TECH LIBRARY 1 SVPP Supplier Manuals EthosEnergy Speed Input Module II User Manual.pdf
PDF 794 KB Posted
- Attached to
- Launch Operations Support Contract (LOSC) Request for Proposal (RFP) – FINAL Federal contract opportunity
- Solicitation number
- FA4610-22-R-0001
About this file
This document is a final request for proposal for launch operations support contract services. The 30th Space Wing at Vandenberg Air Force Base is seeking proposals to provide facilities support, operations support, and mission support services for Department of Defense space launch activities. Proposals are due no later than January 27, 2022. The resulting contract will have a North American Industry Classification System code of 561210 for facilities support services. The solicitation includes a 37-page performance work statement and related appendices outlining required services. Additional attachments provide security classification specifications, Department of Labor wage determinations for applicable service employee classifications, and collective bargaining agreements. Exhibits include contract data requirements and data item descriptions. Templates are also included for offerors to submit staffing plans, subcontractor consent forms, and organizational conflict of interest mitigation plans with their proposals.
View the file
Other files for this federal contract opportunity
Show all 50
Launch Operations Support Contract (LOSC) Request for Proposal (RFP) – FINAL has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EthosEnergy Group
591 West 66 th Street
Loveland, CO 80538
Speed Input Module II
USER MANUAL
SIM-II
S
IM
-I I
Speed Input Module II – User Manual
Page i
Revision Date Reason Approved
A Apr 2012 Original Revision J. Schleis
Page ii
Page iii
Table of Contents
1 INTRODUCTION
1.1 PURPOSE
1.2 SUPPLEMENTAL MANUALS
1.3 AUDIENCE
1.4 TECHNICAL SUPPORT
2 PRODUCT SAFETY
2.1 DEFINITIONS
2.2 GENERAL SAFETY
3 OPERATION
3.1 OVERVIEW
3.2 HARDWARE DESIGN
3.3 FRONT STATUS LIGHTS
3.4 FREQUENCY MEASUREMENT
3.5 SPEED CALCULATION
3.6 OVERSPEED FUNCTION
3.7 WATCHDOG FUNCTION
3.8 DIAGNOSTICS
4 INSTALLATION
4.1 MOUNTING ON DIN RAIL
4.2 REMOVING FROM DIN RAIL
4.3 POWER SUPPLY AND GROUNDING
4.4 WIRING TO SPEED PROBES
4.5 WIRING TO PASSIVE PROBES
4.6 WIRING TO ACTIVE PROBES
4.7 WIRING TO RELAY OUTPUTS
4.8 PLC COMMUNICATIONS NETWORK
4.9 SERIAL COMMUNICATIONS
APPENDIX A: SPECIFICATION
A1 POWER INPUT
A2 PASSIVE PROBE INPUTS
A3 ACTIVE PROBE INPUTS
A4 RELAY OUTPUTS
A5 ENVIRONMENTAL CONDITIONS
A6 PLC COMMUNICATIONS
A7 RS232 COMMUNICATIONS
APPENDIX B: MEMORY MAP
B1 CONTROLNET MEMORY MAP
APPENDIX C: CONFIGURATION RECORD
Page iv
C1 CHANNEL 1
C2 CHANNEL 2
C3 CHANNEL 3
C4 CHANNEL 4
C5 PLC COMMUNICATIONS
APPENDIX D: CONTROLLOGIX CONTROLNET SETUP
D1 REGISTER EDS FILE
D2 VERIFY INSTALLATION
D3 CONFIGURE SOFTWARE
APPENDIX E: ELECTRONIC DATA SHEET (EDS)
APPENDIX F: SERIAL COMMUNICATION INTERFACE
F1 READ ADDRESS
F2 WRITE ADDRESS
F3 ADDRESS LISTING
F3.1 Revision A
APPENDIX G: CONTROLNET COMMUNICATIONS BOARD
G1 NETWORK ACCESS PORT (NAP)
G2 CONTROLNET CHANNELS A & B
G3 NODE NUMBER SWITCHES (X10 AND X1)
G4 INDICATOR LIGHTS
APPENDIX H: REGULATORY COMPLIANCE
H1 EUROPEAN COMPLIANCE FOR CE MARKING
H2 OTHER EUROPEAN COMPLIANCE
H3 OTHER
H4 EC DECLARATION OF CONFORMITY
1 Introduction
1.1 Purpose
This manual describes the operation and installation of the Speed Input Module II (part numbers starting with ‘SIM-II’).
