Technical_Data_of_Proposed_BESS.xlsx
XLSX spreadsheet 65 KB Posted
- Attached to
- Battery Energy Storage System (BESS)
- Solicitation number
- 2023-RFP-030
- Issued by
- Los Angeles County, California
About this file
The document is a comprehensive Technical Data spreadsheet for a Battery Energy Storage System (BESS) prepared for Pasadena Water and Power (PWP), a department of the City of Pasadena, California. The solicitation seeks a private entity to design, engineer, permit, finance, procure, operate, and maintain a 25 MW lithium-ion battery storage system with a minimum 4-hour storage capability at PWP's Glenarm Power Plant. The proposed project involves a minimum 15-year Energy Storage Agreement (ESA) with options for the City to purchase the BESS at the Commercial Operation Date, Year Two, and Year Five after COD. The technical specification covers extensive requirements across eleven sections including mandatory minimum requirements, performance standards, safety protocols, communications and controls, balance of system, installation details, mechanical and environmental specifications, operations and maintenance, and interconnection requirements.
The contract opportunity includes multiple technical and compliance specifications, with key requirements such as UL 9540 and UL 9540A safety certifications, compliance with California Rule 21 and IEEE 1547-2018 standards, and detailed operational parameters including a 100 MWh storage capacity, 60 Hz frequency, and 34.5 kV connection point. The proposal must demonstrate the BESS's ability to meet specific performance metrics like roundtrip efficiency, cycle life, calendar life degradation, and thermal management. Financial considerations include a 15-year warranty period, expected system availability metrics, and provisions for maintenance and potential system upgrades. The technical data spreadsheet serves as a comprehensive evaluation tool for potential bidders to demonstrate their system's capabilities and alignment with PWP's detailed technical and operational requirements.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Instructions Instructions:
| Step 1: | Confirm that the proposed BESS meets the Mandatory Minimum Requirements in Section 1 - "Mandatory Minimum Requirements" |
| Step2: | Complete Sections 2-9. If the requested informatino is not applicable to the proposed BESS, indicate "N/A" |
| Step 3: | Completed document must be included in the Technical Proposal of the RFP response |
List of Standards and Codes
| List of Standards and Codes - Technical Data of Proposed BESS | |
| Below is a subset of select applicable Standards and Codes for the Proposed BESS. This list is not exhaustive and additional standards and codes may apply. It is the responsibility of the Qualified Respondents to verify any proposed design meets all relevant industry codes and standards for Battery Energy Storage Systems. | |
| Electrical - Below are some but not all of the specific codes and standards that apply. | |
| Standard | Description |
| ANSI C50.41 | Polyphase Induction Motors for Power Generating Stations |
| ANSI C80.1& UL6 | Steel conduit for electrical and instrument wiring shall comply with this standard |
| ANSI C80.4 & UL 514 | Metallic conduit fittings shall comply with this standard |
| IEEE C57.13 | Standard Requirements for Instrument Transformers |
| IEEE-112 | IEEE Standard Test Procedure for Polyphase Induction Motors and Generators |
| ANSI/IEEE 141 | Recommended Practice for Electrical Power Distribution for Industrial Plants |
| ANSI/IEEE 142 | Recommended Practice for Protection and Coordination of Industrial Plants. |
| ANSI/IEEE 242 | Recommended Practice for Protection and Coordination of Industrial Plants. |
| IEEE 399 | Recommended Practice for Industrial and Commercial Power System Analysis |
| IEEE 430 | Standard Procedures for the Measurement of Radio Noise from Overhead Power Lines and Substations |
| IEEE 519 | Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems. |
| IEEE 693 | Recommended Practice for Seismic Design of Substations |
| IEEE 1547 | Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces |
| IEEE C2 | National Electrical Safety Code |
| NEC 706 | Energy Storage Systems |
| NEMA MG1 | Motors and Generators |
| UL 1642 | Lithium Batteries |
| UL 1741/1741 SA | Standard for Inverters, Converters, Controllers, and Interconnection System Equipment for Use with Distributed Energy Resources |
| UL 1973 | Standard for Batteries for Use in Stationary, Vehicle Auxiliary Power and Light Electric Rail (LER) Applications |
| UL 9540 | Safety of Energy Storage Systems and Equipment |
| UL 9540A | Standard for Test Method for Evaluating Thermal Runaway Fire Propagation in Battery Energy Storage Systems |
| Fire Detection and Protection - Below are some but not all of the specific codes and standards that apply. Standard Description | |
| Standard | Description |
| CFC | Chapter 12, Energy Systems Supplement Effective July 1, 2021 |
| NFPA 10 | Standard for Portable Fire Extinguishers |
| NFPA 12 | Standard on Carbon Dioxide Extinguishing Systems |
| NFPA 13 | Standard for the Installation of Sprinkler Systems |
| NFPA 15 | Water Spray Fixed Systems |
| NFPA 24 | Standard for the Installation of Private Fire Service Mains and Their Appurtenances. |
| NFPA 25 | Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems |
| NFPA 30 | Flammable and Combustible Liquids Code |
| NFPA 70 | National Electrical Code |
| NFPA 70B | Recommended Practice for Electrical Equipment Maintenance |
| NFPA 72 | National Fire Alarm Code |
