Upgrade Nurse Call Drawings Part3.pdf

PDF 9 MB Posted

Attached to
Z2DZ-- Project 626A4-20-104 - Upgrade Nurse Call System
Solicitation number
36C24921R0141
Issued by

About this file

This document package outlines requirements for an upgrade to the nurse call system at the Alvin C. York VA Medical Center campuses in Murfreesboro and Nashville, Tennessee. The solicitation calls for experienced healthcare contractors to replace nurse call devices, cabling, and equipment cabinets across multiple buildings according to provided drawings, specifications, and a statement of work. The contractor must coordinate all work with the center of responsibility and nurse manager. The upgrade aims to replace an existing one-for-one system with new devices shown on drawings. Work includes demolition of current components, installation of new nurse call stations, cabling, and equipment in patient rooms, corridors, and ancillary spaces across several buildings. The solicitation number is 36C24921R0141 and responses are due by an unspecified date. The Department of Veterans Affairs Veterans Health Administration is listed as the contracting agency.

View the file

Other files

File Type Posted
36C24921R0141 0008.docx DOCX document
JA Brand Name Nurse Call System.pdf PDF
36C24921R0141 0007.docx DOCX document
36C24921R0141 0006.docx DOCX document
36C24921R0141 0005.docx DOCX document
WD TN20220083 01-07-2022 Davidson County TN.pdf PDF
36C24921R0141 0004.docx DOCX document
WD TN20220100 01-07-2022 Rutherford County TN.pdf PDF
36C24921R0141 0003.docx DOCX document
36C24921R0141 0002.docx DOCX document
Government Answers to Industry Questions Upgrade Nurse Call System.pdf PDF
Nashville Nurse Call Site Visit 12.20.21.pdf PDF
36C24921R0141 0001.docx DOCX document
Murfreesboro Nurse Call Site Visit 12.21.21.pdf PDF
VHA Supplemental Contract Requirements for Combatting COVID-19 Updated 12-14-2021.pdf PDF
WD TN20210083 07_09_2021_Davidson.pdf PDF
Upgrade Nurse Call Drawings Part4.pdf PDF
Price Proposal Template.xlsx XLSX spreadsheet
36C24921R0141_1.docx DOCX document
Contractor EMR Certification Form.pdf PDF
PPQ-Template.pdf PDF
Upgrade Nurse Call Drawings Part2.pdf PDF
Upgrade Nurse Call Drawings Part5.pdf PDF
General Conditions Breakout.xlsx XLSX spreadsheet
Specs Combined Upgrade Nurse Call.pdf PDF
Upgrade Nurse Call Drawings Part1.pdf PDF
Upgrade Nurse Call Drawings Part6.pdf PDF
WD TN20210100 07_09_2021_Rutherford.pdf PDF
RFI Form 36C24921R0141.pdf PDF
Show all 29

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CORRIDOR

G31

G67

STOR

G23F

SPD

G23E

CORRIDOR

G14

CORRIDOR

G46

CORRIDOR

G47

CORRIDOR

G48

CORRIDOR

G45

CORRIDOR

G44

HAC

G23B

PATHOLOGY

G23

EQUIPMENT

G36B

CAMERA

EXAM

G37B

CONTROL/EXAM

RM

G37C

CORRIDOR

G25

CHEST

RM

G16

CONTROL

RM

G15

RAD RM

G17

REST

RM

G23C

G42

NUCLEAR

MED

G37A

CORRIDOR

G49

STAIR

G38

PT

WAITING

G20

STAIR-1

G14A

SOILED

UTILITY

G45R

PHY

WORKROOM

G45S

DENTAL

G07

DENTAL

G09

FAN

RM 6

G22

MULTI

PURP

G45T

EXAM

G45V

TLT

G45Q

CORRIDOR

G39J

NUCLEAR

MED/RAD

G39

ELEVATOR-2

ELEVATOR-1

LINEN

CHUTE

G21A

EXAM

G45L

HOLDINGULTRASOUND

G14

TLT

G45U

ULTRASOUND

G18

RECEPTION

G19

TLT

G18A

TLT

G20A

TLT

G18A

ELEC

G17

MECH

G05

FAN

RM-3

G13

TLT

G06

OPERATORY

G09A

SPD

G23D

WALK-IN

REFRIG

ELEC

EQUIP

G29

ELEC

G28

MALE

LOCKERS

G01A

SPD

OFFICE

G01B

MECH

G41CLEAN

STORAGE

G01

STAIR

G27

X-RAY

G07D

VEST

G07A

DARK

RM

G07B

OPERATORY

G08A

TLT

G35

ELEC

SWITCHGEAR

G30 TLT

G32

STOR

G33

CHANGE

RM

G03

WORKROOM

G09C

WAITING

TLT

G37B

VEST

G44B

CORRIDOR

G01C

MED

RESIDENTS

G24

SPD

ASST

CHIEF

G24A

MECH

SPACE

G44A

ELECTRICAL

EQUIP

G25

ELECTRICAL

EQUIP

G26

LOCKERS

G36

STATIONARY

IMAGING

G37E MECH

G37L

NUCLEAR

MED

G37

ULTRASOUND

G34

EXAM

G45N

ULTRASOUND

G18

SECY

AND

CLERK

G12

WAITING

G07C

DECONTAMINATION

G02

G032

STERILIZATION/CLEAN

RM

G01D

RECEIVING

G42

HAC

G40A

MECH

G40

ELEC

G39L

STRESS

LAB

G39K

BONE

DENSITY

EXAM

G39i

STOR

G39H

MULTI

PURP

G39A

LOGISTICS

G39B

OFFICE

G39C

HOT LAB

INJECTION ROOM

G39D

OFFICE

G39E

OFFICE

G39F

OFFICE

G39G

STOR

G08

OPERATORY

G09D

LAB

G09B

OPERATORY

G09E

OPERATORY

G10

CHIEF

DENTAL

G11

EXAM

G36A

TOILET

G36C

CONTROL

G36D

RECEPTION

G36E

G39J

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

JULY 19, 2021 ADRJVE

626A4-20-10420-171

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A. 107Engineers Architects

U.S. Department of Veterans Affairs

TVHS- NASHVILLE CAMPUS

1310 24TH AVE S,NASHVILLE, TENNESSEE 37212

TVHS- ALVIN C. YORK CAMPUS

3400 LEBANON PIKE, MURFREESBORO, TENNESSEE 37129

UPGRADE NURSE CALL SYSTEM

NASHVILLE/MURFREESBORO

CAMPUS

01T110

MURFREESBORO BUILDING 1-

"G" FLOOR NURSE CALL OVERALL PLAN

1 MURFREESBORO BUILDING 1 - "G" FLOOR NURSE CALL OVERALL PLAN

SCALE: 1/16" = 1' 0"

01TD111

01TN111

01TD112

01TN112

N O

R

TH

TRUE

8 16 320

1. LOCATION OF NEW NURSE CALL EQUIPMENT

CABINET AND HEAD END EQUIPMENT.

A. REUSE THE EXISTING NURSE CALL RACEWAY

SYSTEM FOR NEW NURSE CALL CABLING. PROVIDE

"J-HOOKS" 2' O.C. WHERE NEW CABLING IS TO BE

INSTALLED.

B. PROVIDE UL LISTED FIRE/SMOKE RATED SLEEVES

WHERE PENETRATING EXISTING FIRE/SMOKE RATED

WALLS.

SHEET NOTES:

SHEET KEY NOTES:#

DocuSign Envelope ID: BA659FA3-E303-449B-A1FA-811899152E7D

7/19/2021

PORCH

165164

163A

161A

160A

129C

142126

107A

106A 155

156A

156B

153A

146A

144143

146A

108A

114A

105 104

102 101 100 159 158

157 156

136 137

138A 139

140 141 142

125A

116117118

119B 123 122121120119

119A

111A

111C

111B

149A

145 144

CORR

CORRIDORCORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

CORR

CORRIDOR

CORRIDOR

CORRIDOR

DIRECTORS

CONFERENCE

ELEVATOR-2

NURSING

TELEPHONE

TELE

STORAGE

LABORATORY

CHIEFPATHOLOGY

RESPITORY

SUPV

TOILET

HAC

TELE TELE

STOR

TOILET

TOILET

ELEC

HAC

STAFF

LOUNGE

LOCKERS

PATH

LAB

OFFICESECY

CHUTE

TOILET

STAIR

-2

MECH

SPACE

PUBLIC

AFFAIRS

STAIR

#3

ELEVATOR-1

TOILET

MULTI

PURP

CORRIDOR

WAITING

STAIR

-1

ECHO

LAB

HOME

OXYGEN

WAITING

ECHO

LAB

PULM

LAB

MAIN

LOBBY OFFICE

CHIEF

OF

STAFF

SECY TO

DEPUTY

CME

DEPUTY

CME

CONFERENCE COO

WAITING RM

OFFICE

SEC'S-DIR &

ASST DIR MED

CTR

DIRECTOR DIRECTOR

COO

NASHVILLE TOILET

CONFERENCE

RM

TOILET

TELEPHONE

OPERATORS

NURSING

NURSING

ARTERIAL

BLOOD

GAS

LAB

CHIEF OF

STAFF

OFFICE

ELEC

EEG

LABPHYS

CHIEF

PULM

DISEASE

READING

THERAPY SPD

EQUIP

DECON

VENTILATOR

STORAGE

RESP

THERAPYIRM

MED

RM

CORR

PHYSICIANS

PHYSICIANS

PHYSICIANS

MED

SVC-AO

MED SVC

CLERKS

PHYSICIAN

PHYSICIAN

MED

SVC

MED

SVC

CHIEF

NURSING

NURSING

NURSING

NURSING

NURSING

NURSING

NURSING

OFFICE

DIRECTOR DIRECTOR

DIRECTOR

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

JULY 19, 2021 ADRJVE

626A4-20-10420-171

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A. 107Engineers Architects

U.S. Department of Veterans Affairs

TVHS- NASHVILLE CAMPUS

1310 24TH AVE S,NASHVILLE, TENNESSEE 37212

TVHS- ALVIN C. YORK CAMPUS

3400 LEBANON PIKE, MURFREESBORO, TENNESSEE 37129

UPGRADE NURSE CALL SYSTEM

NASHVILLE/MURFREESBORO

CAMPUS

01T120

MURFREESBORO BUILDING 1 -

"1" FLOOR NURSE CALL OVERALL PLAN

1 MURFREESBORO BUILDING 1 - "1" FLOOR NURSE CALL OVERALL PLAN

SCALE: 1/16" = 1' 0"

01TD121

01TN121

01TD121

N O

R

TH

TRUE

8 16 320

1. LOCATION OF NEW NURSE CALL EQUIPMENT

CABINET AND HEAD END EQUIPMENT.

A. REUSE THE EXISTING NURSE CALL RACEWAY

SYSTEM FOR NEW NURSE CALL CABLING. PROVIDE

"J-HOOKS" 2' O.C. WHERE NEW CABLING IS TO BE

INSTALLED.