1.2 Supplemental Manuals
The following manuals are essential to the proper use and troubleshooting the Speed Input
Module.
The PLC software manual
The PLC’s communication software (if separate) manual
The PLC’s communication controller (if separate) manual
1.3 Audience
This manual is written for those who are already familiar with the communication network utilized and the PLC/PC that is being used. It will assist in integrating the Speed Input
Module into the communication network.
1.4 Technical Support
Technical support is available from EthosEnergy Group 24/7 via the toll free customer service phone number.
+1 800-437-9769
2 Product Safety
2.1 Definitions
A WARNING indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury.
A CAUTION indicates a potentially hazardous situation that, if not avoided, could result in damage to equipment or property.
A NOTE provides other helpful information that does not fall under the warning or caution categories.
2.2 General Safety
This manual defines a controlling device and care must be taken to fully understand scope of equipment prior to installation and/or maintenance of said equipment.
Read this entire manual and all other related publications pertaining to the work to be performed before installing, operating, or servicing this equipment.
Practice all plant and safety instructions and precautions. Failure to follow instructions can cause personal injury and/or property damage.
Any unauthorized modifications to or use of this equipment outside its specified mechanical, electrical, or other operating limits may cause personal injury and/or property damage, including damage to the equipment. Any such unauthorized modifications: (i) constitute "misuse" and/or "negligence" within the meaning of the product warranty thereby excluding warranty coverage for any resulting damage, and (ii) invalidate product certifications or listings.
All electronic equipment is static-sensitive, some components more than others. To protect these components from static damage, you must take special precautions to minimize or eliminate electrostatic discharges. When storing this product, it should be done so in an antistatic protective bag. Do not open the case as this exposes the printed circuit board (PCB) to electrostatic discharge.
Refer to all the instructions and warnings specified in this User Manual before using the equipment.
3 Operation
3.1 Overview
The Speed Input Module (SIM) is a high-speed interface between speed sensing devices and a PLC. It simultaneously operates as a stand-alone device for overspeed detection. Up to four independent speed sensor channels can be configured via a serial interface.
All magnetic pickup styles are supported. Passive magnetic sensors (variable reluctance) are widely used because of their known failure modes. Active probes (Hall Effect or zero speed) can be used with the SIM by wiring into different terminals on the module. Both TTL and supply tracking versions of active probes are compatible with the SIM. Each of the input channels can be configured for a different style.
In order to interface with Allen-Bradley and other similar PLCs, the SIM incorporates a communication network interface module.
As an overspeed detection device, each channel has its own setpoint and trip relay output.
Figure 1
3.2 Hardware Design
Inside the SIM is an Intel Series 196 microcontroller that handles configuration, measurement, and serial communications. An additional processor is responsible for the communications interface.
All of the configuration data is stored in non-volatile memory accessible by the microcontroller. This data is available for configuration via the serial communication port.
The serial communication software runs continuously on the CPU. An external interrupt triggers the speed calculation software on a regular basis. This allows the SIM to produce speed data to the communications network on a consistent recursion rate of ten milliseconds.
A proprietary communication protocol is utilized to monitor and change the non-volatile memory and other module information.
3.3 Front Status Lights
Two status lights are visible on the front of the SIM. The following table is a description of each state and meaning.
Signal Color LED State Meaning
NORMAL green on SIM ready for operation off watchdog has timed out (see below)
OVERSPEED red on one of the four input channels have exceeded the programmed overspeed setpoint (latching) off no overspeed conditions present
Table 1
Communications Status LED’s are located on the right side of the module, close to the BNC connectors. See Appendix G for details.
3.4 Frequency Measurement
A unique frequency multiplication and counter scheme allows the SIM to measure speed with high accuracy in a short period of time. Frequencies above 100Hz are encoded within
0.025% of the selected full scale. Below 100Hz, the counter changes its calculation to monitor over a longer interval.
The input signal is shaped and fed to a phase-locked-loop that multiplies the incoming frequency. This multiplied frequency is connected to a high speed counter accessible by the microcontroller. Every ten milliseconds, the counter’s value is gathered. The counter difference between samples and the multiplier gain are used to calculate the input frequency.
Previously calculated data is stored and used in the calculation of the current frequency to produce a higher resolution measurement.
Several checks including the following are performed on the counter data to validate the frequency calculation.
When a frequency input channel transitions from zero to a valid signal, the frequency
(and resulting speed) calculation is rate limited for three seconds. This signal validation period is necessary for redundant applications where on-line replacement of the SIM is possible. Invalid frequency measurements generated from connecting a live speed signal are ignored. Once the signal is validated, no further time delays are introduced.