| NFPA 90A | Standard for the Installation of Air-Conditioning and Ventilating Systems |
| NFPA 101 | Life Safety Code |
| NFPA 550 | Guide to Fire Safety Concepts Tree |
| NFPA 750 | Standard on Water Mist Fire Protection Systems |
| NFPA 850 | Recommended Practices for Fire Protection for Electric Generating Plants and High Voltage Direct Current Converter Stations. |
| NFPA 855 | Standard for the Installation of Stationary Energy Storage Systems |
| Infrastructure Protection - Below are some but not all of the specific codes and standards that apply. Standard Description | |
| Standard | Description |
| NERC CIP | Cyber Security Requirements |
| Instrumentation & Controls - Below are some but not all of the specific codes and standards that apply. Standard Description | |
| Standard | Description |
| ASTM A123 type 316 | Control tubing instrument air shall be fabricated of stainless steel 316. |
| ANSI/EIA RS-310-D | Rack-mounting standards |
| IEEE C37.1 | Standard for SCADA and Automation Systems |
| ISA | Instrument Loop Diagrams |
| IEEE C 37 | Optical Interface and Generator Relay Protection |
| IEEE 802 | Networks |
| IEEE 519 | Harmonic Control for VFD |
| ISA 5.1 | Instrumentation Symbols and Identification |
| ISA 5.4 | Instrument Loop Diagrams |
| UL 508A | Industrial Control Panel |
| Mechanical - Below are some but not all of the specific codes and standards that apply. Standard Description | |
| Standard | Description |
| 40CFR60 | Standards of Performance for New Stationary Sources |
| API 521 | Pressure Relieving and De-Pressuring Systems |
| ANSI B73.1 | Centrifugal Pumps |
| ANSI S 1.4 | Specification for Sound Level Meters |
| AMCA | Fans |
| ASHRAE 15 | Safety Standard for Refrigeration Systems and Designation and Classification of Refrigerants |
| ASHRAE 147 | Reducing the Release of Halogenated Refrigerants from Refrigerating and Air - Conditioning Equipment and Systems |
| ASME B16 Series | Pipe Fittings |
| ASME A13.1 | Scheme for the Identification of Piping Systems |
| ASME B&PV Code Section V | Non-Destructive Examination |
| ASME B&PV Code Section VIII | Rules for Construction of Pressure Vessels |
| SCAQMD 1415.1 | Reduction of Refrigerant Emissions from Stationary Refrigeration Systems |
| Structural - Below are some but not all of the specific codes and standards that apply. Standard Description | |
| Standard | Description |
| CBC | California Building Code (CBC), latest edition, at time of submittal to City Building Department for approval. |
| ASTM A36 | Structural Steel |
| ASTM A572, GR 50 | High Strength Steel |
| ASTM A500 GRB: ASTM A501 | Structural Tubing |
| ASTM A1011 | Steel Floor Grating |
| ASTM A786, Pattern No.4 | Checkered Floor Plate |
| ASTM A53 GR B | Pipe Grade |
| ASTM A500 GR B or ASTM A501 | Pipe Handrail: 1 ½ in. Schedule 40 |
| AISC 360 | Specification for Structural Steel Buildings |
| Additional Standards and Code that apply | |
| Standard | Description |
| IEC 62619 | |
| IEEE 1679.1 | Recommended practices for Lithium-Based Batteries in stationary applications |
| IEEE 1375 | Guidance in the protection of Stationary Battery Systems |
| IEEE 946 | Recommended practices for the Design of DC Power Systems for Stationary Applications |
| IEEE 1491 | Guide for Selection and use of Battery Monitoring Equipment in Stationary Applications |
| IEEE 2030 | Guide for Smart Grid Interoperability of Energy Technology and Information Technology Operation with the Electric Power System (EPS), End-use Applications, and Loads |
| IEEE 2030.5 | Standard for Smart Energy Profile Application Protocol |
| IEEE 2030.2.1 | Guide for Design, Operation, and maintenance of Battery Energy Storage Systems, both Stationary and Mobile, and Applications Integrated with Electric Power Systems |
| IEEE 1453 | Standard for Measurement and Limits of Voltage Fluctuations and Associated Light Flicker on AC Power Systems |
1-Mandatory Minimum Requirement
| Mandatory Minimum Requirements -- Technical Data of Proposed BESS | ||||||
| Items | Parameters | Definitions | Units | Buyer Requirement | Buyer Designation | Supplier Provided Values |
| MMR1 | Size of BESS | How many Megawatts(MW) of power can it deliver as nameplate capacity | MW | 25 | Contract Requirement | |
| MMR2 | Amount Storage of BESS | How many Megawatt-hours (MWh) can this BESS store as maximum capacity | MWh | 100 | Contract Requirement | |
| MMR3 | Length of Storage Duration | How many Hours can the BESS store energy for? | Hours | 4 | Contract Requirement | |
| MMR4 | AC Frequency | What frequency is energy released at once connected to the distribution system | Hz | 60 | Contract Requirement | |
| MMR5 | Output Frequency Range | What range of frequency is expected from the BESS | Hz | 59.0 Hz- 60.0 Hz | Contract Requirement | |
| MMR6 | Point of Connection Voltage | What voltage will the BESS operate at the Point of Connection | kV | 34.5 kv | Contract Requirement |
2-Performance
| BESS Performance - STANDARD -- Technical Data of Proposed BESS | |||||||
| Items | Parameters | Definitions | Units | Buyer Requirement | Buyer Designation | Supplier Provided Values | |
| P1 | Rated Discharge Power - Facility | The maximum steady state active power at which the Facility can continuously deliver at the point of common coupling (PCC). | kW AC | per proposer supply option | Contract Requirement | ||
| P2 | Rated Discharge Power - BESS | The maximum steady state active power at which the BESS can continuously deliver at the AC terminals of the Power Conversion System (PCS). | kW AC | per proposer supply option | Contract Requirement | ||