B. PROVIDE UL LISTED FIRE/SMOKE RATED SLEEVES

WHERE PENETRATING EXISTING FIRE/SMOKE RATED

WALLS.

SHEET NOTES:

SHEET KEY NOTES:#

CORR

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

RESTROOM WITH

SHOWER

356A

RESTROOM

WITH

SHOWER

309A

RESTROOM

WITH SHOWER

327A

CLINICAL

PHARMACY

NURSE

STATION

ONE BED ROOM

RESTROOM

WITH

SHOWER

325A

TWO BED ROOM

TWO BED ROOM

TWO BED ROOM

RESTROOM

WITH

SHOWER

320A

TWO BED ROOM

TELE

STOR

ELEC

RESTROOM

WITH

SHOWER

341A

ONE BED ROOM

RESTROOM

WITH

SHOWER

338A

CORRIDOR

RESTROOM

WITH

SHOWER

373A

TWO BED ROOM

PHYS

HAC

STAIR-3

STAIR-2

CORRIDOR

NURSES

STATION

MECH

CONGRE BATH

ELEC.

STOR

TELE

351A

TELE

HAC

TLT

359A

ONE BED ROOM

STAIR-1

MECH

ONE BED ROOM

NURSE MGR

TELE

LOCKER

NOUR KITCH

PHYSICIAN

STOR

RESTROOM

WITH

SHOWER

329A

ONE BED ROOM

ONE BED ROOM

TWO BED ROOM

TWO BED ROOM

CLEAN

EQUIPMENT

ELEC

ISOLATION

ANTE

313B

RESTROOM

WITH

SHOWER

313A

CHARTING

314A

MED

314B

DAY RM

CLEAN

LINEN

ONE BED ROOM

TWO BED ROOM

RESTROOM

WITH

SHOWER

317A

STOR

ONE BED ROOM

RESTROOM

WITH SHOWER

358A

TWO BED ROOM

TWO BED ROOM

SLEEP LAB

MECH

SPACE

301A

SLEEP LAB

RESTROOM

WITH

SHOWER

RESTROOM

WITH

SHOWER

304A

CONTROL

RETHERM

STAFF

RESTROOM

WITH

SHOWER

344A

TELE

DINING

RESTROOM

WITH

SHOWER

345A

TWO BED ROOM

LIVING

CENTER

RESIDENT

NOUR.

PALLIATIVE

NURSE

COORDINATOR

352A

CHAPEL

INTERDISCIPLINE

TREATMENT

ROOM

SOCIAL

WORKER

PHYSICIAN

SLEEP LAB

BREAK RM

ELEVATOR - 2

ELEVATOR - 1

STAFF

TLT

LINEN

SOILED

UTILITY

ELEC

CHUTE

ONE BED ROOM

ISOLATION

ANTE

372B

REST RM WITH

SHOWER

372A

MDS NURSE

ASSISTANT

NURSE

MANAGER

PHYS ASST

RESTROOM

WITH SHOWER

362A

ONE BED ROOM

ONE BED ROOM

REST RM

WITH

SHOWER

368A

ONE BED ROOM

ONE BED ROOM

RESTROOM

WITH

SHOWER

366A

ONE BED ROOM

ONE BED ROOM

RESTROOM

WITH

SHOWER

364A

STOR

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

JULY 19, 2021 ADRJVE

626A4-20-10420-171

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A. 107Engineers Architects

U.S. Department of Veterans Affairs

TVHS- NASHVILLE CAMPUS

1310 24TH AVE S,NASHVILLE, TENNESSEE 37212

TVHS- ALVIN C. YORK CAMPUS

3400 LEBANON PIKE, MURFREESBORO, TENNESSEE 37129

UPGRADE NURSE CALL SYSTEM

NASHVILLE/MURFREESBORO

CAMPUS

01T140

MURFREESBORO BUILDING 1 -

"1B" FLOOR NURSE CALL OVERALL

PLAN

1 MURFREESBORO BUILDING 1 - "1B" FLOOR NURSE CALL OVERALL PLAN

SCALE: 1/16" = 1' 0"

01TD141

01TN141

01TD142

01TN142

N O

R

TH

TRUE

8 16 320

1. LOCATION OF NEW NURSE CALL EQUIPMENT

CABINET AND HEAD END EQUIPMENT.

A. REUSE THE EXISTING NURSE CALL RACEWAY

SYSTEM FOR NEW NURSE CALL CABLING. PROVIDE

"J-HOOKS" 2' O.C. WHERE NEW CABLING IS TO BE

INSTALLED.

B. PROVIDE UL LISTED FIRE/SMOKE RATED SLEEVES

WHERE PENETRATING EXISTING FIRE/SMOKE RATED

WALLS.

SHEET NOTES:

SHEET KEY NOTES:#

LOADING DOCK OUTDOOR

TRANSFORMER

PATIO

HYDRO

THERAPY

COAT

A106A

TOILET

B115

TOILET

B117A

TOILET

B147A

CORRIDOR

C002

CORRIDOR

C015

CORRIDOR

C016

CORRIDOR

C013

CORRIDOR

C004

CORRIDOR

C014

CORRIDOR

C003

CORRIDOR

CO11

CORRIDOR

COO9

CORRIDOR

C008

CORRIDOR

COO7

TOILET

STAFF

B105

DAY AREA

B107

NURSE

STATION

B106

INTERVIEW

RM

B104

2- BED RM

B148

2- BED RM

B147

TOILET

B145A

2- BED RM

B146

2- BED RM

B145

TOILET

B143A

2- BED RM

B144

2- BED RM

B143

TOILET

B138A

CONG.

BATH

B137

2- BED RM

B138

TOILET

B139A

2- BED RM

B139

TOILET

B141A

2- BED RM

B140

2- BED RM

B141

2- BED RM

B142

TOILET

B121

NURSE

MGR

B122

TOILET

B123A STORAGE

B124

1- BED RM

B123

TOILET

B125A

2- BED RM

B125

2- BED RM

B126

TOILET

B127A

2- BED RM

B127

TOILET

B131A

TOILET

B133A

2- BED RM

B134

2- BED RM

B133

2- BED RM

B132

2- BED RM

B131

TOILET

B129A

2- BED RM

B130

2- BED RM

B129

OXY/EQUIP

STG

B128

2- BED RM

B118

2- BED RM

B117

2- BED RM

B116

2- BED RM

B114

TOILET

B112

2- BED RM

B113

2- BED RM

B111

TOILET/

SHOWER

B110

STORAGE

B109

CONFERENCE

RM

B108

SOILED

LINEN

A115

MECH

A114

ELECTRICAL

A114A

GENERATOR

A114B

REC

THERAPY

A111

RE-THERM

A112E

STORAGE

A112D

OFFICE

A112C

HAC

A112B

TRASH

COLLECT

A113

STORAGE

A112

STORAGE

A112A

DINING

RM

A110

PT CLINIC

A120

PT / OT OFFICE

A120B

STORAGE

A120A

STORAGE

A122

STORAGE

A121A

OCC THERAPY

A121

NURSING

A103

CHAPLAIN

A101

PHYSICIAN ASST

A102

CONFERENCE RM

A104

MULTI

PURPOSE

A105

TOILET

A109

TOILET

A108

STORAGE

A107

RESIDENTS

LOUNGE

C152

NURSE

STATION

C012

LOCKER

A106

SIGNAL

TELE

C100WORK

C101

STORAGE

C103

NOUR

KITCHEN

C102

STORAGE

C152A

MED

C151

STAFF

TOILET

C150

CHAPLAIN

OFFICE

C149

TOILET

C147A

NURSE MGR

C148

1- BED RM

C147

TOILET

C146

LAUNDRY

C143

TOILET

C144A

1- BED RM

C145

1- BED RM

C144

TOILET

C141A

1- BED RM

C142

1- BED RM

C141

OXYGEN

STORAGE

C140

CLEAN

LINEN

C132

SOILED

UTILITY

C133

TOILET

C134A

2- BED RM

C134

2- BED RM

C135

TOILET

C136A

2- BED RM

C136

2- BED RM

C137

TOILET

C138A

2- BED RM

C138

2- BED RM

C139

ELECTRICAL

C116

TOILET

C117A

CONGREGATE

BATH

C117

TOILET

C104A

2- BED RM

C104

2- BED RM

C105

TOILET

C106A

2- BED RM

C106

2- BED RM

C107

TOILET

C108A

2- BED RM

C108

2- BED RM

C109

HAC

C115

TOILET

C114A

2- BED RM

C114

TOILET

C112A

2- BED RM

C113

2- BED RM

C112

TOILET

C110A

2- BED RM

C111

2- BED RM

C110

TOILET

C118A

2- BED RM

C118

2- BED RM

C119

TOILET

C120A

2- BED RM

C120

2- BED RM

C121

TOILET

C122A

2- BED RM

C122

2- BED RM

C123

PRIVATE

BATH

C131

DENTAL

TREATMENT

C130

TOILET

C129A

STORAGE

C128

1- BED

RM

C129

TOILET

C126A

2- BED RM

C127

TOILET

C124A

2- BED RM

C126

2- BED RM

C125

2- BED RM

C124

TLT

ELEC

ROOM

B136

LAUNDRY

B135

SOCIAL

WORKER

B120NURSE

PRACT

B119

NURSE

NOOK

HAC

B102

CLEAN

LINEN

B149

B150

BIO

MED

B151

TELECOM

B152

LOUNGE

B154

MDS

B155

TLT

B156

B153

RECEPT./

WORK ORDER

DESK

TOILET

B154A

B137A

MEDS ROOM

NURSE

STATION

DAY ROOM

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

JULY 19, 2021 ADRJVE

626A4-20-10420-171

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A. 107Engineers Architects

U.S. Department of Veterans Affairs

TVHS- NASHVILLE CAMPUS

1310 24TH AVE S,NASHVILLE, TENNESSEE 37212

TVHS- ALVIN C. YORK CAMPUS

3400 LEBANON PIKE, MURFREESBORO, TENNESSEE 37129

UPGRADE NURSE CALL SYSTEM

NASHVILLE/MURFREESBORO

CAMPUS

116T110

MURFREESBORO BUILDING 116 -

NURSE CALL OVERALL PLAN

1 MURFREESBORO BUILDING 116 - NURSE CALL OVERALL PLAN

SCALE: 1/16" = 1' 0"

N O

R

TH

TRUE

8 16 320

01TD111

01TN111

01TD111

01TN111

01TD112

01TN112

116TD113

116TN113

116TD113

116TN113

1. LOCATION OF NEW NURSE CALL EQUIPMENT

CABINET AND HEAD END EQUIPMENT.

A. REUSE THE EXISTING NURSE CALL RACEWAY

SYSTEM FOR NEW NURSE CALL CABLING. PROVIDE

"J-HOOKS" 2' O.C. WHERE NEW CABLING IS TO BE

INSTALLED.