Rate limiting is performed to ignore momentary abnormalities in the input signal.
Execution time is measured with each scan. Subtle differences in the analog clock are known and used to compensate the measured values.
The multiplier for the input frequency is selectable based upon the desired frequency range of the input signal. The highest possible multiplier (smallest possible frequency range) should be used for the greatest measured resolution. The following selections can be made via the serial interface.
Multiplier (PLL Gain)
Maximum Input Frequency
Max Readable
RPM
8 25 kHz 32767
16 12.5 kHz 32767
32 6250 Hz 32767
64 3125 Hz 32767
128 1560 Hz 3276.7
256 780 Hz 327.67
Table 2
3.5 Speed Calculation
Rotational speed is calculated with the sensor configuration and the pulses per revolution of the shaft. Each input channel can be configured independently.
Two configuration values are available: teeth per revolution of the shaft, and an offset. In cases where a gear ratio or other arrangement exists, the number of teeth can be entered as a fractional amount with two decimal places.
Typically, the offset is not used unless the specific gear ratio cannot be entered with enough resolution to generate an accurate speed calculation.
When the smaller frequency ranges are selected (1560 Hz or 780 Hz), the speed calculation provides decimals to the user. A range of 1560 Hz selects a single decimal place and a range of 780 Hz provides two decimal places. Since the SIM produces the speed data in integer format, the decimals are provided as a multiplier in the speed calculation. For example, if the range is 1560 Hz and the actual speed is 436.75 rpm, the SIM produces a speed value of 4367
(436.75 x 10 for one decimal place). For the same speed, if the range were 780 Hz the result would be a speed value of 43675 (436.75 x 100 for two decimal places).
3.6 Overspeed Function
Each channel is configured with an independent overspeed setpoint. If the SIM calculates a rotational speed that exceeds the setpoint, the corresponding relay output is de-energized
(opening the contact) and the OVERSPEED light is lit. The overspeed relay and the light are latched in the SIM. The overspeed latch can be reset by pulsing the reset bit via the communication link (See the memory map in Appendix B) or power cycle the SIM.
The highest speed measured is captured and stored in RAM. Monitoring and clearing this value is possible from the serial communication interface.
The highest speed captured is lost if power to the module is removed
3.7 Watchdog Function
The microcontroller periodically triggers an independent monostable circuit utilized as a watchdog. In the event the processor does not trigger the monostable every eight milliseconds, a relay (available to the user as 5R) de-energizes, and the communications interface flags that the unit has failed.
Possible causes for the hardware watchdog to fail include invalid configuration, failed power-up or periodic self-tests, or faulty hardware. See the Diagnostics section below for a detailed listing of internal tests that are performed that result in a watchdog failure indication.
A watchdog counter is also available to the PLC to monitor the SIM and the communications link. An internal counter is incremented each time data is produced to the communication network. This counter is included in the memory map to be monitored by the PLC. If for any reason the counter does not change, communications to the SIM has been lost. This trigger can be utilized in the PLC to take the appropriate action.
3.8 Diagnostics
Self-diagnostics are performed by the SIM. If any fault is found, the microcontroller is commanded to set all speed and frequency data to a failed value, 65535 (-1 if signed integers are used in the PLC), and all relays are deenergized (including the watchdog). Diagnostics can be categorized into two sets of faults.
The first set is checked on power up to determine that the SIM hardware and software are configured properly and no faults exist. These tests include:
EEPROM checksum
NVM copy into RAM (access errors and checksum)
RAM access fault
The second set of tests is performed continuously while the SIM is running to ensure the module is operating properly. These include:
NVM checksum
EEPROM checksum
Invalid configuration (maximum frequency range incorrect)
Speed calculation error
Divide by zero
Serial communication fault
Timeout of 10ms interrupt routine
The fault information is communicated via the serial interface link and the communication network. See the memory map in Appendix B for further communication interface details.
4 Installation
4.1 Mounting on DIN Rail
1. Position the SIM on the DIN rail at a slight angle.
2. Hook the left side of the SIM mounting plate to the DIN rail while holding the module at a slight angle away from the DIN rail.
3. Press the SIM down onto the DIN rail until the mounting plate snaps into place.
4. If the mounting plate does not lock into place, use a screwdriver or similar device to move the spring loaded locking tab away from the DIN rail while pushing the module onto the DIN rail and release the locking tab to lock the adapter in place.