| P3 | Rated Charge Power - BESS | The maximum steady state active power at which the BESS can continuously absorb at the AC terminals of the PCS. | kW AC | per proposer supply option | Contract Requirement | ||
| P4 | Rated Reactive Power - BESS | The maximum steady state reactive power (active power = 0, lagging or leading) at which the BESS can continuously deliver/absorb at the AC terminals of the PCS. | kVAR | ||||
| P5 | Rated Apparent Power - BESS | The maximum steady state apparent power that the BESS can continuously deliver/absorb. | kVA | ||||
| P6 | Capability Curve | Provide a capability curve that shows active and reactive power limits across all four quadrants. | Provide Curve | ||||
| P7 | Available Discharge Energy - Facility | The accessible energy that can be provided by the Facility when discharging at rated power at Beginning of Life (BOL). | kWh AC | per proposer supply option | Contract Requirement | ||
| P8 | Available Discharge Energy - BESS | The accessible energy that can be provided by the BESS when discharging at rated power at BOL. | kWh AC | per proposer supply option | Response Required | ||
| P9 | Recommended Discharge Energy - BOL | The quantity of manufacturer-defined usable energy at BOL to maximize life of the asset when subjected to daily or more frequent cycling. | kWh AC | Response Required | |||
| P10 | Recommended Maximum State of Charge | The maximum percentage state of charge the manufacturers recommend to maximize life of the asset when subjected to daily or more frequent cycling. This value references the SOC reported to the BESS site controller. | % | Response Required | |||
| P11 | Recommended Minimum State of Charge | The minimum percentage state of charge the manufacturers recommend to maximize life of the asset when subjected to daily or more frequent cycling. This value references the SOC reported to the BESS site controller. | % | Response Required | |||
| P12 | Average State of Charge | The average percentage state of charge of the system over its operational life the manufacturers recommend to maximize life of the asset | % | Response Required | |||
| P13 | Charge Duration | The minimum amount of time required for the BESS to be charged at rated charge power over entire SOC range. | Hours | 4 | Response Required | ||
| P14 | Recommended Charge Power | Recommended charge power while staying within the manufacturer's rated guidelines on SOC and internal temperatures. | kW | per proposer supply option | Response Required | ||
| P15 | Roundtrip Efficiency - Facility | ||||||
| AC to AC (RTEAC) | Total AC roundtrip efficiency of the Facility defined as the ratio of the delivered discharge energy to the delivered charge energy in a Full Duty Cycle of the Facility at the PCC, including facility parasitic loads. Specify EOL and BOL values. | - | - | Response Required | |||
| 100% DoD Cycles, Full rated power. | % | Response Required | |||||
| Efficiency over specified duty cycle. | % | Response Required | |||||
| P16 | Roundtrip Efficiency - BESS | ||||||
| AC to AC (RTEAC) | Total roundtrip efficiency of the BESS defined as the ratio of the delivered discharge energy to the delivered charge energy in a Full Duty Cycle at the PCS output terminals, including BESS parasitic loads. Specify EOL and BOL values. | - | - | Response Required | |||
| 100% DoD Cycles, Full rated power. | % | Response Required | |||||
| Efficiency over specified duty cycle. | % | Response Required | |||||
| P17 | Charge Ramp Rate | The maximum rate that the BESS can change its input power. This may vary in multiple dimensions such as SOC and/or other parameters of the system. Break out into multiple line item values, as applicable. | kW/Min | Response Required | |||
| P18 | Discharge Ramp Rate | The maximum rate that the BESS can change its output power. This may vary in multiple dimensions such as SOC and/or other parameters of the system. Break out into multiple line item values, as applicable. | kW/Min | Response Required | |||
| P19 | System Latency | Time measured between when the control signal is sent and the BESS responds to the signal by changing the discharge or charge power value by more than 1% of the control setpoint. | Seconds | Response Required | |||
| P20 | Self-Discharge Rate | Rate at which the BESS will lose SOC while being held at __% SOC, not including auxiliary load energy. | %/hr | Response Required | |||
| P21 | Cycle Life Ratings | The number of cycles that the energy storage system can perform until EOL, independent of calendar life degradation, at specified depth of discharge after which electricity storage becomes inoperable or unusable for a given application. The values should represent response of the system across the rated temperature range. Supplier to designate the assumed average resting SOC and active SOC for each. Supplier to provide cycle life at various increments of DoD power, i.e. 100%, 75%, 50%, 25%, etc. | Provide Cycle Life Graph | Response Required | |||
| P22 | Calendar Life Degradation | Annual degradation of rated discharge energy, independent of cycle life degradation. | %/year | Response Required | |||
| P23 | Specified Duty Cycle | Site specific cycling requirement (e.g. 1 full discharge per day or kwh throughput per day). Buyer to specify requirement, which may include charge/discharge rate, DoD, and EOL conditions. Supplier to confirm this requirement can be met. | Y/N | Y | Response Required | ||
| P24 | Annual Degradation for Specified Duty Cycle | Degradation rate of rated discharge energy and impedance (if applicable) with buyer-specified duty cycle. This includes both calendar and cycle life degradation. | Chart or %/year | Response Required | |||