B. PROVIDE UL LISTED FIRE/SMOKE RATED SLEEVES

WHERE PENETRATING EXISTING FIRE/SMOKE

RATED WALLS.

SHEET NOTES:

SHEET KEY NOTES:#

G67

CORRIDOR

G14

CORRIDOR

G46

CORRIDOR

G47

CORRIDOR

G45

CORRIDOR

G25

CHEST

RM

G16

CONTROL

RM

G15

RAD RM

G17

PT

WAITING

G20

STAIR-1

G14A

SOILED

UTILITY

G45R

PHY

WORKROOM

G45S

DENTAL

G07

DENTAL

G09

FAN

RM 6

G22

MULTI

PURP

G45T

EXAM

G45V

TLT

G45Q

LINEN

CHUTE

G21A

EXAM

G45L

HOLDINGULTRASOUND

G14

TLT

G45U

ULTRASOUND

G18

RECEPTION

G19

TLT

G18A

TLT

G20A

TLT

G18A

ELEC

G17

MECH

G05

FAN

RM-3

G13

TLT

G06

OPERATORY

G09A

SPD

OFFICE

G01B

X-RAY

G07D

VEST

G07A

DARK

RM

G07B

OPERATORY

G08A

CHANGE

RM

G03

WORKROOM

G09C

VEST

G44B

EXAM

G45N

ULTRASOUND

G18

SECY

AND

CLERK

G12

WAITING

G07C

DECONTAMINATION

G02

G032

STERILIZATION/CLEAN

RM

G01D

STOR

G08

OPERATORY

G09D

LAB

G09B

OPERATORY

G09E

OPERATORY

G10

CHIEF

DENTAL

G11

N

E

N

E

TO BUILDING 120

TO BUILDING 120

DENTAL

TO BUILDING 117

RADIOLOGY

TK403

EXISTING PANEL -

PANEL '2LC1G'

AREA OF WORK

KEY PLAN

A B C

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

JULY 19, 2021 ADRJVE

626A4-20-10420-171

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.

NURSE CALL PATIENT BED INTERFACE RECEPTACLE (37 PIN)

WALL RATINGS

1 HR FIRE WALL

1 HR FIRE SMOKE WALL

2 HOUR FIRE WALL

2 HOUR FIRE SMOKE WALL

NON-RATED SMOKE PARTITION

SMOKE RESISTIVE HAZARDOUS

ROOM ENCLOSURE

107Engineers Architects U.S. Department of Veterans Affairs

TVHS- NASHVILLE CAMPUS

1310 24TH AVE S,NASHVILLE, TENNESSEE 37212

TVHS- ALVIN C. YORK CAMPUS

3400 LEBANON PIKE, MURFREESBORO, TENNESSEE 37129

UPGRADE NURSE CALL SYSTEM

NASHVILLE/MURFREESBORO

CAMPUS

NURSE CALL EQUIPMENT CABINETNCE

NURSE CALL SYMBOL LEGEND

SYMBOL DESCRIPTION

A NURSE CALL AUXILIARIES

B ENHANCED NURSE CALL, STAND ALONE, CODE

BLUE STATION WITH CLEAR BUTTON COVER

D NURSE CALL DUTY STATION

NURSE CALL EMERGENCY STATION

(SEE T-001 FOR MORE SPECIFICS, PB - PUSH BUTTON NO

PULL CORD, HS - HIGH SECURITY STEEL COVER PLATE)

M NURSE CALL MASTER STATION/CONSOLE

NURSE CALL PATIENT STATION

(PB - PUSH BUTTON, M - MICROPHONE, K -KEYED, HS - HIGH

SECURITY STEEL COVER PLATE)

N NURSE CALL DOME LIGHT

(Z - ZONE LIGHT, V - VANDAL RESISTANT)

N NURSE CALL DOME LIGHT - WALL MOUNTED

BUTTON STATION WITH CLEAR BUTTON COVER

NUMBER OF BUTTONS (1 - SINGLE BUTTON, 2 - DOUBLE

BUTTON)

BUTTON PROGRAMING (B- CODE BLUE, P - PUSH FOR HELP,

S - STAFF ASSIST)

C

NURSE CALL PATIENT STATION WITH CALL CORD INCLUDES:

- CODE BLUE

- STAFF ASSIST

- AUDIO

- CLEAR BUTTON COVER

(2 - DUAL PATIENT STATION, HS - VANDAL RESISTANT HIGH

SECURITY STEEL COVER PLATE)

E

N

S S S S S S

P

Z

M

PB

S

T NURSE CALL STAFF TERMINAL

MATV OR CATV WALL MOUNTED

MATV OR CATV CEILING MOUNTED

NURSE CALL PATIENT STATION WITH PILLOW SPEAKER (GET

WELL) INCLUDES:

- CODE BLUE

- STAFF ASSIST

- AUDIO

- CLEAR BUTTON COVER

(2 - DUAL PATIENT STATION, HS - VANDAL RESISTANT HIGH

SECURITY STEEL COVER PLATE)

HS

R

BS

P

01TD111

MURFREESBORO BUILDING 1-

"G" FLOOR NURSE CALL PARTIAL

DEMOLITION PLAN AREA A

1 MURFREESBORO BUILDING 1 - "G" FLOOR NURSE CALL PARTIAL DEMOLITION PLAN AREA A

SCALE: 1/8" = 1' 0"

N O

R

TH

TRUE

4 8 160

SE

E

D

ET

AI

L

1/

TD

SE

E

D

ET

AI

L

1/

TD

A. THE EXISTING CONDITIONS, DEVICES,

EQUIPMENT, CABLING, AND CONDUITS ARE

BASED ON THE BEST AVAILABLE INFORMATION

AT THE TIME OF SURVEY AND VISUAL

INSPECTION. VERIFY EXISTING CONDITIONS.

B. DEMOLISH ALL NURSE CALL DEVICES SHOWN.

ALL EXISTING NURSE CALL DEVICES TO BE

REPLACED WITH NEW NURSE CALL DEVICES UNO.

C. PROVIDE STAINLESS STEEL COVER PLATE FOR

ALL UNUSED NURSE CALL DEVICE LOCATIONS.

D. DEMOLISH ALL EXISTING NURSE CALL CABLING

BACK TO THE NURSE CALL EQUIPMENT CABINET.

E. FOLLOW ICRA REQUIREMENTS.

F. REMOVE ALL TRASH DAILY FROM THE WORK

AREA.

G. REUSE THE EXISTING NURSE CALL RACEWAY

SYSTEM FOR NEW NURSE CALL CABLING.

H. THE REMOVAL OF ANY EXISTING NURSE CALL

DEVICES SHALL NOT INTERRUPT THE NURSE

CALL DEVICES IN OTHER ROOMS. BOTH EXISTING

NURSE CALL SYSTEM AND NEW NURSE CALL

SYSTEMS SHALL BE IN OPERATION UNTIL NEW

NURSE CALL SYSTEM IS COMPLETELY

OPERATIONAL ON EACH FLOOR.

I. PATCH EXISTING WALL OR CEILING NURSE CALL

OPENINGS IF NOT USED AND PAINT TO MATCH.

J. PATCH AND PAINT AT THE LOCATION OF THE

EXISTING NURSE CALL EQUIPMENT CABINET.

K. ALL NURSE CALL WORK SHALL BE COORDINATED

WITH THE COR AND NURSE MANAGER.

L. PATCH ALL PENETRATIONS AND OPENINGS IN

SMOKE AND FIRE WALLS WITH APPROVED UL

LISTED MATERIALS. SUBMIT APPLICATION PER

VA. SEE SPECIFICATIONS FOR FORM.

M. THE NURSE CALL SYSTEM IS A ONE FOR ONE

REPLACEMENT WITH NEW DEVICES AND/OR AS

SHOWN ON DRAWINGS.

N. COORDINATE ALL NURSE CALL SYSTEM WITH

COR.

O. PATCH ALL NURSE CALL RACEWAY

PENETRATIONS OR OPENINGS IN SMOKE OR FIRE

WALLS WITH AN APPROVED UL LISTED MATERIAL.

SHEET NOTES:

G31

G48

CORRIDOR

G45

EQUIPMENT

G36B

CAMERA

EXAM

G37B

CONTROL/EXAM

RM

G37C

G42

NUCLEAR

MED

G37A

CORRIDOR

G49

STAIR

G38

FAN

RM 6

G22

CORRIDOR

G39J

NUCLEAR

MED/RAD

G39

ELEVATOR-2

ELEVATOR-1

ELEC

EQUIP

G29

ELEC

G28

MALE

LOCKERS

G01A

SPD

OFFICE

G01B

MECH

G41CLEAN

STORAGE

G01

STAIR

G27

TLT

G35

ELEC

SWITCHGEAR

G30 TLT

G32

STOR

G33

WAITING

TLT

G37B

VEST

G44B

CORRIDOR

G01C

MECH

SPACE

G44A

LOCKERS

G36

STATIONARY

IMAGING

G37E MECH

G37L

NUCLEAR

MED

G37

ULTRASOUND

G34

RECEIVING

G42

HAC

G40A

MECH

G40

ELEC

G39L

STRESS

LAB

G39K

BONE

DENSITY

EXAM

G39i

STOR

G39H

MULTI

PURP

G39A

LOGISTICS

G39B

OFFICE

G39C

HOT LAB

INJECTION ROOM

G39D

OFFICE

G39E

OFFICE

G39F

OFFICE

G39G

EXAM

G36A

TOILET

G36C

CONTROL

G36D

RECEPTION

G36E

G39J

E

B B

B

B

N

EXISTING PANEL -

PANEL '2GE'

S S

S S

S S

S S

S

SSS

S S

S

S S

S

S

EXISTING PANEL -

PANEL 'CEG'

AREA OF WORK

KEY PLAN

A B C

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

JULY 19, 2021 ADRJVE

626A4-20-10420-171

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.