4.2 Removing from DIN rail
1. Remove all of the wiring connections by pulling out the plug connectors on both sides.
2. Move the spring-loaded locking tab (on right side of module) away from the DIN rail with a screwdriver or similar device.
3. With the locking tab held out, tilt the module away from the DIN rail and then unhook the left side.
4.3 Power Supply and Grounding
The SIM should be connected to a nominal 24 Vdc power supply. The input power should be protected by a fuse or breaker no greater than two amps. Power input is wired via the J5 pluggable connector.
Figure 2
An instrument ground should be supplied and connected to J5 Shield (S) terminal. This terminal is connected to all of the shield terminals on the module; it is not connected to chassis.
Improper shield grounding can cause invalid speed measurement or erroneous overspeed detection.
Shield (S)
Supply (-)
Supply (+)
J5
4.4 Wiring to Speed Probes
The SIM will accept either Passive or Active speed probes on each of the 4 channels. The
SIM will automatically use the probe type that is wired. Therefore, either the Passive channel, OR Active channel should be wired.
Any unused inputs should be shorted (P1 to P2) for noise immunity.
4.5 Wiring to Passive Probes
Passive speed signals are coupled through a transformer to the SIM. Terminals P1 and P2 are the 1:1 connection. If extremely low voltages are present at the passive probe, Terminals
P1 and P3 may be used, making the input an amplifying 1:2 connection. Refer to Appendix
A for input signal levels. Connectors J1 and J2 are for connecting passive probes to the SIM as shown below.
Figure 3
Input 1 Common (1P1)
Input 1 Center Tap (1P3)
Input 1 Primary (1P2)
Shield (S)
Input 2 Common (2P1)
Input 2 Center Tap (2P3)
Input 2 Primary (2P2)
J1
J2
Shield (S)
Input 3 Common (3P1)
Input 3 Center Tap (3P3)
Input 3 Primary (3P2)
Shield (S)
Input 4 Common (4P1)
Input 4 Center Tap (4P3)
Input 4 Primary (4P2)
Shields can be connected to the Shield (S) terminals if a connection is made from J5 Shield
(S) terminal to instrument ground. Shields should only be terminated to a ground at one point. If a shield connection to ground is made elsewhere, leave the shields disconnected at the SIM.
4.6 Wiring to Active Probes
Active speed signals are optically isolated in the SIM. Power for the active probes is not supplied by the SIM. An external power supply should be used to power active probes. This external supply does not need to be referenced to the power supply for the SIM. Connectors J3 and J4 are for connecting active probes to the SIM as shown below.
Figure 4
Shields can be connected to the Shield (S) terminals if a connection is made from J5 Shield
(S) terminal to instrument ground. Shields should only be terminated to a ground at one point. If a connection to ground is made elsewhere, leave the shields disconnected at the
SIM.
Any unused inputs should be shorted (P1 to P2) for noise immunity.
Input 3 Signal (3A+)
Input 3 Common (3A-)
Shield (S)
Input 4 Signal (4A+)
Input 4 Common (4A-)
Input 1 Signal (1A+)
Input 1 Common (1A-)
Shield (S)
Input 2 Signal (2A+)
Input 2 Common (2A-)
J3
J4
4.7 Wiring to Relay Outputs
Each relay output is an independent, dry contact, and normally open output (Form A).
Relays one through four represent the overspeed for channels one through four, respectively.
The fifth relay is tied to the watchdog circuit. All of the relays are normally energized.
During normal conditions, all of the contacts are closed. In the case of an overspeed, the corresponding relay contacts open. For a watchdog event, all relay contacts open. Connector J6 is used to connect all five of the relay outputs as shown below.
Each Relay is protected with an internal 4 amp fuse (non-field serviceable). If any of these fuses are blown, the unit must be returned to the factory for repair.
Figure 5
4.8 PLC Communications Network
The SIM is capable of communications to a PLC over a deterministic network. This typically is ControlNet, however, other versions are available. The ControlNet interface is a redundant media, deterministic network that allows regular scheduled communication to the
PLC for real time control applications. The physical network connection is a pair of coaxial
BNC connectors at the right side of the box. The leftmost BNC is the “A” network connection and the right BNC is the “B” network connection. See Appendix G for details on the ControlNet Interface.
Data is contained in an 18 word read and a 16 word write memory space. All information is passed as integers to the PLC. See Appendix B for a detailed memory map.