| P25 | End of Life (EOL) Criteria | The condition of the BESS at the end of life in terms of remaining capacity, impedance, efficiency, and other pertinent parameters. | Chart | Response Required | |||
| P26 | Minimum Charge Time | The minimum amount of time required for the BESS to be charged from minimum SOC to its rated maximum SOC | Hours | Response Required | |||
| P27 | Typical Recharge Time | This should include any time for a rest period needed between a full or partial charge or discharge cycle | Hours | Response Required | |||
| P28 | Minimum Discharge Time | The minimum amount of time required for the BESS to be discharged from maximum SOC to its rated minimum SOC | Hours | Response Required |
3-Safety
| SAFETY REQUIREMENTS - Technical Data of Proposed BESS | ||||||
| Items | Parameters | Definitions | Units | Buyer Requirement | Buyer Designation | Supplier Provided Values |
| S1 | UL9540 Listing | BESS has been tested and certified compliant to UL9540 Standard for Energy Storage Systems and Equipment | Y/N | Y | Contract Requirement | |
| S2 | UL 9540A Testing | BESS has conducted large scale fire testing per UL 9540A Test Method for Evaluating Thermal Runaway Fire Propagation in Battery Energy Storage Systems | Y/N | Y | Contract Requirement | |
| S3 | NESC/NEC/NFPA Compliant Service Access | Service areas in which a human needs to work compliant to the applicable electric safety standard. | Y/N | Y | Contract Requirement | |
| S4 | Active Hardware Safety Features | Features in place to mitigate or reduce impact of a cell failure or fire. Examples: active cell protections, adequate sensing and control, exhaust ventilation, fire suppression, gas phase suppression, temperature monitoring and alarms, water based suppression. See below for additional definitions. | Describe | Response Required | ||
| S5 | Passive Hardware Safety Features | Features in place to mitigate or reduce impact of a cell failure or fire. Examples: passive arc flash protection. See below for additional definitions. | Describe | Response Required | ||
| S6 | Continuous Hardware Safety Features | Features in place to mitigate or reduce impact of a cell failure or fire. Examples: BMS balancing algorithms/circuit sizing, BMS control, container HVAC, container monitoring, insulation monitoring, inverter/PCS controls, redundant HVAC, situational awareness, voltage monitoring and SOC estimation. See below for additional definitions. | Describe | Response Required | ||
| S7 | Safety Design Considerations | Features in place to mitigate or reduce impact of a cell failure or fire. Examples: arc flash design protections, BMS disconnect/shutdown, cell and module thermal management, container/structural resiliency, deflagration protection, design review, facility design and siting, module resiliency, passive cell and circuit protection and design, redundant failure detection, site electrical protections, system certification and standards compliance, system electrical abuse tolerance, System shutdown/disconnect, thermal isolation/cascading protection. See below for additional definitions. | Describe | Response Required | ||
| S8 | System Property Safety Features | Features in place to mitigate or reduce impact of a cell failure or fire. Examples: Cell electrical, physical, and thermal abuse tolerance, cell and system design quality control, maintenance and commissioning, disposal response. See below for additional definitions. | Describe | Response Required | ||
| S9 | Process and Procedures | Features in place to mitigate or reduce impact of a cell failure or fire. Examples: Emergency and first response, process control, training. See below for additional definitions. | Describe | Response Required | ||
| S10 | Lockable Disconnects (LOTO) | Power connections between major system components (such as between the BESS and PCS) are separable by disconnect switch which can be locked in the open position | Y/N | Y | Response Required | |
| S11 | Visible Disconnect | Visible open point between electrical interconnection point and facility. | Y/N | Y | Response Required | |
| S12 | Safety Signage | Safety signs warning of high voltage and/or chemical hazards within the BESS perimeter. | Y/N | Y | Response Required | |
| S13 | Emergency Stop Switches | Prominently positioned, easily accessed switches that can render the system immediately inoperable. | Y/N | Y | Response Required | |
| S14 | Emergency Egress | More than one exit from service areas which contain high voltage and/or significantly flammable materials. | Y/N | Y | Response Required | |
| S15 | External Beacon/Siren for Emergency | Emergency beacons, auditory and/or visual indicators located on exterior of enclosures. | Y/N | Y | Response Required | |
| S16 | Remote Signaling for Emergency Conditions/Alarms | Provisions for remote signaling to remotely positioned terminals or systems of faults. | Y/N | Y | Response Required | |
| S17 | Ground Fault Detection | BESS detects the presence of an un-intended connection to ground of one of its power lines (AC and DC). | Y/N | Y | Response Required | |
| S18 | Ground Fault Response | Response of the system after a ground fault indication. | Describe | Response Required | ||
| S19 | Toxicity of Fire Suppresant | Provide Safety Data Sheet (SDS). | Attach | Response Required | ||
| S20 | Toxicity of Suppresant Runoff | Provide chemical analysis or list of materials present in liquid and solid residual during a fire suppresant event. | Describe | Response Required | ||
