51MM) FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL.

2. THROUGH PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF OPENING SHALL BE MIN OF 0 IN. (0 MM)(POINT CONTACT) TO MAX 1-3/8 IN. (35 MM).

PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING

TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:

A. STEEL PIPE - NOM 30 IN. (762 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.

A1. IRON PIPE - NOM 30 IN. (762 MM) DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.

B. CONDUIT - NOM 6 IN. (152 MM) DIAM (OR SMALLER) RIGID STEEL CONDUIT.

C. CONDUIT - NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING.

3. PACKING MATERIAL - POLYETHYLENE BACKER ROD OR NOM 1 IN. (25 MM) THICKNESS OF TIGHTLY-PACKED CERAMIC (ALUMINA SILICA) FIBER BLANKET, MINERAL WOOL BATT OR GLASS FIBER INSULATION MATERIAL USED AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF SOLID CONCRETE OR CONCRETE BLOCK WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF CAULK FILL MATERIAL (ITEM 4). AS AN ALTERNATE WHEN MAX PIPE SIZE IS 10 IN. (254 MM) DIAM AND WHEN MAX ANNULAR SPACE IS 1 IN. (25 MM), A MIN 1 IN. (25 MM) THICKNESS OF TIGHTLY-PACKED CERAMIC FIBER BLANKET OR MINERAL WOOL BATT PACKING MATERIAL MAY BE RECESSED MIN 1/2 IN. (13 MM) FROM BOTTOM SURFACE OF FLOOR OR FROM EITHER SIDE OF SOLID CONCRETE WALL.

4. FILL,VOID OR CAVITY MATERIALS* - CAULK OR SEALANT - APPLIED TO FILL THE ANNULAR SPACE TO THE

MIN THICKNESS SHOWN IN THE FOLLOWING TABLE:

(A) BR = POLYETHYLENE BACKER ROD.

CF = CERAMIC FIBER BLANKET.

GF = GLASS FIBER INSULATION.

MW = MINERAL-WOOL BATT.

(B) CAULK INSTALLED FLUSH WITH TOP SURFACE OF FLOOR OR BOTH SURFACES OF WALL.

(C) CAULK INSTALLED FLUSH WITH BOTTOM SURFACE OF FLOOR OR ONE SURFACE OF SOLID (NON-

CONCRETE BLOCK) WALL.

3M COMPANY - CP 25WB+ CAULK OR FB-3000 WT SEALANT.

(NOTE: W RATING APPLIES ONLY WHEN FB-3000 WT SEALANT IS USED.)

*BEARING THE UL CLASSIFICATION MARKING

MAX PIPE DIAM

IN. (MM)

10 (254)

10 (254)

30 (762)

MAX ANNULAR

SPACE IN. (MM)

1 (25)

1 (25)

2-1/2 (64)

PACKING MATL

TYPE (a)

BR, CF, GF OR MW

CF OR MW

BR, CF, GF OR MW

MIN. CAULK THKNS

IN. (MM)

1/2 (13) (b)

1/2 (13) (c)

1 (25) (b)

System No. C-AJ-1001 June 15, 2005 F Rating - 3 Hr T Rating - 0 Hr

W Rating - Class I (See Item 4)

SECTION A-A

4 4 1

A

A

1. FLOOR OR WALL ASSEMBLY - LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M3) CONCRETE.

EXCEPT AS NOTED IN TABLE UNDER ITEM 4, MIN THICKNESS OF SOLID CONCRETE FLOOR OR WALL ASSEMBLY IS 4-1/2 IN. (114 MM). FLOOR MAY ALSO BE CONSTRUCTED OF ANY MIN 6 IN. (152 MM) THICK UL CLASSIFIED HOLLOW CORE PRECAST CONCRETE UNITS* . WHEN FLOOR IS CONSTRUCTED OF HOLLOW CORE PRECAST CONCRETE UNITS, PACKING MATERIAL (ITEM 3) AND CAULK FILL MATERIAL (ITEM 4) TO BE INSTALLED SYMMETRICALLY ON BOTH SIDES OF FLOOR, FLUSH WITH FLOOR SURFACE. WALL ASSEMBLY MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF OPENING IS IN SOLID LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE. FLOOR IS 32 IN. (813 MM).

MAX DIAM OF OPENING IN FLOOR CONSTRUCTED OF HOLLOW-CORE PRECAST CONCRETE UNITS IS 7 IN. (178 MM).

SEE CONCRETE BLOCKS (CAZT) AND PRECAST CONCRETE UNITS (CFTV) CATEGORIES IN THE FIRE RESISTANCE

DIRECTORY FOR NAMES OF MANUFACTURERS.

1A. STEEL SLEEVE (OPTIONAL, NOT SHOWN) - MAX 15 IN. (381 MM) ID (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL SLEEVE CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY. SLEEVE MAY EXTEND A MAX OF 2 IN. (51 MM) ABOVE TOP OF FLOOR OR BEYOND EITHER SURFACE OF WALL. MAX 16 IN. (406 MM) ID (OR SMALLER) MIN 0.028 (0.71 MM) WALL THICKNESS (OR HEAVIER) GALVANIZED STEEL SLEEVE CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY. SLEEVE

MAY EXTEND A MAX OF 1/2 IN. (13 MM) BEYOND EITHER SURFACE OF FLOOR OR WALL.