Shield (S)
Overspeed 1 NO (1R1)
Overspeed 1 Com (1R2)
Overspeed 2 NO (2R1)
Overspeed 2 Com (2R2)
Overspeed 3 NO (3R1)
Overspeed 3 Com (3R2)
Overspeed 4 NO (4R1)
Overspeed 4 Com (4R2)
Watchdog 5 NO (5R1)
Watchdog 5 Com (5R2)
J6
4.9 Serial Communications
Configuration of the SIM is performed via the serial communication network. A Null-
Modem cable is required. The protocol is defined in Appendix E along with an address listing.
Appendix A: Specification
A1 Power Input
Characteristic Specification
Supply Voltage 24 Vdc
Operating Supply Range 20-32 Vdc
Power Consumption 15W maximum
A2 Passive Probe Inputs
Characteristic Specification
Isolation transformer coupled, hi-pot to 1,000
VRMS
Input Impedance 10 kΩ at 1 kHz
Frequency Range 1 Hz to 25 kHz
Minimum Signal Level
(terminals 1 & 2)
0.5 V peak (frequencies < 1 kHz)
1.5 V peak (frequencies ≥ 1 kHz)
Minimum Signal Level
(terminals 1 & 3)
0.25 V peak (frequencies < 1 kHz)
0.75 V peak (frequencies ≥ 1 kHz)
Maximum Signal Level 70 V peak & 50 V rms
A3 Active Probe Inputs
Characteristic Specification
Isolation opto-coupled, 2.5 kV minimum
Input Impedance 1.5 kΩ
Frequency Range 1 Hz to 10 kHz
Minimum ON Signal Level 0.5 mA, 2.5 Vdc nominal
Maximum OFF Signal Level 0.1 mA, 1 Vdc nominal
Maximum Input Signal 20 mA, 30 Vdc nominal
A4 Relay Outputs
Characteristic Specification
Contact Ratings
(resistive load)
0.5 A at 125 Vac
2.0 A at 30 Vdc
0.5 A at 125 Vdc
Maximum Switching Power 60 W
Maximum Switching Voltage 220 Vdc
Maximum Switching Current 2.0 A
Operating Time (Setting) 6 ms maximum, 1.5 ms nominal
Operating Time (Resetting) 3 ms maximum, 1 ms nominal
A5 Environmental Conditions
Characteristic Specification
Operating Temperature 0 °C to 50 °C (32 °F to 122 °F)
Storage Temperature -25 °C to +70 °C (-13 °F to + 158 °F)
Humidity 5 % to 90 % RH non-condensing
Size 7.5”H x 5.125”W x 2.75”D
Weight approximately 2 lb. 1 oz.
A6 PLC Communications
ControlNet Communications
Characteristic Specification
Communication Mode CIP, peer-to-peer
Input* Words 18
Output* Words 16
Data Type integer
Connector 75Ω BNC, redundant media
*Input and output are referenced to the PLC
A7 RS232 Communications
Characteristic Specification
Baud Rate 9600 bits per second
Parity None
Bits 8
Stop Bits 1
Flow Control Hardware
Connection Null Modem Cable
Appendix B: Memory Map
B1 ControlNet Memory Map
Inputs
Input
Word
MSB LSB Description
0 Reserved Reserved
1 Reserved Reserved
2 Frequency Signal 1 Frequency in Hz for input channel 1
3 Frequency Signal 2 Frequency in Hz for input channel 2
4 Frequency Signal 3 Frequency in Hz for input channel 3
5 Frequency Signal 4 Frequency in Hz for input channel 4
6 Speed Signal 1 Speed in RPM for input channel 1
7 Speed Signal 2 Speed in RPM for input channel 2
8 Speed Signal 3 Speed in RPM for input channel 3
9 Speed Signal 4 Speed in RPM for input channel 4
10 Status 2 Status 1* Individual channel fault status
11 Status 4 Status 3 Individual channel fault status
12 Zero Overspeed** Overspeed status for each channel
13 Watchdog Communication watchdog counter (10ms increments)
14 Fault*** Fault status for the SIM
15 Reserved Reserved
16 Reserved Reserved
17 Reserved Reserved
* Status Byte
Value Description
0 Normal
1 Fault
** Overspeed Byte
Bit Description
0 Overspeed on channel 1 (1 = overspeed; 0 = normal)
1 Overspeed on channel 2 (1 = overspeed; 0 = normal)
2 Overspeed on channel 3 (1 = overspeed; 0 = normal)
3 Overspeed on channel 4 (1 = overspeed; 0 = normal)
4 Spare
5 Spare
6 Spare
7 Spare
*** Fault Word
Bit Description
0 No Faults
1 Reserved
2 Reserved
3 EEPROM checksum error
4 Serial communication task fault
5 Execution timeout
6 NVM checksum fault
7 NVM access fault
8 EEPROM power-up error
9 Communication Board Fault
10 Invalid PLL gain
11 Speed calculation overflow
12 Divide by zero
13 Reserved
14 Reserved
15 Reserved
Outputs
Output
Word
MSB LSB Description
0 Overspeed Reset * Overspeed reset command
1 - 15 Reserved Reserved
* Overspeed Reset Word
Bit Description
0 Reset channel 1
1 Reset channel 2
2 Reset channel 3
3 Reset channel 4
4 Spare
5 Spare
6 Spare
7 Spare
To reset an overspeed a pulse to the channel's bit is required (low → high → low).