| S4.3 | Exhaust Ventilation | Effectiveness of exhaust ventilation to remove battery off-gas, heat, and smoke which may result in adverse atmospheric conditions | Describe | Response Required | ||
| S4.6 | Temperature Monitoring and Alarms | Thermal monitoring within the container including BMS, fire alarm thermal monitoring and any BoS temperature monitoring | Describe | Response Required | ||
| S4.7 | Water Based Suppression System | Water based suppression system including NFPA 13 sprinklers, NFPA 15 sprayers, deluge systems, or NFPA 750 water mist systems designed to suppress fire | Describe | Response Required | ||
| S6.2 | BMS Control | Includes monitoring and shutdown/isolation capabilities of the affected BMS/module or system if necessary. | Describe | Response Required | ||
| S6.3 | Container HVAC | Heating, ventilation and air conditioning for the overall container designed to maintain overall system temperature and humidity levels. | Describe | Response Required | ||
| S6.7 | Redundant HVAC | Design, sizing, and hardware physical redundancy of the HVAC system such that failure of one or multiple units does not result in adverse conditions within the container or system | Describe | Response Required | ||
| S7.5 | Deflagration Protection | NFPA 68, NFPA 69, or other deflagration protection | Describe | Response Required | ||
| S7.6 | Pre-Incident Guide | Pre-Incident Guide to serve as a training platform. | Provide | Y | Contract Requirement | |
| S7.7 | Emergency Response Plan | Emergency Response Plan including, but not limited to an overview of the facility along with an explanation of the equiment contained therein, define hazards and recommended response associated with a battery energy storage system. | Provide | Y | Contract Requirement |
4-Comms and Controls
| COMMUNICATIONS and CONTROLS - Technical Data of Proposed BESS | ||||||
| Items | Parameters | Definitions | Units | Buyer Requirement | Buyer Designation | Supplier Provided Values |
| C1 | CA Rule 21 Phase 2 | Supports California Rule 21 Phase 2 Functions | Y/N | Y | Contract Requirement | |
| C2 | CA Rule 21 Phase 3 | Supports California Rule 21 Phase 3 Functions | Y/N | Y | Response Required | |
| C3 | IEEE 1547-2018 | Supports IEEE 1547-2018 Functions | Y/N | Y | Contract Requirement | |
| C4 | IEEE 1547-2018 / 2030.5 | If supports IEEE 1547-2018, supports IEEE 2030.5 requirements in IEEE 1547-2018 | Y/N | Y | Response Required | |
| C5 | IEEE 1547-2018 / SunSpec Modbus | If supports IEEE 1547-2018, supports SunSpec/MESA Modbus requirements in IEEE 1547-2018 | Y/N | Y | Contract Requirement | |
| C6 | IEEE 1547-2018 / DNP3 | If supports IEEE 1547-2018, supports IEEE 1815/DNP requirements in IEEE 1547-2018 | Y/N | Y | Contract Requirement | |
| C7 | Certified IEEE 1547-2018 | If supports IEEE 1547-2018, certified to IEEE 1547-2018 (IEEE P1547.1) | Y/N | Y | Response Required | |
| C8 | Supports DNP3 | Supports IEEE 1815/DNP3 for grid-facing communications. | Y/N | Y | Response Required | |
| C9 | Supports DNP3, Utility Custom | If supports IEEE 1815/DNP3, vendor will implement utility provided DNP point map and information model | Y/N | Y | Response Required | |
| C10 | Supports DNP3, Vendor Custom | If supports IEEE 1815/DNP3, utility will implement vendor provided DNP point map and information model. | Y/N | Y | Response Required | |
| C11 | Supports DNP3, AN2018-001 | If supports IEEE 1815/DNP3, AN2018-001/MESA will be used as the DNP point map and information model. | Y/N | Y | Optional | |
| C12 | Support 2030.5 | Supports IEEE 2030.5 for grid-facing communications. | Y/N | Y | Response Required | |
| C13 | Support IEC-61850 | Supports IEC-61850 using IEC-61850-7-420. | Y/N | Y | Optional | |
| C14 | Support Modbus within DER, Custom | Supports SunSpec/MESA Modbus for intra-DER communications. | Y/N | Y | Response Required | |
| C15 | Support Modbus within DER, SunSpec/MESA | Supports Modbus for intra-DER communications using SunSpec/MESA Modbus specification. | Y/N | Y | Response Required | |
| C16 | State of Charge (SOC) | The control system can monitor the available energy stored in the aggregate energy storage system. | Y/N | Y | Contract Requirement | |
| C17 | SOC Calculation | Description of how the SOC is calculated and parameters used | Describe | Response Required | ||
| C18 | Energy SOH | The control system can monitor the ability of the energy storage system to store energy relative to its BOL capacity through EOL. | Y/N | Y | Response Required | |
| C19 | Operating Data Collection/Points List | List of data collected by the control system (data elements, refresh rates). | List | Response Required | ||
| C20 | On-Site Control Screen | Describe capabilities to monitor and operate from local control panels. | List | Response Required | ||
| C21 | Remote Monitoring of Status and Faults | Data and conditions alarms that are available to remote monitoring systems (data elements, alarms, refresh rates, event recording for data monitored during events, etc.) | Y/N | Y | Contract Requirement | |
| C22 | SCADA HMI Refresh Rate | The slowest data update rate on the SCADA HMI for any variable. | Hz | Response Required | ||
| C23 | SCADA Response Times | Time between command issued via the on-site HMI and initiation of facility response. | s | Response Required | ||
| C24 | Cyber Security Measures | Specify additional details on physical and cyber security (data transfer, data storage, connectivity, controllability, role-based access, encryption, passwords, VPN, firmware updates, software and hardware patches etc.) | List | Response Required | ||