NURSE CALL PATIENT BED INTERFACE RECEPTACLE (37 PIN)

WALL RATINGS

1 HR FIRE WALL

1 HR FIRE SMOKE WALL

2 HOUR FIRE WALL

2 HOUR FIRE SMOKE WALL

NON-RATED SMOKE PARTITION

SMOKE RESISTIVE HAZARDOUS

ROOM ENCLOSURE

107Engineers Architects U.S. Department of Veterans Affairs

TVHS- NASHVILLE CAMPUS

1310 24TH AVE S,NASHVILLE, TENNESSEE 37212

TVHS- ALVIN C. YORK CAMPUS

3400 LEBANON PIKE, MURFREESBORO, TENNESSEE 37129

UPGRADE NURSE CALL SYSTEM

NASHVILLE/MURFREESBORO

CAMPUS

NURSE CALL EQUIPMENT CABINETNCE

NURSE CALL SYMBOL LEGEND

SYMBOL DESCRIPTION

A NURSE CALL AUXILIARIES

B ENHANCED NURSE CALL, STAND ALONE, CODE

BLUE STATION WITH CLEAR BUTTON COVER

D NURSE CALL DUTY STATION

NURSE CALL EMERGENCY STATION

(SEE T-001 FOR MORE SPECIFICS, PB - PUSH BUTTON NO

PULL CORD, HS - HIGH SECURITY STEEL COVER PLATE)

M NURSE CALL MASTER STATION/CONSOLE

NURSE CALL PATIENT STATION

(PB - PUSH BUTTON, M - MICROPHONE, K -KEYED, HS - HIGH

SECURITY STEEL COVER PLATE)

N NURSE CALL DOME LIGHT

(Z - ZONE LIGHT, V - VANDAL RESISTANT)

N NURSE CALL DOME LIGHT - WALL MOUNTED

BUTTON STATION WITH CLEAR BUTTON COVER

NUMBER OF BUTTONS (1 - SINGLE BUTTON, 2 - DOUBLE

BUTTON)

BUTTON PROGRAMING (B- CODE BLUE, P - PUSH FOR HELP,

S - STAFF ASSIST)

C

NURSE CALL PATIENT STATION WITH CALL CORD INCLUDES:

- CODE BLUE

- STAFF ASSIST

- AUDIO

- CLEAR BUTTON COVER

(2 - DUAL PATIENT STATION, HS - VANDAL RESISTANT HIGH

SECURITY STEEL COVER PLATE)

E

N

S S S S S S

P

Z

M

PB

S

T NURSE CALL STAFF TERMINAL

MATV OR CATV WALL MOUNTED

MATV OR CATV CEILING MOUNTED

NURSE CALL PATIENT STATION WITH PILLOW SPEAKER (GET

WELL) INCLUDES:

- CODE BLUE

- STAFF ASSIST

- AUDIO

- CLEAR BUTTON COVER

(2 - DUAL PATIENT STATION, HS - VANDAL RESISTANT HIGH

SECURITY STEEL COVER PLATE)

HS

R

BS

P

01TD112

MURFREESBORO BUILDING 1 - "G"

FLOOR NURSE CALL PARTIAL

DEMOLITION PLAN AREA B

1 MURFREESBORO BUILDING 1 - "G" FLOOR NURSE CALL PARTIAL DEMOLITION PLAN AREA B

SCALE: 1/8" = 1' 0"

N O

R

TH

TRUE

4 8 160

SE

E

D

ET

AI

L

1/

TD

SE

E

D

ET

AI

L

1/

TD

A. THE EXISTING CONDITIONS, DEVICES,

EQUIPMENT, CABLING, AND CONDUITS ARE

BASED ON THE BEST AVAILABLE INFORMATION

AT THE TIME OF SURVEY AND VISUAL

INSPECTION. VERIFY EXISTING CONDITIONS.

B. DEMOLISH ALL NURSE CALL DEVICES SHOWN.

ALL EXISTING NURSE CALL DEVICES TO BE

REPLACED WITH NEW NURSE CALL DEVICES UNO.

C. PROVIDE STAINLESS STEEL COVER PLATE FOR

ALL UNUSED NURSE CALL DEVICE LOCATIONS.

D. DEMOLISH ALL EXISTING NURSE CALL CABLING

BACK TO THE NURSE CALL EQUIPMENT CABINET.

E. FOLLOW ICRA REQUIREMENTS.

F. REMOVE ALL TRASH DAILY FROM THE WORK

AREA.

G. REUSE THE EXISTING NURSE CALL RACEWAY

SYSTEM FOR NEW NURSE CALL CABLING.

H. THE REMOVAL OF ANY EXISTING NURSE CALL

DEVICES SHALL NOT INTERRUPT THE NURSE

CALL DEVICES IN OTHER ROOMS. BOTH EXISTING

NURSE CALL SYSTEM AND NEW NURSE CALL

SYSTEMS SHALL BE IN OPERATION UNTIL NEW

NURSE CALL SYSTEM IS COMPLETELY

OPERATIONAL ON EACH FLOOR.

I. PATCH EXISTING WALL OR CEILING NURSE CALL

OPENINGS IF NOT USED AND PAINT TO MATCH.

J. PATCH AND PAINT AT THE LOCATION OF THE

EXISTING NURSE CALL EQUIPMENT CABINET.

K. ALL NURSE CALL WORK SHALL BE COORDINATED

WITH THE COR AND NURSE MANAGER.

L. PATCH ALL PENETRATIONS AND OPENINGS IN

SMOKE AND FIRE WALLS WITH APPROVED UL

LISTED MATERIALS. SUBMIT APPLICATION PER

VA. SEE SPECIFICATIONS FOR FORM.

M. THE NURSE CALL SYSTEM IS A ONE FOR ONE

REPLACEMENT WITH NEW DEVICES AND/OR AS

SHOWN ON DRAWINGS.

N. COORDINATE ALL NURSE CALL SYSTEM WITH

COR.

O. PATCH ALL NURSE CALL RACEWAY

PENETRATIONS OR OPENINGS IN SMOKE OR FIRE

WALLS WITH AN APPROVED UL LISTED MATERIAL.

SHEET NOTES:

AREA OF WORK

KEY PLAN

A B C167

163A

129C

CORRIDOR

CORRIDOR

CORR

TELEPHONE

TOILET

STAIR

-2

MECH

SPACE

TOILET

TELEPHONE

OPERATORS

NURSING

NURSING

TO BUILDING 2

161A

160A

142126

107A

106A

146A

144143

108A

114A

105 104

102 101

125A

116117118

119B 123 122121120119

119A

111A

111C

111B

CORRIDOR

CORRIDOR

CORRIDOR

STORAGE

LABORATORY

CHIEFPATHOLOGY

RESPITORY

SUPV

TOILET

HAC

TELE

STAFF

LOUNGE

LOCKERS

PATH

LAB

OFFICESECY

CHUTE

TOILET

MULTI

PURP

CORRIDOR

WAITING

STAIR

-1

ECHO

LAB

HOME

OXYGEN

WAITING

ECHO

LAB

PULM

LAB

ARTERIAL

BLOOD

GAS

LAB

CHIEF OF

STAFF

OFFICE

ELEC

EEG

LABPHYS

CHIEF

PULM

DISEASE

READING

THERAPY SPD

EQUIP

DECON

VENTILATOR

STORAGE

RESP

THERAPYIRM

MED

RM

CORR

PHYSICIANS

PHYSICIANS

PHYSICIANS

MED

SVC-AO

MED SVC

CLERKS

PHYSICIAN

PHYSICIAN

MED

SVC

MED

SVC

CHIEF

TO BUILDING 117

TO BUILDING 120

N C

E 1

S S

S S

S S

S S

S S

S S

TO BUILDING 120

TK403

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

JULY 19, 2021 ADRJVE

626A4-20-10420-171

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.

NURSE CALL PATIENT BED INTERFACE RECEPTACLE (37 PIN)

WALL RATINGS

1 HR FIRE WALL

1 HR FIRE SMOKE WALL

2 HOUR FIRE WALL

2 HOUR FIRE SMOKE WALL

NON-RATED SMOKE PARTITION

SMOKE RESISTIVE HAZARDOUS

ROOM ENCLOSURE

107Engineers Architects U.S. Department of Veterans Affairs

TVHS- NASHVILLE CAMPUS

1310 24TH AVE S,NASHVILLE, TENNESSEE 37212

TVHS- ALVIN C. YORK CAMPUS

3400 LEBANON PIKE, MURFREESBORO, TENNESSEE 37129

UPGRADE NURSE CALL SYSTEM

NASHVILLE/MURFREESBORO

CAMPUS

NURSE CALL EQUIPMENT CABINETNCE

NURSE CALL SYMBOL LEGEND

SYMBOL DESCRIPTION

A NURSE CALL AUXILIARIES

B ENHANCED NURSE CALL, STAND ALONE, CODE

BLUE STATION WITH CLEAR BUTTON COVER

D NURSE CALL DUTY STATION

NURSE CALL EMERGENCY STATION

(SEE T-001 FOR MORE SPECIFICS, PB - PUSH BUTTON NO

PULL CORD, HS - HIGH SECURITY STEEL COVER PLATE)

M NURSE CALL MASTER STATION/CONSOLE

NURSE CALL PATIENT STATION

(PB - PUSH BUTTON, M - MICROPHONE, K -KEYED, HS - HIGH

SECURITY STEEL COVER PLATE)

N NURSE CALL DOME LIGHT

(Z - ZONE LIGHT, V - VANDAL RESISTANT)

N NURSE CALL DOME LIGHT - WALL MOUNTED

BUTTON STATION WITH CLEAR BUTTON COVER

NUMBER OF BUTTONS (1 - SINGLE BUTTON, 2 - DOUBLE

BUTTON)

BUTTON PROGRAMING (B- CODE BLUE, P - PUSH FOR HELP,

S - STAFF ASSIST)

C

NURSE CALL PATIENT STATION WITH CALL CORD INCLUDES:

- CODE BLUE

- STAFF ASSIST

- AUDIO

- CLEAR BUTTON COVER

(2 - DUAL PATIENT STATION, HS - VANDAL RESISTANT HIGH

SECURITY STEEL COVER PLATE)

E

N

S S S S S S

P

Z

M

PB

S

T NURSE CALL STAFF TERMINAL

MATV OR CATV WALL MOUNTED

MATV OR CATV CEILING MOUNTED

NURSE CALL PATIENT STATION WITH PILLOW SPEAKER (GET

WELL) INCLUDES:

- CODE BLUE

- STAFF ASSIST

- AUDIO

- CLEAR BUTTON COVER

(2 - DUAL PATIENT STATION, HS - VANDAL RESISTANT HIGH

SECURITY STEEL COVER PLATE)

HS

R

BS

P

01TD121

MURFREESBORO BUILDING 1-

"1" FLOOR NURSE CALL PARTIAL

DEMOLITION PLAN AREAS A AND C

2 MURFREESBORO BUILDING 1 - "1" FLOOR NURSE CALL PARTIAL DEMOLITION PLAN AREA A

SCALE: 1/8" = 1' 0"

N O

R

TH

TRUE

4 8 160

1. DEMOLISH EXISTING NURSE CALL EQUIPMENT IN

EXISTING DATA RACK.

2. EXISTING CODE BLUE CONSOLES TO BE REMOVED.

A. THE EXISTING CONDITIONS, DEVICES,

EQUIPMENT, CABLING, AND CONDUITS ARE

BASED ON THE BEST AVAILABLE INFORMATION

AT THE TIME OF SURVEY AND VISUAL

INSPECTION. VERIFY EXISTING CONDITIONS.

B. DEMOLISH ALL NURSE CALL DEVICES SHOWN.

ALL EXISTING NURSE CALL DEVICES TO BE

REPLACED WITH NEW NURSE CALL DEVICES UNO.

C. PROVIDE STAINLESS STEEL COVER PLATE FOR

ALL UNUSED NURSE CALL DEVICE LOCATIONS.

D. DEMOLISH ALL EXISTING NURSE CALL CABLING

BACK TO THE NURSE CALL EQUIPMENT CABINET.