Appendix C: Configuration Record
C1 Channel 1 Parameter Default Range As Left
Pulses / Revolution 60.00 1.00 to 655.35
Speed Offset 0 0 to 100
Max Frequency 25 kHz 25 kHz, 12.5 kHz, 6250 Hz, 3125 Hz, 1560 Hz, 780 Hz
Overspeed Setpoint 1100 0 to 65535
C2 Channel 2 Parameter Default Range As Left
Pulses / Revolution 60.00 1.00 to 655.35
Speed Offset 0 0 to 100
Max Frequency 25 kHz 25 kHz, 12.5 kHz, C3 Channel 3 Parameter Default Range As Left
Pulses / Revolution 60.00 1.00 to 655.35
Speed Offset 0 0 to 100
Max Frequency 25 kHz 25 kHz, 12.5 kHz, C4 Channel 4 Parameter Default Range As Left
Pulses / Revolution 60.00 1.00 to 655.35
Speed Offset 0 0 to 100
Max Frequency 25 kHz 25 kHz, 12.5 kHz, C5 PLC Communications Parameter Default Range As Left
Node 7 1 to 99
Appendix D: ControlLogix ControlNet Setup For those using the SIM with the Allen-Bradley ControlLogix processor, the following example shows how to setup the ControlNet network and the application program.
D1 Register EDS File
Before attempting to configure the SIM in an application or browse it in the
ControlNet network, the Electronic Data Sheet (EDS) must be registered on the computer utilized to program the device.
With RSLinx installed on the computer, go to:
Start → Programs → Rockwell Software → RSLinx Tools → EDS Hardware
Installation Tool
Follow the instructions to ‘Add’ the EDS file for the SIM. If you do not have an electronic copy of the EDS file, copy the text in Appendix E to a text file named “83-
7278-EDS_ABS_CNT_V_1_7.eds”.
D2 Verify Installation
Utilizing RSLinx, browse to the ControlNet network containing the SIM. When the network is browsed, the SIM should be recognized with an icon representing the module. If the ControlNet node address for the SIM is shown as unknown (question mark), the EDS file was not registered successfully.
D3 Configure Software
In RSLogix 5000, you must have a ControlNet module configured in the
ControlLogix chassis that is physically connected to the SIM. Under the ControlNet module, define a ‘Generic ControlNet Module’ with the following parameters:
Parameter Recommended Setting
Name Any
Description Any
Comm Format Data - INT
Node As required to match SIM address
Connection Parameters Assembly Instance
Size
Input 100 18
Output 150 16
Configuration 4 0
Appendix E: Electronic Data Sheet (EDS)
[File]
DescText = "AnyBus-S ControlNet";
CreateDate = 07-19-1999;
CreateTime = 11:11:51;
ModDate = 03-10-2004;
ModTime = 15:00:00;
Revision = 1.7;
[Device]
VendCode = 90;
VendName = "HMS Networks";
ProdType = 12;
ProdTypeStr = "Communication Adapter";
ProdCode = 1;
MajRev = 1;
MinRev = 50;
ProdName = "Anybus-S ControlNet";
Catalog = "Anybus-S ControlNet";
[Device Classification]
Class1 = 1_RSNetWorx_Adapter;
Class2 = ControlNet;
[Port]
Port1 = ControlNet_Redundant, "Port A", "20 F0 24 01", 2;
[Params]
Param2 =
0, $ first field shall equal 0
,, $ path size,path
0x0000, $ descriptor
199, $ data type : 16-bit Unsigned Integer
2, $ data size in bytes
"Output Size", $ name
"", $ units
"", $ help string
0,450,16, $ min,max,default data values
0,0,0,0, $ mult,dev,base,offset scaling not used