| C25 | Architecture Diagram | Provide a communication diagram, showing BESS components, communication devices, data connections, interactions with other systems, such as any grid-facing communication, cloud services, etc. | Provide | Contract Requirement | ||
| C26 | Grid Services | List any available pre-programmed grid services available in the site controls (e.g., demand forecasting, load following, market participation schemes, etc.) | Describe | Response Required |
5-BOS
| BALANCE OF SYSTEM REQUIREMENTS - Technical Data of Proposed BESS | ||||||
| Items | Parameters | Definitions | Units | Buyer Requirement | Buyer Designation | Supplier Provided Values |
| B1 | “Ready” State Energy Consumption | Average hourly energy consumption of Facility when BESS is ON, ready to provide power instantaneously (< 1 sec). All subsystems are connected, but no grid power is flowing except that which is required to maintain state of charge if necessary. | kWh AC per hour | Response Required | ||
| B2 | “Standby” State Energy Consumption | Average hourly energy consumption of Facility when BESS is ON, but some subsystems are disconnected or off to save energy. | kWh AC per hour | Response Required | ||
| B3 | Auxiliary Power Provision | Does the auxiliary power need a separate feed from the premises, or does it get supplied from the main grid connection? | Describe | Response Required | ||
| B4 | Thermal Management System Type | Describe thermal management systems that are used to heat or cool the BESS (HVAC, Chiller, Blower, etc.). Provide all assumed conditions and detailed calculations of performance at representative operating points during BOL and EOL. Describe redundancy units (if any). | Type | Response Required | ||
| B5 | Thermal System Capacity | Amount of heat (watts) the thermal system can remove (or add) from (to) the BESS. | Tons/ Watts | Response Required | ||
| B6 | “Sleep” State Energy Consumption | Average hourly energy consumption of Facility when BESS is mostly off, except for communication and safety equipment. | kWh AC per hour | Response Required | ||
| B7 | “OFF” State Energy Consumption | Average hourly energy consumption of Facility when BESS is completely off, except for required safety equipment. | kWh AC per hour | Response Required | ||
| B8 | Auxiliary Power - Peak | Auxiliary peak power (locked rotor, etc.) used to size the ratings of in-line fuses and wiring and other thermally intolerant assets. | kW | Response Required | ||
| B9 | Auxiliary Power - Continuous | Auxiliary continuous power (used to estimate system tare losses and to size the continuous rating of a power transformer or other thermally tolerant devices). | kW | Response Required |
6-Installation
| INSTALLATION - STANDARD- Technical Data of Proposed BESS | ||||||
| Items | Parameters | Definitions | Units | Buyer Requirement | Buyer Designation | Supplier Provided Values |
| I1 | Site Plan | Provide a proposed site plan showing all required BESS equipment. Include all underground work required and perimeter fence line, if applicable. | Drawing | Contract Requirement | ||
| I2 | Total Land Use Requirements | Length x Width (LxW) including all required clearances, keep-away and access areas, including BESS, control room, auxiliary equipment, any special access and space required for construction, service, fire separation, etc. | ft2 | Contract Requirement | ||
| I3 | Enclosure Type | A description of the system enclosure including that supplied with the system, provided as a part of the site installation and/or comprised of building assemblies associated with the installation, including HVAC systems. | Describe | Response Required | ||
| I4 | Equipment Footprint | Length x Width (LxW) of equipment only (Includes BESS modules and all ancillary units as required) in intended layout. | ft x ft | Contract Requirement | ||
| I5 | Height | Equipment height plus safe clearance distances above the equipment. | ft | Contract Requirement | ||
| I6 | Weight | Weight of all individual sub-systems (PCS, Battery module, accessories, etc.) and the maximum shipping weights of all assembled enclosures that will be transported to the project site. | lb | Contract Requirement | ||
| I7 | Maximum Equipment Structural Loading | Maximum weight per loaded area for any one piece of equipment. | lb/ft2 | Response Required | ||
| I8 | Site Exterior Lighting | Buyer to specify requirement; Seller to confirm if included in scope. | Y/N | Response Required | ||
| I9 | Lightning Protection | Buyer to specify requirement; Seller to confirm if included in scope. | Y/N | Response Required | ||
| I10 | Ground Grid | Buyer to specify requirement; Seller to confirm if included in scope. | Y/N | Response Required | ||
| I11 | Grounding Points on Exterior Chassis | Number and positions of grounding points on the exterior chassis. | Qty | Response Required | ||
| I12 | Surveillance Cameras | Describe video/IR cameras included to monitor BESS and service areas? Describe their operation, recording means, transmission, etc. | Describe | Compatible with existing | Response Required | |
| I13 | Entry/Access | Describe entry and access restrictions for the facility and BESS equipment. | Describe | Response Required | ||
| I14 | Cells Per Module | Battery cells per module | Qty | Response Required | ||
| I15 | Cell Type | Battery Cell type/chemistry | Describe | Response Required | ||
| I16 | Module Configuration | Battery module configuration | Describe | Response Required | ||
| I17 | Battery Weight | Individual battery weight | lb | Response Required |
Any required fields not completed above should attach the response below. Please reference the Item Number.