E. FOLLOW ICRA REQUIREMENTS.

F. REMOVE ALL TRASH DAILY FROM THE WORK

AREA.

G. REUSE THE EXISTING NURSE CALL RACEWAY

SYSTEM FOR NEW NURSE CALL CABLING.

H. THE REMOVAL OF ANY EXISTING NURSE CALL

DEVICES SHALL NOT INTERRUPT THE NURSE

CALL DEVICES IN OTHER ROOMS. BOTH EXISTING

NURSE CALL SYSTEM AND NEW NURSE CALL

SYSTEMS SHALL BE IN OPERATION UNTIL NEW

NURSE CALL SYSTEM IS COMPLETELY

OPERATIONAL ON EACH FLOOR.

I. PATCH EXISTING WALL OR CEILING NURSE CALL

OPENINGS IF NOT USED AND PAINT TO MATCH.

J. PATCH AND PAINT AT THE LOCATION OF THE

EXISTING NURSE CALL EQUIPMENT CABINET.

K. ALL NURSE CALL WORK SHALL BE COORDINATED

WITH THE COR AND NURSE MANAGER.

L. PATCH ALL PENETRATIONS AND OPENINGS IN

SMOKE AND FIRE WALLS WITH APPROVED UL

LISTED MATERIALS. SUBMIT APPLICATION PER

VA. SEE SPECIFICATIONS FOR FORM.

M. THE NURSE CALL SYSTEM IS A ONE FOR ONE

REPLACEMENT WITH NEW DEVICES AND/OR AS

SHOWN ON DRAWINGS.

N. COORDINATE ALL NURSE CALL SYSTEM WITH

COR.

O. PATCH ALL NURSE CALL RACEWAY

PENETRATIONS OR OPENINGS IN SMOKE OR FIRE

WALLS WITH AN APPROVED UL LISTED MATERIAL.

N O

R

TH

TRUE

4 8 1601

MURFREESBORO BUILDING 1- "1" FLOOR NURSE

CALL PARTIAL DEMOLITION PLAN AREA C

SCALE: 1/8" = 1' 0"

SHEET NOTES:

DEMOLITION KEY NOTES:

RESTROOM WITH

SHOWER

356A

CORRIDOR

RESTROOM

WITH

SHOWER

373A

TWO BED ROOM

CORRIDOR

NURSES

STATION

MECH

CONGRE BATH

ELEC.

STOR

TELE

351A

TELE

HAC

TLT

359A

ONE BED ROOM

STAIR-1

ONE BED ROOM

RESTROOM

WITH SHOWER

358A

TWO BED ROOM

TWO BED ROOM

RESTROOM

WITH

SHOWER

345A

TWO BED ROOM

LIVING

CENTER

RESIDENT

NOUR.

PALLIATIVE

NURSE

COORDINATOR

352A

CHAPEL

INTERDISCIPLINE

TREATMENT

ROOM

SOCIAL

WORKER

BREAK RM

STAFF

TLT

LINEN

SOILED

UTILITY

ELEC

CHUTE

ONE BED ROOM

ISOLATION

ANTE

372B

REST RM WITH

SHOWER

372A

MDS NURSE

ASSISTANT

NURSE

MANAGER

PHYS ASST

RESTROOM

WITH SHOWER

362A

ONE BED ROOM

ONE BED ROOM

REST RM

WITH

SHOWER

368A

ONE BED ROOM

ONE BED ROOM

RESTROOM

WITH

SHOWER

366A

ONE BED ROOM

ONE BED ROOM

RESTROOM

WITH

SHOWER

364A

E

E

PS

P S

PS

EE

E

E

D

P S

E

E

P

N

N N

N

N N N N

N N

P S

E

N N

E

P S

E

E

P S

M

P S P

S

E

E E

E

E E

EXISTING PANEL -

PANEL '2LC1W-A'

TK403

P S

P S

P

SP

S P S

P S 2

J J

N

N

1 1 1

1 1

1 1

AREA OF WORK

KEY PLAN

A B C

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

JULY 19, 2021 ADRJVE

626A4-20-10420-171

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.

NURSE CALL PATIENT BED INTERFACE RECEPTACLE (37 PIN)

WALL RATINGS

1 HR FIRE WALL

1 HR FIRE SMOKE WALL

2 HOUR FIRE WALL

2 HOUR FIRE SMOKE WALL

NON-RATED SMOKE PARTITION

SMOKE RESISTIVE HAZARDOUS

ROOM ENCLOSURE

107Engineers Architects U.S. Department of Veterans Affairs

TVHS- NASHVILLE CAMPUS

1310 24TH AVE S,NASHVILLE, TENNESSEE 37212

TVHS- ALVIN C. YORK CAMPUS

3400 LEBANON PIKE, MURFREESBORO, TENNESSEE 37129

UPGRADE NURSE CALL SYSTEM

NASHVILLE/MURFREESBORO

CAMPUS

NURSE CALL EQUIPMENT CABINETNCE

NURSE CALL SYMBOL LEGEND

SYMBOL DESCRIPTION

A NURSE CALL AUXILIARIES

B ENHANCED NURSE CALL, STAND ALONE, CODE

BLUE STATION WITH CLEAR BUTTON COVER

D NURSE CALL DUTY STATION

NURSE CALL EMERGENCY STATION

(SEE T-001 FOR MORE SPECIFICS, PB - PUSH BUTTON NO

PULL CORD, HS - HIGH SECURITY STEEL COVER PLATE)

M NURSE CALL MASTER STATION/CONSOLE

NURSE CALL PATIENT STATION

(PB - PUSH BUTTON, M - MICROPHONE, K -KEYED, HS - HIGH

SECURITY STEEL COVER PLATE)

N NURSE CALL DOME LIGHT

(Z - ZONE LIGHT, V - VANDAL RESISTANT)

N NURSE CALL DOME LIGHT - WALL MOUNTED

BUTTON STATION WITH CLEAR BUTTON COVER

NUMBER OF BUTTONS (1 - SINGLE BUTTON, 2 - DOUBLE

BUTTON)

BUTTON PROGRAMING (B- CODE BLUE, P - PUSH FOR HELP,

S - STAFF ASSIST)

C

NURSE CALL PATIENT STATION WITH CALL CORD INCLUDES:

- CODE BLUE

- STAFF ASSIST

- AUDIO

- CLEAR BUTTON COVER

(2 - DUAL PATIENT STATION, HS - VANDAL RESISTANT HIGH

SECURITY STEEL COVER PLATE)

E

N

S S S S S S

P

Z

M

PB

S

T NURSE CALL STAFF TERMINAL

MATV OR CATV WALL MOUNTED

MATV OR CATV CEILING MOUNTED

NURSE CALL PATIENT STATION WITH PILLOW SPEAKER (GET

WELL) INCLUDES:

- CODE BLUE

- STAFF ASSIST

- AUDIO

- CLEAR BUTTON COVER

(2 - DUAL PATIENT STATION, HS - VANDAL RESISTANT HIGH

SECURITY STEEL COVER PLATE)

HS

R

BS

P

01TD141

MURFREESBORO BUILDING 1 -

"1B" FLOOR NURSE CALL PARTIAL

DEMOLITION PLAN AREA A

1 MURFREESBORO BUILDING 1 - "1B" FLOOR NURSE CALL PARTIAL DEMOLITION PLAN AREA A

SCALE: 3/32" = 1' 0"

N O

R

TH

TRUE

4 8 160

SE

E

D

ET

AI

L

1/

TD

SE

E

D

ET

AI

L

1/

TD

A. THE EXISTING CONDITIONS, DEVICES,

EQUIPMENT, CABLING, AND CONDUITS ARE

BASED ON THE BEST AVAILABLE INFORMATION

AT THE TIME OF SURVEY AND VISUAL

INSPECTION. VERIFY EXISTING CONDITIONS.

B. DEMOLISH ALL NURSE CALL DEVICES SHOWN.

ALL EXISTING NURSE CALL DEVICES TO BE

REPLACED WITH NEW NURSE CALL DEVICES UNO.

C. PROVIDE STAINLESS STEEL COVER PLATE FOR

ALL UNUSED NURSE CALL DEVICE LOCATIONS.

D. DEMOLISH ALL EXISTING NURSE CALL CABLING

BACK TO THE NURSE CALL EQUIPMENT CABINET.

E. FOLLOW ICRA REQUIREMENTS.

F. REMOVE ALL TRASH DAILY FROM THE WORK

AREA.

G. REUSE THE EXISTING NURSE CALL RACEWAY

SYSTEM FOR NEW NURSE CALL CABLING.

H. THE REMOVAL OF ANY EXISTING NURSE CALL

DEVICES SHALL NOT INTERRUPT THE NURSE

CALL DEVICES IN OTHER ROOMS. BOTH EXISTING

NURSE CALL SYSTEM AND NEW NURSE CALL

SYSTEMS SHALL BE IN OPERATION UNTIL NEW

NURSE CALL SYSTEM IS COMPLETELY

OPERATIONAL ON EACH FLOOR.

I. PATCH EXISTING WALL OR CEILING NURSE CALL

OPENINGS IF NOT USED AND PAINT TO MATCH.

J. PATCH AND PAINT AT THE LOCATION OF THE

EXISTING NURSE CALL EQUIPMENT CABINET.

K. ALL NURSE CALL WORK SHALL BE COORDINATED

WITH THE COR AND NURSE MANAGER.

L. PATCH ALL PENETRATIONS AND OPENINGS IN

SMOKE AND FIRE WALLS WITH APPROVED UL

LISTED MATERIALS. SUBMIT APPLICATION PER

VA. SEE SPECIFICATIONS FOR FORM.

M. THE NURSE CALL SYSTEM IS A ONE FOR ONE

REPLACEMENT WITH NEW DEVICES AND/OR AS

SHOWN ON DRAWINGS.

N. COORDINATE ALL NURSE CALL SYSTEM WITH

COR.

O. PATCH ALL NURSE CALL RACEWAY

PENETRATIONS OR OPENINGS IN SMOKE OR FIRE

WALLS WITH AN APPROVED UL LISTED MATERIAL.

1. EXISTING TELEVISION CONNECTION TO BE

REPLACED WITH NEW. EXISTING TELEVISION TO

REMAIN.