0,0,0,0, $ mult,dev,base,offset link not used
0; $ decimal places not used
Param3 =
0, $ first field shall equal 0
,, $ path size,path
0x0000, $ descriptor
199, $ data type : 16-bit Unsigned Integer
2, $ data size in bytes
"Input Size", $ name
"", $ units
"", $ help string
4,454,20, $ min,max,default data values
0,0,0,0, $ mult,dev,base,offset scaling not used
0,0,0,0, $ mult,dev,base,offset link not used
0;
[Connection Manager]
Connection1 =
0x04010002, $ trigger & transport
$ 0-15 = supported transport classes (class 1)
$ 16 = cyclic (1 = supported)
$ 17 = change of state (0 = not supported)
$ 18 = on demand (0 = not supported)
$ 19-23 = reserved (must be zero)
$ 24-27 = exclusive owner
$ 28-30 = reserved (must be zero)
$ 31 = client 0 (don't care for classes 0 and 1)
0x44240405, $ point/multicast & priority & realtime format
$ 0 = O=>T fixed (1 = supported)
$ 1 = O=>T variable (0 = not supported)
$ 2 = T=>O fixed (1 = supported)
$ 3 = T=>O variable (0 = not supported)
$ 4-7 = reserved (must be zero)
$ 8-10 = O=>T header (4 byte run/idle)
$ 11 = reserved (must be zero)
$ 12-14 = T=>O header
$ 15 = reserved (must be zero)
$ 16-19 = O=>T point-to-point
$ 20-23 = T=>O multicast
$ 24-27 = O=>T scheduled
$ 28-31 = T=>O scheduled
,Param2,, $ O=>T RPI,Size,Format
,Param3,, $ T=>O RPI,Size,Format
,, $ config part 1 (dynamic assemblies)
,, $ config part 2 (module configuration)
"Discrete Exclusive Owner", $ connection name
"", $ Help string
"20 04 24 01 2C 96 2C 64"; $ exclusive output path
1_PLC5C_RTD_Format1 = 1_PLC5C_1794_Discrete_RTD_Format;
Appendix F: Serial Communication Interface The serial interface is a master/slave based protocol with embedded checksums. Each address is written to or read from with a separate request. A single reply is transmitted from the SIM for each command. The reply is one of three possibilities: acknowledge and return of the requested data, acknowledgement of a successful write to memory, or a not acknowledged message when the command was not understood.
The embedded message checksum is calculated as a rolling sum of each byte in the message before the checksum.
Note: Messages are shown below in hexadecimal.
F1 Read Address
The following message is transmitted to the SIM for a read request:
Read Length Address -1 Registers Checksum
0xD2 0x7 LSB MSB 0x0 LSB MSB
The corresponding acknowledge message is formatted as shown below:
Ack Length Data Checksum
0x86 0x6 LSB MSB LSB MSB
If the read command was not understood by the SIM, the following message is replied:
Nak Length Checksum
0x95 0x4 0x99 0x00
F2 Write Address
The following message is transmitted to the SIM for a write request:
Write Length Address -1 Registers Data Checksum
0xC2 0x9 LSB MSB 0x0 LSB MSB LSB MSB
The corresponding acknowledge message is formatted as shown below:
Ack Length Checksum
0x86 0x4 0x8A 0x00
If the write command was not understood by the SIM, the following message is replied:
Nak Length Checksum
0x95 0x4 0x99 0x00
F3 Address Listing
F3.1 Revision A
The following list of addresses is valid for Revision A of the SIM. Not all of the addresses can be written to as noted in the table.