7-Mechanical and Environmental
| MECHANICAL AND ENVIRONMENTAL - STANDARD - Technical Data of Proposed BESS | |||||||
| Items | Parameters | Definitions | Units | Buyer Requirement | Buyer Designation | Supplier Provided Values | |
| M1 | BESS Operational Temperature Range | Temperature range at which the BBESS can operate at its rated capacity. | specify | ||||
| °F or °C | Contract Requirement | ||||||
| M2 | BESS Storage Temperature Range | Temperature range in which BESS can be stored when not energized. | specify | ||||
| °F or °C | Response Required | ||||||
| M3 | BESS Operational Humidity Range | Range of humidity in which the BESS can operate according to its full specifications. | %RH | Response Required | |||
| M4 | BESS Storage Humidity Range | Humidity range in which BESS can be stored when not energized. | %RH | Response Required | |||
| M5 | BESS System Maximum Operational Altitude | Rated maximum altitude at which the BESS can perform according to its full specifications. | ft ASL | Response Required | |||
| M6 | Other Equipment Storage requirements | Environmental requirements to be maintained around spare parts and system components prior to installation and/or during temporary storage. | Describe | Response Required | |||
| M7 | BESS Enclosure Rating | NEMA or IEC - Ingress Protection (IP) rating for the BESS enclosure (e.g. NEMA 3R, NEMA 4X, IP32, IP 66) | Type | NEMA 3R | Response Required | ||
| M8 | BESS Enclosure Coating Rating | Specify, if any, requirements for enclosure coating, including thicknBESS and type of paint, rust and corrosion resistance, thermal conductivity, or other enclosure coverings. | Type | Response Required | |||
| M9 | Hazardous Location Classification | Hazardous location class, division and zone as defined by the National Electric Code. Buyer to specify and Supplier to confirm equipment is properly rated. | Y/N | Y | Response Required | ||
| M10 | Dust, Rodent and Insect Barriers | Specify how BESS is protected from dust, rodent and insects, including sealing cable penetrations. | Describe | Response Required | |||
| M11 | Sound Emissions from Enclosure(s) | Audible Noise dB at 6ft high and 3ft distance from enclosure. | dB | Response Required | |||
| Audible Noise dB at 6ft high at site boundary. | dB | Response Required | |||||
| Audible Noise dB at _ft high and _ft distance from enclosure. | dB | Response Required | |||||
| M12 | Fluid Spill/ Containment Systems (Moat, Tank or Pond) | Type, amount, and under which conditions. | Describe | Response Required | |||
| M13 | US EPA EPCRA compliance | Indicate compliance of on site listed materials and any needed reporting | Y/N | Y | Response Required | ||
| M17 | Wind Speed Limit | Rated wind speed before damage to the BESS occurs. | mph | Response Required | |||
| M18 | Flood Tolerance Height | Rated flood tolerance height. | ft | Response Required | |||
| M19 | Seismic Certification | Equipment is seismic certified per requirements defined by the International Building Code. | Y/N | Y | Contract Requirement | ||
| M20 | Particulate Matter (Airborne) | Type, amount of emitted airborne particulates and under which conditions with respect to the energy through-put | Lb. M Wh | If Applicable | |||
| M21 | Gas Emissions | Provide Type and Amount of gas emitted, under which conditions with respect to the eneryg through-put. Exampls incldue criteria pollutants (NOx, SOx) Green House Gases (CO2, CH4, N2O) and fugitive emissions from cooling equipment and circuit breakers (refrigerants, SF6) | Lb. M Wh | If Applicable |
8-O&M
| OPERATION and MAINTENANCE (O&M) REQUIREMENTS - Technical Data of Proposed BESS | ||||||
| Items | Parameters | Definitions | Units | Buyer Requirement | Buyer Designation | Supplier Provided Values |
| OM1 | Warranty Period | Standard warranty period for BESS and individual sub systems and major components (if different than BESS). | Years | 15 | Response Required | |
| OM2 | Expected System Availability | Percentage of available hours per year that the system is in full operation performing application specific functions taking into account both planned and unplanned down-time. | % | Response Required | ||
| OM3 | Expected battery refresh charge and discharge cycles per year | Intervals of complete cycling needed annually to maintain warranty. Describe the procedure for refresh charge and frequency. | Describe | Response Required | ||
| OM4 | Expected Yearly Planned Down-Time for Maintenance | Expected time required for regular maintenance and types of maintenance. | Hrs/Year | Response Required | ||
| OM5 | Expected Yearly Unplanned Down-Time of System for Repair | Expected down-time due to forced outages. | Hrs/Year | Response Required | ||
| OM6 | Expected Service Life before Major Replacement | Specify all known and required parts or systems replacement schedules. | Part - Year | Response Required | ||
| OM7 | Startup Time | The time that the BESS takes to go from an OFF state to an ON state. Startup Time shall include any manufacturer required warm-up and initialization times. | Seconds | Response Required | ||
| OM8 | Wake Time | The time that the BESS takes to go from a hibernation state to an ON state. | Seconds | Response Required | ||
| OM9 | Shutdown Time | The time that the BESS takes to go from an ON state to an OFF state. | Seconds | Response Required | ||
| OM10 | Control Power UPS Back-Up Time | Expected minimum autonomy time on back-up power (provided by the UPS). | Hours | Response Required | ||
| OM11 | Documentation Provided throughout the Project Life Cycle | Design drawings, calculations and files (original format) | Y/N | Y | Response Required | |
| Site and Facilities requirements and drawings (original format) | Y/N | Y | Response Required | |||
| Software and Firmware Updates - Operation and Controls | Y/N | Y | Optional | |||
| FAT, SAT and other Systems testing files | Y/N | Y | Optional | |||
| Installation Manuals | Y/N | Y | Contract Requirement | |||
| Commissioning Manuals | Y/N | Y | Response Required | |||
| Operation Manuals | Y/N | Y | Contract Requirement | |||
| Maintenance Manuals, Preventative Maintenance Schedule | Y/N | Y | Response Required | |||
| Service Manuals | Y/N | Y | Optional | |||
| Training Manuals and On Site Training for Operation and Service | Y/N | Y | Response Required | |||
| Spare parts listings | Y/N | Y | Response Required | |||
| Safety Datasheets (SDS) | Y/N | Y | Response Required | |||
| Lockout-Tagout Procedures (or MOPs) for all equipment at various disconnect points (e.g., switchgear/substation accBESS, PCS, battery enclosures, battery racks, battery modules, etc.) | Y/N | Y | Response Required | |||
