Technical Capability Attachment.docx

DOCX document 22 KB Posted

Attached to
Generator Rental 1000kW
Solicitation number
N4215826QS011
Issued by

About this file

This is a Statement of Work Attachment that establishes technical specifications and certification requirements for a diesel generator rental solicitation at Norfolk Naval Shipyard (NNSY) in Portsmouth, Virginia. The Navy requires rental of one trailer-mounted 1,000 kW minimum standby diesel generator for a one-year period with an option to extend month-to-month for up to three additional months. The generator must deliver 450 volts, 3-phase, 3-wire ungrounded output with a standby rating of 1,000 kW minimum and continuous operating power of 750 kW minimum.

The equipment specifications include strict dimensional and weight limitations (not exceeding 20 feet length by 8 feet width, with maximum weight of 45,000 lbs), a rain-tight outdoor enclosure, block heater, battery charging circuit, and fuel capacity sufficient for 24-hour continuous operation at full base load. The generator must be capable of parallel operation with the ship's ungrounded electrical plant and compatible with Navy-furnished output cables. Critical requirements include recent vintage equipment (not more than ten years old), an output circuit breaker with long-time overcurrent trip set at 150 percent of base load rating, lifting points with current capacity certifications, and testing completed within two weeks of delivery. Vendors must complete and submit Tables A, B, and C with technical specification data and sign a certification confirming compliance with all stated specifications and contractor responsibilities to be considered for award.

View the file

Other files

File Type Posted
Questions and answers updated.docx DOCX document
Questions and answers.docx DOCX document
Solicitation Amendment N4215826QS0110001 SF 30.pdf PDF
Solicitation - N4215826QS011.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STATEMENT OF WORK ATTACHMENT

Topside Undocking / Destructive Weather Emergency Diesel Generator

Vendor shall certify that equipment being quoted meets the capabilities listed below and that vendor can assume all contractor responsibilities stated below by initialing at the bottom. Furthermore, vendor shall provide technical specification data sheet in Tables A, B, and C for the equipment that will be provided. In order to be considered for award, this must be completed and submitted with the vendor quote.

PURPOSE OF REQUEST: Service rental from vendor to provide one (1) trailer mounted 1,000 kW minimum Standby Power, 1,000 kW Standby Diesel Generator.

LOCATION: Norfolk Naval Shipyard (NNSY), Bldg 298, Portsmouth, VA 23709 PERIOD OF PERFORMANCE: One year with clause to extend month to month for 3 months if needed.

Table A

TECHNICAL CAPABILITIES STATEMENT

1,000 kW Standby Diesel Generator
YES
NO

Output: 450volts, 3 phase, 3 wire ungrounded.

Standby Rating of 1,000kW (minimum), Continuous Power (COP) of 750kW (minimum)

Must be equipped with a block heater and battery charging circuit and suitable pigtails for mating with NNSY 120V distribution services cans.

Diesel generator shall be capable of parallel operation with ship’s ungrounded electric plant.

Diesel generator shall be capable of paralleling with a shipboard diesel generator, diesel to be ungrounded with neutral lifted.

Safety Devices: Output circuit breaker Long Time Overcurrent trip set to 150% of Base Load COP current rating.

Diesel generator unit dimensions shall not exceed 20’ L x 8’ W. Weight not to exceed 45,000 lbs.

Diesel fuel capacity must be capable of twenty-four (24) hour minimum run time prior to refueling at full Continuous Base Load. (onboard and/or external fuel tank included)

External fuel tank shall be 1240 gallons maximum, if utilized. Unit dimensions shall not exceed 10’ L by 8’ W, fully fueled weight not to exceed 15,000 lbs. In lieu of one (1) tank, two (2) tanks can be used with dimensions not to exceed 5’-5 3/8” by 7’-8 5/8” max weight per tank 6200lbs (fully fueled). Fuel cell lifting points shall have current capacity certifications.

Onboard/External fuel tank(s) shall allow for refueling while diesel generator is operating.

Self-contained cooling system.

Trailer mounted. Lifting points shall have current capacity certifications.

Outdoor enclosure. Unit shall be equipped with rain-tight enclosure & block heater.

1,000 kW Standby Diesel Generator (cont)
YES
NO

The Diesel generator shall be of recent vintage (not more than ten years old), clean, and well maintained. The generator winding shall be a minimum of 5MΩ above ground with neutral disconnected. The unit shall have been tested within two weeks of delivery and applicable test data sent with unit.

All neutral connections shall be disconnected and isolated from generator windings and any additional equipment as necessary.

Unit shall have posted operating instructions in the vicinity of the control panel that clearly state how to start, stop and operate the diesel generator and output circuit breaker. The posted instructions shall include any necessary steps for proper operation of the diesel generator in parallel with ship’s service motor generator. Operating instructions may require clarification at ship’s request after delivery, and vendor is to clarify instructions as necessary.

Unit shall be compatible with Shipyard furnished “THOF-500E”-T-500 lugged output cables (4 per phase). If mechanical lug connections are provided, they shall be sized for 500MCM (4 per phase).

Table B

Rating (kW)
Rating (Amps)

Standby Power

Prime Power

Base Load Continuous Operating Power (COP)

Table C

Load (kW)
Burn Rate (Gallons/HR)
Run Time (Hours)

Standby Power

Prime Power

Base Load Continuous Operating Power (COP)

TECHNICAL CAPABILITY/CONTRACTOR RESPONSIBILITY CERTIFICATION

Vendor hereby certifies that vendor’s service meets or exceeds all specifications and contractor responsibilities stated in this solicitation, in their entirety, with no exceptions. ___________ (initials)

___________________________________________________________________________________
SignaturePrinted Name
___________________________________________________________________________________
TitleDate