Address Bit Description Read / Write
1 - Overspeed setpoint for channel 1 R/W
2 - Overspeed setpoint for channel 2 R/W
3 - Overspeed setpoint for channel 3 R/W
4 - Overspeed setpoint for channel 4 R/W
5 0 - 3 1 = Max Freq for channel 1 equal to 25kHz R/W
2 = Max Freq for channel 1 equal to 12.5 kHz R/W
3 = Max Freq for channel 1 equal to 6250 Hz R/W
4 = Max Freq for channel 1 equal to 3125 Hz R/W
5 = Max Freq for channel 1 equal to 1560 Hz R/W
6 = Max Freq for channel 1 equal to 780 Hz R/W
4 - 7 1 = Max Freq for channel 2 equal to 25kHz R/W
2 = Max Freq for channel 2 equal to 12.5 kHz R/W
3 = Max Freq for channel 2 equal to 6250 Hz R/W
4 = Max Freq for channel 2 equal to 3125 Hz R/W
5 = Max Freq for channel 2 equal to 1560 Hz R/W
6 = Max Freq for channel 2 equal to 780 Hz R/W
8 - 11 1 = Max Freq for channel 3 equal to 25kHz R/W
2 = Max Freq for channel 3 equal to 12.5 kHz R/W
3 = Max Freq for channel 3 equal to 6250 Hz R/W
4 = Max Freq for channel 3 equal to 3125 Hz R/W
5 = Max Freq for channel 3 equal to 1560 Hz R/W
6 = Max Freq for channel 3 equal to 780 Hz R/W
12 -
1 = Max Freq for channel 4 equal to 25kHz R/W
2 = Max Freq for channel 4 equal to 12.5 kHz R/W
3 = Max Freq for channel 4 equal to 6250 Hz R/W
4 = Max Freq for channel 4 equal to 3125 Hz R/W
5 = Max Freq for channel 4 equal to 1560 Hz R/W
6 = Max Freq for channel 4 equal to 780 Hz R/W
7 - Speed offset for channel 1 R/W
8 - Speed offset for channel 2 R/W
9 - Speed offset for channel 3 R/W
10 - Speed offset for channel 4 R/W
12 - Pulses per revolution x 100 for channel 1 R/W
13 - Pulses per revolution x 100 for channel 2 R/W
14 - Pulses per revolution x 100 for channel 3 R/W
15 - Pulses per revolution x 100 for channel 4 R/W
Address Bit Description Read / Write
129 - Calculated speed for channel 1 R
130 - Calculated speed for channel 2 R
131 - Calculated speed for channel 3 R
132 - Calculated speed for channel 4 R
181 0 Reserved R
1 Reserved R
2 Reserved R
3 EEPROM checksum error R
4 Serial communication task fault R
5 Execution timeout R
6 NVM checksum fault R
7 NVM access fault R
8 EEPROM power-up error R
9 Reserved R
10 Invalid Max Input Freq R
11 Speed calculation overflow R
12 Divide by zero R
13 Reserved R
14 Reserved R
15 Reserved R
187 0 0=Normal; 1=Overspeed on channel 1 R
1 0=Normal; 1=Overspeed on channel 2 R
2 0=Normal; 1=Overspeed on channel 3 R
3 0=Normal; 1=Overspeed on channel 4 R
194 - Calculated frequency for channel 1 R
195 - Calculated frequency for channel 2 R
196 - Calculated frequency for channel 3 R
197 - Calculated frequency for channel 4 R
206 0 0=Normal; 1=Hardware fault on channel 1 R
4 0=Normal; 1=Hardware fault on channel 2 R
207 0 0=Normal; 1=Hardware fault on channel 3 R
4 0=Normal; 1=Hardware fault on channel 4 R
Appendix G: ControlNet Communications Board The following appendix is an excerpt from the HMS Industrial Networks documentation [83-
8559 – Fieldbus Appendix AnyBus-S ControlNet, Revision 2.00]. The following diagram identifies the interfaces available to the user and their orientation.
# Description
2 Network Access Port (NAP)
3 ControlNet Channel A
4 ControlNet Channel B
5 Node # switch (x10)
6 Node # switch (x1)
7 ControlNet Status Indicators
G1 Network Access Port (NAP)
The NAP (Network Access Port) provides temporary access to the ControlNet network for diagnostics and configuration.
G2 ControlNet Channels A & B
The module is equipped with two BNC contacts for connection to ControlNet. If redundant operation is desired, both connectors are used; otherwise connector A or B is used.
G3 Node Number Switches (x10 and x1)
On a ControlNet network, each node must be assigned its own unique node address. The module features on board switches for ControlNet node configuration, providing an address range of 1 to 99.
In this example, the node address is set to 42 (4 x 10 + 2 x 1).
NOTE: If either of the switches is changed, power must be cycled to the unit to use the new address.
G4 Indicator Lights
The following diagram describes the indicator lights that are next to the ControlNet node number switches. These lights display the health of the ControlNet connection and can aid in troubleshooting communications.
Appendix H: Regulatory Compliance
H1 European Compliance for CE Marking
EMC Directive: 2004/108/EC COUNCIL DIRECTIVE
Low Voltage Directive: 73/23/EC COUNCIL DIRECTIVE
H2 Other European Compliance
RoHs Directive: 2002/95/EC COUNCIL DIRECTIVE
H3 Other
Machinery Protection: API 612 compliant
H4 EC Declaration of Conformity
Tel: 970-669-0801 (direct)
800-437-9769 (toll free)
Fax: 970-669-1299
S
IM
-I I
File details come from the government source that posted it. Updated .