| OM20 | MTBF | Mean Time Between Failures (MTBF) or actual field failure data. | Year | Response Required | ||
| OM21 | Expected Period between major Exterior Refinishing | Exstimated time before exterior refinishing when operated in the intended customer application | Year |
9-Interconnection
| INTERCONNECTION -REQUIREMENTS - Technical Data of Proposed BESS | ||||||
| Items | Parameters | Definitions | Units | Buyer Requirement | Buyer Designation | Supplier Provided Values |
| IN1 | Single Line Diagram | Provide a single line diagram of proposed interconnection at the PCC including any required isolation or step-up transformer, AC protection gear (e.g. motorized breaker, fused links, mechanical disconnects, etc.), PT/CT, metering, auxiliary loads or generators, other interconnection equipment and BESS related equipment. Equipment must comply with any other specifications or standards provided by buyer separate from this Energy Storage Technical Specification. | Drawing | Contract Requirement | ||
| IN2 | Three Line Diagram | Provide a three line diagram of proposed interconnection at the PCC including any required isolation or step-up transformer, AC protection gear (e.g. motorized breaker, fused links, mechanical disconnects, etc.), PT/CT, metering, auxiliary loads or generators, other interconnection equipment and BESS related equipment. Equipment must comply with any other specifications or standards provided by Buyer separate of this Energy Storage Technical Specification. | Drawing | Response Required | ||
| IN3 | Facility Power | The maximum steady state active power at which the Facility can continuously deliver at the point of common coupling (PCC). | kW | per proposer supply option | Contract Requirement | |
| IN4 | Facility Reactive Power | The maximum continuous reactive power (active power = 0, lagging or leading) the facility can provide without overheating. | kVAR | Response Required | ||
| IN5 | Facility Apparent Power | The maximum continuous apparent power that the Facility can provide into the AC grid continuously | kVA | Response Required | ||
| IN6 | Rated AC Current - Facility | The maximum AC current that the Facility can provide to or consume from the grid continuously. | Amps | Response Required | ||
| IN7 | Rated AC Current - BESS | The maximum AC current that the BESS can provide to or consume from the grid continuously. | Amps | Response Required | ||
| IN8 | Interconnection Voltage | Interconnection voltage of the Facility. Buyer specified, information only. Supplier required to meet this specification. | Vac | 13800 | Contract Requirement | |
| IN9 | System Power Factor Range | Leading and lagging power factor range. | - | 0.9 | Response Required | |
| IN10 | PT/CTs Requirements | Specify quantity, location, type and accuracy class (if applicable). | Describe | Response Required | ||
| IN11 | Metering Requirements | Describe metering requirements. | Describe | Response Required | ||
| IN12 | Transformer Rating | The continuous power rating of the transformer. | MVA | Response Required | ||
| IN13 | Transformer Specification | Attach transformer specification or provide the following information: configuration required by buyer (e.g. delta-wye), temperature rise and rating, impedance, BIL, taps, efficiency. | Describe | Response Required | ||
| IN14 | MV Protection Type | Specify the type of AC protection gear (e.g. motorized breaker, fused links, mechanical disconnects, relays, protective switchgear etc.). | Describe | Response Required | ||
| IN18 | UL1741 Compliance | Inverter has been tested and certified compliant UL 1741 Standard for Inverters, Converters, Controllers and Interconnection System Equipment for Use With Distributed Energy Resources | Y/N | Y | Contract Requirement | |
| IN19 | Additional Interconnection Compliance Capability | List any additional certifications (e.g., UL1741-SA, Rule 21, etc.). | Describe | Response Required | ||
| IN22 | DC Injection | Inverter meets IEEE 1547 requirements to minimize DC current injection. | Y/N | Y | Contract Requirement | |
| IN25 | Black Start | Does the system perform "Black Start" startup services for microgrid or other islanded generators? | Y/N | Response Required | ||
| IN26 | Inverter Conversion Loss | What level of loss is expected from the Inverter | %/hour | Response Required |
11-Acronyms
| Acronyms - Technical Data of Proposed BESS | |
| AC | alternating current |
| ANSI | American National Standards Institute |
| BIL | basic insulation level |
| BESS | Battery Energy Storage System |
| BMS | Battery management system |
| BOL | beginning of life |
| CT | current transformer |
| DC | direct current |
| DER | distributed energy resource |
| DoD | depth of discharge |
| EMI | electromagnetic interference |
| EOL | end of life |
| EPA | Environmental Protection Agency |
| EPCRA | Emergency Planning and Community Right-to-Know Act |
| EPRI | Electric Power Research Institute |
| ES | energy storage |
| ESD | electrostatic discharge |
| ESIC | Energy Storage Integration Council |
| ESS | energy storage system |
| EU | European Union |
| FAT | factory acceptance test |
| FMEA | failure modes and effects analysis |
| HVAC | heating ventilation and air conditioning |
| IEC | International Electrotechnical Commission |
| IEEE | Institute of Electrical and Electronics Engineers |
| IR | infrared |
| ISO | International Organization for Standardization |
| LOPA | Layer of Protection Analysis |
| LOTO | lockout/tagout |
| L x W | length times width |
| MOP | Method of Procedure |
| MTBF | mean time between failures |
| MV | medium voltage |
| NEC | National Electrical Code |
| NEMA | National Electrical Manufacturers Association |
| NESC | National Electrical Safety Code |
| NFPA | National Fire Protection Association |
| OSHA | Occupational Safety and Health Administration |
| PCC | point of common coupling |
| PCS | power conversion system |
| PT | potential transformer |
| REACH | Registration, Evaluation, Authorisation and Restriction of Chemicals (EU) |
| RFI | request for information |
| RFP | request for proposal |
| RFQ | request for quotation |
| RTE | roundtrip efficiency |
| RoHS | Restriction of Hazardous Substances Directive |
| SAT | site acceptance test |
| SCADA | supervisory control and data acquisition |
| SDS | safety datasheets |
| SIL | safety integrity level |
| SOC | state of charge |
| SOH | state of health |
| SOP | standard operating procedure |
| THD | total harmonic distortion |
| UPS | uninterruptible power supply |
| VPN | virtual private network |
| WEEE | waste electrical and electronic equipment |