SHEET NOTES:

DEMOLITION KEY NOTES:

CORR

CORRIDOR

CORRIDOR

CORRIDOR

300 RESTROOM

WITH

SHOWER

309A

RESTROOM

WITH SHOWER

327A

CLINICAL

PHARMACY

NURSE

STATION

ONE BED ROOM

RESTROOM

WITH

SHOWER

325A

TWO BED ROOM

TWO BED ROOM

TWO BED ROOM

RESTROOM

WITH

SHOWER

320A

TWO BED ROOM

TELE

STOR

ELEC

RESTROOM

WITH

SHOWER

341A

ONE BED ROOM

RESTROOM

WITH

SHOWER

338A

TWO BED ROOM

PHYS

HAC

STAIR-3

STAIR-2

MECH

ONE BED ROOM

NURSE MGR

TELE

LOCKER

NOUR KITCH

PHYSICIAN

STOR

RESTROOM

WITH

SHOWER

329A

ONE BED ROOM

ONE BED ROOM

TWO BED ROOM

TWO BED ROOM

CLEAN

EQUIPMENT

ELEC

ISOLATION

ANTE

313B

RESTROOM

WITH

SHOWER

313A

CHARTING

314A

MED

314B

DAY RM

CLEAN

LINEN

ONE BED ROOM

TWO BED ROOM

RESTROOM

WITH

SHOWER

317A

STOR

SLEEP LAB

MECH

SPACE

301A

SLEEP LAB

RESTROOM

WITH

SHOWER

RESTROOM

WITH

SHOWER

304A

CONTROL

RETHERM

STAFF

RESTROOM

WITH

SHOWER

344A

TELE

DINING

PHYSICIAN

SLEEP LAB

BREAK RM

ELEVATOR - 2

ELEVATOR - 1

STAFF

TLT

STOR

P

N N N N N

N N N N ND

E

E

PS

N

N

P S

P S

S P

P S

E E

EE

P S

P S

P S

E

E

E P S

E

E

PSP S

EE

M

E E

EE

P

P

P

EXISTING PANEL -

PANEL '2LC1Y'

TK403

P S 2

P

P S 2

S P

N

N N

E

P S

S PS P

PS

S P

1 1

1 1

1 1

1 1

AREA OF WORK

KEY PLAN

A B C

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

JULY 19, 2021 ADRJVE

626A4-20-10420-171

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.

NURSE CALL PATIENT BED INTERFACE RECEPTACLE (37 PIN)

WALL RATINGS

1 HR FIRE WALL

1 HR FIRE SMOKE WALL

2 HOUR FIRE WALL

2 HOUR FIRE SMOKE WALL

NON-RATED SMOKE PARTITION

SMOKE RESISTIVE HAZARDOUS

ROOM ENCLOSURE

107Engineers Architects U.S. Department of Veterans Affairs

TVHS- NASHVILLE CAMPUS

1310 24TH AVE S,NASHVILLE, TENNESSEE 37212

TVHS- ALVIN C. YORK CAMPUS

3400 LEBANON PIKE, MURFREESBORO, TENNESSEE 37129

UPGRADE NURSE CALL SYSTEM

NASHVILLE/MURFREESBORO

CAMPUS

NURSE CALL EQUIPMENT CABINETNCE

NURSE CALL SYMBOL LEGEND

SYMBOL DESCRIPTION

A NURSE CALL AUXILIARIES

B ENHANCED NURSE CALL, STAND ALONE, CODE

BLUE STATION WITH CLEAR BUTTON COVER

D NURSE CALL DUTY STATION

NURSE CALL EMERGENCY STATION

(SEE T-001 FOR MORE SPECIFICS, PB - PUSH BUTTON NO

PULL CORD, HS - HIGH SECURITY STEEL COVER PLATE)

M NURSE CALL MASTER STATION/CONSOLE

NURSE CALL PATIENT STATION

(PB - PUSH BUTTON, M - MICROPHONE, K -KEYED, HS - HIGH

SECURITY STEEL COVER PLATE)

N NURSE CALL DOME LIGHT

(Z - ZONE LIGHT, V - VANDAL RESISTANT)

N NURSE CALL DOME LIGHT - WALL MOUNTED

BUTTON STATION WITH CLEAR BUTTON COVER

NUMBER OF BUTTONS (1 - SINGLE BUTTON, 2 - DOUBLE

BUTTON)

BUTTON PROGRAMING (B- CODE BLUE, P - PUSH FOR HELP,

S - STAFF ASSIST)

C

NURSE CALL PATIENT STATION WITH CALL CORD INCLUDES:

- CODE BLUE

- STAFF ASSIST

- AUDIO

- CLEAR BUTTON COVER

(2 - DUAL PATIENT STATION, HS - VANDAL RESISTANT HIGH

SECURITY STEEL COVER PLATE)

E

N

S S S S S S

P

Z

M

PB

S

T NURSE CALL STAFF TERMINAL

MATV OR CATV WALL MOUNTED

MATV OR CATV CEILING MOUNTED

NURSE CALL PATIENT STATION WITH PILLOW SPEAKER (GET

WELL) INCLUDES:

- CODE BLUE

- STAFF ASSIST

- AUDIO

- CLEAR BUTTON COVER

(2 - DUAL PATIENT STATION, HS - VANDAL RESISTANT HIGH

SECURITY STEEL COVER PLATE)

HS

R

BS

P

01TD142

MURFREESBORO BUILDING 1 -

"1B" FLOOR NURSE CALL PARTIAL

DEMOLITION PLAN AREAS B AND C

1 MURFREESBORO BUILDING 1 - "1B" FLOOR NURSE CALL PARTIAL DEMOLITION PLAN AREAS B AND C

SCALE: 1/8" = 1' 0"

N O

R

TH

TRUE

4 8 160

SE

E

D

ET

AI

L

1/

TD

SE

E

D

ET

AI

L

1/

TD

A. THE EXISTING CONDITIONS, DEVICES,

EQUIPMENT, CABLING, AND CONDUITS ARE

BASED ON THE BEST AVAILABLE INFORMATION

AT THE TIME OF SURVEY AND VISUAL

INSPECTION. VERIFY EXISTING CONDITIONS.

B. DEMOLISH ALL NURSE CALL DEVICES SHOWN.

ALL EXISTING NURSE CALL DEVICES TO BE

REPLACED WITH NEW NURSE CALL DEVICES UNO.

C. PROVIDE STAINLESS STEEL COVER PLATE FOR

ALL UNUSED NURSE CALL DEVICE LOCATIONS.

D. DEMOLISH ALL EXISTING NURSE CALL CABLING

BACK TO THE NURSE CALL EQUIPMENT CABINET.

E. FOLLOW ICRA REQUIREMENTS.

F. REMOVE ALL TRASH DAILY FROM THE WORK

AREA.

G. REUSE THE EXISTING NURSE CALL RACEWAY

SYSTEM FOR NEW NURSE CALL CABLING.

H. THE REMOVAL OF ANY EXISTING NURSE CALL

DEVICES SHALL NOT INTERRUPT THE NURSE

CALL DEVICES IN OTHER ROOMS. BOTH EXISTING

NURSE CALL SYSTEM AND NEW NURSE CALL

SYSTEMS SHALL BE IN OPERATION UNTIL NEW

NURSE CALL SYSTEM IS COMPLETELY

OPERATIONAL ON EACH FLOOR.

I. PATCH EXISTING WALL OR CEILING NURSE CALL

OPENINGS IF NOT USED AND PAINT TO MATCH.

J. PATCH AND PAINT AT THE LOCATION OF THE

EXISTING NURSE CALL EQUIPMENT CABINET.

K. ALL NURSE CALL WORK SHALL BE COORDINATED

WITH THE COR AND NURSE MANAGER.

L. PATCH ALL PENETRATIONS AND OPENINGS IN

SMOKE AND FIRE WALLS WITH APPROVED UL

LISTED MATERIALS. SUBMIT APPLICATION PER

VA. SEE SPECIFICATIONS FOR FORM.

M. THE NURSE CALL SYSTEM IS A ONE FOR ONE

REPLACEMENT WITH NEW DEVICES AND/OR AS

SHOWN ON DRAWINGS.

N. COORDINATE ALL NURSE CALL SYSTEM WITH

COR.

O. PATCH ALL NURSE CALL RACEWAY

PENETRATIONS OR OPENINGS IN SMOKE OR FIRE

WALLS WITH AN APPROVED UL LISTED MATERIAL.

1. EXISTING TELEVISION CONNECTION TO BE

REPLACED WITH NEW. EXISTING TELEVISION TO

REMAIN.

SHEET NOTES:

DEMOLITION KEY NOTES:

TELE

G28

LOBBY

ELEV #1

STAIR

ELEC SUPERVISOR

CORR

G06

G10G07

G03A

G12M

G24

G23 G22 G21

G18J

G18H

G18G

EXAM

G18I

G18F G18K

G18E

G18N

G18Q

G18D

G17 G16

G14

G15

CHECK-IN

VITAL

CORRIDOR

TELE

STAIRS

TLT

SOILED

EXAM

EXAM

EXAM

EXAMEXAM

EXAM

WAITING

NURSE

PHYSICIAN

TLT

TLT

G18C

G18B

G18A

G18M

G18O

G18P

G18

G12K

G12N

G08C

G08

G08B

STOR

MULTI-PURPOSE

EXIT CORRIDOR

ADMIN

G09

G10A

G09B

G12A

G12

G12D G12E G12F G12G

G12B

G12Q

G12P

GO1

G02

CLEAN

SOILED

G15A

CORR

G21P

CORRIDOR G27

G25

TLT

DN

STAIR

UP

ELEV #2 MECH

PHARMACY GENERAL AREA

WAITING

NURSE WORKROOM

G21A

RECP

G21B

MED

G21C

G21D

G21E

G21F

G21J

G21H

G21K

G21N G21M EXAM

EXAM

EXAM

G21G

DOC

WKRM

EXAM

EXAM

EXAM

CLEAN

LINEN

SPDTLT

MED SPECIALTY

OFFICE

ELEV LOBBY

OFFICE

OFFICE

G29

ELEC

CORRIDOR

MECH

HAC

TLT

G05 G04P

TLT G04R

RECEPTION

G04Q

TLT

FIRM D

G04

G04N

SOILED

HOLDING

G04A

MECH

CORRIDOR

G04B

G04C

MED

G04E

STOR

CORR

G04I

G04M

EXAM

EXAM

G04F

G04G

EXAM

G04L

EXAM

G04K

EXAM

EXAM

G04J

EXAM

G04H

ALCOVE

G04D

OFFICE OFFICE OFFICE

VAULT

DISPENSING

LINEN

STOR

G15B

G15C

UTY

UTY

G20

TELE

G03

HAC

3G

CLINIC

G15D

PIPE C

H

ASE

G30

NURSEWAITING

PHARM

G08D

OFFICE

G12C

TECH

G08A

OFFICE

CHASE

CHEMO

G12J

ANTE

G12H

IV PREP

VEST

DF

N

E

N

E

M

FIRM "D"

PRIMARY

CARE

EXISTING PANEL -

PANEL '2L3A'

TO

BUILDING

CORRIDOR

TO

BUILDING

CORRIDOR

TO

BUILDING

TK403

S S

S S

S S

AREA OF WORK

KEY PLAN

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

JULY 19, 2021 ADRJVE

626A4-20-10420-171

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.