2. THROUGH PENETRANTS - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. MAX ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND EDGE OF THROUGH OPENING OR SLEEVE IS DEPENDENT ON THE PARAMETERS SHOWN IN ITEM 4. MIN ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND EDGE OF THROUGH OPENING IS 0 IN. (0 MM) (POINT CONTACT). PIPE CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE FOLLOWING TYPES AND

SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:

A. STEEL PIPE - NOM 30 IN. (762 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.

B. IRON PIPE - NOM 30 IN. (762 MM) DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.

C. CONDUIT - NOM 6 IN. (152 MM) DIAM (OR SMALLER) RIGID STEEL CONDUIT.

D. CONDUIT - NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING.

E. COPPER - TUBING NOM 6 IN. (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBE.

F. COPPER PIPE - NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

3. PACKING MATERIAL - POLYETHYLENE BACKER ROD OR NOM 1 IN. (25 MM) THICKNESS OF TIGHTLY-PACKED MINERAL WOOL BATT OR GLASS FIBER INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO

ACCOMMODATE THE REQUIRED THICKNESS OF CAULK FILL MATERIAL (ITEM 4).

4. FILL,VOID OR CAVITY MATERIAL* - CAULK OR SEALANT - APPLIED TO FILL THE ANNULAR SPACE FLUSH WITH TOP SURFACE OF FLOOR. IN WALL ASSEMBLIES, REQUIRED CAULK THICKNESS TO BE INSTALLED SYMMETRICALLY ON BOTH SIDES OF WALL, FLUSH WITH WALL SURFACE. AT POINT CONTACT LOCATION BETWEEN PENETRANT AND SLEEVE OR BETWEEN PENETRANT AND CONCRETE, A MIN 1/4 IN. (6 MM) DIAM BEAD OF CAULK SHALL BE APPLIED AT TOP SURFACE OF FLOOR AND AT BOTH SURFACES OF WALL. THE HOURLY F RATINGS AND THE MIN REQUIRED CAULK THICKNESSES

ARE DEPENDENT UPON A NUMBER OF PARAMETERS, AS SHOWN IN THE FOLLOWING TABLE:

(A)MIN 2 IN. (51 MM) THICKNESS OF MINERAL WOOL BATT INSULATION REQUIRED IN ANNULAR SPACE.

(B)MIN 1 IN. (25 MM) THICKNESS OF MINERAL WOOL BATT INSULATION REQUIRED IN ANNULAR SPACE ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. MIN 1 IN. (25 MM) THICKNESS OF CAULK TO BE INSTALLED FLUSH WITH EACH SURFACE

OF FLOOR OR WALL ASSEMBLY.

3M COMPANY - CP 25WB+ CAULK OR FB-3000 WT SEALANT. (NOTE: W RATING APPLIES ONLY WHEN FB-3000 WT SEALANT

IS USED.)

*BEARING THE UL CLASSIFICATION MARKING

MIN FLOOR OR

WALL THKNS IN.

(MM)

2-1/2 (64)

2-1/2 (64)

4-1/2 (114)

NOM PIPE TUBE OR

CONDUIT DIAM IN.

(MM)

1/2-12 (13-305)

1/2-12 (13-305)

1/2-6 (13-152)

MAX

ANNULAR

SPACE IN.

(MM)

1-3/8 (35)

3-1/4 (83)

MIN. CAULK

THKNS IN.

(MM)

1/2 (13)

1 (25)

1/4 (6) (a)

System No. C-AJ-1044 June 15, 2005

F Ratings - 2, 3, and 4 Hr (See Items 2A and 4) T Rating - 0 Hr

L Rating At Ambient - 2 CFM/sq ft L Rating At 400 F - less than 1 CFM/sq ft

W Rating - Class I (See Item 4)

SECTION A-A

A

A

F

RATING

HR

1-3/8 (35)

1/2 (13)

1 (25)

1 (25)

1 (25)

2 (51)

1 (25) (b)1-3/8 (35)

3-1/4 (83)

2 (51)

2 (51)

2 (51)

1-1/4 (32)1/2-12 (13-305)

1/2-12 (13-305)

22-30 (558-762)

1/2-20 (13-508)

1/2-6 (13-152)

1/2-20 (13-508)

4-1/2 (114)

4-1/2 (114)

4-1/2 (114)

4-1/2 (114)

4-1/2 (114)

5-1/2 (140)

1. WALL ASSEMBLY - THE 1, 2, 3 OR 4 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:

A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS (MAX 2 HR FIRE RATED ASSEMBLIES) OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER SPACED 16 IN. (406 MM) OC WITH NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER END PLATES AND CROSS BRACES. STEEL STUDS TO BE MIN 3-5/8 IN. (92 MM)

WIDE BY 1-3/8 IN. (35 MM) DEEP CHANNELS SPACED MAX 24 IN. (610 MM) OC.

B. GYPSUM BOARD* - NOM 1/2 OR 5/8 IN. (13 OR 16 MM) THICK, 4 FT. (122 CM) WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF

OPENING IS 26 IN. (660 MM).

2. THROUGH PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM.

This is the start of the file's text. The full file is on GovTribe.