| Location: | BRICKELL PLAZA FEDERAL BUILDING | Property Manager: | |
| Bldg. # | FL0079ZZ | 909 SE 1st Ave | |
| Miami, FL 33131 |
Contract Specialist Carolina McFaul O & M Contractor IEI
General Information:
Quantity of Floors 9 Age of Building 49 Operating Hours 5:00AM TO 5:00 PM
| Elevators | Building Operating Plan | Yes | Quantity of Agencies | 8 | ||
| Judges | N/A | |||||
| Passengers | 2 | List Agencies *(Of special note are law enforcement and agencies with 24 hour operations)* | ||||
| Freight | 1 | US COAST GUARD, US CUSTOMS, US HUD. EPA, USDA, LABOR DEPARTMENT, NATIONAL OCEANIC AND US DEPARTMENT OF AGRICULTURE | ||||
| Prisoner | N/A | |||||
| Total |
Comments:
Child Care Centers
| Interior: | ||
| Special Equipment | No | If yes, identify below: |
| Playground | No |
Environmental
| GSA Owned Fuel Tanks | Qty. | Asbestos | Yes | |
| Above Ground | 3 | |||
| Under Ground | N/A | Lead Paint | No |
GSA Owned Generators 2 PCB's
Firing Range N/A If yes, last date of lead clean up? N/A
Note to Contractor: Asbestos, Lead, or any other hazardous material may be in the building (particularly older ones) and has not been discovered yet so all suspicious material found should be treated as such.
Major Alteration Project: N/A
Comments:
Building Equipment
Building Automation System
Make NIAGARA Model N/A Software Version N/A
Is BAS on GSA network? No Types of controller? Pneumatics
HVAC
| Item | Qty | Item | Qty | Item | Qty | Item | Qty |
| AHU | 17 | PIU | N/A | FCU | N/A | RTU | 12 |
| VAV | N/A | OAF | N/A | VAV w Fan | 1 | RAF | 1 |
| Duct Heaters | N/A |
FAN COIL UNITS
Qty. 27
| Make | DAIKIN 4TH FLOOR | Model | SWP033HLS27 | Serial # | FBOU 140600219 | ||
| Make | DAIKIN 4TH FLOOR | Model | SWP033HLS27 | Serial # | FBOU 140600418 | ||
| Make | DAIKIN 9TH FLOOR | Model | SWP033HLS27 | Serial # | FBOU 140501274 | ||
| Make | DAIKIN 9TH FLOOR | Model | SWP033HLS27 | Serial # | FBOU 140501321 | ||
| Make | DAIKIN 5TH FLOOR | Model | SWP023HLS27 | Serial # | FBOU 140101313 | ||
| Make | DAIKIN 5TH FLOOR | Model | SWP023HLS27 | Serial # | FBOU 1405011509 | ||
| Make | DAIKIN 6TH FLOOR | Model | SWP023HLS27 | Serial # | FBOU140600007 | ||
| Make | DAIKIN 6TH FLOOR | Model | SWP023HLS27 | Serial # | FBOU140501723 | ||
| Make | DAIKIN 7TH FLOOR | Model | SWP023HLS27 | Serial # | FBOU140600005 | ||
| Make | DAIKIN 7TH FLOOR | Model | SWP023HLS27 | Serial # | FBOU140600006 | ||
| Make | DAIKIN 8TH FLOOR | Model | SWP038HLS27 | Serial # | FBOU140600023 | ||
| Make | GOODMAN | LOBBY IST FL | Model | GSC130603BB | Serial # | 1204706385 | |
| Make | CARRIER | IST FL | Model | 38MAQB24R-3 | Serial # | 1818V23519 | |
| Make | CARRIER | 1ST FL | Model | 38MAQB24R-3 | Serial # | 1818V23513 | |
| Make | DAIKIN | 1ST FL | Model | AKN24NMVJU | Serial # | G004130 | |
| Make | UT CARRIER IST FL | Model | 38HDC036321 | Serial # | 3897 | ||
| Make | GOODMAN | Model | GSC130301DB | Serial # | 1104079301 | ||
| Make | WINDOW UNIT 1 | Model | N/A | Serial # | N/A | ||
| Make | WINDOW UNIT 2 | Model | N/A | Serial # | N/A | ||
| Make | WINDOW UNIT 3 | Model | N/A | Serial # | N/A | ||
| Make | WINDOW UNIT 4 | Model | N/A | Serial # | N/A | ||
| Make | WINDOW UNIT 5 | Model | N/A | Serial # | N/A | ||
| Make | WINDOW UNIT 6 | Model | N/A | Serial # | N/A | ||
| Make | WINDOW UNIT 7 | Model | N/A | Serial # | N/A |
UPS Systems
Qty. 1 Ownership GSA
Make CHLORIDE Model n/a Serial # N/A
Make N/A Model Serial # N/A
Make N/A Model Serial # N/A
Domestic Water Heater
Qty. 8 Last Inspection Date Feb-20
| Make | RUD | Model | PENO-2 | Serial # | RU0993A23271 | Type | Electric |
| Make | GENERAL ELECTRIC | Model | GEL10M06AAG | Serial # | GEA441303304 | Type | Electric |
| Make | A.O SMITH | Model | ECT 120 200 | Serial # | K07M009612 | Type | Electric |
| Make | RELIABLE 501 | Model | 510 10MS8K | Serial # | E95534562 | Type | Electric |