NURSE CALL PATIENT BED INTERFACE RECEPTACLE (37 PIN)

WALL RATINGS

1 HR FIRE WALL

1 HR FIRE SMOKE WALL

2 HOUR FIRE WALL

2 HOUR FIRE SMOKE WALL

NON-RATED SMOKE PARTITION

SMOKE RESISTIVE HAZARDOUS

ROOM ENCLOSURE

107Engineers Architects U.S. Department of Veterans Affairs

TVHS- NASHVILLE CAMPUS

1310 24TH AVE S,NASHVILLE, TENNESSEE 37212

TVHS- ALVIN C. YORK CAMPUS

3400 LEBANON PIKE, MURFREESBORO, TENNESSEE 37129

UPGRADE NURSE CALL SYSTEM

NASHVILLE/MURFREESBORO

CAMPUS

NURSE CALL EQUIPMENT CABINETNCE

NURSE CALL SYMBOL LEGEND

SYMBOL DESCRIPTION

A NURSE CALL AUXILIARIES

B ENHANCED NURSE CALL, STAND ALONE, CODE

BLUE STATION WITH CLEAR BUTTON COVER

D NURSE CALL DUTY STATION

NURSE CALL EMERGENCY STATION

(SEE T-001 FOR MORE SPECIFICS, PB - PUSH BUTTON NO

PULL CORD, HS - HIGH SECURITY STEEL COVER PLATE)

M NURSE CALL MASTER STATION/CONSOLE

NURSE CALL PATIENT STATION

(PB - PUSH BUTTON, M - MICROPHONE, K -KEYED, HS - HIGH

SECURITY STEEL COVER PLATE)

N NURSE CALL DOME LIGHT

(Z - ZONE LIGHT, V - VANDAL RESISTANT)

N NURSE CALL DOME LIGHT - WALL MOUNTED

BUTTON STATION WITH CLEAR BUTTON COVER

NUMBER OF BUTTONS (1 - SINGLE BUTTON, 2 - DOUBLE

BUTTON)

BUTTON PROGRAMING (B- CODE BLUE, P - PUSH FOR HELP,

S - STAFF ASSIST)

C

NURSE CALL PATIENT STATION WITH CALL CORD INCLUDES:

- CODE BLUE

- STAFF ASSIST

- AUDIO

- CLEAR BUTTON COVER

(2 - DUAL PATIENT STATION, HS - VANDAL RESISTANT HIGH

SECURITY STEEL COVER PLATE)

E

N

S S S S S S

P

Z

M

PB

S

T NURSE CALL STAFF TERMINAL

MATV OR CATV WALL MOUNTED

MATV OR CATV CEILING MOUNTED

NURSE CALL PATIENT STATION WITH PILLOW SPEAKER (GET

WELL) INCLUDES:

- CODE BLUE

- STAFF ASSIST

- AUDIO

- CLEAR BUTTON COVER

(2 - DUAL PATIENT STATION, HS - VANDAL RESISTANT HIGH

SECURITY STEEL COVER PLATE)

HS

R

BS

P

03TD111

MURFREESBORO BUILDING 3 -

"G" FLOOR NURSE CALL DEMOLITION

PLAN

1 MURFREESBORO BUILDING 3 - "G" FLOOR NURSE CALL DEMOLITION PLAN

SCALE: 1/8" = 1' 0"

N O

R

TH

TRUE

0 4 8 16

A. THE EXISTING CONDITIONS, DEVICES,

EQUIPMENT, CABLING, AND CONDUITS ARE

BASED ON THE BEST AVAILABLE INFORMATION

AT THE TIME OF SURVEY AND VISUAL

INSPECTION. VERIFY EXISTING CONDITIONS.

B. DEMOLISH ALL NURSE CALL DEVICES SHOWN.

ALL EXISTING NURSE CALL DEVICES TO BE

REPLACED WITH NEW NURSE CALL DEVICES UNO.

C. PROVIDE STAINLESS STEEL COVER PLATE FOR

ALL UNUSED NURSE CALL DEVICE LOCATIONS.

D. DEMOLISH ALL EXISTING NURSE CALL CABLING

BACK TO THE NURSE CALL EQUIPMENT CABINET.

E. FOLLOW ICRA REQUIREMENTS.

F. REMOVE ALL TRASH DAILY FROM THE WORK

AREA.

G. REUSE THE EXISTING NURSE CALL RACEWAY

SYSTEM FOR NEW NURSE CALL CABLING.

H. THE REMOVAL OF ANY EXISTING NURSE CALL

DEVICES SHALL NOT INTERRUPT THE NURSE

CALL DEVICES IN OTHER ROOMS. BOTH EXISTING

NURSE CALL SYSTEM AND NEW NURSE CALL

SYSTEMS SHALL BE IN OPERATION UNTIL NEW

NURSE CALL SYSTEM IS COMPLETELY

OPERATIONAL ON EACH FLOOR.

I. PATCH EXISTING WALL OR CEILING NURSE CALL

OPENINGS IF NOT USED AND PAINT TO MATCH.

J. PATCH AND PAINT AT THE LOCATION OF THE

EXISTING NURSE CALL EQUIPMENT CABINET.

K. ALL NURSE CALL WORK SHALL BE COORDINATED

WITH THE COR AND NURSE MANAGER.

L. PATCH ALL PENETRATIONS AND OPENINGS IN

SMOKE AND FIRE WALLS WITH APPROVED UL

LISTED MATERIALS. SUBMIT APPLICATION PER

VA. SEE SPECIFICATIONS FOR FORM.

M. THE NURSE CALL SYSTEM IS A ONE FOR ONE

REPLACEMENT WITH NEW DEVICES AND/OR AS

SHOWN ON DRAWINGS.

N. COORDINATE ALL NURSE CALL SYSTEM WITH

COR.

O. PATCH ALL NURSE CALL RACEWAY

PENETRATIONS OR OPENINGS IN SMOKE OR FIRE

WALLS WITH AN APPROVED UL LISTED MATERIAL.

WOMEN'S

CLINIC

CORRIDOR

STAIR-1

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

LOUNGE

CORRIDOR

CORRIDOR

OFFICE,

WAITING, OR

STORAGE

120A

EXAM RM

120B

W/C TOILET

120C

EXAM

120D

EXAM

120E

OFFICE

12OF

EXAM

120G

W/C TOILET

120H

EXAM

120I

OFFICE

120J

EXAM

120K

TOILET

120L

WAITING

120M

RECEPTION

120N

STAIR-2

STORAGE

EYE EXAM

125B

RECEPTION

125C

128A

LOBBY

ELEV

-2

MINOR SURGY

TELE

HAC

STAIR-3

TOILET

135A

EXAM

135B

EXAM

135C

135D

EXAM

135E

135F

CLEAN

STORAGE

135F1

TOILET

135G

STORAGE

135H

OFFICE

CHECK-IN WAITING RM

ELEC

CONSULT/EXAM

WAITING

141A

EXAM

STORAGE

BREAKROOM

OFFICE

CHECK-IN

OFFICE

MECH

SURGY EXAM

SURGY EXAM

ELEV

-1

TOILET

TOILET

EYE EXAM

EYE EXAM

STORAGE

EYE EXAM

ELEC

PODIATRY EXAM

PODIATRY EXAM

MECH

PODIATRY EXAM

PODIATRY

PODIATRY EXAM

PHARMACY ROOF

EYE

EXAM

CLINIC

156B

127C

126A

127C

127D

126D

127A

127B

PROTOCOL

PHOTO

PRE-OP

CLEAN

EYE

EXAM

126B

EYE

EXAM

FIELDS

VISUAL

EYE

EXAM

MANAGER

WORKROOM

NURSE

151B

151A

EYE

FITTER

SURGERY

128C

WORKUP

ROOM

STOR

128B

EYE

EXAM EYE

EXAM

EYE EXAM/

PROCEDURE

TLT

TLT

LASER

116A

DILATION

ROOM

ROOM

116A

PODIATRY

WAITING

113A

STOR

PODIATRY EXAM

N

N

N

N

N

N N

E

E

E

E

E

N

E E

N

E

M

PODIATRY

ORTHO WHOLE

HEALTH

OPTO

NEUROLOGY

EXISTING

PANEL -

PANEL '2C3B'

EXISTING

PANEL -

PANEL '2C3B'

TO

BUILDING

TK403

S S

S S

S

S S

S

S S

S

S S

S S

S S

TK403

AREA OF WORK

KEY PLAN

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

JULY 19, 2021 ADRJVE

626A4-20-10420-171

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.

NURSE CALL PATIENT BED INTERFACE RECEPTACLE (37 PIN)

WALL RATINGS

1 HR FIRE WALL

1 HR FIRE SMOKE WALL

2 HOUR FIRE WALL

2 HOUR FIRE SMOKE WALL

NON-RATED SMOKE PARTITION

SMOKE RESISTIVE HAZARDOUS

ROOM ENCLOSURE

107Engineers Architects U.S. Department of Veterans Affairs

TVHS- NASHVILLE CAMPUS

1310 24TH AVE S,NASHVILLE, TENNESSEE 37212

TVHS- ALVIN C. YORK CAMPUS

3400 LEBANON PIKE, MURFREESBORO, TENNESSEE 37129

UPGRADE NURSE CALL SYSTEM

NASHVILLE/MURFREESBORO

CAMPUS

NURSE CALL EQUIPMENT CABINETNCE

NURSE CALL SYMBOL LEGEND

SYMBOL DESCRIPTION

A NURSE CALL AUXILIARIES

B ENHANCED NURSE CALL, STAND ALONE, CODE

BLUE STATION WITH CLEAR BUTTON COVER

D NURSE CALL DUTY STATION

NURSE CALL EMERGENCY STATION

(SEE T-001 FOR MORE SPECIFICS, PB - PUSH BUTTON NO

PULL CORD, HS - HIGH SECURITY STEEL COVER PLATE)

M NURSE CALL MASTER STATION/CONSOLE

NURSE CALL PATIENT STATION

(PB - PUSH BUTTON, M - MICROPHONE, K -KEYED, HS - HIGH

SECURITY STEEL COVER PLATE)

N NURSE CALL DOME LIGHT

(Z - ZONE LIGHT, V - VANDAL RESISTANT)

N NURSE CALL DOME LIGHT - WALL MOUNTED

BUTTON STATION WITH CLEAR BUTTON COVER

NUMBER OF BUTTONS (1 - SINGLE BUTTON, 2 - DOUBLE

BUTTON)

BUTTON PROGRAMING (B- CODE BLUE, P - PUSH FOR HELP,

S - STAFF ASSIST)

C

NURSE CALL PATIENT STATION WITH CALL CORD INCLUDES:

- CODE BLUE

- STAFF ASSIST

- AUDIO

- CLEAR BUTTON COVER

(2 - DUAL PATIENT STATION, HS - VANDAL RESISTANT HIGH

SECURITY STEEL COVER PLATE)

E

N

S S S S S S

P

Z

M

PB

S

T NURSE CALL STAFF TERMINAL

MATV OR CATV WALL MOUNTED

MATV OR CATV CEILING MOUNTED

NURSE CALL PATIENT STATION WITH PILLOW SPEAKER (GET

WELL) INCLUDES:

- CODE BLUE

- STAFF ASSIST

- AUDIO

- CLEAR BUTTON COVER

(2 - DUAL PATIENT STATION, HS - VANDAL RESISTANT HIGH

SECURITY STEEL COVER PLATE)

HS

R

BS

P

03TD121

MURFREESBORO BUILDING 3 -

"A" FLOOR NURSE CALL DEMOLITION

PLAN

1 MURFREESBORO BUILDING 3 - "A" FLOOR NURSE CALL DEMOLITION PLAN

SCALE: 1/8" = 1' 0"

N O

R

TH

TRUE

0 4 8 16

A. THE EXISTING CONDITIONS, DEVICES,

EQUIPMENT, CABLING, AND CONDUITS ARE

BASED ON THE BEST AVAILABLE INFORMATION

AT THE TIME OF SURVEY AND VISUAL

INSPECTION. VERIFY EXISTING CONDITIONS.