| Make | NO ACCESS | Model | NO ACCESS | Serial # | NO ACCESS | Type | |
| Make | NO ACCESS | Model | NO ACCESS | Serial # | NO ACCESS | Type | |
| Make | NO ACCESS | Model | NO ACCESS | Serial # | NO ACCESS | Type | |
| Make | NO ACCESS | Model | NO ACCESS | Serial # | NO ACCESS | Type |
Boilers
Qty. 1 Last Inspection Date
Type Hot Water Make RHEEM Model RB1040CS Serial# 1272X41
Type Make Model Serial#
Type Make Model Serial#
Type Make Model Serial#
Cooling Towers
Qty. 1
Make MARLEY Model NC 228195 Serial # NC 83D5FISS
Make Model Serial #
Make Model Serial #
Generators
Building Load 480 V Last Load Bank Test N/A Last Fuel Analysis Oct-20
| Make | Kohler | Model | 500R0271 | Serial # | 230212 | Gas | Diesel | |
| Day Tank Fuel Capacity | 2000 |
Make CATERPILLAR Model SR4 Serial # 4413H5960 Gas Diesel
Day Tank Fuel Capacity 2000
Make Fuel Tank only Model Serial # Gas Diesel
Main Fuel Capacity
Fire Alarm System
Make NOTIFIER Model AM 2020 Serial # N/A
Device Count
| Smoke Detector | 39 | Phoneline for Central Station Monitoring | O&M Contractor | |
| Heat Detector | 8 | |||
| Duct Detector | 15 | Date of last annual test? | Feb-20 | |
| Pull Station | 34 | |||
| Water Flows | 12 | |||
| Tampers | 26 | |||
| Strobes | 68 | |||
| Speakers | 78 | |||
| Combo. Speaker / Strobes | 13 | |||
| Beam Detectors | N/A | |||
| Batteries | 12 |
Fire Sprinkler System
| Wet | Yes | Date of last annual test? | 2019 | Date of last semi-annual test? | 2019 |
| Dry | N/A | Date of last annual test? | N/A | Date of last semi-annual test? | N/A |
| Stand Pipe | Yes | Date of last annual test? | 2019 | Date of last semi-annual test? | 2019 |
Does building have a fire pump? Yes
Specialize Fire Suppression Systems
| FM-200 | N/A | Date of last annual test? | N/A |
| CO2 | N/A | Date of last annual test? | N/A |
| Inergen | N/A | Date of last annual test? | N/A |
| Novec1230 | N/A | Date of last annual test? | N/A |
| IG55 | N/A | Date of last annual test? | N/A |
Does building have a kitchen hood system? N/A
Emergency Lights
How many battery operated emergency lights at facility? 50
Fire Extinguishers Types
| Type | QTY. | ||
| Water | N/A | How many require 12 year hydrostatic testing? | 0 |
| A-B-C | 56 | ||
| B-C | N/A | ||
| CO2 | N/A | ||
| K | N/A |
Security System
Card Readers
Make GALLAGHER Model Qty. 18
Key Pads
Make N/A Model N/A Qty. N/A
Parking Security Devices
| Items | Qty. | Items | Qty. | Items | Qty. |
| Pop Up Bollard | N/A | Wedge Plates | N/A | Judges Garage Doors | N/A |
| Building Garage Doors | N/A | Sally Ports | N/A | Building Gates | 54 |
Plumbing
| Back Flow Prevention Devices | Last Testing Date | 3/24/20 | ||
| Qty. | 1 |
| Item | Qty. | Item | Qty. |
| Automatic Soap Dispensers | N/A | Outside Water Hoses Bibbs | 11 |
| Automatic Towel Dispensers | N/A | FDC Connections | 8 |
| Automatic Flush Valves | 20 | Emergency Eye Wash Stations/ Showers | 4 |
| Automatic Faucets | 26 | Hot Water Circulation Pump | 1 |
| Water Fountains with Filters | 17 NO FILTERS | Roof Drains | 12 |
| Water Filters | N/A | Outside Drains | 8 |
| Building Ice Makers | N/A | ||
| Grease Traps | N/A |
Decorative Water Fountains Yes
Waterless Urinal Yes
Make AMERICAN STANDARD Model 6541 Qty. 21
Make Model Qty.
Roof System
What is the age of roof? 8 YEARS
Warranty YES Warranty Holder GSA
Does roof have anchorage point system installed? N/A
If Yes, how many and what type?
| Item | Qty. |
| Anchor Point | 0 |
| Davit Arms | 0 |
Electrical System
Last thermal scan completion date? Feb-19
Has Arch Flash Study been completed? No If yes, what is the completion date?
Last date of switchgear testing? Feb-18
Specialize Chemical Free Water Treatment System No
If yes, what type of system is installed? CRISSMAN CONSULTING
Warranty Yes Warranty Expiration Date N/A
Warranty Holder Information N/A
Building Information Sheets
Sheet2
Answers:
Sheet3
ESRI_MAPINFO_SHEET
DO NOT EDIT
For Esri use only