B. DEMOLISH ALL NURSE CALL DEVICES SHOWN.

ALL EXISTING NURSE CALL DEVICES TO BE

REPLACED WITH NEW NURSE CALL DEVICES UNO.

C. PROVIDE STAINLESS STEEL COVER PLATE FOR

ALL UNUSED NURSE CALL DEVICE LOCATIONS.

D. DEMOLISH ALL EXISTING NURSE CALL CABLING

BACK TO THE NURSE CALL EQUIPMENT CABINET.

E. FOLLOW ICRA REQUIREMENTS.

F. REMOVE ALL TRASH DAILY FROM THE WORK

AREA.

G. REUSE THE EXISTING NURSE CALL RACEWAY

SYSTEM FOR NEW NURSE CALL CABLING.

H. THE REMOVAL OF ANY EXISTING NURSE CALL

DEVICES SHALL NOT INTERRUPT THE NURSE

CALL DEVICES IN OTHER ROOMS. BOTH EXISTING

NURSE CALL SYSTEM AND NEW NURSE CALL

SYSTEMS SHALL BE IN OPERATION UNTIL NEW

NURSE CALL SYSTEM IS COMPLETELY

OPERATIONAL ON EACH FLOOR.

I. PATCH EXISTING WALL OR CEILING NURSE CALL

OPENINGS IF NOT USED AND PAINT TO MATCH.

J. PATCH AND PAINT AT THE LOCATION OF THE

EXISTING NURSE CALL EQUIPMENT CABINET.

K. ALL NURSE CALL WORK SHALL BE COORDINATED

WITH THE COR AND NURSE MANAGER.

L. PATCH ALL PENETRATIONS AND OPENINGS IN

SMOKE AND FIRE WALLS WITH APPROVED UL

LISTED MATERIALS. SUBMIT APPLICATION PER

VA. SEE SPECIFICATIONS FOR FORM.

M. THE NURSE CALL SYSTEM IS A ONE FOR ONE

REPLACEMENT WITH NEW DEVICES AND/OR AS

SHOWN ON DRAWINGS.

N. COORDINATE ALL NURSE CALL SYSTEM WITH

COR.

O. PATCH ALL NURSE CALL RACEWAY

PENETRATIONS OR OPENINGS IN SMOKE OR FIRE

WALLS WITH AN APPROVED UL LISTED MATERIAL.

ARCHWAYCC- 5/7

CC-5/6

PROSTHETICS

G14

PROSTHETICS

OFFICE

G11E

BIO-MED

STORAGE

BIO-MED

REPAIR

G27

STORAGE

G15C

OFFICE

G15B

PROSTHETICS

G11H

CORRIDOR

G34

CORRIDOR

G33

CORRIDOR

G32

CORRIDOR

G11

CORRIDOR

G31

CORRIDOR

G30

OCCUPATIONAL

THERAPY CLINIC

G15

STAIR

G12

PROSTHETICS

G11G

PROSTHETICS

G11F

WAITING

G11D

TELE

G11C

TOILET

G11B

TOILET

G11A

CHILD

CARE

STORE

G10

STORE

G10A

EMS EQUIP

STORE

G09

ELECTRICAL/

SWITCHBOARD

G08

SECURITY

MONITORING

G07

SECURITY

MONITORING

G06

STORE

PHAR

G05A

PHARMACY

OFFICES

G05

TELE

G04

TOILET

G03B

PMRS

G03A

PMRS

G03 PMRS

G02

TOILET

G01B

KT

CLINIC

G01

ELEVATOR

KT

COORD

G01A

TOILET

G29D

MALE

LOCKER

G29C

EMPLOYEE

LOUNGE

G29

FEMALE

LOCKER

G29A

TOILET

G29B

TELE

G28

BIO-MED

SUPV

G27C

BIO-MED

CHIEF

G27B

BIO-MED

RECEIVING

G27A

VACANT

G26

VENDING

G25

TOILET

G25A

STAIR

G19HAC

G18

MECH

PROSTHETICS

OFFICE

G17

TOILET

G15D

LINEN

CHUTE

G16

TOILET

G15AMECH

G13

RECEPTION

G11P

PROSTHETICS

G11N

PROSTHETICS

G11M

ASSIST

CHIEF

PROSTHETICS

G11L

STORE

CHIEF

PROSTHETICS

G11K

PROSTHETICS

OFFICE

G11J

PRINTER

G21A

WAITING

G20

KIOSK

G35A

RECEPTION

G21

TEAM

G23

TREATMENT

G22

CORR

G35

N

NE

E E

EXISTING

PANEL -

PANEL

'2N5G1(2)'

TK404

S S

S S

S S

S S

S S

S S S

S S

S S

S S

S

AREA OF WORK

KEY PLAN

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

JULY 19, 2021 ADRJVE

626A4-20-10420-171

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.

NURSE CALL PATIENT BED INTERFACE RECEPTACLE (37 PIN)

WALL RATINGS

1 HR FIRE WALL

1 HR FIRE SMOKE WALL

2 HOUR FIRE WALL

2 HOUR FIRE SMOKE WALL

NON-RATED SMOKE PARTITION

SMOKE RESISTIVE HAZARDOUS

ROOM ENCLOSURE

107Engineers Architects U.S. Department of Veterans Affairs

TVHS- NASHVILLE CAMPUS

1310 24TH AVE S,NASHVILLE, TENNESSEE 37212

TVHS- ALVIN C. YORK CAMPUS

3400 LEBANON PIKE, MURFREESBORO, TENNESSEE 37129

UPGRADE NURSE CALL SYSTEM

NASHVILLE/MURFREESBORO

CAMPUS

NURSE CALL EQUIPMENT CABINETNCE

NURSE CALL SYMBOL LEGEND

SYMBOL DESCRIPTION

A NURSE CALL AUXILIARIES

B ENHANCED NURSE CALL, STAND ALONE, CODE

BLUE STATION WITH CLEAR BUTTON COVER

D NURSE CALL DUTY STATION

NURSE CALL EMERGENCY STATION

(SEE T-001 FOR MORE SPECIFICS, PB - PUSH BUTTON NO

PULL CORD, HS - HIGH SECURITY STEEL COVER PLATE)

M NURSE CALL MASTER STATION/CONSOLE

NURSE CALL PATIENT STATION

(PB - PUSH BUTTON, M - MICROPHONE, K -KEYED, HS - HIGH

SECURITY STEEL COVER PLATE)

N NURSE CALL DOME LIGHT

(Z - ZONE LIGHT, V - VANDAL RESISTANT)

N NURSE CALL DOME LIGHT - WALL MOUNTED

BUTTON STATION WITH CLEAR BUTTON COVER

NUMBER OF BUTTONS (1 - SINGLE BUTTON, 2 - DOUBLE

BUTTON)

BUTTON PROGRAMING (B- CODE BLUE, P - PUSH FOR HELP,

S - STAFF ASSIST)

C

NURSE CALL PATIENT STATION WITH CALL CORD INCLUDES:

- CODE BLUE

- STAFF ASSIST

- AUDIO

- CLEAR BUTTON COVER

(2 - DUAL PATIENT STATION, HS - VANDAL RESISTANT HIGH

SECURITY STEEL COVER PLATE)

E

N

S S S S S S

P

Z

M

PB

S

T NURSE CALL STAFF TERMINAL

MATV OR CATV WALL MOUNTED

MATV OR CATV CEILING MOUNTED

NURSE CALL PATIENT STATION WITH PILLOW SPEAKER (GET

WELL) INCLUDES:

- CODE BLUE

- STAFF ASSIST

- AUDIO

- CLEAR BUTTON COVER

(2 - DUAL PATIENT STATION, HS - VANDAL RESISTANT HIGH

SECURITY STEEL COVER PLATE)

HS

R

BS

P

05TD111

MURFREESBORO BUILDING 5 -

"G" FLOOR NURSE CALL DEMOLITION

PLAN

1 MURFREESBORO BUILDING 5 - "G" FLOOR NURSE CALL DEMOLITION PLAN

SCALE: 1/8" = 1' 0"

N O

R

TH

TRUE

0 4 8 16

PROSTHETICS

PHYSICAL

THERAPY

A. THE EXISTING CONDITIONS, DEVICES,

EQUIPMENT, CABLING, AND CONDUITS ARE

BASED ON THE BEST AVAILABLE INFORMATION

AT THE TIME OF SURVEY AND VISUAL

INSPECTION. VERIFY EXISTING CONDITIONS.

B. DEMOLISH ALL NURSE CALL DEVICES SHOWN.

ALL EXISTING NURSE CALL DEVICES TO BE

REPLACED WITH NEW NURSE CALL DEVICES UNO.

C. PROVIDE STAINLESS STEEL COVER PLATE FOR

ALL UNUSED NURSE CALL DEVICE LOCATIONS.

D. DEMOLISH ALL EXISTING NURSE CALL CABLING

BACK TO THE NURSE CALL EQUIPMENT CABINET.

E. FOLLOW ICRA REQUIREMENTS.

F. REMOVE ALL TRASH DAILY FROM THE WORK

AREA.

G. REUSE THE EXISTING NURSE CALL RACEWAY

SYSTEM FOR NEW NURSE CALL CABLING.

H. THE REMOVAL OF ANY EXISTING NURSE CALL

DEVICES SHALL NOT INTERRUPT THE NURSE

CALL DEVICES IN OTHER ROOMS. BOTH EXISTING

NURSE CALL SYSTEM AND NEW NURSE CALL

SYSTEMS SHALL BE IN OPERATION UNTIL NEW

NURSE CALL SYSTEM IS COMPLETELY

OPERATIONAL ON EACH FLOOR.

I. PATCH EXISTING WALL OR CEILING NURSE CALL

OPENINGS IF NOT USED AND PAINT TO MATCH.

J. PATCH AND PAINT AT THE LOCATION OF THE

EXISTING NURSE CALL EQUIPMENT CABINET.

K. ALL NURSE CALL WORK SHALL BE COORDINATED

WITH THE COR AND NURSE MANAGER.

L. PATCH ALL…